19
ROOM NAME ABBREVIATIONS DRAWING ABBREVIATIONS INDEX OF DRAWINGS BUILDING SUMMARY LEGEND A ACSNG ACCESSIONING (LAB) ACTV ACTIVITY ADMIN RCPT ADMINISTRATIVE RECEPTION ADMIT ADMITTING STATION ADL BDRM ADULT BEDROOM ADL KIT ADULT KITCHEN AEROB AEROBICS AREA AC AIR CONDITIONING ALC ALCOVE ANESTH ANESTHESIA ANIM STOR ANIMAL STORAGE ANTE ANTE ROOM AV AUDIO VISUAL AUDLGY AUDIOLOGY ATM AUTOMATED TELLER AUTOP AUTOPSY B BARM KIT BARIUM KITCHEN BED RM BEDROOM BIO HAZ BIO - HAZARD BIO EQUIP BIOLOGY EQUIPMENT BIO MED BIO - MEDICAL BIO MED ENG BIO - MEDICAL ENGINEERING BIO MED LAB BIO - MEDICAL LABORATORY BIO MED SAT BIO - MEDICAL SATELLITE BIO WST BIO - MEDICAL WASTE BLD BNK BLOOD BANK BLD DNR BLOOD DONOR AREA BLD DWG BLOOD DRAWING BLD GAS BLOOD GAS LABORATORY BRD RM BOARD ROOM BLR RM BOILER ROOM BNE DNSTY BONE DENSITY BKPG BOOK KEEPING BTQUE BOUTIQUE BRKDN BREAK DOWN BRK RM BREAK ROOM BRKDN/EQ BREAKDOWN EQUIPMENT BRST FD BREAST FEEDING BRST ULT BREAST ULTRASOUND BULK ST BULK STORAGE C CG WSH CAGE WASH CNTEN CANTEEN CARD GYM CARDIAC CATH GYM CARD CATH CARDIAC CATHETERIZATION CARD CIRCUIT CARDIAC CIRCUIT CARD REHAB CARDIAC REHABILITATION CARD RM CARDIAC ROOM C/V COND CARDIOVASCULAR CONDITIONING C/V EXAM CARDIOVASCULAR EXAM C/V STRESS TEST CARDIOVASCULAR STRESS TESTING CAST CAST ROOM/ORTHO/FRACTURE CATH PROC CATHETERIZATION PROCEDURE CHNG (M - MALE, F - FEMALE, CHANGING ROOM H/C - HANDICAPPED) CHRT RD CHART READING CHRT/HLD CHART HOLDING CHRT/DCT CHARTING/DICTATION CHEM COLD ST CHEMICAL COLD STORAGE CHEM ST CHEMICAL STORAGE CHEM CHEMISTRY CHEMO CHEMOTHERAPY CHILD BIRTH ED CHILD BIRTH EDUCATION CHILD WTG CHILD BIRTH WAITING CLSRM CLASSROOM CLSRM/CONF CLASSROOM CONFERENCE CLSRM/CNSLT CLASSROOM CONSULT CLN EQP CLEAN EQUIPMENT CLN HOLD CLEAN HOLDING CLN LINEN CLEAN LINEN CLN MED CLEAN MEDICATION CLN ST CLEAN STORAGE CLN SPLY CLEAN SUPPLY CLN SPLY/ST CLEAN SUPPLY STORAGE CLN UTIL CLEAN UTILITY CLERCL/FLS CLERICAL/FILES CLIN CONS CLINICAL CONSULT CLIN WK CLINICAL WORKSTATION CL CLOSET CLD RM COLD ROOM COMM COMMUNICATION COMM EQ COMMUNICATION EQUIPMENT COMMUNITY COMMUNITY ASSEMBLY CT COMPUTED TOMOGRAPHY CT CNTRL COMPUTED TOMOGRAPHY CONTROL CT IMAG COMPUTED TOMOGRAPHY IMAGING CT PREP COMPUTED TOMOGRAPHY PREPARATION CMWP COMPOSITE METAL WALL PANEL CT READ COMPUTED TOMOGRAPHY READING CT SCAN COMPUTED TOMOGRAPHY SCAN CT SIM COMPUTED TOMOGRAPHY SIMULATOR COMP COMPUTER COMP SERVER COMPUTER SERVER COMP ST COMPUTER STATION CNCSN CONCESSION AREA CNCRG CONCIERGE CONF/CNSLT CONFERENCE/CONSULT CONF CONFERENCE CONF/EDU CONFERENCE/EDUCATION CONF/GRP/THERAPY CONFERENCE/GROUP/THERAPY CONF/LIB CONFERENCE/LIBRARY CONF/LNG CONFERENCE/LOUNGE CONF/OFF CONFERENCE/OFFICE CONF/TEACH CONFERENCE/TEACHING COUNSEL COUNSELING CNSLT CONSULT CNSLT/CONF CONSULT/CONFERENCE COPY COPY AREA CORR CORRIDOR CTYRD COURTYARD CCU CRITICAL CARE UNIT C - SECT C - SECTION DELIVERY CYSTOL LAB CYSTOLOGY LABORATORY CYSTOL CYSTOSCOPY D DKRM DARKROOM DAYRM DAY ROOM DECON DECONTAMINATION DECON SHWR DECONTAMINATION SHOWER DENTAL LAB DENTAL LABORATORY DIAL DIALYSIS DICT DICTATION DICT WK DICTATION WORKROOM DIET DIETICIAN DGTL IMAG DIGITAL IMAGING DIN DINING DIN/ACT DINING/ACTIVITY DISH DISHROOM DSPTCH DISPATCH DISTRIB DISTRIBUTION DSMTRY DOSIMETRY E ECHO ECHOCARDIOGRAM ECHO READ ECHOCARDIOGRAM READING EDUC EDUCATION ROOM ELEC ELECTRICAL ELEC CL ELECTRICAL CLOSET ELEV CTRL ELEVATOR CONTROL EKG READ ELECTROCARDIOGRAM READING EKG ELECTROCARDIOGRAM TESTING EEG ELECTROENCEPHALOGRAM TESTING EP LAB ELECTROPHYSIOLOGY LABORATORY EREG LAB ELECTRORETINOGRAPHY EMER ELEC EMERGENCY ELECTRICITY EMER GEN EMERGENCY GENERATOR ROOM EMP HEALTH EMPLOYEE HEALTH ENDO ENDOSCOPY PROCEDURE ENV SERV ENVIRONMENTAL SERVICES EQPM EQUIPMENT EQPM ALC EQUIPMENT ALCOVE EXAM EXAM ROOM EXAM/CNSLT EXAM/CONSULT EXAM/TREAT EXAM/TREATMENT EXERC EXERCISE EXIST EXISTING F FAM RM FAMILY ROOM FEED FEEDING ROOM FF FINISH FLOOR FILE FILE STORAGE FILES/ADMIN FILES ADMINISTRATION FILM PROC FILM PROCESSING ROOM FILM READ FILM READING FIN FINANCE FIN COUN FITNESS CTR AUTOCL FINANCIAL COUNSEL FITNESS CENTER AUTOCLAVE/FLASH STERILIZER FLUORO FLUOROSCOPY FMWP FORMED METAL WALL PANEL FOOD ST FOOD STORAGE FORM PREP FORMULA PREPARATION FREE WGT FREE WEIGHT AREA FR SECT FROZEN SECTION FNCTN RM FUNCTION ROOM FUT EXP FUTURE EXPANSION G GAR GARAGE GEN STORES GENERAL STORES GEN GENERATOR GIFT GIFT SHOP GLAUC CTR GLAUCOMA CENTER GWN WTG GOWN WAITING GWN WTG F GOWN WAITING FEMALE GWN WTG M GOWN WAITING MALE GRIEVING GRIEVING ROOM GROSS GROSSING I ICE ICE MACHINE INF RESUS INFANT RESUSCITATION INFEC CTRL INFECTION CONTROL INFO INFORMATION DESK INFO SYSTEM INFORMATION SYSTEM INFUS INFUSION AREA INT INTERVIEW INV INVENTORY ISOL ISOLATION ROOM IV PREP IV PREPARATION IV ST IV STORAGE K KIT KITCHEN KIT/SAT KITCHEN SATELLITE L LDR LABOR/DELIVERY/RECOVERY LDRP LABOR/DELIVERY/RECOVERY/POST PARTUM LAB LABORATORY LAB/SAT LABORATORY/SATELLITE LDRY LAUNDRY LIB LIBRARY LIB/CONF LIBRARY/CONFERENCE LIB/MEDIT LIBRARY/MEDITATION LIGHT ADAPT LIGHT ADAPTATION LINR ACC LINEAR ACCELERATOR LIN CH LINEN CHUTE LIN STR LINEN STORAGE LR LIVING ROOM DOCK LOADING DOCK LKRS LOCKERS LKRS F LOCKERS FEMALE LKRS M LOCKERS MALE LKRS/CHNG LOCKERS/CHANGING LONG EX LONG EXAM ROOM M MACH RM MACHINE ROOM MRI MAGNETIC RESONANCE IMAGING MAIL MAIL ROOM MAINT MAINTENANCE MAMMO/STEREO MAMMOGRAPHY/STEREOTACTIC MGMT MANAGEMENT MANIFOLD MANIFOLD ROOM MRKTG MARKETING MATL MGMT MATERIALS MANAGEMENT MECH MECHANICAL MECH/ELEC MECHANICAL/ELECTRICAL MED REC MEDICAL RECORDS MEDS MEDICATION ROOM MEDIT MEDITATION MTG MEETING ROOM MEZZ MEZZANINE MICRO BIO LAB MICROBIOLOGY LABORATORY MOB DK MOBILE DOCK N NARC CLO NARCOTICS CLOSET NICU NEONATAL INTENSIVE CARE UNIT NEW NUR NEWBORN NURSERY NIGHT PHARM NIGHT PHARMACY NITROGEN ST NITROGEN STORAGE NOISY ACTV NOISY ACTIVITY NOUR NOURISHMENT NUC MED NUCLEAR MEDICINE NRS STA NURSE STATION O OBSERV OBSERVATION OBSERV/EXAM OBSERVATION EXAM OBSERV/TREAT OBSERVATION TREATMENT OB/GYN OBSTETRIC/GYNECOLOGY OT OCCUPATIONAL THERAPY OFF OFFICE OFF SHRD OFFICE SHARED OFF/CONF OFFICE/CONFERENCE OFF/CONS OFFICE CONSULT OFF/EXAM OFFICE/EXAM ON - CALL LNG ON - CALL LOUNGE OR OPERATING ROOM OR CARDIAC OR CARDIOTHORACIC OR EQ ST OR EQUIPMENT STORAGE OR ORTHO OR ORTHOPEDIC ORTHO ORTHOPEDIC ROOM ORTHO ST ORTHOPEDIC STORAGE OSTOMY ST OSTOMY STORAGE OXYGEN ST OXYGEN STORAGE P PNTR PANTRY PARENT LKRS PARENT LOCKERS PASS PASSAGE PATH LAB PATHOLOGY LABORATORY PAT BAY PATIENT BAY PAT EDUC PATIENT EDUCATION PAT HOLD PATIENT HOLDING PAT INTAKE PATIENT INTAKE PAT LKRS PATIENT LOCKERS PAT LNG PATIENT LOUNGE PAT PREP PATIENT PREPARATION PAT REG PATIENT REGISTRATION PED PEDIATRIC PED BAY PEDIATRIC BAY PED BLOOD DWG PEDIATRIC BLOOD DRAWING PED OBSERV PEDIATRIC OBSERVATION PED PLAY PEDIATRIC PLAY PHARM PHARMACY PHARM ST PHARMACY STORAGE PHLEB PHLEBOTOMY PT PHYSICAL THERAPY PT GYM PHYSICAL THERAPY GYM PT TRT PHYSICAL THERAPY TREATMENT/ MODALITY ROOM PT/OT PHYSICAL THERAPY/OCCUPATIONAL THERAPY PT/OT GYM PHYSICAL THERAPY/OCCUPATIONAL THERAPY GYM PET POSITION EMISSION TOMOGRAPHY PACU POST ANESTHESIA CARE UNIT PREP PREPARATION AREA PREP/RECOV PREPARATION/RECOVERY PRIV PRIVATE PRIV BAY PRIVATE BAY PRIV BDRM PRIVATE BEDROOM PRIV RM PRIVATE ROOM PROC PROCEDURE ROOM PROC/ASSESS PROCEDURE/ASSESSMENT PSYCH PSYCHIATRY PSYCHOL PSYCHOLOGY PUMP AM PUMPING ROOM Q RAD RADIOLOGY READ READING ROOM RCPT/CSHR RECEPTION/CASHIER REC ARC RECORD ARCHIVE REC ST RECORD STORAGE RECOV RECOVERY RECOV BAY RECOVERY BAY RECOV/OBS RECOVERY OBSERVATION RECYC RECYCLING REFR REFRIGERATOR REGIST REGISTRATION REGIST/FIN REGISTRATION/FINANCIAL REHAB GYM REHABILITATION GYM RESRCH RESEARCH RES RM RESIDENT ROOM RESRCE RESOURCE RESRCE LIB RESOURCE LIBRARY RESP RESPIRATORY RT RESPIRATORY THERAPY REST RESTAURANT RETHERM RETHERM PANTRY RETINA CTR RETINA CENTER QUIET ACTV QUIET ACTIVITY QUIET RM QUIET ROOM R S STR STAIR STAT LAB STAT LABORATORY STEAM STEAM ROOM STER PROC STERILE PROCEDURE STER ST STERILE STORAGE STER SPLY STERILE SUPPLY STER STERILIZER ST STORAGE STRESS LAB STRESS LABORATORY STRESS TEST STRESS TESTING STCH ALC STRETCHER ALCOVE STCH ST STRETCHER STORAGE SUB STA SUB - STATION SUB STER SUB - STERILE SUB WTG SUB - WAITING SPLY SUPPLY SUPP SUPPORT SURG SURGERY SYN LAB SYNCOPE LABORATORY T TECH TECHNICIANS TEL TELEPHONE TEL ALC TELEPHONE ALCOVE TEL CL TELEPHONE CLOSET TEL VND TELEPHONE VENDING TEL/DATA TELEPHONE/DATA TV TELEVISION LOUNGE TEMP ST TEMPORARY STORAGE TEST TESTING TLT (M - MALE, F - FEMALE, P - PUBLIC TOILET H/C - HANDICAP, S - STAFF, U - UNISEX) TLT/SH (H/C - HANDICAP, TB - TUB) TOILET SHOWER TRANS TRANSCRIPTION TRANS WK TRANSCRIPTION WORKSTATION TRANSFUS TRANSFUSION TRANSFUS BAY TRANSFUSION BAY TRSH TRASH TRAUMA TRAUMA ROOM TRMT TREATMENT TRMT BAY TREATMENT BAY TREAT/PROC TREATMENT/PROCEDURE ROOM TUB TUB ROOM U ULTRA ULTRASOUND UBM ULTRASOUND BIOMICROSCOPY UNIT SECY UNIT SECRETARY UTIL UTILITY V VND VENDING VEST VESTIBULE VIEW VIEWING VISUAL VISUAL FIELD W WAIT WAITING WARM WARMING PANTRY WASH WASHING AREA W/C ALC WHEELCHAIR ALCOVE W/C ST WHEELCHAIR STORAGE WK AREA WORK AREA WK STA WORK STATIONS WK RM WORKROOM PRIV H/C HANDICAP PRIVACY BEDROOM SHWR H/C HANDICAP SHOWERS TLT H/C STAFF HANDICAP STAFF TOILET TLT H/C HANDICAP TOILET TLT SH H/C HANDICAP TOILET/SHOWER TUB H/C HANDICAP TUB HEM HEMATOLOGY HISTO HISTOLOGY HOLD HOLDING HOOD HOOD AREA HOT LAB HOT LABORATORY HSKPG HOUSEKEEPING HVF HUMPHREYS VISUAL FIELD HYDRO HYDROTHERAPY TANKS H S SCHED SCHEDULING SCOP CLN SCOPE CLEANING SCOP ST SCOPE STORAGE SCRUB ALC SCRUB ALCOVE SCRUB SCRUB AREA SECL SECLUSION ROOM SECUR SECURITY SEMI PRIV RM SEMI PRIVATE ROOM SERO SEROLOGY SERV SERVERY SVC SERVICE SERV ENTRY SERVICE ENTRY SHELL SHELL SPACE SHWR (M - MALE, F - FEMALE, SHOWER H/C - HANDICAP) SIM SIMULATOR SINK ALC SINK ALCOVE SITZ SITZ BATH SLP LAB SLEEP LABORATORY SLP STUDY SLEEP STUDY ROOM SOIL HOLD SOILED HOLDING SOIL LN SOILED LINEN SOIL UTL SOILED UTILITY SOL SOLARIUM SORT SORTING AREA SP CARE NUR SPECIAL CARE NURSING SPEC PROC SPECIAL PROCEDURES SP SERV SPECIAL SERVICES SP STUD SPECIAL STUDIES SP TEST SPECIAL TESTING SPEC SPECIMEN STAGE I STAGE I - PACU STAGE I ISOL STAGE I ISOLATION - PACU STAGE II STAGE II - RECOVERY STAGE II ISOL STAGE II ISOLATION - RECOVERY A AB ANCHOR BOLT AD AREA DRAIN AC AIR CONDITIONING ACT ACOUSTICAL CEILING TILE ADD ADDENDUM ADD'L ADDITIONAL ADJ ADJACENT AFF ABOVE FINISHED FLOOR AGGR AGGREGATE AL ALUM ALUMINUM ALT ALTERNATE ANOD ANODIZED APPROX APPROXIMATE ARCH ARCHITECTURAL B B.M. BENCH MARK BD BOARD BETW BETWEEN BF BACKFACE BG BUMPER GUARD BL BED LOCATOR BL BUILDING LINE BLDG BUILDING BLKG BLOCKING BM BEAM BOT BOTTOM BR BUMPER RAIL BRG BEARING BSMT BASEMENT BU ROD BACK - UP ROD BUR BUILT - UP ROOF BW BEARING WALL C C COMPACT PARKING SPACE CC CUBICLE CURTAIN CDR CARD READER CEM CEMENT CER CERAMIC CG CORNER GUARD CIP CAST IN PLACE CJ CONTROL JOINT CJ CONSTRUCTION JOINT CL CENTER LINE CLG CEILING CLR CLEAR CMU CONCRETE MASONRY UNIT COL COLUMN COMM COMMUNICATIONS CONC CONCRETE CONN CONNECTION CONST CONSTRUCTION CONT CONTINUOUS COORD COORDINATE CPE CHLORINATED POLYETHYLENE CORR CORRIDOR CR COLD ROLLED CR CRASH RAIL CSK COUNTERSUNK CT CERAMIC TILE CTD CENTERED CTR CENTER CW CURTAIN WALL D D DEPTH DBA DEFORMED BAR ANCHOR DET DETAIL DF DECORATIVE FILM DIA DIAMETER DIAPH DIAPHRAGM DIM DIMENSION DJ DEFLECTION JOINT DL DEAD LOAD DN DOWN DRG DRAWING DS DOWN SPOUT DWGS DRAWINGS DWLS DOWELS E EA EACH EF EACH FACE EFG ENTRANCE FLOOR GRILLE EIFS EXTERIOR INSULATION AND FINISH SYSTEM EJ EXPANSION JOINT EL ELEVATION ELEC ELECTRIC ELEV ELEVATOR EOS EDGE OF SLAB EQ EQUAL EQUIP EQUIPMENT ESC ESCALATOR EW EACH WAY EWC ELECTRIC WATER COOLER EXIST EXISTING EXP BLT EXPANSION BOLT EXT EXTERIOR F FD FLOOR DRAIN FDN FOUNDATION FE FIRE EXTINGUISHER FEC FIRE EXTINGUISHER CABINET FF FINISH FLOOR FHC FIRE HOSE CABINET FIB FIBERGLASS FIN FINISH FLR FLOOR FS FAR SIDE FT FOOT FT FLOOR TRANSITION FTG FOOTING FV FIELD VERIFY FVC FIRE VALVE CABINET G GA GAUGE GALV GALVANIZED GB GRADE BEAM GEN GENERAL GFRC GLASS - FIBER REINFORCED CONCRETE GI GALVANIZED IRON GL GLASS GM GLAZED MASONRY UNIT GND GROUND GR GRADE GRG GLASS - REINFORCED GYPSUM GYP BD GYPSUM BOARD H HB HOSE BIB HDW HARDWARE HDWD HARDWOOD HK HOOK HM HOLLOW METAL HOR HORIZONTAL HP HIGH POINT HR HOUR HS HEADED STUD HSKP HOUSEKEEPING HT HEIGHT HW HAND WASH HW HEAD OF WALL I IBC INTERNATIONAL BUILDING CODE ID INSIDE DIAMETER INSUL INSULATION INT INTERIOR K K KIPS (1000 LB) KO KNOCK - OUT KP KICKPLATE KPD KEYPAD KSF KIPS PER SQUARE FOOT L L ANGLE LAV LAVATORY LG LONG LKB LOCKABLE LL LIVE LOAD LLH LONG LEG HORIZONTAL LLV LONG LEG VERTICAL LOC LOCATION LP LOW POINT LT LIGHT LWC LIGHTWEIGHT CONCRETE M MAS MASONRY MAT'L MATERIAL MAX MAXIMUM MECH MECHANICAL MEMB MEMBRANE MEP MECHANICAL, ELECTRICAL AND PLUMBING MFG MANUFACTURER MGO MEDICAL GAS OUTLET MIN MINIMUM MISC MISCELLANEOUS MO MASONRY OPENING MOB MEDICAL OFFICE BUILDING MOD BIT MODIFIED BITUMEN MOD MODIFIED MSL MEAN SEA LEVEL MTL METAL N NA NOT AVAILABLE NIC NOT IN CONTRACT NOA NOTICE OF ACCEPTANCE BY FLORIDA GOVERNING AUTHORITY NOM NOMINAL NS NEAR SIDE NTS NOT TO SCALE NWC NORMAL WEIGHT CONCRETE O OA OVER ALL OC ON CENTER OD OUTSIDE DIAMETER OD OVERFLOW DRAIN OFCI OWNER FURNISHED, CONTRACTOR INSTALLED OFOI OWNER FURNISHED, OWNER INSTALLED OH OPPOSITE HAND OPNG OPENING OPP OPPOSITE OSF OUTSIDE FACE P P LAM PLASTIC LAMINATE PC PRECAST CONCRETE PCF POUNDS PER CUBIC FOOT PCP PORTLAND CEMENT PLASTER PENT PENTHOUSE PL PROPERTY LINE PL PLATE PLUMB PLUMBING PLYWD PLYWOOD PP PUSH PLATE POL POLISHED PORT CEM PORTLAND CEMENT PR PAIR PREFAB PREFABRICATED PSF POUNDS PER SQUARE FOOT PSI POUNDS PER SQUARE INCH PT POINT PT PNEUMATIC TUBE PTD PAINTED R R RISER RAD RADIUS RAF RUBBERIZED ASPHALT FLASHING RAM RUBBERIZED ASPHALT MEMBRANE RAU RUBBERIZED ASPHALT UNDERLAYMENT RCP REFLECTED CEILING PLAN RD ROOF DRAIN REBAR REINFORCING BAR RECP RECEPTACLE REF REFER OR REFERENCE REINF REINFORCING RELOC RELOCATE/RELOCATED REQ'D REQUIRED RFVC RECESSED FIRE VALVE CABINET RM ROOM RO ROUGH OPENING SAB SOUND ATTENUATION BLANKET SBC STANDARD BUILDING CODE SCHED SCHEDULE SDL SUPERIMPOSED DEAD LOAD SECT SECTION S/H SINGLE HUNG SHWR SHOWER SIM SIMILAR SO STRUCTURAL OPENING SOG SLAB ON GRADE SP STAND PIPE SPA SPACE, SPACING SPEC SPECIFICATION SQ SQUARE SS STAINLESS STEEL SSF SOLID SURFACE STA STATION STC SOUND TRANSMISSION CLASS STD STANDARD STIFF STIFFENER STIR STIRRUP STL STEEL STRUC STRUCTURAL SYM SYMMETRICAL SYS SYSTEM S T T TREAD T&B TOP AND BOTTOM TC TOP OF CURB TEL TELEPHONE TEMP TEMPERATURE THK THICK TLT TOILET TO TOP OF TOB TOP OF BEAM TOC TOP OF CONCRETE TOF TOP OF FOOTING TOP TOP OF PARAPET TOS TOP OF SLAB TOSTL TOP OF STEEL TRSH CH TRASH CHUTE TW TOP OF WALL TYP TYPICAL U U/C UNDER COUNTER U/G UNDERGROUND UNO UNLESS NOTED OTHERWISE VAR VARIES VCT VINYL COMPOSITION TILE VERT VERTICAL VEST VESTIBULE VWC VINYL WALL COVERING V W/ WITH W/C WHEEL CHAIR W/O WITHOUT W WIDTH WP WATERPROOF(ING) WD WOOD WF WIDE FLANGE WL WIND LOAD WP WORK POINT WPO WORK POINT - POINT OF ORIGIN WP1 WORK POINT - NUMBERED WWF WELDED WIRE FABRIC W NUMBERING SYSTEM: A2.10/01 DISCIPLINE: C - CIVIL L - LANDSCAPE A - ARCHITECTURE M - MECHANICAL E - ELECTRICAL P - PLUMBING S - STRUCTURAL K - FOOD SERVICE SERIES NUMBER SHEET NUMBER WITHIN SERIES NUMBER OF PLAN, DETAIL, ETC. ON SHEET CONCRETE/ PRECAST CONCRETE SOIL SAND, EIFS FINISH COAT, OR CEMENT PLASTER BRICK CMU STONE FIBERGLASS SEMI RIGID INSULATION FIBERGLASS BATT INSULATION MINERAL WOOL SEMI RIGID INSULATION EXPANDED POLYSTYRENE RIGID INSULATION EXTRUDED POLYSTYRENE RIGID INSULATION POLYISOCYANURATE RIGID INSULATION GYPSUM BOARD EXTERIOR GYPSUM SHEATHING EXTERIOR CEMENT BOARD COATED GLASS MAT WATER RESISTANT GYP BD PLYWOOD COVER BOARD MATERIALS ROOM NAME XXXXX X X 1 A0.X X X A3 A3 ROOM NAME/NUMBER EXISTING COLUMN CENTERLINE COLUMN CENTERLINE ACCESSORY DEMOLITION NUMBERED NOTES BUILDING WALL SECTION EXTERIOR ELEVATION SECTION DETAIL PLAN, BLOW - UP DETAIL INTERIOR ELEVATION PARTITION TYPE WITH NO SOUND ATTENUATION PARTITION TYPE WITH SOUND ATTENUATION CMU WALL NEW WALL EXISTING WALL DEMO WALL 1 HOUR FIRE WALL 2 HOUR FIRE WALL 3 HOUR FIRE WALL 4 HOUR FIRE WALL NON - RATED SMOKE WALL 1 HOUR SMOKE WALL 2 HOUR SMOKE WALL 1 HOUR SHAFT WALL 2 HOUR SHAFT WALL DRAWING SYMBOLS CEILING SYMBOLS BUILDING EXPANSION JOINT GYP BD CEILING SUPPLY AIR RETURN AIR ACCESS PANEL FLUORESCENT LIGHT WALL MOUNTED FLUORESCENT FIXTURE EXIT SIGNS - HATCH INDICATES EXIT TEXT AND ARROW INDICATES DIRECTION SMOKE DETECTOR WALL WASHER PENDANT TYPE LIGHT FIXTURE WALL MOUNTED LIGHT FIXTURE DOWNLIGHT STRIP LIGHT SPEAKER MEDICAL GAS MEDICAL EQUIPMENT CORNER GUARDS CRASH RAIL BUMPER RAIL HAND RAIL BED LOCATOR WALL PROTECTION IV TRACK CUBICLE CURTAIN TRACK EDGE OF SLAB FACE OF BUILDING PROJECT INFORMATION PROJECT NAME: INTERMOUNTAIN LAYTON PARKWAY PCH AUDIOLOGY CLINIC ADDRESS: 201 WEST LAYTON PARKWAY, LAYTON , UT 84041 PROPOSED USE: OUTPATIENT CLINIC BUILDING - TENANT IMPROVEMENT OWNER - CONTACT PERSON: MILT WHITE PHONE: 435 - 770 - 9328 ARCHITECT - CONTACT PERSON: GARY BLAZZARD PHONE: 801 - 532 - 2393 APPLICABLE CODES - BUILDING CODE: 2015 INTERNATIONAL BUILDING CODE - MECHANICAL: 2015 INTERNATIONAL MECHANICAL CODE - PLUMBING: 2015 INTERNATIONAL PLUMBING CODE - ELECTRICAL: 2014 NATIONAL ELECTRICAL CODE - FIRE CODE: 2015 INTERNATIONAL FIRE CODE - STATE/CITY AMENDMENTS: 2011 UTAH ADMINISTRATIVE CODE - LIFE SAFETY CODE: 2009 LIFE SAFETY CODE (NFPA 101) - ACCESSIBILITY CODE: 2010 AMERICANS WITH DISABILITIES ACT - ENERGY CODE: 2015 IECC - SIGN CODE: PER CITY ORDINANCE - ANSI: 2009 ICC A117.1 - 09 - FM INSURED: NO BUILDING PLANNING OCCUPANCY: B MIXED OCCUPANCY? YES / NO REQUIRED FIRE SEPARATION: NONE REQUIRED TYPE OF CONSTRUCTION CONSTRUCTION TYPE: EXISTING TYPE II - B GENERAL BUILDING LIMITATIONS FIRE PROTECTION SYSTEMS - FIRE EXTINGUISHING SYSTEM: YES / NO - STANDPIPE SYSTEM: YES / NO - SMOKE CONTROL: YES / NO TYPE: NFPA 13 (IBC 903.3.1.1) CLASS: CLASS I (IBC 905.3.1, EXCEPTION 1) FIRE RESISTANT CONSTRUCTION/FIREPROOFING SCHEDULE ITEM REQ'D RATING / HR UL/FM # WHERE APPLICABLE - EXTERIOR WALLS: LOAD BEARING - NON - LOAD BEARING - FIRE/PARTY WALLS - SHAFTS - TENANT SEPARATION - INTERIOR WALL: LOAD BEARING - NON - LOAD BEARING - COLUMNS - BEAMS - FLOOR/CEILING - ROOF/CEILING X X X X N/A X X X X X X FIRE PROOFING NOTES 1. ALL FIRE RESISTIVE RATINGS ARE ASSUMED TO BE THERMALLY UNRESTRAINED. 2. ALL BEAMS AND COLUMNS SHALL BE ADJUSTED USING W/D OR A/P RATIOS TO DETERMINE THE CORRECT FIREPROOFING THICKNESS. S D 01 001 ESSENTIAL FACILITY (CHAPTER 16, IBC) ESSENTIAL FACILITY? YES / NO +9' - 0" CEILING HEIGHT S EXHAUST AIR CR - 3 BG HR AAA 3 AAA 3 A0.X X 01 SUSPENDED LIGHT SUSPENDED FLUORESCENT LIGHT CHANDELIER PROJECTOR A0.X X 01 A0.X X BL ITEM ALLOWED / REQUIRED ACTUAL / PROVIDED HEIGHT OF BUILDING NUMBER OF STORIES MAX SINGLE FLOOR AREA TOTAL AREA OF BUILDING PENTHOUSE AND ROOF STRUCTURE PARKING SPACES* EXISTING/ NOT APPLICABLE EXISTING/ NOT APPLICABLE EXISTING/ NOT APPLICABLE EXISTING/ NOT APPLICABLE 69,000 SF LEVEL 1: 5,269 SF; LEVEL 3: 10,517 SF 207,000 SF MAX 15,786 SF EXISTING/ NOT APPLICABLE EXISTING/ NOT APPLICABLE STD: X HIGH RISE? YES / NO ACC: X TTL: X STD: X ACC: X TTL: X DUMMY SECTION DETAIL A0.X X TYPE II - B 0 HR 0 HR 3 HR 2 HR N/A 0 HR 0 HR 0 HR 0 HR 0 HR 0 HR A0.X X NOTE: *ALL PARKING FOR COMPLETE BUILD - OUT OF CLINIC BUILDING WAS ACCOUNTED FOR & SUBMITTED PREVIOUSLY IN BID PACKAGE #1 - SITE PACKAGE VICINITY MAP HKS ARCHITECTS, INC. SALT LAKE CITY, UTAH 84101 ARCHITECT 90 SOUTH 400 WEST, SUITE 110 REVISION PROJECT NUMBERS DATE SHEET TITLE PLOT DATE: INTERMOUNTAIN HEALTHCARE SALT LAKE CITY, UTAH 84111 OWNER 36 SOUTH STATE STREET ISSUE © 2016 HKS, INC. INTERMOUNTAIN LAYTON PARKWAY CLINIC PCH AUDIOLOGY REMODEL 2018 SHEET NO. HKS: 201 WEST LAYTON PARKWAY LAYTON, UT 84041 VAN BOERUM & FRANK ASSOCIATES, INC. MECHANICAL & PLUMBING ENGINEER 330 SOUTH 300 EAST SALT LAKE CITY, UT 84111 SPECTRUM ENGINEERS SALT LAKE CITY, UTAH 84111 ELECTRICAL ENGINEER 324 S. STATE ST. STE. 400 12/10/2018 8:14:09 AM A0.02B PROJECT INFORMATION 11/02/2018 22506.000 CONSTRUCTION DOCUMENTS PCH TI INDEX OF DRAWINGS - PCH AUDIOLOGY Sheet Issue Status SHEET NUMBER SHEET NAME CD ISSUE 12-10-2018 PCH TI A0.02B PROJECT INFORMATION PCH TI ALS.03A LIFE SAFETY PLAN - LEVEL 3 - PCH PCH TI A2.03H PCH AUDIOLOGY FLOOR PLANS PCH TI A2.70A FINISH INFORMATION- PCH PCH TI A2.71 INTERIOR DETAILS - FLOOR TRANSITION DETAILS PCH TI A3.01 PARTITION TYPES PCH TI A3.02 PARTITION HEAD AND FRAMING DETAILS PCH TI A3.30 DOOR, SAFETY GLAZING INFORMATION PCH TI A3.50H INTERIOR ELEVATIONS / CABINET DETAILS PCH TI M0.01A MECHANICAL SYMBOLS, DETAILS AND SCHEDULES PCH TI M2.34C MECHANICAL & PLUMBING PLANS PCH TI EE001 SYMBOL SCHEDULE, SHEET INDEX PCH TI EP101 PCH AUDIOLOGY ELECTRICAL PLANS - LEVEL 3 PCH TI EP501 DETAILS PCH TI EP502 DETAILS PCH TI EP503 DETAILS PCH TI ET601 TELECOM DETAILS PCH TI EC601 SYSTEM DIAGRAMS PCH TI EC602 SYSTEM DIAGRAMS NO. DESCRIPTION DATE

ROOM NAME ABBREVIATIONS DRAWING ABBREVIATIONS …gramoll.com/wp-content/uploads/2018/12/PCH-CD-181210.pdf · infus infusion area int interview ... pump am pumping room q rad radiology

Embed Size (px)

Citation preview

ROOM NAME ABBREVIATIONS DRAWING ABBREVIATIONS INDEX OF DRAWINGS BUILDING SUMMARY

LEGEND

A

ACSNG ACCESSIONING (LAB)ACTV ACTIVITYADMIN RCPT ADMINISTRATIVE RECEPTIONADMIT ADMITTING STATIONADL BDRM ADULT BEDROOMADL KIT ADULT KITCHENAEROB AEROBICS AREAAC AIR CONDITIONINGALC ALCOVEANESTH ANESTHESIAANIM STOR ANIMAL STORAGEANTE ANTE ROOMAV AUDIO VISUALAUDLGY AUDIOLOGYATM AUTOMATED TELLERAUTOP AUTOPSY

B

BARM KIT BARIUM KITCHENBED RM BEDROOMBIO HAZ BIO-HAZARDBIO EQUIP BIOLOGY EQUIPMENTBIO MED BIO-MEDICALBIO MED ENG BIO-MEDICAL ENGINEERINGBIO MED LAB BIO-MEDICAL LABORATORYBIO MED SAT BIO-MEDICAL SATELLITEBIO WST BIO-MEDICAL WASTEBLD BNK BLOOD BANKBLD DNR BLOOD DONOR AREABLD DWG BLOOD DRAWINGBLD GAS BLOOD GAS LABORATORYBRD RM BOARD ROOMBLR RM BOILER ROOMBNE DNSTY BONE DENSITYBKPG BOOK KEEPINGBTQUE BOUTIQUEBRKDN BREAK DOWNBRK RM BREAK ROOMBRKDN/EQ BREAKDOWN EQUIPMENTBRST FD BREAST FEEDINGBRST ULT BREAST ULTRASOUNDBULK ST BULK STORAGEC

CG WSH CAGE WASHCNTEN CANTEENCARD GYM CARDIAC CATH GYMCARD CATH CARDIAC CATHETERIZATIONCARD CIRCUIT CARDIAC CIRCUITCARD REHAB CARDIAC REHABILITATIONCARD RM CARDIAC ROOMC/V COND CARDIOVASCULAR CONDITIONINGC/V EXAM CARDIOVASCULAR EXAMC/V STRESS TEST CARDIOVASCULAR STRESS TESTINGCAST CAST ROOM/ORTHO/FRACTURECATH PROC CATHETERIZATION PROCEDURECHNG (M-MALE, F-FEMALE, CHANGING ROOMH/C-HANDICAPPED)CHRT RD CHART READINGCHRT/HLD CHART HOLDINGCHRT/DCT CHARTING/DICTATIONCHEM COLD ST CHEMICAL COLD STORAGECHEM ST CHEMICAL STORAGECHEM CHEMISTRYCHEMO CHEMOTHERAPYCHILD BIRTH ED CHILD BIRTH EDUCATIONCHILD WTG CHILD BIRTH WAITINGCLSRM CLASSROOMCLSRM/CONF CLASSROOM CONFERENCECLSRM/CNSLT CLASSROOM CONSULTCLN EQP CLEAN EQUIPMENTCLN HOLD CLEAN HOLDINGCLN LINEN CLEAN LINENCLN MED CLEAN MEDICATIONCLN ST CLEAN STORAGECLN SPLY CLEAN SUPPLYCLN SPLY/ST CLEAN SUPPLY STORAGECLN UTIL CLEAN UTILITYCLERCL/FLS CLERICAL/FILESCLIN CONS CLINICAL CONSULTCLIN WK CLINICAL WORKSTATIONCL CLOSETCLD RM COLD ROOMCOMM COMMUNICATIONCOMM EQ COMMUNICATION EQUIPMENTCOMMUNITY COMMUNITY ASSEMBLYCT COMPUTED TOMOGRAPHYCT CNTRL COMPUTED TOMOGRAPHY CONTROLCT IMAG COMPUTED TOMOGRAPHY IMAGINGCT PREP COMPUTED TOMOGRAPHY

PREPARATIONCMWP COMPOSITE METAL WALL PANELCT READ COMPUTED TOMOGRAPHY READINGCT SCAN COMPUTED TOMOGRAPHY SCANCT SIM COMPUTED TOMOGRAPHY SIMULATORCOMP COMPUTERCOMP SERVER COMPUTER SERVERCOMP ST COMPUTER STATIONCNCSN CONCESSION AREACNCRG CONCIERGECONF/CNSLT CONFERENCE/CONSULTCONF CONFERENCECONF/EDU CONFERENCE/EDUCATIONCONF/GRP/THERAPY

CONFERENCE/GROUP/THERAPYCONF/LIB CONFERENCE/LIBRARYCONF/LNG CONFERENCE/LOUNGECONF/OFF CONFERENCE/OFFICECONF/TEACH CONFERENCE/TEACHINGCOUNSEL COUNSELINGCNSLT CONSULTCNSLT/CONF CONSULT/CONFERENCECOPY COPY AREACORR CORRIDORCTYRD COURTYARDCCU CRITICAL CARE UNITC-SECT C-SECTION DELIVERYCYSTOL LAB CYSTOLOGY LABORATORYCYSTOL CYSTOSCOPY

D

DKRM DARKROOMDAYRM DAY ROOMDECON DECONTAMINATIONDECON SHWR DECONTAMINATION SHOWERDENTAL LAB DENTAL LABORATORYDIAL DIALYSISDICT DICTATIONDICT WK DICTATION WORKROOMDIET DIETICIANDGTL IMAG DIGITAL IMAGINGDIN DININGDIN/ACT DINING/ACTIVITYDISH DISHROOMDSPTCH DISPATCHDISTRIB DISTRIBUTIONDSMTRY DOSIMETRY

E

ECHO ECHOCARDIOGRAMECHO READ ECHOCARDIOGRAM READINGEDUC EDUCATION ROOMELEC ELECTRICALELEC CL ELECTRICAL CLOSETELEV CTRL ELEVATOR CONTROLEKG READ ELECTROCARDIOGRAM READINGEKG ELECTROCARDIOGRAM TESTINGEEG ELECTROENCEPHALOGRAM TESTINGEP LAB ELECTROPHYSIOLOGY LABORATORYEREG LAB ELECTRORETINOGRAPHYEMER ELEC EMERGENCY ELECTRICITYEMER GEN EMERGENCY GENERATOR ROOMEMP HEALTH EMPLOYEE HEALTHENDO ENDOSCOPY PROCEDUREENV SERV ENVIRONMENTAL SERVICESEQPM EQUIPMENTEQPM ALC EQUIPMENT ALCOVEEXAM EXAM ROOMEXAM/CNSLT EXAM/CONSULTEXAM/TREAT EXAM/TREATMENTEXERC EXERCISEEXIST EXISTINGF

FAM RM FAMILY ROOMFEED FEEDING ROOMFF FINISH FLOORFILE FILE STORAGEFILES/ADMIN FILES ADMINISTRATIONFILM PROC FILM PROCESSING ROOMFILM READ FILM READINGFIN FINANCEFIN COUN FITNESS CTR AUTOCL FINANCIAL COUNSEL FITNESS CENTER

AUTOCLAVE/FLASH STERILIZERFLUORO FLUOROSCOPYFMWP FORMED METAL WALL PANELFOOD ST FOOD STORAGEFORM PREP FORMULA PREPARATIONFREE WGT FREE WEIGHT AREAFR SECT FROZEN SECTIONFNCTN RM FUNCTION ROOMFUT EXP FUTURE EXPANSIONG

GAR GARAGEGEN STORES GENERAL STORESGEN GENERATORGIFT GIFT SHOPGLAUC CTR GLAUCOMA CENTERGWN WTG GOWN WAITINGGWN WTG F GOWN WAITING FEMALEGWN WTG M GOWN WAITING MALEGRIEVING GRIEVING ROOMGROSS GROSSING

I

ICE ICE MACHINEINF RESUS INFANT RESUSCITATIONINFEC CTRL INFECTION CONTROLINFO INFORMATION DESKINFO SYSTEM INFORMATION SYSTEMINFUS INFUSION AREAINT INTERVIEWINV INVENTORYISOL ISOLATION ROOMIV PREP IV PREPARATIONIV ST IV STORAGE

K

KIT KITCHENKIT/SAT KITCHEN SATELLITE

L

LDR LABOR/DELIVERY/RECOVERYLDRP LABOR/DELIVERY/RECOVERY/POST

PARTUMLAB LABORATORYLAB/SAT LABORATORY/SATELLITELDRY LAUNDRYLIB LIBRARYLIB/CONF LIBRARY/CONFERENCELIB/MEDIT LIBRARY/MEDITATIONLIGHT ADAPT LIGHT ADAPTATIONLINR ACC LINEAR ACCELERATORLIN CH LINEN CHUTELIN STR LINEN STORAGELR LIVING ROOMDOCK LOADING DOCKLKRS LOCKERSLKRS F LOCKERS FEMALELKRS M LOCKERS MALELKRS/CHNG LOCKERS/CHANGINGLONG EX LONG EXAM ROOM

M

MACH RM MACHINE ROOMMRI MAGNETIC RESONANCE IMAGINGMAIL MAIL ROOMMAINT MAINTENANCEMAMMO/STEREO MAMMOGRAPHY/STEREOTACTICMGMT MANAGEMENTMANIFOLD MANIFOLD ROOMMRKTG MARKETINGMATL MGMT MATERIALS MANAGEMENTMECH MECHANICALMECH/ELEC MECHANICAL/ELECTRICALMED REC MEDICAL RECORDSMEDS MEDICATION ROOMMEDIT MEDITATIONMTG MEETING ROOMMEZZ MEZZANINEMICRO BIO LAB MICROBIOLOGY LABORATORYMOB DK MOBILE DOCK

N

NARC CLO NARCOTICS CLOSETNICU NEONATAL INTENSIVE CARE UNITNEW NUR NEWBORN NURSERYNIGHT PHARM NIGHT PHARMACYNITROGEN ST NITROGEN STORAGENOISY ACTV NOISY ACTIVITYNOUR NOURISHMENTNUC MED NUCLEAR MEDICINENRS STA NURSE STATION

O

OBSERV OBSERVATIONOBSERV/EXAM OBSERVATION EXAMOBSERV/TREAT OBSERVATION TREATMENTOB/GYN OBSTETRIC/GYNECOLOGYOT OCCUPATIONAL THERAPYOFF OFFICEOFF SHRD OFFICE SHAREDOFF/CONF OFFICE/CONFERENCEOFF/CONS OFFICE CONSULTOFF/EXAM OFFICE/EXAMON-CALL LNG ON-CALL LOUNGEOR OPERATING ROOMOR CARDIAC OR CARDIOTHORACICOR EQ ST OR EQUIPMENT STORAGEOR ORTHO OR ORTHOPEDICORTHO ORTHOPEDIC ROOMORTHO ST ORTHOPEDIC STORAGEOSTOMY ST OSTOMY STORAGEOXYGEN ST OXYGEN STORAGE

P

PNTR PANTRYPARENT LKRS PARENT LOCKERSPASS PASSAGEPATH LAB PATHOLOGY LABORATORYPAT BAY PATIENT BAYPAT EDUC PATIENT EDUCATIONPAT HOLD PATIENT HOLDINGPAT INTAKE PATIENT INTAKEPAT LKRS PATIENT LOCKERSPAT LNG PATIENT LOUNGEPAT PREP PATIENT PREPARATIONPAT REG PATIENT REGISTRATIONPED PEDIATRICPED BAY PEDIATRIC BAYPED BLOOD DWG PEDIATRIC BLOOD DRAWINGPED OBSERV PEDIATRIC OBSERVATIONPED PLAY PEDIATRIC PLAYPHARM PHARMACYPHARM ST PHARMACY STORAGEPHLEB PHLEBOTOMYPT PHYSICAL THERAPYPT GYM PHYSICAL THERAPY GYMPT TRT PHYSICAL THERAPY TREATMENT/

MODALITY ROOMPT/OT PHYSICAL THERAPY/OCCUPATIONAL

THERAPYPT/OT GYM PHYSICAL THERAPY/OCCUPATIONAL

THERAPY GYMPET POSITION EMISSION TOMOGRAPHYPACU POST ANESTHESIA CARE UNITPREP PREPARATION AREAPREP/RECOV PREPARATION/RECOVERYPRIV PRIVATEPRIV BAY PRIVATE BAYPRIV BDRM PRIVATE BEDROOMPRIV RM PRIVATE ROOMPROC PROCEDURE ROOMPROC/ASSESS PROCEDURE/ASSESSMENTPSYCH PSYCHIATRYPSYCHOL PSYCHOLOGYPUMP AM PUMPING ROOM

Q

RAD RADIOLOGYREAD READING ROOMRCPT/CSHR RECEPTION/CASHIERREC ARC RECORD ARCHIVEREC ST RECORD STORAGERECOV RECOVERYRECOV BAY RECOVERY BAYRECOV/OBS RECOVERY OBSERVATIONRECYC RECYCLINGREFR REFRIGERATORREGIST REGISTRATIONREGIST/FIN REGISTRATION/FINANCIALREHAB GYM REHABILITATION GYMRESRCH RESEARCHRES RM RESIDENT ROOMRESRCE RESOURCERESRCE LIB RESOURCE LIBRARYRESP RESPIRATORYRT RESPIRATORY THERAPYREST RESTAURANTRETHERM RETHERM PANTRYRETINA CTR RETINA CENTER

QUIET ACTV QUIET ACTIVITYQUIET RM QUIET ROOM

R

S

STR STAIRSTAT LAB STAT LABORATORYSTEAM STEAM ROOMSTER PROC STERILE PROCEDURESTER ST STERILE STORAGESTER SPLY STERILE SUPPLYSTER STERILIZERST STORAGESTRESS LAB STRESS LABORATORYSTRESS TEST STRESS TESTINGSTCH ALC STRETCHER ALCOVESTCH ST STRETCHER STORAGESUB STA SUB-STATIONSUB STER SUB-STERILESUB WTG SUB-WAITINGSPLY SUPPLYSUPP SUPPORTSURG SURGERYSYN LAB SYNCOPE LABORATORY

T

TECH TECHNICIANSTEL TELEPHONETEL ALC TELEPHONE ALCOVETEL CL TELEPHONE CLOSETTEL VND TELEPHONE VENDINGTEL/DATA TELEPHONE/DATATV TELEVISION LOUNGETEMP ST TEMPORARY STORAGETEST TESTINGTLT (M-MALE, F-FEMALE, P-PUBLIC TOILET H/C-HANDICAP, S-STAFF, U-UNISEX)TLT/SH (H/C-HANDICAP, TB-TUB) TOILET SHOWERTRANS TRANSCRIPTIONTRANS WK TRANSCRIPTION WORKSTATIONTRANSFUS TRANSFUSIONTRANSFUS BAY TRANSFUSION BAYTRSH TRASHTRAUMA TRAUMA ROOMTRMT TREATMENTTRMT BAY TREATMENT BAYTREAT/PROC TREATMENT/PROCEDURE ROOMTUB TUB ROOM

U

ULTRA ULTRASOUNDUBM ULTRASOUND BIOMICROSCOPYUNIT SECY UNIT SECRETARYUTIL UTILITY

V

VND VENDINGVEST VESTIBULEVIEW VIEWINGVISUAL VISUAL FIELD

W

WAIT WAITINGWARM WARMING PANTRYWASH WASHING AREAW/C ALC WHEELCHAIR ALCOVEW/C ST WHEELCHAIR STORAGEWK AREA WORK AREAWK STA WORK STATIONSWK RM WORKROOM

PRIV H/C HANDICAP PRIVACY BEDROOMSHWR H/C HANDICAP SHOWERSTLT H/C STAFF HANDICAP STAFF TOILETTLT H/C HANDICAP TOILETTLT SH H/C HANDICAP TOILET/SHOWERTUB H/C HANDICAP TUBHEM HEMATOLOGYHISTO HISTOLOGYHOLD HOLDINGHOOD HOOD AREAHOT LAB HOT LABORATORYHSKPG HOUSEKEEPINGHVF HUMPHREYS VISUAL FIELDHYDRO HYDROTHERAPY TANKS

H

S

SCHED SCHEDULINGSCOP CLN SCOPE CLEANINGSCOP ST SCOPE STORAGESCRUB ALC SCRUB ALCOVESCRUB SCRUB AREASECL SECLUSION ROOMSECUR SECURITYSEMI PRIV RM SEMI PRIVATE ROOMSERO SEROLOGYSERV SERVERYSVC SERVICESERV ENTRY SERVICE ENTRYSHELL SHELL SPACESHWR (M-MALE, F-FEMALE, SHOWER H/C - HANDICAP)SIM SIMULATORSINK ALC SINK ALCOVESITZ SITZ BATHSLP LAB SLEEP LABORATORYSLP STUDY SLEEP STUDY ROOMSOIL HOLD SOILED HOLDINGSOIL LN SOILED LINENSOIL UTL SOILED UTILITYSOL SOLARIUMSORT SORTING AREASP CARE NUR SPECIAL CARE NURSINGSPEC PROC SPECIAL PROCEDURESSP SERV SPECIAL SERVICESSP STUD SPECIAL STUDIESSP TEST SPECIAL TESTINGSPEC SPECIMENSTAGE I STAGE I - PACUSTAGE I ISOL STAGE I ISOLATION - PACUSTAGE II STAGE II - RECOVERYSTAGE II ISOL STAGE II ISOLATION - RECOVERY

A

AB ANCHOR BOLTAD AREA DRAINAC AIR CONDITIONINGACT ACOUSTICAL CEILING TILEADD ADDENDUMADD'L ADDITIONALADJ ADJACENTAFF ABOVE FINISHED FLOORAGGR AGGREGATEAL ALUM ALUMINUMALT ALTERNATEANOD ANODIZEDAPPROX APPROXIMATEARCH ARCHITECTURAL

B

B.M. BENCH MARKBD BOARDBETW BETWEENBF BACKFACEBG BUMPER GUARDBL BED LOCATORBL BUILDING LINEBLDG BUILDINGBLKG BLOCKINGBM BEAMBOT BOTTOMBR BUMPER RAILBRG BEARINGBSMT BASEMENTBU ROD BACK-UP RODBUR BUILT-UP ROOFBW BEARING WALL

C

C COMPACT PARKING SPACECC CUBICLE CURTAINCDR CARD READERCEM CEMENTCER CERAMICCG CORNER GUARDCIP CAST IN PLACECJ CONTROL JOINTCJ CONSTRUCTION JOINTCL CENTER LINECLG CEILINGCLR CLEARCMU CONCRETE MASONRY UNITCOL COLUMNCOMM COMMUNICATIONSCONC CONCRETECONN CONNECTIONCONST CONSTRUCTIONCONT CONTINUOUSCOORD COORDINATECPE CHLORINATED POLYETHYLENECORR CORRIDORCR COLD ROLLEDCR CRASH RAILCSK COUNTERSUNKCT CERAMIC TILECTD CENTEREDCTR CENTERCW CURTAIN WALLD

D DEPTHDBA DEFORMED BAR ANCHORDET DETAILDF DECORATIVE FILMDIA DIAMETERDIAPH DIAPHRAGMDIM DIMENSIONDJ DEFLECTION JOINTDL DEAD LOADDN DOWNDRG DRAWINGDS DOWN SPOUTDWGS DRAWINGSDWLS DOWELS

E

EA EACHEF EACH FACEEFG ENTRANCE FLOOR GRILLEEIFS EXTERIOR INSULATION AND

FINISH SYSTEMEJ EXPANSION JOINTEL ELEVATIONELEC ELECTRICELEV ELEVATOREOS EDGE OF SLABEQ EQUALEQUIP EQUIPMENTESC ESCALATOREW EACH WAYEWC ELECTRIC WATER COOLEREXIST EXISTINGEXP BLT EXPANSION BOLTEXT EXTERIORF

FD FLOOR DRAINFDN FOUNDATIONFE FIRE EXTINGUISHERFEC FIRE EXTINGUISHER CABINETFF FINISH FLOORFHC FIRE HOSE CABINETFIB FIBERGLASSFIN FINISHFLR FLOORFS FAR SIDEFT FOOTFT FLOOR TRANSITIONFTG FOOTINGFV FIELD VERIFYFVC FIRE VALVE CABINETG

GA GAUGEGALV GALVANIZEDGB GRADE BEAMGEN GENERALGFRC GLASS-FIBER REINFORCED

CONCRETEGI GALVANIZED IRONGL GLASSGM GLAZED MASONRY UNITGND GROUNDGR GRADEGRG GLASS-REINFORCED GYPSUMGYP BD GYPSUM BOARD

H

HB HOSE BIBHDW HARDWAREHDWD HARDWOODHK HOOKHM HOLLOW METALHOR HORIZONTALHP HIGH POINTHR HOURHS HEADED STUDHSKP HOUSEKEEPINGHT HEIGHTHW HAND WASHHW HEAD OF WALL

I

IBC INTERNATIONAL BUILDINGCODE

ID INSIDE DIAMETERINSUL INSULATIONINT INTERIOR

K

K KIPS (1000 LB)KO KNOCK-OUTKP KICKPLATEKPD KEYPADKSF KIPS PER SQUARE FOOT

L

L ANGLELAV LAVATORYLG LONGLKB LOCKABLELL LIVE LOADLLH LONG LEG HORIZONTALLLV LONG LEG VERTICALLOC LOCATIONLP LOW POINTLT LIGHTLWC LIGHTWEIGHT CONCRETE

M

MAS MASONRYMAT'L MATERIALMAX MAXIMUMMECH MECHANICALMEMB MEMBRANEMEP MECHANICAL, ELECTRICAL

AND PLUMBINGMFG MANUFACTURERMGO MEDICAL GAS OUTLETMIN MINIMUMMISC MISCELLANEOUSMO MASONRY OPENINGMOB MEDICAL OFFICE BUILDINGMOD BIT MODIFIED BITUMENMOD MODIFIEDMSL MEAN SEA LEVELMTL METAL

N

NA NOT AVAILABLENIC NOT IN CONTRACTNOA NOTICE OF ACCEPTANCE BY FLORIDA GOVERNING

AUTHORITYNOM NOMINALNS NEAR SIDENTS NOT TO SCALENWC NORMAL WEIGHT CONCRETE

O

OA OVER ALLOC ON CENTEROD OUTSIDE DIAMETEROD OVERFLOW DRAINOFCI OWNER FURNISHED,

CONTRACTOR INSTALLEDOFOI OWNER FURNISHED, OWNER INSTALLEDOH OPPOSITE HANDOPNG OPENINGOPP OPPOSITEOSF OUTSIDE FACE

P

P LAM PLASTIC LAMINATEPC PRECAST CONCRETEPCF POUNDS PER CUBIC FOOTPCP PORTLAND CEMENT

PLASTERPENT PENTHOUSEPL PROPERTY LINEPL PLATEPLUMB PLUMBINGPLYWD PLYWOODPP PUSH PLATEPOL POLISHEDPORT CEM PORTLAND CEMENTPR PAIRPREFAB PREFABRICATEDPSF POUNDS PER SQUARE FOOTPSI POUNDS PER SQUARE INCHPT POINTPT PNEUMATIC TUBEPTD PAINTEDR

R RISERRAD RADIUSRAF RUBBERIZED ASPHALT

FLASHINGRAM RUBBERIZED ASPHALT

MEMBRANERAU RUBBERIZED ASPHALT

UNDERLAYMENTRCP REFLECTED CEILING PLANRD ROOF DRAINREBAR REINFORCING BARRECP RECEPTACLEREF REFER OR REFERENCEREINF REINFORCINGRELOC RELOCATE/RELOCATEDREQ'D REQUIREDRFVC RECESSED FIRE VALVE

CABINETRM ROOMRO ROUGH OPENING

SAB SOUND ATTENUATION BLANKET

SBC STANDARD BUILDING CODESCHED SCHEDULESDL SUPERIMPOSED DEAD LOADSECT SECTIONS/H SINGLE HUNGSHWR SHOWERSIM SIMILARSO STRUCTURAL OPENINGSOG SLAB ON GRADESP STAND PIPESPA SPACE, SPACINGSPEC SPECIFICATIONSQ SQUARESS STAINLESS STEELSSF SOLID SURFACESTA STATIONSTC SOUND TRANSMISSION

CLASSSTD STANDARDSTIFF STIFFENERSTIR STIRRUPSTL STEELSTRUC STRUCTURALSYM SYMMETRICALSYS SYSTEM

S

T

T TREAD T&B TOP AND BOTTOMTC TOP OF CURBTEL TELEPHONETEMP TEMPERATURETHK THICKTLT TOILETTO TOP OFTOB TOP OF BEAMTOC TOP OF CONCRETETOF TOP OF FOOTINGTOP TOP OF PARAPETTOS TOP OF SLABTOSTL TOP OF STEELTRSH CH TRASH CHUTETW TOP OF WALLTYP TYPICAL

U

U/C UNDER COUNTER U/G UNDERGROUNDUNO UNLESS NOTED OTHERWISE

VAR VARIES VCT VINYL COMPOSITION TILEVERT VERTICALVEST VESTIBULEVWC VINYL WALL COVERING

V

W/ WITHW/C WHEEL CHAIRW/O WITHOUTW WIDTHWP WATERPROOF(ING)WD WOODWF WIDE FLANGEWL WIND LOADWP WORK POINTWPO WORK POINT - POINT OF

ORIGINWP1 WORK POINT - NUMBEREDWWF WELDED WIRE FABRIC

W

NUMBERING SYSTEM:

A2.10/01

DISCIPLINE:C - CIVILL - LANDSCAPEA - ARCHITECTUREM - MECHANICALE - ELECTRICALP - PLUMBINGS - STRUCTURALK - FOOD SERVICE

SERIES NUMBER

SHEET NUMBER WITHIN SERIES

NUMBER OF PLAN, DETAIL, ETC. ON SHEET

CONCRETE/ PRECAST CONCRETE

SOIL

SAND, EIFS FINISH COAT, OR CEMENT PLASTER

BRICK

CMU

STONE

FIBERGLASS SEMI RIGID INSULATION

FIBERGLASS BATT INSULATION

MINERAL WOOL SEMI RIGID INSULATION

EXPANDED POLYSTYRENE RIGID INSULATION

EXTRUDED POLYSTYRENE RIGID INSULATION

POLYISOCYANURATE RIGID INSULATION

GYPSUM BOARD

EXTERIOR GYPSUM SHEATHING

EXTERIOR CEMENT BOARD

COATED GLASS MAT WATER RESISTANT GYP BD

PLYWOOD

COVER BOARD

MATERIALS

ROOM NAME

XXXXX

X

X

1

A0.XX

X

A3

A3

ROOM NAME/NUMBER

EXISTING COLUMN CENTERLINE

COLUMN CENTERLINE

ACCESSORY

DEMOLITION NUMBERED NOTES

BUILDING WALL SECTION

EXTERIOR ELEVATION

SECTION DETAIL

PLAN, BLOW-UP DETAIL

INTERIOR ELEVATION

PARTITION TYPE WITH NO SOUND ATTENUATION

PARTITION TYPE WITH SOUND ATTENUATION

CMU WALL

NEW WALL

EXISTING WALL

DEMO WALL

1 HOUR FIRE WALL

2 HOUR FIRE WALL

3 HOUR FIRE WALL

4 HOUR FIRE WALL

NON-RATED SMOKE WALL

1 HOUR SMOKE WALL

2 HOUR SMOKE WALL

1 HOUR SHAFT WALL

2 HOUR SHAFT WALL

DRAWING SYMBOLS

CEILING SYMBOLS

BUILDING EXPANSION JOINT

GYP BD CEILING

SUPPLY AIR

RETURN AIR

ACCESS PANEL

FLUORESCENT LIGHT

WALL MOUNTED FLUORESCENT FIXTURE

EXIT SIGNS - HATCH INDICATES EXIT TEXT AND ARROW INDICATES DIRECTION

SMOKE DETECTOR

WALL WASHER

PENDANT TYPE LIGHT FIXTURE

WALL MOUNTED LIGHT FIXTURE

DOWNLIGHT

STRIP LIGHT

SPEAKER

MEDICAL GAS

MEDICAL EQUIPMENT

CORNER GUARDS

CRASH RAIL

BUMPER RAIL

HAND RAIL

BED LOCATOR

WALL PROTECTION

IV TRACK

CUBICLE CURTAIN TRACK

EDGE OF SLAB

FACE OF BUILDING

PROJECT INFORMATIONPROJECT NAME: INTERMOUNTAIN LAYTON PARKWAY PCH AUDIOLOGY CLINIC

ADDRESS: 201 WEST LAYTON PARKWAY, LAYTON , UT 84041

PROPOSED USE: OUTPATIENT CLINIC BUILDING - TENANT IMPROVEMENT

OWNER-CONTACT PERSON: MILT WHITE PHONE: 435-770-9328

ARCHITECT - CONTACT PERSON: GARY BLAZZARD PHONE: 801-532-2393

APPLICABLE CODES- BUILDING CODE: 2015 INTERNATIONAL BUILDING CODE

- MECHANICAL: 2015 INTERNATIONAL MECHANICAL CODE

- PLUMBING: 2015 INTERNATIONAL PLUMBING CODE

- ELECTRICAL: 2014 NATIONAL ELECTRICAL CODE

- FIRE CODE: 2015 INTERNATIONAL FIRE CODE

- STATE/CITY AMENDMENTS: 2011 UTAH ADMINISTRATIVE CODE

- LIFE SAFETY CODE: 2009 LIFE SAFETY CODE (NFPA 101)

- ACCESSIBILITY CODE: 2010 AMERICANS WITH DISABILITIES ACT

- ENERGY CODE: 2015 IECC

- SIGN CODE: PER CITY ORDINANCE

- ANSI: 2009 ICC A117.1-09

- FM INSURED: NOBUILDING PLANNINGOCCUPANCY: B

MIXED OCCUPANCY? YES / NO

REQUIRED FIRE SEPARATION: NONE REQUIRED

TYPE OF CONSTRUCTIONCONSTRUCTION TYPE: EXISTING TYPE II-B

GENERAL BUILDING LIMITATIONS

FIRE PROTECTION SYSTEMS- FIRE EXTINGUISHING SYSTEM: YES / NO

- STANDPIPE SYSTEM: YES / NO

- SMOKE CONTROL: YES / NO

TYPE: NFPA 13 (IBC 903.3.1.1)

CLASS: CLASS I (IBC 905.3.1, EXCEPTION 1)

FIRE RESISTANT CONSTRUCTION/FIREPROOFING SCHEDULE

ITEM REQ'D RATING / HR UL/FM # WHERE APPLICABLE

- EXTERIOR WALLS: LOAD BEARING- NON-LOAD BEARING

- FIRE/PARTY WALLS

- SHAFTS

- TENANT SEPARATION

- INTERIOR WALL: LOAD BEARING

- NON-LOAD BEARING

- COLUMNS

- BEAMS

- FLOOR/CEILING

- ROOF/CEILING

X

X

X

X

N/A

X

X

X

X

X

X

FIRE PROOFING NOTES

1. ALL FIRE RESISTIVE RATINGS ARE ASSUMED TO BE THERMALLY UNRESTRAINED.

2. ALL BEAMS AND COLUMNS SHALL BE ADJUSTED USING W/D OR A/P RATIOS TO DETERMINE THE CORRECT FIREPROOFING THICKNESS.

SD

01

001

ESSENTIAL FACILITY (CHAPTER 16, IBC)ESSENTIAL FACILITY? YES / NO

+9'-0" CEILING HEIGHT

S

EXHAUST AIR

CR - 3

BG

HR

AAA3

AAA3

A0.XX

01

SUSPENDED LIGHT

SUSPENDED FLUORESCENT LIGHT

CHANDELIER

PROJECTOR

A0.XX

01

A0.XX

BL

ITEM ALLOWED / REQUIRED ACTUAL / PROVIDED

HEIGHT OF BUILDING

NUMBER OF STORIES

MAX SINGLE FLOOR AREA

TOTAL AREA OF BUILDING

PENTHOUSE AND ROOF STRUCTURE

PARKING SPACES*

EXISTING/ NOT APPLICABLE EXISTING/ NOT APPLICABLE

EXISTING/ NOT APPLICABLE EXISTING/ NOT APPLICABLE

69,000 SF LEVEL 1: 5,269 SF;LEVEL 3: 10,517 SF

207,000 SF MAX 15,786 SF

EXISTING/ NOT APPLICABLE EXISTING/ NOT APPLICABLE

STD: X

HIGH RISE? YES / NO

ACC: X TTL: X STD: X ACC: X TTL: X

DUMMY SECTION DETAILA0.X

X

TYPE II-B

0 HR

0 HR

3 HR

2 HR

N/A

0 HR

0 HR

0 HR

0 HR

0 HR

0 HR

A0.XX

NOTE: *ALL PARKING FOR COMPLETE BUILD-OUT OF CLINIC BUILDING WAS ACCOUNTED FOR & SUBMITTED PREVIOUSLY IN BID PACKAGE #1 - SITE PACKAGE

VICINITY MAP

HKS ARCHITECTS, INC.

SALT LAKE CITY, UTAH 84101

ARCHITECT

90 SOUTH 400 WEST, SUITE 110

REVISION

PROJECT NUMBERS

DATE

SHEET TITLE

PLO

T D

AT

E:

INTERMOUNTAIN HEALTHCARE

SALT LAKE CITY, UTAH 84111

OWNER

36 SOUTH STATE STREET

ISSUE

© 2016 HKS, INC.

IN

TE

RM

OU

NT

AIN

LA

YT

ON

PA

RK

WA

Y C

LIN

IC

PC

H A

UD

IO

LO

GY

RE

MO

DE

L 2

01

8

SHEET NO.

HKS:

20

1 W

ES

T L

AY

TO

N P

AR

KW

AY

L

AY

TO

N, U

T 8

40

41

VAN BOERUM & FRANK ASSOCIATES, INC.MECHANICAL & PLUMBING ENGINEER

330 SOUTH 300 EAST SALT LAKE CITY, UT 84111

SPECTRUM ENGINEERS

SALT LAKE CITY, UTAH 84111

ELECTRICAL ENGINEER

324 S. STATE ST. STE. 400

12/1

0/20

18 8

:14:

09 A

M

A0.02B

PROJECT

INFORMATION

11/02/2018

22506.000

CONSTRUCTION

DOCUMENTS

PCH TI

INDEX OF DRAWINGS - PCH AUDIOLOGY

Sheet Issue StatusSHEET

NUMBER SHEET NAMECD ISSUE12-10-2018

PCH TI A0.02B PROJECT INFORMATION █PCH TI ALS.03A LIFE SAFETY PLAN - LEVEL 3 - PCH █PCH TI A2.03H PCH AUDIOLOGY FLOOR PLANS █PCH TI A2.70A FINISH INFORMATION- PCH █PCH TI A2.71 INTERIOR DETAILS - FLOOR TRANSITION DETAILS █PCH TI A3.01 PARTITION TYPES █PCH TI A3.02 PARTITION HEAD AND FRAMING DETAILS █PCH TI A3.30 DOOR, SAFETY GLAZING INFORMATION █PCH TI A3.50H INTERIOR ELEVATIONS / CABINET DETAILS █PCH TI M0.01A MECHANICAL SYMBOLS, DETAILS AND SCHEDULES █PCH TI M2.34C MECHANICAL & PLUMBING PLANS █PCH TI EE001 SYMBOL SCHEDULE, SHEET INDEX █PCH TI EP101 PCH AUDIOLOGY ELECTRICAL PLANS - LEVEL 3 █PCH TI EP501 DETAILS █PCH TI EP502 DETAILS █PCH TI EP503 DETAILS █PCH TI ET601 TELECOM DETAILS █PCH TI EC601 SYSTEM DIAGRAMS █PCH TI EC602 SYSTEM DIAGRAMS █

NO. DESCRIPTION DATE

LIFE SAFETY PLAN LEGEND

EXIT ENCLOSURE

EXIT CORRIDOR

SUITE

BUSINESS OCCUPANCY

EXIT SYMBOL

EXIT SIGN -HATCH INDICATES

EXIT TEXT AND ARROW

INDICATES DIRECTION

ASSEMBLY

1 HR FIRE BARRIER

2 HR FIRE BARRIER

SMOKE PARTITION (NON RATED)NON RATED WALL

SMOKE COMPARTMENT WALL

2 HR FIRE / SMOKE BARRIER

FIRE DEPARTMENT CONNECTION

FIRE EXTINGUISHER CABINET

FIRE EXTINGUISHER

TRAVEL DISTANCE FROM THE MOST REMOTE

POINT TO THE CLOSEST EXIT

TRAVEL DISTANCE WITHIN A SMOKE ZONE TO AN ADJACENT

SMOKE ZONE

XXX'-X"

XXX'-X"

FDC

FEC

FE

FDC

OCCUPANCY SEPARATION WALL

HORIZONTAL EXIT WALL

1 HR FIRE / SMOKE BARRIER

RETAIL

STORAGE

3-HR FIRE WALL - BUILDING SEPARATION (I-2 TO B)& HORIZONTAL EXIT

FEC

FEC

FEC

20

3' -

0"

B OCCUPANCYI-2 OCCUPANCY

NO SMOKE COMPARTMENTS REQUIRED

EXTENT OF CURRENT SCOPE. ALL OTHER AREAS REVIEWEDWITH PREVIOUSLY ISSUEDCONSTRUCTION DOCUMENTS

FEC

FEC

FE

FE

EXIT 3D

EXIT 3A

EXIT 3B

EXIT 3C

EXIT 3E

250' - 0"

FEC

HKS ARCHITECTS, INC.

SALT LAKE CITY, UTAH 84101

ARCHITECT

90 SOUTH 400 WEST, SUITE 110

REVISION

PROJECT NUMBERS

DATE

SHEET TITLE

PLO

T D

AT

E:

INTERMOUNTAIN HEALTHCARE

SALT LAKE CITY, UTAH 84111

OWNER

36 SOUTH STATE STREET

ISSUE

© 2016 HKS, INC.

IN

TE

RM

OU

NT

AIN

LA

YT

ON

PA

RK

WA

Y C

LIN

IC

PC

H A

UD

IO

LO

GY

RE

MO

DE

L 2

01

8

SHEET NO.

HKS:

20

1 W

ES

T L

AY

TO

N P

AR

KW

AY

L

AY

TO

N, U

T 8

40

41

VAN BOERUM & FRANK ASSOCIATES, INC.MECHANICAL & PLUMBING ENGINEER

330 SOUTH 300 EAST SALT LAKE CITY, UT 84111

SPECTRUM ENGINEERS

SALT LAKE CITY, UTAH 84111

ELECTRICAL ENGINEER

324 S. STATE ST. STE. 400

12/1

0/20

18 7

:34:

48 A

M

ALS.03A

LIFE SAFETY PLAN -

LEVEL 3 - PCH

12/10/2018

22506.000

CONSTRUCTION

DOCUMENTS

PCH TI

1" = 20'-0"01 LIFE SAFETY PLAN - LEVEL 3 - PCH TINOTE: CROSS-HATCHED AREA INDICATES SCOPE PREVIOUSLY ISSUED. REFER TO BID PACKAGE #3

THIRD LEVEL PCH B-OCCUPANCY SUMMARY

AREA PRIMARY USE AREA OL FACTOR OCCUPANT LOAD

CLINIC BUSINESS 922 SF 100 SF 10CLINIC BUSINESS 1908 SF 100 SF 20CLINIC MECHANICAL 343 SF 300 SF 2CLINIC BUSINESS 897 SF 100 SF 9CLINIC BUSINESS 1222 SF 100 SF 13CLINIC BUSINESS 300 SF 100 SF 4REHAB CLINIC BUSINESS 448 SF 100 SF 5REHAB CLINIC BUSINESS 2468 SF 100 SF 25REHAB CLINIC BUSINESS 845 SF 100 SF 9REHAB CLINIC BUSINESS 750 SF 100 SF 8REHAB CLINIC BUSINESS 289 SF 100 SF 3REHAB CLINIC STORAGE 126 SF 300 SF 1GRAND TOTAL 10517 SF 109

NO. DESCRIPTION DATE

CLG HT AFF

REF RCP FOR

S T

4

4.8

5.7

2.9

3' -

0"

6' - 0"

2' - 0" 6' - 8"

1/20 GRADE RISE(NOT A RAMP)(NO HANDRAILS)4" RISE

7' - 0" 9' - 3 1/4"

12' -

0"

5' -

0"12

' - 0

"

6" 6 1/4"

2' - 4"

5"

A3

EXIST

A3

A3

EXIST

EXIST

A3 EXISTA3 EXISTPW

A3

A3A3

A3

A3

A3 A3

A3A3

NG

NG

EXAM 1

34214

EXAM 2

34216

PAT TLT

34218

EXAM 3

34220

ECHO

34230

EEG

34234

EXAM

34226

AUD EXAM

34227

LAB

34229

CORRIDOR

34231

AUD EXAM

34233

OFFICE

34235

CORRIDOR

34237

AUD EXAM

34238AUD

CONTROL

34239

CORR

34246

A3

A3

A3

A3

A3

A3

A3

A3

CO

RR

IDO

R

3424

1

6"

NEW ALUMINUMDOOR / FRAMEAND GLAZING -SEE A3.30 ELEVATION

1' -

6"

REMOVE EXISTING WALLTO HEIGHT OF NEWDOOR OPENING

PATCH WALLS WHEREEXISTING WALL WASREMOVED (PW)

3424

1

ELEVATEDFLOOR AREAAND RAMP(HATCHED) -SEE FLOORPLAN NOTE 7

UP

FUTUREDEVELOPEDSPACE

FUTUREDEVELOPEDSPACE

H2

H2FEC

1' - 3"

9"9"

1' -

4"8"

A3.

50H

/04

A3.

50H

/03

A3.

50H

/05

A3.

50H

/03

OP

P34

233

3423

534

229

3422

7

A3.

50H

/07

A3.50H/06

34241A

3' -

0"

S T

4.8

5.7

2.9

+8'-10"

+8'-10"

BULKHEAD+8'-0"(FV)

+8'-10"

+9'-0"

+9'-0"

+8'-6"+8'-6"

+8'-6"+8'-6"

PATCH CEILING SYSTEMWHERE DISTURBED TO PROVIDE NEW BULKHEADREMOVE EXISTING WALL AS

NECESSARY TO FORM BULKHEAD

5' - 0"

4' -

6"4'

- 6"

5' - 0" CUBICLECURTAIN TRACKS

3-5/8" METALSTUD / GYPBOARD BULKHEAD

CEILINGS BYBOOTH VENDOR BULKHEAD BOTTOM IS INTENDED

TO BE 1/2" ABOVE THE TOPOF THE BOOTH

+9'-0" (ABOVE MAINFLOOR LEVEL)

NEW GYP BDCEILING ONHORIZONTALMETAL STUDFRAMING(INTEGRATE INTOEXISTING CEILING)

+8'-6"

+9'-0" EXPOSED TOSTRUCTURE

EXPOSED TOSTRUCTURE

S T

4

4.8

5.75.7

2.9

SHVB20SHV20

WP011,2,3,4

EXAM 134214

SHVB20SHV20

WP01

EXAM 234216

1,2,3,4

SHVB20SHV20

WP011,2,3,4

EXAM 334220

SHVB20SHV20

WP01

EEG34234

1,2,3,4

PTB03PT03

CT06

PAT TLT34218

3,5

032

032

032

IPT20

IPT22

SH

V25

SH

V20

SH

V25

SH

V20

SH

V25

SH

V20

SH

V25

SH

V20

IPT06

CT07

TYP.5' - 0"

IPT06

IPT06

SHV18

SHV18(EXIST)

2' - 0"

13' - 1 1/2"

SHV18

CPT06 CPT06

NEW SHEET VINYL

EXISTING CARPETAND BASE TOREMAIN - PROVIDETRANSITION STRIP

CB06CPT06

IPT27

AUD EXAM34227

3, 4SHVB20SHV20

IPT27

LAB34229

4

SHVB18SHV18

IPT01

CORRIDOR34231

4

CB06CPT06

IPT27

AUD EXAM34233

3, 4

CB06CPT06

IPT27

OFFICE34235

3

SHVB18SHV18

IPT01

CORRIDOR34241

4

CB06CPT06

IPT01

CORRIDOR34237

4

SHVB18SHV18

IPT01

CORR34246

3,4

IPT

06IP

T06

SHELLED SPACE -NO FINISHES

SHELLED SPACE -NO FINISHES

SHELLED SPACE -NO FINISHES

PREFABRICATEDRAMP WITH INTEGRALSLIP RESISTANTSURFACE

WP

CB06CB06

PAINT NEW CEILINGAREA TO MATCH ADJACENTGYP BD

PATCH / PROVIDE NEW CARPET FLOORING AND BASE:CARPET (CPT01) SHAW, QUARTZ TILE, 5T017, ZIRCON, 18X36BASE (CB01) SHAW, DESIGN SERIES V30

PAINT DISTURBED WALLSIPT01:SHERWIN WILLIAM, 7005, PURE WHITE

CG2

CG2

CG2

CG2

CG2

FLOOR PLAN / FINISH GENERAL NOTES

1. REFER TO SHEET A3.01 FOR PARTITION TYPES, GRAPHIC AND SYMBOLIC DESIGNATIONS, NOTES, AND DETAILS

'EXIST' NEXT TO WALL TYPE SYMBOL INDICATES THE WALL TYPEIS EXISTING (SHOWN FOR REFERENCE)

2. REFER TO SHEET A3.50 FOR INTERIOR ELEVATIONS, MILLWORK DETAILS AND INFORMATION3. DIMENSIONS ARE TO FACE OF DRYWALL OR FINISH, U.N.O. 4. COORDINATE WALL DEMOLITION REQUIRED FOR UTILITY WORK. NOT ALL WALL PATCH LOCATIONS MAY BE INDICATED5. PROVIDE 2 HOUR FLOOR PENETRATION SEALS WHERE PIPING OR CONDUIT PENETRATES FLOOR BELOW AND FLOOR ABOVE6. PATCH ALL SPRAYED ON FIREPROOFING WHERE DISTRBUTED BY DEMOLITION OR REMODEL CONSTRUCTION, TO ORIGINAL CONDITION, AS DETERMINED BY THE BUILDING OFFICIAL7. ELEVATED FLOOR AREA (ELEVATED 4" TO MATCH HEIGHT OF AUDIOLOGY BOOTH FLOOR) SHALL BE CONSTRUCTED OF 2-1/2" METAL STUDS AT 12" O.C. (16 GA), 5/8" CEMENT BOARD (PERPENDICULAR TO METAL STUDS) AND 1" CONCRETE TOPPING. RAMP SHALL BE 'PRARIE VIEW INDUSTRIES' SL##36 RAMP OR EQUAL (CUSTOM FABRICATE RAMP WITH SLOPE TO BE 1/20 OR LESS) RAMP SHALL BE FASTENED TO FLOOR WITH 2" EXPANSION ANCHORS (COUNTERSUNK HEADS)8. 'FUTURE DEVELOPED SPACE' SHALL RECEIVE TAPED AND MUDDED DRYWALL FINISH (TO MEET 1 HOUR WALL RATING) ON THE UNFINISHED SIDE OF THE WALL

SHEET KEYNOTES

'NG' PROVIDE NEW GYP BD ON EXIST STUD AND GYP FRAMING - FULL HEIGHT, IN THIS ROOM AS REQUIRED TO ACHIEVE 'G' WALL TYPE ASSEMBLY. SEE WALL TYPES ON SHEET A3.01

'PW' PATCH EXISTING GYP BD WALL AS NECESSARY AFTER INSTALLATION OF UTILITIES AND/OR WHERE EXISTING WALLS ARE REMOVED OR MODIFIED. NOT ALL LOCATIONS MAY BE INDICATED. COORDINATE WITH DEMOLITION

AND UTILITY DRAWINGS. PROVIDE NEW WALL AND BASE FINISH ON ENTIRE WALL.

"WP' PAINT ENTIRE WALL WHERE DISTURBED BY DEMOLITION OR REMODEL WORK. MATCH EXISTING PAINT COLOR

4 7/8"

TYP

3"4"

3 5/8" METAL STUD DIAGONAL SUPPORT AT 48" OC MAX

CLG AS SCHED

5/8" GYP BD ON MTL STUDS

LINE OF STRUCTURE

3 5/8" MTL STUD HOR BRACING -BRACE AT 24" OC WHEN VERTICAL HEIGHT EXCEEDS 48"

3 5/8" MTL STUDS AT 16" OC

2" X 22 GA CONTINUOUS METAL STRAP TYP EACH SIDE

TYPICAL: 12 GA AT LAY-IN CLNG OR 8 GA AT GYP BD CLG VERTICAL HANGER WIRE AT 4'-0" EA WAY W/ MIN 3 TIGHT TURNS IN 1 1/2" BOTH ENDS OF WIRE TYPICAL (8" OUT FROM WALL TYP)12 GA AT LAY-IN CLG OR 8 GA AT GYP BD CLG BRACING WIRE W/ MIN 4 TIGHT TURNS IN 1 1/2" BOTH ENDS OF WIRE TYP PROVIDED ORIENTED 90 TO EACH OTHER AT 12'-0" OC 1ST POINT 6' FROM EACH WALLCOMPRESSION STRUTS: 1 1/2" DEEP 20 GA WALL STUD ATTACH TO MAIN RUNNERS WITH 1/4" MACHINE BOLT AND TO STRUCTURE WITH 3/16" DIAMETER POWER-DRIVEN FASTENER. COMPRESSION STRUT SHALL NOT REPLACE HANGER WIRE

MAIN RUNNER

CROSS RUNNER

2" (MAX) FROM BRACING WIRES TO CROSS RUNNERS

CEILING FIXTUR

E 45°

MAX (TYP)

12 GA AT LAY-IN CLG OR 8 GA AT GYP BD CLNG WIRE ATTACHED TO OPPOSING CORNERS AT FIXTURES DIAGONAL

1. ICBO (INTERNATIONAL COUNCIL OF BUILDING OFFICIALS) EVALUATION REPORT - 4071 GYPSUM WALLBOARD (066). (THIS REPORT HAS THE SAME REQUIREMENTS FOR GYP BD CEILINGS AND LAY-IN CEILING.

2. ALL LATERAL SUPPORTS MUST BE LOCATED A MIN OF 6" (152mm) FROM HORIZONTAL UNBRACED PIPES AND DUCTWORK.

3. VERTICAL STRUTS FASTENED TO THE MAIN RUNNER SHALL BE EXTENDED TO AND FASTENED TO THE STRUCTURAL MEMBERS SUPPORTING THE ROOF OR FLOOR ABOVE. THE STRUT SHALL BE ADEQUATE TO RESIST THE VERTICAL LOAD INDUCED BY THE BARRIER WIRES.

4. THE VERTICAL STRUTS AT HORIZONTAL RESTRAINT POINTS SHALL BE PLACED 12'-0" (3658mm) OC IN BOTH DIRECTIONS, WITH THE FIRST POINT WITHIN 6'-0" (1830mm) FROM EACH WALL.

NOTES

HKS ARCHITECTS, INC.

SALT LAKE CITY, UTAH 84101

ARCHITECT

90 SOUTH 400 WEST, SUITE 110

REVISION

PROJECT NUMBERS

DATE

SHEET TITLE

PLO

T D

AT

E:

INTERMOUNTAIN HEALTHCARE

SALT LAKE CITY, UTAH 84111

OWNER

36 SOUTH STATE STREET

ISSUE

© 2016 HKS, INC.

IN

TE

RM

OU

NT

AIN

LA

YT

ON

PA

RK

WA

Y C

LIN

IC

PC

H A

UD

IO

LO

GY

RE

MO

DE

L 2

01

8

SHEET NO.

HKS:

20

1 W

ES

T L

AY

TO

N P

AR

KW

AY

L

AY

TO

N, U

T 8

40

41

VAN BOERUM & FRANK ASSOCIATES, INC.MECHANICAL & PLUMBING ENGINEER

330 SOUTH 300 EAST SALT LAKE CITY, UT 84111

SPECTRUM ENGINEERS

SALT LAKE CITY, UTAH 84111

ELECTRICAL ENGINEER

324 S. STATE ST. STE. 400

12/1

0/20

18 7

:34:

33 A

M

A2.03H

PCH AUDIOLOGY

FLOOR PLANS

11/07/2018

22506.000

CONSTRUCTION

DOCUMENTS

PCH TI

1/8" = 1'-0"1 PCH AUDIOLOGY FLOOR PLAN1/8" = 1'-0"2 PCH AUDIOLOGY REF CLG PLAN

1/8" = 1'-0"3 PCH AUDIOLOGY FINISH PLAN

ETR

REFLECTED CEILING NOTES / KEYNOTESETR = EXISTING CEILING SYSTEM TO REMAIN

1. CUBICLE CURTAIN TRACKS ARE CONTRACTOR PROVIDED. CUBICLE CURTAINS ARE OWNER PROVIDED

1 1/2" = 1'-0"4 FURR DOWN DETAIL - BK-011 1/2" = 1'-0"5CEILING GRID ATTACHMENT

FOR SEISMIC CONDITION

INTERIOR FINISH REMARKS

1 MULTIPLE FLOOR FINISHES IN THIS AREA, REFER TO PLANS FOR MORE INFORMATION.2 MULTIPLE BASE FINISHES IN THIS AREA, REFER TO PLANS AND ELEVATIONS FOR MORE

INFORMATION.3 MULTIPLE WALL FINISHES IN THIS AREA. REFER TO PLANS AND ELEVATIONS FOR MORE

INFORMATION.4 INTEGRAL COVE BASE IN THIS AREA.5 EPOXY PAINT TO BE USED IN THIS AREA.6 IPT01 TO BE USED AT THIS LOCATION ABOVE WALL FINISH UNLESS NOTED OTHERWISE7 PORCELAIN TILE TO BE INSTALLED FULL HEIGHT AT WET WALL AND BEHIND SINK LOCATIONS.

PORCELAIN TILE TO BE INSTALLED 60"H ABOVE PORCELAIN TILE COVE BASE CAPPED WITH METALTRIM PIECE (MT02) AT ALL OTHER WALLS. TILE TO BE INSTALLED IN STACKED INSTALLATION.

8 INTEGRAL COVED BASE SHALL BE 6" HIGH9 ALL PENETRATIONS IN THIS AREA INCLUDING LIGHTING, HVAC, PLUMBING, ETC THROUGH CEILINGS

OR WALLS MUST BE SEALED

2. NEW CEILINGS ARE ACT02, TYPICAL

PAINT IPT01:SHERWIN WILLIAMS SW7005 PURE WHITE

NO. DESCRIPTION DATE

LINEN/STORAGE0254

VT01RB01IPT01

ROOM NUMBERROOM NAME

FLOORBASETYPICAL WALL

*REMARKS NUMBERS COORDINATE WITH FINISH REMARKS LEGEND LOCATED ON ALL FINISH FLOOR PLAN SHEETS

1*REMARKS

FINISH TAG LEGEND

RS01 A B

"A" INDICATES MOTORIZED SHADE IF "A" IS OMITTED SHADE IS MANUALLY OPERATED

INDICATES FABRIC SELECTION - SEE FINISH SCHEDULE

ROLLER SHADE TAG LEGEND

"B" INDICATES DOUBLE ROLL W/ BLACK OUT SHADE - SEE RS02 IN FINISH SCHEDULE, IF "B" IS OMITTED SHADE IS A SINGLE ROLL SHADE

PROVIDE 18" ACCENT PAINT (IPT24) FROM EDGE OF DOOR FRAME TO DRYWALL REVEAL.REFER TO ELEVATIONS FOR MORE INFO.

INTERIOR FINISH PLAN NOTES_PCH

030031 PROVIDE 18" ACCENT PAINT (IPT18) FROM EDGE OF DOOR FRAME TO DRYWALL REVEAL.REFER TO ELEVATIONS FOR MORE INFO.032 PROVIDE 18" ACCENT PAINT (IPT06) FROM EDGE OF DOOR FRAME TO DRYWALL REVEAL.REFER TO ELEVATIONS FOR MORE INFO.033 PROVIDE 18" ACCENT PAINT (IPT27) FROM EDGE OF DOOR FRAME TO DRYWALL REVEAL.REFER TO ELEVATIONS FOR MORE INFO.

HKS ARCHITECTS, INC.

SALT LAKE CITY, UTAH 84101

ARCHITECT

90 SOUTH 400 WEST, SUITE 110

REVISION

PROJECT NUMBERS

DATE

SHEET TITLE

PLO

T D

AT

E:

INTERMOUNTAIN HEALTHCARE

SALT LAKE CITY, UTAH 84111

OWNER

36 SOUTH STATE STREET

ISSUE

© 2016 HKS, INC.

IN

TE

RM

OU

NT

AIN

LA

YT

ON

PA

RK

WA

Y C

LIN

IC

PC

H A

UD

IO

LO

GY

RE

MO

DE

L 2

01

8

SHEET NO.

HKS:

20

1 W

ES

T L

AY

TO

N P

AR

KW

AY

L

AY

TO

N, U

T 8

40

41

VAN BOERUM & FRANK ASSOCIATES, INC.MECHANICAL & PLUMBING ENGINEER

330 SOUTH 300 EAST SALT LAKE CITY, UT 84111

SPECTRUM ENGINEERS

SALT LAKE CITY, UTAH 84111

ELECTRICAL ENGINEER

324 S. STATE ST. STE. 400

12/1

0/20

18 7

:34:

35 A

M

A2.70A

FINISH INFORMATION-

PCH

11/07/2018

22506.000

CONSTRUCTION

DOCUMENTS

PCH TI

INTERIOR FINISH GENERAL NOTES

1 PATTERN NAME, COLOR AND NUMBER FOR EACH MATERIAL ARE GIVEN WHEREVER POSSIBLE ON THE FINISH PLAN. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TOBRING ANY DISCREPANCIES TO THE ATTENTION OF THE ARCHITECT/DESIGNER SO THAT THE CORRECT MATERIAL IS INSTALLED.

2 REFERENCE A2 SERIES DRAWINGS FOR INTERIOR FINISH PLANS.3 REFERENCE A2 SERIES FOR WALL PROTECTION LOCATIONS.4 REFERENCE SHEET A3.24 FOR TYPES AND CONFIGURATIONS OF WALL PROTECTION.5 REFERENCE A2.71 FOR TYPICAL FLOORING TRANSITION DETAILS.6 REFERENCE A3 SERIES DRAWINGS FOR MILLWORK INFORMATION.7 REFERENCE A3 SERIES DRAWINGS FOR INTERIOR SPECIALTY ELEVATIONS.8 REFERENCE A4 SERIES FOR ALL CEILING FINISHES.9 REFERENCE A3.24 FOR TYPICAL WALL PROTECTION ELEVATION FINISHES AND MOUNTING HEIGHT LOCATIONS & LOCKER FINISH INFORMATION.10 DRYWALL TO RECEIVE A LEVEL FIVE (5) FINISH EVERYWHERE.11 ALL PT/CT EXPOSED OUTSIDE CORNERS SHALL RECEIVE MT01.12 ALL CORNER GUARDS ARE CG02, UNO.13 WELDING ROD AT WELDED SEAMS IN SHEET VINYL SHALL MATCH THE DARKER OF THE SHEET VINYL COLORS AT SEAMS THAT DIVIDE TWO COLORS UNLESS NOTED

OTHERWISE.14 WHEN SHOWN, INSTALL INTEGRAL BASE TO A HEIGHT OF 4" AFF, UNO.15 ALL FLOORING TRANSITIONS SHALL BE CENTERED UNDER THE DOOR IN THE CLOSED POSITION.16 DASHED IN FURNITURE TO BE O.F.O.I.17 ALL FLOORING TO BE INSTALLED PERPENDICULAR TO ROOM WALLS UNLESS NOTED OTHERWISE.18 BULKHEADS/SOFFITS/FURDOWNS SHOULD BE FINISHED WITH THE SAME MATERIAL AND OR COLOR ON ALL FACES AS SPECIFIED, UNLESS SPECIFICALLY NOTED OTHERWISE.19 ALL MATERIALS AND FINISHES TO BE INSTALLED ACCORDING TO MANUFACTURERS RECOMENDATIONS. ANY DISCREPANCIES BETWEEN WHAT IS INDICATED ON DRAWINGS

AND MANUFACTURERS INSTRUCTIONS SHOULD BE BROUGHT TO THE ARCHITECTS ATTENTION IMMEDIATELY AND PRIOR TO ORDER AND INSTALLATION OF MATERIALS.20 WHERE ATYPICAL CONDITIONS OCCUR, CONTRACTOR IS TO VERIFY FINISH TREATMENT WITH ARCHITECT BEFORE PROCEEDING.21 WIREWAYS, ACCESS PANELS, MECHANICAL DEVICES, ETC. SHALL BE FINISHED TO MATCH ADJACENT SURFACE UNLESS NOTED OTHERWISE.22 PROVIDE CRACK ISOLATION MEMBRANCE AS REQUIRED AT ALL PORCELAIN TILE FLOORING. FLOORING CONTRACTOR TO COORDINATE WITH DESIGNER.23 CONTINUE ALL FLOORING MATERIALS BENEATH ALL CASEWORK. MILLWORK, FURNTIURE, INCLUDING KNEESPACES, UNLESS NOTED OTHERWISE.24 CUT TILES TO NEVER BE LESS THAN 3". IF NECESSARY, CUT (2) TILES TO MAKE UP THE DIFFERENCE25 REFER TO PROJECT MANUAL SECTION "CAST-IN-PLACE CONCRETE" FOR SPECIFICATIONS FOR SEALED CONCRETE (SC) AND HARDENER/SEALER OR HARDENER SEALED

CONCRETE (HSC)27 AT I-2 OCCUPANCIES, ALL INTERIOR WALL AND CEILING FINISHES TO MEET CLASS B INTERIOR FINISH REQUIREMENTS. ADMINISTRATIVE AND ROOMS WITH A CAPACITY OF LESS

THAN 4 PERSONS ARE PERMITTED TO HAVE CLASS C INTERIOR FINISHES AS NOTED ON IBC TABLE 803.928 AT B OCCUPANCIES, ALL INTERIOR WALL AND CEILING FINISHES TO MEET CLASS C INTERIOR FINISH REQUIREMENTS AS NOTED ON IBC TABLE 803.929 AT U OCCUPANCIES, THERE ARE NO RESTRICTIONS REGARDING INTERIOR FINISHES30 ALL WALLS TO BE PAINTED IPT01 UNLESS NOTED OTHERWISE.31 ALL WALLS WITHIN PRIMARY CHILDREN'S SUITE TO BE PAINTED IPT27 UNLESS NOTED OTHERWISE

INTERIOR MATERIALS LEGEND

QT QUARRY TILEQTB QUARRY TILE BASEQZ QUARTZ SURFACERB RESILIENT BASERS ROLLER SHADESC SEALED CONCRETE

SDG SUSPENDED DECORATIVE GRIDSDT STATIC DISSAPTIVE TILESE SERVICE ELEVATOR

SHR SHEET RUBBER FLOORINGSHRB SHEET RUBBER BASESHV SHEET VINYL FLOORING

SHVB SHEET VINYL BASESS STAINLESS STEEL

SSB STAINLESS STEEL BASESSF SOLID SURFACE FABRICATIONSST STONE

SWP SHEET WALL PROTECTIONTC TRAFFIC COATINGTF TACKABLE FARBIC

TLP TOILET PARTITIONTZ POURED TERRAZZO

TZB TERRAZZO BASEUP UPHOLSTERY

VCT VINYL COMPOSITION TILEWC WALL COVERING

WDC WOOD CEILINGWDS WOOD SLAT WALLWM WALK OFF MATWP WALL PROTECTION ASSEMBLY

INTERIOR MATERIALS LEGEND

ACT ACOUSTICAL CEILING TILEAWP ACOUSTICAL WALL PANELCB CARPET BASECC CUBICAL CURTAINCG CORNER GUARDCLC COLUMN COVERCPT CARPET TILECR CRASH RAILCT CERAMIC TILE

CTB CERAMIC TILE BASEDG DECORATIVE GLAZINGDP DECORATIVE PANELEG ENTRANCE GRILLEPB EPOXY BASEEPT EPOXY PAINTFL FILM

FWC FABRIC WALL COVERINGGL GLAZING

GLT GLASS TILEGYP GYPSUM WALL BOARDHR HAND RAILIPT INTERIOR PAINTMT METAL TRIM

MTC METAL CEILINGOHR ORNAMENTAL HANDRAIL/RAILINGSPE PASSENGER ELEVATORPL PLASTIC LAMINATEPT PORCELAIN TILE

PTB PORCELAIN TILE BASE

INTERIOR TYPICAL FINISHES

IPT01 HOLLOW METAL FRAMESIPT01 GYPSUM BOARD HORIZONTAL SOFFIT SURFACES AND CEILINGSIPT01 INTERIOR HOLLOW METAL DOORSIPT06 EXPOSED DUCTWORKIPT06 PREFINISHED GRILLES/DIFFUSERS ON EXPOSED DUCTWORKIPTXX EXPOSED STRUCTURE, ROOF DECK, AND MEP COMPONENTSIPTXX METAL PORTIONS OF STAIRS

XX ELECTRICAL DEVICES COLOR (COORDINATE W/ELECTRICAL)WD01 INTERIOR WOOD DOORSCLC01 EXPOSED COLUMNSPL01 VERTICAL CASEWORK/MILLWORK TO BE PLASTIC LAMINATE, UNLESS NOTED OTHERWISE

SSF01 HORIZONTAL COUNTERTOPS TO BE SOLID SURFACE UNLESS NOTED OTHERWISE

INTERIOR FINISH REMARKS

1 MULTIPLE FLOOR FINISHES IN THIS AREA, REFER TO PLANS FOR MORE INFORMATION.2 MULTIPLE BASE FINISHES IN THIS AREA, REFER TO PLANS AND ELEVATIONS FOR MORE

INFORMATION.3 MULTIPLE WALL FINISHES IN THIS AREA. REFER TO PLANS AND ELEVATIONS FOR MORE

INFORMATION.4 INTEGRAL COVE BASE IN THIS AREA.5 EPOXY PAINT TO BE USED IN THIS AREA.6 IPT01 TO BE USED AT THIS LOCATION ABOVE WALL FINISH UNLESS NOTED OTHERWISE7 PORCELAIN TILE TO BE INSTALLED FULL HEIGHT AT WET WALL AND BEHIND SINK LOCATIONS.

PORCELAIN TILE TO BE INSTALLED 60"H ABOVE PORCELAIN TILE COVE BASE CAPPED WITH METALTRIM PIECE (MT02) AT ALL OTHER WALLS. TILE TO BE INSTALLED IN STACKED INSTALLATION.

8 INTEGRAL COVED BASE SHALL BE 6" HIGH9 ALL PENETRATIONS IN THIS AREA INCLUDING LIGHTING, HVAC, PLUMBING, ETC THROUGH CEILINGS

OR WALLS MUST BE SEALED

INTERIOR FINISH PLAN NOTES

001 ALIGN FLOOR TRANSITION WITH ADJACENT WALL OR EDGE OF MILLWORK002 PAINTED DRYWALL CONTROL JOINT AT THIS LOCATION. REFER TO FINISH PLANS AND ARCHITECTURAL INTERIOR ELEVATIONS FOR

ADDITIONAL INFORMATION REGUARDING THE PAINT AND REVEAL PATTERN INFORMATION.029 INSTALL TILE OR CARPET TILE IN DIRECTION OF ARROW.

INTERIOR DESIGN SELECTION SUMMARY - PCH TI

NAME MANUFACTURER STYLE NUMBER COLOR SIZE COMMENTS CONTACT

ACOUSTICAL CEILING TILEACT02 ARMSTRONG OPTIMA SQUARE LAY-IN 3152 WHITE 24" X 24" USE GRID: SDG01 MATTHEW SANDER 323.219.5036

CARPET BASECB06 SHAW CONTRACT UTOPIAN 43575 WINTER CLOUD 4"H PEDS CLINIC ROB HOLT 801.554.3883

CARPET TILECPT06 SHAW CONTRACT QUARTZ TILE 5T017 AZURITE 18" X 36" PEDS CLINIC + PRIMARY

CHILDRENSROB HOLT 801.554.3883

CORNER GUARDSCG01 C/S ACROVYN CORNER GUARD SM-20N PUMICE 3" LEGS X 4' HIGH PVC FREECG02 C/S ACROVYN CORNER GUARD SM-20N PUMICE 3" LEGS X 8' HIGH PVC FREECG15 C/S ACROVYN ACROVYN 4000 END GUARD SSM-25MN TBD 2" LEGS X 8' HIGH PVC FREE

INTERIOR PAINTIPT03 SHERWIN WILLIAMS SW6106 KILIM BEIGE 2 COATS MINIMUM TOM BRUMMETT 310.999.9396IPT05 SHERWIN WILLIAMS SW6478 WATERY 2 COATS MINIMUM TOM BRUMMETT 310.999.9396IPT06 SHERWIN WILLIAMS SW7611 TRANQUIL AQUA 2 COATS MINIMUM TOM BRUMMETT 310.999.9396IPT08 SHERWIN WILLIAMS SW6423 RYE GRASS 2 COATS MINIMUM TOM BRUMMETT 310.999.9396IPT18 SHERWIN WILLIAMS SW6367 VIVA GOLD 2 COATS MINIMUM TOM BRUMMETT 310.999.9396IPT20 SHERWIN WILLIAMS SW6492 JETSTREAM 2 COATS MINIMUM TOM BRUMMETT 310.999.9396IPT24 SHERWIN WILLIAMS SW6508 SECURE BLUE 2 COATS MINIMUM TOM BRUMMETT 310.999.9396IPT25 SHERWIN WILLIAMS SW6710 MELANGE GREEN 2 COATS MINIMUM TOM BRUMMETT 310.999.9396IPT26 SHERWIN WILLIAMS SW9018 HONEY BEES 2 COATS MINIMUM TOM BRUMMETT 310.999.9396IPT27 BENJAMIN MOORE OC14 NATURAL CREAM 2 COATS MINIMUM CONSTANCE 201.912.2829

PLASTIC LAMINATEPL01 ARBORITE W-465 EV MOCHA MODERN CHERRY WOODLOOK EILEEN WALKER 714.388.8420PL05 ARBORITE P-355 RM WEATHERED HEMP OFFICE COUNTER TOPS NON

FURNITUREEILEEN WALKER 714.388.8420

PL08 ARBORITE W-464 EV BLONDE MODERN CHERRY EILEEN WALKER 714.388.8420

SHEET VINYL BASESHVB17 JOHNSONITE ACCENT WOOD 29012 ALLOVER WOOD BROWN 6" HIGH ELLEN WREN 440.708.5873SHVB18 JOHNSONITE OPTIMA 861 CLOVER LEAF 6" HIGH ELLEN WREN 440.708.5873SHVB19 JOHNSONITE OPTIMA 843 PACIFICA 6" HIGH ELLEN WREN 440.708.5873SHVB20 JOHNSONITE OPTIMA 821 FROTHY LATTE 6" HIGH ELLEN WREN 440.708.5873SHVB21 JOHNSONITE OPTIMA 863 ABLAZED 6" HIGH ELLEN WREN 440.708.5873SHVB22 JOHNSONITE OPTIMA 831 HOT GINGER 6" HIGH ELLEN WREN 440.708.5873SHVB23 JOHNSONITE OPTIMA 834 PARSLEY 6" HIGH ELLEN WREN 440.708.5873SHVB24 JOHNSONITE OPTIMA 838 SEASPRAY 6" HIGH ELLEN WREN 440.708.5873SHVB25 JOHNSONITE OPTIMA 839 SUBMERGED 6" HIGH ELLEN WREN 440.708.5873

SHEET VINYL FLOORINGSHV17 JOHNSONITE ACCENT WOOD 29012 ALLOVER WOOD BROWN SHEET ELLEN WREN 440.708.5873SHV18 JOHNSONITE OPTIMA 861 CLOVER LEAF SHEET ELLEN WREN 440.708.5873SHV19 JOHNSONITE OPTIMA 843 PACIFICA SHEET ELLEN WREN 440.708.5873SHV20 JOHNSONITE OPTIMA 821 FROTHY LATTE SHEET ELLEN WREN 440.708.5873SHV21 JOHNSONITE OPTIMA 863 ABLAZED SHEET ELLEN WREN 440.708.5873SHV22 JOHNSONITE OPTIMA 831 HOT GINGER SHEET ELLEN WREN 440.708.5873SHV23 JOHNSONITE OPTIMA 834 PARSLEY SHEET ELLEN WREN 440.708.5873SHV24 JOHNSONITE OPTIMA 838 SEASPRAY SHEET ELLEN WREN 440.708.5873SHV25 JOHNSONITE OPTIMA 839 SUBMERGED SHEET ELLEN WREN 440.708.5873

SHEET WALL PROTECTIONSWP01 C/S ACROVYN .040" THICKNESS, RIGID SHEET 858 PUMICE VARIOUS PVC FREE ELISA CONTRERAS 626-665-1321SWP05 NOT USEDSWP06 C/S ACROVYN .040" THICKNESS, RIGID SHEET 223 DANUBE VARIOUS PVC FREE ELISA CONTRERAS 626-665-1321SWP07 C/S ACROVYN .040" THICKNESS, RIGID SHEET 848 ASPEN VARIOUS PVC FREE ELISA CONTRERAS 626-665-1321SWP08 NOT USEDSWP09 C/S ACROVYN .040" THICKNESS, RIGID SHEET 311 CELERY VARIOUS PVC FREE ELISA CONTRERAS 626-665-1321

SOLID SURFACING FABRICATIONSSSF01 CORIAN CLAM SHELL VARIES MONICA SAMS 562.631.1078SSF03 CORIAN WHISPER VARIES MONICA SAMS 562.631.1078

SUSPENDED DECORATIVE GRIDSDG01 ARMSTRONG PRELUDE XL 15/16" WHITE LAY-IN MATTHEW SANDER 323.219.5036

NO. DESCRIPTION DATE

(SCHLUTER SCHIENE)(SCHLUTER SCHIENE)

(SCHLUTER SCHIENE)

(MERCER 633)

(MERCER 705)

TYPE FT-17

TYPE FT-16

TYPE FT-11

TYPE FT-10

TYPE FT-14

TYPE FT-15

METAL STRIPS

LEVELING COMPOUND

RESILIENT FLOORING

THIN-SET TERRAZZO

DIVIDER STRIP

1/4" TILE RESILIENT FLOORING

LEVELING COMPOUND

LEVELING COMPOUND

1/4" CARPETRESILIENT FLOORING

1/4" TILE 1/4" CARPET

LEVELING COMPOUND

CONCRETERESILIENT FLOORING

CENTERLINEDOOR &

THRESHOLD

VINYL MOULDINGS

1/4" TO 5/16" GLUE DOWN CARPET

1/4" CARPETSHEET VINYL

CENTERLINEDOOR &

THRESHOLD

NOTE: USE JOHNSONITE SLT-49-A (BEIGE) WITH SHV01, SHV02, SHV03, & SHV04 (HOSPITAL PORTION)USE SLT-20-A (CHARCOAL) WITH ALL OTHER SHV SELECTIONS (CLINIC PORTION)

TYPE FT-8

INTERIOR FINISH DETAILS

BRICK PATTERN

2' -

0"

2' - 0"

WALL FINISH (SEE FINISH PLAN)FRAMING

COVE STICK SHEET VINYL FLOORING

SHEET VINYL INTEGRAL BASE 6"

1/8" CLEAR ANODIZED ALUMINUM COVE CAP

BASE DETAILS SCALE: 3" = 1'0"

WALL AND CORNER GUARDS SCHEDULE SCALE: 3" = 1' - 0"

MISCELLANEOUS SPECIALTIES AND EQUIPMENT SCALE: 1/4" = 1' - 0"

MOUNTING DETAIL -REFER TO SHEET A3.01

FINISH FLOOR

DRAWING DESIGNATION

4' -

0"

B

FEC FIRE EXTINGUISHER & CABINET

MOUNTING DETAIL -REFER TO SHEET A3.01

FINISH FLOOR

DRAWING DESIGNATION CORNER GUARD

CG-2

SURFACE MOUNTED - NOT FIRE RATED

- FULL HEIGHT

CG-1 CG-2

3"

3"

TOILET ACCESSORY MOUNTING DIAGRAM SCALE: 1/4" = 1'-0"

NOTE:

1. ACCESSORIES LISTED MAY HAVE GAPS IN ALPHABETICAL LISTING.

2. ACCESSORIES CAN APPEAR ON FLOOR PLANS OR INTERIOR ELEVATIONS.

FINISH FLOOR

TOILET ACCESSORY TYPE

MOUNTING DETAIL - REFER TO SHEET A3.02

DRAWING DESIGNATION

CL

PAPER TOWELS

A

A2 SURFACE MOUNTED

PO

INT

3' -

4" T

OD

ISP

EN

SIN

G

TO

SP

OU

T

SOAP DISP

A

J1 SURFACE MOUNTED

3' -

4"

OWNER FURNISHED, CONTRACTOR INSTALLED

OWNER FURNISHED, CONTRACTOR INSTALLED

RESPONSIBILITY:

ALL ITEMS ARE CONTRACTOR FURNISHED, CONSTRACTOR INSTALLED, UNO)

HKS ARCHITECTS, INC.

SALT LAKE CITY, UTAH 84101

ARCHITECT

90 SOUTH 400 WEST, SUITE 110

REVISION

PROJECT NUMBERS

DATE

SHEET TITLE

PLO

T D

AT

E:

INTERMOUNTAIN HEALTHCARE

SALT LAKE CITY, UTAH 84111

OWNER

36 SOUTH STATE STREET

ISSUE

© 2016 HKS, INC.

IN

TE

RM

OU

NT

AIN

LA

YT

ON

PA

RK

WA

Y C

LIN

IC

PC

H A

UD

IO

LO

GY

RE

MO

DE

L 2

01

8

SHEET NO.

HKS:

20

1 W

ES

T L

AY

TO

N P

AR

KW

AY

L

AY

TO

N, U

T 8

40

41

VAN BOERUM & FRANK ASSOCIATES, INC.MECHANICAL & PLUMBING ENGINEER

330 SOUTH 300 EAST SALT LAKE CITY, UT 84111

SPECTRUM ENGINEERS

SALT LAKE CITY, UTAH 84111

ELECTRICAL ENGINEER

324 S. STATE ST. STE. 400

12/1

0/20

18 7

:34:

37 A

M

A2.71

INTERIOR DETAILS -

FLOOR TRANSITION

DETAILS

11/07/2018

22506.000

CONSTRUCTION

DOCUMENTS

FLOOR TRANSITIONS SCALE: HALF

1/2" = 1'-0"08 CARPET TILE INSTALLATION

3" = 1'-0"12 BASE DETAIL-SHEET VINYL 6"

NO. DESCRIPTION DATE

REFER TO PARTITION HEAD DETAILS

SEALANT

MTL RUNNER

SEALANT

MTL RUNNER

5/8" GYP BD EACH SIDE

LINE OF STRUCTURE

LINE OF CEILING

LINE OF STRUCTURE

FLOOR PLAN DESIGNATION NO SOUND ATTENUATION

FLOOR PLAN DESIGNATION WITH SOUND ATTENUATION

STUD SIZE

PART WIDTH

FIRE RATING

UL LISTING

WITH SOUND

STC:NO SOUND

REMARKS

3 5/8" 4 7/8"NON-

RATED N/A 49W/3" SAB

40

2 1/2"

6"

3 5/8"

2 1/2"

6"

3 5/8"

2 1/2"

6"

3 5/8"

3 3/4"

7 1/4"

4 7/8"

3 3/4"

4 7/8"

7 1/4"

3 3/4"

7 1/4"

4 7/8"

NON-RATED

NON-RATED

SMOKE RESIST

SMOKE RESIST

SMOKE RESIST

ONE HOUR

ONE HOUR

ONE HOUR

ONE HOUR/ SMOKE RESIST

U465 49W/3" SAB

40

2 1/2" 3 3/4"

ONE HOUR/ SMOKE RESIST

N/A 49W/3" SAB

40

6" 7 1/4"

ONE HOUR/ SMOKE RESIST

U465 49W/3" SAB

40

N/A

N/A

N/A

N/A

N/A

U465

N/A

U465

49W/3" SAB

40

49W/3" SAB

40

49W/3" SAB

40

49W/3" SAB

40

49W/3" SAB

40

49W/3" SAB

40

49W/3" SAB

40

49W/3" SAB

40

REFER TO PARTITION HEAD DETAILS

TYPE "G"

SEALANT

MTL RUNNER

SEALANT

MTL RUNNER

2 LAYERS 5/8" GYP BD ONE SIDE ONLY

LINE OF STRUCTURE

LINE OF CEILING

LINE OF STRUCTURE

3 5/8" 5 1/2"NON-

RATED N/A 51W/3" SAB

44

2 1/2"

6"

3 5/8"

4 3/8"

7 7/8"

5 1/2"

NON-RATED

NON-RATED

ONE HOUR/ SMOKE RESIST

U419 51W/3" SAB

44

2 1/2" 4 3/8"

ONE HOUR/ SMOKE RESIST

U419

6" 7 7/8"

ONE HOUR/ SMOKE RESIST

U419

3 5/8" 5 1/2"SMOKE RESIST

2 1/2"

6"

4 3/8"

7 7/8"

SMOKE RESIST

SMOKE RESIST

3 5/8" 5 1/2"ONE

HOUR U419

2 1/2"

6"

4 3/8"

7 7/8"

ONE HOUR

ONE HOUR

U419

U419

N/A

N/A

N/A

N/A

N/A

51W/3" SAB

44

51W/3" SAB

44

51W/3" SAB

44

51W/3" SAB

44

51W/3" SAB

44

51W/3" SAB

44

51W/3" SAB

44

51W/3" SAB

44

51W/3" SAB

44

51W/3" SAB

44

REFER TO PARTITION HEAD DETAILS

TYPE "H"

MTL RUNNER

SEALANT

MTL RUNNER

5/8" GYP BD

3 5/8" 4 1/4"NON-

RATED N/A

2 1/2"

6"

3 1/8"

6 5/8"

NON-RATED

NON-RATED

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

LINE OF STRUCTURE

LINE OF STRUCTURE

REFER TO PARTITION HEAD DETAILS

TYPE "J"

MTL RUNNER

SEALANT

MTL RUNNER

5/8" GYP BD

3 5/8" 4 1/4"NON-

RATED N/A

2 1/2"

6"

3 1/8"

6 5/8"

NON-RATED

NON-RATED

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

LINE OF STRUCTURE

LINE OF STRUCTURE

LINE OF CEILING

TYPE "K"

1 5/8" 3"NON-

RATED N/A

2 1/2"

3 5/8"

4"

5"

NON-RATED

NON-RATED

N/A

N/A

N/A

N/A

N/A

N/A

N/A

N/A

SEALANT

MTL RUNNER

5/8" GYP BD

LINE OF STRUCTURE

LINE OF STRUCTURE

BRACE EACH STUD AT 4'-0" OC VERTICALLY

LINE OF STRUCTURE OR OTHER CONSTRUCTION PROVIDING BACK-UP FOR STUD BRACING

A3 A3

A2 A2

A6 A6

A3

A2 A2

A6 A6

A3

A2 A2

A6 A6

A3

A2 A2

A6 A6

G3 G3

G2 G2

G6 G6

G3 G3

G2 G2

G6 G6

G3 G3

G2 G2

G6 G6

G6 G6

G2 G2

G3 G3

H3

H2

H6

J3

J2

J6

K1

K2

K3

FLOOR PLAN DESIGNATION NO SOUND ATTENUATION

FLOOR PLAN DESIGNATION WITH SOUND ATTENUATION

STUD SIZE

PART WIDTH

FIRE RATING

UL LISTING

WITH SOUND

STC:NO SOUND

REMARKS

FLOOR PLAN DESIGNATION NO SOUND ATTENUATION

FLOOR PLAN DESIGNATION WITH SOUND ATTENUATION

STUD SIZE

PART WIDTH

FIRE RATING

UL LISTING

SOUND TRANS CLASS REMARKS

FLOOR PLAN DESIGNATION NO SOUND ATTENUATION

FLOOR PLAN DESIGNATION WITH SOUND ATTENUATION

STUD SIZE

PART WIDTH

FIRE RATING

UL LISTING

REMARKS

FLOOR PLAN DESIGNATION NO SOUND ATTENUATION

FLOOR PLAN DESIGNATION WITH SOUND ATTENUATION

STUD SIZE

PART WIDTH

FIRE RATING

UL LISTING

REMARKS

LINE OF CEILING

LINE OF CEILING

TYPE "A"

PARTITION WIDTH

REFER TO SCHEDULEBELOW FOR

PARTITION WIDTH

REFER TO SCHEDULEBELOW FOR

3"

PARTITION WIDTH

REFER TO SCHEDULEBELOW FOR

PARTITION WIDTH

REFER TO SCHEDULEBELOW FOR

3"

PARTITION WIDTH 3" MIN

REFER TO SCHEDULEBELOW FOR

SOUND TRANS CLASS

SOUND TRANS CLASS

NOTES

PARTITION TYPE INCLUDED IN SCOPE OF WORK

PARTITION TYPE NOT INCLUDED IN SCOPE OF WORK

1. PARTITIONS ARE DISTINGUISHED ON FLOOR PLANS BY SYMBOL DESIGNATION, GRAPHIC DESIGNATION OR A COMBINATION OF BOTH DESIGNATIONS.

2. THERE ARE TWO TYPES OF SYMBOL DESIGNATIONS, ONE FOR PARTITIONS NOT REQUIRING SOUND ATTENUATION AND ANOTHER FOR PARTITIONS WHICH REQUIRE SOUND ATTENUATION. REFER TO PARTITION MATRICES FOR SOUND ATTENUATION BLANKET (SAB) MINIMUM THICKNESS FOR STC INDICATED.

3. THERE ARE TWO SYMBOL DESIGNATION SYSTEMS USED. THE FIRST SYSTEM CONSISTS OF TWO AND THREE CHARACTERS, THE FIRST CHARACTER IS A LETTER INDICATING THE PARTITION TYPE. THE SECOND CHARACTER IS NUMERIC INDICATING THE STUD OR CMU WIDTH. REFER TO LEGEND BELOW. THIS SYSTEM IS USED TO DEFINE WALL TYPES: A, B, C, D, E, F, H, J, K, M, R

THE # CHARACTER BELOW THE LINE INDICATES THE HEIGHT OF THE SPECIFIC WALL COMPONENT. THE HEIGHT OF A SPECIFIC WALL COMPONENT. REFER TO THE LEGEND BELOW. THIS SYSTEM IS USED TO DEFINE WALL TYPES: G, L, P, Q, S, T, U, W, X, Y, Z

4. IF NO SYMBOL DESIGNATION IS PROVIDED, THE STUD SIZE WILL BE 3 5/8".

5. THE GRAPHIC DESIGNATION IS INCORPORATED FOR PARTITIONS REQUIRED TO BE SMOKE RESISTANT, FIRE RESISTANT, OR BOTH FIRE AND SMOKE RESISTANT. REFER TO NOTE 18.

6. "LINE OF STRUCTURE" INDICATED FOR EACH PARTITION IS DIAGRAMMATIC ONLY AND DOES NOT INDICATE EXACT CONSTRUCTION CONDITIONS OR GEOMETRY.

7. ALL DIMENSIONS ARE FROM FACE OF GYPSUM BOARD TO FACE OF GYPSUM BOARD. REFER TO PARTITION MATRICES FOR PARTITION WIDTH DIMENSIONS UNLESS INDICATED TO BE SHOWN ON PLAN.

8. SEALANT:1. FIRE RESISTANCE RATED PARTITIONS SHALL USE RATED FIRE/SMOKE FIRE RESISTANT FILL

MATERIAL IN CONJUNCTION WITH AN APPROPRIATE RATED FIRE/SMOKE FIRE STOPPING SYSTEM.

2. NON-RATED PARTITIONS AND NON-RATED SMOKE RESISTANT PARTITIONS SHALL USE ACOUSTICAL SEALANT.

9. INSULATION: - HEAD CONDITIONS AT FLOOR/ROOF DECK1. FIRE RESISTANCE RATED PARTITIONS SHALL USE MINERAL WOOL INSULATION.2. NON-RATED PARTITIONS REQUIRING SOUND ATTENUATION SHALL USE SOUND ATTENUATION BLANKETS (SAB).3. PROVIDE FULL THICKNESS INSULATION INSIDE ALL STUD BOX BEAMS AND HEADERS WHICH

OCCUR IN WALLS WITH SOUND ATTENUATION.

10. REFER TO SPECIFICATIONS FOR MINIMUM STUD THICKNESS, MAXIMUM SPACING AND ALLOWABLE LIMITING HEIGHTS DEFLECTION CRITERIA FOR GYPSUM BOARD ASSEMBLIES.

11. FOR PARTITIONS INDICATED TO RECEIVE SOUND ATTENUATION BLANKETS (SAB), EXTEND SAB TO FULL HEIGHT OF PARTITION UNLESS OTHERWISE INDICATED. FLOOR TRACK TO BE SET IN A CONT BED OF SEALANT.

12. FIRE RESISTANT AND FIRE RESISTANT SMOKE BARRIER RATINGS ARE TO SURROUND ALL OPENINGS IN RATED PARTITIONS.

NUMERIC CHARACTER

STUD WIDTH

CMU WIDTH

12346812

1 5/8"2 1/2"3 5/8"

4"6"

3 5/8"5 5/8"7 5/8"

11 5/8"

13. SMOKE RESISTANT, FIRE RESISTANT, AND FIRE RESISTANT SMOKE BARRIER PARTITIONS SHALL EXTEND AND SEAL TO INSIDE FACE OF EXTERIOR SHEATHING, INCLUDING EXTENSIONS THROUGH SOFFITS.

14. EACH PARTITION SHOWN ON THE DRAWINGS TO HAVE A FIRE AND SMOKE RESISTANT RATING SHALL BE IDENTIFIED AS SUCH WITH A LABEL ABOVE THE CEILING ON EACH SEGMENT OF THE WALL AND 6' - 0" OC MAX EACH SIDE.

15. REFER TO TOILET ACCESSORIES SHEET AND CASEWORK SHEET FOR MOUNTING DETAIL INFORMATION.

16. REFER TO THE METAL FABRICATIONS DETAILS FOR MF REFERENCES IN PARTITIONS SECTION.

17. REFER TO STRUCTURAL DRAWINGS FOR REINFORCING INFORMATION.

18. GRAPHIC DESIGNATION

19. DO NOT APPLY BULLNOSE BLOCK AT CORNER GUARD LOCATIONS.

20. MASONRY REINFORCEMENT: REFERENCE STRUCTURAL DRAWINGS.

21. HW (HEAD OF WALL) DETAILS DO NOT ALTER PARTITION TYPES NOTED ON PLANS.

3 HR FIRE BARRIER2 HR SMOKE BARRIER2 HR FIRE BARRIER2 HR FIRE BARRIER/SHAFT WALL1 HR SMOKE BARRIER1 HR FIRE BARRIER1 HR FIRE BARRIER/SHAFT WALLSMOKE PARTITION (NON RATED)

PRIORITY

1 HIGHEST

2

3

4 LOWEST

NOTE:

1. NOT ALL PARTITION TYPES SHOWN ON THIS SHEET ARE USED ON THIS PROJECT.

2. THE SHADED PORTIONS OF A PARTITION TYPE ARE NOT INCLUDED IN THE SCOPE OF THE WORK.

3. THE UN-SHADED PORTIONS OF ALL PARTITION TYPES ARE INTENDED TO BE IN THE SCOPE OF THE WORK.

HATCHING:

NUMERIC CHARACTER

CMU/BRICK HEIGHT

12345

9' - 4"10' - 8"12' - 8"18' - 8"14' - 0"

SYMBOL DESIGNATIONS(NO SOUND ATTENUATION)

SYMBOL DESIGNATION(WITH SOUND ATTENUATION)

X# X#XXXX# XXXX

#

A3

A3

A3

EXISTING 'A3' WALLCONSTRUCTION

NEW LAYER OF GYP BDADDED TO ACHIEVE 'G3'ASSEMBLY

HKS ARCHITECTS, INC.

SALT LAKE CITY, UTAH 84101

ARCHITECT

90 SOUTH 400 WEST, SUITE 110

REVISION

PROJECT NUMBERS

DATE

SHEET TITLE

PLO

T D

AT

E:

INTERMOUNTAIN HEALTHCARE

SALT LAKE CITY, UTAH 84111

OWNER

36 SOUTH STATE STREET

ISSUE

© 2016 HKS, INC.

IN

TE

RM

OU

NT

AIN

LA

YT

ON

PA

RK

WA

Y C

LIN

IC

PC

H A

UD

IO

LO

GY

RE

MO

DE

L 2

01

8

SHEET NO.

HKS:

20

1 W

ES

T L

AY

TO

N P

AR

KW

AY

L

AY

TO

N, U

T 8

40

41

VAN BOERUM & FRANK ASSOCIATES, INC.MECHANICAL & PLUMBING ENGINEER

330 SOUTH 300 EAST SALT LAKE CITY, UT 84111

SPECTRUM ENGINEERS

SALT LAKE CITY, UTAH 84111

ELECTRICAL ENGINEER

324 S. STATE ST. STE. 400

12/1

0/20

18 7

:34:

39 A

M

A3.01

PARTITION TYPES

11/07/2018

22506.000

CONSTRUCTION

DOCUMENTS

PCH TI

NO. DESCRIPTION DATE

DOUBLE 20 GA 3 5/8" OR 6" MTL STUDS

CLIP ANGLE - 20 GA X 1 1/2" X 1 1/2" X 3" FOR 3 5/8" STUDS AND 5" FOR 6" STUDS EACH SIDE

20 GA MTL TRACK

CLIP ANGLE - 20 GA X 1 1/2" X 1 1/2" X 3" FOR 3 5/8" STUDS AND 5" FOR 6" STUDS EACH SIDE

20 GA MIN MTL TRACK

CLIP ANGLE - 20 GA X 1 1/2" X 1 1/2" X 3" FOR 3 5/8" STUDS AND 5" FOR 6" STUDS

20 GA MIN MTL TRACK

CLIP ANGLE - 20 GA X 1 1/2" X 1 1/2" X 3" FOR 3 5/8" STUDS AND 5" FOR 6" STUDS

20 GA MIN MTL TRACK

CLIP ANGLE - 20 GA X 1 1/2" X 1 1/2" X 3" FOR 3 5/8" STUDS AND 5" FOR 6" STUDS

20 GA MIN MTL TRACK AT FLOOR

2 1/2" X 2 1/2" 20 GA MTL STRAP AT 2'-0" OC WITH 4 SCREWS (2 INTO EACH STUD EA SIDE)

20 GA MIN MTL TRACK AT FLOOR

DOUBLE 20 GA MTL STUDS

MIN 20 GA MTL STUDS FACING OPPOSITE DIRECTIONS TO ALLOW MOUNTING PLATE ATTACHMENT

14 GA STL RUNNER TRACK-CLIP FLANGES AND FOLD WEB TO FORM ATTACHMENT FLANGE

RE

FER

TY

PIC

AL

MO

UN

TIN

G

HE

IGH

TS

8" MIN DEEPER IF REQUIRED

TYPE CTYPE BTYPE A

RE

FER

TY

PIC

AL

MO

UN

TIN

G

HE

IGH

TS

CONT 20 GA 4" WIDE MTL BACK-UP PLATE

HSS 4x2x3/16 W/ 1/8" THICK END PLATES (MIN 8- #12 TEK SCREWS)

RE

FER

TY

PIC

AL

MO

UN

TIN

G

HE

IGH

TS

TYPE D

MIN 18 GA MTL DOUBLE STUDS AT 16" OC TO ALLOW MOUNTING PLATE ATTACHMENT

BARIATRIC GRAB BAR

RE

FER

TY

PIC

AL

MO

UN

TIN

G

HE

IGH

TS

CONT 16 GA 8" WIDE MTL BACK-UP PLATE

2"4"

2"

05 05

02 01 03 01

04

DOUBLE STUDS (FULL HEIGHT)

DOUBLE STUDS (FULL HEIGHT)

DOUBLE STUDS (FULL HEIGHT)

MOUNTING DETAILB

8' - 6" MAX4' - 6" MAXSTONE VENEER WALLS

16 GA STUDS AT 4' - 6" MAX 8' - 6" MAX

DOOR OPENING DOUBLE DOOR OPENING

BELOW CEILING OPENING

LARGE BELOW CEILING

OPENING

PROVIDE DIAGONAL BRACING OF TOP TRACK AT 48" OC MAX BETWEEN FULL HEIGHT STUDS

05

02

DOOR OPENING05

02

DOOR OPENING05

01

DOUBLE DOOR OPENING

03

BELOW CEILING OPENING

01

LARGE BELOW CEILING

OPENING05

03

ABOVE CEILING

OPENING

LARGE ABOVE CEILING

OPENING

04

01

01

01

OPENING ABOVE CEILING WHICH INTERRUPTS

LOWER OPENINGS JAMB STUDS

MOUNTING DETAIL B

DOUBLE STUDS

DOUBLE STUDS

DOUBLE STUDS

DOUBLE STUDS

DOUBLE STUDS

STONE VENEER WALLS16 GA STUDS AT 20 GA STUDS AT

WALL MOUNTED ARCHITECTURAL

CABINETS/MILLWORK /ATTACHED SHELVING

4' - 6" MAX 8' - 6" MAX 4' - 6" MAX4' - 6" MAX 8' - 6" MAX

STUDS ARE TO BE 20 GAGEIF GREATER THAN 8' - 6" ALL

8' - 6" MAX 8' - 6" MAX4' - 6" MAX

22 GA MIN BOTTOM TRACK (TYP)

FLOOR LINE

22 GA MIN MTL TOP TRACK (TYP UNO)

CEILING LINE

UNDERSIDE OF SLAB, FLOOR OR ROOF DECK

2" WIDE 22 GA MIN METAL STRAP

NOTES:

1. ALL STUDS ARE SPACED 16" OC MAXIMUM.

2. ALL STUDS SHALL BE "C" STUDS WITH 1/4" FLANGE MINIMUM.3. DENOTES SHELVING OR CABINETRY.

4. DENOTES STONE.

5. IN NO CASE SHALL DOUBLE STUDS AT SIDES OF OPENING BE CUT FOR DUCTWORK OR OTHER MECHANICAL SYSTEMS.

6. AT LEAD LINED PARTITIONS STUDS SHOULD BE 20 GA.

ACCESSORY/EQUIPMENT MOUNTING DETAILS PARTITION FRAMING DETAILS

04

TYPICAL INTERIOR PARTITION FRAMING

AT SHOWER SEATS16 GA STUDS AT 12" OC

NON-RATED OR SMOKE RESISTANT

FLUTED STEEL DECK/CONCRETE FLOOR OR ROOF PERPENDICULAR OR DIAGONAL TO

FLUTES

CONT 2" WIDE X 22 GA MTL STRAP FOR TOP ATTACHMENT OF GYP BD

CONT 20 GA MIN 3" DEEP LEG DEFLECTION TRACK ATTACH TO DECK AT 12" OC MAX

DO NOT ATTACH GYP BD OR STUDS TO DEFLECTION TRACK IN THIS AREA

SEALANT

NON-RATED OR SMOKE RESISTANT

CONCRETE FLOOR OR ROOF

CONT 20 GA MIN 3" DEEP LEG DEFLECTION TRACK ATTACH TO DECK AT 12" OC MAXDO NOT ATTACH

GYP BD OR STUDS TO DEFLECTION TRACK IN THIS AREA

SEALANT

CONT 2" WIDE X 22 GA MTL STRAP FOR TOP ATTACHMENT OF STUDS

1"

1"

1"

4"

NON-RATED

FLUTED STEEL DECK/CONCRETE FLOOR OR ROOF PERPENDICULAR OR DIAGONAL TO

FLUTES

LINE OF CEILING AS SCHEDULED

CONT 2" WIDE X 22 GA MTL STRAP FOR TOP ATTACHMENT OF STUDS

CONT 20 GA MIN 3" DEEP LEG DEFLECTION TRACK ATTACH TO DECK AT 12" OC MAX

DO NOT ATTACH GYP BD OR STUDS TO DEFLECTION TRACK IN THIS AREA

1"

4"

LINE OF CEILING AS SCHEDULED

CONT 2" WIDE X 22 GA MTL STRAP FOR TOP ATTACHMENT OF STUDS

CONT 20 GA MIN 3" DEEP LEG DEFLECTION TRACK ATTACH TO DECK AT 12" OC MAXDO NOT ATTACH

GYP BD OR STUDS TO DEFLECTION TRACK IN THIS AREA

NON-RATED

CONCRETE FLOOR OR ROOF

1"

4 1/

8"

LINE OF CEILING AS SCHEDULED

CONT 2" WIDE X 22 GA MTL STRAP FOR TOP ATTACHMENT OF STUDS

DO NOT ATTACH GYP BD OR STUDS TO DEFLECTION TRACK IN THIS AREA

CONT 20 GA MIN 3" DEEP LEG DEFLECTION TRACK ATTACH TO DECK AT 12" OC MAX

WHEN PARTITION IS ALIGNED AT DECK FLUTE RECESS - PROVIDE A 6" X 10" X 22 GA MTL PLATE AT DECK FLUTE RECESS THAT IS CONTIGUOUS WITH PARTITION - ATTACH MTL PLATE TO DECK WITH POWDER DRIVEN FASTENERS AT SAME SPACING REQUIRED FOR PARTITION TOP TRACK

NON-RATED

FLUTED STEEL DECK/CONCRETE FLOOR OR ROOF PARALLEL TO FLUTES

3/4"

3/4"

3/4" 3/

4"

3/4"

1"

4 1/

8"

NON-RATED OR SMOKE RESISTANT

FLUTED STEEL DECK/CONCRETE FLOOR OR ROOF PARALLEL TO FLUTES

CONT 2" WIDE X 22 GA MTL STRAP FOR TOP ATTACHMENT OF GYP BD

CONT 20 GA MIN 3" DEEP LEG DEFLECTION TRACK ATTACH TO DECK AT 12" OC MAX

DO NOT ATTACH GYP BD OR STUDS TO DEFLECTION TRACK IN THIS AREA

SEAL ONE SIDE OF PARTITION AGAINST PASSAGE OF SMOKE

WHEN PARTITION IS ALIGNED AT DECK FLUTE RECESS - PROVIDE A 6" X 10" X 22 GA MTL PLATE AT DECK FLUTE RECESS THAT IS CONTIGUOUS WITH PARTITION - ATTACH MTL PLATE TO DECK WITH POWDER DRIVEN FASTENERS AT SAME SPACING REQUIRED FOR PARTITION TOP TRACK

1"

1"

4 1/

8"

ONE HOUR FIRE RESISTANT AND ONE HOUR

FIRE RESISTANT SMOKE BARRIER

UL-HW-D-0107

FLUTED STEEL DECK/CONCRETE FLOOR OR ROOF PARALLEL TO FLUTES

DO NOT ATTACH GYP BD OR STUDS TO DEFLECTION TRACK IN THIS AREA

SPRAY APPLIED FIRESTOP MATERIAL EACH SIDE - MIN 1/2" OVERLAP AT GYP BD AND DECK

CONT 2" WIDE X 22 GA MTL STRAP -ATTACH GYP BD TO STRAP AT 8" OC MAX

FILL GAP BETWEEN SLAB AND TOP OF WALL WITH MINERAL WOOL INSULATION

CONT 22 GA MIN 3" DEEP LEG DEFLECTION TRACK ATTACH TO DECK AT 12" OC MAX 1

1/2"

4"

1"

1"

4 1/

8"

1 1/

2"

SPRAY APPLIED FIRESTOP MATERIAL EACH SIDE - MIN 1/2" OVERLAP AT GYP BD AND DECK CONT 2" WIDE X 22 GA MTL STRAP -ATTACH GYP BD TO STRAP AT 8" OC MAX

DO NOT ATTACH GYP BD OR STUDS TO DEFLECTION TRACK IN THIS AREA

CONT 20 GA MIN 3" DEEP LEG DEFLECTION TRACK ATTACH TO DECK AT 12" OC MAXFILL DECK FLUTE RECESS WITH MINERAL WOOL INSULATION

ONE HOUR FIRE RESISTANT AND ONE HOUR

FIRE RESISTANT SMOKE BARRIER

UL-HW-D-0107

FLUTED STEEL DECK/CONCRETE FLOOR OR ROOF PERPENDICULAR OR DIAGONAL TO

FLUTES

1"

1"

4 1/

4"

1 1/

2"

FILL GAP BETWEEN SLAB AND TOP OF WALL WITH MINERAL WOOL INSULATION

SPRAY APPLIED FIRESTOP MATERIAL EACH SIDE - MIN 1/2" OVERLAP AT GYP BD AND DECK

CONT 2" WIDE X 22 GA MTL STRAP -ATTACH GYP BD TO STRAP AT 8" OC MAX

DO NOT ATTACH GYP BD OR STUDS TO DEFLECTION TRACK IN THIS AREA

CONT 20 GA MIN 3" DEEP LEG DEFLECTION TRACK ATTACH TO DECK AT 12" OC MAX

ONE HOUR FIRE RESISTANT AND ONE

HOUR FIRE RESISTANT SMOKE BARRIER

UL-HW-D-0108

CONCRETE FLOOR OR ROOF SLAB

1"

1"1"

4 3/

8"

CONT 2" WIDE X 22 GA MTL STRAP -ATTACH GYP BD TO STRAP AT 8" OC MAX

DO NOT ATTACH GYP BD OR STUDS TO DEFLECTION TRACK IN THIS AREA

CONT 20 GA MIN 3" DEEP LEG DEFLECTION TRACK ATTACH TO Z CLIP AT 16" OC MAX

CONT 20 GA FORMED Z CLIP WITH 2" LEGS -ATTACH TO BEAM AT 16" OC MAX

SPRAYED FIRE RESISTIVE MATERIAL

SPRAY APPLIED FIRESTOP MATERIAL EACH SIDE - MIN 1/2" OVERLAP AT GYP BD AND DECK

FILL GAP BETWEEN SPRAYED FIRE RESISTIVE MATERIAL AND TOP OF WALL WITH MINERAL WOOL INSULATION

FILL FLUTES ABOVE BEAMS WITH SPRAYED FIRE RESISTIVE MATERIAL

ONE HOUR FIRE RESISTANT AND ONE HOUR

FIRE RESISTANT SMOKE BARRIER

UL-HW-D-0267

FLUTED STEEL DECK/CONCRETE FLOOR OR ROOF PERPENDICULAR OR DIAGONAL TO

FLUTES

PARTITION HEAD DETAILS

NOTE:REFER TO UL LISTING FOR COMPLETE ASSEMBLY REQUIREMENTS

NOTE:REFER TO UL LISTING FOR COMPLETE ASSEMBLY REQUIREMENTS

NOTE:REFER TO UL LISTING FOR COMPLETE ASSEMBLY REQUIREMENTS

NOTE:REFER TO UL LISTING FOR COMPLETE ASSEMBLY REQUIREMENTS

3/4"

3/4"

3/4"

.

MINERAL WOOL INSULATION

3/4"

3/4"

3/4"

CONT 20 GA GALV MTL STRAP ACROSS MTL DECK FLUTES

3/4"

22 GA MIN MTL TRACK AT FLOOR

DOUBLE 18 GA MTL STUDS AT BOTH JAMBS

2 1/2" X 2 1/2" 20 GA MTL STRAP AT 2'-0" OC WITH 4 SCREWS (2 INTO EACH STUD EA SIDE)

FRAME ANCHORS

3"

18 GA "KING" STUD WITH 3" FLANGES

3" = 1'-0"01DOUBLE DOOR/LARGE

OPENING HEADER3" = 1'-0"02DOOR

OPENING HEADER3" = 1'-0"03 OPENING HEADER

3" = 1'-0"04LARGE

OPENING JAMB STUDS3" = 1'-0"05B

OPTION 2

DOOR OPENING

JAMB STUDS3" = 1'-0"05A

OPTION 1

DOOR OPENING

JAMB STUDS

HKS ARCHITECTS, INC.

SALT LAKE CITY, UTAH 84101

ARCHITECT

90 SOUTH 400 WEST, SUITE 110

REVISION

PROJECT NUMBERS

DATE

SHEET TITLE

PLO

T D

AT

E:

INTERMOUNTAIN HEALTHCARE

SALT LAKE CITY, UTAH 84111

OWNER

36 SOUTH STATE STREET

ISSUE

© 2016 HKS, INC.

IN

TE

RM

OU

NT

AIN

LA

YT

ON

PA

RK

WA

Y C

LIN

IC

PC

H A

UD

IO

LO

GY

RE

MO

DE

L 2

01

8

SHEET NO.

HKS:

20

1 W

ES

T L

AY

TO

N P

AR

KW

AY

L

AY

TO

N, U

T 8

40

41

VAN BOERUM & FRANK ASSOCIATES, INC.MECHANICAL & PLUMBING ENGINEER

330 SOUTH 300 EAST SALT LAKE CITY, UT 84111

SPECTRUM ENGINEERS

SALT LAKE CITY, UTAH 84111

ELECTRICAL ENGINEER

324 S. STATE ST. STE. 400

12/1

0/20

18 7

:34:

41 A

M

A3.02

PARTITION HEAD AND

FRAMING DETAILS

11/07/2018

22506.000

CONSTRUCTION

DOCUMENTS

PCH TI

NO. DESCRIPTION DATE

2" 5/8"

PA

RTN

SC

HE

D1/

2"

1 15

/16”

1 15

/16”

VA

RIE

S

APPLIED STOP AT GLAZING

TYPICAL -

HOLLOW METAL

1

DOUBLE

EGRESS

2

CASE OPENING

3

MUNTIN

4

BORROWED LITE

5

2 5/8"

PA

RTN

SC

HE

D1/

2"

1 3/8" 5/8"5/8"

EQ

EQ

1 15

/16”

PA

RTN

SC

HE

D1/

2" 2" 2" 1/2"

APPLIED STOP AT GLAZING

2" 5/8"

PA

RTN

SC

HE

D1/

2"

APPLIED STOP AT GLAZING

TYPICAL -

ALUMINUM

6

1 1/2"

1/4"

PA

RTN

SC

HE

D

DOOR LEGEND

DOOR NOTES

1. CONTRACTORS TO USE THE ARCHITECT'S FLOOR PLAN DESIGNATION DOOR NUMBER IN ADDITION TO THE ROOM NUMBER ON ALL SHOP DRAWING SCHEDULE SUBMITTALS.

DOOR TYPESVISION PANELS, LOUVER TYPES, AND ACCESSORIES

DOOR AND BORROWED LITE FRAME TYPES SCALE: 1" = 1' -0"

DOOR PLAN DESIGNATION

SUFFIX FOR MULTIPLE DOORS AT A ROOM

DOOR NUMBER SAME AS ROOM NUMBER

4" MIN6" PREFERRED OPENING MIN CLEAR

1' - 6" (PULL SIDE)

CLOSER AND LATCH

1' - 0" (PUSH SIDE) MINCLEAR IF DOOR HAS

DOOR OPENING LOCATION

A. DOORS SHOWN ADJACENT TO A FLANKING WALL OR OTHER FIXED OBSTRUCTION, SHALL BE LOCATED AS SHOWN ABOVE.

B. OTHER LOCATIONS SHALL BE ON CENTERLINE OF ROOM OR AS SPECIFICALLY DIMENSIONED.

DOOR FIRE RATING101X

90

HOLD OPEN DEVICE

VISION PANEL OR LOUVER ACCESSORY

POWER OPERATOR

DOOR LEGEND

DOOR NOTES

1. CONTRACTORS TO USE THE ARCHITECT'S FLOOR PLAN DESIGNATION DOOR NUMBER IN ADDITION TO THE ROOM NUMBER ON ALL SHOP DRAWING SCHEDULE SUBMITTALS.

CONTROL JOINT AT DOOR FRAMES

SINGLE DOORS

ALIGN WITH EDGE OF DOOR FRAME CORNER ON HINGE SIDE

DOUBLE DOORS

ALIGN WITH EDGE OF DOOR FRAME CORNER

1

RATED60/90

100 SQ IN MAX

6" 3"

33”

MA

X42

2

NON-RATED OR

RATED 20/45 MIN

MIN6"

X

MIN6"

42”

Y

3

RATED20/45 MIN

X

MA

X42

”Y

1296 SQ IN MAX

6" 6"

ACCESSORIES

4

NON-RATED

10"

6" 6"

6"

SINGLE DOORS

4' X 8' GYP BD PANEL CONFIGURATION

DOUBLE DOORS

GYPSUM BD CONFIGURATION AT DOORS

BOTTOM OF STRUCTURE

4' X 8' GYP BD PANEL CONFIGURATION

BOTTOM OF STRUCTURE

VA

RIE

S

VA

RIE

S

VA

RIE

S

EXTEND CJ TO BOTTOM OF STRUCTURE AT RATED WALLS 4" ABOVE CEILINGS AT NON-RATED WALLS

CASED OPENING

ALIGN WITH EDGE OF CASED OPENING

ARMOR PLATE

KICK PLATE

KICK/ARMOR PLATE LEGEND:K: KICK PLATEA: ARMOUR PLATE1. DOOR PUSH SIDE2. DOOR PULL SIDE3. BOTH SIDES

EXAMPLE: K1 = PUSH SIDE KICK PLATE

EXTEND CJ TO BOTTOM OF STRUCTURE AT RATED WALLS 4" ABOVE CEILINGS AT NON-RATED WALLS

EXTEND CJ TO BOTTOM OF STRUCTURE AT RATED WALLS 4" ABOVE CEILINGS AT NON-RATED WALLS

A1FLUSHSINGLE

C1

ALUMINUMSINGLE

10"

INTERIOR ALUMINUM STOREFRONT DOOR / GLAZING

6' - 0" R.O.

8' -

0" R

.0.

3' - 0"

4-1/2" ALUMINUMSTOREFRONT SYSTEM -MATCH ADJACENT DOOR / GLASS SYSTEM

ALL PANES SHALL BETEMPERED GLASS

DASHED FRAMING FOR PAIR (DOUBLE) OF DOORS - REF FRAMING DETAILS A3.02 FOR TRACK AND STUD NOTES

GYP BOARD

HOLLOW METAL FRAME

GENERAL NOTES

REFERENCE FRAMING DETAILS SHEETS A3.02 FOR TRACK AND STUDS NOTES.

SEALANT AT PERIMETER OF FRAME TO MATCH FRAME PAINT COLOR

REF FRAMING DETAILS A3.02 FOR TRACK AND STUD NOTES

GYP BOARD

HOLLOW METAL FRAME

SEALANT AT PERIMETER OF FRAME TO MATCH FRAME PAINT COLOR

ALUMINUM FRAME

GYP BOARDSEALANT AT PERIMETER OF FRAME TO MATCH FRAME PAINT COLOR

ALUMINUM FRAME

GYP BOARD

SEALANT AT PERIMETER OF FRAME TO MATCH FRAME PAINT COLOR

WALL CONSTRUCTION -SEE PLAN

HKS ARCHITECTS, INC.

SALT LAKE CITY, UTAH 84101

ARCHITECT

90 SOUTH 400 WEST, SUITE 110

REVISION

PROJECT NUMBERS

DATE

SHEET TITLE

PLO

T D

AT

E:

INTERMOUNTAIN HEALTHCARE

SALT LAKE CITY, UTAH 84111

OWNER

36 SOUTH STATE STREET

ISSUE

© 2016 HKS, INC.

IN

TE

RM

OU

NT

AIN

LA

YT

ON

PA

RK

WA

Y C

LIN

IC

PC

H A

UD

IO

LO

GY

RE

MO

DE

L 2

01

8

SHEET NO.

HKS:

20

1 W

ES

T L

AY

TO

N P

AR

KW

AY

L

AY

TO

N, U

T 8

40

41

VAN BOERUM & FRANK ASSOCIATES, INC.MECHANICAL & PLUMBING ENGINEER

330 SOUTH 300 EAST SALT LAKE CITY, UT 84111

SPECTRUM ENGINEERS

SALT LAKE CITY, UTAH 84111

ELECTRICAL ENGINEER

324 S. STATE ST. STE. 400

12/1

0/20

18 7

:34:

43 A

M

A3.30

DOOR, SAFETY

GLAZING INFORMATION

11/07/2018

22506.000

CONSTRUCTION

DOCUMENTS

PCH TI

3" = 1'-0"01INTERIOR DOOR

HEAD DETAIL - HOLLOW METAL

3" = 1'-0"02INTERIOR DOOR

JAMB DETAIL - HOLLOW METAL

3" = 1'-0"04INTERIOR DOOR

HEAD DETAIL - ALUMINUM

3" = 1'-0"03INTERIOR DOOR

JAMB DETAIL - ALUMINUM

DOOR SCHEDULE LEVELS 3-5 AUDIOLOGY

DO

OR

NU

MB

ER

WID

TH

HE

IGH

T

DO

OR

TY

PE

FRA

ME

TY

PE

MATERIALS AND FINISHES

DO

OR

RA

TIN

G

DETAILS

CO

MM

EN

TS

DO

OR

MA

TER

IAL

FRA

ME

MA

TER

IAL

HE

AD

JAM

B

SIL

L

34227 3' - 0" 7' - 0" A1 1 WD HM - A3.30H/01 A3.30H/02 -34229 3' - 0" 7' - 0" A1 1 WD HM - A3.30H/01 A3.30H/02 -34233 3' - 0" 7' - 0" A1 1 WD HM - A3.30H/01 A3.30H/02 -34235 3' - 0" 7' - 0" A1 1 WD HM - A3.30H/01 A3.30H/02 -34241 3' - 0" 6' - 10" C1 6 AL / GL ALUM - A3.30H/04 A3.30H/03 -

NO. DESCRIPTION DATE

A3.

5002

BASE CABINET OR EQUIPMENT

UPPER CABINET OR EQUIPMENT

FUR DOWN OR FASCIA PANEL

CEILING LINE OF STRUCTURE

TYPE B MOUNTING

TYPE B MOUNTING

20 GA METAL STUDS

TYPE B MOUNTING

NOTE:DO NOT CUT VERTICAL STUD FLANGES

NOTE:REFER TO SHEET A3.02 FOR MOUNTING DETAILS

TYPICAL CABINET DIMENSIONS

NOTE: ALL CABINET DIMENSIONS GIVEN ARE NOMINAL. SCHEDULED CEILING HEIGHT

84"

60"54"48"36"34"

30"

FF

2' - 0"

4"

2' - 0 3/4" 2' - 0"

MIN

2' -

3"

MOUNTING SUPPORT TYPE B TYP

BASE CABINET COUNTERTOP APRON / KNEE SPACE

PLAM - PLASTIC LAMINATE UNOCP - CAST PLASTIC (SOLID SURFACING MATERIAL)ER - EPOXY RESINSS - STAINLESS STEELST - STONE

SS

SCHEDULED CEILING HEIGHT

FF

84"

60"54"48"36"34"

30"2' - 0"

1' - 3"

UPPER CABINET BEYOND

FUR DOWN OR FASCIA PANEL FUR DOWN

OR FASCIA PANEL

MOUNTING SUPPORT TYPE B TYP

1' - 0"

3' -

6"

5"BASE CABINET

WIRE ACCESS SLOT

1' - 0"

3' -

4"

BASE CABINET

WIRE ACCESS SLOT

FULL HEIGHT UPPER CABINET NURSE STATION LABORATORY

CABINET TYPES

UPPER CABINETS

84"

DOOR FRONT

OPEN GLASS FRONT DOORS

GLASS FRONT SLIDING DOORS

OPEN CHART SLOTS

DOOR FRONT WITH SLOTS

FF

BASE CABINETS

FF

FF

F

F F

DOOR(S) WITH DRAWERS

OPEN DOORS DOOR(S) WITH APRON

FILM SLOTS

BOX, BOX,BOX, BOX,DRAWERS

BOX, FILE,FILE DRAWERS

BOX, BOX,FILE DRAWERS

PULL-OUT SINGLE DRAWER

FILE, FILE DRAWERS

DRAWER WITH VERTICAL CHART SLOTS BELOW

DRAWER W/ OPEN SHELF

DRAWER W/ OPEN BELOW

LAT FILE, LAT FILE DRAWERS

FULL HEIGHT CABINETS

FF

FS FS FS

FS

G

G

FS

G

G

G

G

DOOR FRONT

DOUBLE DOOR FRONT

OPEN GLASS FRONT

DOUBLE GLASS FRONT

COAT ROD WITH SHELF

COAT ROD WITH SHELF DOUBLE DOOR

COAT ROD WITH SHELF

COAT ROD WITH SHELF DOUBLE DOOR

DOUBLE BASE UPPER

DOUBLE BASE OPEN UPPER

FIXED SHELVES 48" AFF AT ACCESSIBLE LOCKERS

COAT ROD

FIXED SHELVES AT STANDARD LOCKERS

COAT ROD

F

F

GGGG

UB UC UD UE UF

BB BC BE BF

BG BH BJ BK BL BM BN BP

FBFAFA

BABA BD BD

UAUA

FC FC FHFGFE FE FEA FEA

KEYBOARD STORAGE

PULL-OUT TRASH HOLDER

BQ

1' - 3"

3" MAX1 1/2" MIN

1/8”

SCRIBE TO WALL

FILLER PANEL

LINE OF WALL

DOOR

PLAN - WALL FILLER PANEL AT END WALL

APLAN - END PANEL

BDOOR

FLUSH

END PANEL

1 1/

4”5

1/2”

COUNTERTOP

APRON

36"

OR

34"

AF

F

ARCHITECTURAL CABINET TYPICAL DETAILS

APRON

COUNTERTOP

1 1/

4”1

1/2”

30"

AF

F

1 1/

4”1

1/2”

30"

AF

F

COUNTERTOP

PENCIL DRAWER

SECTIONS - KNEE SPACE / APRON

CPLAN - INSIDE CORNER

FILLER PANELS BETWEEN ADJACENT CABINETS

D

4" MAX2 1/4" MIN

4" M

AX

2 1/

4" M

IN

1/8”

DOOR

DOOR OR DRAWER

FILLER PANEL

1/8”

CABINET PULL

DRAWER FRONT

DOOR

STRETCHER

SECTION - DOOR TO DRAWERDRAWER TO DRAWER SIM

ESECTION - OPEN

CABINET TO DRAWER

F

CABINET PULL

DRAWER FRONT

END PANEL OR CABINET BEYOND

STRETCHER

1 1/

4”1/

8”

CABINET PULL

DOOR

COUNTERTOP

1/8”

1/8”

2 1/

2”

DOOR

VALANCE

CABINET PULL

SECTION -COUNTERTOP WITH

DOOR BELOW

GSECTION - UPPER CABINET WITH DOORS AT VALANCE

H

1/8”

2 3/

8”

SECTION - UPPER CABINET OPEN SHELF

VALANCE

I

END PANEL OR CABINET BEYOND

VALANCE

2 3/

8”

END PANEL

CABINET BOTTOM

SECTION - UPPER CABINET AT EXPOSED

SIDE

J

1/8”

1/8”

DOOR

CABINET PULL

PLAN - CABINET TO CABINET AT DOORS

KPLAN - DOOR TO

DOOR

L

1/8”

DOOR

CABINET PULL

FIN CLG

FASCIA PANEL WITH INTEGRAL SUPPORT

END PANEL

SECTION - UPPER CABINET FASCIA PANEL RETURN

M

1”

2”

FASCIA PANEL WITH INTEGRAL SUPPORT AT 36" OC MAX (MIN 2)

DOOR

GYP BD FUR DOWN

FUR DOWN SECTION AT UPPER CABINET

N

SCRIBE TO BACK WALL

CABINET BOTTOM

LINE OF WALL

SECTION - UPPER CABINET - BOTTOM OF

BACK WALL

O

MIN1”

CABINET COUNTERTOP

LINE OF WALL

PLAN - CASEWORK AT WALL ADJACENT

P

LINE OF BASE CABINET BELOW

R 2"

PLAN - AT OUTSIDE CORNER OF

COUNTERTOPS

Q

END PANEL

SCRIBE TO BACK WALL

END PANEL AT WALL

R

BASE CABINET

COUNTERTOP

COUNTERTOP EXTENSION AT END OF BASE CABINET

S

1/8”

4”

4”

DOOR

EXTEND WALL BASE UNO

FLOOR

SECTION -CABINET DOOR

AT BASE

T

EQUIP

END PANEL

SECTION - END CAP

U

FIN CLG

FASCIA PANEL WITH INTEGRAL SUPPORT AT 36" OC MAX (MIN 2)

DOOR

UPPER CABINET FASCIA PANEL CLOSURE

V

END PANEL

SECTION - END CAP

W

END PANEL

LINE OF BACK WALL

SCRIBE TO WALL

PLAN - END PANEL AT BACK WALL

X

PLAN

SECTION

3”

PLAN

4”

COUNTERTOP SUPPORT BRACKET. PAINT TO MATCH WALL COLOR

MOUNTING SUPPORT TYPEPAINT TO MATCH WALL COLOR

B

3/4" PLAM COVERED BACKING

SECTION - COUNTERTOP SUPPORT BRACKET AT KNEE SPACE

2”

2”

EQ EQ

2”

EQ

EQ

2”

UPPER CABINET DOOR

DRAWER

BASE CABINET

CABINET PULL LOCATIONS

2 1/2” 2" 1"

2 1/

2”

2 1/

2”

WIRE ACCESS GROMMET

COMPUTER PAPER SLOT GROMMET

LINE OF CABINET BELOW COUNTERTOP

PLAN - COMPUTER CUT OUT

6”

2”

1/8”

LOCK

CLEAR MUTE

2”

CLEAR MUTE

CLEAR MUTE

CLEAR MUTE

3/8”

PLAM TO MATCH CAB

3/8”

PLAM TO MATCH CAB

CABINET LEGEND

CABINET ELEVATION LEGENDSCHEDULED CLG HEIGHT

84"

60"

54"

48"

36"

34"

30"

FF

AL

KG G

P

A

K

L L

K

N V

B

36

36

30

I O H

T

BU

U

C C F

R

E

AS

EQUIP

KS

36a

36 18 18 30

SS

M

X

J

X

S

FUR DOWN OR FASCIA PANEL

ADJUSTABLE SHELF INDICATION

COUNTERTOP DESIGNATION IF OTHER THAN PLASTIC LAMINATE

CABINET ELEVATION ABBREVIATION

CABINET WIDTH AND ACCESSORY

VIEW ICON INDICATES ORIENTATION OF VIEW ON PLAN

ROOM NAMEROOM NUMBER

ACCESSORY LEGEND (LOWER CASE LETTERS ONLY)

a - DRAWER / CABINET LOCKb - WASTE CHUTE - 8" DIA HOLE IN COUNTERTOPc - SLIDING WRITING SHELFd - GROMMETe - P-LAM CLAD PANEL, INSERT TO MATCH CABINET DOOR / DRAWERS

ELEVATION ABBREVIATION LEGEND

AS - ACCESSIBLE SINKF - FILE DRAWERFS - FIXED SHELFKB - KEYBOARD DRAWERKS - KNEE SPACEG - GLASS FRONTTL - TASK LIGHTING

CABINET ELEVATION LEGEND SCHEDULED CLG HEIGHT

84"

60"

54"

48"

36"

34"

30"

FF

KS

ROOM NAMEROOM NUMBER

A

A

P

K

L

N V

B

H O I

G

C

K

L

B W

Q

TFUR DOWN OR FASCIA PANEL

ADJUSTABLE SHELF INDICATION

CABINET ELEVATION ABBREVIATION

VIEW ICON INDICATES ORIENTATION OF VIEW ON PLAN

CABINET ELEVATION LEGEND SCHEDULED CLG HEIGHT

84"

60"

54"

48"

36"

34"

30"

FF

ROOM NAMEROOM NUMBER

SS C E

R B D

AS

COUNTERTOP DESIGNATION IF OTHER THAN PLASTIC LAMINATE

CABINET ELEVATION ABBREVIATION

VIEW ICON INDICATES ORIENTATION OF VIEW ON PLANCABINET GENERAL

NOTES1. CABINET WIDTHS TO BE BASED ON MODULE INCREMENTS OF 3" UNO.

2. PROVIDE FILLER PANELS TO FINISH OUT TO SCRIBE CABINETS TO WALL.

3. PROVIDE FILLER PANELS AND TRIM WHERE EQUIPMENT IS LOCATED WITHIN CABINETS.

4. PROVIDE FINISHED END PANELS END RETURNS AT OPEN ENDED CABINETS, KNEE SPACES, AND ACCESSIBLE SINKS.

5. PROVIDE 1 1/2" THICK FINISHED END PANEL AT FREE STANDING END OF ACCESSIBLE SINKS AND KNEE SPACES.

6. WHEN FILLER PANELS ARE REQUIRED AT BOTH ENDS OF CASEWORK TERMINATION, BOTH FILLER PANELS SHALL BE EQUAL WIDTH.

7. PROVIDE WALL BRACKET SUPPORTS AT 36" OC MAX TO SUPPORT COUNTERTOP AT CONTINUOUS KNEE SPACE.

8. PROVIDE END SPLASH WHEN COUNTERTOP IS ADJACENT TO WALL AT SIDES.

9. PROVIDE HOLES FOR GROMMETS IN COUNTERTOPS AND AT THE FOLLOWING LOCATIONS: - 1 EACH WIRE ACCESS HOLE WITH GROMMET AT KNEE SPACE. - WIRE ACCESS HOLES WITH GROMMETS AT 38" OC FOR CONTINUOUS RUNS OF KNEE SPACE. - 1 WIRE ACCESS GROMMET BEHIND EACH KEYBOARD DRAWER. - 1 COMPUTER PAPER SLOT GROMMET BEHIND EACH PRINTER.

10. PROVIDE ADJUSTABLE SHELVES IN CABINETS AT THE FOLLOWING LOCATIONS UNO ON ELEVATIONS: - BASE CABINET - 1 SHELF - FULL HEIGHT CABINET - 5 SHELVES, 1 FIXED. - WALL CABINET - 1 SHELF AT 24" HIGH, 2 SHELVES AT TALLER CABINETS NOTE: SHELVES TO BE 3/4" THICK FOR SPANS UP TO 32" AND 1" THICK FOR SPANS UP TO 36".

11. GLASS FRONTS TO BE 1/4" THICK CLEAR TEMPERED GLASS UNO.

12. PROVIDE AN APRON AT ALL KNEE SPACES 30" OR HIGHER UNO.

13. VERTICAL SURFACES TO BE PLASTIC LAMINATE (PL01) UNO. HORIZONTAL SURFACES TO BE SOLID SURFACE (SSF01) UNO.

14. FILLER PANEL FINISHED WITH WOOD GRAIN LAMINATE SHALL HAVE THEIR GRAIN RUNNING IN THE SAME DIRECTION AS THE CABINET.

FASCIA PANEL JOINTS8'-0" MAX BETWEEN

TASK LIGHTING

ALIGN FASCIA PANEL JOINTS WITH WALL CABINET JOINTS

FF

30"

34"36"48"54"60"

84"

SCHEDULED CEILING HEIGHT

FF

30"

34"36"48"54"60"

84"

SCHEDULED CEILING HEIGHT

EXAM 2 OPPOSITE

J1

A2

SOLID SURFACECOUNTERTOP /SPLASH

FILLER PANEL

FILLER PANEL

FILLERPANELS

27" 27" 27" 30" 30"

30"27"27"27"

3' -

9"

2' - 0" 2' - 10" 3' - 0"

3' -

0"

30"

AS

FILLERPANELS

30" 27"

24" DEEP CABINETS

FILLERPANELS

A2

J1FILLERPANELS

18" 36" 36" 36"

36"36"33"

3' -

9"

1' - 10" 3' - 0" 3' - 0"

3' -

0"

36"

AS

FILLERPANELS

5' -

0"

33" 33"

FILLERPANEL

SOLID SURFACECOUNTERTOP

DESK(FURNITURE)

18" 18" 18" 18"

24" DEEP CABINETS,TYP

NTS02TYPICAL STUD WALL SUPPORTING

EQUIPMENT AND CABINETRY

HKS ARCHITECTS, INC.

SALT LAKE CITY, UTAH 84101

ARCHITECT

90 SOUTH 400 WEST, SUITE 110

REVISION

PROJECT NUMBERS

DATE

SHEET TITLE

PLO

T D

AT

E:

INTERMOUNTAIN HEALTHCARE

SALT LAKE CITY, UTAH 84111

OWNER

36 SOUTH STATE STREET

ISSUE

© 2016 HKS, INC.

IN

TE

RM

OU

NT

AIN

LA

YT

ON

PA

RK

WA

Y C

LIN

IC

PC

H A

UD

IO

LO

GY

RE

MO

DE

L 2

01

8

SHEET NO.

HKS:

20

1 W

ES

T L

AY

TO

N P

AR

KW

AY

L

AY

TO

N, U

T 8

40

41

VAN BOERUM & FRANK ASSOCIATES, INC.MECHANICAL & PLUMBING ENGINEER

330 SOUTH 300 EAST SALT LAKE CITY, UT 84111

SPECTRUM ENGINEERS

SALT LAKE CITY, UTAH 84111

ELECTRICAL ENGINEER

324 S. STATE ST. STE. 400

12/1

0/20

18 7

:34:

45 A

M

A3.50H

INTERIOR ELEVATIONS

/ CABINET DETAILS

12/10/2018

22506.000

CONSTRUCTION

DOCUMENTS

PCH TI

1/4" = 1'-0"3 AUDIOLOGY EXAM

1/4" = 1'-0"4 AUDIOLOGY HALL1/4" = 1'-0"5 AUDIOLOGY LAB SOUTH

1/4" = 1'-0"6 AUDIOLOGY LAB EAST

1/4" = 1'-0"7 AUDIOLOGY OFFICE SOUTH

PLASTIC LAMINATE VERTICAL SURFACE:PL08 TYPICAL

NO. DESCRIPTION DATE

VAV BOX SCHEDULEAIR FLUID (2)

COOLING HEATING LEAVING TOTAL

MANUFACTURER INLET MAXIMUM MAXIMUM MINIMUM AIR TEMP. NC LEVEL HEAT FLUID

AND AREA SIZE AIR AIR AIR DB @ 2" S.P. LOAD FLOW WORKING

ID MODEL NUMBER SERVED (IN) (CFM) (CFM) (CFM) (DEG. F) AIR RAD (MBH) (GPM) FLUID REMARKS

LEVEL 3

VR-B3-43 PRICE SDV AUDIOLOGY BOOTHS 6 225 225 225 80 18 15 5.8 0.5 WATER (1)(2)(3)(4)

VR-B3-44 PRICE SDV EXAM ROOMS 6 220 220 220 80 19 18 5.7 0.5 WATER (1)(2)(3)(4)

VR-B3-45 PRICE SDV LAB 8 415 205 205 80 24 22 5.3 0.5 WATER (1)(2)(3)(4)

VR-B3-46 PRICE SDV SHELL SPACE 8 450 135 135 80 25 22 3.5 0.5 WATER (1)(2)(3)(4)

(1) ENTERING AIR AT 52 DEG. F. @ 4,300 FEET ELEVATION.

(2) GPM BASED ON 130 DEG. F. ENTERING WATER TEMPERATURE; 100 DEG. F. LEAVING WATER TEMPERATURE.

(3) COIL MAXIMUM WATER P.D. AT 5.0 FT HD; MAXIMUM BOX AIR P.D. IS 0.40 IN. W.G.

(4) PRESSURE INDEPENDENT TYPE BOX.

PLUMBING FIXTURE SCHEDULECW HW W V

ID FIXTURE (IN) (IN) (IN) (IN) NOTES

S-1 WORK SINK 1/2 1/2 2 1 1/2

SINK (BASIN INTEGRAL TO COUNTERTOP): CHICAGO 786-GN8FCXKABCP FAUCET, WITH WRIST BLADE HANDLES, GN8FC RIGID/SWING GOOSENECK SPOUT WITH 1.5 GPM LAMINAR FLOW CONTROL IN SPOUT. WATTSLFUSG-B-M2 THERMOSTATIC MIXING VALVE WITH WATTS # 7 DUAL CHECK VALVES ON HOT AND COLD LINES INSTALLED IN CEILING. FLEXIBLE STAINLESS STEEL SUPPLIES WITH WITH LOOSE KEY ANGLE STOPS.; FLEXIBLESTAINLESS STEEL SUPPLIES WITH LOOSE KEY ANGLE STOPS; CHICAGO 327-XCP OPEN-GRID STRAINER AND CAST BRASS P-TRAP WITH CLEAN OUT PLUG. PROVIDE ADA COMPLIANT UNDER COUNTER PIPING WRAP BYTRUE-BRO, COLOR TO BE WHITE.

S-2 2-COMP SINK 1/2 1/2 1 1/2 1 1/2

SINK (STAINLESS STEEL, COUNTER MOUNTED, DOUBLE COMPARTMENT): ELKAY LR4322 18 GA. TYPE 304 STAINLESS STEEL SINK, 33"X22"X6-1/2" DEEP, CHICAGO 786-GN8FCABCP FAUCET, WITH WRIST BLADE HANDLES,RIGID/SWING GOOSENECK SPOUT WITH 1.5 GPM LAMINAR FLOW CONTROL IN SPOUT. WATTS LFUSG-B-M2 THERMOSTATIC MIXING VALVE WITH ZURN MODEL SXL STRAINERS AND ZURN MODEL 40XL2 CHECK VALVES ONHOT AND COLD LINES INSTALLED IN CEILING. FLEXIBLE STAINLESS STEEL SUPPLIES WITH WITH LOOSE KEY ANGLE STOPS.; FLEXIBLE STAINLESS STEEL SUPPLIES WITH LOOSE KEY ANGLE STOPS; CHICAGO 327-XCPOPEN-GRID STRAINER AND CAST BRASS P-TRAP WITH CLEAN OUT PLUG. PROVIDE ADA COMPLIANT UNDER COUNTER PIPING WRAP BY TRUE-BRO, COLOR TO BE WHITE.

GRILLES, REGISTERS AND DIFFUSERSMAX MAX

ID MANUFACTURER MODEL SIZE CFM NC DESCRIPTION

6'' DIA 110 SQUARE PLAQUE CEILING DIFFUSERS. REMOVABLE FACE & CORE

8'' DIA 235 FRAME SHALL BE FOR SURFACE OR LAY-IN MOUNTING AS REQUIRED

CD-1 EH PRICE SPD 10'' DIA 420 30 BY CEILING TYPE. LAY-IN FRAMES SHALL BE 24" x 24", 24" x 12"

12'' DIA 600 OR 12" x 12" AS REQUIRED TO FIT CEILING TILE SPACE AVAILABLE.

14'' DIA 800 PROVIDE ROUND NECK ADAPTER. COLOR TO BE SELECTED BY ARCHITECT.

15'' DIA 850

6'' DIA 100 PERFORATED FACE RETURN AIR GRILLE, REMOVABLE FACE & CORE.

8'' DIA 210 FRAME SHALL BE FOR SURFACE OR LAY-IN MOUNTING AS REQUIRED

RG-1 / EG-1 EH PRICE PDDR 10'' DIA 380 30 BY CEILING TYPE. LAY-IN FRAMES SHALL BE 24" x 24", 24" x 12" OR

12'' DIA 600 12" x 12" AS REQUIRED TO FIT CEILING TILE SPACE AVAILABLE. AIR

14'' DIA 750 QUANTITY SHALL MATCH ROOM SUPPLY OR EXHAUST AIR QUANTITY.

15'' DIA 1000 PROVIDE ROUND NECK ADAPTER. COLOR TO BE SELECTED BY ARCHITECT.

LAVATORY MIXING VALVE DETAIL

NO SCALE

HWS

HWR

HIGH EFFICIENCY TAKE-OFF DETAIL

NO SCALE

CABLE BRACING FOR ROUND AND OVAL DUCTS

VARIABLE VOLUME BOX DETAIL

NO SCALE

DIFFUSER CONNECTION DETAIL

NO SCALE

VAV/CV BOX PIPING DETAIL WITH 2-WAY AUTO-VALVE

NO SCALE

FIRE DAMPER & FIRE/SMOKE DAMPER DETAILS

NO SCALE

BRANCH DUCT TAKE-OFF & DAMPER

NO SCALENO SCALE

RECTANGULAR DUCT

AIR FLOW

45°

FLEX DUCT

VOLUME DAMPER

RECTANGLE TO

ROUND TRANSITION

SEE CONNECTION SCHEDULE AND DETAILS

CABLE-SEE DETAIL, BRACING ANDCONNECTION SCHEDULES FOR SIZEOF ANGLE, BOLT AND CABLE.

DUCT HANGER ASRECOMMENDEDBY SMACNA

1 1/2" X12 GA. SHEETMETAL HANGER STRAP

2 1/2" X 12 GA. SHEETMETAL RESTRAINT STRAP INSULATION WHERE

OCCURS

4545

W

INACCESSIBLEDAMPER ISOPERATOR WHEREREMOTE CEILING

45

L=1/4 W (4" MIN.)NOTE:

L

AIR FLOW

INTERSECTIONSTO ELBOWS ORTHAN TWO DUCT WIDTHSBE INSTALLED CLOSERDAMPERS SHOULD NOTNOTE:

VOLUMEDAMPERPROVIDECONCEALEDCEILINGDAMPERREGULATOR

AIR F

LOW

MAIN SUPPLY DUCT SEE PLAN FOR SIZE

STRAP HANGERS - SUPPORTFROM STRUCTURE AS REQUIRED

REHEAT COIL

TRANSITION TO RECTANGULAR SHEETMETAL DUCT

BRANCH DUCT TO BE THE SAME SIZE ASBOX INLET UNLESS NOTED OTHERWISE.

VARIABLE VOLUME BOXSEE PLAN FOR SIZE

RECTANGULAR SHEETMETAL DUCT LINED WITH 1"ACOUSTICAL INSULATION 6'-0" MIN. DOWN STREAM OF

VALVE BEFORE FIRST TAKE-OFF. SEE SPECIFICATIONS.

6

M0.01A

7

6

M0.01A

SECURE WIRE

SECURE DIFFUSER

(TYPICAL)

TO STRUCTURE

45°

METAL STRAP4" WIDE SHEET

ABOVE TO STRUCTURE

CEILING DIFFUSER

SPIRAL DUCT

CEILING

5'-0" MAXIMUM LENGTH

ACOUSTICAL FLEX. DUCT

CLAMPING DEVICE (TYP.)

8

M0.01A

SHUT-OFF VALVE (TYP)

UNION (TYP)

FLOW SETTER

STRAINER BLOW DOWN WITH VALVE,HOSE CONNECTION AND CAP. SAMESIZE AS BLOW DOWN

1/2" DRAIN LINE WITH VALVE,HOSE CONNECTION AND CAP

NOTE: CONNECT HWS TO LOWERLEAVING AIR SIDE OF COIL

REHEAT COIL

DROP BRANCH PIPING OFF BOTTOM OF MAINS AT 45 DEGREES

5/8" MANUAL AIR VENT WHERE COILABOVE MAINS

P & T TEST PLUG (TYPICAL)

AUTO 2-WAY VALVE

REDUCER (TYPICAL)

3

M0.01A

FIRE DAMPER

WALL

MOTOR OPERATOR PERMANUFACTURER'S LISTING

FIRE/SMOKEDAMPER

DUCT

SLEEVES, JOINTS AND ANGLES PERMANUFACTURER'S LISTING

FIRE/SMOKETYPE 'A'

TYPE 'B'

WALL

BLADES OUT OFAIR STREAM

FIRE DAMPERS

TYPE 'C'

SLEEVES, JOINTS AND ANGLES PERMANUFACTURER'S LISTING

4

M0.01A

2

M0.01AM0.01A

COLD SUPPLY130° HOT WATER

110° HOT WATER

MIXING VALVE

5

M0.01A

CHECK VALVE (TYP)

STRAINER (TYP)

A

M101

A

M-101

12X12

200

12X12

200

12X12200

22X22200

12X12200

DUCTWORK/GRILLES PIPING PLUMBING

LINETYPES

3-1" SLOTS@ 48" 400

W R

12/12

45° D

FD

FSD

SD

8/8

1.25D

(NAME)

12/8

12ø

12/12 12ø

1.5D

D

12� 12/12

HWR

HWS

E(NAME)

P-1

1

T

EF

1

THERMOSTATIC MIXING VALVE

RISE OR DROP

COTG

FCO

VENT (SEWER)

SEWER (ABOVE GRADE)

SEWER (BELOW GRADE)

NEGATIVE PRESSURE DUCT - RISE

POSITIVE PRESSURE DUCT - DROP

POSITIVE PRESSURE DUCT - RISE

THERMOSTAT

HOSE BIBB

FLOOR DRAIN

FLOOR SINK

BRANCH - TOP CONNECTION

BRANCH - BOTTOM CONNECTION

FIXTURE FROM LEVEL ABOVE

KEYED NOTE IDENTIFICATION

EQUIPMENT IDENTIFICATION

DETAIL TAG - TOP FIGURE IS DETAIL NO. BOTTOM FIGURE IS SHEET NO.

SECTION TAG - TOP FIGURE IS SECTION NO. BOTTOM FIGURE IS SHEET NO.

POINT OF CONNECTION

PLUMBINGFIXTURES

DOMESTIC HOT WATER RETURN

(DHWR)

DOMESTIC HOT WATER (DHW)

DOMESTIC COLD WATER (DCW)

FLOOR CLEAN-OUTOR CLEAN-OUT TOGRADE

BRANCH - SIDE CONNECTION

RISER - UP (ELBOW)

RISER - DOWN (ELBOW)

ARROW INDICATES DIRECTION OF FLOW INPIPE

CALIBRATED BALANCINGVALVE WITH GPM INDICATED

CHECK VALVE

REDUCER EXISTING PIPING

HEATING HOT WATER SUPPLY

HEATING HOT WATER RETURN

TOP FIGURES INDICATENECK SIZE. BOTTOMFIGURE INDICATES CFM.

NEGATIVE PRESSURE DUCT - DROP

ROUND DUCT - RISE

ROUND DUCT - DROP

TURNING VANES

CEILING SUPPLY DIFFUSER

CEILING RETURN REGISTER

CEILING EXHAUST REGISTER,

(BALANCE TO MATCH SUPPLY IF

RETURN CFM IS NOT SHOWN)

CEILING SUPPLY DIFFUSERWITH FLEXIBLE DUCT

CEILING AIR GRILLE WITHFLEXIBLE DUCT

LINEAR DIFFUSER WITH PLENUM AND FLEXIBLE DUCTCONNECTION. NO. OF SLOTS & SIZE OF SLOT ON TOP,ACTIVE LENGTH AND CFM ON BOTTOM

RECTANGULAR DUCT WITH FREE AREADIMENSIONS SHOWN IN INCHES.

ROUND DUCT WITH FREE AREA DIMENSIONSSHOWN IN INCHES.

R/W=1. ROUND DUCT SIMILAR TO RECTANGULAR

RECTANGULAR TO RECTANGULAR OR ROUND TO ROUNDDUCT TRANSFORMATION MAXIMUM 15° INCLUDED ANGLEEXCEPT WHERE SHOWN OTHERWISE.

RECTANGULAR TO ROUND DUCT TRANSFORMATION

TAP ENTRY AREA EQUALS 150% OF BRANCH AREA

HIGH EFFICIENCY FITTING

MANUAL VOLUME DAMPER

FIRE DAMPER IN DUCT, W/ ACCESS PANEL REQD.

COMBINATION FIRE/SMOKE DAMPER W/ ACCESS PANEL

SMOKE DAMPER W/ ACCESS PANEL

SINGLE DUCT AIR TERMINAL BOX VARIABLE OR

CONSTANT VOLUME. MIN. 1-1/2 TERMINAL INLETSIZE STRAIGHT DUCT AT TERMINAL INLET.

LATERAL STRAINER WITH BLOW-OFF VALVE,PROVIDE HOSE END WITH CAP WHERE DISCHARGEIS NOT PIPED TO DRAIN

LEGEND OF MECHANICAL SYMBOLS AND ABBREVIATIONS

SHUT OFF VALVE

BALL VALVE

ATC - 2 WAY VALVE

ATC - 3 WAY VALVE

TEMPERATURE AND PRESSURE

TEST PORT

THERMOMETER WELL

THERMOMETER - TEMP RANGE AS INDICATED

PRESSURE GAUGE WITHSHUT OFF PLUG VALVE

0-1

00 F

UNION

ECCENTRIC REDUCER

PIPE CAP

SHUT OFF PLUG VALVE FOR

FOR USE WITH PRESSURE GAUGE

WATER HAMMER ARRESTOR

CLEAN-OUT

ANNOTATIONS

GPM0.0

OR

OR

OR

OR

OR

OR

OR

OR

OR

LIC

EN

SE

D

PROFESS IONA

L

EN

GIN

EE

R

No. 178893

S

TA

T E O F UTA

H

DONALD K.

BRADSHAW

HKS ARCHITECTS, INC.

SALT LAKE CITY, UTAH 84101

ARCHITECT

90 SOUTH 400 WEST, SUITE 110

REVISION

PROJECT NUMBERS

DATE

SHEET TITLE

PLO

TD

AT

E:

INTERMOUNTAIN HEALTHCARE

SALT LAKE CITY, UTAH 84111

OWNER

36 SOUTH STATE STREET

ISSUE

© 2016 HKS, INC.

IN

TE

RM

OU

NT

AIN

LA

YT

ON

PA

RK

WA

Y C

LIN

IC

PC

H A

UD

IO

LO

GY

CL

IN

IC

2018

SHEET NO.

HKS:

201 W

ES

T L

AY

TO

N P

AR

KW

AY

L

AY

TO

N, U

T 8

4041

CONSTRUCTION

DOCUMENTS

12/5

/2018 1

:58:0

0 P

M

M0.01A

MECHANICAL

SYMBOLS, DETAILS

AND SCHEDULES

12/5/18

18972.000

PCH Audiology

NO. DESCRIPTION DATE

S T

3

4

4.8

5.9

5.7

2.9

RC

8/8

VR

B3-43

6ø75

6ø75

6ø75

1

1

8ø135

6ø100

6ø110

6ø110

8ø180

12/10

8/8

VR

B3-45

VR

B3-44

8ø135

6ø100

8ø180

6ø100

6ø100

8ø170

FD

12/1010/8

VR

B3-46

FD12/10

450 CFM

450CFM

46/2

240/2

2

42/1

870/3

6

46/20

(E)

(E)

(E)

(E)

(E)

10/10

EXAM

OFFICE

EXAM

LAB

CONTROLROOM

EXAMROOM

# KEYED NOTES

1. CONNECT TO AUDIO BOOTH SUPPLY SILENCERWITH 6" DIAMETER FLEXIBLE DUCT AND BALANCETO CFM SHOWN. COORDINATE AIRFLOWREQUIREMENTS AND DUCT CONNECTIONS WITHAPPROVED EQUIPMENT SUBMITTAL.

2. PROVIDE NEW ZONE ISOLATION VALVES INACCESSIBLE LOCATION.

3. VALVE AND CAP FOR FUTURE EXPANSION.

4. CONNECT TO EXISTING 4" WASTE RISER.

5. CONNECT TO EXISTING 4" VENT RISER.

6. PROVIDE FIRE SPRINKLERS IN AUDIOLOGYBOOTHS. COORDINATE WITH THE BOOTHMANUFACTURER AND SHOW ON THE FIRESPRINKLING PLANS.

S T

3

4

4.8

5.9

5.7

2.9

3/4"3/4"

3/4"3/4"

3/4"3/4"

3/4"3/4"

3/4"3/4"VR

B3-45

VR

B3-44

VR

B3-46

VR

B3-43

3/4"3/4"

T

T

T

T

EXAM

OFFICE

EXAM

LAB

CONTROLROOM

EXAMROOM

S T

3

4

5.9

5.7

2.9

RC

S-1S-2

S-1

2"1 1/4"

3/4"

3/4"

3/4"

3/4"

1 1/2"

5

3/4"

3/4"

EXAMOFFICE

EXAM

LAB

CONTROLROOM EXAM

ROOM

3

2

6

S T

3

4

5.9

5.7

2.9

RC

2"

SS

S

4

2"

LIC

EN

SE

D

PROFESS IONA

L

EN

GIN

EE

R

No. 178893

S

TA

T E O F UTA

H

DONALD K.

BRADSHAW

HKS ARCHITECTS, INC.

SALT LAKE CITY, UTAH 84101

ARCHITECT

90 SOUTH 400 WEST, SUITE 110

REVISION

PROJECT NUMBERS

DATE

SHEET TITLE

PLO

TD

AT

E:

INTERMOUNTAIN HEALTHCARE

SALT LAKE CITY, UTAH 84111

OWNER

36 SOUTH STATE STREET

ISSUE

© 2016 HKS, INC.

IN

TE

RM

OU

NT

AIN

LA

YT

ON

PA

RK

WA

Y C

LIN

IC

PC

H A

UD

IO

LO

GY

CL

IN

IC

2018

SHEET NO.

HKS:

201 W

ES

T L

AY

TO

N P

AR

KW

AY

L

AY

TO

N, U

T 8

4041

CONSTRUCTION

DOCUMENTS

12/5

/2018 1

:58:1

6 P

M

M2.34C

MECHANICAL &

PLUMBING PLANS

12/05/18

18972.000

PCH AUDIOLOGY

1/8" = 1'-0"1 MECHANICAL PLAN 1/8" = 1'-0"2 MECHANICAL PIPING PLAN

1/8" = 1'-0"3 LEVEL 3 PLUMBING PLAN 1/8" = 1'-0"4 LEVEL 2 PLUMBING PLAN

NO. DESCRIPTION DATE

SYMBOL LEGENDSYMBOL DESCRIPTION

SYMBOL LEGENDSYMBOL DESCRIPTION

SYMBOL LEGENDSYMBOL DESCRIPTION

SYMBOL LEGENDSYMBOL DESCRIPTION

D

P PANIC DURESS SWITCH.

TV DISTRIBUTION

DC DIRECTIONAL COUPLER.

TERMINATOR, 75 OHM (TV DISTRIBUTION).

SYMBOL LEGENDSYMBOL DESCRIPTION

WAP

GENERAL ELECTRICAL NOTES1. CLARIFICATION METHODS: AT THE TIME OF BIDDING, BIDDERS SHALL

FAMILIARIZE THEMSELVES WITH THE DRAWINGS AND SPECIFICATIONS. ANY

QUESTIONS, MISUNDERSTANDINGS, CONFLICTS, DELETIONS, DISCONTINUED

PRODUCTS, CATALOG NUMBER DISCREPANCIES, DISCREPANCIES BETWEEN

THE EQUIPMENT SUPPLIED AND THE INTENT OR FUNCTION OF THE

EQUIPMENT, ETC, SHALL BE SUBMITTED TO THE ARCHITECT/ENGINEER IN

WRITING FOR CLARIFICATION PRIOR TO ISSUANCE OF THE FINAL ADDENDUM

AND BIDDING OF THE PROJECT. WHERE DISCREPANCIES OR MULTIPLE

INTERPRETATIONS OCCUR, THE MOST STRINGENT (WHICH IS GENERALLY

RECOGNIZED AS THE MOST COSTLY) THAT MEETS THE INTENT OF THE

DOCUMENTS SHALL BE ENFORCED.

2. OWNER FURNISHED ITEMS: THE OWNER WILL FURNISH MATERIAL AND

EQUIPMENT AS INDICATED IN THE CONTRACT DOCUMENTS TO BE

INCORPORATED INTO THE WORK. THESE ITEMS ARE ASSIGNED TO THE

INSTALLER AND COSTS FOR RECEIVING, HANDLING, STORAGE, IF REQUIRED,

AND INSTALLATION ARE INCLUDED IN THE CONTRACT SUM.

A. THE INSTALLER'S RESPONSIBILITIES ARE THE SAME AS IF THE INSTALLER

FURNISHED THE MATERIALS OR EQUIPMENT.

B. THE OWNER WILL ARRANGE AND PAY FOR DELIVERY OF OWNER

FURNISHED ITEMS FREIGHT ON BOARD JOB SITE AND THE INSTALLER

WILL INSPECT DELIVERIES FOR DAMAGE. IF OWNER FURNISHED ITEMS

ARE DAMAGED, DEFECTIVE OR MISSING, DOCUMENT DAMAGED ITEMS

WITH THE TRANSPORT COMPANY AND THE OWNER WILL ARRANGE FOR

REPLACEMENT. THE OWNER WILL ALSO ARRANGE FOR

MANUFACTURER'S FIELD SERVICES, AND THE DELIVERY OF

MANUFACTURER'S WARRANTIES AND BONDS TO THE INSTALLER.

C. THE INSTALLER IS RESPONSIBLE FOR DESIGNATING THE DELIVERY DATES

OF OWNER FURNISHED ITEMS AND FOR RECEIVING, UNLOADING AND

HANDLING OWNER FURNISHED ITEMS AT THE SITE. THE INSTALLER IS

RESPONSIBLE FOR PROTECTING OWNER FURNISHED ITEMS FROM

DAMAGE, INCLUDING DAMAGE FROM EXPOSURE TO THE ELEMENTS, AND

TO REPAIR OR REPLACE ITEMS DAMAGED AS A RESULT OF HIS

OPERATIONS.

3. EXPOSED STRUCTURE AREAS (EXCLUDING MECHANICAL, ELECTRICAL, AND

COMMUNICATION SPACES): INSTALL RACEWAYS BETWEEN DECK AND

STRUCTURE WHEREVER POSSIBLE IN EXPOSED STRUCTURE CEILING AREAS.

ROUTE RACEWAYS IN CONCEALED AREAS WHEREVER POSSIBLE. REFER ALL

CONDITIONS WHERE RACEWAYS MUST BE INSTALLED WHICH CANNOT

COMPLY WITH THESE REQUIREMENTS TO THE ARCHITECT.

4. SUBMITTALS: PROVIDE SUBMITTALS IN THREE RING BINDERS WITH JOB NAME,

SUBCONTRACTOR, AND VOLUME ON THE BINDING. PREPARE TABS FOR EACH

SPECIFICATION SECTION REQUIRING SUBMITTALS. PREPARE INDEX OF

EQUIPMENT SUBMITTED IN EACH TAB.

5. REFLECTED CEILING PLANS: COORDINATE THE LOCATION OF LIGHT FIXTURES

WITH THE ARCHITECTURAL REFLECTED CEILING PLANS. REFER ALL

DISCREPANCIES TO THE ARCHITECT AND ENGINEER.

CONTRACT LIMIT LINE: DASHDOT, WIDE LINE.

PROPERTY LINE: DASHED, WIDE LINE.

DEMOLITION LINE: DASHED, MEDIUM LINE.

EXISTING TO REMAIN LINE: THIN LINE.

HIDDEN FEATURES LINE: HIDDEN, THIN LINE.

NEW LINE: MEDIUM LINE.

MATCH LINE INDICATOR: CENTER, EXTRA WIDE LINE.

BREAK, ROUND.

BREAK, STRAIGHT: TO BREAK PARTS OF DRAWING.

EQUIPMENT INDICATOR.

REVISION INDICATOR.

KEYNOTE INDICATOR.

ROOM OR SPACE NUMBER.

ELEVATION OR SECTION INDICATOR, INTERIOR: A5INDICATES ELEVATION OR SECTION NUMBER, E-201INDICATES DRAWING SHEET WHERE ELEVATION OR SECTIONIS SHOWN.

ELEVATION OR SECTION INDICATOR, EXTERIOR: A5INDICATES ELEVATION OR SECTION NUMBER, E-201INDICATES DRAWING SHEET WHERE ELEVATION OR SECTIONIS SHOWN.

DETAIL INDICATOR: A5 INDICATES DETAIL NUMBER, E-501INDICATES DRAWING SHEET WHERE DETAIL IS SHOWN.

REFERENCE AND LINE SYMBOLS

MATCH LINE

SEE XX/X-XXX

CU-1

1

1

100

A5

E-201

A5

E-201

A5

E-501

LADDER RACK.

JUNCTION BOX, CEILING.C

EARTH GROUND (ONE-LINE DIAGRAM).

WIREWAY.

PULL BOX.

DUCT CELL FLOOR HEADER.

JUNCTION BOX, DUCT, UNDERFLOOR. TRIPLE, DOUBLE ORSINGLE DUCT SYSTEM AS INDICATED BY THE NUMBER OFPARALLEL LINES. DESIGNATIONS AS SHOWN FOR WIRINGAND/OR RACEWAY SYMBOLS.

JUNCTION BOX, SYSTEMS FURNITURE POWER CONNECTION.SP

JUNCTION BOX, SYSTEMS FURNITURE COMMUNICATION CONNECTION.SC

JUNCTION BOX.

CONDUCTOR RUN IDENTIFICATION.

CONDUCTOR & CONDUIT ("CC") SCHEDULE INDICATOR.REFER TO ONE-LINE DIAGRAM.

CONDUIT STUB. DIMENSION RECORD DRAWINGS AND MARK.

LOW VOLTAGE WIRING: DIVIDE, MEDIUM LINE.

FLEXIBLE WIRING.

WIRING TURNED DOWN OR AWAY FROM OBSERVER.

WIRING TURNED UP OR TOWARDS OBSERVER.

WIRING.

WIRING METHODS

J

W W

PB

J

J

J

1

1

WIRING AND/OR RACEWAY: THIN LINE. WHERE "X" = :

CATV = CABLE TELEVISIONCCTV = CLOSED CIRCUIT TELEVISION

FA = FIRE ALARMFO = FIBER OPTICSI = INTERCOM

OTHERS AS NOTED IN OTHER SCHEDULES. RACEWAYS AND

WIRING SHALL BE SIZED AS SHOWN AND/OR SPECIFIED.

X

NC = NURSE CALL P = POWERRC = RIGID CONDUITS = SOUNDT = TELEPHONE

TV = TELEVISION

FEEDER HOMERUN: REFER TO ONE-LINE DIAGRAMS ANDEQUIPMENT SCHEDULE FOR CONDUIT AND CONDUCTORREQUIREMENTS. ARROWS DO NOT NECESSARILY INDICATE THEQUANTITY OF CONDUCTORS.

ADP-1

BRANCH CIRCUIT HOME RUN TO PANELBOARD: NUMBEROF ARROWS INDICATES NUMBER OF CIRCUITS. LETTERAND NUMBER NOTATIONS IDENTIFY PANEL AND CIRCUITNUMBERS. USE #12 CONDUCTORS, EXCEPT #10CONDUCTORS SHALL BE INSTALLED IF DISTANCES EXCEEDTHOSE SPECIFIED IN THE ELECTRICAL SPECIFICATIONS.

A-1,3,5

WIRING DEVICES

RECEPTACLE, DUPLEX, WEATHERPROOF: NEMA 5-20R.WP

RECEPTACLE, DUPLEX WITH GROUND FAULT CIRCUITINTERRUPTER, WET LABEL, "WEATHERPROOF IN USE":NEMA 5-20R.W

RECEPTACLE, DUPLEX WITH GROUND FAULT CIRCUITINTERRUPTER, WEATHERPROOF: NEMA 5-20R.WP

RECEPTACLE, DUPLEX WITH GROUND FAULT CIRCUITINTERRUPTER: NEMA 5-20R.

RECEPTACLE, DUPLEX, CONNECTED TO UPS: NEMA 5-20R.

RECEPTACLE, DUPLEX ON EMERGENCY POWER: NEMA 5-20R.

RECEPTACLE, DUPLEX, FLOOR, UNDER CARPET: NEMA 5-20R.UC

RECEPTACLE, DUPLEX, SWITCHED: NEMA 5-20R.

RECEPTACLE, DUPLEX, ISOLATED GROUND: NEMA 5-20R.IG

RECEPTACLE, DUPLEX, DEDICATED CIRCUIT: NEMA 5-20R.D

RECEPTACLE, DUPLEX, CEILING: NEMA 5-20R.C

RECEPTACLE, DUPLEX, ABOVE COUNTER: NEMA 5-20R.A

RECEPTACLE, DUPLEX: NEMA 5-20R.

RECEPTACLE, SINGLE: NEMA 5-20R.

S

DF

RECEPTACLE, DUPLEX WITH GROUND FAULT CIRCUITINTERRUPTER, DRINKING FOUNTAIN: CONCEAL WATERCOOLER RECEPTACLE BEHIND WATER COOLER. SEEMECHANICAL/PLUMBING SHOP DRAWINGS FORINSTALLATION REQUIREMENTS.

TRANSITION CABINET (ONE-LINE DIAGRAM).

PANELBOARD WITH CIRCUIT BREAKER AND SUB FEEDLUGS (ONE-LINE DIAGRAM).

PANELBOARD WITH SUB FEED LUGS (ONE-LINE DIAGRAM).

PANELBOARD WITH MAIN LUGS ONLY AND SURGEPROTECTION WITH CIRCUIT BREAKER (ONE-LINE DIAGRAM).

PANELBOARD WITH MAIN AND SUB FEED CIRCUITBREAKER (ONE-LINE DIAGRAM).

PANELBOARD WITH MAIN CIRCUIT BREAKER. SIZE ANDPHASE AS SHOWN (ONE-LINE DIAGRAM).

PANELBOARD WITH MAIN LUGS ONLY. BUS SIZE ANDPHASE AS SHOWN (ONE-LINE DIAGRAM).

PANELBOARD (ONE-LINE DIAGRAM).

CAPACITOR (ONE-LINE DIAGRAM).

BATTERY (ONE-LINE DIAGRAM).

TRANSFORMER, CURRENT (ONE-LINE DIAGRAM).

TRANSFORMER (ONE-LINE DIAGRAM).

EXHAUST FAN OUTLET.

MOTOR.

CIRCUIT BREAKER, SOLID STATE WITH GROUND FAULTPROTECTION (ONE-LINE DIAGRAM).

GFP

CIRCUIT BREAKER, SOLID STATE (ONE-LINE DIAGRAM).

CIRCUIT BREAKER, MOTOR CIRCUIT PROTECTION(ONE-LINE DIAGRAM).

CIRCUIT BREAKER, MOLDED CASE WITH SHUNT TRIP(ONE-LINE DIAGRAM).

STARTER (ONE-LINE DIAGRAM).

ELECTRICAL POWER AND DISTRIBUTION

225/3

"1H" "1H"

225/3 225/3"1H" "1H"

25/3

225/3

"1H"

60/3

225/3

"1H"

225/3

"1H"

225/3

"1H"

"1H"

F

MCP

STARTER, COMBINATION WITH DISCONNECT SWITCH.

DISCONNECT SWITCH, UNFUSED.

DISCONNECT SWITCH, FUSED.

75 TRANSFORMER: NUMBER INDICATES kVA.

SWITCH, TOGGLE MOTOR STARTER WITH OVERLOAD PROTECTION.

LIGHTING RELAY, CONTACTOR PANEL, OR DIMMING ENCLOSURE.

DISTRIBUTION PANEL OR SWITCHBOARD.

PANELBOARD CABINET, SURFACE MOUNTED, 2 SECTION.

PANELBOARD CABINET, SURFACE MOUNTED, 1 SECTION.

PANELBOARD CABINET, FLUSH MOUNTED.

PUSHBUTTONS, MOTOR CONTROL.

PUSHBUTTON.

STARTER OR MOTOR CONTROLLER.

VARIABLE FREQUENCY MOTOR CONTROLLER (ONE-LINE DIAGRAM).

METER.

GENERATOR, POWER (ONE-LINE DIAGRAM).

GENERATOR, ANNUNCIATOR (ONE-LINE DIAGRAM).G

SERVICE ENTRANCE SURGE PROTECTION (ONE-LINE DIAGRAM).

DIGITAL MULTIMETER (ONE-LINE DIAGRAM).

TRANSFER SWITCH (ONE-LINE DIAGRAM).

CT CABINET PER UTILITY'S REQUIREMENTS (ONE-LINE DIAGRAM).

ST

LP

DP#__

VFDVFC

M

G

DMM

ALARM, STROBE, CEILING MOUNTED. SUBSCRIPTINDICATES CANDELA RATING.

ALARM, HORN, CEILING MOUNTED. SUBSCRIPT INDICATESCANDELA RATING.

ALARM, HORN/STROBE, ONE ASSEMBLY, CEILING MOUNTED. SUBSCRIPT INDICATES CANDELA RATING.

ALARM, HORN/STROBE, ONE ASSEMBLY. SUBSCRIPTINDICATES CANDELA RATING.

FIRE AND SMOKE DAMPER.

SMOKE DAMPER.

DETECTOR, TAMPER SWITCH WITH VALVE: TAMPERSWITCHES SHALL BE PROVIDED AND INSTALLED WITH FIRESPRINKLER SYSTEM AND SHALL BE CONNECTED TOLOCATIONS SHOWN ON THE FIRE SPRINKLER SHOPDRAWINGS.

DETECTOR, FLOW SWITCH: FLOW SWITCHES SHALL BEPROVIDED AND INSTALLED WITH FIRE SPRINKLER SYSTEMAND SHALL BE CONNECTED TO LOCATIONS SHOWN ONTHE FIRE SPRINKLER SHOP DRAWINGS.

ALARM, MINI HORN/STROBE, ONE ASSEMBLY.

ALARM, HORN/STROBE WITH GUARD, ONE ASSEMBLY.

ALARM, CHIME/STROBE, ONE ASSEMBLY.

ALARM, HORN/SPEAKER, WEATHERPROOF.

STROBE. SUBSCRIPT INDICATES CANDELA RATING.

DETECTOR, HEAT.

DETECTOR, SMOKE, DUCT WITH HOUSING AND SAMPLING TUBE.

DETECTOR, SMOKE, ELEVATOR RECALL DESIGNATION.

DETECTOR, SMOKE, BEAM TRANSMITTER.

DETECTOR, SMOKE, BEAM RECEIVER.

DETECTOR, SMOKE.

MAGNETIC DOOR HOLDER.

SHUT DOWN RELAY: INSTALL RELAY IN CONTROL CIRCUITOF EQUIPMENT TO BE CONTROLLED IN THE EVENT OF AFIRE.

FIRE ALARM MANUAL PULL STATION.

MONITOR MODULE.

CONTROL MODULE.

FIRE ALARM NOTIFICATION POWER SUPPLY.

FIRE ALARM CONTROL PANEL, SEMI-RECESSED.

FIRE SYSTEM ANNUNCIATOR.

FIRE ALARM

75

75

75

75

FSD

SD

M

G

C

WP

75

E

BT

BR

R

P

MM

CM

FPS

FCP

FSA

AUTOMATIC DOOR CLOSERS: DOOR CLOSERS SHALL BEFURNISHED WITH DOOR HARDWARE AND CONNECTED TOBY FIRE ALARM INSTALLERS.

C

RELAY MODULE.RM

SPEAKER, 8".

PROJECTOR, CEILING MOUNTED.

SCREEN, PROJECTION, CEILING MOUNTED.

AUDIO/VISUAL OUTLET. HDMI UNLESS OTHERWISE NOTED.PROVIDE A/V CABLING BETWEEN INPUT AND OUTPUT RECEPTACLES.

MEDIA CONNECTION PLATE.

EQUIPMENT CABINET.

CALL SWITCH, INTERCOM.

SPEAKER, USER DEFINED.

SPEAKER, SURFACE.

SPEAKER, RECESSED.

SPEAKER, MASKING.

HORN, WEATHER RESISTANT.

HORN.

SPEAKER, EXISTING.

SPEAKER, BLIND MOUNT.

SPEAKER, 12".

SPEAKER, 6".

SPEAKER, 4".

SPEAKER, WALL MOUNTED.

SPEAKER, CEILING MOUNTED.

X

TECHNOLOGY SYSTEM CABLE. SEE SPECIFIC JOB

EQUIPMENT LIST FOR APPLICABLE DESIGNATIONS.

EXAMPLES:

C = CONTROL CABLE

G = GROUND CABLE, 10 AWG, 1 CONDUCTOR, GREEN INSULATED

L = LINE LEVEL CABLE

M = MICROPHONE CABLE

S = SPEAKER CABLE, 70 VOLT SYSTEM

Z = SPEAKER CABLE, 8 OHM SYSTEM

TECHNOLOGY SYSTEMS

S8

XX

SS

SR

SM

SHW

SH

SE

SB

S12

S6

S4

S#

S#

PANNING CAMERA TRANSVERSE ANGLE.

CCTV CAMERA WITH PAN, TILT AND ZOOM.

CCTV CAMERA/ENCLOSURE WITH LENS, TYPICAL. SEE SCHEDULE.

CCTV MONITOR.

CCTV HEADEND EQUIPMENT.

CCTV

360°

PTZ

M

CCTV

ULTRASONIC MOTION DETECTOR.

PASSIVE INFRARED SENSOR.

BELL.

REMOTE DOOR RELEASE BUTTON.RL

EXIT REQUEST.

DOOR SWITCH, BALANCED MAGNETIC CONTROL.

KEYPAD/CARD READER COMBINATION.

CARD READER.

CARD ACCESS DOOR TYPE #1 OR AS NOTED. SEE SCHEDULE.

INTRUSION DETECTION HEADEND EQUIPMENT.

SECURITY CONTROL PANEL.

SECURITY

U

IR

ER

KCR

CR

#1

SEC

CTR

CIRCUIT BREAKER, MOLDED CASE (ONE-LINE DIAGRAM).

CIRCUIT BREAKER SOLID STATE WITH LONG, SHORT,INSTANTANEOUS AND GROUND FAULT TRIP SETTING

CIRCUIT BREAKER SOLID STATE WITH LONG, SHORT &INSTANTANEOUS TRIP SETTING.

LSIG

LSI

RECEPTACLE, DUPLEX WITH GROUND FAULT CIRCUITINTERRUPTER, CONNECTED TO UPS: NEMA 5-20R.

RECEPTACLE, DUPLEX, TAMPER RESISTANT: NEMA 5-20R.T

SWITCH, WEATHERPROOF.

SWITCH, TIMER OPERATED.

SWITCH, PILOT LIGHT.

SWITCH, KEY OPERATED.

SWITCH, DOOR.

SWITCH, FOUR-WAY ("x" INDICATES FIXTURES CONTROLLED).X

SWITCH, THREE-WAY ("x" INDICATES FIXTURES CONTROLLED).X

SWITCH, DOUBLE POLE ("x" INDICATES FIXTURES CONTROLLED).X

SWITCH, SINGLE POLE ("x" INDICATES FIXTURES CONTROLLED).X

SWITCH, DIMMER.

MULTI-OUTLET ASSEMBLY: NEMA 5-20R.

RECEPTACLE, RANGE: NEMA 10-50R.

RECEPTACLE, DRYER: NEMA 10-30R.

RECEPTACLE, SPECIAL PURPOSE ON EMERGENCY POWER.PROVIDE RECEPTACLE TO MATCH EQUIPMENT PLUG.

RECEPTACLE, SPECIAL PURPOSE. PROVIDE RECEPTACLETO MATCH EQUIPMENT PLUG.

RECEPTACLE, QUADRAPLEX WITH GROUND FAULT CIRCUITINTERRUPTER: NEMA 5-20R.

RECEPTACLE, QUADRAPLEX, CONNECTED TO UPS: NEMA 5-20R.

RECEPTACLE, QUADRAPLEX ON EMERGENCY POWER:NEMA 5-20R.

RECEPTACLE, QUADRAPLEX: NEMA 5-20R.

WP

T

P

K

DS

4

3

2

D

J

R

D

POWER POLE. "#" SHOWN ON DRAWINGS. REFER TOWIRING DEVICE SCHEDULE IN THE ELECTRICALSPECIFICATIONS FOR CONFIGURATION AND DEVICES.

PP#

FLUSH FLOOR BOX. "#" SHOWN ON DRAWINGS. REFER TOWIRING DEVICE SCHEDULE IN THE ELECTRICALSPECIFICATIONS FOR CONFIGURATION AND DEVICES.

FB#

FLUSH FIRE RATED POKE THRU. "#" SHOWN ONDRAWINGS. REFER TO WIRING DEVICE SCHEDULE IN THEELECTRICAL SPECIFICATIONS FOR CONFIGURATION ANDDEVICES.

PT#

WIRING DEVICES

EGRESS DIRECTION ARROW.

NL NIGHT LIGHT: DO NOT SWITCH.

EM EMERGENCY.

FIXTURE IDENTIFICATION, CONNECTED TO GENERATOR ASINDICATED: (W-3)INDICATES FIXTURE TYPE AS SCHEDULED.

(W-3)

FIXTURE IDENTIFICATION: (W-3) INDICATES FIXTURE TYPEAS SCHEDULED.

(W-3)

LIGHTING (REFER TO FIXTURE SCHEDULE FOR SYMBOLS)

LITE TOUCH STATION INDICATOR.

OCCUPANCY SENSOR, ULTRASONIC, OMNI-DIRECTIONAL, CEILING.U

OCCUPANCY SENSOR, DUAL TECHNOLOGY, DIRECTIONAL.

OCCUPANCY SENSOR, DUAL TECHNOLOGY, WALL.

OCCUPANCY SENSOR, DUAL TECHNOLOGY,OMNI-DIRECTIONAL, CEILING.

LIGHTING CONTROL

WS-101

LAN RACK, FLOOR STANDING. OWNER PROVIDED.

TELEPHONE TERMINAL BOARD, FIRE TREATED PLYWOOD PAINTED.

COMMUNICATIONS OUTLET, 1 DATA PORT, 1 ANALOG PORT.

TELEPHONE, WALL MOUNTED: WALL PHONE.W

COMMUNICATIONS OUTLET, 3 DATA PORT.

COMMUNICATIONS OUTLET, 2 DATA PORT.

COMMUNICATIONS OUTLET, 1 DATA PORT.

STRUCTURED CABLING

DISCONNECT WITH FUSE AND MOTOR STARTERCOMBINATION (ONE-LINE DIAGRAM).

DISCONNECT, NONFUSED (ONE-LINE DIAGRAM).

DISCONNECT, FUSED (ONE-LINE DIAGRAM).

OCCUPANCY SENSOR, DUAL TECHNOLOGY,OMNI-DIRECTIONAL, DAYLIGHT CONTROLLER CEILING.P

COMMUNICATIONS OUTLET, 1 ANALOG PORT.

WIRELESS ACCESS POINT OUTLET, 2 DATA PORT.

VACANCY DETECTOR.V

MOMENTARY DIMMING SWITCH. OCCUPANCY DETECTOR WILLTURN LIGHTS ON TO 50% LEVEL. OCCUPANT CAN MANUALLY RAISETHE LIGHT LEVEL TO 100%.

M

MOMENTARY SWITCH WILL TURN ON LIGHTS AFTER BEINGENABLED BY VACANCY DETECTOR.M

RECEPTACLE, SPECIAL PURPOSE. PROVIDE RECEPTACLETO MATCH EQUIPMENT PLUG.

ELECTRICAL POWER AND DISTRIBUTION

VACANCY SENSOR, DUAL TECHNOLOGY, OMNI-DIRECTIONAL,CEILING.

RECEPTACLE, DUPLEX, HOSPITAL GRADE: NEMA 5-20R.

RECEPTACLE, DUPLEX, HOSPITAL GRADE ON EMERGENCYPOWER: NEMA 5-20R.

RECEPTACLE, DUPLEX WITH GROUND FAULT CIRCUITINTERRUPTER, HOSPITAL GRADE: NEMA 5-20R.

RECEPTACLE, DUPLEX WITH GROUND FAULT CIRCUITINTERRUPTER, HOSPITAL GRADE ON EMERGENCY POWER: NEMA5-20R.

RECEPTACLE, QUADRAPLEX, HOSPITAL GRADE: NEMA 5-20R.

RECEPTACLE, QUADRAPLEX, HOSPITAL GRADE ON EMERGENCYPOWER: NEMA 5-20R.

RECEPTACLE, QUADRAPLEX WITH GROUND FAULT CIRCUITINTERRUPTER, HOSPITAL GRADE: NEMA 5-20R.

RECEPTACLE, QUADRAPLEX WITH GROUND FAULT CIRCUITINTERRUPTER, HOSPITAL GRADE ON EMERGENCY POWER: NEMA5-20R.

RECEPTACLE, USB

TELEPHONE, WALL MOUNTED, 1 ANALOG PORT.

RECEPTACLE, USB, HOSPITAL GRADE

RECEPTACLE, DUPLEX, HOSPITAL GRADE: NEMA 5-20R.CONTROLLED BY OCCUPANCY SENSOR & ROOM CONTROLLER.S

EPO RADIOLOGY EMERGENCY SHUT OFF.

TV OUTLET.

ABBREVIATIONSNOTE: ALL ABBREVIATIONS MAY NOT BE USED.

1P SINGLE POLE

1PH SINGLE-PHASE

1WAY ONE-WAY

2/C TWO-CONDUCTOR

2WAY TWO-WAY

3/C THREE-CONDUCTOR

3PH THREE-PHASE

3WAY THREE-WAY

4OUT QUADRUPLE RECEPTACLE

OUTLET

4PDT FOUR-POLE DOUBLE THROW

4PST FOUR-POLE SINGLE THROW

4W FOUR-WIRE

4WAY FOUR-WAY

A ABOVE COUNTER

AC ARMORED CABLE

ADA AMERICANS WITH

DISABILITIES ACT

ADJ ADJACENT

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AIC AMPERE INTERRUPTING

CAPACITY

ALUM ALUMINUM

AMP AMPERE

ANN ANNUNCIATOR

AP ACCESS POINT

(WIRELESS DATA)

AR AS REQUIRED

ASC AMPS SHORT CIRCUIT

ATS AUTOMATIC TRANSFER

SWITCH

AV AUDIO VISUAL

AWG AMERICAN WIRE GAGE

BB XFMR BUCK-BOOST

TRANSFORMER

C CEILING MOUNTED

CATV COMMUNITY ANTENNA

TELEVISION

CB CIRCUIT BREAKER

CCBA CUSTOM COLOR AS

SELECTED BY ARCHITECT

CCTV CLOSED CIRCUIT

TELEVISION

CFBA CUSTOM FINISH AS

SELECTED BY ARCHITECT

CF/CI CONTRACTOR FURNISHED/

CONTRACTOR INSTALLED

CF/OI CONTRACTOR FURNISHED/

OWNER INSTALLED

CKT CIRCUIT

CM CONSTRUCTION MANAGER

CND CONDUIT

CO CONVENIENCE OUTLET

COR CONTRACTING OFFICER'S

REPRESENTATIVE

CP CONTROL PANEL

CT CURRENT TRANSFORMER

CTV CABLE TELEVISION

CU COPPER

dBA UNIT OF SOUND LEVEL

DPDT DOUBLE POLE DOUBLE

THROW

DS DISCONNECT SWITCH

EA EACH

EM EMERGENCY

EMT ELECTRICAL METALLIC

TUBING

ENT ELECTRICAL NONMETALLIC

TUBING

EPO EMERGENCY POWER OFF

EQUIP EQUIPMENT

EX EXISTING

F FURNITURE MOUNTED

FA FIRE ALARM

FCP FIRE ALARM CONTROL

PANEL

FLA FULL LOAD AMPS

FMC FLEXIBLE METALCONDUIT

FOB FREIGHT ON BOARD

FVNR FULL VOLTAGE

NON-REVERSING

FVR FULL VOLTAGE REVERSING

G GROUND

GEN GENERATOR

GFCI GROUND FAULT CIRCUIT

INTERRUPTER

GFP GROUND FAULT

PROTECTION

HD HEAVY DUTY

HID HIGH INTENSITY DISCHARGE

HOA HAND-OFF-AUTOMATIC

HP HORSE POWER

HPF HIGH POWER FACTOR

HPS HIGH PRESSURE SODIUM

HV HIGH VOLTAGE

HZ HERTZ

IG ISOLATED GROUND

IMC INTERMEDIATE METAL

CONDUIT

IN/IS INSULATED/ISOLATED

I/O INPUT/OUTPUT

IR INFRARED

J-BOX JUNCTION BOX

KV KILOVOLT

KVA KILOVOLT AMPERE

kVAR KILOVOLT AMPERE

REACTIVE

kW KILOWATT

kWh KILOWATT HOUR

LED LIGHT EMITTING DIODE

LFMC LIQUID TIGHT FLEXIBLE

METAL CONDUIT

LFNC LIQUID TIGHT FLEXIBLE

NONMETALLIC CONDUIT

LPS LOW PRESSURE SODIUM

LRA LOCKED ROTOR AMPS

LTG LIGHTING

LV LOW VOLTAGE

MATV MASTER ANTENNA

TELEVISION SYSTEM

MAX MAXIMUM

MC METAL CLAD

MCA MINIMUM CIRCUIT AMPS

MCB MAIN CIRCUIT BREAKER

MCC MOTOR CONTROL CENTER

MCP MOTOR CIRCUIT

PROTECTION

MDP MAIN DISTRIBUTION PANEL

MG MOTOR GENERATOR

MH MANHOLE

MIN MINIMUM

MLO MAIN LUGS ONLY

MOCP MAXIMUM OVERCURRENT

PROTECTION

NA NOT APPLICABLE

NC NORMALLY CLOSED

NEC NATIONAL ELECTRICAL

CODE

NEMA NATIONAL ELECTRICAL

MANUFACTURERS

ASSOCIATION

NFC NATIONAL FIRE CODE

NFPA NATIONAL FIRE

PROTECTION ASSOCIATION

NIC NOT IN CONTRACT

NL NIGHT LIGHT

NO NORMALLY OPEN

NTS NOT TO SCALE

OC ON CENTER

OCP OVER CURRENT

PROTECTION

OF/CI OWNER FURNISHED/

CONTRACTOR INSTALLED

OF/OI OWNER FURNISHED/

OWNER INSTALLED

OFP OBTAIN FROM PLANS

OH DR OVERHEAD (COILING) DOOR

OL OVERLOAD

PB PUSHBUTTON

PF POWER FACTOR

PH PHASE

PNL PANEL

PT POTENTIAL TRANSFORMER

PTZ PAN/TILT/ZOOM

QTY QUANTITY

R REMOVE

RCP REFLECTED CEILING PLAN

RMC RIGID METAL CONDUIT

RNC RIGID NONMETALLIC

CONDUIT

RPM REVOLUTIONS PER MINUTE

RR REMOVE AND RELOCATE

SCA SHORT CIRCUIT AMPS

SCBA STANDARD COLOR AS

SELECTED BY ARCHITECT

SF SQUARE FOOT (FEET)

SFBA STANDARD FINISH AS

SELECTED BY ARCHITECT

SPDT SINGLE POLE, DOUBLE

THROW

SPEC SPECIFICATION

SPST SINGLE POLE, SINGLE

THROW

S/S START/STOP

ST SINGLE THROW

SWBD SWITCHBOARD

SWGR SWITCHGEAR

TL TWIST LOCK

TP TELEPHONE POLE

TP TWISTED PAIR

TTB TELEPHONE TERMINAL

BOARD

TV TELEVISION

TVSS TRANSIENT VOLTAGE

SURGE SUPPRESSER

TYP TYPICAL

UF UNDERFLOOR

UGND UNDERGROUND

UPS UNINTERRUPTIBLE POWER

SUPPLY

V VOLTS

VA VOLT AMPERE

VFC/VFD VARIABLE FREQUENCY

MOTOR CONTROLLER

W/ WITH

W/O WITHOUT

WP WEATHERPROOF

XFMR TRANSFORMER

JOHANSEN

No. 185978

PETER E.

LIC

EN

SE

D

P ROF E S S I ONA L

EN

GI N

EE

R

ST A T E O F U T A H

HKS ARCHITECTS, INC.

SALT LAKE CITY, UTAH 84101

ARCHITECT

90 SOUTH 400 WEST, SUITE 110

REVISION

PROJECT NUMBERS

DATE

SHEET TITLE

PLO

TD

AT

E:

INTERMOUNTAIN HEALTHCARE

SALT LAKE CITY, UTAH 84111

OWNER

36 SOUTH STATE STREET

ISSUE

© 2016 HKS, INC.

IN

TE

RM

OU

NT

AIN

LA

YT

ON

PA

RK

WA

Y C

LIN

IC

PC

H A

UD

IO

LO

GY

CL

IN

IC

2018

SHEET NO.

HKS:

201 W

ES

T L

AY

TO

N P

AR

KW

AY

L

AY

TO

N, U

T 8

4041

12/07/18

12/7

/2018 1

2:5

8:0

2 P

M

C:\U

se

rs\jrw

\Do

cu

me

nts

\20

18

06

76

EL

EC

CE

NT

RA

L_jr

w.r

vt

EE001

SYMBOL SCHEDULE,

SHEET INDEX

12/07/18

22506.000

CONSTRUCTION

DOCUMENTS

ELECTRICAL SHEET INDEXEE001 SYMBOL SCHEDULE, SHEET INDEX

EP101 PCH AUDIOLOGY ELECTRICAL PLANS - LEVEL 3

EP501 DETAILS

EP502 DETAILS

EP503 DETAILS

ET601 TELECOM DETAILS

EC601 SYSTEMS DIAGRAMS & DETAILS

EC602 SYSTEMS DIAGRAMS & DETAILS

NO. DESCRIPTION DATE

J

J J

JJ

JJ

JJ

JJ

JJ

JJ

JJ

J J J J J J J J

J

J J

CR

#1

J

S

S

S

S

S

D

D

SEB

SEB

Z

D D

ZZ

SEB

SEB

RCB2

RCB2

RC

B2

S T

4

4.8

5.7

5.9

2.9

RC

"M3LQ""M3L3"

"M3L2"

"M3L1"

"M3LHS"

"M3LS"

"FPS"

"MLX3"

"MH3"

EX

EX

EXEX

EX

EX

EXEX EX

"M3L4"EX

"MLDP2"EX

WAP

S

A

A

A

WAP

A

A

A

A

A

A

A

A

M3L2-8,108

M3L2-2,4,6

2,4

2

CORR

34246

EXAM 2

34216

MANAGER OFFICE

34236

ECHO

34230

EXAM 3

34220

MEDS

34224

EXAM 4

34226

SOILED

34232

SHARED OFFICE(16)

34274

ALCOVE

34222

VITALS

34212

CORR

34244

EEG

34234

PAT TLT

34218

EXAM 1

34214

SHELL SPACE

33112

BREAK

34248

EXAM 4

33123

5

M3L2-12

M3L2-14,16

77

S T

4

4.8

5.7

2.9

RC

CORR

34246

EXAM 2

34216

ECHO

34230

EXAM 3

34220

EEG

34234

PAT TLT

34218

EXAM 1

34214

EXAM 4

33123

(E10-1)

(E10

-1)

(E10-1)

2

2

2

(E10-1)

(NN

FP

-3)

3

4

(G-3)(G-2)

(NN

FP

-3)

(NN

FP

-3)

(G-2) (G-3)

S T

4

4.8

5.7

2.9

RC

CORR

34246

EXAM 2

34216

ECHO

34230

EXAM 3

34220

EEG

34234

PAT TLT

34218

EXAM 1

34214

EXAM 4

33123

WAP

WAP

S T

4

4.8

5.7

2.9

RC

#5

VSS3B

1

ACS3B

P

P

PP

P

CORR

34246

EXAM 2

34216

ECHO

34230

EXAM 3

34220

CORR

34244

EEG

34234

PAT TLT

34218

EXAM 1

34214

SHELL SPACE

33112

EXAM 4

33123

6

6

6

S T

4

4.8

5.7

2.9

RC

CORR

34246

EXAM 2

34216

ECHO

34230

EXAM 3

34220

EEG

34234

PAT TLT

34218

EXAM 1

34214

EXAM 4

33123

JOHANSEN

No. 185978

PETER E.

LIC

EN

SE

D

P ROF E S S I ONA L

EN

GI N

EE

R

ST A T E O F U T A H

HKS ARCHITECTS, INC.

SALT LAKE CITY, UTAH 84101

ARCHITECT

90 SOUTH 400 WEST, SUITE 110

REVISION

PROJECT NUMBERS

DATE

SHEET TITLE

PLO

TD

AT

E:

INTERMOUNTAIN HEALTHCARE

SALT LAKE CITY, UTAH 84111

OWNER

36 SOUTH STATE STREET

ISSUE

© 2016 HKS, INC.

IN

TE

RM

OU

NT

AIN

LA

YT

ON

PA

RK

WA

Y C

LIN

IC

PC

H A

UD

IO

LO

GY

CL

IN

IC

2018

SHEET NO.

HKS:

201 W

ES

T L

AY

TO

N P

AR

KW

AY

L

AY

TO

N, U

T 8

4041

12/07/18

12/7

/2018 1

2:5

8:1

6 P

M

C:\U

se

rs\jrw

\Do

cu

me

nts

\20

18

06

76

EL

EC

CE

NT

RA

L_jr

w.r

vt

EP101

PCH AUDIOLOGY

ELECTRICAL PLANS -

LEVEL 3

12/07/18

22506.000

CONSTRUCTION

DOCUMENTS

GENERAL SHEET NOTESSHEET KEYNOTES

SCALE: 1/8" = 1'-0"

PCH AUDIOLOGY POWER PLAN -LEVEL 3

1SCALE: 1/8" = 1'-0"

PCH AUDIOLOGY LIGHTING PLAN -LEVEL 3

2SCALE: 1/8" = 1'-0"

PCH AUDIOLOGY TELECOM PLAN -LEVEL 3

3SCALE: 1/8" = 1'-0"

PCH AUDIOLOGY SYSTEMS PLAN -LEVEL 3

4SCALE: 1/8" = 1'-0"

PCH AUDIOLOGY FIRE ALARM PLAN -LEVEL 3

5

1 ALL RECEPTACLES TO BE HOSPITAL GRADE AND TAMPER PROOF.

2 ALL CIRCUITING MUST MEET GROUNDING REQUIREMENTS FROM NEC 517-13.

1 WALL MOUNT CAMERA AT 86" AFF. SUCH THAN THE CAMERA CAN VIEW UP/DOWNTHE CORRIDOR WITHOUT OBSTRUCTION FROM LIGHT FIXTURES.

2 PENDANT MOUNT EXIT SIGNS SO THEY CAN BE VIEWED BELOW PENDANT HALLWAYFIXTURES.

3 CIRCUIT TO EXISTING EGRESS LIGHT CIRCUIT FEEDING EXISTING WEST HALLWAYEGRESS LIGHT FIXTURES.

4 CONNECT AND CONTROL NEW HALLWAY FIXTURES WITH EXISTING WEST HALLWAYFIXTURES.

5 PROVIDE 120 VOLT POWER ABOVE CEILING FOR VAV CONTROLS.

6 PROVIDE ONE DATA DROP TO EACH "RCB2" LOCATION. NURSE CALL CONTROL UNITLOCATED ABOVE CEILING.

7 PROVIDE 120V CICUIT FOR AUDIO BOOTHS.

NO. DESCRIPTION DATE

SHEET KEYNOTES

2

1

1. LOCATE RECEPTACLES BEHIND DRINKING FOUNTAINS.

2. REFER TO ARCHITECTURAL ELEVATIONS FOR PLACEMENT OF OUTLETS.

3. LOCATE AT BOTTOM OF BEAMS IF D < .1H AND W < .4H OR AT CEILING FOR LEVEL

CEILINGS. FOR PAN-TYPE CEILINGS, CORRIDORS, SMALL ROOMS,

SLOPED/BEAMED CEILINGS, AND OTHER CONDITIONS, REFER TO NFPA 72.

4. LOCATE DETECTOR ANYWHERE IN SHADED AREA BUT NOT IN TOP 4" OF PEAK.

5. LOCATE AT BOTTOM OF BEAMS IF D/H < .1 OR W/H < .4; OTHERWISE, LOCATE IN

BEAM POCKET. FOR D > 4 REDUCE SPACING .33 PERPENDICULAR TO BEAMS.

3 5

4

GENERAL SHEET NOTES1. DETERMINE MOUNTING HEIGHTS OF ELECTRICAL AND ELECTRONIC

EQUIPMENT IN THE FOLLOWING ORDER OF PRIORITY:

1 - ELEVATIONS (ARCHITECTURAL, ELECTRICAL, MECHANICAL, ETC).

2 - EQUIPMENT SHOP DRAWINGS.

3 - FIELD INSTRUCTIONS.

2. LOCATE RECEPTACLES SERVING THE SAME TYPE OF USE AT A UNIFORM

HEIGHT UNLESS DIRECTED OTHERWISE.

3. MECHANICAL, ELECTRICAL, AND COMMUNICATION ROOMS: COORDINATE

LOCATION OF LIGHTING AND POWER RECEPTACLES WITH EQUIPMENT, PIPING,

AND DUCTWORK. DO NOT INSTALL RECEPTACLES BEHIND EQUIPMENT OR

WHERE OTHERWISE INACCESSIBLE. POSITION LIGHTING REGARDLESS OF

WHERE SHOWN ON DRAWING TO PROVIDE PROPER ILLUMINATION.

4. MOUNT RECEPTACLE BOXES FOR SWITCHES AND RECEPTACLES WITH LONG

AXIS OF THE DEVICE VERTICAL UNLESS OTHERWISE INDICATED.

5. SET BOXES WITH PLASTER RINGS FLUSH WITH FINISHED SURFACE.

6. LOCATE BOX COVERS OR DEVICE PLATES SO THEY WILL NOT SPAN DIFFERENT

TYPES OF BUILDING FINISHES EITHER VERTICALLY OR HORIZONTALLY.

7. VERIFY ALL DOOR CONDITIONS ON ARCHITECTURAL DRAWINGS PRIOR TO

INSTALLING SWITCHES.

8. LOCATE WIRING DEVICES WHICH ARE ADJACENT AND ARE COMPATIBLE

VOLTAGES IN ONE PLATE.

DUPLEX RECEPTACLE

DUPLEXRECEPTACLE

COMMUNICATIONS RECEPTACLE

COMMUNICATIONS RECEPTACLE

1FIRE ALARM MOUNTING DETAILS

2

LIGHTINGMOUNTING DETAILS

3COMMUNICATION MOUNTING DETAILS

4

BOXMOUNTING DETAILS

5ADA DETAIL

6SWITCH MOUNTING DETAILS

7RECEPTACLE MOUNTING DETAILS

NO SPECIAL REQUIREMENTS

FINISH FLOOR

LIGHT FIXTURE

WALL MOUNTED

COMMUNICATION

RECEPTACLES

LIGHT FIXTURE

PENDANT

PENDANT EXIT SIGNS

PAY PHONEWALL PHONE

GENERAL USE:

EXIT

FINISH FLOOR

FOR SPECIAL EQUIPMENT

DEDICATED RECEPTACLE

WALL BRACKET TV COUNTER - TYPICAL

ABOVE

RECEPTACLES ABOVE OR BELOW COUNTER

WINDOW

OR

BOXES ON OPPOSITE SIDES OF WALL

GREATER THAN 2'

DOOR WITH SIDELIGHT

RECEPTACLES

SWITCHES STANDARD DOOR LESS THAN 2'

DOOR WITH SIDELIGHT

WALL BRACKET TVNO SPECIAL REQUIREMENTS

GENERAL USE:DUPLEX

FINISH FLOOR

DEDICATED RECEPTACLE

FOR SPECIAL EQUIPMENT

RESIDENTIAL BATHROOM

PLATE FOR SWITCH AND

COMBINATION 48" MAX

DOOR WITH NO

AT LATCH SIDE

PLACE FOR SWITCH

GENERAL USE: ADA

FINISH FLOOR

CABINETS

CONTROL STATION

RECEPTACLE IN LIGHTING

DRINKING FOUNTAIN TILE WALLS

MIRROR

CENTERIN TILE

DO NOT LOCATEABOVE SINK

DUPLEXRECEPTACLE

INACCESSIBLE OUTLETLESS THAN 15" ABOVE

FLOOR PERMISSIBLE

30" X 48" CLEAR FLOORSPACE PERPENDICULAR TOTHE WALL FOR A FORWARD

REACH TO CONTROLS

ADDITIONAL OUTLET INACCESSIBLE LOCATION

FORWARD REACHTO LIGHT AND

FAN SWITCHESAS WELL AS

THERMOSTAT

SWITCHLOCATION

SWITCHLOCATION SIDELIGHT

LESS THAN 2'

SIDELIGHTGREATER

THAN 2'

SWITCHLOCATION

SWITCHLOCATION

METALFRAME

METALFRAME

COMMUNICATIONSRECEPTACLE

COUNTER TOP

GROMMET

COMMUNICATIONSRECEPTACLE

STUD INBETWEEN

FIRE ALARM PULL STATION

HORN/STROBE OR STROBE

PULL STATION

FINISH FLOOR

WALLWALLMOUNT DUPLEXOUTLET BEHINDWATER COOLER

DRINKING FOUNTAIN - SIDE ELEVATIONS

COORDINATELOCATION OFDUPLEX OUTLETWITHEQUIPMENTSUPPLIER

REGULAR HANDICAPPED

COMMUNICATIONSRECEPTACLE

NTS

NTS NTS NTS

NTS NTS

NTS

REFER TO ARCHITECTURAL ELEVATIONS FORPLACEMENT OF OUTLETS.

RECEPTACLES BELOW COUNTER

WINDOW

FULL HEIGHT

COUNTER TOP

GROMMET

DUPLEX RECEPTACLE

DUPLEXRECEPTACLE

VENDING MACHINES

REFRIGERATORS AND

RECEPTACLES ABOVE COUNTER

WITH BACKSPLASHWITHOUT BACKSPLASH

COUNTER TOP

BACKSPLASH

BETWEEN BEAMS ADJACENT TO SUPPLY AIROR SMOKE DETECTOR SMOOTH SLOPED CEILING (PEAKED)

HEAT OR SMOKE DETECTOR ON SMOKE DETECTORSMOKE DETECTOR

DIFFUSER(SUPPLY OR

RETURN)

WALL MOUNTED HEAT

HORN/STROBE

STROBE OR

FIRE ALARM

PANEL "FCP"

CONTROL

ANNUNCIATOR "FSA"

FIRE SYSTEM HEAT OR SMOKE DETECTOR ON

SMOOTH SLOPED CEILING (SHED)

S = SPACEBETWEEN

DETECTORS

BETWEEN BEAMS

HEAT DETECTORHORN OR BELL (NO STROBE)

18"

MIN

HE

IGH

TA

S N

OT

ED

HE

IGH

T P

ER

ELE

VA

TIO

N O

RA

S N

OT

ED 3

6"

MA

X

48"

MA

X

16"

MIN

2'-0"

48"

MA

X

16"

MIN

24"MIN

48"

MA

X

2'-0"

16"

MIN

48"

MA

X

48"

MA

X

48"

MA

X

48"

MA

X

48"

MA

X

18"

MIN

CO

OR

DIN

AT

EH

EIG

HT

WIT

HE

QU

IPM

EN

T

CO

OR

DIN

AT

EW

ITH

EQ

UIP

ME

NT

CO

OR

DIN

AT

EH

EIG

HT

WIT

HE

QU

IPM

EN

T

±46"

MA

X(V

ER

IFY

HE

IGH

TO

F B

AC

KS

PL

AS

H)

60"

16"

MIN

6"

MA

X

6"

MA

X

72"

60"

90"

4"

MIN

3' MIN

12"

MA

X

3'MAX

SS

1/2 S

D

W

3'-0"3'-0"

1/2 S S S 1/2 S

>7.2°

D

H

W

6"

MIN

4"

H

48"

MA

X 80"

MIN

6"

MIN

96"

MA

X

JOHANSEN

No. 185978

PETER E.

LIC

EN

SE

D

P ROF E S S I ONA L

EN

GI N

EE

R

ST A T E O F U T A H

HKS ARCHITECTS, INC.

SALT LAKE CITY, UTAH 84101

ARCHITECT

90 SOUTH 400 WEST, SUITE 110

REVISION

PROJECT NUMBERS

DATE

SHEET TITLE

PLO

TD

AT

E:

INTERMOUNTAIN HEALTHCARE

SALT LAKE CITY, UTAH 84111

OWNER

36 SOUTH STATE STREET

ISSUE

© 2016 HKS, INC.

IN

TE

RM

OU

NT

AIN

LA

YT

ON

PA

RK

WA

Y C

LIN

IC

PC

H A

UD

IO

LO

GY

CL

IN

IC

2018

SHEET NO.

HKS:

201 W

ES

T L

AY

TO

N P

AR

KW

AY

L

AY

TO

N, U

T 8

4041

12/07/18

12/7

/2018 1

2:5

8:2

4 P

M

C:\U

se

rs\jrw

\Do

cu

me

nts

\20

18

06

76

EL

EC

CE

NT

RA

L_jr

w.r

vt

EP501

DETAILS

12/07/18

22506.000

CONSTRUCTION

DOCUMENTS

NO. DESCRIPTION DATE

3"

MIN

MIN

36"

DE

PT

H

3" MIN 6" TYP

DEMANDFLEX BALLAST

VIOLET WIRE

GREY WIRE

FLUORESCENT

LAMPS

DEMANDFLEX BALLAST

VIOLET WIRE

GREY WIRE

FLUORESCENT

LAMPS

SD

VIO

LE

T

GR

EY

CLASS 2 CONTROL

VOLTAGE

LOW VOLTAGE

0-10V DIMMING

BALLAST

CONTROLLER

CLASS 1 CONTROL

VOLTAGE

WHITE

BLUE

RED 1

ORANGE

YELLOW/BLACK

YELLOW

YELLOW/WHITE

NO

COM

NO

DIVERSA

SENSOR

DIODE PULSE

1 POLE

-R

VACANCY SENSOR

(TYPICAL PRIMARY)

W

B

24

VAC

R1L

N

CLASS 2

CONTROL

NEUTRAL

VOLTAGE

CLASS 1

CONTROL

VOLTAGE

DISTRIBUTION

CABINET

(BY OTHERS)

GENERAL NOTESTYPICAL FOR WOOD AND METAL STUD ROUGH-IN.

PLASTER RINGS NOT SHOWN.

LOCATE ALL OUTLET BOXES IN ACCORDANCE WITH ARCHITECTURAL AND

MECHANICAL DRAWINGS AND WITH ALL APPLICABLE SHOP DRAWINGS.

IN ACCORDANCE WITH UBC 709-7 EXCEPTION 1, OUTLETS ON OPPOSITE

SIDES OF WALLS OR PARTITIONS IN THE SAME STUD SPACE IN A RATED FIRE

SEPARATION WALL MUST BE SEPARATED BY A MINIMUM OF 24" HORIZONTAL

DISTANCE.

IN NON-RATED WALLS, OUTLETS ON OPPOSITE SIDES OF WALLS OR

PARTITIONS MUST BE SEPARATED BY 16" FOR SOUND ATTENUATION.

1.

2.

3.

4.

5.

NOTE: TIE WIRE SHALL NOT BEUSED AS A COMPONENT OF ANYRACEWAY HANGER SYSTEM.

METHODS DETAIL3

TYPICAL ROUGH-IN REQUIREMENTS DETAIL2

RECESSED FIXTURE MOUNTING DETAIL5

TYPICAL CONDUIT RACK DETAIL6

TYPICAL FIRESTOP FOR CABLES/CONDUITTHROUGH CONCRETE FLOORING

CABLES/CONDUIT THRUGYPSUM WALL BOARDMETAL CONDUIT THRU

TYPICAL FIRESTOP FOR

98

7

FIRESTOP FOR

13FLOOR BOX #11

1TYPICAL SECONDARY DUCT BANK DETAIL

4VOICE/DATA RISER

TYPICAL RACEWAY SUPPORT

CONCRETE WALLS10

OCCUPANCY/VACANCY SENSORCONNECTION SCHEMATIC

FB# PT#

STRUCTURAL UNIT

BEAM, CLAMP OR HANGERCLAMP AS REQUIRED BY

WEIGHT SUPPORTED

ALL THREAD - SIZE AS REQUIRED

RACEWAY, .5" THROUGH 6"

CONDUIT HANGER

STRUCTURAL UNIT

RACEWAY - .5" THROUGH 1"

BEAM, CLAMP OR HANGERCLAMP AS REQUIRED BY

WEIGHT SUPPORTED

RACEWAY -.5" THROUGH 1"

NTS

BAR STRAPSBAR STRAPS

BAR STRAPS

TYPICALWALLOUTLETS

PROVIDE CONDUIT SUPPORTS INACCORDANCE WITH NEC SPACINGREQUIREMENTS FOR TYPE OFRACEWAY REQUIRED.

AS REQUIRED FOR TYPEOF CONSTRUCTION.

TYPICALOUTLET BOX

TYPICALOUTLET BOX

NTS

RECESSED TROFFER LAY-IN CEILING GRID SYSTEM

WIRE HANGER AT EACH CORNER OF FIXTURE (TYP)INDEPENDENT OF CEILING SUPPORT SYSTEM. FIXTURE CLAMP - PROVIDE ONE PER

SIDE OF FIXTURE.

NTS

BEAM CLAMP, HANGER CLAMPOR APPROVED SUPPORT, AS

REQUIRED BY WEIGHTSUPPORTED

CONDUIT CLAMP - .5" TO 1"UNISTRUT 2 PIECE CHANNEL PIPE

STRAPS - 1.25" TO 6"

UNISTRUT CHANNEL - SIZE ASREQUIRED BY WEIGHT SUPPORTED

STRUCTURALBEAM, JOIST,SLAB, ETC.

ALL THREADED ROD -SIZE AS REQUIRED

RACEWAY .5" TO 6" (TYP)

NTS

NTS

OR MINERAL WOOL)

(BACKER ROD, FIBERGLASS

DAMMING MATERIAL

FIRE RATED CONCRETE

FLOOR SLAB

CONDUIT OR

INSULATED CABLESCP 25WB CAULK

NTS NTS

MAY EXTEND A MAX.

BOTH SIDES OF WALL

CP 25WB CAULK ON

ALUMINUM FOIL TAPE

FS-195 WRAP/STRIP 2" WIDE,

ONE WRAP OF 3M BARRIER

INSTALLED FOIL SIDE OUT

WOOD OR STEEL STUD

PUTTY

METALLIC CONDUIT

CAULK OR MP MOLDABLE

3M FIRE BARRIER CP 25

1/4" MIN. DIAMETER BEAD OF

2" (51 mm) BEYOND

THIS WALL SURFACE

GYPSUM WALL BOARD

2 HOUR FIRE RATED

FIRE RATED CONCRETE/

CONCRETE BLOCK WALLDAMMING MATERIAL

OR MINERAL WOOL)

(BACKER ROD, FIBERGLASS

NON-METALIC SLEEVE

INSULATED CABLES

FB11

NTS

DUPLEX RECEPTACLE

NTS

SCALE: 1/16"=1'-0"

NOTES:

1. MAINTAIN SPACE BETWEEN CONDUITS AS INDICATED ON DETAIL.

2. THE LAST 10' OF DUCTS ENTERING MANHOLE, PULL BOX, TUNNEL OR DUCT

TRENCH SHALL BE RMC WITH OZ/GEDNEY BELL ENDS.

3. ALL BENDS SHALL BE LARGE RADIUS.

4. ALL CONDUIT ABOVE GROUND, ALL BENDS AND FIRST 10' BELOW GROUND

SHALL BE WRAPPED RMC. CONDUIT BELOW GROUND MAY BE PVC.

5. PROVIDE POLYPROPYLENE PULL ROPE IN EMPTY CONDUITS.

6. DUCT BANKS SHALL HAVE A MINIMUM SLOPE OF 4" PER 100 FEET.

7. REFER TO ONE-LINE DIAGRAM FOR NUMBER AND SIZE OF CONDUITS.INCLUDE 1EA. 4" SPARE IN ADDITION TO THOSE INDICATED ON THE ONE-LINEDIAGRAM.

WARNING TAPE

UNDISTURBED EARTH

DONUT STYLE SPACERS

COMPACTED SAND BACK FILL

BACK FILL

CONDUIT

FLOOR LINE

ACCESSIBLE CEILING

TYPICALVOICE

OUTLET

TYPICAL FLUSHMOUNT POKE THRU

NTS

TYPICALFLOOR BOX

TYPICALVOICE/DATA

OUTLET

TYPICALDATA

OUTLET

PROVIDE 5" SQUARE BOX WITH 2 7/8" DEEPSINGLE GANG MUD RING AND COVER PLATE.

1.25" CONDUIT STUBTO CABLE TRAY

1.25" CONDUIT

1.25" CONDUIT

TYP. WALL1.25" CONDUIT STUBTO CABLE TRAY

1" CONDUIT STUBTO CABLE TRAY

NO SCALE

2.4

4"

JOHANSEN

No. 185978

PETER E.

LIC

EN

SE

D

P ROF E S S I ONA L

EN

GI N

EE

R

ST A T E O F U T A H

HKS ARCHITECTS, INC.

SALT LAKE CITY, UTAH 84101

ARCHITECT

90 SOUTH 400 WEST, SUITE 110

REVISION

PROJECT NUMBERS

DATE

SHEET TITLE

PLO

TD

AT

E:

INTERMOUNTAIN HEALTHCARE

SALT LAKE CITY, UTAH 84111

OWNER

36 SOUTH STATE STREET

ISSUE

© 2016 HKS, INC.

IN

TE

RM

OU

NT

AIN

LA

YT

ON

PA

RK

WA

Y C

LIN

IC

PC

H A

UD

IO

LO

GY

CL

IN

IC

2018

SHEET NO.

HKS:

201 W

ES

T L

AY

TO

N P

AR

KW

AY

L

AY

TO

N, U

T 8

4041

12/07/18

12/7

/2018 1

2:5

8:2

9 P

M

C:\U

se

rs\jrw

\Do

cu

me

nts

\20

18

06

76

EL

EC

CE

NT

RA

L_jr

w.r

vt

EP502

DETAILS

12/07/18

22506.000

CONSTRUCTION

DOCUMENTS

NO. DESCRIPTION DATE

BRACE ALL CONDUIT WITH 2 1/2" I.D. AND LARGER, AND

ALL BUSWAY, CABLE TRAY AND CONDUIT RACKS.

DETAILS SHOWN PROVIDE A LATERAL BRACING

SYSTEM. A TYPICAL VERTICAL SUPPORT SYSTEM

MUST ALSO BE USED. HOWEVER, WHERE BRACE

OCCURS THE VERTICAL ANGLE SHOWN MAY REPLACE

A TYPICAL VERTICAL SUPPORT.

TRANSVERSE BRACING AT 30'-0" O.C. MAX.

LONGITUDINAL BRACINGS AT 60'-0" O.C. MAX.

TRANSVERSE BRACING FOR ONE CONDUIT OR

BUSWAY SECTION MAY ALSO ACT AS LONGITUDINAL

BRACING FOR THE CONDUIT OR BUSWAY SECTION

CONNECTED PERPENDICULAR TO IT, IF THE BRACING

IS INSTALLED WITHIN 24" OF THE ELBOW OR TEE AND

SIMILAR SIZE.

DO NOT USE BRANCH LINES TO BRACE MAIN LINES.

PROVIDE FLEXIBILITY IN JOINTS WHERE PIPES PASS

THROUGH BUILDING SEISMIC OR EXPANSION JOINTS,

OR WHERE RIGIDLY SUPPORTED PIPES CONNECT TO

EQUIPMENT WITH VIBRATION ISOLATORS.

AT VERTICAL CONDUIT AND BUSWAY RISERS,

WHEREVER POSSIBLE, SUPPORT OF WEIGHT OF THE

RISER AT A POINT OR POINTS ABOVE THE CENTER OF

GRAVITY OF THE RISER. PROVIDE LATERAL GUIDES AT

THE TOP AND BOTTOM OF THE RISER, AND AT

INTERMEDIATE POINTS NOT TO EXCEED 30'-0" ON

CENTER.

PROVIDE LARGE ENOUGH CONDUIT SLEEVES

THROUGH WALLS OR FLOORS TO ALLOW FOR

ANTICIPATED DIFFERENTIAL MOVEMENTS.

DO NOT FASTEN ONE RIGID CONDUIT OR BUSWAY

SYSTEM TO TWO DISSIMILAR PARTS OF A BUILDING

THAT MAY RESPOND IN A DIFFERENT MODE DURING

AN EARTHQUAKE: FOR EXAMPLE, A WALL AND A ROOF.

REFER TO SPECIFICATIONS AND MANUFACTURER'S

LITERATURE FOR ADDITIONAL REQUIREMENTS.

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

SEISMIC BRACING GENERAL NOTES

2TYPICAL SINGLE CONDUIT BRACING

TYPICAL SINGLE CONDUIT BRACING4

BASE STAND1

NORMAL WEIGHT CONCRETE ANCHORAGE3

CONCRETE ANCHORAGE5

TYPICAL CONDUIT RACK BRACING6

LIGHT WEIGHT

NOTE:

1. BLOW ALL HOLES CLEAN W/OIL FREE

COMPRESSED AIR.

2. FOLLOW ALL MANUFACTURES

RECOMMENDATIONS.

1/8"

OPTION 2

ADHESIVESET IN HILTI HY150

INSERT DRILLED ANDINTERNALLY THREADED

1/2" DIA. HILTI

6" MIN.EMBED

4-4x3 1/2'x5/16x0'-5 1/2" TYP.

EACH END. 2-5/8" A325

BOLTS EA. LEG (OR EQUIVALENT

WELDED CONN.)

PROVIDE ANGLE MEMBERS ASDETERMINED BY A STRUCTURAL ENGINEERPER SPECIFICATION SECTION 16071.

PROVIDE ANGLE MEMBERS ASDETERMINED BY A STRUCTURAL ENGINEERPER SPECIFICATION SECTION 16071.

"L"

(6'-0"

MA

X.)

NOTE:

BOLT TO ANGLE

DIAGONAL ANGLE

ROD CLIP

PIPE

"ELCEN" HANGER

NOTE:

1/8" X 1" @ 24" O.C.

ITEMS NOT NOTED SAME AS ABOVE

DIAGONAL & LONGITUDINAL ANGLES -ALTERNATE SIDES

ADD PIPE SLEEVE THATHAS AN I.D. 1/4" + LARGERTHAN O.D. OF BOLT

LONGITUDINAL DIAGONAL

DOTTED) SEE NOTE #4 .ANGLE AS REQ'D (SHOWN

ROD

VERTICAL ANGLE

STEEL BEAM

CLAMP "ELCEN"

TYPE OR EQUAL

NOTE: BEAM

CLAMP USED FOR

VERTICAL ANGLE

ONLY.CLAMPBOLT

A

STEEL BEAM

EQ

.E

Q.

3 1/2"

SAME FOR VERT., DIAG. &

ANCHORAGE PER DETAILS

CONNECTION TO STRUCTURALSUPPORTING MEMBER TO BE

LONG.

OPTION 1

ADHESIVE

1/2" DIA.THREADED ROD

DRILLED ANDSET IN HILTI HY150

6" MIN.EMBED

SUPPORTEXISTING

EXISTING SUPPORT

NEW INSTALLATION:1/2" DIA. HILTI KWIKBOLT II INSTALLED INNORMAL WT. CONC.,SEE DETAIL 2/A FORINSTALLATION IN LIGHTWT. CONC.

3-1/2" MIN.6" MIN.EMBED EMBED

6" MIN.EMBED

HILTI PRODUCTTECHNICAL GUIDE-HILTI QUICH BOLT 2-HARDCONCRETE-GRADEADHESIVE-APPROVEDFOR SOFTCONCRETE-GLUE AND

EQ.EQ.

VERTICAL&

DIAGONALANGLES B

12'-0" MAXIMUM

SPREADER CHANNEL

SEE SCHEDULE.

PROVIDE ANGLE MEMBERS ASDETERMINED BY A STRUCTURAL ENGINEERPER SPECIFICATION SECTION 16071.

LONG.ANGLEASREQ'D(SHOWNDASHED)

NOTE:

STEEL BEAM

CONCRETE FLOOR

STAND BASE:L4"X4"X1/4"

STAND BASE:L4"X4"X1/4"

EMBED

L3"X3"X1/4"X3" LONG

CONCRETE ANCHORAGE DETAIL

TOP VIEW

STAND BASE:L4"X4"X1/4"

SIDE VIEW

3 SIDE TYP.

KWIK BOLT II, PERW/(1) 1/2"X7" HILTI

ANCHOR ANGLES:

WELD

1/8"

EXISTING RETROFIT:L3"X3"X1/4"X3" LONGW/ 1/2" DIA. HILTI KWIKBOLT II INSTALLED INNORMAL WT. CONC.,SEE DETAIL 2/A FORINSTALLATION IN LIGHTWT. CONC.

6" MIN.EMBED

WELD 3 SIDES

WELD

TYP.

THRUSIDE

WELD

1/8"

6" MIN.

1/8"TYP.

NTS

NTS

NTS

NTS

NTS

NTS

JOHANSEN

No. 185978

PETER E.

LIC

EN

SE

D

P ROF E S S I ONA L

EN

GI N

EE

R

ST A T E O F U T A H

HKS ARCHITECTS, INC.

SALT LAKE CITY, UTAH 84101

ARCHITECT

90 SOUTH 400 WEST, SUITE 110

REVISION

PROJECT NUMBERS

DATE

SHEET TITLE

PLO

TD

AT

E:

INTERMOUNTAIN HEALTHCARE

SALT LAKE CITY, UTAH 84111

OWNER

36 SOUTH STATE STREET

ISSUE

© 2016 HKS, INC.

IN

TE

RM

OU

NT

AIN

LA

YT

ON

PA

RK

WA

Y C

LIN

IC

PC

H A

UD

IO

LO

GY

CL

IN

IC

2018

SHEET NO.

HKS:

201 W

ES

T L

AY

TO

N P

AR

KW

AY

L

AY

TO

N, U

T 8

4041

12/07/18

12/7

/2018 1

2:5

8:3

4 P

M

C:\U

se

rs\jrw

\Do

cu

me

nts

\20

18

06

76

EL

EC

CE

NT

RA

L_jr

w.r

vt

EP503

DETAILS

12/07/18

22506.000

CONSTRUCTION

DOCUMENTS

NO. DESCRIPTION DATE

C

4

TYPICAL 2-PORTDATA OUTLET

3

TYPICAL 'WAP'DATA OUTLET

1

WIRELESS APMOUNTING DETAIL

2STATION PATCH PANEL, (SPP1), TDR

NO SCALENO SCALE

01 02

01 11 0101

CAT 6A, RJ-45INSERT, YELLOW,TYP

SURFACE MOUNTBOX

LABEL, STATIONNUMBER

(EXAMPLE ONLY)

01 02

01 11 01

CAT 6A, RJ-45INSERT, BLUE,TYP(MOUNT INANGLEDPOSITION INFACEPLATE)

LABEL, STATIONNUMBER(EXAMPLE ONLY)

SINGLE GANGFACEPLATE

01

BLANK INSERT,TYP

NO SCALE

SURFACE MOUNTED 2POSITION BOX WITH 2 CAT 6JACKS, TYP.

(2) CAT 6 PATCH CORDS, TYP.

DROP CEILING MOUNT

GROMMET

(2) CAT 6 CABLES, TYP.(SUPPORT BY J-HOOKS)

NO SCALE

1 RU PANEL

CAT 6A JACKS, TYPICAL

JOHANSEN

No. 185978

PETER E.

LIC

EN

SE

D

P ROF E S S I ONA L

EN

GI N

EE

R

ST A T E O F U T A H

HKS ARCHITECTS, INC.

SALT LAKE CITY, UTAH 84101

ARCHITECT

90 SOUTH 400 WEST, SUITE 110

REVISION

PROJECT NUMBERS

DATE

SHEET TITLE

PLO

TD

AT

E:

INTERMOUNTAIN HEALTHCARE

SALT LAKE CITY, UTAH 84111

OWNER

36 SOUTH STATE STREET

ISSUE

© 2016 HKS, INC.

IN

TE

RM

OU

NT

AIN

LA

YT

ON

PA

RK

WA

Y C

LIN

IC

PC

H A

UD

IO

LO

GY

CL

IN

IC

2018

SHEET NO.

HKS:

201 W

ES

T L

AY

TO

N P

AR

KW

AY

L

AY

TO

N, U

T 8

4041

12/07/18

12/7

/2018 1

2:5

8:3

8 P

M

C:\U

se

rs\jrw

\Do

cu

me

nts

\20

18

06

76

EL

EC

CE

NT

RA

L_jr

w.r

vt

ET601

TELECOM DETAILS

12/07/18

22506.000

CONSTRUCTION

DOCUMENTS

NO. DESCRIPTION DATE

J

J

J

J

JJ J

J

J

J

J

J

BC

SD

D

Z

BCB

BSE

E

SE

SR

GR

CBGR

RAD

RCB2

StaffCLOSED

StaffOPEN

R

NOTE:

1. PAGING SYSTEM BASED ON BIAMP VOCIA PLATFORM.

2. ZONE DETERMINATION SHALL BE MADE BY HOSPITAL.

3. "PAGE" LOCATIONS AND RM NUMBERS:

PAGE 1a - TEC 12400

PAGE 1b - DATA 14800

PAGE 2a - TDR 22142

PAGE 2b - DATA 24876

PAGE 3 - TDR 31116

PAGE 4 - TDR 42160

PAGE 5 - TDR 52159

NETWORKSWITCH

(NIC)

TEC 12400

VI-6

VOIP-1

SIPTRUNKINPUT

NETWORKSWITCH

(NIC)

S S

S S

TYPICAL SPEAKER ZONES

S S

TYPICAL OF ALL PAGE LOCATIONS

S

S

S

TERMINAL BLOCK (WALL MOUNTED)

MS-1

TTS-1

VA-8600e

LAN

P P

P P

P P

P

P

P

1OVERHEAD PAGING SYSTEM DIAGRAM (VOCIA)NO SCALE

#1CR

#3

#2CR

#4

CR

AUTO OPENER

CR

#5

CR

AUTO OPENER

#6CR

CARD ACCESS DOOR TYPE SCHEDULEDOORTYPE #

SYMBOL DESCRIPTION PROTECTED SIDE ELEVATION UNPROTECTED SIDE ELEVATION LOCK TYPE(S) DIVISION OF WORK AND COMMENTS

TYPE 1

HARDWARE SETS:

1.W R2, 3.W R2

SINGLE DOOR, WIRELESS CARD

READER

(FREE EGRESS)

*HARDWARE BY 281300

WIRELESSMORTISE LOCKSET

SECURITY CONTRACTOR PROVIDES:

• WEL

HARDWARE CONTRACTOR PROVIDES:

• NONE

LOCK CONTROLLED BY:

• CR

TYPE 3

HARDWARE SETS:

7.0, 8.0

SINGLE DOOR, 1 CARDREADER,(FREE EGRESS)

ELECTRICLOCKSET

SECURITY CONTRACTOR PROVIDES:

• CR, L/PS, FH, DH

HARDWARE CONTRACTOR PROVIDES:

• EL, EPT

LOCK CONTROLLED BY:

• CR

TO ACS

TYPE 2

HARDWARE SETS:

5.W R2, 6.W R2

SINGLE DOOR, WIRELESS

CARD READER

(FREE EGRESS)

EM CLOSER WITH MOTION

DETECTOR

*HARDWARE BY 281300

WIRELESSMORTISE LOCKSET

SECURITY CONTRACTOR PROVIDES:

• WEL

HARDWARE CONTRACTOR PROVIDES:

• EM CLOSER

LOCK CONTROLLED BY:

• CR

TYPE 4

HARDWARE SET:

1.0

SINGLE DOOR, 1 CARD READER

WITH AUTO OPENER

CONTINUOUS HINGE POWER

TRANSFER

ELECTRIC EXITDEVICE WITHAUTO OPENER

TO ACS

SECURITY CONTRACTOR PROVIDES:

• CR, FH, DH, L/PS

HARDWARE CONTRACTOR PROVIDES:

• EED, EH, ADA

LOCK CONTROLLED BY:

• CR

TYPE 5 TO ACS

HARDWARE SET:

2.0

DOUBLE DOOR, 1 CARD READER(1 FIXED LEAF WITH AUTOOPENER)

(EGRESS SIDE)

ELECTRIC STRIKE SECURITY CONTRACTOR PROVIDES:

• CR, L/PS, FH, DH

HARDWARE CONTRACTOR PROVIDES:

• ES, EH

LOCK CONTROLLED BY:

• CR

TYPE 6

HARDWARE SETS:

3, 4

SINGLE DOOR, NETWORK CARD

READER

(FREE EGRESS)

FRAME POWER TRANSFER OR

CONTINUOUS HINGE

*HARDWARE BY 281300

ACCESS MORTISELOCKSET

SECURITY CONTRACTOR PROVIDES:

• AEL, FH, DH, L/PS

HARDWARE CONTRACTOR PROVIDES:

• EPT

LOCK CONTROLLED BY:

• CR

TO ACS

AUDIO-VIDEO SYSTEM EQUIPMENT LISTTHE ITEMS INDICATED BELOW SHALL NOT BE CONSTRUED AS A "BILL OF MATERIALS". THIS LIST IDENTIFIES ITEMS OF SIGNIFICANCE USED DURING THE DESIGN OFTHE ELECTRONIC SYSTEMS INSTALLATION. WHERE THE ITEMS INDICATED ARE ONE PORTION OF AN ASSEMBLY, THE ENTIRE ASSEMBLY SHALL BE PROVIDEDUNLESS SPECIFIED OTHERWISE. PROVIDE ALL MISCELLANEOUS HARDWARE AND SUPPORTS WHICH MAY NOT BE LISTED HERE, FOR A COMPLETE INSTALLATION.COMPARE CATALOG NUMBERS WITH DESCRIPTIONS AND NOTIFY ENGINEER OF DISCREPANCIES PRIOR TO BID. IF CATALOG NUMBERS DO NOT MATCHDESCRIPTIONS, THE DESCRIPTIONS TAKE PRECEDENCE. PROVIDE COMPLETE SUBMITTAL FOR APPROVAL PRIOR TO PURCHASING ANY EQUIPMENT OR CABLE.REFER TO SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.

SYMBOL DESCRIPTION QTY ACCEPTABLE TYPE

OFPTP

TOUCH PANEL, WALL MOUNTED, 5" DISPLAY CRESTRON TSW-552

OFPDIGITAL PRESENTATION SYSTEM DMPS3-300-CDMPS

DRXOFP CRESTRON DM-4K-100C

DTXOFPHDMI AND XGA TWISTED PAIR TRANSMITTER, 8G+ CRESTRON DM-TX-201-C

TWISTED PAIR DIGITAL VIDEO RECEIVER, HDMI OUT, 8G+

CONNECTION PANEL #1, WALL MOUNTED (TRANSMITTER) OFP CRESTRON DM-TX-200-C-2GCP1

OFPMICROPHONE INPUT, 3 PIN, XLR SWITCHCRAFT

OFP70V POWER AMPLIFIER ATLAS SOUND AA50 PHD

AMP

IROFP CRESTRON GLS-PART-CNPARTITION SENSOR

MONOFP NEC V801 (80")LARGE VIDEO DISPLAY

OFP ATLAS SOUND FAP82TSPEAKER, 8", CEILING MOUNTED W/ GRILLES

OFP MIDDLE ATLANTIC ERK-2128EQUIPMENT RACK #1, FLOOR MOUNTED, 46RU, 28" DEEP, PIVOTING,REAR RACK RAILS.AV

M

CP2

HDMI

SW

HDMI

D/A

CONNECTION PANEL #2, WALL MOUNTED OR AS NOTED (RECEIVER)

HDMI DISTRIBUTION AMPLIFIER W/ AUDIO CONVERSION

OFP CRESTRON DM-RMC-4K-100-C-1G

OFP CRESTRON

OFP CRESTRON HD-DA-2HDMI DISTRIBUTION AMPLIFIER , 1 x 2

NURSE CALL SYMBOL LISTSYMBOL MANUF. BACKBOX BOX MOUNTING HEIGHTPART # DESCRIPTION

P2520A07 CODE BLUE PUSH BUTTON SWITCH

P2506NNC8A00-D ICON BASED-LIGHT LED DOME LIGHTSTEEL CITY CYLE-3/4, RACO 591,

OR ANY OTHER 3.5" DEEP SINGLE GANG BACK BOX.

P2520A08 STAFF EMERGENCY PUSH BUTTON SWITCH

P2500NNC1B00 STAFF CONSOLE, DESK MOUNT

4" SQUARE 3.5" DEEP BACK BOX WITH SINGLE GANG MUD RING.

REFER TO ELEVATION

P2519NNC1A24 POE SWITCH

P2520B01 BATH SWITCH, W/CANCEL, SUPERVISED

HILL-ROM P2521B02 UPS, RACK MOUNTABLE, 2U - NON-SEISMIC

NCM

P2506NNC1B00 DOME LIGHT, SINGLE LEDRACO 231, WITH RACO 778 RING,

OR ANY OTHER 4" SQUARE 2 1/8" DEEP BACK BOX.

P2505NNC1B00 AUDIO STATION BED CONNECTOR (ASBC)

P2506NNC8A00-7 ICON BASED-LIGHT LED ZONE LIGHT

DRAWINGS

REFER TO ELEVATIONDRAWINGS

REFER TO ELEVATIONDRAWINGS

REFER TO ELEVATIONDRAWINGS

REFER TO ELEVATIONDRAWINGS

REFER TO ELEVATIONDRAWINGS

REFER TO ELEVATION

DRAWINGS

REFER TO ELEVATIONDRAWINGS

REFER TO ELEVATIONDRAWINGS

REFER TO ELEVATIONDRAWINGS

STAFF STATION - STANDARD ROOM STATION W/O CODEHILL-ROM

HILL-ROM

HILL-ROM

HILL-ROM

HILL-ROM

HILL-ROM

HILL-ROM

HILL-ROM

HILL-ROM

HILL-ROM

POE-24

HILL-ROM

HILL-ROM

HILL-ROM

HILL-ROM

HILL-ROM

HILL-ROM

HILL-ROM

P2520B02

P2594NNC1B01

P2594NNC2C00

P2594NNC2C11

P2594NNC4A10

P2599NNC2A00

RTLS-CLOSED

RTLS-OPEN

GARVIN 52181-3/4, WITH GARVIN 52C13 RING, OR ANY OTHER

BATH SWITCH, W/O CANCEL, SUPERVISED

GRAPHICAL ROOM STATION (GRS) - STAFF

GRAPHICAL ROOM STATION (GRS) - PATIENT

REMOTE AUDIO DEVICE

RCB2 ROOM CONTROL BOARD

RTLS - STAFF LOCATING LOCATION-CLOSED AREA

RTLS - STAFF LOCATING LOCATION-GLASS/OPEN AREA

REFER TO ELEVATIONDRAWINGS

REFER TO ELEVATIONDRAWINGS

REFER TO ELEVATIONDRAWINGS

REFER TO ELEVATIONDRAWINGS

REFER TO ELEVATIONDRAWINGS

REFER TO ELEVATIONDRAWINGS

REFER TO ELEVATIONDRAWINGS

REFER TO ELEVATIONDRAWINGS

STEEL CITY 58371 3/4R, RACO 561,

OR ANY OTHER SINGLE GANG BACK BOX.

STEEL CITY CYLE-3/4, RACO 591,

OR ANY OTHER 3.5" DEEP SINGLE GANG BACK BOX.

OR ANY OTHER 2.5" DEEP, TWO OR THREE GANG BACK BOX.

RACO 561 BACK BOX,

OR ANY OTHER 2.5" DEEP SINGLE GANG BACK BOX.

RACO 561 BACK BOX,

OR ANY OTHER 2.5" DEEP SINGLE GANG BACK BOX.

RACO 561 BACK BOX,

OR ANY OTHER 2.5" DEEP SINGLE GANG BACK BOX.

RACO 561 BACK BOX,

OR ANY OTHER 2.5" DEEP SINGLE GANG BACK BOX.

OR ANY OTHER 2.5" DEEP, TWO OR THREE GANG BACK BOX.

OR ANY OTHER 2.5" DEEP, TWO OR THREE GANG BACK BOX.

OR ANY OTHER 2.5" DEEP, TWO OR THREE GANG BACK BOX.

STEEL CITY GW-225G, RACO 691

OR ANY OTHER 3.5" DEEP, TWO OR THREE GANG BACK BOX.

STEEL CITY GW-235G, RACO 696

STEEL CITY GW-225G, RACO 691

STEEL CITY GW-225G, RACO 691

STEEL CITY GW-225G, RACO 691

OR ANY OTHER TWO GANG BACK BOX.

STEEL CITY GW-225G, RACO 691

OR ANY OTHER TWO GANG BACK BOX.

STEEL CITY GW-225G, RACO 691

P2594NNC3B00 GRAPHICAL ANNUNCIATORREFER TO ELEVATION

GADRAWINGS

HILL-ROMSTEEL CITY 58371 3/4R, RACO 561,

OR ANY OTHER SINGLE GANG BACK BOX.

P2516A01 EQUIPMENT RECEPTACLE, WITH CALL CORDREFER TO ELEVATIONDRAWINGS

HILL-ROMEQ STEEL CITY 58371 3/4R, RACO 561,

OR ANY OTHER SINGLE GANG BACK BOX.

P2594NNC3A00 STAFF CONSOLE, WALL MOUNTREFER TO ELEVATION

NCMDRAWINGS

HILL-ROMSTEEL CITY 58371 3/4R, RACO 561,

OR ANY OTHER SINGLE GANG BACK BOX.W

MAP985A REMOTE ENTERTAINMENT STATIONOR ANY OTHER TWO GANG BACK BOX.

REFER TO ELEVATIONDRAWINGS

STEEL CITY GW-225C, RACO 691CURBELL

StaffBAY

HILL-ROM RTLS-BAY RTLS - STAFF LOCATING LOCATION-BAYREFER TO ELEVATIONDRAWINGSOR ANY OTHER TWO GANG BACK BOX.

STEEL CITY GW-225G, RACO 691

HILL-ROM PILLOW SPEAKEKER, REQUIRES ASBC.

P2520A07 PUSH FOR ASSISTANCE PUSH BUTTON SWITCHREFER TO ELEVATIONRACO 561 BACK BOX,

HILL-ROMBPC

UPS, APCRackmount Non-Seismic

STAFF STATION - STANDARD ROOM STATION W/ CODEHILL-ROM P2594NNC1B01REFER TO ELEVATIONDRAWINGSOR ANY OTHER 2.5" DEEP, TWO OR THREE GANG BACK BOX.

STEEL CITY GW-225G, RACO 691SRCB

P2520A07 CODE PINK PUSH BUTTON SWITCHREFER TO ELEVATION

HILL-ROMB

CP RACO 561 BACK BOX,

ABBREVIATIONSDBL = DOUBLE

DIR = DIRECTION

HDWR = HARDWARE

C = CONDUIT

4SQ = FOUR SQUARE

W/ = WITH

1G = 1 GANG

PWR = POWER

ACC = ACCESSIBLE

OCC = OCCUPANCY

TYP = TYPICAL

L/PS = LOCK POWER SUPPLY

CR = CARD READER

CI = DOOR CONTACT INDICATOR

EPT = ELECTRIC POWER TRANSFER

ES = ELECTRIC STRIKE

ED = EXIT DEVICE

ML = ELECTROMAGNETIC LOCK

KS = KEY SWITCH

ACS = ACCESS CONTROL SYSTEM

EL = ELECTRIC LOCKSET

MD = MOTION DETECTOR

TLC = TIME/SYSTEM LOCK CONTROL

ELC = EMERGENCY LOCK CONTROL

IDS = INTRUSION DETECTION SYSTEM

ADA = AUTO DOOR OPENER

REX = REQUEST TO EXIT

FA = FIRE ALARM SYSTEM

OFP = OBTAIN FROM PLANS

A/R = AS REQUIRED

EED = ELECTRIC EXIT DEVICE

AEL = ACCESS ELECTRIC LOCKSET

AED = ACCESS ELECTRIC EXIT DEVICE

FH = FRAME HARNESS

DH = DOOR HARNESS

EH = ELECTRIC HINGE

PB = PUSH BUTTON RELEASE

PROVIDE RACEWAY AND EQUIPMENT AS INDICATED FOR CARD ACCESS

DOOR TYPE INDICATED. REFER TO SECTION 281300 AND CARD ACCESS

LOCK CONTROL DETAILS FOR ADDITIONAL REQUIREMENTS.

PROVIDE CONCEALED .75" C TYPICAL FOR LINES SHOWN TO DEVICE BOXES

ON PROTECTED SIDE AND UNPROTECTED SIDE ELEVATIONS.

CONFIRM CORRECT CARD ACCESS DOOR RACEWAY, LOCK VOLTAGE, AND

EXIT SWITCH CURRENT RATING (2 AMPS MIN.) WITH DIV. 8 FURNISHED CARD

ACCESS DOOR HARDWARE PER DIV. 8 DOOR HARDWARE SPECIFICATIONS.

LOCATE CARD READER BOX AS INDICATED ON FLOOR PLANS. RACEWAY

AND BOXES BY DIV. 26. REFER TO 281300 FOR CARD ACCESS SYSTEM

REQUIREMENTS.

DOUBLE 4SQ J-BOX ON PROTECTED SIDE OF DOORWAY (SIDE OPPOSITE OF

CARD READER) ABOVE ACCESSIBLE CEILING OR IN OTHER ACCESSIBLE

LOCATION. PROVIDE COVER FOR J-BOX.

ELECTRIC LOCKING HARDWARE (MAG LOCKS, ELECTRIC STRIKES, POWER

TRANSFER HINGES, ETC.) BY DIV 8. REVIEW DOOR HARDWARE FURNISHED

AND VERIFY LOCK VOLTAGES AND OPERATIONAL FUNCTIONALITY OF LOCKS.

CONTACT ENGINEER WITH QUESTIONS OR CONCERNS.

4.

3.

1.

2.

NOTES

5.

6.

CARD READERIN DOORHARDWARE

WIRELESSELECTRICLOCKSET

4SQ J-BOXABOVE ACC

CEILING

ELECTRIC POWERTRANSFER 1G BOX INFRAME

FRAME HARNESSIN .75" C

DOOR HARNESSIN DOOR

ELECTRICLOCKSET

CARD READERIN DOORHARDWARE

4SQ J-BOXABOVE ACC

CEILING

.75" C (TYP)

WIRELESSELECTRICLOCKSET

PP = PUSH PAD ACTUATOR

EDL = ELECTRIC DEADLATCH

EED = ELECTRIC EXIT DEVICE

EM CLOSER 1GBOX IN FRAME

.75" C (TYP)

4SQ J-BOXABOVE ACC

CEILING

CARD READER4SQ BOX W/ 1GRING

4SQ J-BOXABOVE ACC

CEILING

ELECTRIC POWERHINGE 1G BOX INFRAME

FRAME HARNESSIN .75" C

DOOR HARNESSIN DOOR

ELECTRICEXIT DEVICE

.75" C (TYP)

4SQ J-BOXABOVE ACC

CEILING

CARD READER4SQ BOX W/ 1GRING

.75" C (TYP)

4SQ J-BOXABOVE ACC

CEILING

CARD READER4SQ BOX W/ 1GRING

POWER HINGE 1GBOX IN FRAME

ELECTRIC STRIKE FIXED LEAF

DOOR HARNESSIN DOOR

FRAMEHARNESS IN .75"

C (TYP)

4SQ J-BOXABOVE ACC

CEILINGPEL = NETWORK MORTISE LOCK (POE)

CARD READERIN DOORHARDWARE

4SQ J-BOXABOVE ACC

CEILING

ELECTRIC POWERTRANSFER 1G BOXIN FRAME

FRAME HARNESSIN .75" C

DOOR HARNESSIN DOOR

ELECTRICLOCKSET

40"

40"

40"

JOHANSEN

No. 185978

PETER E.

LIC

EN

SE

D

P ROF E S S I ONA L

EN

GI N

EE

R

ST A T E O F U T A H

HKS ARCHITECTS, INC.

SALT LAKE CITY, UTAH 84101

ARCHITECT

90 SOUTH 400 WEST, SUITE 110

REVISION

PROJECT NUMBERS

DATE

SHEET TITLE

PLO

TD

AT

E:

INTERMOUNTAIN HEALTHCARE

SALT LAKE CITY, UTAH 84111

OWNER

36 SOUTH STATE STREET

ISSUE

© 2016 HKS, INC.

IN

TE

RM

OU

NT

AIN

LA

YT

ON

PA

RK

WA

Y C

LIN

IC

PC

H A

UD

IO

LO

GY

CL

IN

IC

2018

SHEET NO.

HKS:

201 W

ES

T L

AY

TO

N P

AR

KW

AY

L

AY

TO

N, U

T 8

4041

12/07/18

12/7

/2018 1

2:5

7:5

3 P

M

C:\U

se

rs\jrw

\Do

cu

me

nts

\20

18

06

76

EL

EC

CE

NT

RA

L_jr

w.r

vt

EC601

SYSTEMS DIAGRAMS &

DETAILS

12/07/18

22506.000

CONSTRUCTION

DOCUMENTS

NO. DESCRIPTION DATE

J

J

J

J

J

J

J

J

J

J

J

J

UTP (CAT6A)

VSS1b

UTP (CAT6A)

VSS2a

UTP (CAT6A)

VSSX

UTP (CAT6A)

PATCHPANEL

OWNER'SLAN SWITCH

PATCHPANEL

PATCHPANEL

PATCHPANEL

CAM 1

CAM 2

CAM 1

CAM 2

CAM 1

CAM 2

CAM 1

CAM 2

OWNER'SLAN SWITCH

OWNER'SLAN SWITCH

OWNER'SLAN SWITCH

TYPICAL OFALL CAMERA

TYPES

TYPICAL OFALL CAMERA

TYPES

TYPICAL OFALL CAMERA

TYPES

TYPICAL OFALL CAMERA

TYPES

PATCH CORDS (TYP)BY CONTRACTOR

PATCH CORDS (TYP)BY CONTRACTOR

PATCH CORDS (TYP)BY CONTRACTOR

PATCH CORDS (TYP)BY CONTRACTOR

MON

KB

GENETECVMS

SERVER

OWNER'SLAN SWITCH

TYPICALCLIENTWORKSTATION

120 VAC

LOCK

POWER

SUPPLY

DOORWAY, TYPICAL- SEE

EQUIPMENT LIST &

RACEWAY SCHEDULECR

CR

DOORWAY, TYPICAL- SEE

EQUIPMENT LIST &

RACEWAY SCHEDULE

ACS SYSTEM RISER

REQUEST TO OPEN (TYP)R

FIRE ALARM INTERFACE

ACCESS

CONTROLLER/

PROCESSOR

(16 READERS)

OWNER'S

LAN SWITCH

OWNER'S

LAN SWITCH

120 VAC

LOCK

POWER

SUPPLY

DOORWAY, TYPICAL- SEE

EQUIPMENT LIST &

RACEWAY SCHEDULECR

CR

DOORWAY, TYPICAL- SEE

EQUIPMENT LIST &

RACEWAY SCHEDULE

REQUEST TO OPEN (TYP)R

ACCESS

CONTROLLER/

PROCESSOR

(16 READERS)

OWNER'S

LAN SWITCH

ACS1a

ACS1b

120 VAC

LOCK

POWER

SUPPLY

DOORWAY, TYPICAL- SEE

EQUIPMENT LIST &

RACEWAY SCHEDULECR

CR

DOORWAY, TYPICAL- SEE

EQUIPMENT LIST &

RACEWAY SCHEDULE

REQUEST TO OPEN (TYP)R

ACCESS

CONTROLLER/

PROCESSOR

(16 READERS)

OWNER'SLAN SWITCH

ACS2a

120 VAC

LOCK

POWER

SUPPLY

TYPE #5 CARD ACCESS

DOORWAY, TYPICAL- SEE

EQUIPMENT LIST &

RACEWAY SCHEDULECR

#4

CR

#5

TYPE #4 CARD ACCESS

DOORWAY, TYPICAL- SEE

EQUIPMENT LIST &

RACEWAY SCHEDULE

REQUEST TO OPEN (TYP)R

FIRE ALARM INTERFACE

ACCESS

CONTROLLER/

PROCESSOR

(16 READERS)

OWNER'S

LAN SWITCH

ACSX

OWNER'S LAN NETWORK (TYP)

FIRE ALARM INTERFACE

FIRE ALARM INTERFACE

FIRE ALARM INTERFACE

OWNER'S LAN NETWORK (TYP)

ACS HEADEND

*VSS1a

SERVER

CAT 6APATCHPANEL

AH CR MEDICAL CABINETS AND REDGES

#1 CR TYPICAL FOR DOOR TYPES 1, 2, 3, AND 7

CAT 6APATCHPANEL

AH CR MEDICAL CABINETS AND REDGES

#1 CR TYPICAL FOR DOOR TYPES 1, 2, 3, AND 7

CAT 6APATCHPANEL

AH CR MEDICAL CABINETS AND REDGES

#1 CR TYPICAL FOR DOOR TYPES 1, 2, 3, AND 7

CAT 6APATCHPANEL

AH CRMEDICAL CABINETSAND REDGES

#1 CRTYPICAL FOR DOORTYPES 1, 2, 3, AND 7

NOTES:

1. ACCESS CONTROL SYSTEM BASED UPON MULTIPLE CARD READERS

PER ACCESS CONTROLLER/PROCESSOR. PROVIDE QUANTITY OF

iSTAR PRO AND iSTAR ULTRA CONTROLLER'S PER ACS BASED ON

IDENTIFIED ACCESS READER LOCATIONS SHOWN IN THE EY SHEET

SERIES, PLUS 20%.

2. ACCESS CONTROLLER "ACS" INDICATED SHALL INCLUDE ANY

ISOLATION MODULES, BUFFER MODULES, EXTERNAL POWER

SUPPLIES, INPUT/OUTPUT MODULES, OR FORMAT CONVERTER

MODULES (NOT SHOWN) REQUIRED TO SUPPORT CARD READER OR

KEYPAD TYPES INDICATED, FOR COMPLETE AND FUNCTIONING CARD

READER AND DOOR CONTROL.

3. PROVIDE SEPARATE WIRE PAIRS FOR REQUEST TO EXIT AND DOOR

CONTACT INDICATOR, FROM ACCESS DOOR TO ACCESS CONTROLLER

PANEL. SINGLE PAIR, FROM ACCESS DOOR TO CONTROLLER PANEL,

FOR REQUEST TO EXIT AND DOOR CONTACT INDICATOR, NOT

ACCEPTABLE.

4. REQUEST TO EXIT AND DOOR CONTACT INDICATOR CIRCUITS SHALL

BE SUPERVISED FOR OPEN CIRCUIT OR SHORT CIRCUIT FAULTS

BETWEEN THE DEVICE CONTACTS AND ACCESS CONTROLLER.

5. LENEL DOOR CONTROLLERS SHALL BE INSTALLED AT THE IDENTIFIED

"ACS" LOCATIONS IN THE FOLLOWING TDR ROOMS:

ACS1a - TDR 11303

ACS1b - TDR 12807

ACSC - TDR C122

ACS2a - TDR 21221

ACS2b - TDR 22607

ACS3a - TDR 31462

ACS3b - TDR 32402

ACS4a - TDR 41318

CR( )

TYPE #5 CARD ACCESS

#4

#5

TYPE #4 CARD ACCESS

CR( )

TYPE #5 CARD ACCESS

#4

#5

TYPE #4 CARD ACCESS

CR( )

TYPE #5 CARD ACCESS

#4

#5

TYPE #4 CARD ACCESS

CR( )

1

* COORDINATE MOUNTING HEIGHTS WITH ARCHITECTURAL ELEVATIONS BEFORE INSTALLATION.

SECURITY EQUIPMENT SCHEDULE

SEE SECTION 281300

SEE SECTION 281300

SEE SECTION 281600

SEE VSS CAMERA/ENCLOSURE TYPE

REFER TO CARD ACCESS DOOR

TYPE SCHEDULE & SECTION 281300

SCHEDULE

ACCEPTABLE TYPES

VSS CAMERA/ENCLOSURE TYPE, TYPICAL. REFER TOVSS CAMERA/ENCLOSURE TYPE SCHEDULE.

CARD ACCESS DOOR TYPE, TYPICAL. REFER TO CARDACCESS DOOR TYPE SCHEDULE.

TRANSIENT VOLTAGE SURGE SUPPRESSER "TVSS"

DURESS BUTTON

CARD ACCESS CONTROLLERS & PWR SUPPLIES

SYMBOL DESCRIPTION

CARD READER

OFP4SQ W/ 1GUNDER COUNTER

& STUBS A/R

4"x4" GUTTER

NOTED

72"

J-BOX - 18"

AS

RING

A/R

A/R

SEE SCHEDULE

ROUGH-IN

4SQ W/ 1G

SEE SCHEDULE

SEE SCHEDULE

SEE SCHEDULE

40"

MOUNTING *

RING

OFP

OFP

QTY

OFP

A/R

VIDEO SURVEILLANCE SYSTEM COORDINATE WITH OWNER

CR

#1

RACK MOUNTED

ACS

TVSS

VSS

DESCRIPTION

VSS CAMERA/ENCLOSURE ROUGH-IN SCHEDULE

INCLUDES

INTERIOR CAMERA - FIXED DOME(CEILING MOUNTED)

* JUNCTION BOX ABOVE ACCESSIBLE CEILING WITH 1" CONDUIT TO VSS

EXTERIOR CAMERA - FIXED DOME(WALL MOUNTED)

INTERIOR CAMERA - FIXED DOME(WALL MOUNTED)

* JUNCTION BOX AT +90" ABOVE FINISHED FLOOR, WITH 1" CONDUIT BACK TO VSS

* JUNCTION BOX AT +120" ABOVE FINISHED FLOOR, WITH 1" CONDUIT BACK TO VSS

VSS CAMERA SCHEDULE

TYPEINTERIOR (INT)/EXTERIOR (EXT)

DESCRIPTION AXIS MODEL #

1

2

3

4

5

INT

INT

EXT

INT/EXT

INT/EXT

FIXED DOME, VARIFOCAL, CEILING MOUNT P3354

P3354

Q3505-VE

Q3708-PVE

P3707-PE

FIXED DOME, VARIFOCAL, WALL MOUNT

FIXED DOME, VARIFOCAL, WALL MOUNT

FIXED DOME, WALL MOUNT (180°)

FIXED DOME, CEILING MOUNT (360°)

SEE SECTION 281300DOOR MONITOR - CONTACT INDICATOR SWITCH SEE SCHEDULESEE SCHEDULE OFPCI

PROVIDE APERIO HUB MODEL AH-40-IN2-NNNNAPERIO HUB (IP) CEILING OFP1G BOXAH

PROVIDE HES K100 WIRELESS READER/LOCKSETWIRELESS READER AND LOCKSET FOR MED CABINET PER MANUF.ON CABINET OFPCR

IP INTERCOM WALL STATION OFPI

54"

CARD READER FOR FRIDGE AND/OR FREEZER 4SQ W/ 1G40"RING

OFPCRF

PROVIDE HID READER WITH HES 660 SERIESLOCKSET

PROVIDE AXIS A8004-VE NETWORK VIDEO DOORSTATION

3-GANGVERTICAL BOX

P

1ACCESS CONTROL SYSTEM (ACS) DIAGRAM

2VIDEO SURVEILLANCE SYSTEM (VSS) RISER DIAGRAM

NO SCALENO SCALE - FOR REFERENCE ONLY - SEE ET SHEETS FOR WIRING INFORMATION

JOHANSEN

No. 185978

PETER E.

LIC

EN

SE

D

P ROF E S S I ONA L

EN

GI N

EE

R

ST A T E O F U T A H

HKS ARCHITECTS, INC.

SALT LAKE CITY, UTAH 84101

ARCHITECT

90 SOUTH 400 WEST, SUITE 110

REVISION

PROJECT NUMBERS

DATE

SHEET TITLE

PLO

TD

AT

E:

INTERMOUNTAIN HEALTHCARE

SALT LAKE CITY, UTAH 84111

OWNER

36 SOUTH STATE STREET

ISSUE

© 2016 HKS, INC.

IN

TE

RM

OU

NT

AIN

LA

YT

ON

PA

RK

WA

Y C

LIN

IC

PC

H A

UD

IO

LO

GY

CL

IN

IC

2018

SHEET NO.

HKS:

201 W

ES

T L

AY

TO

N P

AR

KW

AY

L

AY

TO

N, U

T 8

4041

12/07/18

12/7

/2018 1

2:5

7:5

8 P

M

C:\U

se

rs\jrw

\Do

cu

me

nts

\20

18

06

76

EL

EC

CE

NT

RA

L_jr

w.r

vt

EC602

SYSTEMS DIAGRAMS &

DETAILS

12/07/18

22506.000

CONSTRUCTION

DOCUMENTS