Specification RSM02 Ver 5
Ergon Energy Corporation Limited ABN 50 087 646 062
Ergon Energy Corporation Limited
Specification for UDC Compatible Materials Listing
RSM02
Last Updated 12 November 2010
Abstract: material for electrical underground distribution construction (UDC)
Specification for UDC COMPATIBLE MATERIALS LISTING
Check this is the latest version before use. i Specification RSM02 Ver 5
Ergon Energy Corporation Limited ABN 50 087 646 062
Contents 1. Purpose and Scope...................................................................................................... 1
2. References.................................................................................................................... 1
3. Definitions and Abbreviations .................................................................................... 1
4. Security......................................................................................................................... 1
5. Safety and Environmental Considerations ................................................................ 1
6. Acts, Regulations, and Requirements........................................................................ 1
7. Compatible Material List and Suppliers ..................................................................... 2
8. Provision of Drawings, Technical and Purchasing Specifications.......................... 2
9. Material Requirement Specifications ......................................................................... 2
10. Material Approvals....................................................................................................... 2
Appendix A – Category A Material List ............................................................................. 3
CATEGORY A MATERIAL LIST – CABLES ....................................................................... 3
CATEGORY A MATERIAL LIST – SURGE ARRESTERS ................................................. 6
CATEGORY A MATERIAL LIST – PADMOUNTED SUBSTATIONS & HV SWITCHGEAR ..................................................................................................................... 7
CATEGORY A MATERIAL LIST – PADMOUNTED SUBSTATIONS & HV SWITCHGEAR ..................................................................................................................... 8
CATEGORY A MATERIAL LIST – STREETLIGHTING.................................................... 13
CATEGORY A MATERIAL LIST – STREETLIGHTING.................................................... 14
CATEGORY A MATERIAL LIST – STREETLIGHTING.................................................... 15
CATEGORY A MATERIAL LIST – STREETLIGHTING.................................................... 16
CATEGORY A MATERIAL LIST – STREETLIGHTING.................................................... 17
Appendix B – Category B Material List ........................................................................... 18
CATEGORY B MATERIAL LIST....................................................................................... 18
Appendix C – Supplier Details......................................................................................... 29
SUPPLIER DETAILS.......................................................................................................... 29
Specification for UDC COMPATIBLE MATERIALS LISTING
Check this is the latest version before use. Page 1 of 29 Specification RSM02 Ver 5
Ergon Energy Corporation Limited ABN 50 087 646 062
1. Purpose and Scope This document has been prepared to aid the Developer by listing materials required for Underground Distribution Construction (UDC) in residential distribution up to 11kV, or 22kV as applicable, within the Ergon Energy distribution area.
Category A Materials are listed in Appendix A and the Developer is offered the option of procuring all or part of these materials from either Ergon Energy or other suppliers.
Category B Materials are listed in Appendix B and the Developer is required to purchase these materials from Ergon Energy or Energex as detailed in RSM01 UDC Materials specification.
Contact details for manufacturers/suppliers listed in Appendix A of this specification are provided in Appendix C.
All Developer supplied material shall be in accordance with this specification and referenced documents.
2. References 2.1. Ergon Energy Documents The requirements detailed in the Network Extension Agreement shall prevail over the requirements of this Document to the extent of any inconsistency.
This specification shall be read in conjunction with RSM01 UDC Materials specification.
Note: Except where varied by this specification all referenced Clauses of RSM01 UDC Materials specification, apply.
3. Definitions and Abbreviations 3.1. Definitions Refer RSM01, UDC Materials specification.
3.2. Abbreviations EPS – Ergon Purchasing Specifications
ETS – Ergon Technical Standards
JTS – Joint Technical Standards
TS – Technical Standards
Also refer RSM01, UDC Materials specification.
4. Security All issues of security are the responsibility of the Developer.
5. Safety and Environmental Considerations Refer Clause 6.
6. Acts, Regulations, and Requirements 6.1. Laws and Authorisations The Developer must comply with all Laws and relevant Authorisations.
Specification for UDC COMPATIBLE MATERIALS LISTING
Check this is the latest version before use. Page 2 of 29 Specification RSM02 Ver 5
Ergon Energy Corporation Limited ABN 50 087 646 062
6.2. Safety Management System The Contractor shall have documented and implemented a Safety Management System that complies with all current statutory requirements.
6.3. Other authorities The Developer must comply with specific requirements of other Authorities and Utilities.
7. Compatible Material List and Suppliers Material list Appendix A of this specification references material specifications and/or known manufacturers/suppliers names and catalogue numbers to best reflect the manner in which the materials are purchased within Ergon Energy. Known manufacturers/suppliers and catalogue numbers listed in this document are not intended to be exclusive and the Developer may purchase materials not directly listed provided the Developer satisfies the requirements detailed in RSM01 UDC Materials specification.
Lists include a column titled ‘SPECIFICATION/STANDARD COMMENT’ for reference to additional material not included in this document. Entries such as ‘ETS XX-XX-XX, TS XX-XX-XX, or JTS XX-XX-XX refer to comprehensive technical specifications; EPSXXXX refer to brief purchasing specifications.
8. Provision of Drawings, Technical and Purchasing Specifications The Customer Connection Officer will make available to the Developer on request a data file in PDF format that includes specifications and drawings referenced from the material lists in the column titled ‘SPECIFICATION/STANDARD COMMENT’. Each specification / standard is available separately.
9. Material Requirement Specifications Material inquiries and purchasing orders on manufacturers/suppliers should include the following:
a) Complete item description;
b) Ergon Energy’s Purchasing Specification, or ETS, TS, or JTS Technical Specification as applicable;
c) Catalogue number, where applicable;
d) Drawing, where nominated; and
e) Relevant Australian (or other referenced) Standards.
Ergon Energy accepts no liability for the correctness of the drawings and specifications and it is the Developer’s responsibility to ensure that materials purchased are suitable for the intended use.
10. Material Approvals The “Material Approval Form” and accompanying process/requirements detailed in RSM01 UDC Materials specification shall be used to request approval to purchase category “A” materials.
Specification for UDC COMPATIBLE MATERIALS LISTING
Check this is the latest version before use. Page 3 of 29 Specification RSM02 Ver 5
Ergon Energy Corporation Limited ABN 50 087 646 062
Appendix A – Category A Material List
CATEGORY A MATERIAL LIST – CABLES CABLES - LV
I.I.No. DESCRIPTION KNOWN MANUFACTURERS / SUPPLIERS
SPECIFICATION / STANDARD/ COMMENTS
1632489 CABLE U/G 4C 16mm2 Cu XLPE PVC Olex Aust. Specification ETS 04-01-04
1634155 CABLE U/G 4C 240mm2 Alum Stranded Sector XLPE PVC Olex Aust.* Midland Metals Specification ETS 04-01-04
2422178 CABLE, Power, Electrical 0.6/1kV 4mm2 2 Core Flat (7/0.85) CU PVC Insulated / PVC Sheathed Black
CABLES - LV - INSECT PROTECTED
I.I.No. DESCRIPTION KNOWN MANUFACTURERS / SUPPLIERS
SPECIFICATION / STANDARD/ COMMENTS
2400272 CABLE U/G 4C 240mm2 Alum Stranded Sector XLPE/PVC with Nylon Jacket and Sacrificial PVC Sheath
Midland Metals Olex Cables Specification ETS 04-01-04
2400273 CABLE U/G 4C 16mm2 Cu XLPE/PVC with Nylon Jacket and Sacrificial PVC Sheath
Midland Metals. Olex Cables Specification ETS 04-01-04
2406943 CABLE ELECTRICAL UNDER GROUND 0.6/1kV, 2 Core, 16mm1 (7/1.70) Cu Neutral Screened PVC Insulated/PVC Sheathed/Nylon Jacket
Midland Metals
2410371 CABLE U/G 0.6/1kV, 4 Core 50mm2 Cu Nylon Jacket and Sacrificial PVC Sheath XLPE Insulated/PVC Sheathed)
Specification ETS 04-01-04
CABLES -11kV
I.I.No. DESCRIPTION KNOWN MANUFACTURERS / SUPPLIERS
SPECIFICATION / STANDARD/ COMMENTS
2429942 6.35/11kV, 3 x 1 Core TR-Triplex, 35mm2 Al, TR-XLPE Insulated 40/0.85mm Cu Wire Screen, Water Blocking Tape PVC/HDPE Sheathed
Midland Metals Specification ETS 04 -01-05
2429959 6.35/11kV, 3 x 1 Core TR-Triplex, 185mm2 Al, TR-XLPE Insulated Midland Metals Specification ETS 04 -01-05
Specification for UDC COMPATIBLE MATERIALS LISTING
Check this is the latest version before use. Page 4 of 29 Specification RSM02 Ver 5
Ergon Energy Corporation Limited ABN 50 087 646 062
48/1.35mm Cu Wire Screen, Water Blocking Tape PVC/HDPE Sheathed
* CURRENT SUPPLIER (WHERE MORE THAN ONE SUPPLIER LISTED) CABLES -11kV INSECT PROTECTED
I.I.No. DESCRIPTION KNOWN MANUFACTURERS / SUPPLIERS
SPECIFICATION / STANDARD/ COMMENTS
2429918 6.35/11kV, 1 Core, 400mm2 Cu, TR-XLPE Insulated 40/1.7 Cu Wire Screen, Water Blocking Tape PVC/Insect Protected (Nylon Jacket), HDPE Sheathed
Midland Metals Specification ETS 04 -01-06
2429967 6.35/11kV, 3 x 1 Core Triplex, 35mm2 Al TR-XLPE Insulated 40/0.85mm Cu Wire Screen, Water Blocking Tape PVC/Insect Protected (Nylon Jacket) HDPE Sheathed
Midland Metals Specification ETS 04 -01-05
2429975 6.35/11kV, 3 x 1 Core Triplex, 185mm2 Al TR-XLPE Insulated 48/1.35mm Cu Wire Screen, Water Blocking Tape PVC/Insect Protected (Nylon Jacket) HDPE Sheathed
Midland Metals Specification ETS 04 -01-05
2429983 6.35/11kV, 3 x 1 Core Triplex, 240mm2 Cu TR-XLPE Insulated 40/1.7mm Cu Wire Screen, Water Blocking Tape PVC/Insect Protected (Nylon Jacket) HDPE Sheathed
Midland Metals Specification ETS 04 -01-06
CABLES – 22kV
I.I.No. DESCRIPTION KNOWN MANUFACTURERS / SUPPLIERS
SPECIFICATION / STANDARD/ COMMENTS
2429926 12.7/22kV, 1 Core, 630mm2 Al, TR-XLPE Insulated 52/1.53mm Cu Wire Screen, Semi Conductive, Water Blocking Tape Polylaminate Al
Midland Metals Specification ETS 04 -01-05
2429934 12.7/22kV, 3 x 1 Core Triplex, 185mm2 Al TR-XLPE Insulated 48/1.35mm Cu Wire Screen, Semi Conductive, Water Blocking Tape Polylaminate Al
Midland Metals Specification ETS 04 -01-05
* CURRENT SUPPLIER (WHERE MORE THAN ONE SUPPLIER LISTED) CABLES – 22kV INSECT PROTECTED
Specification for UDC COMPATIBLE MATERIALS LISTING
Check this is the latest version before use. Page 5 of 29 Specification RSM02 Ver 5
Ergon Energy Corporation Limited ABN 50 087 646 062
I.I.No. DESCRIPTION KNOWN MANUFACTURERS / SUPPLIERS
SPECIFICATION / STANDARD/ COMMENTS
2429991 12.7/22kV, 3 x 1 Core Triplex, 35mm2 Al TR-XLPE Insulated 40/0.85mm Cu Wire Screen, Water Blocking Tape PVC/Insect Protected (Nylon Jacket) HDPE Sheathed
Midland Metals Specification ETS 04 -01-05
CABLES – 33kV
I.I.No. DESCRIPTION KNOWN MANUFACTURERS / SUPPLIERS
SPECIFICATION / STANDARD/ COMMENTS
2423655 19.1/33kV, 1 Core 50mm2 Al ,TR-XLPE Insulated/Copper Wire Screened 4.9kA 1 Sec, Water Blocked, PVC, Nylon Jacket, HPDE Sheathed 1.3mm
Midland Metals Specification ETS 04-02-03
2424984 19.1/33kV, 1 Core, 300mm2 Al, TR- XLPE Insulated/Copper Wire Screened, Water Blocked, LLDPE, HDPE Sheathed, Insect Protected.
Midland Metals Specification ETS 04 -02-02
Specification for UDC COMPATIBLE MATERIALS LISTING
Check this is the latest version before use. Page 6 of 29 Specification RSM02 Ver 5
Ergon Energy Corporation Limited ABN 50 087 646 062
CATEGORY A MATERIAL LIST – SURGE ARRESTERS SURGE ARRESTERS
I.I.No. DESCRIPTION KNOWN MANUFACTURERS / SUPPLIERS
SPECIFICATION / STANDARD/ COMMENTS
0701112 SURGE ARRESTER 22kV 10kA AK Power Solutions
Specification TS 09-01-01
2403488 SURGE ARRESTER 11kV 10kA Bri-Tech P/L Specification TS 09-01-01
* CURRENT SUPPLIER (WHERE MORE THAN ONE SUPPLIER LISTED)
Specification for UDC COMPATIBLE MATERIALS LISTING
Check this is the latest version before use. Page 7 of 29 Specification RSM02 Ver 5
Ergon Energy Corporation Limited ABN 50 087 646 062
CATEGORY A MATERIAL LIST – PADMOUNTED SUBSTATIONS & HV SWITCHGEAR 11kV PADMOUNTED SUBSTATIONS
I.I.No. DESCRIPTION KNOWN MANUFACTURERS / SUPPLIERS
SPECIFICATION / STANDARD/ COMMENTS
0104275 TRANSFORMER Distribution 11kV 750kVA 3ph Padmount w/- LV Sw/Gear, no HV Sw/Gear Front Entry
Wilson Transformers*
ABB Australia Specification JTS 02-04-01
0104276 TRANSFORMER Distribution 11kV 1000kVA 3ph Padmount w/- LV Sw/Gear, no HV Sw/Gear Front Entry
Wilson Transformers*
ABB Australia Specification JTS 02-04-01
0104277 TRANSFORMER Distribution 11kV 100kVA 3ph Padmount w/- LV Sw/Gear, no HV Sw/Gear Front Entry
Wilson Transformers*
ABB Australia Specification JTS 02-04-01
0104634 TRANSFORMER Distribution 11kV 500kVA 3ph Padmount w/-Weber LV Sw/Gear, and HV RMU Front Entry
Wilson Transformers*
ABB Australia Specification JTS 02-04-01
2405701 TRANSFORMER Distribution 11kV 315kVA 3ph Padmount w/-Weber LV Sw/Gear, no HV Sw/Gear Front Entry
Wilson Transformers*
ABB Australia Specification JTS 02-04-01
2405702 TRANSFORMER Distribution 11kV 500kVA 3ph Padmount w/-Weber LV Sw/Gear, no HV Sw/Gear Front Entry
Wilson Transformers*
ABB Australia Specification JTS 02-04-01
2405703 TRANSFORMER Distribution 11kV 1000kVA 3ph Padmount w/- LV Sw/Gear, and HV RMU Front Entry
Wilson Transformers*
ABB Australia Specification JTS 02-04-01
2406728 TRANSFORMER Distribution 11kV 315kVA 3ph Padmount w/- LV Sw/Gear, and HV RMU Front Entry
Wilson Transformers*
ABB Australia Specification JTS 02-04-01
2406855 TRANSFORMER Distribution 11kV 750kVA 3ph Padmount w/- LV Sw/Gear, and HV RMU Front Entry
Wilson Transformers*
ABB Australia Specification JTS 02-04-01
* CURRENT SUPPLIER (WHERE MORE THAN ONE SUPPLIER LISTED)
Specification for UDC COMPATIBLE MATERIALS LISTING
Check this is the latest version before use. Page 8 of 29 Specification RSM02 Ver 5
Ergon Energy Corporation Limited ABN 50 087 646 062
CATEGORY A MATERIAL LIST – PADMOUNTED SUBSTATIONS & HV SWITCHGEAR 22kV PADMOUNTED SUBSTATIONS
I.I.No. DESCRIPTION KNOWN MANUFACTURERS / SUPPLIERS
SPECIFICATION / STANDARD / COMMENTS
2404656 TRANSFORMER DISTRIBUTION22kV, 500kVA, Three Phase, Padmount, with LV Switchgear and no HV Switchgear4100mm Long Cubicle
Wilson Transformers*
Schneider Electrical
Specification ETS 02-02-02 W
2404659 TRANSFORMER DISTRIBUTION22kV, 1000kVA, Three Phase, Padmount, with LV Switchgear and no HV Switchgear,4100mm Long Cubicle
Wilson Transformers*
Schneider Electrical
Specification ETS 02-02-02 W
2408037 TRANSFORMER DISTRIBUTION22 kV/433-250kVA, 200kVA, 3 Phases(Rectangular Type) ONAN padmounted substation complete with LV Switchgear &HV SFU (1 x switch disconnectors & 1 Fuse)
Wilson Transformers
Specification ETS 02-02-02 W
2408052 TRANSFORMER DISTRIBUTION22 kV/433-250 V, 315kVA 3 Phases(Rectangle Type) ONAN padmount substation complete with LV switchgear & HVRMU (2 x disconnectors & 2 x Fuse Switch)
Wilson Transformers
Specification ETS 02-02-02 W
2408078 TRANSFORMER DISTRIBUTION22kV/433-250V, 315kVA, 3 Phases(Rectangle Type) ONAN padmounted substation complete with LV switchgear and HV RMU (3 x switch disconnectors and 1 fuse)
Wilson Transformers
Specification ETS 02-02-02 W
2408094 TRANSFORMER DISTRIBUTION22kV/433-250V,500kVA,3 Phases(Rectangle Type) ONAN padmounted substation complete with LV switchgear and HV RMU (2 x switch disconnectors and 2 fuses)
Wilson Transformers
Specification ETS 02-02-02 W
2408110 TRANSFORMER DISTRIBUTION22kV/433-250V, 500kVA,3 Phases(Rectangle Type) ONAN padmounted substation complete with LV switchgear and HV RMU (3 x switch disconnectors and 1 fuse)
Wilson Transformers
Specification ETS 02-02-02 W
2408144 TRANSFORMER DISTRIBUTION22kV/433-250V, 1000kVA, 3 Phases(Rectangle Type) ONAN padmounted substation complete with LV switchgear and HV RMU (2 x switch disconnectors and 2 x fuses)
Wilson Transformers
Specification ETS 02-02-02 W
2408169 TRANSFORMER DISTRIBUTION22kV/433-250V, 1000kVA, 3 Phases(Rectangle Type) ONAN padmounted substation complete with LV switchgear and HV RMU (3 x switch disconnectors and 1 x fuse)
Wilson Transformers
Specification ETS 02-02-02 W
2424067 TRANSFORMER DISTRIBUTION Padmount, 22kV/433-250V, 315kVA, 3 Ph, 50 Hz, ONAN, with LV Switchgear and no HV Switchgear,
Wilson Transformers
Specification ETS 02-02-02 W
Specification for UDC COMPATIBLE MATERIALS LISTING
Check this is the latest version before use. Page 9 of 29 Specification RSM02 Ver 5
Ergon Energy Corporation Limited ABN 50 087 646 062
I.I.No. DESCRIPTION KNOWN MANUFACTURERS / SUPPLIERS
SPECIFICATION / STANDARD / COMMENTS
(Rectangular plinth nominal size 1310mm x 4100mm)
2424075 TRANSFORMER DISTRIBUTION Padmount, 22kV/433-250V, 315kVA, 3 Ph, 50 Hz, ONAN, with LV switchgear and HV RMU (2 x switch disconnectors and 1 x fuse switch). (Rectangular plinth nominal size 1310 x 4100mm)
Wilson Transformers
Specification ETS 02-02-02 W:
2424083 TRANSFORMER DISTRIBUTION Padmount, 22kV/433-250V, 500kVA, 3 Ph, 50 Hz, ONAN, with LV switchgear and HVRMU (2 x switch disconnectors and 1 x fuse switch). (Rectangular plinth nominal size 1310 x 4100mm)
Wilson Transformers
Specification ETS 02-02-02 W
2424091 TRANSFORMER DISTRIBUTION Padmount, 22kV/433-250V, 1000kVA, 3 Ph, 50 Hz, ONAN, with LV switchgear and HVRMU (2 x switch disconnectors and 1 x fuse switch). (Rectangular plinth nominal size 1310 x 4100mm)
Wilson Transformers
Specification ETS 02-02-02 W
* CURRENT SUPPLIER (WHERE MORE THAN ONE SUPPLIER LISTED)
Specification for UDC COMPATIBLE MATERIALS LISTING
Check this is the latest version before use. Page 10 of 29 Specification RSM02 Ver 5
Ergon Energy Corporation Limited ABN 50 087 646 062
11kV CABLEBOX TRANSFORMERS (GROUND MOUNT)
I.I.No. DESCRIPTION KNOWN MANUFACTURERS / SUPPLIERS
SPECIFICATION / STANDARD/ COMMENTS
2427243 TRANSFORMER DISTRIBUTION, Cable Entry Distribution Transformer with HV Cable box and LV bushings, 11kV/433-250 V, 500kVA, 3 Ph, 50 Hz, ONAN
Specification ETS 02-03-01
2427250 TRANSFORMER DISTRIBUTION, Cable Entry Distribution Transformer with HV Cable box and LV bushings, 11kV/433-250 V, 750kVA, 3 Ph, 50 Hz, ONAN
Specification ETS 02-03-01
2427268 TRANSFORMER DISTRIBUTION, Cable Entry Distribution Transformer with HV Cable box and LV bushings, 11kV/433-250 V, 1000kVA, 3 Ph, 50 Hz, ONAN
Specification ETS 02-03-01
2427276 TRANSFORMER DISTRIBUTION, Cable Entry Distribution Transformer with HV Cable box and LV bushings, 11kV/433-250 V, 1500kVA, 3 Ph, 50 Hz, ONAN
Specification ETS 02-03-01
22kV CABLEBOX TRANSFORMERS (GROUND MOUNT)
I.I.No. DESCRIPTION KNOWN MANUFACTURERS / SUPPLIERS
SPECIFICATION / STANDARD/ COMMENTS
2404649 TRANSFORMER DISTRIBUTION, Cable Entry Distribution Transformer with HV Cable box and LV bushings, 22kV/433-250 V, 1000kVA, 3 Ph, 50 Hz, ONAN
ABB Australia Specification ETS 02-02-02 A
2404650 TRANSFORMER DISTRIBUTION, Cable Entry Distribution Transformer with HV Cable box and LV bushings, 22kV/433-250 V, 500kVA, 3 Ph, 50 Hz, ONAN
ABB Australia Specification ETS 02-02-02 A
2408011 TRANSFORMER DISTRIBUTION, Cable Entry Distribution Transformer with HV Cable box and LV bushings, 22kV/433-250 V, 1500kVA, 3 Ph, 50 Hz, ONAN
ABB Australia Specification ETS 02-02-02 A
Specification for UDC COMPATIBLE MATERIALS LISTING
Check this is the latest version before use. Page 11 of 29 Specification RSM02 Ver 5
Ergon Energy Corporation Limited ABN 50 087 646 062
1.10 11kV AND 22kV OUTDOOR SWITCHGEAR
I.I.No. DESCRIPTION KNOWN MANUFACTURERS / SUPPLIERS
SPECIFICATION / STANDARD/ COMMENTS
0104249 Ring Main Unit 12 kV 2 x Feeder Switches 1 x Fuse Switch C/W Cubicle & Plinth Safe Link CFC
ABB Australia Specification ETS 06-08-01
0104250 Ring Main Unit 24 kV 3 x Feeder Switches 1 x Fuse Switch C/W Cubicle & Plinth F&G
Delta Power Specification ETS 06-08-01
0104252 Ring Main Unit 24 kV 2 x Feeder Switches 1 x Fuse Switch C/W Cubicle & Plinth F&G
Delta Power Specification ETS 06-08-01
0104255 Ring Main Unit 24 kV 2 x Feeder Switches 2 x Fuse Switch C/W Cubicle & Plinth F&G
Delta Power Specification ETS 06-08-01
0104256 Ring Main Unit 12 kV 3 x Feeder Switches C/W Cubicle & Plinth Safe Link CCC
ABB Australia Specification ETS 06-08-01
0104257 Ring Main Unit 12 kV 2 x Feeder Switches 2 x Fuse Switch C/W Cubicle & Plinth Safe Link CFCF
ABB Australia Specification ETS 06-08-01
0104258 Ring Main Unit 12 kV 3 x Feeder Switches 1 x Fuse Switch C/W Cubicle & Plinth Safe Link CFCC
ABB Australia Specification ETS 06-08-01
0104261 Ring Main Unit 24 kV 3 x Feeder Switches C/W Cubicle & Plinth F&G
Delta Power Specification ETS 06-08-01
0104395 Ring Main Unit, Switchgear, 12kV comprising of 1 feeder switch, 1 circuit breaker and on switch fuse complete with cubicle and plinth,(Safeplus CVF)
ABB Australia Specification ETS 06-08-01
0104396 Ring Main Unit, Switchgear, 12kV 3-way switch unit comprising of 2 feeder switch disconnectors and 1 circuit breaker complete with cubicle and plinth, (Safering CCV)
ABB Australia Specification ETS 06-08-01
0104397 Ring Main Unit, Switchgear, 12kV RMU comprising of 1 feeder switch disconnector, 1 circuit breaker and 2 switch fuses complete with cubicle and plinth, (Safeplus CVFF)
ABB Australia Specification ETS 06-08-01
0104398 Ring Main Unit, Switchgear, 24kV RMU comprising of 1 feeder switch disconnector, 1 circuit breaker and one switch fuse complete with cubicle and plinth
Delta Power Specification ETS 06-08-01
0104399 Ring Main Unit, Switchgear, 24kV 3-way switch unit comprising of 2 feeder switch disconnectors and 1 circuit breaker complete with cubicle and plinth
Delta Power Specification ETS 06-08-01
Specification for UDC COMPATIBLE MATERIALS LISTING
Check this is the latest version before use. Page 12 of 29 Specification RSM02 Ver 5
Ergon Energy Corporation Limited ABN 50 087 646 062
I.I.No. DESCRIPTION KNOWN MANUFACTURERS / SUPPLIERS
SPECIFICATION / STANDARD/ COMMENTS
0104400 Ring Main Unit, Switchgear, 24kV ring main unit comprising of 1 feeder switch disconnector, 1 circuit breaker and 2 switch fuses complete with cubicle and plinth
Delta Power Specification ETS 06-08-01
0105005 Ring Main Unit 12 kV 4 x Feeder Switches C/W Cubicle & Plinth Safe Link CCCC
ABB Australia Specification ETS 06-08-01
0105006 Ring Main Unit 24 kV 4 x Feeder Switches C/W Cubicle & Plinth F&G
Delta Power Specification ETS 06-08-01
Specification for UDC COMPATIBLE MATERIALS LISTING
Check this is the latest version before use. Page 13 of 29 Specification RSM02 Ver 5
Ergon Energy Corporation Limited ABN 50 087 646 062
CATEGORY A MATERIAL LIST – STREETLIGHTING STREETLIGHT POLES & OUTREACHES - MINOR ROAD - ESTATE
I.I.No. DESCRIPTION KNOWN MANUFACTURERS / SUPPLIERS
SPECIFICATION / STANDARD/ COMMENTS
0924058 POLE Steel Lighting 4.5m Estate Minor road BPM Green Ingal EPS Bonnell’s Supply TS 05-02-01
0924065 POLE Steel Lighting 4.5m Estate Minor road BPM Blue/Grey Ingal EPS Bonnell’s Supply TS 05-02-01
1.13 STREETLIGHT POLES & OUTREACHES - MINOR ROAD - GALV
I.I.No. DESCRIPTION KNOWN MANUFACTURERS / SUPPLIERS
SPECIFICATION / STANDARD/ COMMENTS
0126019 POLE Steel Galv Lighting 5.5m BPM Minor Road GM Poles P/L* Ingal EPS Bonnell’s Supply TS 05-02-01
0126029 OUTREACH ARM 1.5m Galv Single Minor Road GM Poles P/L* Ingal EPS Pollards Bonnell’s Supply TS 05-02-01
2403725 OUTREACH ARM 1.5m Galv Double Minor Road GM Poles P/L* Ingal EPS Pollards Bonnell’s Supply TS 05-02-01
Specification for UDC COMPATIBLE MATERIALS LISTING
Check this is the latest version before use. Page 14 of 29 Specification RSM02 Ver 5
Ergon Energy Corporation Limited ABN 50 087 646 062
CATEGORY A MATERIAL LIST – STREETLIGHTING STREETLIGHT POLES & OUTREACHES - MAJOR ROAD
I.I.No. DESCRIPTION KNOWN MANUFACTURERS / SUPPLIERS
SPECIFICATION / STANDARD/ COMMENTS
0922012 POLE Concrete S/Lighting 10.25. BIG Major Road Rocla Conc. TS 05-02-01
1104682 OUTREACH ARM Extension 1.5m Galv Single Major Road GM Poles P/L* Ingal EPS TS 05-02-01
1104685 OUTREACH ARM 3.0m Galv Single Major Road GM Poles P/L* Ingal EPS TS 05-02-01
2401888 POLE Steel S/Lighting 7.0m BPM Major Road GM Poles P/L* Ingal EPS TS 05-02-01
2401889 POLE Steel S/Lighting 8.5m BPM Major Road GM Poles P/L Ingal EPS TS 05-02-01
2401890 POLE Steel S/Lighting 10.0m BPM Major Road GM Poles P/L Ingal EPS TS 05-02-01
2403022 POLE Concrete S/Lighting 8.5m BIG Major Road Rocla Conc. TS 05-02-01
2403718 OUTREACH ARM 1.5m Galv Single Major Road GM Poles P/L* Ingal EPS Pollards TS 05-02-01
2403723 OUTREACH ARM 1.5m Galv Double Major Road Ingal EPS TS 05-02-01
2405754 OUTREACH ARM 3.0m Galv Double 2.0m Uplift Major Road GM Poles P/L* Ingal EPS Pollards TS 05-02-01
2406973 POLE Concrete S/Lighting 11.9m BIG Major Road Rocla Conc.* GM Poles P/L TS 05-02-01
Specification for UDC COMPATIBLE MATERIALS LISTING
Check this is the latest version before use. Page 15 of 29 Specification RSM02 Ver 5
Ergon Energy Corporation Limited ABN 50 087 646 062
CATEGORY A MATERIAL LIST – STREETLIGHTING LUMINAIRES
I.I.No. DESCRIPTION KNOWN MANUFACTURERS / SUPPLIERS
SPECIFICATION / STANDARD/ COMMENTS
1138096 STREETLIGHT Nostalgia 50W Mercury Vapour Type 1 Green Sylvania TS 05-01-01
1138101 STREETLIGHT Nostalgia 80W Mercury Vapour Type 1 Green Sylvania TS 05-01-01
1138111 STREETLIGHT Nostalgia 50W Mercury Vapour Type 2 Blue/Grey Sylvania TS 05-01-01
1138115 STREETLIGHT Nostalgia 80W Mercury Vapour Type 2 Blue/Grey Sylvania TS 05-01-01
1150075 S/LIGHT LUMINAIRE 50W Mercury Vapour 34mm Spigot Minor Rd. Sylvania TS 05-01-01
1150078 S/LIGHT LUMINAIRE 80W Mercury Vapour 34mm Spigot Minor Rd. Sylvania TS 05-01-01
1150080 S/LIGHT LUMINAIRE 125W Mercury Vapour 34mm Spigot Minor Rd. Sylvania TS 05-01-01
1150251 S/LIGHT LUMINAIRE 150W H P Sodium 42mm Spigot Major Rd Sylvania TS 05-01-01
1150252 S/LIGHT LUMINAIRE 150W H P Sodium Aeroscreen 42mm Spigot Major Rd
Sylvania TS 05-01-01
1150253 S/LIGHT LUMINAIRE 250W H P Sodium 42mm Spigot Major Rd Sylvania TS 05-01-01
1150255 S/LIGHT LUMINAIRE 250W H P Sodium Aeroscreen 42mm Spigot Major Rd
Sylvania TS 05-01-01
Specification for UDC COMPATIBLE MATERIALS LISTING
Check this is the latest version before use. Page 16 of 29 Specification RSM02 Ver 5
Ergon Energy Corporation Limited ABN 50 087 646 062
CATEGORY A MATERIAL LIST – STREETLIGHTING LUMINAIRES (continued)
I.I.No. DESCRIPTION KNOWN MANUFACTURERS / SUPPLIERS
SPECIFICATION / STANDARD/ COMMENTS
1150285 S/LIGHT LUMINAIRE 400W H P Sodium 42mm Spigot Major Rd Sylvania TS 05-01-01
1150288 S/LIGHT LUMINAIRE 400W H P Sodium Aeroscreen 42mm Spigot Major Rd
Sylvania TS 05-01-01
2403257 S/LIGHT LUMINAIRE 70W H P Sodium 34mm Spigot Minor Rd Sylvania TS 05-01-01
2403262 S/LIGHT LUMINAIRE 100W H P Sodium 42mm Spigot Major Rd Sylvania TS 05-01-01
2403271 S/LIGHT LUMINAIRE 100W H P Sodium 42mm Spigot Aeroscreen Major Rd
Sylvania TS 05-01-01
2403273 STREETLIGHT Nostalgia 70W HP Sodium Type 1 Green Sylvania TS 05-01-01
2403275 S/LIGHT LUMINAIRE 50W Mercury Vapour Aeroscreen 34mm Spigot Minor Rd.
Sylvania TS 05-01-01
2403276 S/LIGHT LUMINAIRE 80W Mercury Vapour Aeroscreen 34mm Spigot Minor Rd.
Sylvania TS 05-01-01
2405828 S/LIGHT LUMINAIRE 70W H P Sodium 42mm Spigot Aeroscreen Minor Rd
Sylvania TS 05-01-01
2406971 STREETLIGHT Nostalgia 70W HP Sodium Type 2 Blue/Grey Sylvania TS 05-01-01
Specification for UDC COMPATIBLE MATERIALS LISTING
Check this is the latest version before use. Page 17 of 29 Specification RSM02 Ver 5
Ergon Energy Corporation Limited ABN 50 087 646 062
CATEGORY A MATERIAL LIST – STREETLIGHTING LAMPS
I.I.No. DESCRIPTION KNOWN MANUFACTURERS / SUPPLIERS
SPECIFICATION / STANDARD/ COMMENTS
1140819 LAMP 50W Mercury Vapour Diffuse Bulb Fluoro Type E27 Cap Rexel Aust. TS 05-03-01
1140823 LAMP 80W Mercury Vapour Diffuse Bulb Fluoro Type E27 Cap Rexel Aust. TS 05-03-01
1140827 LAMP 125W Mercury Vapour Diffuse Bulb Fluoro Type E27 Cap Sylvania TS 05-03-01
1141598 LAMP 150W Sodium Vapour HP Clear Tube Type E40 Cap Sylvania TS 05-03-01
1141599 LAMP 250W Sodium Vapour HP Clear Tube Type E40 Cap Sylvania TS 05-03-01
1141639 LAMP 400W Sodium Vapour HP Clear Tube Type E40 Cap Sylvania TS 05-03-01
2403341 LAMP 100W HP Sodium Vapour Clear Tube Type E40 Cap Sylvania * Phillips Lighting TS 05-03-01
2405832 LAMP 70W HP Sodium Vapour Diffused Bulb Type E27 Cap Sylvania TS 05-03-01
* CURRENT SUPPLIER (WHERE MORE THAN ONE SUPPLIER LISTED)
Specification for UDC COMPATIBLE MATERIALS LISTING
Check this is the latest version before use. Page 18 of 29 Specification RSM02 Ver 5
Ergon Energy Corporation Limited ABN 50 087 646 062
Appendix B – Category B Material List CATEGORY B MATERIAL LIST
I.I.No. DESCRIPTION
0104146 CLAMP Trefoil Cast Alum suit 22kV 50mm2 Cable 29.2mm Dia
0104186 BRACKET Streetlight Major Road Type MA1, 1.5m O/R
0104187 BRACKET Streetlight Major Road Type MA2, 3.0m O/R
0104188 BRACKET Streetlight Major Road Type MA3, 4.5m O/R, 2.5m Uplift
0104190 BRACKET Streetlight Major Road Type MA4, 3.0m O/R, 4.0m Uplift
0104193 CLAMP Cable 30-100mm Dia -2x13mm Holes 95 Centres
0104201 GUARD cable Polymeric 2700 L suit 100mm Dia Cable
0104207 END CAP suit 25mm2 ABC Cables
0104210 BRACKET Angle Galv Service Cable
0104264 JOINT KIT U/G 11kV 185mm2 Alum Triplex XLPE
0104269 JOINT KIT U/G 11kV 185mm2 Alum Triplex XLPE Insect Protected
0104270 JOINT KIT U/G 11kV 240mm2 Cu Triplex XLPE Insect Protected
0104271 JOINT KIT U/G 11kV 35mm2 Alum Triplex XLPE
0104272 JOINT KIT U/G 11kV 35mm2 Alum Triplex XLPE Insect Protected
0104283 TERMINATION KIT O/D 11kV 240mm2 Cu Triplex XLPE Insect Protected
0104285 TERMINATION KIT O/D 22kV 185mm2 Alum Triplex XLPE
I.I.No. DESCRIPTION
0104286 TERMINATION KIT O/D 22kV 35mm2 Alum Triplex XLPE Insect Protected (superceded – for use on DBT IP cable only)
0104287 TERMINAL for 11/22kV Cable Pole Termination Surge Arrester Connection- M12 Cable Connection
0104288 TERMINATION & CONNECTION KIT 11kV 185mm2 Alum Triplex XLPE to Padmount Bushings
0104289 TERMINATION & CONNECTION KIT 11kV 35mm2 Alum Triplex XLPE to Padmount Bushings (superceded – do not use on Midlands cable – use 2430122)
0104291 TERMINATION KIT O/D11kV 35mm2 Alum Triplex XLPE (superceded – do not use on Midlands cable – use 2430130)
0104293 TERMINATION KIT O/D LV 240mm2 Alum 4Core XLPE Cable with Solvent Wipes, Lugs. This item suits Insect Protected & Non-Insect Protected cables.
0104310 LABEL Padmount Substation- Separate HV & LV Earthing-CAUTION
0104311 LABEL Padmount Substation- Separate HV & LV Earthing-WARNING
0104312 SWITCH, ISOLATING ISOLATOR, 1000A Complete with Removable Solid Links, Suit LV Distribution Cabinet
0104314 BRACKET, MOUNTING Wall Mounting Support LV Distribution Cabinet 6 Module Including 2 Mounting Bars and fixings.
Specification for UDC COMPATIBLE MATERIALS LISTING
CATEGORY B MATERIAL LIST
Check this is the latest version before use. Page 19 of 29 Specification RSM02 Ver 5
Ergon Energy Corporation Limited ABN 50 087 646 062
I.I.No. DESCRIPTION
0104315 LV Distribution Cabinet 6 Module fitted with 1 x 1000A Isolator 2 x 630A Fuse Switches and 3 x Fuse 100A Auxiliary Supply Panel,
0104316 JOINT KIT U/G 22kV 185mm2 Alum Triplex XLPE
0104317 JOINT KIT U/G 22kV 630mm2 Alum 1C XLPE
0104318 TERMINATION & CONNECTION KIT 11kV 240mm2 Cu Triplex XLPE Insect Protected to Padmount Bushings
0104330 JOINT KIT U/G 22kV 35mm2 Alum Triplex XLPE Insect Protected
0104333 POLE, ASSET IDENTIFICATION NUMBER Ergon Energy DWG 901732-01
0104341 GUARD EARTH 25mm OD Heavy Duty HFT Conduit 2.65m long for HV &LV Earth (NOT SWER)
0104402 CLAMP 22kV 1C 35mm2 Cable Connection at F&G RMU -30mm Dia Cable
0104403 BOLT ASSEMBLY, Foundation Precast Foundation LV Distribution Cabinet 6 Module.
0104404 ELBOW CONNECTOR SET (3) 630A suit 22kV 1C 35mm2 Alum XLPE Insect Protected. RMU Terms.
0104405 BOLT ASSEMBLY, Foundation Hold Down Bolt Assembly Suit LV Distribution Cabinet.
0104406 WASHER Spring M8 Stainless Steel Grade 316
0104407 Numeral, Sign; [1], Black on yellow reflective, Pressure sensitive marker 3m (Sheets of 55) (See also 2406451)
0104408 Numeral, Sign; [2], Black on yellow reflective, Pressure sensitive marker 3m (Sheets of 55)
0104409 Numeral, Sign; [3], Black on yellow reflective, Pressure sensitive marker 3m (Sheets of 55)
I.I.No. DESCRIPTION
0104410 Numeral, Sign; [4], Black on yellow reflective, Pressure sensitive marker 3m (Sheets of 55)
0104411 Numeral, Sign; [5], Black on yellow reflective, Pressure sensitive marker 3m (Sheets of 55)
0104412 Numeral, Sign; [6] & [9], Black on yellow reflective, Pressure sensitive marker 3m (Sheets of 55)
0104413 Numeral, Sign; [7], Black on yellow reflective, Pressure sensitive marker 3m (Sheets of 55)
0104414 Numeral, Sign; [8], Black on yellow reflective, Pressure sensitive marker 3m (Sheets of 55)
0104422 CLAMP Trefoil Cast Alum suit 22kV 35mm2 I/P Cable 27-29mm Dia
0104423 CLAMP trefoil Cast Alum suit 11kV 240mm2 I/P Cable 39-41mm Dia
0104424 Precast Base Slab
0104435 SCREW Timber 12/11 x 50mm 5/16” HWF T17 Class 3
0104463 ELBOW CONNECTOR SET (3) 630A Bolted suit 22kV 1C 630mm2 Al XLPE Cable.
0104477 TERMINATION KIT OUTDOOR 22kV 630mm2 Alum 1C XLPE
0104478 TERMINATION KIT O/D 11kV 35mm2 Alum Triplex XLPE Insect Protected (superceded – for use on DBT IP cable only)
0104479 TERMINATION KIT O/D 11kV 185mm2 Alum Triplex XLPE Insect Protected (superceded – for use on DBT IP cable only)
0104480 CLAMP 22kV 1C 630mm2 Cable Connection F&G RMU
Specification for UDC COMPATIBLE MATERIALS LISTING
CATEGORY B MATERIAL LIST
Check this is the latest version before use. Page 20 of 29 Specification RSM02 Ver 5
Ergon Energy Corporation Limited ABN 50 087 646 062
I.I.No. DESCRIPTION
0104481 BOLT Hex M8 x 20mm Galv c/w Galv Hex Nut
0104486 CLAMP Trifoil S/Steel suit 11kV 35mm2 Cable 24-27mm Dia.
0104487 CLAMP Trifoil S/Steel suit 11kV 185mm2 Cable 33-37mm Dia.
0104490 LUG Compression Cu 37/.064 (Imp) suit M12 Bolt
0104495 TERMINAL for 11/22kV Cable Pole Termination Surge Arrester Connection- M16 Cable Connection
0104496 GUARD Cable Galv Steel 2700x130x130mm
0104497 GASKET 40x3x250L Neoprene
0104498 CLAMP Trefoil Cast Alum suit 11kV 35mm2 Cable 25-27mm Dia
0104499 CLAMP Trefoil Cast Alum suit 22kV 185mm2 Cable 40.5-42.5mm Dia
0104676 OUTREACH ARM 3.0m Galv Single Major Road suit 3-4way H/Frame
0104677 OUTREACH ARM 1.5m Galv Single Major Road suit 3-4way H/Frame
0104678 OUTREACH HEADFRAME Galv 4way Major Rd suit 3.0m O/R
0104679 OUTREACH HEADFRAME Galv 4way Major Rd suit 1.5m O/R
0104680 OUTREACH HEADFRAME Galv 3way Major Rd suit 3.0m O/R
0104681 OUTREACH HEADFRAME Galv 3way Major Rd suit 1.5m O/R
0104692 BRACKET Streetlight Minor Road Type MI2, 3.0m O/R, 1.0m Uplift
I.I.No. DESCRIPTION
0105008 TERMINATION & CONNECTION KIT 11kV 400mm2 Cu 1C XLPE Insect Protected to ABB Safe Link RMU
0105009 TERMINATION KIT O/D 11kV 400mm2 Cu 1C XLPE Insect Protected
0105010 CLAMP Cast Aluminium, suit 11kV 35mm2 Cable, Cabus No 5130 c/w Galv Hex Bolt & Unistrut P3300 Channel Nut
0105011 CLAMP Cast Aluminium, suit 11kV 185 & 240mm2 Cable, Cabus No 5141 c/w Galv Hex Bolt & Unistrut P3300 Channel Nut
0105012 CLAMP Trefoil Cast Alum suit 11kV 400mm2 Cable
0105013 CLAMP Cast Aluminium, suit 11kV 400mm2 Cable, Cabus No 5154 c/w Galv Hex Bolt & Unistrut P3300 Channel Nut
0105031 TERMINATION & CONNECTION KIT 11kV 35mm2 Alum Triplex XLPE to ABB Safe Link RMU (superceded – do not use on Midlands cable – use 2430171))
0105032 TERMINATION & CONNECTION KIT 11kV 35mm2 Alum Triplex XLPE Insect Protected to ABB Safe Link RMU (superceded – for use on DBT IP cable only)
0105033 TERMINATION & CONNECTION KIT 11kV 185mm2 Alum Triplex XLPE to ABB Safe Link RMU
0105034 TERMINATION & CONNECTION KIT 11kV 185mm2 Alum Triplex XLPE Insect Protected to ABB Safe Link RMU
0105035 TERMINATION & CONNECTION KIT 11kV 240mm2 Cu Triplex XLPE Insect Protected to ABB Safe Link RMU
Specification for UDC COMPATIBLE MATERIALS LISTING
CATEGORY B MATERIAL LIST
Check this is the latest version before use. Page 21 of 29 Specification RSM02 Ver 5
Ergon Energy Corporation Limited ABN 50 087 646 062
I.I.No. DESCRIPTION
0105044 JOINT KIT U/G 11kV 400mm2 Cu 1C XLPE Insect Protected
0112041 BRACKET, Universal Cable Support
0119011 CABLE GLOVE suit 185 to 300mm2 4C XLPE U/G Cable
0120036 SHROUD Insulating Type 2
0121008 END CAP Heatshrink (with Sealant) suit Cables 17-30 O/D
0121075 END CAP Heatshrink (with Sealant) suit Cables 30-45 O/D
0121083 END CAP Heatshrink (with Sealant) suit Cables 45-65 O/D
0124002 FUSE LINK 32A 415V HRC Cartridge VK Type 57mm x 22.2mm dia.
0124015 FUSE LINK 60A 415V HRC Cartridge VK Type 57mm x 22.2mm dia.
0136053 ELBOW CONNECTOR 200A suit 22kV 35mm2 Al Triplex XLPE Cable. Tfx & RMU Terms.
0140819 FUSE LINK 80A 500V HRC Din Type Size 1.
0140827 FUSE LINK 100A 500V HRC Din Type Size 1.
0140835 FUSE LINK 125A 500V HRC Din Type Size 1.
0140843 FUSE LINK 160A 500V HRC Din Type Size 1.
0140851 FUSE LINK 200A 500V HRC Din Type Size 1.
0140878 FUSE LINK 250A 500V HRC Din Type Size 1.
0140884 FUSE LINK 200A 500V HRC Din Type Size 2.
0140886 FUSE LINK 315A 500V HRC Din Type Size 2.
0140894 FUSE LINK 355A 500V HRC Din Type Size 2.
I.I.No. DESCRIPTION
0140908 FUSE LINK 400A 500V HRC Din Type Size 2.
0140916 FUSE LINK 500A 500V HRC Din Type Size 3.
0141106 FUSE HOLDER 100A 500V 6/50mm2 for U/G Fuse Panels – VK Fuse Links
0141254 PANEL, FUSE 3 x 100A Fuseholders & 1 x 6 Hole Neutral Link.
0141258 FUSE PANEL 6 x 100A Fuse holders & 1 x 6hole Neutral Link
0150008 INSULATOR Busbar Standoff Indoor 660V M10 Thread both ends
0152574 BALLMARKER 4inch 3M Power Red
0156610 KIT HEATSHRINK TERMINATION I/D (lug seals only) suit 240mm2 4C XLPE. This item suits Insect Protected & Non-Insect Protected cables.
0157126 SIGN Warning U/G Cables Type 2
0157134 SIGN Warning U/G Cables Type 1
0157746 LINK Compression Cu 35mm2 (19/1.53) Hex Die A/F 9.2mm Cu
0158012 LUG Compression Cu 10mm2 M10 Bolt Hex Die A/F 5.7mm Cu
0158020 LUG Compression Cu 16mm2 M10 Bolt Hex Die A/F 6.3mm Cu
0158023 LUG Compression Cu 16mm2 M12 Bolt Hex Die A/F 6.3mm Cu
0158572 LUG Compression Cu 95mm2 M12 Bolt Hex Die A/F 14.2mm Cu
0158637 LUG Compression Cu 35mm2 M12 Bolt Hex Die A/F 9.2mm Cu
Specification for UDC COMPATIBLE MATERIALS LISTING
CATEGORY B MATERIAL LIST
Check this is the latest version before use. Page 22 of 29 Specification RSM02 Ver 5
Ergon Energy Corporation Limited ABN 50 087 646 062
I.I.No. DESCRIPTION
0158670 LUG Compression Alum 240mm2 M12 Bolt Hex Die A/F 28.4mm
0168002 COVER PILLAR URD Short 315mm H x 235mm W x 300mm D Green (Polypropylene)
0168004 COVER PILLAR URD Tall 550mm H x 230mm W x 295mm D Green (Polypropylene)
0168052 PIT, UTILITY Pit U/G Body Type P4, Black HDPE.
0168055 Lid for U/G Body Type P4, Concrete, Marked "Electrical Cables".
0168535 UNICULVERT, Concrete, Padmount Transformer Uniculvert with 2 End Walls.
0168560 BASE PILLAR URD 350mm H x 550mm W x 510mm D Green (Polypropylene)
0168575 BUSBAR Phase Connection 80 x 40 x 6mm – U/G Pillars
0182007 TAPE U/G Marking 150mm Wide x 500m PVC Orange (Danger Electric Cable Below)
0184880 Heatshrink tubing
0186032 Cable Lubricant 5 litre
0325402 CEMENT 20kg Bag Type GP
0343764 Alvan R3 Grease
0406226 BRACKET Fuse Mtg Galv LV ABC
0406303 BUCKLE: Suit 10mm S/Steel Band.
0408931 FUSE LINK 80A 415V HRC Cartridge VK Type 57mm x 22.2mm dia.
I.I.No. DESCRIPTION
0408939 FUSE LINK, CARTRIDGE 415V AC, HRC Cartridge VK Type, 100 Amp, 57mm x 22.2mm Dia,
0411207 CONNECTOR IPC 25/95mm2 Main 6/35mm2 Tap w/- S/S Fasteners
0411215 CONNECTOR IPC 35/95mm2 Main 35/95mm2 Tap w/- S/S Fasteners
0411223 CONNECTOR IPC 50/150mm2 Bare Alum Main 35/95mm2 IPC Tap w/- S/S Fasteners
0411231 CONNECTOR IPC 7/95mm2 Bare Cu Main 35/95mm2 IPC Tap w/- S/S Fasteners
0411401 CLAMP PG Non Tension Alum 95-240mm2 and Cu 70-185mm2
0411405 CLAMP PG Non Tension Cu 16-150mm2
0414092 TERMINATION (STRAIN CLAMP) ABC 25mm2 2,3 or 4Core Cable
0414121 CONNECTOR IPC 5/19mm Dia Alum Main 6/35mm2 IPC Tap w/- S/S Fasteners
0414131 CONNECTOR IPC 3/14mm Dia Cu Main 6/35mm2 IPC Tap w/- S/S Fasteners
0426142 FUSEHOLDER 100A 415V 6/35mm2 Service Fuse
0431526 GUARD Wildlife Galv Sheet
0431534 GUARD HFT Conduit 2.65M L For HV & LV Earth (Not SWER)
0431542 SADDLE Earth Guard, HFT, Single Sided 20mm with M6 hole, for HV & LV Earth (Not SWER),
0447015 LUG Compression Bi-Metal ABC 95mm2 Cu Palm M12 Bolt Hex Die A/F 21.5mm Cu
0453001 Numeral [0], Vinyl, 40mm, Black, Application paper Fuji-Cal2, (Strip of 5 Numerals)
Specification for UDC COMPATIBLE MATERIALS LISTING
CATEGORY B MATERIAL LIST
Check this is the latest version before use. Page 23 of 29 Specification RSM02 Ver 5
Ergon Energy Corporation Limited ABN 50 087 646 062
I.I.No. DESCRIPTION
0453005 Numeral [1], Vinyl, 40mm, Black, Application paper Fuji-Cal2, (Strip of 5 Numerals)
0453009 Numeral [2], Vinyl, 40mm, Black, Application paper Fuji-Cal2, (Strip of 5 Numerals)
0453013 Numeral [3], Vinyl, 40mm, Black, Application paper Fuji-Cal2, (Strip of 5 Numerals)
0453017 Numeral [4], Vinyl, 40mm, Black, Application paper Fuji-Cal2, (Strip of 5 Numerals)
0453021 Numeral [5], Vinyl, 40mm, Black, Application paper Fuji-Cal2, (Strip of 5 Numerals)
0453025 Numeral [6], Vinyl, 40mm, Black, Application paper Fuji-Cal2, (Strip of 5 Numerals)
0453029 Numeral [7], Vinyl, 40mm, Black, Application paper Fuji-Cal2, (Strip of 5 Numerals)
0453033 Numeral [8], Vinyl, 40mm, Black, Application paper Fuji-Cal2, (Strip of 5 Numerals)
0453037 Numeral [9], Vinyl, 40mm, Black, Application paper Fuji-Cal2, (Strip of 5 Numerals)
0620613 FUSE LINK,CARTRIDGE12kV, Full Range, 10 Amp, Barrel 292mmLg 50.8mm Dia plus End Caps 34mm Lg 45mm Dia with Striker Pin
0620648 FUSE LINK,CARTRIDGE12kV, Full Range, 20 Amp, Barrel 292mmLg 50.8mm Dia plus End Caps 34mm Lg 45mm Dia with Striker Pin
0621008 FUSE LINK 40A 11kV HRC RMU Unit Din Type Air Insulated.
0621016 FUSE LINK 80A 11kV HRC RMU Unit Din Type Air Insulated.
0621113 FUSE LINK 20A 22kV HRC RMU Unit Din Type Air Insulated
I.I.No. DESCRIPTION
0621208 FUSE LINK, CARTRIDGE 500V AC, HRC DIN Type, 630 Amp, Size 3.
0621342 GREASE Oxide Inhibiting Alminox (325g Tube)
0675094 SWITCH FUSE 630A 660V 3pole – Din Size 3 suits Dist cabinet and 11kV Padmount LV Switch Board
0675123 SWITCH FUSE 400A 415V ABC – Din Size 1 & 2
0719437 CLAMP earth rod U-Bolt Type 13/15mm Dia Rod & 16/120mm2 Cu cables
0924070 SLIP BASE ASSEMBLY: Major Street Light Pole Mounting (Poles up to 10m) ForM24 X 2250 / 350 PCD Foundation Bolt Assembly, Shear Washer and 3 x M36 x125mm Long Bolts.
0924076 POLE, PUBLIC LIGHTING, METAL Major Road, 8.5m Above Ground, Slip Base Mounting, 76mm OD Spigot.
1001102 TIE Cable Natural Nylon 200 x 4.8mm (Halon Free)
1001110 TIE Cable Nylon UV Resistant Black 430 x 5mm (410x4.8)
1010901 PARTS KIT, Terminal Junction box, Fixed Base Pole Kit, C/W 16a 6kac/B, M8 X 4 Sq mm Terminal Lug, 2 terminal Blocks, For Fixed Base Streetlight Pole.
1090397 LUG Compression Cu 25mm2 M12 Bolt Hex Die A/F 7.7mm Cu
1090425 LUG Compression Cu 150mm2 M12 Bolt Hex Die A/F 18.3mm Cu
1103813 TERMINAL PANEL Streetlight Pole Minor Rd
1103815 TERMINAL PANEL Streetlight Pole Major Rd
1104638 BRACKET Streetlight Minor Road Type MI1, 1.2m O/R
Specification for UDC COMPATIBLE MATERIALS LISTING
CATEGORY B MATERIAL LIST
Check this is the latest version before use. Page 24 of 29 Specification RSM02 Ver 5
Ergon Energy Corporation Limited ABN 50 087 646 062
I.I.No. DESCRIPTION
1175094 SWITCH PE CELL D2 Base 400VA Low Rating to 125W Minor Rd.
1184026 SWITCH PE CELL Nema Base 1800VA High Rating-700W Major Rd.
1311142 CONDUCTOR Annealed Bare Cu 35mm2 (19/1.53)
1313013 CABLE Aerial 1C 16mm2 (7/1.70) HDCU XLPE
1313021 CABLE Aerial 1C 35mm2 (19/1.53) HDCU XLPE
1420001 CABLE Aerial ABC 4x95mm2 Alum XLPE
1420068 CABLE Aerial ABC 2x6mm2 (7/1.04) HDCU XLPE
1542773 CABLE Building 1C 4mm2 (7/0.85) Cu PVC Red
1542919 CABLE, Power, Electrical 0.6/1kV, 6mm2, 1 Core, (7/1.04) CU PVC Insulated Green / Yellow
1542943 CABLE Building 1C 10mm2 (7/1.35) Cu PVC
1543095 CABLE Electrical 1C 16mm2 (7/1.70) Cu XLPE
1543133 CABLE Electrical 1C 150mm2 (37/2.25) Cu XLPE
1543140 CABLE Electrical 1C 185mm2 (37/2.52) Cu XLPE PVC Black
1702852 BOLT Hex M10 x 25mm Galv c/w Galv Hex Nut
1703255 BOLT Hex M12 x 40mm Galv c/w Galv Hex Nut
1703263 BOLT Hex M12 x 50mm Galv c/w Galv Hex Nut
1703816 BOLT Hex M16 x 40mm Galv c/w Galv Hex Nut
1704065 BOLT Hex M16 x 350mm Galv c/w Galv Hex Nut
1704596 BOLT Hex M20 x 300mm Galv c/w Galv Hex Nut
1712911 EYEBOLT M16 x 200mm Galv c/w Galv Hex Nut
1727649 BOLT Hex M16 x 50mm S/Steel Grade 316 c/w S/Steel Hex Nut Grade 304
I.I.No. DESCRIPTION
1727678 SETSCREW Hex M12 x 40mm S/Steel Grade 316 c/w S/Steel Hex Nut Grade 304
1727679 BOLT Hex M12 x 50mm S/Steel Grade 316 c/w S/Steel Hex Nut Grade 304
1728507 EYENUT M16 Galv
1749330 NUT, Hex, M12, Stainless Steel Grade 304
1757622 COACHSCREW M10 x 50mm Galv
1757894 COACHSCREW M12 x 100mm Galv
1757924 COACHSCREW M12 x 150mm Galv
1762602 SETSCREW Hex M8 x 40mm S/Steel Grade 316 c/w S/Steel Hex Nut Grade 304
1762608 SETSCREW Hex M10 x 25mm S/Steel Grade 316 c/w S/Steel Hex Nut Grade 304
1762644 SETSCREW Hex M12 x 25mm S/Steel Grade 316 c/w S/Steel Hex Nut Grade 304
1762652 SETSCREW Hex M12 x 35mm S/Steel Grade 316 c/w S/Steel Hex Nut Grade 304
1777534 WASHER Round M10 Galv
1777542 WASHER Round M12 Galv
1777569 WASHER Round M16 Galv
1777577 WASHER Round M20 Galv
1778010 WASHER Spring M16 S/Steel Grade 316
1778093 WASHER Volute M16/20 S/Steel Grade 316
1778107 WASHER Volute M20/24 S/Steel Grade 316
1779103 WASHER Round M16 S/Steel Grade 316
1779110 WASHER Round M8 S/Steel Grade 316
Specification for UDC COMPATIBLE MATERIALS LISTING
CATEGORY B MATERIAL LIST
Check this is the latest version before use. Page 25 of 29 Specification RSM02 Ver 5
Ergon Energy Corporation Limited ABN 50 087 646 062
I.I.No. DESCRIPTION
1779111 WASHER Round M10 S/Steel Grade 316
1779112 WASHER Round M12 S/Steel Grade 316
1779138 WASHER Spring M10 S/Steel Grade 316
1779139 WASHER Spring M12 S/Steel Grade 316
1779154 WASHER Spring M10 Galv.
1779156 WASHER Spring M12 Galv.
1779158 WASHER Spring M16 Galv.
1780535 WASHER Round M12 S/Steel Grade 316
1780586 WASHER Square M16 50x50x5mm Galv
1780594 WASHER Square M20 75x75x6mm Galv
1865711 FOAM Self-expanding Polyurethane 500gm Pressure Pack superceded
1975817 TAPE 3M Scotch Super 33+ Black PVC
1975825 PUTTY 3MScotchfil 36mm x 1.5m
1978107 TAPE 3M Scotch Electrical No.35 Red
1978115 TAPE 3M Scotch Electrical No.35 White
1978123 TAPE 3M Scotch Electrical No.35 Blue
1978212 TAPE 3m Scotch Vinyl Mastic 101mm x 3m
2113005 CONDUIT, Non-metallic, Flexible PVC, 16mm Black (30M Rolls)
2173040 SADDLE Double Sided 25mm HFT with 8mm Fixing Holes
2400040 EYEBOLT M16 x 150 Galv c/w Galv Hex Nut
2400152 COACHSCREW M16 x 80mm Galv
2400186 NUT Unistrut M8 Type P4007 suit P3300 Channel
I.I.No. DESCRIPTION
2400187 NUT Unistrut M10 Type P4008 suit P3300 Channel
2400260 CABLE ELECTRICAL UNDER GROUND 0.6/1kV, 2 Core, 4mm2 (7/0.85) Cu Neutral screened PVC Insulated, PVC Sheathed Nylon Jacket
2400399 BEND,ELECTRICAL CONDUITUPVC, 80mm, 90Deg, 450mm Radius, Light Duty, Orange
2400662 EYEBOLT M16 x 250 Galv c/w Galv Hex Nut
2400821 SADDLE Copper 8mm (5/16”) Double Sided w/- 2x5mm Holes
2400888 BASE PILLAR URD 530mm x 530mm x 320mm H for large Green Polyethylene Pillars
2400889 COVER PILLAR Large Green Polyethylene Link Pillars suit Base IIN 2400888
2400915 HEATSHRINK GLOVE 4C 16mm2 LV XLPE/PLYSW PVC
2401071 TERMINAL STRIP Neutral Link 5Dbl Screws 16mm2 Cu Lug
2401220 BRACKET 11/22kV Cable Termination
2402333 CIRCUIT BREAKER 16A 250-440V 6kA, DIN Rail Mtg.
2402959 SETSCREW Hex M10 x 20mm S/Steel Grade 316 c/w S/Sl Hex Nut Grade 304
2403010 POLE, PUBLIC LIGHTING, METAL Major Road, 10m, Slip Base Mounted, Steel.
2403016 POLE, PUBLIC LIGHTING, METAL Major Road 7m, Slip Base Mounted, Steel.
2403164 FUSE LINK 100A 500V HRC Din Type Size 2.
2403168 FUSE LINK 125A 500V HRC Din Type Size 2.
Specification for UDC COMPATIBLE MATERIALS LISTING
CATEGORY B MATERIAL LIST
Check this is the latest version before use. Page 26 of 29 Specification RSM02 Ver 5
Ergon Energy Corporation Limited ABN 50 087 646 062
I.I.No. DESCRIPTION
2403244 CABLE Building 2.5mm2 2Core (7/0.67) Cu PVC Black
2403554 COVER U/G Electrical Cable PVC Orange 200mmx5mmx2m Long Marked ‘ELECTRIC CABLE’
2403725 OUTREACH ARM, 1.5m, Galv, Double, Minor Road Street Lighting.
2403730 HOOK SCREW Service Coach screw Thread w/- Neutral Bonding Tab
2403766 Cable Lubricant 10 litre
2403871 NUT Unistrut Channel M8 Type P1007
2403872 NUT Unistrut Channel M10 Type P1008
2403911 CLAMP Trifoil suit 3x185mm2 Cable
2403912 CLAMP Trifoil suit 3x35mm2 Cable
2404019 CLAMP Trefoil Cast Alum suit 22kV 630mm2 Cable
2404139 FUSE LINK 40A 22kV HRC RMU Unit Din Type Air Insulated
2404207 URD 250A CFS Unit suits Linking Pillar & Commercial/Industrial Pillar
2404208 FRAME, LV Pillar Large, Support Frame Assembly c/w Neutral Bars & Fuse Panel
2404209 FUSE LINK Solid Cu 250A 500V Din Type Size 1.
2404210 ELBOW CONNECTOR SET (3) 630A suit 22kV 1C 185mm2 Al XLPE cable. Tfx & RMU Terms.
2404223 ELBOW CONNECTOR 200A Deadbreak suit 22kV 185mm2 Al 1C XLPE cable. Tfx & RMU Terms.
2404363 Grease, Pfisterer P1
2404421 FORCE SPRING Stainless Steel Size 3 (Constant Force) U/G Cable Earth Kits
I.I.No. DESCRIPTION
2404544 EARTH ELECTRODE 1.44m x 13mm Dia Cu Clad Steel Taper Jointed
2404546 COUPLING Earth Rod 13mm Dia Taper Joint type
2404548 DRIVING POINT Earth Rod 13mm Dia Taper Joint type
2404922 FUSE LINK 25A 11kV HRC RMU Unit Din Type Air Insulated.
2404926 FUSE LINK,CARTRIDGE 12kV, Full Range, RMU DIN Type Air Insulated, 50 Amp, Barrel 292mm Lg 76.2mm Dia plus End
2404944 FUSE LINK Solid Cu 400A 500V Din Type Size 2.
2405059 Cable Lubricant 20 litre
2405101 LUG Compression Cu 185mm2 M12 Bolt Hex Die A/F20.0mm Cu
2405324 EARTH ENHANCEMENT COMPOUND Premixed
2406020 ADHESIVE to Attach Site Identifier No’s
2406142 TUBING Heat-shrink 51/16 x 225mm Long
2406179 SIGN Plaque U/G Cable Location Small (Kerb). This plaque is generally used in paved areas and does not replace the Brass “E” markers (for use at kerbs) required to identify cable locations.
2406180 SIGN Plaque U/G Cable Location Large (Footpath). This plaque is generally used in paved areas and does not replace the Brass “E” markers (for use at kerbs) required to identify cable locations.
2406252 FUSE LINK 250A 500V HRC Din Type Size 2
2406261 FUSE LINK 63A 11kV HRC RMU Unit Din Type Air Insulated.
Specification for UDC COMPATIBLE MATERIALS LISTING
CATEGORY B MATERIAL LIST
Check this is the latest version before use. Page 27 of 29 Specification RSM02 Ver 5
Ergon Energy Corporation Limited ABN 50 087 646 062
I.I.No. DESCRIPTION
2406323 BRACKET Streetlight Major Road Spigot Adaptor for Wood Pole
2406398 LUG Compression Bi-Metal 240mm2 Cu Palm M12 Bolt Hex Die A/F 28.4mm Cu
2406451 Numeral, Sign; [0], Black on yellow reflective, Pressure sensitive marker 3m (Sheets of 55) (See also 0104407)
2406713 CONNECTOR IPC 95/240mm2 Bare Alum Main 35/95mm2 IPC Tap w/- S/S Fasteners
2406888 SCREW Timber 12/11 x 25mm 5/16” HWF T17 Class 3
2406972 BUSHING Strain Relief Nylon R/Angle Type 8.0mm Black - 2C cables
2406976 BEND UPVC Conduit 40mm NB 90Deg. 300mm Rad HD Orange
2406977 BOLT Hex M6 x 65mm S/Steel Grade 316 c/w S/Steel Hex Nut Grade 304
2406978 WASHER Round suit M6 Bolt (OD 16mm Approx) S/Steel Grade 316
2406979 WASHER Round M6 S/Steel Grade 316
2406980 SCREW Metal Thread M5x40mm Nickel Plated Brass Cheese Hd
2406981 SCREW Metal Thread M5x65mm Nickel Plated Brass Cheese Hd
2406982 NUT Hex M5 Thin Nickel Plated Brass
2406983 WASHER Round M5 Nickel Plated Brass
2406985 GUARD Cable Steel Galv 2700 x 100 x 100mm
2406990 TERMINATION KIT O/D11kV 185mm2 Alum Triplex XLPE
I.I.No. DESCRIPTION
2406991 TERMINATION KIT O/D LV 16mm2 Alum 4Core XLPE Cable with 4W Glove, 4 x Tubing, 4 x Crimp Links. This item suits Insect Protected & Non-Insect Protected cables.
2406992 POST U/G Cable Warning Sign
2406993 SIGN Plaque U/G cable Location Corner. This plaque is generally used in paved areas and does not replace the Brass “E” markers (for use at kerbs) required to identify cable locations.
2407011 TUBING Heat Shrink 75/25 220mm Long
2407012 SITE IDENTIFICATION NUMBER, 5 Digits,
2418861 TERMINAL BOARD Panel, Street Light Pole, Slip Base.
2422160 TERMINAL BOX Fixed Base Pole Kit C/W , 2 x Terminal Blocks For Fixed Base Street Light Pole
2422657 GUARD Cable, Polymeric 2700mm minimum Long, Suitable For 40mm Dia Cable
2424919 TERMINAL BOARD Panel, Street Light Pole, Slip Base.
2427359 TERMINATION KIT,ELECTRICAL CABLE,UNDERGROUND, Indoor, LV, 4-16MM2 Cu, Neutral Screened PVC Insulated, Nylon Jacket (NJ) Insect Protection, PVC Sheathed Cable
2429876 TERMINATION KIT OUTDOOR 11kV, 185mm2, Al, Triplex (1C wound 3 in hand) TR-XLPE Cable, Insect Protected, Inc Cable Term Kit Solvent Wipes, Cable Core & Screen Lugs (For use with cable 2429975)
2429884 TERMINATION KIT OUTDOOR 22kV, 35mm2, Al, Triplex (1C wound 3 in hand) TR-XLPE Cable, Insect Protected, Inc Cable Term Kit Solvent Wipes, Cable Core & Screen Lugs (For use with cable 2429991)
Specification for UDC COMPATIBLE MATERIALS LISTING
CATEGORY B MATERIAL LIST
Check this is the latest version before use. Page 28 of 29 Specification RSM02 Ver 5
Ergon Energy Corporation Limited ABN 50 087 646 062
I.I.No. DESCRIPTION
2430122 TERMINATION KIT INDOOR 11kV, 35mm2, Al, Triplex (1C wound 3 in hand) TR-XLPE Cable, 11kV Magnefix MD Series RMU & SFU, Inc Cable Term Kit, Holec 502.0047/3 Connection Kit, Cable Screen Lugs & Fixings (For use with cable 2429942)
2430130 TERMINATION KIT OUTDOOR 11kV, 35mm2, Al, Triplex (1C wound 3 in hand) TR-XLPE Cable, Inc Cable Term Kit Solvent Wipes, Cable Core & Screen Lugs (For use with cable 2429942)
2430148 TERMINATION KIT OUTDOOR 11kV, 35mm2, Al, Triplex (1C wound 3 in hand) TR-XLPE Cable, Insect Protected Inc Cable Term Kit Solvent Wipes, Cable Core & Screen Lugs (For use with cable 2429967)
2430155 TERMINATION KIT INDOOR 11kV, 35mm2, Al, Triplex (1C wound 3 in hand) TR-XLPE Cable, Insect Protected, 11kV ABB SD Series RMU, Inc Cable Term Kit, Bush Insulation, Cable Core &Screen Lugs & Fixings (For use with cable 2429967)
2430163 TERMINATION KIT INDOOR 11kV, 35mm2, Al, Triplex (1C wound 3 in hand) TR-XLPE Cable, Insect Protected, 11kV Magnefix MD Series RMU, Inc Cable Term Kit Holec 502.0047/3 Connection Kit Cable Screen Lugs & Fixings (For use with cable 2429967)
I.I.No. DESCRIPTION
2430171 TERMINATION KIT INDOOR 11kV, 35mm2, Al, Triplex (1C wound 3 in hand) TR-XLPE Cable, 11kV ABB SafeLink RMU, Inc Cable Term Kit, Cable Core & Screen Lugs Fixings (For use with cable 2429942)
2430189 TERMINATION KIT INDOOR 11kV, 35mm2, Al, Triplex (1C wound 3 in hand) TR-XLPE Cable, Insect Protected, 11kV ABB SafeLink RMU, Inc Cable Term Kit, Cable Core & Screen Lugs & Fixings (For use with cable 2429967)
2430197 TERMINATION KIT INDOOR 11kV, 35mm2, Al, Triplex (1C wound 3 in hand) TR-XLPE Cable, 11kV ABB SD Series RMU, Inc Cable Term Kit, Solvent Wipes Bushing Insulation, Cable Core & Screen Lugs & Fixings (For use with cable 2429942)
TBA Terminations for 50mm2 and 300mm2 cables
Specification for UDC COMPATIBLE MATERIALS LISTING
Check this is the latest version before use. Page 29 of 29 Specification RSM02 Ver 5
Ergon Energy Corporation Limited ABN 50 087 646 062
Appendix C – Supplier Details SUPPLIER DETAILS Supplier Name Shown on Schedule Full Supplier Name Postal Address Phone No. Fax No.
ABB Australia ABB Australia Pty Limited PO Box 3042, Darra Qld 4076 07 3713 9111 07 3713 9200
AK Power Sol. AK Power Solutions Pty Ltd PO Box 6907 Blacktown DC NSW 2148 02 9676 3500 02 9676 3511
Bonnell’s Supply Bonnell’s Supply 5 Rose Street, Campbelltown NSW 2560 02 4627 6500 02 4627 6533
Bri-Tech P/L Bri-Tech Pty Ltd 304 Fison Avenue East, Eagle Farm Qld 4009 07 3868 3811 07 3868 3313
Delta Power Delta Power Australia P/L PO Box 203 Narellan NSW 2567 02 4648 3336 02 4648 3337
Energex Energex
Material & Inventory Manager PO Box 1461 Brisbane QLD 4001
E-mail - [email protected]
GM Poles GM Poles Pty Ltd 36 Industrial Avenue, Wacol, Qld 4076 07 3271 3222 07 3271 3078
Ingal EPS Ingal EPS PO Box 3559 Sunnybank, Qld 4109 07 3323 2555 07 3323 1297
Midland Metals Midland Metals Overseas Pte Ltd 24 Raffles Place, 25-05 Clifford Centre Singapore 048621
001165 6536 1290
001565 6536 1831
Olex Aust. Olex Australia Pty Limited 541 Bilsen Road, Geebung Qld 4034 07 3259 2600 07 3259 2606
Phillips Lighting Phillips Lighting Australia Locked Bag 30 North Ryde NSW 1670 _ _
Pollards Pollards Galvanizing Pty Ltd PO Box 1409 Cairns, Qld, 4870 07 4051 5444 07 4051 0961
Rexel Aust. Rexel Australia 14 Toonburra Street, Bundaberg Qld 4670 07 4152 4177 07 3335 1222
Rocla Conc. Rocla Concrete Poles Monier Road, Parkhurst, Qld 4702 07 4936 1233 07 4936 1708
Schneider Elect. Schneider Electric (Australia) Pty Limited 30 Graystone Street, Tingalpa Qld 4173 07 3890 2112 07 3890 2098
Sylvania Sylvania Lighting Int. Pty Ltd 25 Donkin Street, South Brisbane Qld 4000 07 3844 2071 07 3846 3689