Robert Poole Building #056 Addendum 2 Additions and Renovations Page 1 of 1 4/17/2018
Robert Poole Building #056 Secondary Technology
Bid Package April 17, 2018
ADDENDUM NO. 2
This Addendum is issued pursuant to the Instructions to Bidders and Conditions of the Contract. This Addendum serves to clarify, revise, and supersede information in the Bid Documents, and previously issued Addenda.
The bidder shall acknowledge receipt of this Addendum in the appropriate space on the Bid Form.
The Bid Date remains unchanged by this Addendum.
The following items will become part of the Bid Documents for this project:
1. JMT attachment Addendum #2 dated 4/16/2018.
END OF ADDENDUM NO. 2
Robert Poole Building #056
Addendum #2
Page 1
Addendum #2 DATE: 04/16/2018
PROJECT: Robert Poole Building #056
The following documents are in response to RFIs submitted on 4/12/18. Original RFI questions
are in black with responses in red. Additional sketches are attached to provide clarification to
some questions.
In addition to the RFI responses below, please note the relocation of the speakers in the
Collaborative Stair 224. Speakers shall be installed where indicated on Sheet TSD1.7
1. Please confirm that any AV systems in the Auditorium, Gymnasium or Dining area are not
part of this contract.
Correct, AV systems in the Gymnasium or Dining area are not part of this contract. This
school does not have an auditorium.
2. Drawing TSD5.1, Detail 7 shows the dimensions of the Extron Wall-Vault wall-mount
enclosure. The drawing shows that the enclosure’s backplate, which attaches to the wall, has
two cutouts, one for quad AC power and one for cable access. This would require two (2)
double gang junction boxes that are separated by only 1.3” on the wall at the ‘C’ locations for
the enclosure. During our walk-through, we noted several instances in which there was
considerably more separation between the junction boxes at the ‘C’ locations. Please confirm
these boxes will be properly spaced prior to installation, as no modifications can or will be made
to the enclosure backplates.
Enclosure backplates have been field modified and installed on previous projects. For
locations with more than 1.3” of separate between junction boxes, please field modify
the enclosure to accommodate the cabling. Any modifications necessary will need to be
made to the Extron enclosure in the field at no additional cost to the owner. If any
locations are found that will not accommodate the backplates after field modification,
please notify the contractor and JMT immediately.
3. Our review of the drawings have revealed about eight (8) Classrooms in which the drawings
show three (3) speakers in the classroom. While it is possible to wire a pair of speakers in
parallel to one channel and a single speaker to another channel, the volume for the speakers
wired to each channel will be different and there is no individual channel volume control, so
some speakers will be louder than others with no way to compensate for the volume difference.
Please confirm whether this number can be lowered to two (2) speakers or raised to four (4)
speakers and if which configuration should apply to which Classrooms.
Robert Poole Building #056
Addendum #2
Page 2
Please see attached revised sheets for new speaker configurations in the following
classrooms:
105A – Increased to 4 speakers
124 – Increased to 4 speakers
123 – Increased to 4 speakers
207 – Decreased to 2 speakers
201A – Increased to 4 speakers
202A – Increased to 4 speakers
220 – Increased to 4 speakers
231 – Increased to 4 speakers
321 – Increased to 4 speakers
327 – Increased to 4 speakers
328 – Increased to 4 speakers
329 – Increased to 4 speakers
4. The walk-through revealed several Classrooms on Level 1 in which the ceilings were very
high. We do not recommend installing ceiling speakers in areas with such high ceilings, as the
sound from the speakers will likely diffuse and reverberate to the point where intelligibility may
be affected. Please confirm whether ceiling speakers are still required in these rooms or if
surface speakers should be substituted and where they should be located.
Please see attached revised sheets for new speaker configurations.
5. Drawing TSD-1.1, detail 2, shows a Flex Space 121C-1 which has a Classroom system, but
no speakers are shown, presumably due to the open ceiling. Please confirm this system should
not have speakers included.
Please provide wall mounted speakers where indicated in attached revised sheets.
6. Drawing TSD-1.7 shows three (3) ceiling speakers in Theater/Dance Classroom 231. During
the walk-through, we noted that half the ceiling in this room is open and quite high and therefore
will not accommodate ceiling speakers. Please verify what speakers should be installed in this
room and where they should be located.
Please see attached revised sheets for new speaker configuration in Classroom 231.
Also note the new location of the Wireless Access Point to be installed on the drop
ceiling portion of the classroom.
7. Please confirm how many Classroom systems require surface mounted speakers instead of
ceiling speakers. The drawings only show one, but we believe there are Classrooms such as
231 and others that may be better served with surface mount speakers.
Robert Poole Building #056
Addendum #2
Page 3
Please see attached revised sheets for new speaker configurations.
8. Due to the extreme height of some of the Classrooms, we will require man-lifts to get access
to the ceiling for cable pulls, as well as equipment installation. Please confirm that the AV
vendor should provide any lifts and that we will be able to bring them into the worksite.
Any lifts required will have to be provided by the AV contractor. A small man-lift can be
used on the first floor only as long as floor protection is provided.
9. Please confirm if the Comcast Set top boxes that the school will provide for the Video
Distribution System head-end rack are analog or digital.
The Comcast set-top box/ DTA boxes are digital standard definition cable TV boxes.
10. Please confirm the make and model of the rack for the CATV head-end for the Cable
Distribution system. Neither the Specifications nor the Drawings provide this information.
Please be advised that we cannot use a 2-post rack as specified in the drawings (TSD-5.0,
detail 2) for the video distribution head-end equipment.
Please provide a 2-post for Video Distribution rack as indicated on TSD-5.0 Detail 2.
Make and model shall be in accordance with specifications. The most recent school
projects following this design have both used 2-post racks. For equipment that cannot
be rack-mounted please provide a rack mounted shelf.
11. Please confirm whether Performance and Payment Bond should be included as part of the
base bid or if it should be included as an Add-Alt.
Performance and Payment Bond is an additional cost as indicated on the Bid Form.
FEC
FE
C
SE SESESEF
EC
VP OFFICE
040
CONF
041
CORRIDOR
001F
STAIR A2-0
SA2-0
L
STG-COLLAB
049
STAIR A1-0
SA1-0
STG-ART
047
TR
049A
ELEC
048
ART STUDIO
046
ENV SCI
044
JC
051
STG-SCI
045
PREP
043STG-ADMIN
042
MEN
050
CORRIDOR-2
001G-2
WOMEN
052
C
L
PR PR
C
A1
A1
A1
DD
DD
DD
A1
A1
A1
A1
DDDDDDDD
DD
DD
DD
DD
3" CONDUIT TO GREEN HOUSE
DD
A1
A1
L1
PR1
W W
WW
MATC
HLIN
E
SEE TSD
-1.2
TSD-5.1
2
2
2
1
1
2 2 2 2 2 2
2
EXISTING CABLE TRAY (TYP.)
3
4
W
11
A1
EXISTING CONDUIT PATHWAYS6
CTE FLEX SPACE-1
121C-1
MEN
125
STG-PLTW
124A
STAIR A1-1
SA1-1
STG - CISCO
122A
CTE VEST
121A
WOMEN
126
STAIR A2-1
SA2-1
PR
PR
PR
PRL
L
L
CC
C
C
DD
DD
DD
DD
DD DD DD DD DD
DD
DDDD
DD
PLTW CR-1
124-1
GATEWAY CR
123
STG
121B
CISCO LAB
122
A1
DD
STG - COLLAB
121B
EX. 12" X 4" LADDER RACK8' AFF
L
DD DD
DD DD
WW
W
MATC
HLIN
E
SEE TSD
-1.3
11
1
1
2
EXISTING CABLE TRAY (TYP.)
4 55
5
5
W
W
W
SE
SE SE
SE
SE
SE
SE
SE
SE
SE
SE
SE
2
2
2
2
2
2
2
2
SE
SE
2 7
7
2
7
7
7
7
77
7
7
7
7
INFORMATION SHOWN ON THIS DRAWING PERTAINING TO EXISTING CONDITIONS HAVE BEEN OBTAINED FROMAVAILABLE BUILDING DRAWINGS OR GENERAL FIELD OBSERVATIONS AND MAY NOT INDICATE ACTUAL EXISTINGCONDITIONS IN DETAIL OR DIMENSION. THE CONTRACTOR IS RESPONSIBLE FOR DETERMINING THE ACTUALEXISTING CONDITIONS PRIOR TO FABRICATION OR PERFORMANCE OF ANY WORK. SHOULD CONDITIONS BEDISCOVERED THAT PREVENT EXECUTION OF THE WORK AS INDICATED, THE CONTRACTOR SHALL IMMEDIATELYNOTIFY THE ENGINEER IN WRITING AND AWAIT DIRECTION BEFORE PROCEEDING WITH THE WORK.
UNLESS OTHERWISE NOTED, TECHNOLOGY ITEMS SHOWN HEAVY SOLID ( ) SHALL BE NEW, ANDTECHNOLOGY ITEMS SHOWN LIGHT SOLID ( ) SHALL BE EXISTING TO REMAIN.
LOW-VOLTAGE CABLING SHALL BE RUN THROUGH EXISTING CONDUIT AND SLEEVES AS DESIGNATED IN THE A/EDESIGN DOCUMENTS. COORDINATE INSTALLATION OF ALL LOW-VOLTAGE CABLING WITH THE A/E DESIGNDOCUMENTS. TER 019B SHALL SERVE AS THE SERVICE PROVIDER POINT OF DEMARCATION. LOW VOLTAGECABLING RUNS ARE DESGINATED AS A DASHED HEAVY LINE ( ) INTO PENETRATIONS.
CABLE ROUTING IS SHOWN DIAGRAMATICALLY AS A SINGLE DASHED-LINE. ALL LOW VOLTAGE CABLING INHALLWAYS SHOULD BE HUNG FROM WIRE RUN IN CABLE TRAYS FURNISHED AND INSTALLED BY OTHERS. CABLESSHALL BE SEPERATED IN BUNDLES TO DIFFERENTIATE BETWEEN DATA, VOIP, AND SECURITY USAGE, BACK TOTHE TR ROOM SERVING THAT AREA.
J-HOOKS SHALL BE SPACED NO MORE THAN 5'-6" APART FOR SUPPORT OF LOW VOLTAGE CABLING. J-HOOKS TOBE USED IN HALLWAYS ONLY WHEN FIELD CONDITIONS REQUIRE. J-HOOKS TO BE USED IN OTHERROOMS/SPACES.
COORDINATE LOCATION OF ALL CEILING MOUNTED DEVICES AND CABLE RUNS WITH EXISTING CONDITIONS INTHE FIELD.
PENETRATIONS SHOWN ON DRAWINGS ARE EXISTING 2" CONDUITS UNLESS OTHERWISE NOTED.
GENERAL SHEET NOTES:1.
2.
3.
4.
5.
6.
7.
SHEET KEYNOTES:
C RUBELING & ASSOCIATES
A B C D E F G H J K L M N P Q R S T U
1
2
3
4
5
6
7
8
9
10
11
12
13
14
TITLE:
SCALE:
DATE:
PROJ. NO:
SHEET:
JOHNSON,MIRMIRAN,
& THOMPSON40 WIGHT AVE
HUNT VALLEY, MD 21030410.329.3100
FAX: 410.472.2200
CONSULTANT:
REVISIONS:
AD
DIT
ION
S &
RE
NO
VA
TIO
NS
AT
RO
BE
RT
PO
OL
E B
UIL
DIN
G #
056
BA
LT
IMO
RE
CIT
Y P
UB
LIC
SC
HO
OL
S
17-11797-003
Q:\2017\1711797_003_Design_-_Robert_Pool\CADD\MEP\Robert Poole Technology Design.rvt 4/17/2018 8:46:41 AM
As indicated
TECHNOLOGY -LEVELS 0A & 1APLAN
03/26/18
TSD-1.1
1300
W 3
6TH
ST
., B
AL
TIM
OR
E, M
D 2
1211
1/8" = 1'-0"TSD-1.1
LEVEL 0A1
1/8" = 1'-0"TSD-1.1
LEVEL 1A2
0' 4' 8' 16' 32'
1 PROVIDE EXTRON WALL VAULT SYSTEM AND CABLING AS PER DETAIL 10 ON SHEET TSD-5.3.
2 ALL DATA, VOIP, AND WIFI CABLES IN ROOM SHALL BE FED THROUGH EXISTING 2" CONDUIT SLEEVES ABOVE CEILING ANDFOLLOW DEDICATED PATHWAYS BACK TO TR/TER ROOMS.
3 PROVIDE (1) CAT 6A CABLE FOR WAP IN GREENHOUSE. WIFI CABLES SHALL BE FED THROUGH EXISTING 3" UNDERGROUNDCONDUIT EXTERIOR TO BUILDING AND FOLLOW DEDICATED PATHWAYS BACK TO TR/TER ROOMS. COORDINATE WITH BCS ONLOCATION OF WAP IN GREENHOUSE.
4 TWO EXISTING 4" FLOOR PENETRATIONS FROM LEVEL 0A CEILING TO LEVEL 1A FOR LOW VOLTAGE CABLES.
5 ALL DATA, VOIP, AND WIFI CABLES IN ROOM SHALL BE FED ABOVE DROP CEILING WITH J HOOKS AND FOLLOW DEDICATEDPATHWAYS BACK TO TR/TER ROOMS.
6 FOUR EXISTING 4" CONDUIT PENETRATIONS FOR ALL LOW VOLTAGE CABLES INTO TELECOMMUNICATION ROOM.
7 WALL MOUNTED SOUND ENHANCEMENT SPEAKER SHALL BE MOUNTED 10' AFF.
No. Description Date
ADDENDUM 22 4/16/2018
2
WD
FEC
FEC
FE
C
SE
SESE
SE SE
SE
SE
SE
SE
SE
SECURITY
101B
WORK-1
101C-1
T/SH
116
PASSAGE
110
CAREER READINESS
106B
LOBBY
100B
SW OFF
107E
PSY OFF
107D
FLEX SPACE
106VEST
100A
MAIN OFF RECEP
101A
TEST
102G
GUID RECEP
102ASTG
102BTR
102L
SW OFF
107C
PSY OFF
107B
CONF
101H
PRINCIPAL
101G AD ASST
101D
FLEX OFF
101E
FLEX OFF
107A
PASSAGE
107
CORRIDOR
100D
FLEX OFF
107F
ATTEN
101L
REST
103DSTG
101F
EXAM
103F
PASSAGE
103L
NURSE
103B
REST
103C
PANTRY
113
ELEC
104C
TLT
104B
OFF
102F
EXAM
103H
CAREER
102C
OFF
102D
OFF
102E
FACULTY
104E
SP ED OFF
104A
CORRIDOR
100C
WAIT
103A
TLT
103K
STG-SP ED
104D
CONF
102H
TR
114
ELEC
112
SCH STORE
109
STG-FURN
140
SGA OFF
109B
TLT
101K
STOR-SEC
101M
MEDIA CENTER
105A
PROJECT-1
105C-1
FLEX OFF
104F
PASSAGE
104STAIR B1-1
SB1-1
STG
103J
PASSAGE
101J
STG
107H
STAIR B2-1
SB2-1
TLT
109C
A1 A1A1
A1
A1
A1
A1A1
A1
A1
A1
A1 A1A1
A1
A1
A1
V
A1
A1
A1
A1
A1
L1
A1
A1
A1
A1
L1
A1
A1
A1
L1
A1
A1
STORAGE
105C STG
107J
A1
A1
A1
FLEX OFF
107G
A1
A1
A1 A1
PR
A1
PASSAGE
106A
L1
PR1
A1
V
STAIR B3-1
SB3-1
JC
108CARE
115B
LAUN
115A
DD
A1
1" CONDUIT TROUGH FLOORINTO CASEWORK FOR LOW
VOLTAGE CABLES.
A1
STG
105D
L1
A1
TLT
103G
L
L
C
C
PR
PR
A1
PR1
DD
A1A1
L1
PR1
A1
V
PR1
PR1
PR1
W
W
W
W
W
W
W
W
W W
WW
W
W
W
W
W
W
W
W
MA
TC
HLIN
E
SE
E T
SD
-1.1
MA
TC
HLIN
E
SE
E T
SD
-1.4
MA
TC
HLIN
E
SE
E T
SD
-1.4
MA
TC
HLIN
E
SE
E T
SD
-1.4
TR 102L SERVICE AREA TR 114 SERVICE AREA
1
1
2
22
2
2
2
2
2
2
2
2 3
2 2 22
2
2
22
2
2
22
2
2
44
2
2
2
2
2
2
2
2 2
2
22
2
2
2 2
3
2
2
2
2
2
TR 102L SERVICE AREA TR 114 SERVICE AREA
CAFETERIA AV EQUIPMENT CABINET (NIC)
CL
C WALL BOX PORTION OF TYPICAL "C" OUTLET. 8' AFF
KEYPAD PORTION OF TYPICAL "C" OUTLET. 48" AFF
TSD-5.1
1
TSD-5.1
10
A1
5
6
1
6
DD
T
7
2
INFORMATION SHOWN ON THIS DRAWING PERTAINING TO EXISTING CONDITIONS HAVE BEEN OBTAINED FROMAVAILABLE BUILDING DRAWINGS OR GENERAL FIELD OBSERVATIONS AND MAY NOT INDICATE ACTUAL EXISTINGCONDITIONS IN DETAIL OR DIMENSION. THE CONTRACTOR IS RESPONSIBLE FOR DETERMINING THE ACTUALEXISTING CONDITIONS PRIOR TO FABRICATION OR PERFORMANCE OF ANY WORK. SHOULD CONDITIONS BEDISCOVERED THAT PREVENT EXECUTION OF THE WORK AS INDICATED, THE CONTRACTOR SHALL IMMEDIATELYNOTIFY THE ENGINEER IN WRITING AND AWAIT DIRECTION BEFORE PROCEEDING WITH THE WORK.
UNLESS OTHERWISE NOTED, TECHNOLOGY ITEMS SHOWN HEAVY SOLID ( ) SHALL BE NEW, ANDTECHNOLOGY ITEMS SHOWN LIGHT SOLID ( ) SHALL BE EXISTING TO REMAIN.
LOW-VOLTAGE CABLING SHALL BE RUN THROUGH EXISTING CONDUIT AND SLEEVES AS DESIGNATED IN THE A/EDESIGN DOCUMENTS. COORDINATE INSTALLATION OF ALL LOW-VOLTAGE CABLING WITH THE A/E DESIGNDOCUMENTS. TER 019B SHALL SERVE AS THE SERVICE PROVIDER POINT OF DEMARCATION. LOW VOLTAGECABLING RUNS ARE DESGINATED AS A DASHED HEAVY LINE ( ) INTO PENETRATIONS.
CABLE ROUTING IS SHOWN DIAGRAMATICALLY AS A SINGLE DASHED-LINE. ALL LOW VOLTAGE CABLING INHALLWAYS SHOULD BE HUNG FROM WIRE RUN IN CABLE TRAYS FURNISHED AND INSTALLED BY OTHERS. CABLESSHALL BE SEPERATED IN BUNDLES TO DIFFERENTIATE BETWEEN DATA, VOIP, AND SECURITY USAGE, BACK TOTHE TR ROOM SERVING THAT AREA.
J-HOOKS SHALL BE SPACED NO MORE THAN 5'-6" APART FOR SUPPORT OF LOW VOLTAGE CABLING. J-HOOKS TOBE USED IN HALLWAYS ONLY WHEN FIELD CONDITIONS REQUIRE. J-HOOKS TO BE USED IN OTHERROOMS/SPACES.
COORDINATE LOCATION OF ALL CEILING MOUNTED DEVICES AND CABLE RUNS WITH EXISTING CONDITIONS INTHE FIELD.
PENETRATIONS SHOWN ON DRAWINGS ARE EXISTING 2" CONDUITS UNLESS OTHERWISE NOTED.
GENERAL SHEET NOTES:1.
2.
3.
4.
5.
6.
7.
SHEET KEYNOTES:
C RUBELING & ASSOCIATES
A B C D E F G H J K L M N P Q R S T U
1
2
3
4
5
6
7
8
9
10
11
12
13
14
TITLE:
SCALE:
DATE:
PROJ. NO:
SHEET:
JOHNSON,MIRMIRAN,
& THOMPSON40 WIGHT AVE
HUNT VALLEY, MD 21030410.329.3100
FAX: 410.472.2200
CONSULTANT:
REVISIONS:
AD
DIT
ION
S &
RE
NO
VA
TIO
NS
AT
RO
BE
RT
PO
OL
E B
UIL
DIN
G #
056
BA
LT
IMO
RE
CIT
Y P
UB
LIC
SC
HO
OL
S
17-11797-003
Q:\2017\1711797_003_Design_-_Robert_Pool\CADD\MEP\Robert Poole Technology Design.rvt 4/16/2018 5:35:54 PM
As indicated
TECHNOLOGY -LEVEL 1B PLAN
03/26/18
TSD-1.3
1300
W 3
6TH
ST
., B
AL
TIM
OR
E, M
D 2
1211
1/8" = 1'-0"TSD-1.3
LEVEL 1B1
0' 4' 8' 16' 32'
1 PROVIDE EXTRON WALL VAULT SYSTEM AND CABLING AS PER DETAIL 10 ON SHEET TSD-5.3.
2 ALL DATA, VOIP, AND WIFI CABLES IN ROOM SHALL BE FED THROUGH EXISTING 2" CONDUIT SLEEVES ABOVE CEILINGAND FOLLOW DEDICATED PATHWAYS BACK TO TR/TER ROOMS.
3 THREE EXISTING 4" CONDUIT PENETRATIONS BETWEEN FLOORS FOR LOW VOLTAGE CABLES.
4 TERMINATE DATA AND VOIP CABLES IN "TER 019B" ON FLOOR 0B.
5 TWO EXISTING 2" CONDUIT SLEEVES FOR BACKBONE CABLES FROM "TER 019B" TO "TR 147."
6 FOUR EXISTING 4" CONDUIT PENETRATIONS FOR ALL LOW VOLTAGE CABLES INTO TELECOMMUNICATION ROOM.
7 PROVIDE TWO CAT5E CABLES FROM FACP TO "TER 019B" FOR ANALOG PHONE LINES AND TERMINATE AT VERIZONBLOCK. TECHNOLOGY CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING EXACT LOCATION OFTERMINATIONS IN FACP AND PROVIDE TAGS FOR EACH CABLE WITH THE VERIZON PHONE NUMBER. TERMINATIONSSHALL BE MADE BY CONSTRUCTION MANAGEMENTS TRADE CONTRACTORS AS PART OF GMP WORK.
EXISTING CABLE TRAY (TYP.)
No. Description Date
ADDENDUM 22 4/16/2018
FE
C
FEC
FEC
SESESESESESESESESESESESESE
SE
SE
SE
SESE SESE SE SE SESE
SE
SE
SESE
SE
SE
SE
SE
SE SE
CHEMISTRY
201A
BIOLOGY
202A
PREP
201C
WOMEN
215
TLT
216
COLLAB
202E
CLASSRM (Type 2)
213
CLASSRM (Type 2)
209
SE OFF
209ACLASSRM (Type 2)
204A
CLASSRM (Type 8)
206
TR
219
CORRIDOR
200C
CORRIDOR
200B
CLASSRM (Type 1C)
212
CLASSRM (Type 1B)
210
CLASSRM (Type 1B)
203
CLASSRM (Type 1C)
205
FOT LAB
207
CLASSRM (Type 5)
208
CLASSRM (Type 4)
214
STAIR B2-2
SB2-2
STAIR B1-2
SB1-2 L
C
PR
DD
L
C
PR
PR
PR
L
LC
C
DD
CC
L L
PRPR
DD DD
PR
L
C
DD
DD
A1
A1
PR
L
C
DD
DD
PR
L
C
L
C
PR
DD
CLASSRM (Type 3)
204B
PREP
202B
CLASSRM (Type 3)
211
PR
L
C C
L
PR
DD
DD DD DD
DD
DD
DD
PR
L
C
DD
PR
L
C
DD
PR
L
C
ELEC
218
DD
DD
A1
MEN
217
STG-COLLAB
202C
COLLAB
202D
CORRIDOR
200A
A1
STG-CHEM
201BDD
DD
STAIR B3-2
SB3-2
A1
DD
DD
WWWWWW
W
W W W W W
W
MA
TC
HLIN
E
SE
E T
SD
-1.7
MA
TC
HLIN
E
SE
E T
SD
-1.7
MA
TC
HLIN
E
SE
E T
SD
-1.7
W W
WWW
MA
TC
HLIN
E
SE
E T
SD
-1.5
EXISTING CABLE TRAY (TYP.)
1
2
1
2
11
2
2
3
2
2
2
22 2 2
2 2
2
2
2
2
1
11
1 1
1111
11
TR 102L SERVICE AREA TR 219 SERVICE AREA
TR 102L SERVICE AREA TR 219 SERVICE AREA
TSD-5.1
4
4
5
2
2
2
2
INFORMATION SHOWN ON THIS DRAWING PERTAINING TO EXISTING CONDITIONS HAVE BEEN OBTAINED FROMAVAILABLE BUILDING DRAWINGS OR GENERAL FIELD OBSERVATIONS AND MAY NOT INDICATE ACTUAL EXISTINGCONDITIONS IN DETAIL OR DIMENSION. THE CONTRACTOR IS RESPONSIBLE FOR DETERMINING THE ACTUALEXISTING CONDITIONS PRIOR TO FABRICATION OR PERFORMANCE OF ANY WORK. SHOULD CONDITIONS BEDISCOVERED THAT PREVENT EXECUTION OF THE WORK AS INDICATED, THE CONTRACTOR SHALL IMMEDIATELYNOTIFY THE ENGINEER IN WRITING AND AWAIT DIRECTION BEFORE PROCEEDING WITH THE WORK.
UNLESS OTHERWISE NOTED, TECHNOLOGY ITEMS SHOWN HEAVY SOLID ( ) SHALL BE NEW, ANDTECHNOLOGY ITEMS SHOWN LIGHT SOLID ( ) SHALL BE EXISTING TO REMAIN.
LOW-VOLTAGE CABLING SHALL BE RUN THROUGH EXISTING CONDUIT AND SLEEVES AS DESIGNATED IN THE A/EDESIGN DOCUMENTS. COORDINATE INSTALLATION OF ALL LOW-VOLTAGE CABLING WITH THE A/E DESIGNDOCUMENTS. TER 019B SHALL SERVE AS THE SERVICE PROVIDER POINT OF DEMARCATION. LOW VOLTAGECABLING RUNS ARE DESGINATED AS A DASHED HEAVY LINE ( ) INTO PENETRATIONS.
CABLE ROUTING IS SHOWN DIAGRAMATICALLY AS A SINGLE DASHED-LINE. ALL LOW VOLTAGE CABLING INHALLWAYS SHOULD BE HUNG FROM WIRE RUN IN CABLE TRAYS FURNISHED AND INSTALLED BY OTHERS. CABLESSHALL BE SEPERATED IN BUNDLES TO DIFFERENTIATE BETWEEN DATA, VOIP, AND SECURITY USAGE, BACK TOTHE TR ROOM SERVING THAT AREA.
J-HOOKS SHALL BE SPACED NO MORE THAN 5'-6" APART FOR SUPPORT OF LOW VOLTAGE CABLING. J-HOOKS TOBE USED IN HALLWAYS ONLY WHEN FIELD CONDITIONS REQUIRE. J-HOOKS TO BE USED IN OTHERROOMS/SPACES.
COORDINATE LOCATION OF ALL CEILING MOUNTED DEVICES AND CABLE RUNS WITH EXISTING CONDITIONS INTHE FIELD.
PENETRATIONS SHOWN ON DRAWINGS ARE EXISTING 2" CONDUITS UNLESS OTHERWISE NOTED.
GENERAL SHEET NOTES:1.
2.
3.
4.
5.
6.
7.
SHEET KEYNOTES:
C RUBELING & ASSOCIATES
A B C D E F G H J K L M N P Q R S T U
1
2
3
4
5
6
7
8
9
10
11
12
13
14
TITLE:
SCALE:
DATE:
PROJ. NO:
SHEET:
JOHNSON,MIRMIRAN,
& THOMPSON40 WIGHT AVE
HUNT VALLEY, MD 21030410.329.3100
FAX: 410.472.2200
CONSULTANT:
REVISIONS:
AD
DIT
ION
S &
RE
NO
VA
TIO
NS
AT
RO
BE
RT
PO
OL
E B
UIL
DIN
G #
056
BA
LT
IMO
RE
CIT
Y P
UB
LIC
SC
HO
OL
S
17-11797-003
Q:\2017\1711797_003_Design_-_Robert_Pool\CADD\MEP\Robert Poole Technology Design.rvt 4/16/2018 5:35:56 PM
As indicated
TECHNOLOGY -LEVEL 2B PLAN
03/26/18
TSD-1.6
1300
W 3
6TH
ST
., B
AL
TIM
OR
E, M
D 2
1211
1/8" = 1'-0"TSD-1.6
LEVEL 2B1
0' 4' 8' 16' 32'
1 PROVIDE EXTRON WALL VAULT SYSTEM AND CABLING AS PER DETAIL 10 ON SHEET TSD-5.3.
2 ALL DATA, VOIP, AND WIFI CABLES IN ROOM SHALL BE FED THROUGH EXISTING 2" CONDUIT SLEEVES ABOVE CEILINGAND FOLLOW DEDICATED PATHWAYS BACK TO TR/TER ROOMS.
3 THREE EXISTING 4" CONDUIT PENETRATIONS BETWEEN FLOORS FOR LOW VOLTAGE CABLES.
4 FOUR EXISTING 4" CONDUIT PENETRATIONS BETWEEN FLOORS FOR LOW VOLTAGE CABLES.
5 FOUR EXISTING 4" CONDUIT PENETRATIONS FOR ALL LOW VOLTAGE CABLES INTO TELECOMMUNICATION ROOM.
No. Description Date
ADDENDUM 22 4/16/2018
FE
C
SE
SE
SE
SE
SE
SE
SE
SE
SE
SE SE
SE SE
SE
RESOURCE
223
PLANNING
221
CLASSRM (Type 9)
228
THEATER/DANCE CR
231
CLASSRM (Type 10)
229
PHYSICS
220
JC
222
BIOLOGY
233
PREP
233A
CORRIDOR
200F
OFFICE
226
VP OFF
227
CLASSRM (Type 11)
230
COLLAB STAIR
224
PR
DD
L
C
DD
PR
L
C
PR
L
C
DD
DD
DD
DD
STG
231A
STAIR C1-2
SC1-2
A1
A1
A1
A1 A1
DD
DD
A1
A1A1
A1
A1
DD
DD
DD
DD
DD
PR
L
C
DD
DD
CORRIDOR
200G
PREP
220A
ELEV 1
E1-2
STG-COLLAB
221A
TLT
225A1
A1
CONTROL
232
L CPR
EX. 4" CONDUITTHROUGH WALL 18"AFF
DD
DD
DD
A1
A1
PR
L
C
A1
A1
DD
PR
L
MATC
HLIN
E
SEE TSD
-1.6
MATC
HLIN
E
SEE TSD
-1.6
MATC
HLIN
E
SEE TSD
-1.6
W
W
W
W
W
W
W
W
W
EXISTING CABLETRAY (TYP.)
1
2
2
1
1
2
2
2
2
1
2
2
2
2
2
1
2
2
1
2
A1
C
1
W
SE
SE
SE
SE
2
2
3
3
3
3
SE
SE
4
4
2
2
INFORMATION SHOWN ON THIS DRAWING PERTAINING TO EXISTING CONDITIONS HAVE BEEN OBTAINED FROMAVAILABLE BUILDING DRAWINGS OR GENERAL FIELD OBSERVATIONS AND MAY NOT INDICATE ACTUAL EXISTINGCONDITIONS IN DETAIL OR DIMENSION. THE CONTRACTOR IS RESPONSIBLE FOR DETERMINING THE ACTUALEXISTING CONDITIONS PRIOR TO FABRICATION OR PERFORMANCE OF ANY WORK. SHOULD CONDITIONS BEDISCOVERED THAT PREVENT EXECUTION OF THE WORK AS INDICATED, THE CONTRACTOR SHALL IMMEDIATELYNOTIFY THE ENGINEER IN WRITING AND AWAIT DIRECTION BEFORE PROCEEDING WITH THE WORK.
UNLESS OTHERWISE NOTED, TECHNOLOGY ITEMS SHOWN HEAVY SOLID ( ) SHALL BE NEW, ANDTECHNOLOGY ITEMS SHOWN LIGHT SOLID ( ) SHALL BE EXISTING TO REMAIN.
LOW-VOLTAGE CABLING SHALL BE RUN THROUGH EXISTING CONDUIT AND SLEEVES AS DESIGNATED IN THE A/EDESIGN DOCUMENTS. COORDINATE INSTALLATION OF ALL LOW-VOLTAGE CABLING WITH THE A/E DESIGNDOCUMENTS. TER 019B SHALL SERVE AS THE SERVICE PROVIDER POINT OF DEMARCATION. LOW VOLTAGECABLING RUNS ARE DESGINATED AS A DASHED HEAVY LINE ( ) INTO PENETRATIONS.
CABLE ROUTING IS SHOWN DIAGRAMATICALLY AS A SINGLE DASHED-LINE. ALL LOW VOLTAGE CABLING INHALLWAYS SHOULD BE HUNG FROM WIRE RUN IN CABLE TRAYS FURNISHED AND INSTALLED BY OTHERS. CABLESSHALL BE SEPERATED IN BUNDLES TO DIFFERENTIATE BETWEEN DATA, VOIP, AND SECURITY USAGE, BACK TOTHE TR ROOM SERVING THAT AREA.
J-HOOKS SHALL BE SPACED NO MORE THAN 5'-6" APART FOR SUPPORT OF LOW VOLTAGE CABLING. J-HOOKS TOBE USED IN HALLWAYS ONLY WHEN FIELD CONDITIONS REQUIRE. J-HOOKS TO BE USED IN OTHERROOMS/SPACES.
COORDINATE LOCATION OF ALL CEILING MOUNTED DEVICES AND CABLE RUNS WITH EXISTING CONDITIONS INTHE FIELD.
PENETRATIONS SHOWN ON DRAWINGS ARE EXISTING 2" CONDUITS UNLESS OTHERWISE NOTED.
GENERAL SHEET NOTES:1.
2.
3.
4.
5.
6.
7.
SHEET KEYNOTES:
C RUBELING & ASSOCIATES
A B C D E F G H J K L M N P Q R S T U
1
2
3
4
5
6
7
8
9
10
11
12
13
14
TITLE:
SCALE:
DATE:
PROJ. NO:
SHEET:
JOHNSON,MIRMIRAN,
& THOMPSON40 WIGHT AVE
HUNT VALLEY, MD 21030410.329.3100
FAX: 410.472.2200
CONSULTANT:
REVISIONS:
AD
DIT
ION
S &
RE
NO
VA
TIO
NS
AT
RO
BE
RT
PO
OL
E B
UIL
DIN
G #
056
BA
LT
IMO
RE
CIT
Y P
UB
LIC
SC
HO
OL
S
17-11797-003
Q:\2017\1711797_003_Design_-_Robert_Pool\CADD\MEP\Robert Poole Technology Design.rvt 4/16/2018 5:35:58 PM
As indicated
TECHNOLOGY -LEVEL 2C PLAN
03/26/18
TSD-1.7
1300
W 3
6TH
ST
., B
AL
TIM
OR
E, M
D 2
1211
1/8" = 1'-0"TSD-1.7
LEVEL 2C1
0' 4' 8' 16' 32'
1 PROVIDE EXTRON WALL VAULT SYSTEM AND CABLING AS PER DETAIL 10 ON SHEET TSD-5.3.
2 ALL DATA, VOIP, AND WIFI CABLES IN ROOM SHALL BE FED THROUGH EXISTING 2" CONDUIT SLEEVES ABOVE CEILINGAND FOLLOW DEDICATED PATHWAYS BACK TO TR/TER ROOMS.
3 WALL MOUNTED SOUND ENHANCEMENT SPEAKER SHALL BE MOUNTED 10' AFF.
4 WALL MOUNTED SOUND ENHANCEMENT SPEAKER SHALL BE MOUNTED 15' AFF AND CENTERED ON COLUMN.
No. Description Date
ADDENDUM 22 4/16/2018
2
FE
C
SE
SE
SE SE
SESE
SE SE
SE
SE
SE
SE
SE
SE
SE
SE
SE
SE
ROOF ACCESS
324A
ART STUDIO 3D
327
ART STUDIO
328
VOCAL MUSIC
330
PHYSICS
321
STAIR C1-3
SC1-3
C
L
PR
CORRIDOR
300E
COLLAB
326
STG
328A
STG-INSTR
329A
PR
L
C
C
L
PR
A1
L
C
PR
A1
A1
A1
A1
DD
DD
DD
DD
DD
DD
DD
DD
DD
CORRIDOR
300F
STG-SCI
321A
JC
322
ELEV 1
E1-3
TLT
325
A1
PLANNING
323
INSTR MUSIC
329
KILN
327A
L
PR
C
STG-COLLAB
323A
ASST PRINCIPAL OFFICE
324
DD
DD
A1
A1
A1
A1
A1
DD
MATC
HLIN
E
SEE TSD
-1.8
MATC
HLIN
E
SEE TSD
-1.8
MATC
HLIN
E
SEE TSD
-1.8
W
W
W
W
W
W
W
W
1
2
2
2
2
2
2
2
1
1
2
1
2
2
EXISTING CABLE TRAY (TYP.)
2
INFORMATION SHOWN ON THIS DRAWING PERTAINING TO EXISTING CONDITIONS HAVE BEEN OBTAINED FROMAVAILABLE BUILDING DRAWINGS OR GENERAL FIELD OBSERVATIONS AND MAY NOT INDICATE ACTUAL EXISTINGCONDITIONS IN DETAIL OR DIMENSION. THE CONTRACTOR IS RESPONSIBLE FOR DETERMINING THE ACTUALEXISTING CONDITIONS PRIOR TO FABRICATION OR PERFORMANCE OF ANY WORK. SHOULD CONDITIONS BEDISCOVERED THAT PREVENT EXECUTION OF THE WORK AS INDICATED, THE CONTRACTOR SHALL IMMEDIATELYNOTIFY THE ENGINEER IN WRITING AND AWAIT DIRECTION BEFORE PROCEEDING WITH THE WORK.
UNLESS OTHERWISE NOTED, TECHNOLOGY ITEMS SHOWN HEAVY SOLID ( ) SHALL BE NEW, ANDTECHNOLOGY ITEMS SHOWN LIGHT SOLID ( ) SHALL BE EXISTING TO REMAIN.
LOW-VOLTAGE CABLING SHALL BE RUN THROUGH EXISTING CONDUIT AND SLEEVES AS DESIGNATED IN THE A/EDESIGN DOCUMENTS. COORDINATE INSTALLATION OF ALL LOW-VOLTAGE CABLING WITH THE A/E DESIGNDOCUMENTS. TER 019B SHALL SERVE AS THE SERVICE PROVIDER POINT OF DEMARCATION. LOW VOLTAGECABLING RUNS ARE DESGINATED AS A DASHED HEAVY LINE ( ) INTO PENETRATIONS.
CABLE ROUTING IS SHOWN DIAGRAMATICALLY AS A SINGLE DASHED-LINE. ALL LOW VOLTAGE CABLING INHALLWAYS SHOULD BE HUNG FROM WIRE RUN IN CABLE TRAYS FURNISHED AND INSTALLED BY OTHERS. CABLESSHALL BE SEPERATED IN BUNDLES TO DIFFERENTIATE BETWEEN DATA, VOIP, AND SECURITY USAGE, BACK TOTHE TR ROOM SERVING THAT AREA.
J-HOOKS SHALL BE SPACED NO MORE THAN 5'-6" APART FOR SUPPORT OF LOW VOLTAGE CABLING. J-HOOKS TOBE USED IN HALLWAYS ONLY WHEN FIELD CONDITIONS REQUIRE. J-HOOKS TO BE USED IN OTHERROOMS/SPACES.
COORDINATE LOCATION OF ALL CEILING MOUNTED DEVICES AND CABLE RUNS WITH EXISTING CONDITIONS INTHE FIELD.
PENETRATIONS SHOWN ON DRAWINGS ARE EXISTING 2" CONDUITS UNLESS OTHERWISE NOTED.
GENERAL SHEET NOTES:1.
2.
3.
4.
5.
6.
7.
SHEET KEYNOTES:
C RUBELING & ASSOCIATES
A B C D E F G H J K L M N P Q R S T U
1
2
3
4
5
6
7
8
9
10
11
12
13
14
TITLE:
SCALE:
DATE:
PROJ. NO:
SHEET:
JOHNSON,MIRMIRAN,
& THOMPSON40 WIGHT AVE
HUNT VALLEY, MD 21030410.329.3100
FAX: 410.472.2200
CONSULTANT:
REVISIONS:
AD
DIT
ION
S &
RE
NO
VA
TIO
NS
AT
RO
BE
RT
PO
OL
E B
UIL
DIN
G #
056
BA
LT
IMO
RE
CIT
Y P
UB
LIC
SC
HO
OL
S
17-11797-003
Q:\2017\1711797_003_Design_-_Robert_Pool\CADD\MEP\Robert Poole Technology Design.rvt 4/16/2018 5:36:00 PM
As indicated
TECHNOLOGY -LEVEL 3C PLAN
03/26/18
TSD-1.9
1300
W 3
6TH
ST
., B
AL
TIM
OR
E, M
D 2
1211
1/8" = 1'-0"TSD-1.9
LEVEL 3C1
0' 4' 8' 16' 32'
1 PROVIDE EXTRON WALL VAULT SYSTEM AND CABLING AS PER DETAIL 10 ON SHEET TSD-5.3.
2 ALL DATA, VOIP, AND WIFI CABLES IN ROOM SHALL BE FED THROUGH EXISTING 2" CONDUIT SLEEVES ABOVE CEILINGAND FOLLOW DEDICATED PATHWAYS BACK TO TR/TER ROOMS.
No. Description Date
ADDENDUM 22 4/16/2018
2
2
2