RSTI-EP Slice I/O GFK-2959B Digital Output Modules December 2015 EP-2214, EP-2614, EP-2634, EP-2218, EP-225F Relay Output Module EP-2714 Solid-state Relay Output Module EP-2814
Module Status LED
Channel Status LEDs
Digital Input Connector
Ground
24 V DC
FE
Digital Output Module
GE provides a range of RSTi-EP digital output modules with 4, 8 or 16 outputs, which are primarily used for the incorporation of decentralized actuators.
All outputs are designed for DC-13 discrete outputs according to DIN EN 60947-5-1 and IEC 61131-2 specifications. Frequencies of up to 1 kHz are possible except for relay and SSR output modules. Protection of the outputs ensures maximum system safety (Relay and SSR modules do not support short circuit protection). This consists of an automatic restart following a short-circuit.
The digital relay output module EP-2714 can control up to 4 discrete outputs, each with a maximum of 6 A. Each connector features a potential-free changeover contact. The relay coils are supplied with power from the output current path (IOUT).
The solid-state relay output module EP-2814 uses four semiconductor switches to control up to 4 discrete outputs, each with a maximum of 0.5 A at 255 V AC. The switching characteristics of the semiconductor switch have it as being closed when the voltage crosses zero and open when the current crosses zero. Each connector features a potential-free NO (Normally Open) contact.
The wiring connectors on each module are color coded for ease of wiring. Refer to the section, Field Wiring for additional information.
Each module features a type plate, which includes identification information, the key technical specifications, and a block diagram. In addition, a QR code allows for direct online access to the associated documentation. The software for reading the QR code must support inverted QR codes.
Markers are available as accessories for labelling equipment. Each I/O module can be labelled using the markers to ensure clear identification when replacing individual modules or electronic units.
A green Module Status LED indicates there is communication on the system bus. Additionally, there are Yellow LEDs for each input to indicate when it is active. Refer to the section, LEDs for additional information.
The RSTi-EP station is usually installed on a horizontally positioned DIN rail. Installation on vertically positioned DIN rails is also possible.
Modules should to be allowed to de-energize for a minimum 10 seconds after power down, prior to starting any maintenance activity.
Refer to the RSTi-EP Slice I/O Module User Manual (GFK-2958) for additional information.
Refer to the RSTi-EP Power Supply Reference Guide, a software utility available on PME V9.00, for detailed power-feed requirements. Module Features Positive Logic EP-2634 also supports Negative Logic Spring style technology for ease of wiring DIN rail mounted Double-click installation for positive indication of correct installation Up to 16 outputs Compatible with type-1 and type-3 sensor inputs Supports hot insertion and extraction
© 2015 General Electric Company. All Rights Reserved. * Indicates a trademark of General Electric Company and/or its subsidiaries. All other trademarks are the property of their respective owners.
2 RSTi-EP Slice I/O Digital Output Modules
GFK-2959B
Ordering Information
Module Description
EP-2214 Digital Output, 4 Points, Positive Logic 24VDC, 0.5A, 2,3, or 4 Wire
EP-2218 Digital Output, 8 Points, Positive Logic, 24VDC, 0.5A, 2 Wire
EP-2614 Digital Output, 4 Points, Positive Logic 24VDC, 2.0A, 2,3, or 4 Wire
EP-225F Digital Output, 16 Points, Positive Logic, 24VDC, 0.5A, 1 Wire
EP-2634 Digital Output, 4 Points, Positive/Negative Logic 24VDC, 2.0A, 2,3, or 4 Wire
EP-2714 Digital Relay Output, 4 Points, Positive Logic, 24 - 220 VDC/VAC, 6A, 2 Wire
EP-2814 Digital Output, 4 Points, Positive Logic, 230 VAC, 1A
Specifications
EP-2214 EP-2614 EP-2634 EP-2218 EP-225F System Data Data Process, parameter and diagnostic data depend on the network adapter used. Interface RSTi-EP system bus System bus transfer rate 48 Mbps Outputs Number 4 4 4 8 16 Type P-Logic Switchable
P- or N-Logic P-Logic
Type of load ohmic, inductive, lamp load Response time low » high max. 100 μs; high » low max. 250 μs Max. output current
per channel 0.5 A 2 A 2 A 0.5 A 0.5 A per module 2 A 8 A 8 A 4 A 8 A
Breaking energy (inductive)
150 mJ per channel
Switching frequency Resistive load (min. 47 Ω) 1 kHz
Inductive load (DC 13) 0.2 Hz without free-wheeling diode 1 kHz with suitable free-wheeling diode
Lamp load (12 W) 1 kHz Actuator connection 2-wire, 3-wire, 3-wire + FE 2-wire 1-wire Actuator supply max. 2 A per plug, total max. 8 A -- -- Short-circuit-proof Yes Protective circuit Constant current with thermal switch-off and automatic restart Response time of the current limiting circuit < 100 μs
Module diagnostics Yes Individual channel diagnostics
No
Reactionless Yes -- Yes Yes Yes
Can be used with EP-19xx Yes Yes Yes -- --
For public disclosure
RSTi-EP Slice I/O Digital output Modules 3
GFK-2959B
EP-2214 EP-2614 EP-2634 EP-2218 EP-225F Supply Supply voltage 20.4V – 28.8V
Current consumption from system current path ISYS 8 mA
Current consumption from output current path IOUT
20 mA + load 25 mA + load 20 mA + load 35 mA + load 25 mA + load
General data Operating temperature -20°C to +60°C (-4 °F to +140 °F) Storage temperature -40°C to +85°C (-40 °F to +185 °F) Air humidity (operation/transport)
5% to 95%, noncondensing as per IEC 61131-2
Width 11.5 mm (0.45 in)
Depth 76 mm (2.99 in)
Height 120 mm (4.72 in)
Weight 86 g (3.03 oz) 86 g (3.03 oz) 86 g (3.03 oz) 86 g (3.03 oz) 83 g (2.93 oz)
EP-2714 EP-2814
System Data
Data Process, parameter, and diagnostic data depend on the network adapter used. Interface RSTi-EP system bus System bus transfer rate 48 Mbps
Outputs
Number 4 Type Relay from - C SSR / triac Material for power and data contacts Ni-Au, 3 μm -- Switching characteristic
-- Closing when the voltage crosses zero, Opening when the current crosses zero
Response time 20 ms 10 ms Minimum switching current -- 50 mA per channel Maximum switching current -- 1 A per channel
-- 4 A per module Max. output current 5 A at 60°C (140 °F) /
6 A at 55°C (131 °F) per channel --
20 A at 60°C (140 °F) / 24 A at 55°C (131 °F) per module --
Holding current -- 25 mA
Switching frequency max. 5 Hz up to 20 Hz Short-circuit-proof No Defined trip behaviour of the prescribed external fuse -- 1 A super quick-acting
Protective circuit External fusing with 6 A prescribed -- Service life with AC-15 load and 1-A switching current > 300.000 switching cycles --
Max. switching voltage 255 V AC, UL: 277 V AC, DC corresponding to the derating curve 255 V AC, UL: 277 AC
Reactionless Yes
4 RSTi-EP Slice I/O Digital Output Modules
GFK-2959B
EP-2714 EP-2814
Diagnosis Module diagnosis Yes
Individual channel diagnostics No
Supply
Supply voltage 20.4V – 28.8V
Current consumption from system current path ISYS 8 mA 11 mA
Current consumption from output current path IOUT 20 mA --
General data
Operating temperature -20°C to +60°C (-4 °F to +140 °F) Storage temperature -40°C to +85°C (-40 °F to +185 °F) Air humidity (operation/transport) 5% to 95%, noncondensing as per IEC 61131-2 Width 11.5 mm (0.45 in) Depth 76 mm (2.99 in)
Height 120 mm (4.72 in) Weight 83 g (2.93 oz)
Current Demand for Digital Output Modules
Product ISYS IIN IOUT IS IL EP-2214 8 mA -- 20 mA -- x EP-2614 8 mA -- 25 mA -- x EP-2714 8 mA -- 20 mA -- -- EP-2814 11 mA -- -- -- -- EP-2634 8 mA -- 20 mA -- x EP-2218 8 mA -- 35 mA -- -- EP-225F 8 mA -- 25 mA x -- ISYS
IIN
IOUT
IS
IL
x
Current consumption from the system current path Power consumption from input current path Power consumption from output current path Current demand of the connected sensors Current demand of the connected actuators Must be included when calculating the power supply
For public disclosure
RSTi-EP Slice I/O Digital output Modules 5
GFK-2959B
LEDs LED EP-2214 EP-2614 EP-2634 EP-2218 EP-225F
Module Status
Green: Communication over the system bus Red: Module System Fault or Diagnostic Fault
1.1 Yellow: Output 0 active
Yellow: Output 0 active
Yellow: Output 0 active
Yellow: Output 0 active
Yellow: Output 0 active
1.2 -- -- -- -- Yellow: Output 1 active
1.3 -- -- -- Yellow: Output 1 active
Yellow: Output 2 active
1.4 -- -- -- -- Yellow: Output 3 active
2.1 Yellow: Output 1 active
Yellow: Output 1 active
Yellow: Output 2 active
Yellow: Output 2 active
Yellow: Output 4 active
2.2 -- -- -- -- Yellow: Output 5 active
2.3 -- -- -- Yellow: Output 3 active
Yellow: Output 6 active
2.4 -- -- -- -- Yellow: Output 7 active
3.1 Yellow: Output 2 active
Yellow: Output 2 active
Yellow: Output 3 active
Yellow: Output 4 active
Yellow: Output 8 active
3.2 -- -- -- -- Yellow: Output 9 active
3.3 -- -- -- Yellow: Output 5 active
Yellow: Output 10 active
3.4 -- -- -- -- Yellow: Output 11 active
4.1 Yellow: Output 3 active
Yellow: Output 3 active
Yellow: Output 4 active
Yellow: Output 6 active
Yellow: Output 12 active
4.2 -- -- -- -- Yellow: Output 13 active
4.3 -- -- -- Yellow: Output 7 active
Yellow: Output 14 active
4.4 -- -- -- -- Yellow: Output 15 active
6 RSTi-EP Slice I/O Digital Output Modules
GFK-2959B
LED EP-2714 EP-2814
Module Status
Green: Communication over the system bus Red: No communication on system bus or diagnostic message displayed
Green: Communication over the system bus Red: Collective error diagnostic
1.1 Yellow: Output 0 active Yellow: Output 0 active 1.2 -- --
1.3 -- --
1.4 -- --
2.1 Yellow: Output 1 active Yellow: Output 1 active
2.2 -- --
2.3 -- --
2.4 -- --
3.1 Yellow: Output 2 active Yellow: Output 2 active
3.2 -- --
3.3 -- --
3.4 -- --
4.1 Yellow: Output 3 active Yellow: Output 3 active
4.2 -- -- 4.3 -- -- 4.4 -- --
Field Wiring The connection frame can take up to four connectors, and four wires can be connected to each connector. The Spring style technology allows for either finely stranded or solid wire with crimped wire-end ferrules or ultrasonically welded wires, each with a maximum cross-section of 1.5 mm² (16 guage), to be inserted easily through the opening in the clamping terminal without having to use tools. To insert fine stranded wires without wire-end ferrules, the pusher must be pressed in with a screwdriver and released to latch the wire.
EP-2714 EP-2814
NC 0
COMM 0
NO 0
COMM 0
COMM 0
NO 0
NO 0
Connector with Four Wire Connectors COMM 0 Connector Block (for Relay/SSR Modules)
Connector Specifications: • wire cross-section 0.14 to 1.5 mm² (26 – 16 guage) • max. ampacity: 10 A • 4-pole
The pushers are color-coded for the following connections: • White Signal • Blue GND • Red 24 V DC • Green Functional earth (FE)
For public disclosure
RSTi-EP Slice I/O Digital output Modules 7
GFK-2959B
The modules do not have a fused sensor/activator power supply. All cables to the connected sensors/actuators must be fused corresponding to their conductor cross-sections (as per Standard DIN EN 60204-1, section 12). Refer to the RSTi-EP Slice I/O Module User Manual (GFK-2958) for additional information.
For technical assistance, go to http://support.ge-ip.com.
Connection Diagrams
EP-2214 and EP-2614
EP-2218 EP-225F
EP-2634
8 RSTi-EP Slice I/O Digital Output Modules
GFK-2959
EP-2714 EP-2814
Connection Block Diagrams
EP-2214
GND OUT
24VDC OUT
FE
System bus
EP-2214
For public disclosure
RSTi-EP Slice I/O Digital output Modules 9
GFK-2959
EP-2614
EP-2614
EP-2218
24VDC OUT
GND OUT
System bus
EP-2218
EP-225F
24VDC OUT
System bus
EP-225F
For public disclosure
10 RSTi-EP Slice I/O Digital Output Modules
GFK-2959
EP-2634
EP-2634
EP-2714
EP-2714
EP2814
EP-2814
For public disclosure
RSTi-EP Slice I/O Digital output Modules 11
GFK-2959
Installation in Hazardous Areas EQUIPMENT LABELED WITH REFERENCE TO CLASS I, GROUPS A, B, C & D, DIV. 2 HAZARDOUS AREAS IS SUITABLE FOR USE IN
CLASS I, DIVISION 2, GROUPS A, B, C, D OR NON-HAZARDOUS AREAS ONLY
WARNING - EXPLOSION HAZARD - SUBSTITUTION OF COMPONENTS MAY IMPAIR SUITABILITY FOR CLASS I, DIVISION 2;
WARNING - EXPLOSION HAZARD - WHEN IN HAZARDOUS AREAS, TURN OFF POWER BEFORE REPLACING OR WIRING MODULES; AND
WARNING - EXPLOSION HAZARD - DO NOT CONNECT OR DISCONNECT EQUIPMENT UNLESS POWER HAS BEEN SWITCHED OFF OR THE AREA IS KNOWN TO BE NONHAZARDOUS.
ATEX Marking II 3 G Ex nA IIC T4 Gc
Ta: -20°C to +60°C (-4° F to +140 °F)
Release History Catalog Number Firmware
Version Date Comments
EP-2214, EP-2614, EP-2634, EP-2218, EP-225F, EP2714, EP-2814 N/A Dec-2015 Documentation update only
EP-2214, EP-2614, EP-2634, EP-2218, EP-225F, EP2714, EP-2814 N/A Oct-2015 Initial Release
Important Product Information for this Release Updates None - Documentation update only
Funcional Compatibility N/A
Problems Resolved by this Release None – Documentation update only
New Features and Enhancements None – Documentation update only
For public disclosure
12 RSTi-EP Slice I/O Digital Output Modules
GFK-2959
1-800-433-2682
1-434-978-5100
www.ge-ip.com
Known Restrictions and Open Issues Subject Description
Logging of multiple fault entries when using discrete output modules under output short-circuit or overload condition
Discrete output modules (EP-2214, EP-2218 and EP-225F) offer output short circuit protection. When the short circuit/ overload ( >2A) condition appears, the output is turned off. Diagnostic alarm is generated. Periodically the output is pulsed to check the fault status and this is continued until the short-circuit or overload condition is rectified. The average output current will be there in the output path however it will be very less as compared to the amplitude of regular load current. Please review your system design to determine if the periodic pulsing in overload condition is compatible with selected load components for your application
This behavior has the side-effect of the affected module logging repeated diagnostic messages until the error condition is cleared, this may cause multiple fault table entries when used with RX3i control and PNC.
Operational Notes None
Product Documentation RSTi-EP Slice I/O Module User Manual (GFK-2958)
RSTi-EP Slice I/O Functional Safety Module User Manual (GFK-2956)
For public disclosure