Robert Poole Building #056 Addendum 2 Additions and Renovations Page 1 of 1 4/17/2018 Robert Poole Building #056 Secondary Technology Bid Package April 17, 2018 ADDENDUM NO. 2 This Addendum is issued pursuant to the Instructions to Bidders and Conditions of the Contract. This Addendum serves to clarify, revise, and supersede information in the Bid Documents, and previously issued Addenda. The bidder shall acknowledge receipt of this Addendum in the appropriate space on the Bid Form. The Bid Date remains unchanged by this Addendum. The following items will become part of the Bid Documents for this project: 1. JMT attachment Addendum #2 dated 4/16/2018. END OF ADDENDUM NO. 2

Robert Poole Secondary Technology Bid Package Addendum No. 2 · 2. Drawing TSD5.1, Detail 7 shows the dimensions of the Extron Wall-Vault wall-mount enclosure. The drawing shows that

  • Upload
    others

  • View
    1

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Robert Poole Secondary Technology Bid Package Addendum No. 2 · 2. Drawing TSD5.1, Detail 7 shows the dimensions of the Extron Wall-Vault wall-mount enclosure. The drawing shows that

Robert Poole Building #056    Addendum 2 Additions and Renovations  Page 1 of 1  4/17/2018 

Robert Poole Building #056 Secondary Technology

Bid Package April 17, 2018

ADDENDUM NO. 2

This Addendum is issued pursuant to the Instructions to Bidders and Conditions of the Contract. This Addendum serves to clarify, revise, and supersede information in the Bid Documents, and previously issued Addenda.

The bidder shall acknowledge receipt of this Addendum in the appropriate space on the Bid Form.

The Bid Date remains unchanged by this Addendum.

The following items will become part of the Bid Documents for this project:

1. JMT attachment Addendum #2 dated 4/16/2018.

 

 

END OF ADDENDUM NO. 2

 

 

 

 

Page 2: Robert Poole Secondary Technology Bid Package Addendum No. 2 · 2. Drawing TSD5.1, Detail 7 shows the dimensions of the Extron Wall-Vault wall-mount enclosure. The drawing shows that

Robert Poole Building #056

Addendum #2

Page 1

Addendum #2 DATE: 04/16/2018

PROJECT: Robert Poole Building #056

The following documents are in response to RFIs submitted on 4/12/18. Original RFI questions

are in black with responses in red. Additional sketches are attached to provide clarification to

some questions.

In addition to the RFI responses below, please note the relocation of the speakers in the

Collaborative Stair 224. Speakers shall be installed where indicated on Sheet TSD1.7

1. Please confirm that any AV systems in the Auditorium, Gymnasium or Dining area are not

part of this contract.

Correct, AV systems in the Gymnasium or Dining area are not part of this contract. This

school does not have an auditorium.

2. Drawing TSD5.1, Detail 7 shows the dimensions of the Extron Wall-Vault wall-mount

enclosure. The drawing shows that the enclosure’s backplate, which attaches to the wall, has

two cutouts, one for quad AC power and one for cable access. This would require two (2)

double gang junction boxes that are separated by only 1.3” on the wall at the ‘C’ locations for

the enclosure. During our walk-through, we noted several instances in which there was

considerably more separation between the junction boxes at the ‘C’ locations. Please confirm

these boxes will be properly spaced prior to installation, as no modifications can or will be made

to the enclosure backplates.

Enclosure backplates have been field modified and installed on previous projects. For

locations with more than 1.3” of separate between junction boxes, please field modify

the enclosure to accommodate the cabling. Any modifications necessary will need to be

made to the Extron enclosure in the field at no additional cost to the owner. If any

locations are found that will not accommodate the backplates after field modification,

please notify the contractor and JMT immediately.

3. Our review of the drawings have revealed about eight (8) Classrooms in which the drawings

show three (3) speakers in the classroom. While it is possible to wire a pair of speakers in

parallel to one channel and a single speaker to another channel, the volume for the speakers

wired to each channel will be different and there is no individual channel volume control, so

some speakers will be louder than others with no way to compensate for the volume difference.

Please confirm whether this number can be lowered to two (2) speakers or raised to four (4)

speakers and if which configuration should apply to which Classrooms.

Page 3: Robert Poole Secondary Technology Bid Package Addendum No. 2 · 2. Drawing TSD5.1, Detail 7 shows the dimensions of the Extron Wall-Vault wall-mount enclosure. The drawing shows that

Robert Poole Building #056

Addendum #2

Page 2

Please see attached revised sheets for new speaker configurations in the following

classrooms:

105A – Increased to 4 speakers

124 – Increased to 4 speakers

123 – Increased to 4 speakers

207 – Decreased to 2 speakers

201A – Increased to 4 speakers

202A – Increased to 4 speakers

220 – Increased to 4 speakers

231 – Increased to 4 speakers

321 – Increased to 4 speakers

327 – Increased to 4 speakers

328 – Increased to 4 speakers

329 – Increased to 4 speakers

4. The walk-through revealed several Classrooms on Level 1 in which the ceilings were very

high. We do not recommend installing ceiling speakers in areas with such high ceilings, as the

sound from the speakers will likely diffuse and reverberate to the point where intelligibility may

be affected. Please confirm whether ceiling speakers are still required in these rooms or if

surface speakers should be substituted and where they should be located.

Please see attached revised sheets for new speaker configurations.

5. Drawing TSD-1.1, detail 2, shows a Flex Space 121C-1 which has a Classroom system, but

no speakers are shown, presumably due to the open ceiling. Please confirm this system should

not have speakers included.

Please provide wall mounted speakers where indicated in attached revised sheets.

6. Drawing TSD-1.7 shows three (3) ceiling speakers in Theater/Dance Classroom 231. During

the walk-through, we noted that half the ceiling in this room is open and quite high and therefore

will not accommodate ceiling speakers. Please verify what speakers should be installed in this

room and where they should be located.

Please see attached revised sheets for new speaker configuration in Classroom 231.

Also note the new location of the Wireless Access Point to be installed on the drop

ceiling portion of the classroom.

7. Please confirm how many Classroom systems require surface mounted speakers instead of

ceiling speakers. The drawings only show one, but we believe there are Classrooms such as

231 and others that may be better served with surface mount speakers.

Page 4: Robert Poole Secondary Technology Bid Package Addendum No. 2 · 2. Drawing TSD5.1, Detail 7 shows the dimensions of the Extron Wall-Vault wall-mount enclosure. The drawing shows that

Robert Poole Building #056

Addendum #2

Page 3

Please see attached revised sheets for new speaker configurations.

8. Due to the extreme height of some of the Classrooms, we will require man-lifts to get access

to the ceiling for cable pulls, as well as equipment installation. Please confirm that the AV

vendor should provide any lifts and that we will be able to bring them into the worksite.

Any lifts required will have to be provided by the AV contractor. A small man-lift can be

used on the first floor only as long as floor protection is provided.

9. Please confirm if the Comcast Set top boxes that the school will provide for the Video

Distribution System head-end rack are analog or digital.

The Comcast set-top box/ DTA boxes are digital standard definition cable TV boxes.

10. Please confirm the make and model of the rack for the CATV head-end for the Cable

Distribution system. Neither the Specifications nor the Drawings provide this information.

Please be advised that we cannot use a 2-post rack as specified in the drawings (TSD-5.0,

detail 2) for the video distribution head-end equipment.

Please provide a 2-post for Video Distribution rack as indicated on TSD-5.0 Detail 2.

Make and model shall be in accordance with specifications. The most recent school

projects following this design have both used 2-post racks. For equipment that cannot

be rack-mounted please provide a rack mounted shelf.

11. Please confirm whether Performance and Payment Bond should be included as part of the

base bid or if it should be included as an Add-Alt.

Performance and Payment Bond is an additional cost as indicated on the Bid Form.

Page 5: Robert Poole Secondary Technology Bid Package Addendum No. 2 · 2. Drawing TSD5.1, Detail 7 shows the dimensions of the Extron Wall-Vault wall-mount enclosure. The drawing shows that

FEC

FE

C

SE SESESEF

EC

VP OFFICE

040

CONF

041

CORRIDOR

001F

STAIR A2-0

SA2-0

L

STG-COLLAB

049

STAIR A1-0

SA1-0

STG-ART

047

TR

049A

ELEC

048

ART STUDIO

046

ENV SCI

044

JC

051

STG-SCI

045

PREP

043STG-ADMIN

042

MEN

050

CORRIDOR-2

001G-2

WOMEN

052

C

L

PR PR

C

A1

A1

A1

DD

DD

DD

A1

A1

A1

A1

DDDDDDDD

DD

DD

DD

DD

3" CONDUIT TO GREEN HOUSE

DD

A1

A1

L1

PR1

W W

WW

MATC

HLIN

E

SEE TSD

-1.2

TSD-5.1

2

2

2

1

1

2 2 2 2 2 2

2

EXISTING CABLE TRAY (TYP.)

3

4

W

11

A1

EXISTING CONDUIT PATHWAYS6

CTE FLEX SPACE-1

121C-1

MEN

125

STG-PLTW

124A

STAIR A1-1

SA1-1

STG - CISCO

122A

CTE VEST

121A

WOMEN

126

STAIR A2-1

SA2-1

PR

PR

PR

PRL

L

L

CC

C

C

DD

DD

DD

DD

DD DD DD DD DD

DD

DDDD

DD

PLTW CR-1

124-1

GATEWAY CR

123

STG

121B

CISCO LAB

122

A1

DD

STG - COLLAB

121B

EX. 12" X 4" LADDER RACK8' AFF

L

DD DD

DD DD

WW

W

MATC

HLIN

E

SEE TSD

-1.3

11

1

1

2

EXISTING CABLE TRAY (TYP.)

4 55

5

5

W

W

W

SE

SE SE

SE

SE

SE

SE

SE

SE

SE

SE

SE

2

2

2

2

2

2

2

2

SE

SE

2 7

7

2

7

7

7

7

77

7

7

7

7

INFORMATION SHOWN ON THIS DRAWING PERTAINING TO EXISTING CONDITIONS HAVE BEEN OBTAINED FROMAVAILABLE BUILDING DRAWINGS OR GENERAL FIELD OBSERVATIONS AND MAY NOT INDICATE ACTUAL EXISTINGCONDITIONS IN DETAIL OR DIMENSION. THE CONTRACTOR IS RESPONSIBLE FOR DETERMINING THE ACTUALEXISTING CONDITIONS PRIOR TO FABRICATION OR PERFORMANCE OF ANY WORK. SHOULD CONDITIONS BEDISCOVERED THAT PREVENT EXECUTION OF THE WORK AS INDICATED, THE CONTRACTOR SHALL IMMEDIATELYNOTIFY THE ENGINEER IN WRITING AND AWAIT DIRECTION BEFORE PROCEEDING WITH THE WORK.

UNLESS OTHERWISE NOTED, TECHNOLOGY ITEMS SHOWN HEAVY SOLID ( ) SHALL BE NEW, ANDTECHNOLOGY ITEMS SHOWN LIGHT SOLID ( ) SHALL BE EXISTING TO REMAIN.

LOW-VOLTAGE CABLING SHALL BE RUN THROUGH EXISTING CONDUIT AND SLEEVES AS DESIGNATED IN THE A/EDESIGN DOCUMENTS. COORDINATE INSTALLATION OF ALL LOW-VOLTAGE CABLING WITH THE A/E DESIGNDOCUMENTS. TER 019B SHALL SERVE AS THE SERVICE PROVIDER POINT OF DEMARCATION. LOW VOLTAGECABLING RUNS ARE DESGINATED AS A DASHED HEAVY LINE ( ) INTO PENETRATIONS.

CABLE ROUTING IS SHOWN DIAGRAMATICALLY AS A SINGLE DASHED-LINE. ALL LOW VOLTAGE CABLING INHALLWAYS SHOULD BE HUNG FROM WIRE RUN IN CABLE TRAYS FURNISHED AND INSTALLED BY OTHERS. CABLESSHALL BE SEPERATED IN BUNDLES TO DIFFERENTIATE BETWEEN DATA, VOIP, AND SECURITY USAGE, BACK TOTHE TR ROOM SERVING THAT AREA.

J-HOOKS SHALL BE SPACED NO MORE THAN 5'-6" APART FOR SUPPORT OF LOW VOLTAGE CABLING. J-HOOKS TOBE USED IN HALLWAYS ONLY WHEN FIELD CONDITIONS REQUIRE. J-HOOKS TO BE USED IN OTHERROOMS/SPACES.

COORDINATE LOCATION OF ALL CEILING MOUNTED DEVICES AND CABLE RUNS WITH EXISTING CONDITIONS INTHE FIELD.

PENETRATIONS SHOWN ON DRAWINGS ARE EXISTING 2" CONDUITS UNLESS OTHERWISE NOTED.

GENERAL SHEET NOTES:1.

2.

3.

4.

5.

6.

7.

SHEET KEYNOTES:

C RUBELING & ASSOCIATES

A B C D E F G H J K L M N P Q R S T U

1

2

3

4

5

6

7

8

9

10

11

12

13

14

TITLE:

SCALE:

DATE:

PROJ. NO:

SHEET:

JOHNSON,MIRMIRAN,

& THOMPSON40 WIGHT AVE

HUNT VALLEY, MD 21030410.329.3100

FAX: 410.472.2200

CONSULTANT:

REVISIONS:

AD

DIT

ION

S &

RE

NO

VA

TIO

NS

AT

RO

BE

RT

PO

OL

E B

UIL

DIN

G #

056

BA

LT

IMO

RE

CIT

Y P

UB

LIC

SC

HO

OL

S

17-11797-003

Q:\2017\1711797_003_Design_-_Robert_Pool\CADD\MEP\Robert Poole Technology Design.rvt 4/17/2018 8:46:41 AM

As indicated

TECHNOLOGY -LEVELS 0A & 1APLAN

03/26/18

TSD-1.1

1300

W 3

6TH

ST

., B

AL

TIM

OR

E, M

D 2

1211

1/8" = 1'-0"TSD-1.1

LEVEL 0A1

1/8" = 1'-0"TSD-1.1

LEVEL 1A2

0' 4' 8' 16' 32'

1 PROVIDE EXTRON WALL VAULT SYSTEM AND CABLING AS PER DETAIL 10 ON SHEET TSD-5.3.

2 ALL DATA, VOIP, AND WIFI CABLES IN ROOM SHALL BE FED THROUGH EXISTING 2" CONDUIT SLEEVES ABOVE CEILING ANDFOLLOW DEDICATED PATHWAYS BACK TO TR/TER ROOMS.

3 PROVIDE (1) CAT 6A CABLE FOR WAP IN GREENHOUSE. WIFI CABLES SHALL BE FED THROUGH EXISTING 3" UNDERGROUNDCONDUIT EXTERIOR TO BUILDING AND FOLLOW DEDICATED PATHWAYS BACK TO TR/TER ROOMS. COORDINATE WITH BCS ONLOCATION OF WAP IN GREENHOUSE.

4 TWO EXISTING 4" FLOOR PENETRATIONS FROM LEVEL 0A CEILING TO LEVEL 1A FOR LOW VOLTAGE CABLES.

5 ALL DATA, VOIP, AND WIFI CABLES IN ROOM SHALL BE FED ABOVE DROP CEILING WITH J HOOKS AND FOLLOW DEDICATEDPATHWAYS BACK TO TR/TER ROOMS.

6 FOUR EXISTING 4" CONDUIT PENETRATIONS FOR ALL LOW VOLTAGE CABLES INTO TELECOMMUNICATION ROOM.

7 WALL MOUNTED SOUND ENHANCEMENT SPEAKER SHALL BE MOUNTED 10' AFF.

No. Description Date

ADDENDUM 22 4/16/2018

2

Page 6: Robert Poole Secondary Technology Bid Package Addendum No. 2 · 2. Drawing TSD5.1, Detail 7 shows the dimensions of the Extron Wall-Vault wall-mount enclosure. The drawing shows that

WD

FEC

FEC

FE

C

SE

SESE

SE SE

SE

SE

SE

SE

SE

SECURITY

101B

WORK-1

101C-1

T/SH

116

PASSAGE

110

CAREER READINESS

106B

LOBBY

100B

SW OFF

107E

PSY OFF

107D

FLEX SPACE

106VEST

100A

MAIN OFF RECEP

101A

TEST

102G

GUID RECEP

102ASTG

102BTR

102L

SW OFF

107C

PSY OFF

107B

CONF

101H

PRINCIPAL

101G AD ASST

101D

FLEX OFF

101E

FLEX OFF

107A

PASSAGE

107

CORRIDOR

100D

FLEX OFF

107F

ATTEN

101L

REST

103DSTG

101F

EXAM

103F

PASSAGE

103L

NURSE

103B

REST

103C

PANTRY

113

ELEC

104C

TLT

104B

OFF

102F

EXAM

103H

CAREER

102C

OFF

102D

OFF

102E

FACULTY

104E

SP ED OFF

104A

CORRIDOR

100C

WAIT

103A

TLT

103K

STG-SP ED

104D

CONF

102H

TR

114

ELEC

112

SCH STORE

109

STG-FURN

140

SGA OFF

109B

TLT

101K

STOR-SEC

101M

MEDIA CENTER

105A

PROJECT-1

105C-1

FLEX OFF

104F

PASSAGE

104STAIR B1-1

SB1-1

STG

103J

PASSAGE

101J

STG

107H

STAIR B2-1

SB2-1

TLT

109C

A1 A1A1

A1

A1

A1

A1A1

A1

A1

A1

A1 A1A1

A1

A1

A1

V

A1

A1

A1

A1

A1

L1

A1

A1

A1

A1

L1

A1

A1

A1

L1

A1

A1

STORAGE

105C STG

107J

A1

A1

A1

FLEX OFF

107G

A1

A1

A1 A1

PR

A1

PASSAGE

106A

L1

PR1

A1

V

STAIR B3-1

SB3-1

JC

108CARE

115B

LAUN

115A

DD

A1

1" CONDUIT TROUGH FLOORINTO CASEWORK FOR LOW

VOLTAGE CABLES.

A1

STG

105D

L1

A1

TLT

103G

L

L

C

C

PR

PR

A1

PR1

DD

A1A1

L1

PR1

A1

V

PR1

PR1

PR1

W

W

W

W

W

W

W

W

W W

WW

W

W

W

W

W

W

W

W

MA

TC

HLIN

E

SE

E T

SD

-1.1

MA

TC

HLIN

E

SE

E T

SD

-1.4

MA

TC

HLIN

E

SE

E T

SD

-1.4

MA

TC

HLIN

E

SE

E T

SD

-1.4

TR 102L SERVICE AREA TR 114 SERVICE AREA

1

1

2

22

2

2

2

2

2

2

2

2 3

2 2 22

2

2

22

2

2

22

2

2

44

2

2

2

2

2

2

2

2 2

2

22

2

2

2 2

3

2

2

2

2

2

TR 102L SERVICE AREA TR 114 SERVICE AREA

CAFETERIA AV EQUIPMENT CABINET (NIC)

CL

C WALL BOX PORTION OF TYPICAL "C" OUTLET. 8' AFF

KEYPAD PORTION OF TYPICAL "C" OUTLET. 48" AFF

TSD-5.1

1

TSD-5.1

10

A1

5

6

1

6

DD

T

7

2

INFORMATION SHOWN ON THIS DRAWING PERTAINING TO EXISTING CONDITIONS HAVE BEEN OBTAINED FROMAVAILABLE BUILDING DRAWINGS OR GENERAL FIELD OBSERVATIONS AND MAY NOT INDICATE ACTUAL EXISTINGCONDITIONS IN DETAIL OR DIMENSION. THE CONTRACTOR IS RESPONSIBLE FOR DETERMINING THE ACTUALEXISTING CONDITIONS PRIOR TO FABRICATION OR PERFORMANCE OF ANY WORK. SHOULD CONDITIONS BEDISCOVERED THAT PREVENT EXECUTION OF THE WORK AS INDICATED, THE CONTRACTOR SHALL IMMEDIATELYNOTIFY THE ENGINEER IN WRITING AND AWAIT DIRECTION BEFORE PROCEEDING WITH THE WORK.

UNLESS OTHERWISE NOTED, TECHNOLOGY ITEMS SHOWN HEAVY SOLID ( ) SHALL BE NEW, ANDTECHNOLOGY ITEMS SHOWN LIGHT SOLID ( ) SHALL BE EXISTING TO REMAIN.

LOW-VOLTAGE CABLING SHALL BE RUN THROUGH EXISTING CONDUIT AND SLEEVES AS DESIGNATED IN THE A/EDESIGN DOCUMENTS. COORDINATE INSTALLATION OF ALL LOW-VOLTAGE CABLING WITH THE A/E DESIGNDOCUMENTS. TER 019B SHALL SERVE AS THE SERVICE PROVIDER POINT OF DEMARCATION. LOW VOLTAGECABLING RUNS ARE DESGINATED AS A DASHED HEAVY LINE ( ) INTO PENETRATIONS.

CABLE ROUTING IS SHOWN DIAGRAMATICALLY AS A SINGLE DASHED-LINE. ALL LOW VOLTAGE CABLING INHALLWAYS SHOULD BE HUNG FROM WIRE RUN IN CABLE TRAYS FURNISHED AND INSTALLED BY OTHERS. CABLESSHALL BE SEPERATED IN BUNDLES TO DIFFERENTIATE BETWEEN DATA, VOIP, AND SECURITY USAGE, BACK TOTHE TR ROOM SERVING THAT AREA.

J-HOOKS SHALL BE SPACED NO MORE THAN 5'-6" APART FOR SUPPORT OF LOW VOLTAGE CABLING. J-HOOKS TOBE USED IN HALLWAYS ONLY WHEN FIELD CONDITIONS REQUIRE. J-HOOKS TO BE USED IN OTHERROOMS/SPACES.

COORDINATE LOCATION OF ALL CEILING MOUNTED DEVICES AND CABLE RUNS WITH EXISTING CONDITIONS INTHE FIELD.

PENETRATIONS SHOWN ON DRAWINGS ARE EXISTING 2" CONDUITS UNLESS OTHERWISE NOTED.

GENERAL SHEET NOTES:1.

2.

3.

4.

5.

6.

7.

SHEET KEYNOTES:

C RUBELING & ASSOCIATES

A B C D E F G H J K L M N P Q R S T U

1

2

3

4

5

6

7

8

9

10

11

12

13

14

TITLE:

SCALE:

DATE:

PROJ. NO:

SHEET:

JOHNSON,MIRMIRAN,

& THOMPSON40 WIGHT AVE

HUNT VALLEY, MD 21030410.329.3100

FAX: 410.472.2200

CONSULTANT:

REVISIONS:

AD

DIT

ION

S &

RE

NO

VA

TIO

NS

AT

RO

BE

RT

PO

OL

E B

UIL

DIN

G #

056

BA

LT

IMO

RE

CIT

Y P

UB

LIC

SC

HO

OL

S

17-11797-003

Q:\2017\1711797_003_Design_-_Robert_Pool\CADD\MEP\Robert Poole Technology Design.rvt 4/16/2018 5:35:54 PM

As indicated

TECHNOLOGY -LEVEL 1B PLAN

03/26/18

TSD-1.3

1300

W 3

6TH

ST

., B

AL

TIM

OR

E, M

D 2

1211

1/8" = 1'-0"TSD-1.3

LEVEL 1B1

0' 4' 8' 16' 32'

1 PROVIDE EXTRON WALL VAULT SYSTEM AND CABLING AS PER DETAIL 10 ON SHEET TSD-5.3.

2 ALL DATA, VOIP, AND WIFI CABLES IN ROOM SHALL BE FED THROUGH EXISTING 2" CONDUIT SLEEVES ABOVE CEILINGAND FOLLOW DEDICATED PATHWAYS BACK TO TR/TER ROOMS.

3 THREE EXISTING 4" CONDUIT PENETRATIONS BETWEEN FLOORS FOR LOW VOLTAGE CABLES.

4 TERMINATE DATA AND VOIP CABLES IN "TER 019B" ON FLOOR 0B.

5 TWO EXISTING 2" CONDUIT SLEEVES FOR BACKBONE CABLES FROM "TER 019B" TO "TR 147."

6 FOUR EXISTING 4" CONDUIT PENETRATIONS FOR ALL LOW VOLTAGE CABLES INTO TELECOMMUNICATION ROOM.

7 PROVIDE TWO CAT5E CABLES FROM FACP TO "TER 019B" FOR ANALOG PHONE LINES AND TERMINATE AT VERIZONBLOCK. TECHNOLOGY CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING EXACT LOCATION OFTERMINATIONS IN FACP AND PROVIDE TAGS FOR EACH CABLE WITH THE VERIZON PHONE NUMBER. TERMINATIONSSHALL BE MADE BY CONSTRUCTION MANAGEMENTS TRADE CONTRACTORS AS PART OF GMP WORK.

EXISTING CABLE TRAY (TYP.)

No. Description Date

ADDENDUM 22 4/16/2018

Page 7: Robert Poole Secondary Technology Bid Package Addendum No. 2 · 2. Drawing TSD5.1, Detail 7 shows the dimensions of the Extron Wall-Vault wall-mount enclosure. The drawing shows that

FE

C

FEC

FEC

SESESESESESESESESESESESESE

SE

SE

SE

SESE SESE SE SE SESE

SE

SE

SESE

SE

SE

SE

SE

SE SE

CHEMISTRY

201A

BIOLOGY

202A

PREP

201C

WOMEN

215

TLT

216

COLLAB

202E

CLASSRM (Type 2)

213

CLASSRM (Type 2)

209

SE OFF

209ACLASSRM (Type 2)

204A

CLASSRM (Type 8)

206

TR

219

CORRIDOR

200C

CORRIDOR

200B

CLASSRM (Type 1C)

212

CLASSRM (Type 1B)

210

CLASSRM (Type 1B)

203

CLASSRM (Type 1C)

205

FOT LAB

207

CLASSRM (Type 5)

208

CLASSRM (Type 4)

214

STAIR B2-2

SB2-2

STAIR B1-2

SB1-2 L

C

PR

DD

L

C

PR

PR

PR

L

LC

C

DD

CC

L L

PRPR

DD DD

PR

L

C

DD

DD

A1

A1

PR

L

C

DD

DD

PR

L

C

L

C

PR

DD

CLASSRM (Type 3)

204B

PREP

202B

CLASSRM (Type 3)

211

PR

L

C C

L

PR

DD

DD DD DD

DD

DD

DD

PR

L

C

DD

PR

L

C

DD

PR

L

C

ELEC

218

DD

DD

A1

MEN

217

STG-COLLAB

202C

COLLAB

202D

CORRIDOR

200A

A1

STG-CHEM

201BDD

DD

STAIR B3-2

SB3-2

A1

DD

DD

WWWWWW

W

W W W W W

W

MA

TC

HLIN

E

SE

E T

SD

-1.7

MA

TC

HLIN

E

SE

E T

SD

-1.7

MA

TC

HLIN

E

SE

E T

SD

-1.7

W W

WWW

MA

TC

HLIN

E

SE

E T

SD

-1.5

EXISTING CABLE TRAY (TYP.)

1

2

1

2

11

2

2

3

2

2

2

22 2 2

2 2

2

2

2

2

1

11

1 1

1111

11

TR 102L SERVICE AREA TR 219 SERVICE AREA

TR 102L SERVICE AREA TR 219 SERVICE AREA

TSD-5.1

4

4

5

2

2

2

2

INFORMATION SHOWN ON THIS DRAWING PERTAINING TO EXISTING CONDITIONS HAVE BEEN OBTAINED FROMAVAILABLE BUILDING DRAWINGS OR GENERAL FIELD OBSERVATIONS AND MAY NOT INDICATE ACTUAL EXISTINGCONDITIONS IN DETAIL OR DIMENSION. THE CONTRACTOR IS RESPONSIBLE FOR DETERMINING THE ACTUALEXISTING CONDITIONS PRIOR TO FABRICATION OR PERFORMANCE OF ANY WORK. SHOULD CONDITIONS BEDISCOVERED THAT PREVENT EXECUTION OF THE WORK AS INDICATED, THE CONTRACTOR SHALL IMMEDIATELYNOTIFY THE ENGINEER IN WRITING AND AWAIT DIRECTION BEFORE PROCEEDING WITH THE WORK.

UNLESS OTHERWISE NOTED, TECHNOLOGY ITEMS SHOWN HEAVY SOLID ( ) SHALL BE NEW, ANDTECHNOLOGY ITEMS SHOWN LIGHT SOLID ( ) SHALL BE EXISTING TO REMAIN.

LOW-VOLTAGE CABLING SHALL BE RUN THROUGH EXISTING CONDUIT AND SLEEVES AS DESIGNATED IN THE A/EDESIGN DOCUMENTS. COORDINATE INSTALLATION OF ALL LOW-VOLTAGE CABLING WITH THE A/E DESIGNDOCUMENTS. TER 019B SHALL SERVE AS THE SERVICE PROVIDER POINT OF DEMARCATION. LOW VOLTAGECABLING RUNS ARE DESGINATED AS A DASHED HEAVY LINE ( ) INTO PENETRATIONS.

CABLE ROUTING IS SHOWN DIAGRAMATICALLY AS A SINGLE DASHED-LINE. ALL LOW VOLTAGE CABLING INHALLWAYS SHOULD BE HUNG FROM WIRE RUN IN CABLE TRAYS FURNISHED AND INSTALLED BY OTHERS. CABLESSHALL BE SEPERATED IN BUNDLES TO DIFFERENTIATE BETWEEN DATA, VOIP, AND SECURITY USAGE, BACK TOTHE TR ROOM SERVING THAT AREA.

J-HOOKS SHALL BE SPACED NO MORE THAN 5'-6" APART FOR SUPPORT OF LOW VOLTAGE CABLING. J-HOOKS TOBE USED IN HALLWAYS ONLY WHEN FIELD CONDITIONS REQUIRE. J-HOOKS TO BE USED IN OTHERROOMS/SPACES.

COORDINATE LOCATION OF ALL CEILING MOUNTED DEVICES AND CABLE RUNS WITH EXISTING CONDITIONS INTHE FIELD.

PENETRATIONS SHOWN ON DRAWINGS ARE EXISTING 2" CONDUITS UNLESS OTHERWISE NOTED.

GENERAL SHEET NOTES:1.

2.

3.

4.

5.

6.

7.

SHEET KEYNOTES:

C RUBELING & ASSOCIATES

A B C D E F G H J K L M N P Q R S T U

1

2

3

4

5

6

7

8

9

10

11

12

13

14

TITLE:

SCALE:

DATE:

PROJ. NO:

SHEET:

JOHNSON,MIRMIRAN,

& THOMPSON40 WIGHT AVE

HUNT VALLEY, MD 21030410.329.3100

FAX: 410.472.2200

CONSULTANT:

REVISIONS:

AD

DIT

ION

S &

RE

NO

VA

TIO

NS

AT

RO

BE

RT

PO

OL

E B

UIL

DIN

G #

056

BA

LT

IMO

RE

CIT

Y P

UB

LIC

SC

HO

OL

S

17-11797-003

Q:\2017\1711797_003_Design_-_Robert_Pool\CADD\MEP\Robert Poole Technology Design.rvt 4/16/2018 5:35:56 PM

As indicated

TECHNOLOGY -LEVEL 2B PLAN

03/26/18

TSD-1.6

1300

W 3

6TH

ST

., B

AL

TIM

OR

E, M

D 2

1211

1/8" = 1'-0"TSD-1.6

LEVEL 2B1

0' 4' 8' 16' 32'

1 PROVIDE EXTRON WALL VAULT SYSTEM AND CABLING AS PER DETAIL 10 ON SHEET TSD-5.3.

2 ALL DATA, VOIP, AND WIFI CABLES IN ROOM SHALL BE FED THROUGH EXISTING 2" CONDUIT SLEEVES ABOVE CEILINGAND FOLLOW DEDICATED PATHWAYS BACK TO TR/TER ROOMS.

3 THREE EXISTING 4" CONDUIT PENETRATIONS BETWEEN FLOORS FOR LOW VOLTAGE CABLES.

4 FOUR EXISTING 4" CONDUIT PENETRATIONS BETWEEN FLOORS FOR LOW VOLTAGE CABLES.

5 FOUR EXISTING 4" CONDUIT PENETRATIONS FOR ALL LOW VOLTAGE CABLES INTO TELECOMMUNICATION ROOM.

No. Description Date

ADDENDUM 22 4/16/2018

Page 8: Robert Poole Secondary Technology Bid Package Addendum No. 2 · 2. Drawing TSD5.1, Detail 7 shows the dimensions of the Extron Wall-Vault wall-mount enclosure. The drawing shows that

FE

C

SE

SE

SE

SE

SE

SE

SE

SE

SE

SE SE

SE SE

SE

RESOURCE

223

PLANNING

221

CLASSRM (Type 9)

228

THEATER/DANCE CR

231

CLASSRM (Type 10)

229

PHYSICS

220

JC

222

BIOLOGY

233

PREP

233A

CORRIDOR

200F

OFFICE

226

VP OFF

227

CLASSRM (Type 11)

230

COLLAB STAIR

224

PR

DD

L

C

DD

PR

L

C

PR

L

C

DD

DD

DD

DD

STG

231A

STAIR C1-2

SC1-2

A1

A1

A1

A1 A1

DD

DD

A1

A1A1

A1

A1

DD

DD

DD

DD

DD

PR

L

C

DD

DD

CORRIDOR

200G

PREP

220A

ELEV 1

E1-2

STG-COLLAB

221A

TLT

225A1

A1

CONTROL

232

L CPR

EX. 4" CONDUITTHROUGH WALL 18"AFF

DD

DD

DD

A1

A1

PR

L

C

A1

A1

DD

PR

L

MATC

HLIN

E

SEE TSD

-1.6

MATC

HLIN

E

SEE TSD

-1.6

MATC

HLIN

E

SEE TSD

-1.6

W

W

W

W

W

W

W

W

W

EXISTING CABLETRAY (TYP.)

1

2

2

1

1

2

2

2

2

1

2

2

2

2

2

1

2

2

1

2

A1

C

1

W

SE

SE

SE

SE

2

2

3

3

3

3

SE

SE

4

4

2

2

INFORMATION SHOWN ON THIS DRAWING PERTAINING TO EXISTING CONDITIONS HAVE BEEN OBTAINED FROMAVAILABLE BUILDING DRAWINGS OR GENERAL FIELD OBSERVATIONS AND MAY NOT INDICATE ACTUAL EXISTINGCONDITIONS IN DETAIL OR DIMENSION. THE CONTRACTOR IS RESPONSIBLE FOR DETERMINING THE ACTUALEXISTING CONDITIONS PRIOR TO FABRICATION OR PERFORMANCE OF ANY WORK. SHOULD CONDITIONS BEDISCOVERED THAT PREVENT EXECUTION OF THE WORK AS INDICATED, THE CONTRACTOR SHALL IMMEDIATELYNOTIFY THE ENGINEER IN WRITING AND AWAIT DIRECTION BEFORE PROCEEDING WITH THE WORK.

UNLESS OTHERWISE NOTED, TECHNOLOGY ITEMS SHOWN HEAVY SOLID ( ) SHALL BE NEW, ANDTECHNOLOGY ITEMS SHOWN LIGHT SOLID ( ) SHALL BE EXISTING TO REMAIN.

LOW-VOLTAGE CABLING SHALL BE RUN THROUGH EXISTING CONDUIT AND SLEEVES AS DESIGNATED IN THE A/EDESIGN DOCUMENTS. COORDINATE INSTALLATION OF ALL LOW-VOLTAGE CABLING WITH THE A/E DESIGNDOCUMENTS. TER 019B SHALL SERVE AS THE SERVICE PROVIDER POINT OF DEMARCATION. LOW VOLTAGECABLING RUNS ARE DESGINATED AS A DASHED HEAVY LINE ( ) INTO PENETRATIONS.

CABLE ROUTING IS SHOWN DIAGRAMATICALLY AS A SINGLE DASHED-LINE. ALL LOW VOLTAGE CABLING INHALLWAYS SHOULD BE HUNG FROM WIRE RUN IN CABLE TRAYS FURNISHED AND INSTALLED BY OTHERS. CABLESSHALL BE SEPERATED IN BUNDLES TO DIFFERENTIATE BETWEEN DATA, VOIP, AND SECURITY USAGE, BACK TOTHE TR ROOM SERVING THAT AREA.

J-HOOKS SHALL BE SPACED NO MORE THAN 5'-6" APART FOR SUPPORT OF LOW VOLTAGE CABLING. J-HOOKS TOBE USED IN HALLWAYS ONLY WHEN FIELD CONDITIONS REQUIRE. J-HOOKS TO BE USED IN OTHERROOMS/SPACES.

COORDINATE LOCATION OF ALL CEILING MOUNTED DEVICES AND CABLE RUNS WITH EXISTING CONDITIONS INTHE FIELD.

PENETRATIONS SHOWN ON DRAWINGS ARE EXISTING 2" CONDUITS UNLESS OTHERWISE NOTED.

GENERAL SHEET NOTES:1.

2.

3.

4.

5.

6.

7.

SHEET KEYNOTES:

C RUBELING & ASSOCIATES

A B C D E F G H J K L M N P Q R S T U

1

2

3

4

5

6

7

8

9

10

11

12

13

14

TITLE:

SCALE:

DATE:

PROJ. NO:

SHEET:

JOHNSON,MIRMIRAN,

& THOMPSON40 WIGHT AVE

HUNT VALLEY, MD 21030410.329.3100

FAX: 410.472.2200

CONSULTANT:

REVISIONS:

AD

DIT

ION

S &

RE

NO

VA

TIO

NS

AT

RO

BE

RT

PO

OL

E B

UIL

DIN

G #

056

BA

LT

IMO

RE

CIT

Y P

UB

LIC

SC

HO

OL

S

17-11797-003

Q:\2017\1711797_003_Design_-_Robert_Pool\CADD\MEP\Robert Poole Technology Design.rvt 4/16/2018 5:35:58 PM

As indicated

TECHNOLOGY -LEVEL 2C PLAN

03/26/18

TSD-1.7

1300

W 3

6TH

ST

., B

AL

TIM

OR

E, M

D 2

1211

1/8" = 1'-0"TSD-1.7

LEVEL 2C1

0' 4' 8' 16' 32'

1 PROVIDE EXTRON WALL VAULT SYSTEM AND CABLING AS PER DETAIL 10 ON SHEET TSD-5.3.

2 ALL DATA, VOIP, AND WIFI CABLES IN ROOM SHALL BE FED THROUGH EXISTING 2" CONDUIT SLEEVES ABOVE CEILINGAND FOLLOW DEDICATED PATHWAYS BACK TO TR/TER ROOMS.

3 WALL MOUNTED SOUND ENHANCEMENT SPEAKER SHALL BE MOUNTED 10' AFF.

4 WALL MOUNTED SOUND ENHANCEMENT SPEAKER SHALL BE MOUNTED 15' AFF AND CENTERED ON COLUMN.

No. Description Date

ADDENDUM 22 4/16/2018

2

Page 9: Robert Poole Secondary Technology Bid Package Addendum No. 2 · 2. Drawing TSD5.1, Detail 7 shows the dimensions of the Extron Wall-Vault wall-mount enclosure. The drawing shows that

FE

C

SE

SE

SE SE

SESE

SE SE

SE

SE

SE

SE

SE

SE

SE

SE

SE

SE

ROOF ACCESS

324A

ART STUDIO 3D

327

ART STUDIO

328

VOCAL MUSIC

330

PHYSICS

321

STAIR C1-3

SC1-3

C

L

PR

CORRIDOR

300E

COLLAB

326

STG

328A

STG-INSTR

329A

PR

L

C

C

L

PR

A1

L

C

PR

A1

A1

A1

A1

DD

DD

DD

DD

DD

DD

DD

DD

DD

CORRIDOR

300F

STG-SCI

321A

JC

322

ELEV 1

E1-3

TLT

325

A1

PLANNING

323

INSTR MUSIC

329

KILN

327A

L

PR

C

STG-COLLAB

323A

ASST PRINCIPAL OFFICE

324

DD

DD

A1

A1

A1

A1

A1

DD

MATC

HLIN

E

SEE TSD

-1.8

MATC

HLIN

E

SEE TSD

-1.8

MATC

HLIN

E

SEE TSD

-1.8

W

W

W

W

W

W

W

W

1

2

2

2

2

2

2

2

1

1

2

1

2

2

EXISTING CABLE TRAY (TYP.)

2

INFORMATION SHOWN ON THIS DRAWING PERTAINING TO EXISTING CONDITIONS HAVE BEEN OBTAINED FROMAVAILABLE BUILDING DRAWINGS OR GENERAL FIELD OBSERVATIONS AND MAY NOT INDICATE ACTUAL EXISTINGCONDITIONS IN DETAIL OR DIMENSION. THE CONTRACTOR IS RESPONSIBLE FOR DETERMINING THE ACTUALEXISTING CONDITIONS PRIOR TO FABRICATION OR PERFORMANCE OF ANY WORK. SHOULD CONDITIONS BEDISCOVERED THAT PREVENT EXECUTION OF THE WORK AS INDICATED, THE CONTRACTOR SHALL IMMEDIATELYNOTIFY THE ENGINEER IN WRITING AND AWAIT DIRECTION BEFORE PROCEEDING WITH THE WORK.

UNLESS OTHERWISE NOTED, TECHNOLOGY ITEMS SHOWN HEAVY SOLID ( ) SHALL BE NEW, ANDTECHNOLOGY ITEMS SHOWN LIGHT SOLID ( ) SHALL BE EXISTING TO REMAIN.

LOW-VOLTAGE CABLING SHALL BE RUN THROUGH EXISTING CONDUIT AND SLEEVES AS DESIGNATED IN THE A/EDESIGN DOCUMENTS. COORDINATE INSTALLATION OF ALL LOW-VOLTAGE CABLING WITH THE A/E DESIGNDOCUMENTS. TER 019B SHALL SERVE AS THE SERVICE PROVIDER POINT OF DEMARCATION. LOW VOLTAGECABLING RUNS ARE DESGINATED AS A DASHED HEAVY LINE ( ) INTO PENETRATIONS.

CABLE ROUTING IS SHOWN DIAGRAMATICALLY AS A SINGLE DASHED-LINE. ALL LOW VOLTAGE CABLING INHALLWAYS SHOULD BE HUNG FROM WIRE RUN IN CABLE TRAYS FURNISHED AND INSTALLED BY OTHERS. CABLESSHALL BE SEPERATED IN BUNDLES TO DIFFERENTIATE BETWEEN DATA, VOIP, AND SECURITY USAGE, BACK TOTHE TR ROOM SERVING THAT AREA.

J-HOOKS SHALL BE SPACED NO MORE THAN 5'-6" APART FOR SUPPORT OF LOW VOLTAGE CABLING. J-HOOKS TOBE USED IN HALLWAYS ONLY WHEN FIELD CONDITIONS REQUIRE. J-HOOKS TO BE USED IN OTHERROOMS/SPACES.

COORDINATE LOCATION OF ALL CEILING MOUNTED DEVICES AND CABLE RUNS WITH EXISTING CONDITIONS INTHE FIELD.

PENETRATIONS SHOWN ON DRAWINGS ARE EXISTING 2" CONDUITS UNLESS OTHERWISE NOTED.

GENERAL SHEET NOTES:1.

2.

3.

4.

5.

6.

7.

SHEET KEYNOTES:

C RUBELING & ASSOCIATES

A B C D E F G H J K L M N P Q R S T U

1

2

3

4

5

6

7

8

9

10

11

12

13

14

TITLE:

SCALE:

DATE:

PROJ. NO:

SHEET:

JOHNSON,MIRMIRAN,

& THOMPSON40 WIGHT AVE

HUNT VALLEY, MD 21030410.329.3100

FAX: 410.472.2200

CONSULTANT:

REVISIONS:

AD

DIT

ION

S &

RE

NO

VA

TIO

NS

AT

RO

BE

RT

PO

OL

E B

UIL

DIN

G #

056

BA

LT

IMO

RE

CIT

Y P

UB

LIC

SC

HO

OL

S

17-11797-003

Q:\2017\1711797_003_Design_-_Robert_Pool\CADD\MEP\Robert Poole Technology Design.rvt 4/16/2018 5:36:00 PM

As indicated

TECHNOLOGY -LEVEL 3C PLAN

03/26/18

TSD-1.9

1300

W 3

6TH

ST

., B

AL

TIM

OR

E, M

D 2

1211

1/8" = 1'-0"TSD-1.9

LEVEL 3C1

0' 4' 8' 16' 32'

1 PROVIDE EXTRON WALL VAULT SYSTEM AND CABLING AS PER DETAIL 10 ON SHEET TSD-5.3.

2 ALL DATA, VOIP, AND WIFI CABLES IN ROOM SHALL BE FED THROUGH EXISTING 2" CONDUIT SLEEVES ABOVE CEILINGAND FOLLOW DEDICATED PATHWAYS BACK TO TR/TER ROOMS.

No. Description Date

ADDENDUM 22 4/16/2018

2

2

2