11
1 Robust Stability Analysis of LCL Filter Based Synchronverter Under Different Grid Conditions Roberto Rosso, Student Member, IEEE, Jair Cassoli, Giampaolo Buticchi, Senior Member, IEEE, Soenke Engelken, Member, IEEE and Marco Liserre, Fellow, IEEE Abstract—Synchronverters have gained interest due to their capability of emulating synchronous machines (SMs), offering self-synchronization to the grid. Despite the simplicity of the control structure, the adoption of an LCL-filter makes the overall model complex again, posing questions regarding the tuning of the synchronverter and its robustness. The multi-inputs multi- outputs (MIMO) formulation of the problem requires multivari- able analysis. In this paper, the effects of control parameter and grid conditions on the stability of the system are investigated by means of structured singular values (SSV or μ-analysis). A step- by-step design procedure for the control is introduced based on a linearized small-signal model of the system. Then the design repercussions on the stability performance are evaluated through the performed robustness analysis. The developed linearized model is validated against time-domain simulations and labo- ratory experiments. These have been carried out using a power hardware-in-the-loop (PHIL) test bench, which allows to test the synchronverter under different grid conditions. As a conclusion the paper offers a simple guide to tune synchronverters but also a theoretical solid framework to assess the robustness of the adopted design. Index Terms—Synchronverter robust stability analysis, μ- analysis, synchronverter design, power hardware-in-the-loop tests. I. I NTRODUCTION T HE amount of power electronics-based converters con- nected to the grid is growing noticeably causing con- cerns about the stability of the future power system. One of the main issues is related to the decrease of the total inertia of the system, but the risk of possible interactions between controllers of converters operating nearby cannot be underrated. Recent studies have shown that synchronization units of grid connected converters, usually phase-locked loops (PLLs), affect significantly the stability of the converters within their bandwidths [1]. Furthermore, interactions between synchronization units of power converters operating nearby have been observed and especially the fact that such effects are accentuated by weaker grid conditions [2]. During the last decade the concept of virtual synchronous machine (VSM) has been introduced [3]-[7]. Among the proposed control strategies, the synchronverter presented by Zhong et al. [5], [6] has been noted for its easy and intuitive structure and for R. Rosso, J. Cassoli and S. Engelken are with Wobben Re- search and Development (WRD) GmbH, Borsigstr. 26, 26607 Au- rich, Germany (e-mail [email protected], [email protected], [email protected]). G. Buticchi is with the University of Nottingham Ningbo China (UNNC), 199 Taikang East Road, 315100 Ningbo, China (e-mail [email protected].) M. Liserre is with the University of Kiel, Kaiserstr. 2, 24143 Kiel, Germany (e-mail [email protected]). being the first proposed control algorithm in the literature for grid connected converters overcoming completely the need of a dedicated synchronization unit, both for initial synchronization to the main grid as well as during normal operation. Synchronverter design has been recently addressed in sev- eral works [8]-[12]. Some of them rely on strong assumptions, such as grid short circuit ratio (SCR) higher then 10 in order to decouple active and reactive power loops [8]. Recent works presented tuning procedures based on reduced-order models of the system [10], [11]. Pole placement at prescribed locations in order to achieve desired dynamic has been proposed as optimal tuning procedure [11], [12] and eigenvalue analysis is the commonly adopted approach for investigation of stability of grid-connected converters and design purposes [13]. However, none of the works presented in the literature addresses robust stability analysis of the synchronverter. To this extent and according to the multi-inputs multi-outputs (MIMO) nature of the system, multivariable analysis is required [14], [15]. In fact, it is well known that eigenvalues are a poor measure of gain for MIMO systems, since they provide information about a specific system configuration and are not suitable for robust stability analysis and design of multivariable systems, where interactions between inputs and outputs of different channels take place [14]. It is common practice in the power electronics community to represent the grid as a Th´ evenin equivalent with a restive- inductive impedance, whose parameters are calculated accord- ing to the short circuit power at the point of common coupling (PCC) and the estimated X /R ratio [16]. Unfortunately, this representation might be often inaccurate since grid conditions change substantially during the day, due to the presence of other converters operating nearby or due to the variation of the number and characteristics of connected loads. An efficient way for modelling such effects would be to include uncer- tainties on the nominal plant. In this scenario, the structured singular values (SSVs) analysis (commonly μ-analysis) has been proven to be an efficient and reliable way for assessing robust stability of MIMO systems [14], [15], [17]. In this paper, the μ-analysis is performed to assess the robust stability of an LCL grid connected synchronverter. The model developed in [10], based on linearized equations of the system, is adopted for the investigation. A design procedure of the synchronverter, using reduced-order models of active and reactive power loops is presented, which relys on nominal filter parameters and grid conditions. Subsequently, the μ-analysis is performed according to a defined uncertainty function, in order to assess the effects of variations of control parameters

Robust Stability Analysis of LCL Filter Based ...eprints.nottingham.ac.uk/55122/1/TPEL-Reg-2018-08-1721.pdf · robust stability of an LCL grid connected synchronverter. The model

  • Upload
    others

  • View
    13

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Robust Stability Analysis of LCL Filter Based ...eprints.nottingham.ac.uk/55122/1/TPEL-Reg-2018-08-1721.pdf · robust stability of an LCL grid connected synchronverter. The model

1

Robust Stability Analysis of LCL Filter BasedSynchronverter Under Different Grid ConditionsRoberto Rosso, Student Member, IEEE, Jair Cassoli, Giampaolo Buticchi, Senior Member, IEEE, Soenke

Engelken, Member, IEEE and Marco Liserre, Fellow, IEEE

Abstract—Synchronverters have gained interest due to theircapability of emulating synchronous machines (SMs), offeringself-synchronization to the grid. Despite the simplicity of thecontrol structure, the adoption of an LCL-filter makes the overallmodel complex again, posing questions regarding the tuning ofthe synchronverter and its robustness. The multi-inputs multi-outputs (MIMO) formulation of the problem requires multivari-able analysis. In this paper, the effects of control parameter andgrid conditions on the stability of the system are investigated bymeans of structured singular values (SSV or µ-analysis). A step-by-step design procedure for the control is introduced based ona linearized small-signal model of the system. Then the designrepercussions on the stability performance are evaluated throughthe performed robustness analysis. The developed linearizedmodel is validated against time-domain simulations and labo-ratory experiments. These have been carried out using a powerhardware-in-the-loop (PHIL) test bench, which allows to test thesynchronverter under different grid conditions. As a conclusionthe paper offers a simple guide to tune synchronverters but alsoa theoretical solid framework to assess the robustness of theadopted design.

Index Terms—Synchronverter robust stability analysis, µ-analysis, synchronverter design, power hardware-in-the-looptests.

I. INTRODUCTION

THE amount of power electronics-based converters con-nected to the grid is growing noticeably causing con-

cerns about the stability of the future power system. Oneof the main issues is related to the decrease of the totalinertia of the system, but the risk of possible interactionsbetween controllers of converters operating nearby cannot beunderrated. Recent studies have shown that synchronizationunits of grid connected converters, usually phase-locked loops(PLLs), affect significantly the stability of the converterswithin their bandwidths [1]. Furthermore, interactions betweensynchronization units of power converters operating nearbyhave been observed and especially the fact that such effectsare accentuated by weaker grid conditions [2]. During the lastdecade the concept of virtual synchronous machine (VSM)has been introduced [3]-[7]. Among the proposed controlstrategies, the synchronverter presented by Zhong et al. [5],[6] has been noted for its easy and intuitive structure and for

R. Rosso, J. Cassoli and S. Engelken are with Wobben Re-search and Development (WRD) GmbH, Borsigstr. 26, 26607 Au-rich, Germany (e-mail [email protected], [email protected],[email protected]).

G. Buticchi is with the University of Nottingham Ningbo China (UNNC),199 Taikang East Road, 315100 Ningbo, China (e-mail [email protected].)

M. Liserre is with the University of Kiel, Kaiserstr. 2, 24143 Kiel, Germany(e-mail [email protected]).

being the first proposed control algorithm in the literature forgrid connected converters overcoming completely the need of adedicated synchronization unit, both for initial synchronizationto the main grid as well as during normal operation.

Synchronverter design has been recently addressed in sev-eral works [8]-[12]. Some of them rely on strong assumptions,such as grid short circuit ratio (SCR) higher then 10 in orderto decouple active and reactive power loops [8]. Recent workspresented tuning procedures based on reduced-order models ofthe system [10], [11]. Pole placement at prescribed locations inorder to achieve desired dynamic has been proposed as optimaltuning procedure [11], [12] and eigenvalue analysis is thecommonly adopted approach for investigation of stability ofgrid-connected converters and design purposes [13]. However,none of the works presented in the literature addresses robuststability analysis of the synchronverter. To this extent andaccording to the multi-inputs multi-outputs (MIMO) natureof the system, multivariable analysis is required [14], [15]. Infact, it is well known that eigenvalues are a poor measure ofgain for MIMO systems, since they provide information abouta specific system configuration and are not suitable for robuststability analysis and design of multivariable systems, whereinteractions between inputs and outputs of different channelstake place [14].

It is common practice in the power electronics communityto represent the grid as a Thevenin equivalent with a restive-inductive impedance, whose parameters are calculated accord-ing to the short circuit power at the point of common coupling(PCC) and the estimated X /R ratio [16]. Unfortunately, thisrepresentation might be often inaccurate since grid conditionschange substantially during the day, due to the presence ofother converters operating nearby or due to the variation ofthe number and characteristics of connected loads. An efficientway for modelling such effects would be to include uncer-tainties on the nominal plant. In this scenario, the structuredsingular values (SSVs) analysis (commonly µ-analysis) hasbeen proven to be an efficient and reliable way for assessingrobust stability of MIMO systems [14], [15], [17].

In this paper, the µ-analysis is performed to assess therobust stability of an LCL grid connected synchronverter. Themodel developed in [10], based on linearized equations of thesystem, is adopted for the investigation. A design procedure ofthe synchronverter, using reduced-order models of active andreactive power loops is presented, which relys on nominal filterparameters and grid conditions. Subsequently, the µ-analysisis performed according to a defined uncertainty function, inorder to assess the effects of variations of control parameters

Page 2: Robust Stability Analysis of LCL Filter Based ...eprints.nottingham.ac.uk/55122/1/TPEL-Reg-2018-08-1721.pdf · robust stability of an LCL grid connected synchronverter. The model

2

𝑇𝑚 +

𝑇𝑒

− 𝐷𝑝

1

𝐽𝑠

𝜔𝑟𝑒𝑓

ω 1

𝑠

Calculation

𝑣𝑖𝑟𝑡𝑢𝑎𝑙 𝑒𝑚𝑓

𝜃

PW

M

gen

eratio

n

1

𝐾𝑠

𝑄𝑠𝑒𝑡

𝐷𝑞

𝑒∗

𝑉𝑟𝑒𝑓

𝑀𝑓 𝑖𝑓

𝑄

+

-

𝑅𝑓1 𝐿𝑓1

𝑅𝑐

𝐿𝑓2

𝐶

𝑅𝑓2 𝑅𝑔 𝐿𝑔

Filter

𝑖𝐿1 𝑖𝐿2

𝑖𝐶

𝑒 = 𝐸∠𝜃 𝑒𝑔 = 𝐸𝑔∠ 0

1

𝜔𝑛

𝑃𝑠𝑒𝑡

1

𝜔𝑛 P and Q

Calculation

𝑣𝑃𝐶𝐶

𝑖𝑔

𝑃

Control

PCC Grid

+

-𝑣𝑐

Fig. 1. Simplified scheme of the system under study.

and grid conditions on the stability of the system. Throughthe performed investigation effects that are not clearly visibleby means of an eigenvalue analysis are highlighted, especiallythe fact that synchronverters turn to be very robust against griduncertainties under weaker grid conditions, which is exactlythe opposite trend shown by grid connected converters usingdedicated synchronization units [2].

The rest of the paper is structured as follows: in sectionII, the small-signal model of a synchronverter connectedto the grid through an LCL filter along with the adoptedcontrol design procedure are introduced. Section III presentsthe concept of robust stability analysis by means of SSVsand its application to the system under study. In sectionIV, experimental results using a power hardware-in-the-loop(PHIL) test bench are shown, while section V is dedicated tothe conclusions.

II. SMALL-SIGNAL MODEL AND DESIGN

In the following, the small-signal model of a synchronverterconnected to the grid through an output LCL filter presentedin [10] is briefly introduced.

The model has been developed by splitting the overallsystem into two separated subsystems, namely the control andthe plant composed of the filter and the grid. The simplifiedscheme of the system under study is depicted in Fig. 1, whilein Fig. 2, inputs and outputs of the two linearized subsystemsare shown. The design procedure presented in [10] is describedin this section and is adopted in this work for tuning theparameters of the control.

A. Small-signal modelThe synchronverter control structure shown in Fig. 1 con-

tains separated loops for active power P and a reactive power

C(Control)

Δ𝑃𝑠𝑒𝑡

Δ𝑄𝑠𝑒𝑡

Δ𝑃

Δ𝑄

Δ𝑉𝑃𝐶𝐶

𝛥𝐸

𝛥θ

Δ𝑃

Δ𝑄

Δ𝑉𝑃𝐶𝐶

𝛥θ

𝛥𝐸𝑃

𝛥𝑥𝑐 = 𝐴𝑐𝛥𝑥𝑐 + 𝐵𝑐𝛥𝑢𝑐

𝛥𝑦𝑐 = 𝐶𝑐𝛥𝑥𝑐 + 𝐷𝑐𝛥𝑢𝑐

𝛥𝑥𝑔 = 𝐴𝑔𝛥𝑥𝑔 + 𝐵𝑔𝛥𝑢𝑔

𝛥𝑦𝑔 = 𝐶𝑔𝛥𝑥𝑔 + 𝐷𝑔𝛥𝑢𝑔

G (Filter + Grid)

Fig. 2. Inputs and outputs of the two linearized subsystems.

Q. The former emulates the frequency droop mechanismtypical of a SM described by the well-known swing equation:

Jω = Tm−Te−Dpω , (1)

with J representing the mechanical (virtual) inertia, ω thevirtual rotor speed, Dp the feedback gain accounting for the(virtual) mechanical friction of the machine, Te is the electricaltorque and Tm is the mechanical one. Dp does not onlyrepresent the virtual friction of the machine, but also theactive power-frequency droop coefficient of the controller. Tmcan be directly calculated from the active power setpoint Psetsimply by dividing by the nominal frequency ωn. The virtualrotor angle θ is obtained integrating ω and is needed for thecalculation of the virtual back-emf e∗. The reactive power-voltage droop control reacts to a voltage deviation ∆V fromits nominal/reference value with a change of the reactive powersetpoint ∆Q, according to the droop coefficient Dq:

∆Q =−Dq∆V . (2)

The instantaneous reactive power measured at the output ofthe converter is then compared to its setpoint and added to thesignal coming from the voltage droop. The resulting quantityis processed through an integrator with gain 1/K producingthe virtual mutual flux M f i f , which multiplied by the virtualrotor speed ω produces the amplitude of the virtual back-emfEp. Linearization of this product yields:

∆Ep = M f i f 0 ∆ω+∆M f i f ω0, (3)

where quantities with subscript ”0” denote values at theoperating point. The chosen state variables of the controlsystem are the virtual rotor rotational speed ω, the rotor angleθ and the mutual flux M f i f .

The state-space representation of the plant composed of thefilter and the grid is obtained by choosing iL1, iL2 and vc ofFig. 1 as state variables, namely filter current at converter side,filter current at grid side and capacitor voltage, respectively,and writing the equations in dq coordinates. Linearization isrequired for the calculation of active and reactive power aswell as for the voltage amplitude at the PCC:

Page 3: Robust Stability Analysis of LCL Filter Based ...eprints.nottingham.ac.uk/55122/1/TPEL-Reg-2018-08-1721.pdf · robust stability of an LCL grid connected synchronverter. The model

3

∆P = 32 (IL2d0∆vPCCd +VPCCd0∆iL2d+

+VPCCq0∆iL2q + IL2q0∆vPCCq)

∆Q = 32 (VPCCq0∆iL2d + IL2d0∆vPCCq+

−VPCCd0∆iL2q + IL2q0∆vPCCd)

∆VPCC =VPCCd0∆vPCCd+VPCCq0∆vPCCq√

V 2PCCd0+V 2

PCCq0

, (4)

where ∆vPCCd and ∆vPCCq can be calculated as:∆vPCCd = ∆vcd +Rc(∆iL1d−∆iL2d)+

−R f 2∆iL2d−L f 2diL2d

dt +ω0L f 2∆iL2q

∆vPCCq = ∆vcq +Rc(∆iL1q−∆iL2q)+

−R f 2∆iL2q−L f 2diL2q

dt −ω0L f 2∆iL2d

, (5)

where R f 2 and L f 2 represent the resistance and inductanceof the grid-side elements of the filter, respectively, whereas Rcis the capacitor damping resistance.

B. Control Design

The design procedure adopted in this work aims to theoptimization of the step response characteristics of the systemin terms of rise time, overshoot and settling time. Its intentis to provide a simple and intuitive approach for the designof the synchronverter when the characteristics of the filter andthe grid are known, avoiding the designer to rely on a trialand error procedure. It considers active and reactive powerloops separately and approximates the corresponding closed-loop transfer functions to simplified second-order equations.Control parameters are calculated setting a desired dampingfactor. In fact, it is known from control theory that the optimaldynamic response of a second-order system is obtained settingthe damping ratio to 1/

√2 [19]. Therefore, control parame-

ters are simply calculated expressing the equivalent dampingratios of the reduced-order closed loop transfer functions interms of plant and control parameters and chosen so as toobtain the desired damping ratio. Recently, another work onsynchronverter design based on a reduced-order model hasbeen presented in [11]. It is important to point out that theintroduced simplifications may result in design errors, withrepercussions on the performance of the system. In fact, as itwill be shown in the following subsection, it is always rec-comended to check the dynamic performances of the systemusing a full-order model to be sure that they comply with therequired specifications. Regarding stability assessment, sincethe two loops are considered separately and due to the MIMOnature of the system under study, even using the full-ordertransfer functions of the plant in the active and reactive powerloops design might lead to erroneous results [14], [15], due tothe fact that the cross-coupling effects between the two loopsare neglected. For this reason, multivariable systems theoryshould be applied in order to properly design the control.In the next section, the µ-analysis is performed in order toassess the stability margin of the MIMO system under studyagainst a defined set of plant uncertainties, once the controlhas been tuned according to the adopted design procedure.Subsequently, the effects of control parameters variations on

ΔT

𝐷𝑝

1

𝐽𝑠

(a)

Frequency droop loop

Δ𝝎 1

𝑠

Δθ

Filter +

Grid ΔP Δ𝑃𝑠𝑒𝑡

Frequency droop loop

Δ𝝎

(b)

1

𝜔𝑛 ΔT

Fig. 3. (a) Simplified frequency droop loop, (b) simplified active power loop.

the stability of the system are estimated, such that the designercan find the most suitable compromise between dynamicperformances and stability margin. In [10], three differentcases with different grid and filter characteristics have beenexamined, in order to test the effectiveness of the proposeddesign procedure under different system conditions. In thispaper, one of the cases examined in [10], whose parametersare reported in Table I, is taken as reference and used inthe following to describe the adopted design procedure. Inthis work, the filter design is not explicitly addressed andfilter parameters are obtained according to the filter designprocedure presented in [18].

The parameters to be tuned are the P− f droop coefficientsDp and the virtual inertia J for the active power loop alongwith the Q−V droop coefficient Dq and the factor K ofthe reactive power loop. Often droop coefficients are alreadyfixed due to specifications on the steady-state response andtherefore only J and K can be adjusted to improve the dynamicbehaviour. However, the adopted design procedure is valideven in case that the four parameters are freely adjustable.

In Fig. 3(a), the simplified scheme of the synchronverterfrequency droop loop is shown, described by the followingfirst-order transfer function:

∆ω

∆T(s) =

1Dp

1+ s JDp

=K f

1+ s τ f. (6)

In Fig. 3(b), the simplified scheme of the active powerclosed-loop is reported. The plant composed of the filter andthe grid (indicated as G in Fig. 2) is described dynamicallyby the transfer function ∆P

∆θ. Each of the input-output transfer

functions of G can be approximated by an equivalent first-order transfer function by looking at the characteristics of thepoles of the system, shown in Table II for simplicity. Twotime constants identify the dynamic of the system, indicatedas τp1 and τp2 in Table II. The transfer function ∆P

∆θof G can

be approximated to the following first-order transfer function:

PT 1P(s) =Gp

1+ s τre f p, (7)

where GP is the steady-state value of ∆P∆θ

and τre f p the timeconstant of its dominant pole, namely τp1 for this case, ascan be determined by observing its step response. Choosing Jsufficiently small (e.g. τ f ≈ τre f p/10), the frequency drooploop can be neglected and the active power loop can beapproximated by the second-order transfer function reportedbelow:

Page 4: Robust Stability Analysis of LCL Filter Based ...eprints.nottingham.ac.uk/55122/1/TPEL-Reg-2018-08-1721.pdf · robust stability of an LCL grid connected synchronverter. The model

4

Table IPARAMETERS OF THE EXAMINED CASE

Description Symbol ValueInverter rated power Sn (kVA) 300

Short circuit ratio SCR 20Reactive-resistive ratio X/R 10

Line-to-line voltage VLL (Vrms) 400Rated grid frequency fg (Hz) 50

Grid inductance Lg (pu) 0.05Inverter-side filter inductor L f 1 (pu) 0.08

Grid-side filter inductor L f 2 (pu) 0.02Grid resistance Rg (pu) 0.005

Inverter-side filter resistor R f 1 (pu) 0.02Grid-side filter resistor R f 2 (pu) 0.02

Capacitor damping resistor Rc (pu) 0.18Filter capacitor C (pu) 0.05

Table IICHARACTERISTICS OF THE POLES OF G

Pole DampingFrequency(rad/sec)

Time constant(sec)

(p1-p2) -94.8 ± j 314 0.289 328 1.05e-2 (τp1)(p3-p4) -842 ± j 6930 0.120 6980 1.19e-3 (τp2)(p5-p6) -842 ± j 7560 0.111 7610 1.19e-3 (τp2)

Papp(s) =1

T 2p s2 +2ζpTps+1

, (8)

where Tp and ζp represent the inverse natural frequency andthe damping ratio, respectively:

Tp =

√τre f p ωn Dp

Gp; ζp =

12

√Dp ωn

τre f pGp. (9)

Assuming DP bounded in order to comply with steady-state performance requirements, the damping of the simplifiedsecond-order active power loop transfer function cannot beinfluenced otherwise [7]. In case that DP is freely adjustable,it can be tuned so as to achieve ζP = 1/

√2.

A Similar approach can be adopted for the tuning of thereactive power loop. Due to the Q−V droop, two differentloops are identified, namely a reactive power and a voltagecontrol loop, shown in Fig. 4(a) and (b) respectively.

ΔQ Δ𝑄𝑠𝑒𝑡 ΔE𝑝

(a)

Filter + Grid

𝜔𝑛

𝐾𝑠

Δ𝑄𝑠𝑒𝑡 ΔE𝑝

Filter + Grid

Δ𝑉𝑃𝐶𝐶

𝐷𝑞

(b)

𝜔𝑛

𝐾𝑠

Fig. 4. (a) Simplified reactive power loop scheme, (b) simplified VPCC loopscheme.

Also in this case, the behaviours of ∆Q∆Ep

and ∆VPCC∆Ep

ofG are approximated by reduced first-order transfer functionsindicated as PT 1Q and PT 1V , respectively:

PT 1Q(s) =Gq

1+ s τre f q; PT 1V (s) =

Gv

1+ s τre f v, (10)

where Gq and Gv are the steady-state values of ∆Q∆Ep

and

∆VPCC∆Ep

, respectively and τre f Q and τre fV are the time constantsof the respective dominant poles of each transfer function. Theresulting damping factors of the two approximated transferfunctions are reported below:

ζq =12

√K

τre f q ωn Gq; ζv =

12

√K

τre f v ωn Dq Gv. (11)

If Dq can be arbitrarily modified, K and Dq can be chosensuch that ζq = ζv = 1/

√2, otherwise the highest value of K

resulting from the two calculations is chosen.Assuming that Dp and Dq are fixed to 5 % [20], the

calculated control parameters Jopt and Kopt for the case understudy are reported in Table III.

Table IIICONTROL PARAMETERS

Parameter ValueDp 60.8Dq 18371Jopt 6.38e-2Kopt 37459

C. Simulation Results

Simulation results obtained using the full-order model ofthe system and setting the values of the control parametersaccordingly to the adopted design procedure are shown inFig. 5. Active and reactive power loops have been testedseparately and sweeps of J and K are performed. Firstly, theresponse of the system to a step of Pset of 0.3 pu was observed

varying the value of J within the range[

Jopt50 ; 50 Jopt

],

whereas K was set to the calculated optimal value Kopt .Subsequently, the response of the system to a step Qset ofthe same amplitude was simulated varying K within the range[

Kopt5 ; 5 Kopt

], whereas J = Jopt .

The directions of the arrows indicate the increment ofthe corresponding parameters, the red curve is the responseobtained by setting the parameters calculated using the adopteddesign procedure, whereas green curves are for values belowthe calculated optimal one and blue curves for values aboveit. In Fig. 5 (b), the steady-state value of the reactive powerdoes not reach the given setpoint of 0.3 pu due to the voltagedroop controller, which adjusts the reactive power accordingto the measured voltage at the PCC.

III. ROBUST STABILITY ANALYSIS

Most of the works in the literature regarding synchronverterdesign are based either on analysis of linearized systemtransfer functions [8], [10], or eigenvalue analysis [11], [12].Although eigenvalue analysis is an efficient way for assessingsystem stability, it is well known that for MIMO systemseigenvalues are a poor measure of gain [14]. Indeed, eigenval-ues provide only information about a specific configuration ofthe system when inputs and outputs are in the same direction,namely the direction of the eigenvectors. They do not take into

Page 5: Robust Stability Analysis of LCL Filter Based ...eprints.nottingham.ac.uk/55122/1/TPEL-Reg-2018-08-1721.pdf · robust stability of an LCL grid connected synchronverter. The model

5

0 0.05 0.1 0.15 0.2 0.25 0.3

Time [s] (a)

0

0.1

0.2

0.3

0.4

0.5

0.6

[pu]

Transfer Function ("P

/"Pset

)

0 0.05 0.1 0.15 0.2

Time [s] (b)

0

0.05

0.1

0.15

0.2

0.25

0.3

[pu]

Transfer Function ("Q

/"Qset

)

J

K

Fig. 5. (a) Effects of J on the dynamic behaviour of ∆P∆Pset

; (b) effects of K

on the dynamic behaviour of ∆Q∆Qset

. (red): Response with the parameters fromdesign procedure, (green): response for values lower then the optimal one,(blue): response for values higher then the optimal one.

account the possible interactions between different channelsthat typically occur in a MIMO system. For accurate robust-ness assessment of MIMO systems, multivariable analysis isrequired and different methods have been developed, suchas the structured singular values (SSV) or µ-analysis [14],[15], [17]. Singular values provide better information aboutthe gains of the plants and the robustness of the control isverified against a defined set of system uncertainties. Thismethod allows to span a set of possible system configurationinstead of verifying stability only for a specific condition.

Parameter inaccuracies or non-linearities are among themost common sources of uncertainties. Other common sourcesof uncertainties are represented by neglected dynamics due todelays of sensors and/or actuators. These kind of uncertaintysources have a frequency dependent behaviour and can beincluded in the set of uncertain plants by using appropriaterepresentations. The control loops of each grid connected con-verter modify the frequency behaviour of the equivalent gridseen by other converters operating nearby [13]. These effectscan be also included in the stability analysis as uncertaintieson the plant. The common way of modelling uncertainties isto add perturbations to the nominal plant G in an additive ormultiplicative way [14], [15]. The multiplicative representationconsists on defining the set of perturbed plants as:

Gp = G(1+w∆); with ‖∆‖∞ ≤ 1; (12)

where ∆ is a block diagonal normalized matrix including allthe possible perturbations, ‖∆‖∞ represents its H∞ norm andw is a multiplicative weight. The multiplicative representationis often preferred over the additive one, as the numericalvalues of its weights are more informative [14]. For example,at frequencies where |w( jω)| > 1, the uncertainty exceeds100 %. Multiplicative uncertainties are characterized by asmall amplitude for low frequency, increasing to unity andabove at higher frequencies. This is a consequence of dynamicproperties that inevitably occur in physical systems. Uncer-tainties might be located at the input or at the output of theplant. Input multiplicative uncertainty is suitable for modelinguncertain high frequency dynamics and uncertain right halfplane zeros, while output inverse multiplicative uncertainty forlow frequency parameter errors and uncertain right half planepoles [15]. In this work, the input multiplicative uncertaintyrepresentation is used in order to investigate the robustness

of the control against high-order frequency effects, such asresonant grid impedance behaviour or the effects of controllersof other power electronics converters operating nearby. A mul-tiplicative uncertainty weight is defined and, according to it,the robustness of the control is investigated varying controllerparameters and grid conditions. The results are then comparedto eigenvalue analysis, showing that the analysis performedwith structured singular values enables highlighting effects thatcannot be explicitly observed looking at the eigenvalues of thesystem.

A. Problem formulation for µ-analysis

In order to perform the µ-analysis, the system should berepresented in the lower fractional transformation (LFT) form[17]. This process is often referred to as ”pulling out the ∆’s”[15]. In Fig. 6 the steps required for bringing the system in aform suitable for µ-analysis are shown. First, the uncertaintieshave to be ”pulled out” from the plant and the system has tobe put in the form shown in Fig. 6 (a). Subsequently, the N∆-structure shown in Fig. 6 (b) is obtained by means of a LFTbetween the generalized plant P and the controller C, definedas [14]:

P

C

𝜟

N

𝜟

𝜟

M

𝑢 𝑣

𝑤 𝑧

𝑢𝛥 𝑦𝛥

𝑤 𝑧

𝑢𝛥 𝑦𝛥 𝑢𝛥 𝑦𝛥

(a) (b) (c)

Fig. 6. Problem formulation for µ-analysis: (a) general control formulation,(b) N∆-structure, (c) M∆-structure.

N = Fl(P,C)∆= P11 +P12C(I−P22C)−1P21. (13)

Finally, the M∆-structure is simply derived considering thatM = N11. The structured singular value µ is defined as thesmallest structured ∆ (measured in terms of the largest singularvalue σ (∆)), which makes the matrix I−M∆ singular; then[14]:

µ(M)∆=

1min

{ σ | det(I−M∆) = 0 f or structured ∆}. (14)

The inverse of µ(M) can be interpreted as a stability marginwith respect to the structured uncertainty set affecting M.This means that indicating the peak of µ(M) = β across thefrequency range ω, stability is guaranteed for all perturbationswith appropriate structure and with respect to the chosenuncertainty, such that:

maxω

σ(∆)≤ 1β. (15)

It is therefore clear that the resulting stability margin is veryrelated to the uncertainties considered for the analysis.

Page 6: Robust Stability Analysis of LCL Filter Based ...eprints.nottingham.ac.uk/55122/1/TPEL-Reg-2018-08-1721.pdf · robust stability of an LCL grid connected synchronverter. The model

6

B. Application to the system under study

A practical application of µ-analysis to the studied system ispresented in the following. All the required calculations canbe carried out by means of the ”Control System Toolbox”of MATLAB [21]. The generalized plant P shown in Fig. 6(a) can be obtained using the command sysic. The generalcontrol formulation for the particular case under study isshown in Fig. 7, where y∆ =

[z1 z2

]T , u∆ =[w1 w2

]T andthe two multiplicative input uncertainties Wδ1 and Wδ2 havebeen located at the input channels u1 and u2. Outputs of Pare then the control inputs shown in Fig. 2 and representedby the vector v =

[v1 v2 v3 v4 v5]. Using the starp command

from the same toolbox of MATLAB, the star product betweenP and C can be calculated, obtaining (13).

Δ𝑄𝑠𝑒𝑡

Δ𝑃𝑠𝑒𝑡

G

C

Δ𝑃

Δ𝑄

Δ𝑉𝑃𝐶𝐶

Δ𝐸𝑝

Δ𝜗

P

W𝛿1

W𝛿2

𝛿1

𝛿2

𝑧1

𝑧2

𝑤1

𝑤2

𝑢1

𝑢2

𝑣1 𝑣3 𝑣2 𝑣4 𝑣5

𝑤3

𝑤4

Fig. 7. Construction of the generalized plant of the system under study.

101 102 103 104 105

Frequency(rad/s)

-10

-5

0

5

10

15

Mag

nitu

de(d

B)

High-frequency uncertainty

Fig. 8. Multiplicative input uncertainty used for the µ-analysis.

In Fig. 8, the multiplicative input uncertainty used for theanalysis is reported. It shows an amplitude of 50% at lowfrequency, increasing till 500% at very high frequencies. Thechosen weight accounts for low frequency uncertainties due toparametric uncertainty in the model as well as high frequencyneglected dynamic effects or resonant effects of the grid due tothe presence of other converters operating nearby. Consideringthe system with the parameters listed in Table I and Table III,in the following the effects of control parameters J and K aswell as grid SCR variations on the eigenvalues of the systemsare shown and compared to the results obtained through theµ-analysis.

C. Variation of J

In Fig. 9 (a) and (b), the migration of the nine eigenvaluesof the full-order system due to a sweep of J in the range[

Jopt20 ; 20 Jopt

]is shown. The direction of the arrows indicate

Fig. 9. Effects of variation of control parameter J on the eigenvalues of thesystem, (a) migration of λ1, (b) migration of λ2-λ9.

100 101 102 103 104 105

Frequency (rad/s)

0

0.2

0.4

0.6

0.8

1

Mag

nitu

de

7 factor - Mutliplicative INPUT uncertainty

J

J

Fig. 10. Behaviour of µ factor due to variations of J.

the increase of the parameter J. Red points indicate the loca-tions of the eigenvalues for reference conditions representedby J = Jopt , K = Kopt and SCR = 20, whereas green points arefor values of J < Jopt and blue ones for values of J > Jopt . Itis clear that the parameter J is mainly affecting the eigenvalueλ1, causing a migration of the eigenvalue toward the imaginaryaxis, whereas the other eight eigenvalues move leftwards.

In Fig. 10, the results of the µ-analysis are shown, wherecolours have the same meaning as in Fig. 9. Under referenceconditions, the control is quite robust against the definedplant uncertainties. The maximum value of µ = 0.6169 andis reached at a frequency of 277 rad/sec. According to theresults shown in Fig. 10, an increase of J tends to augmentthe robustness of the system at higher frequency, as can bealso deduced from the eigenvalue analysis, since the dominanteigenvalues move leftwards. However, an excessive increaseof this parameter increases the peak of the µ factor at lowerfrequencies, reaching almost the unity for J = 20 Jopt . Thisrepresents an important aspect that needs to be consideredduring the design procedure. In fact, it is common thoughtthat VSMs should reproduce the inertia of a real synchronousmachine of the same size. This requires the introduction ofadditional energy storage in the DC-Link of the converter,increasing sizes and costs. The results shown through thisanalysis indicate that generally high values of virtual inertiaJ do not always correspond to an increment of the stabilitymargin of the converter.

Page 7: Robust Stability Analysis of LCL Filter Based ...eprints.nottingham.ac.uk/55122/1/TPEL-Reg-2018-08-1721.pdf · robust stability of an LCL grid connected synchronverter. The model

7

Fig. 11. Effects of variation of control parameter J on the eigenvalues of thesystem, (a) migration of λ2-λ5, (b) migration of λ6-λ9.

100 101 102 103 104 105

Frequency (rad/s)

0

0.2

0.4

0.6

0.8

1

Mag

nitu

de

7 factor - Mutliplicative INPUT uncertainty

K

K

Fig. 12. Behaviour of µ factor due to variations of K.

D. Variation of K

Fig. 11 (a) and (b) show the migration of the eigenvaluesdue to variation of the parameter K. The parameter is varied

within the range[

Kopt5 ; 5 Kopt

]. λ1 is far away from the

origin and is not relevantly affected. For values of K lowerthen Klim ≈ 9000, λ6 and λ7 are located on the right half planecausing instability.

The results of the µ-analysis shown in Fig. 12 indicate anincrease of the robustness of the system for higher valuesof K at all frequencies. However, for values of K > Koptthe stability margin is not relevantly enhanced. It is worthpointing out that, according to the chosen uncertainty weights,the limit of µ = 1 is reached for K ≈ 19000, which is moreconservative if compared to the limit obtained through theeigenvalue analysis. This is simply explained by the fact thatµ provides information about robustness, covering a wide setof possible plants, while eigenvalues show results only for oneparticular system.

E. Variation of grid SCR

Fig. 13 shows the migration of the eigenvalues due toa decrease of the grid SCR from 20 to 2, when the X/Rratio is set to 10. The direction of the arrows indicates theincrease of the corresponding value, showing clearly that allthe eigenvalues move rightwards when the impedance of the

Fig. 13. Effects of variation of grid SCR on the eigenvalues of the system,(a) migration of λ2-λ5, (b) migration of λ6-λ9.

100 101 102 103 104 105

Frequency (rad/s)

0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

Mag

nitu

de

7 factor - Mutliplicative INPUT uncertainty

SCR

Fig. 14. Behaviour of µ factor due to variations of the grid SCR.

grid is increased. This would lead to the consideration thatthe synchronverter is less stable when connected to a weakergrid. Similar conclusions have been drawn in [22], where thestability of a synchronverter-dominated microgrid has beeninvestigated.

However, looking at the results of the µ-analysis reported inFig. 14, the decrease of the grid SCR has instead the effect ofreducing the µ factor for all frequencies below ≈ 1000rad/sec,where the highest peak of µ is located. This indicates that thecontrol results to be more robust against the defined set ofuncertainties shown in Fig. 8 when connected to a grid withhigher impedance. This can be explained by the fact that thesynchronverter behaves as a SM and basically as a voltagesource behind an impedance. Indeed, stator inductances ofSMs are usually much higher than typical converter filterinductances and their high impedance enhances the stabilityof the machine against high frequency perturbations [23].

It is worth to notice that the behaviour of the synchronverterhighlighted through the performed analysis contrasts the trendof PLL-based converters, which instead result to be much moresensitive to perturbations in the plant (represented for exampleby the presence of other converters operating nearby) whenconnected to a weaker grid [2].

F. Considerations for synchronverter designAccording to the results of the robust stability analysis

performed in this section, the following aspects should be

Page 8: Robust Stability Analysis of LCL Filter Based ...eprints.nottingham.ac.uk/55122/1/TPEL-Reg-2018-08-1721.pdf · robust stability of an LCL grid connected synchronverter. The model

8

taken into account during the design procedure:

• In this work, control parameters have been tuned withoutconsidering any requirements on virtual inertia. In fact,in the design procedure presented in the previous section,J has been set to a proper low value so as to neglectthe dynamic of the frequency droop loop in the activepower control loop. For the specific case under study, astability margin improvement is achieved for values of Jup to ≈ 10 Jopt . However, a further increase of J causesa reduction of the stability margin of the converter at lowfrequencies.

• K affects significantly the stability of the converter. Tocomply with the design procedure presented in the pre-vious section, the highest value of K resulting from (11)has been selected as Kopt . According to the results of theperformed stability analysis and observing the dynamicbehaviour shown in Fig. 5 (b), a further increase of Kover a certain limit simply worsen the dynamic perfor-mances of the converter, without significantly improvingits stability.

• The performed analysis has pointed out that the stabilityof the synchronverter against the defined set of highfrequency uncertainties is augmented by the presence ofhigh impedance between the converter and the grid. Asalready mentioned, stator inductances of SMs are muchhigher than usual converter filter inductances, typicallydesigned so as to optimize the trade-off between powerquality and size of the filter components [18]. A simpleand efficient way for reproducing the characteristics of aSM by means of a VSC without necessarily increasingthe size of the hardware components, is the emulationof virtual impedance through the control [23]. The useof virtual impedances is well-known in the literature andseveral techniques have been proposed for various pur-poses, e. g. harmonic suppressions [24], inverter currentslimitation [25] or output admittance shaping [26], to namebut a few. An overview on the techniques proposed inthe literature is not the focus of this work, but ratherhighlighting that this expedient might be adopted in orderto enhance the stability of the synchronverter [23].

Finally, one might think about including the stability anal-ysis shown in this paper as part of a comprehensive designprocedure, which aims to find the best compromise betweendynamic performances and stability margin. An example of apossible iterative process is reported in Fig. 15. The flowchartshown in Fig. 15 (a) summarizes the steps of the designmethod adopted in this paper and described in section II.B,whereas in Fig. 15 (b), the extended flowchart includingstability margin considerations is depicted.

IV. EXPERIMENTAL RESULTS

Laboratory experiments have been performed in order tovalidate the linearized model used for the analysis. In Fig. 16(a), a simplified scheme of the experimental setup used for thetests is depicted, while in Fig. 16 (b), a picture of the labora-tory environment is shown. Each phase of a 4 kVA converter

Set Dp and Dq according to steady-state

droop charcateristics (e.g. 5%)

Get nominal plant

parameters

(filter and grid)

Design Process

Calculate J setting

and K according to eq.(11)

𝜏𝑓 ≈ 𝜏𝑟𝑒𝑓1/10

Chech dynamic preformances of full-

order model

End

𝑌𝑒𝑠

No

Chech dynamic preformances of

full-order model

End

𝑌𝑒𝑠

No

Define plant uncertainty and check

robust stability

𝑌𝑒𝑠 No

𝑌𝑒𝑠

No

(a)

(b) Design Process

Satisfactory dynamic

performances?

Satisfactory stability

margin?

Virtual impedance

implemented?

Adjust value of K

(higher K: slower response, more damping;

lower K: faster response, less damping)

Set Dp and Dq according to steady-state

droop charcateristics (e.g. 5%)

Preliminary calculation of J setting

and K according to eq.(11) 𝜏𝑓 ≈ 𝜏𝑟𝑒𝑓1/10

Modify plant parameters considering

virtual impedance

Adjust value of J and/or K

and eventually consider virtual

impedance implementation

Satisfactory dynamic

performances?

Adjust value of K (higher K: slower response, more damping;

lower K: faster response, less damping)

Get nominal plant

parameters

(filter and grid)

Fig. 15. (a) Steps of design procedure adopted in this paper and proposed in[10], (b) extended design procedure including robust stability considerations.

Danfoss of the Series FC-302 is connected to a 4-quadrantlinear power amplifier PAS 15000 from Spitzenberger-Spies(single phase rated power 15 kVA, total three phase ratedpower 45 kVA). The converter is additionally equipped witha transformer to provide galvanic isolation.

The principle of PHIL simulations is briefly explained inthe following. A virtual grid is simulated by means of a real-time simulator (RTDS in the specific case). The simulatormeasures the converter currents at the PCC, corresponding tothe currents flowing into the power amplifier. In the RTDS,a grid model runs in real-time, simulating the effects of thecurrents injected by the converter on the virtual grid. Thesimulated voltages at the PCC are sent to the power amplifieras reference values VPCC. The linear power amplifier is able

Page 9: Robust Stability Analysis of LCL Filter Based ...eprints.nottingham.ac.uk/55122/1/TPEL-Reg-2018-08-1721.pdf · robust stability of an LCL grid connected synchronverter. The model

9

to reproduce at its terminal the reference voltages provided bythe simulator almost instantaneously (slew rate > 52 V/µsec).This setup allows testing the behaviour of the converter underdifferent grid conditions simply modifying the parameters ofthe grid model implemented in the simulator. The describedsetup has been used for validation of the model adopted forthe analysis presented in this paper.

A resistive-inductive grid, as the one shown in Fig. 1,has been simulated in the RTDS and the parameters of thevirtual grid have been modified so as to emulate a variationof the grid SCR from 20 to 2 assuming a constant X /R ratioof 10. The control has been tuned following the proceduredescribed in this paper. Setup parameters are shown in TableIV. In Fig. 17, measurements results are compared to time-domain simulations in MATLAB/Simulink/PLECS (where avoltage source has been used to model the converter) andto analytical results obtained from the small-signal model.Steps of active and reactive power of 0.25 pu are shown forthree different values of SCR, namely 20, 10 and 2, whereasthe voltage control droop loop at the PCC has been eitheractivated or deactivated. A good match between simulationsand measurements can be appreciated. As already noticed inFig. 5, the steady-state value of the output reactive powerdoes not reach the given setpoint when the voltage droopis activated. This behaviour is much more accentuated forlower SCR. The Q-V droop does not influence significantlythe dynamic of the active power steps and therefore in Fig. 17only ∆P

∆Psetsteps for the case when the voltage droop is activated

are shown.

Further experimental results are shown in Fig. 18, where

DC-Link Inverter LCL Filter Trafo PCC

Control

(a)

(b)

Power

Amplifier

Grid Model

𝑉𝑃𝐶𝐶

𝐼𝑃𝐶𝐶

dSPACE

Power Amplifier

RTDS

Inverter

DC-Source

𝑇𝑚 +

𝑇𝑒

𝐷𝑝

1

𝐽𝑠

𝜔𝑟𝑒𝑓

ω 1

𝑠

𝜃

1

𝐾𝑠

𝑄𝑠𝑒𝑡

𝐷𝑞 𝑉𝑟𝑒𝑓

𝑀𝑓 𝑖𝑓

𝑄

1

𝜔𝑛

𝑃𝑠𝑒𝑡

1

𝜔𝑛

𝑃

𝑉𝑃𝐶𝐶 𝑉𝑃𝐶𝐶

𝐼𝑃𝐶𝐶

dSPACE RTDS

𝑅𝑔 𝐿𝑔

𝐸𝑔 𝐼𝑃𝐶𝐶

𝑉 𝑃𝐶𝐶

𝑉 𝑃𝐶𝐶 𝑃𝑢𝑙𝑠𝑒𝑠

Fig. 16. (a) Scheme of the laboratory setup, (b) picture of the laboratoryenvironment.

Table IVPARAMETERS EXPERIMENTAL SETUP

Description Symbol ValueInverter rated power Sn 4 kVALine-to-line voltage VLL 400 V (rms)

Rated grid frequency fg 50 HzInverter switching frequency fsw 5 kHzInverter-side filter inductance L f 1 0.03 pu

Grid-side filter inductance L f 2 0.003 puTransformer inductance LT 0.003 pu

Inverter-side filter resistance R f 1 0.0375 puGrid-side filter resistance R f 2 0.018 pu

Capacitor damping resistance Rc 0.037 puFilter capacitor C 0.025 puVirtual inertia Jre f 4e-4Integrator gain Kre f 800

P-Droop coefficient Dp 0.679Q-Droop coefficient Dq 183.71

Description Symbol SCR 20 SCR 10 SCR 2Grid inductance Lg 0.037 pu 0.075 pu 0.37 puGrid resistance Rg 0.0037 pu 0.0075 pu 0.037 pu

the parameters J and K have been varied from the referencevalues shown in Table IV. In Fig. 18 (b) and (e), the dynamicresponses of the system to steps of Pset and Qset of 0.25 pufor K = Kre f /8 are respectively shown, whereas Fig. 18 (c)and (f) show the response of the system for J = 10 Jre f .

Looking at the results shown in Fig. 17 and Fig. 18, it canbe noticed how a decrease of the K value causes a reductionof the high frequency damping of the system. An increase ofthe virtual inertia factor J tends to slow down the system interms of settling time and rise time. Additionally, an increaseof the corresponding overshoot can be observed as well,indicating a reduction of low frequency damping. Operationof the converter has been tested even under extremely weakgrid conditions (SCR = 2), which are typically critical for astandard grid connected converter. It can be noticed how inthis case the response of the system is simply slowed down,but the light overshoot shown in the nominal case (SCR = 20)is eliminated instead. According to the presented results, onecan conclude that the low frequency dynamic behaviour is notworsened by the lower SCR, which is instead the case for anincrease of the virtual inertia J.

V. CONCLUSION

In this paper, the robust stability analysis of a synchronverterconnected to the grid through an output LCL filter is presented.A simple design procedure is introduced, which is used fortuning the control parameters according to nominal filterand grid characteristics. A robust stability analysis has beencarried out based on the SSVs theory, which allows to assessthe stability margin of the system according to a definedset of uncertainties. The effects of the variation of controlparameters as well as grid characteristics on the stability of thesystem have been observed. Through the preformed µ-analysis,some effects, which may not be clearly visible performing aneigenvalue analysis, have been highlighted. Among them, thefact that the synchronverter is more robust to uncertainties inthe plant when connected to a grid with higher impedanceis probably the most interesting. In fact, this behaviour goes

Page 10: Robust Stability Analysis of LCL Filter Based ...eprints.nottingham.ac.uk/55122/1/TPEL-Reg-2018-08-1721.pdf · robust stability of an LCL grid connected synchronverter. The model

10

0 0.05 0.1 0.15 0.2 0.25 0.3Time [sec]

(a)

0

0.1

0.2

0.3A

mpl

itude

[pu

]

"P

/"Pset

- SCR=20

MeasurementsEMT SimulationsSmall-Signal

0 0.05 0.1 0.15 0.2 0.25 0.3Time [sec]

(d)

0

0.1

0.2

0.3

Am

plitu

de [

pu]

"Q

/"Qset

- SCR=20 - Droop OFF

MeasurementsEMT SimulationsSmall-Signal

0 0.05 0.1 0.15 0.2 0.25 0.3Time [sec]

(b)

0

0.1

0.2

0.3

Am

plitu

de [

pu]

"P

/"Pset

- SCR=10

MeasurementsEMT SimulationsSmall-Signal

0 0.05 0.1 0.15 0.2 0.25 0.3Time [sec]

(e)

0

0.1

0.2

0.3

Am

plitu

de [

pu]

"Q

/"Qset

- SCR=10 - Droop OFF

MeasurementsEMT SimulationsSmall-Signal

0 0.05 0.1 0.15 0.2 0.25 0.3Time [sec]

(c)

0

0.1

0.2

0.3

Am

plitu

de [

pu]

"P

/"Pset

- SCR=2

MeasurementsEMT SimulationsSmall-Signal

0 0.05 0.1 0.15 0.2 0.25 0.3Time [sec]

(f)

0

0.1

0.2

0.3

Am

plitu

de [

pu]

"Q

/"Qset

- SCR=2 - Droop OFF

MeasurementsEMT SimulationsSmall-Signal

0 0.05 0.1 0.15 0.2 0.25 0.3Time [sec]

(g)

0

0.05

0.1

0.15

Am

plitu

de [

pu]

"Q

/"Qset

- SCR=20 - Droop ON

MeasurementsEMT SimulationsSmall-Signal

0 0.05 0.1 0.15 0.2 0.25 0.3Time [sec]

(h)

0

0.05

0.1

0.15

Am

plitu

de [

pu]

"Q

/"Qset

- SCR=10 - Droop ON

MeasurementsEMT SimulationsSmall-Signal

0 0.05 0.1 0.15 0.2 0.25 0.3Time [sec]

(i)

0

0.05

0.1

0.15

Am

plitu

de [

pu]

"Q

/"Qset

- SCR=2 - Droop ON

MeasurementsEMT SimulationsSmall-Signal

Fig. 17. Dynamic behaviour of ∆P∆Pset

, step of 0.25 pu: (a) SCR = 20, (b) SCR = 10, (c) SCR = 2. Dynamic behaviour of ∆Q∆Qset

, step of 0.25 pu, Q-V Droop

off: (d) SCR = 20, (e) SCR = 10, (f) SCR = 2. Dynamic behaviour of ∆Q∆Qset

, step of 0.25 pu, Q-V Droop on: (g) SCR = 20, (h) SCR = 10, (i) SCR = 2.

0 0.05 0.1 0.15 0.2Time [sec]

(a)

0

0.1

0.2

0.3

Am

plitu

de [

pu]

"P/"

Pset (J=J

ref ; K=K

ref)

MeasurementsEMT SimulationsSmall-Signal

0 0.05 0.1 0.15 0.2Time [sec]

(d)

0

0.1

0.2

0.3

Am

plitu

de [

pu]

"Q

/"Qset

(J=Jref

; K=Kref

)

MeasurementsEMT SimulationsSmall-Signal

0 0.05 0.1 0.15 0.2Time [sec]

(b)

0

0.1

0.2

0.3

0.4

Am

plitu

de [

pu]

"P/"

Pset (J=J

ref ; K=K

ref/8)

MeasurementsEMT SimulationsSmall-Signal

0 0.05 0.1 0.15 0.2Time [sec]

(e)

0

0.2

0.4

0.6

Am

plitu

de [

pu]

"Q

/"Qset

(J=Jref

; K=Kref

/8)

MeasurementsEMT SimulationsSmall-Signal

0 0.05 0.1 0.15 0.2Time [sec]

(c)

0

0.1

0.2

0.3

0.4

Am

plitu

de [

pu]

"P/"

Pset (J=10 J

ref ; K=K

ref)

MeasurementsEMT SimulationsSmall-Signal

0 0.05 0.1 0.15 0.2Time [sec]

(f)

0

0.1

0.2

0.3

Am

plitu

de [

pu]

"Q

/"Qset

(J=10 Jref

; K=Kref

)

MeasurementsEMT SimulationsSmall-Signal

Fig. 18. Grid SCR = 20, Q-V droop off, X/R=10. Dynamic behaviour of ∆P∆Pset

, step of 0.25 pu: (a) J=Jre f , K=Kre f ; (b) J=Jre f , K=Kre f /8; (c) J=10 Jre f ,

K=Kre f . Dynamic behaviour of ∆Q∆Qset

, step of 0.25 pu: (d) J=Jre f , K=Kre f ; (e) J=Jre f , K=Kre f /8; (f) J=10 Jre f , K=Kre f .

against the trend shown by grid connected converters usinga dedicated synchronization unit. The model used for theanalysis has been validated against simulations and laboratoryexperiments using a PHIL setup.

REFERENCES

[1] B. Wen, D. Boroyevich, R. Burgos, P. Mattavelli, and Z. Shen, ”Analysisof D-Q small-signal impedance of grid-tied inverters,” IEEE Trans.Power Electron., vol. 31, no. 1, pp. 675-687, Jan. 2016.

Page 11: Robust Stability Analysis of LCL Filter Based ...eprints.nottingham.ac.uk/55122/1/TPEL-Reg-2018-08-1721.pdf · robust stability of an LCL grid connected synchronverter. The model

11

[2] R. Rosso, G. Buticchi, M. Liserre, Z. Zou, and S. Engelken, ”Stabilityanalysis of synchronization of parallel power converters,” in Proc. 43rdAnnual Conference of the IEEE Industrial Electronics Society (IECON),Beijing, China, 2017, pp. 440-445.

[3] H.-P. Beck and R. Hesse, ”Virtual synchronous machine”, in Proc.9th Int. Conf. on Electrical Power Quality and Utilization (EQPU),Barcelona, Spain, Oct. 2007, pp. 1-6.

[4] S. D’Arco, J. A. Suul, and O. B. Fosso, ”A virtual synchronousmachine implementation for distributed control of power converters insmartgrids,” Int. J. Electric Power System Research, pp. 180-197, 2015.

[5] Q.-C. Zhong and G. Weiss, ”Synchronverters: inverters that mimicsynchronous generators,” IEEE Trans. Ind. Electron., vol. 58, no. 4,pp. 1259-1267, Apr. 2011.

[6] Q.-C. Zhong, P.-L. Nguyen, Z. Ma, and W. Sheng, ”Self-synchronizedsynchronverters: inverters without a dedicated synchronization unit,”IEEE Trans. Power Electron., vol. 29, no. 2, pp. 617-630, Feb. 2014.

[7] S. Dong and Y. C. Chen, ”Adjusting synchronverter dynamic responsespeed via damping correction loop,” IEEE Trans. Energy Convers., vol.32, no. 2, pp. 608-619, Jul. 2017.

[8] H. Wu, X. Ruan, D. Yang, X. Chen, W. Zhao, Z. Lv, and Q.-C. Zhong,”Small-signal modeling and parameters design for virtual synchronousgenerators,” IEEE Trans. Ind. Electr., vol. 63, no. 7, pp. 4292-4303, Jul.2016.

[9] M. Amin, A. Rygg, and M. Molinas, ”Self-synchronization of windfarms in an MMC-based HVDC system: a stability investigation”, IEEETrans. Energy Conv., vol. 32, no. 2, pp. 458-470, Jun. 2017.

[10] R. Rosso, J. Cassoli, S. Engelken, G. Buticchi, and M. Liserre, ”Analysisand design of LCL filter based synchronverter,” in Proc. IEEE EnergyConv. Congr. and Exp. (ECCE), Cincinnati, OH, 2017, pp. 5587-5594.

[11] S. Dong and Y. C. Chen, ”A method to directly compute synchronverterparameters for desired dynamic response,” IEEE Trans. Energy Conv.,vol. 33, no. 2, pp. 814–825, Jun. 2018.

[12] R. Aouini, B. Marinescu, K. B. Kilani, and M. Elleuch, “Synchronverter-based emulation and control of HVDC transmission,” IEEE Trans. PowerSyst., vol. 31, no. 1, pp. 278–286, Jan. 2016.

[13] X. Wang, F. Blaabjerg, and W. Wu, ”Modeling and analysis of harmonicstability in an AC power-electronics-based power system,” IEEE Trans.Power Electron., vol. 29, no. 12, pp. 6421-6432, Dec. 2014.

[14] S. Skogestad and I. Postlethwaite, ”Multivariable feedback control -analysis and design”, Wiley and Sons, 2001.

[15] K. Zhou and J. C. Doyle, ”Essentials of robust control”, Upper SaddleRiver: NJ. Prentice-Hall, 1998.

[16] L. Jessen, Z. Zou, B. Benkendorff, M. Liserre, and F. W. Fuchs,”Resonance identification and damping in AC-grids by means of multiMW grid converters,” in Proc. 42nd Annual Conference of the IEEEIndustrial Electronics Society (IECON), Florence, 2016, pp. 3762-3768.

[17] S. Sumsurooah, M. Odavic, and S. Bozhko, ”µ approach to robuststability domains in the space of parametric uncertainties for a powersystem with ideal CPL ,” IEEE Trans. Power Electron., vol. 33, no. 1,pp. 833–844, Jan. 2018.

[18] M. Liserre, F. Blaabjerg, and S. Hansen, ”Design and control of an LCL-filter-based three phase active rectifier”, IEEE Trans. Ind. Appl., vol. 41,no. 5, pp. 1281-1291, Sep. 2005.

[19] D. Schroeder, ”Elektrische Antriebe 2, Regelung von Antriebssystemen”,2nd ed., Germany: Springer-Verlag, 2001.

[20] P. Kundur, ”Power System stability and control”, McGraw-Hill, Inc.1994.

[21] G. J. Balas, J. C. Doyle, K. Glover, A. Packard, and R. Smith ”µ Analysisand synthesis toolbox”, Matlab user’s guide.

[22] Z. Shuai, Y. Hu, Y. Peng, C. Tu, and Z. J. Shen, ”Dynamic-stabilityanalysis of synchronverter-dominated microgrid based on bifurcationtheory,” IEEE Trans. Ind. Electr., vol. 64, no.9, pp. 7467-7477, Sep.2017.

[23] V. Natarajan and G. Weiss, ”Synchronverters with better stability due tovirtual inductors, virtual capacitors and anti wind-up,” IEEE Trans. Ind.Electron., vol. 64, no. 7, pp. 5994-6004, Jul. 2017.

[24] A. Terraso, J. I. Candela, J. Rocabert, and P. Rodriguez, ”Grid voltageharmonic damping method for SPC based power converters with multi-ple virtual admittance control,” in Proc. IEEE Energy Conv. Congr. andExp. (ECCE), Cincinnati, OH, 2017, pp. 64-68.

[25] X. Lu, J. Wang, J.M. Guerrero, and D. Zhao, ”Virtual impedance basedfault current limiters for inverter dominated AC microgrids,” IEEETrans. Smart Grid, vol. 9, no. 3, pp. 1599-1612, May 2018.

[26] X. Wang, Y. W. Li, F. Blaabjerg, and P. C. Loh, ”Virtual-impedance-based control for voltage-source and current-source converters,” IEEETrans. Power Electron., vol. 30, no. 12, pp. 7019-7037, Dec. 2015.

Roberto Rosso (S’17) received his B.Sc. in Elec-tronic Engineering and his M.Sc. in Electrical Engi-neering in 2009 and 2012, respectively from the Uni-versity of Catania, Italy. In 2013 he joined the R&Ddivision of the wind turbine manufacture ENERCON(Wobben Research and Development WRD), wherehe is currently working in the control engineeringdepartment. He has been involved in several researchprojects addressing analytical models of electricalmachines and control of electric drive systems. Since2017 he is pursuing the Ph.D. in electrical engineer-

ing at the Christian- Albrechts-University of Kiel, Germany. His researchfocuses on control strategies for grid integration of renewable energy systems.

Jair Cassoli received in 2006 his M.Sc. in elec-trical engineering from the Technical Universityof Dresden, Saxony, Germany. He has been withENERCON R&D division in Aurich, Germany, awind energy converter manufacturer, since 2006 asdevelopment engineer. He is responsible for modelbased design power control strategies for wind en-ergy converters at the control system department. Hehas also been participating in collaboration with gridoperators in several project specific studies concern-ing transient analysis of wind farm grid integration

and protection based on EMTP modelling. His main research fields includecontrol of electric machinery and drives for renewable energy systems andmodelling and analysis of wind power plants connected to large powersystems.

Giampaolo Buticchi (S’10-M’13-SM’17) receivedthe Masters degree in Electronic Engineering in2009 and the Ph.D degree in Information Technolo-gies in 2013 from the University of Parma, Italy. In2012 he was visiting researcher at The Universityof Nottingham, UK. Between 2014 and 2017 hewas a post-doctoral researcher at the University ofKiel, Germany. He is now Associate Professor inElectrical Engineering at The University of Notting-ham Ningbo China. His research area is focusedon power electronics for renewable energy systems,

smart transformer fed micro-grids and dc grids for the More Electric Aircraft.He is author/co-author of more than 150 scientific papers.

Soenke Engelken (S’08-M’12) is the Head of Con-trol Engineering at WRD Wobben Research andDevelopment. The Control Engineering departmentdevelops control solutions for wind energy con-verters, spanning wind turbine controls, electricalsystems controls and grid-side converter controls.Prior to joining Wobben Research and Development,he received his Ph.D. and M.Sc. degrees in controlengineering from the University of Manchester, UK,in 2012 and 2008, respectively, as well as his B.Sc.degree in electrical engineering and computer sci-

ence from Jacobs University Bremen, Germany, in 2007. He is a memberof the IEEE Power and Energy Society, the IEEE Control Systems Society,of CIGRE Joint Working Group A1/C4.52 Wind Generators and Frequency-Active Power Control and of the ENTSO-E Expert Group on High PenetrationIssues.

Marco Liserre (S’00-M’02-SM’07-F’13) receivedthe MSc and PhD degree in Electrical Engineeringfrom the Bari Polytechnic, respectively in 1998and 2002. He has been Associate Professor at BariPolytechnic and Professor at Aalborg University(Denmark). He is currently Full Professor and heholds the Chair of Power Electronics at Christian-Albrechts-University of Kiel (Germany). He haspublished over 300 technical papers (more than 86of them in international peer-reviewed journals) anda book. These works have received more than 20000

citations. Marco Liserre is listed in ISI Thomson report “The world’s mostinfluential scientific minds”.