SHEET NAME
SHEET NO.
DATE
COPYRIGHT STRANG, INC.
DRAWING SET
2021
ARCHITECTURAL MECHANICAL
STRUCTURAL ELECTRICAL
ARCHITECTURAL DESIGN, MECHANICAL,
ELECTRICAL, AND PLUMBING ENGINEERING
STRANG, INC.
STRUCTURAL ENGINEERING
ONEIDA TOTAL INTEGRATED ENTERPRISES
REVISIONS
No. DESCRIPTION DATE
DESIGN TEAM PROJECT IMAGE
SHEET INDEXSTAMPS
SITE LOCATION MAP
TITLE SHEET
T001
09/20/2021
CD
208 JARVIS ST
RIDGEWAY, WI 53582 PROJECT NO. : 2021046
RIDGEWAY COMMUNITY CENTER RENOVATIONS
ELECTRICAL
E001 ELECTRICAL SYMBOLS, ABBREVIATIONS AND GENERAL NOTES
E100A LOWER LEVEL DEMOLITION PLAN - AREA A
E100B LOWER LEVEL DEMOLITION PLAN - AREA B
E101A FIRST FLOOR DEMOLITION PLAN - AREA A
E201A FIRST FLOOR LIGHTING PLAN - AREA A
E300A LOWER LEVEL POWER PLAN - AREA A
E301A FIRST FLOOR POWER PLAN - AREA A
E301B FIRST FLOOR POWER PLAN - AREA B
E302A ROOF POWER PLAN - AREA A
E302B ROOF POWER PLAN - AREA B
E401 FIRST FLOOR SYSTEMS PLAN - AREA B
E701 ELECTRICAL ONE LINE DIAGRAM
E901 ELECTRICAL SCHEDULES
TITLE
T001 TITLE SHEET
GENERAL
G002 GENERAL INFORMATION
G003 LIFE SAFETY PLAN & CODE INFORMATION
STRUCTURAL
S203 ROOF FRAMING PLAN
ARCHITECTURAL
A001 SCHEDULES AND DETAILS
A101A DEMOLITION PLANS - AREA A
A101B DEMOLITION PLAN - AREA B
A150 DEMOLITION PLAN - ROOF
A200 ARCHITECTURAL SITE PLAN
A201A FLOOR PLANS - AREA A
A250A ROOF PLAN
A250B ROOF PLAN - AREA B
A301A REFLECTED CEILING PLAN - AREA A
A301B REFLECTED CEILING PLAN - AREA B
MECHANICAL
M001 HVAC SCHEDULES
M101A MECHANICAL DEMOLITION PLAN - AREA A
M101B MECHANICAL DEMOLITION PLAN - AREA B
M201A MECHANICAL PLAN - AREA A
M201B MECHANICAL PLAN - AREA B
M202 ROOF MECHANICAL PLAN
M801 MECHANICAL DETAILS
PROJECT LOCATION
N
RIDGEWAY
DETAIL REFERENCE
Detail Number
Sheet Number
SECTION REFERENCE
Section Number
Sheet Number
BUILDING SECTION REFERENCE
Building Section Number
Sheet Number
INTERIOR ELEVATION
Interior Elevation Number
Sheet Number
EXTERIOR ELEVATION
Exterior Elevation Number
Sheet Number
ROOM NAME/ROOM NUMBER
PARTITION TYPE
SPECIFIC ELEVATION NOTE
SPECIFIC PLAN NOTE
CEILING HEIGHT
WINDOW/BORROWED LIGHT TYPE
VERTICAL ELEVATION
COLUMN GRID NUMBER
NEW DOOR
DEMO DOOR
REVISION
(Cloud Around Revision)
#
##
###
##
###
##
###
##
###
##
###
#
NAME
ELEVATION
ROOM NAME
RM ##
#
#
#
#'-##"
BL-#
EXISTING DOOR
SPECIFIC DEMOLITION NOTE#
PRECAST CONCRETE
CONCRETE MASONRY UNIT (SECTION)
BRICK (SECTION)
STEEL (SECTION)
RIGID INSULATION (SECTION)
EXTERIOR INSULATION AND FINISH SYSTEM (SECTION)
EXTERIOR INSULATION AND FINISH SYSTEM (ELEVATION)
PLYWOOD (SECTION)
GRANULAR FILL
STONE VENEER (ELEVATION)
SOIL, INFILL
SOIL, UNDISTURBED
6" MAX
3' - 0" MIN 3' - 6" MIN
12" MAXT
.O. S
EA
T
1' -
6" 3'
- 0
"
AT
AC
CE
SS
IBLE
UN
IT
1' -
5"
NOTE:
- ALL FIXTURE MOUNTING INSTALLATION & CLEARANCE DIMENSIONS SHALL MEET ALL ADA ACCESSIBILITY STANDARDS AND NO ACCESSORY SHALL PROJECT MORE THAN 4" FROM WALL.- PROVIDE BLOCKING IN WALLS FOR ALL WALL MOUNTED EQUIPMENT, ACCESSORIES, AND CABINETRY AS REQUIRED; INCLUDING OWNER ITEMS.- ALL ITEMS SHOWN ARE NOT NECESSARILY IN THIS PROJECT.
ELONGATED RIM
GRAB BAR (GB)
1' - 6 1/2"
18" GRAB BAR (GB)
WATER CLOSET URINAL
2' -
6"
3' - 5 1/2"
TOILET PAPER DISPENSER (TPD)
GRAB BAR (GB)
3' -
3"
3' - 3 1/2"
TO
RE
FLE
CT
IVE
SU
RF
AC
E
3' -
4"
2' -
10"
2' -
3"
MIN
MIRROR (MIR)
BOTTOM OF APRON
INSULATE PIPE DRAIN & HOT WATER SUPPLY @ALL SINKS WHERE P.LAM PANEL IS NOT SHOWN
3' -
4"
SOAP DISPENSER (SD)
TO
OP
ER
AB
LE C
ON
TR
OLS
3' -
4"
MA
X
TO
OP
ER
AB
LE C
ON
TR
OLS
3' -
4"
MA
X
2' -
6"
PAPER TOWEL DISPENSER / RECEPTACLE (PTD/R)
SANITARY NAPKIN DISPENSER (SND)
SANITARY NAPKIN RECEPTACLE (SNR)
TO
SP
OU
T O
UT
LET
3' -
0"
MA
X
2' -
3"
MIN
ELECTRIC WATER COOLER (EWC)
ACCESSORIES
B.O
. CA
BIN
ET
2' -
6"
FIRE EXTINGUISHERCABINET (FEC)
ARCHITECTURE
ENGINEERING
INTERIOR DESIGN
MADISON, WI | WAUKESHA, WI
SHEET NAME
PROJECT TITLE
COPYRIGHT STRANG, INC.
DRAWING SET
DATE
PROJECT NO.
SHEET NO.
2021
9/23
/202
1 12
:34:
33 P
M
09/20/2021
208 JARVIS STRIDGEWAY, WI 53582
RIDGEWAYCOMMUNITY CENTERRENOVATIONS
2021046
CD
GENERALINFORMATION
G002
UH UNIT HEATER
UNF UNFINISHED
UNO UNLESS NOTED OTHERWISE
UR URINAL
V VENT, VOLT, VALVE
VAC VACUUM
VCT VINYL COMPOSITION TILE
VERT VERTICAL
VEST VESTIBULE
VSF VINYL SHEET FLOORING
VTR VENT THROUGH ROOF
VWC VINYL WALL COVERING
W WEST, WIDTH, WIDE, WATT, WASTE, WATER
W/ WITH
W/O WITHOUT
WB WOOD BASE
WC WATER CLOSET
WD WOOD
WF WIDE FLANGE
WM WIRE MESH
WP WATERPROOF, WEATHERPROOF
WR WATER RESISTANT, WATER RECEPTACLE
WT WEIGHT
WWF WELDED WIRE FABRIC
YD YARD
MTL METAL
MUL MULLION
N NORTH
NIC NOT IN CONTRACT
NO NUMBER
NOM NOMINAL
NP NON POTABLE WATER
NTS NOT TO SCALE
OA OVERALL, OUTSIDE AIR
OC ON CENTER
OD OUTSIDE DIAMETER
OFCI OWNER FURNISHED CONTRACTOR INSTALLED
OFF OFFICE
OFOI OWNER FURNISHED OWNER INSTALLED
OH OVERHEAD
OHCD OVERHEAD COILING DOOR
OHSD OVERHEAD SECTIONAL DOOR
OP OPERABLE PARTITION
OPG OPENING
OPNG OPENING
OPP OPPOSITE
OPP-H OPPOSITE HAND
PA PUBLIC ADDRESS
PC PLUMBING CONTRACTOR
PDO POWER DOOR OPERATOR
PERP PERPENDICULAR
PL PLATE, PROPERTY LINE
PLAM PLASTIC LAMINATE
PLAS PLASTER
PLBG PLUMBING
PLYWD PLYWOOD
PR PAIR
PT PAINT
PTD PAPER TOWEL DISPENSER
PTD/R PAPER TOWEL DISPENSER / RECEPTACLE
PTN PARTITION
PTR PAPER TOWEL RECEPTACLE
PVT PAVER TILE
QT QUARRY TILE
R RADIUS, RISER
RA RETURN AIR
RB RESILIENT BASE
RBC RESILIENT BASE COVED
RBS RESILIENT BASE STRAIGHT
RD ROOF DRAIN
REF REFERENCE, REFRIGERATOR
REFR REFRIGERATOR
REINF REINFORCED
REM REMOVE
REQ REQUIRED
REQD REQUIRED
RF RESINOUS FLOORING
RM ROOM, RATED METAL
RO ROUGH OPENING
RT RUBBER TILE
RUB RUBBER
RWD REDWOOD
S SOUTH, SINK, SUPPLY
S&V STAIN & VARNISH
SAB SOUND ATTENUATION BLANKET
SAN SANITARY
SB SOIL BORING
SC SOLID CORE
SCD SEAT COVER DISPENSER
SCHED SCHEDULE
SCON SEALED CONCRETE
SD SOAP DISPENSER
SECT SECTION
SF SQUARE FOOT
SH SHELF
SHR SHOWER
SHT SHEET
SIM SIMILAR
SNR SANITARY NAPKIN RECEPTACLE
SNV SANITARY NAPKIN VENDOR
SOG SLAB ON GRADE
SPEC SPECIFICATION
SQ SQUARE
SS STAINLESS STEEL
SSM SOLID SURFACE MATERIAL
ST STONE
STA STATION
STD STANDARD
STL STEEL
STOR STORAGE
STRUC STRUCTURAL
SUSP SUSPENDED
SYM SYMMETRICAL
T TREAD, THRESHOLD
T&B TOP & BOTTOM
T&G TONGUE & GROOVE
TEL TELEPHONE
TEMP TEMPORARY, TEMPERATURE
TER TERRAZZO
THK THICK
TKBD TACK BOARD
TOB TOP OF BEAM
TOF TOP OF FOOTING
TOS TOP OF STEEL
TPD TOILET PAPER DISPENSER
TRANS TRANSPARENT
TV TELEVISION
TW TOP OF WALL
TYP TYPICAL
EMER EMERGENCY
ENCL ENCLOSURE
EP ELECTRIC PANEL, EPOXY
EQ EQUAL
EQUIP EQUIPMENT
ETR EXISTING TO REMAIN
EW EACH WAY
EWC ELECTRIC WATER COOLER
EWH ELECTRIC WATER HEATER
EXH EXHAUST
EXP EXPANSION
EXPO EXPOSED
EXST EXISTING
EXT EXTERIOR
FA FIRE ALARM
FB FACE BRICK, FLOOR BOX
FCTY FACTORY
FD FLOOR DRAIN
FDN FOUNDATION
FE FIRE EXTINGUISHER
FEB FIRE EXTINGUISHER BRACKET
FEC FIRE EXTIINGUISHER CABINET
FF FINISH FLOOR
FFLR FITNESS FLOOR
FH FUME HOOD, FIRE HOSE
FHC FIRE HOSE CABINET
FIN FINISH
FIX FIXTURE
FL FLOOR
FLUOR FLUORESCENT
FO FINISHED OPENING
FOC FACE OF CONCRETE
FOS FACE OF STUD
FPRF FIREPROOFING
FRP FIBERGLASS REINFORCED PLASTIC
FRT FIRE RETARDANT
FRZ FREEZER
FT FOOT, FEET
FTG FOOTING
FURR FURRING
FUT FUTURE
FV FIELD VERIFY
G GAS
GA GAUGE
GALV GALANIZED
GB GRAB BAR
GC GENERAL CONTRACTOR
GL GLASS
GMGS GLASS MAT GYPSUM SHEATING
GND GROUND
GWB GYPSUM WALL BOARD
GYP GYPSUM
H HIGH
HB HOSE BIBB
HBD HARDBOARD
HC HOLLOW CORE
HDWD HARDWOOD
HDWE HARDWARE
HM HOLLOW METAL
HORIZ HORIZONTAL
HP HORSEPOWER
HR HOUR
HSS HOLLOW STRUCTURAL STEEL
HT HEIGHT
HVAC HEATING, VENTILATION, & AIR CONDITIONING
HWD HARDWOOD
ID INSIDE DIAMETER
IE INVERT ELEVATION
IF INSIDE FACE
IMP INSULATED METAL PANEL
INSUL INSULATION
INT INTERIOR
ITD IMPACT TRAFFIC DOOR
JAN JANITOR
JBE JOIST BEARING ELEVATION
JT JOINT
KIT KITCHEN
KO KNOCKOUT
KP KICK PLATE
KS KNEE SPACE
L LENGTH, ANGLE
LAB LABORATORY
LAM LAMINATE
LAV LAVATORY
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LT LIGHT
LWC LIGHT WEIGHT CONCRETE
MATL MATERIAL
MAX MAXIMUM
MB MOP BASIN
MC MECHANICAL CONTRACTOR
MECH MECHANICAL
MEMB MEMBRANE
MEP MECHANICAL, ELECTRICAL, PLUMBING
MEZZ MEZZANINE
MFR MANUFACTURER
MH MANHOLE, MOP HOLDER
MIN MINIMUM
MIR MIRROR
MISC MISCELLANEOUS
ML&P METAL LATH & PLASTER
MO MASONRY OPENING
MTD MOUNTED
# POUND, NUMBER
& AND
< ANGLE
@ AT
A-100 A LABEL - 100 MINUTE FIRE RATING
B-90 B LABEL - 90 MINUTE FIRE RATING
C-45 C LABEL - 45 MINUTE FIRE RATING
D-20 D LABEL - 20 MINUTE FIRE RATING
Ø DIAMETER, ROUND, PHASE
AB ANCHOR BOLT
ABBR ABBREVIATION
ACOUS ACOUSTICAL
ACP ACOUSTICAL CEILING PANEL
ACR ACRYLIC, ACRYLIC MARKER BOARD
ADJ ADJUSTABLE, ADJACENT
AFF ABOVE FINISH FLOOR
AFS AIR FLOW STATION
AGGR AGGREGATE
AHU AIR HANDLING UNIT
AL ALUMINUM
ALT ALTERNATE
AP ACCESS PANEL
APPROX APPROXIMATE
ARCH ARCHITECTURAL, ARCHITECT
ASPH ASPHALT
AV AIR VALVE
BAF BAFFLES
BD BOARD
BHD BULKHEAD
BITUM BITUMINOUS
BL BORROWED LITE
BLDG BUILDING
BLKG BLOCKING
BM BEAM
BN BULLNOSE
BO BOTTOM OF
BOT BOTTOM
BP BASE PLATE
BRG BEARING
BSC BIO-SAFETY CABINET
BTU BRITISH THERMAL UNITS
BTUH BRITISH THERMAL UNITS PER HOUR
BTW BETWEEN
BUR BUILT-UP ROOF
C CONVECTOR, CHANNEL
CAB CABINET
CB CATCH BASIN
CEM CEMENT
CER CERAMIC
CFCI CONTRACTOR FURNISHED, CONTRACTOR INSTALLED
CFM CUBIC FEET PER MINUTE
CG CORNER GUARD
CH COAT HOOK
CHBD CHALKBOARD
CJ CONTROL JOINT
CL CENTER LINE
CLG CEILING
CLOS CLOSET
CLR CLEAR
CMU CONCRETE MASONRY UNIT
COL COLUMN
CONC CONCRETE
CONJ CONSTRUCTION JOINT
CONN CONNECTION
CONST CONSTRUCTION
CONT CONTROL
CONTR CONTRACTOR
CORR CORRIDOR
CPT CARPET
CR CARD READER
CS CAST STONE
CT CERAMIC TILE
CTR CENTER
CTSK COUNTERSINK
CU CONDENSING UNIT
CUH CABINET UNIT HEATER
CYL CYLINDER
D DEPTH
DBA DECK BEARING ANGLE
DBL DOUBLE
DEMO DEMOLITION, DEMOLISH
DEPT DEPARTMENT
DF DRINKING FOUNTAIN
DIA DIAMETER
DIAG DIAGONAL
DIM DIMENSION
DISP DISPENSER
DN DOWN
DO DO OVER, DITTO
DP DAMPPROOFING
DR DOOR
DS DOWNSPOUT
DSD DUCT SMOKE DETECTOR
DT DRAIN TILE
DTL DETAIL
DWG DRAWING
DWL DOWEL
E EAST
EA EACH, EXHAUST AIR
EC ELECTRICAL CONTRACTOR
EF EXHAUST FAN
EHD ELECTRIC HAND DRYER
EIFS EXTERIOR INSULATION FINISH SYSTEM
EJ EXPANSION JOINT
EL ELEVATION
ELEC ELECTRICAL
ELEV ELEVATOR
ABBREVIATIONS MATERIAL LEGEND
SYMBOL LEGEND
SCALE: 3/8" = 1'-0"
STANDARD MOUNTING HEIGHTS
FACP
UP
UP
UP
DN
DN
UP
UP
UP
UP
UP
UP
CLASSIFICATION OF WORK: (IEBC 2015 Sections 503, 504, 505)Level 1 & 2 AlterationProject Area (Level 2 Alteration) 54 sq. ft.
BUILDING AREA:Work Area 54 gross sq. ft. First Floor 15,336 gross sq. ft. Building Total 26,050 gross sq. ft.
PRIMARY BUILDING USES: (IBC 2015 Chapter 3)
Location Occupancy group Floor areaBusiness Group B, Business 5,062 gsfAssembly Group A-3, Assembly 8,984 nsfStorage Group S-2, Low Hazard Storage 4,041 gsf
TYPE OF CONSTRUCTION: 2B (IBC 2015 Chapter 6)
FIRE RESISTANCE RATINGS:Fire Resistance Hourly Ratings for Structural Components: (IBC 2015 Table 601)Primary Structural Frame 0 HourBearing Walls, Exterior 0 HourBearing Walls, Interior 0 HourFloor Construction 0 HourRoof Construction 0 Hour
ALLOWABLE AREA CALCULATIONS:9,500 sq.ft. Basic Allowable Area per A-3 Occupancy (most restrictive) (IBC 2015 Table 506.2) 6,555 sq.ft. Frontage Increase (IBC 2015 Section 506.3) 16,055 sq. ft. Total Allowable Area per Floor
ALLOWABLE HEIGHT CALCULATIONS: (IBC 2015 Tables 504.3 and 504.4)3 stories 55 feet Basic Allowable Height per B OccupancyNA NA Sprinkler Increase 3 stories 55 feet Total Allowable Height
OCCUPANT LOAD CALCULATIONS: (IBC 2015 Table 1004.1.2)Assembly (Exercise Room) 2,962 gsf / 50 = 60 persons Assembly (Unconcentrated) 3,758 nsf / 15 = 250 persons Business 5,062 gsf / 100 = 51 personsKitchen 591 gsf / 120 = 5 personsLibrary (Reading) 633 nsf / 50 = 13 persons Library (Stack) 1,040 gsf / 100 = 11 persons Storage 4,041 gsf / 300 = 14 persons
Total occupancy 404 persons
TOILET FIXTURE CALCULATIONS: (IBC 2015 Table 2902.1)
Type of Use Occupant load Water closets Lavatories Drinking Servicefountains sink
Men Women Men Women Men Women
Assembly (Exerc.) 30 30 0.24 0.46 0.15 0.15 0.06Assembly (Unconc.) 125 125 1 2.49 0.62 0.62 0.25 Business 26 26 1.04 1.04 0.65 0.65 0.26Kitchen 3 3 0.04 0.04 0.01 0.01Library 7 7 0.05 0.1 0.02 0.02Library 6 6 0.05 0.1 0.02 0.02Storage 7 7 0.07 0.07 0.07 0.07
Total required for 202 202 3 5 2 2 1 entire building
Total providedfor entire building 10* 7 6 6 2
Notes * Provided fixtures are 4 WC and 6 Urinals
CODE INFORMATION
EXIT WIDTH CALCULATIONS: (IBC 2015 Section 1005.3.1 & 1005.3.2)
Non-Sprinkled:
Stairs, Required Stairs, Provided Other Egress, Required Other Egress, Provided
404 persons x 108 inches 404 persons x 72 inches0.3 / 2 stairs = 60.6 inches 0.2 / 2 exits = 40.4 inches
FIRE EXTINGUISHER CABINET
EGRESS DIRECTION
60" Ø WHEELCHAIR TURNING SPACE
1 HOUR RATED FIRE PARTITION
2 HOUR RATED FIRE PARTITION
3 HOUR RATED FIRE PARTITION
FECNOT TO SCALE
LIFE SAFETY PLAN LEGEND
OR
OR
OR
830 SF
STORAGE
845 SF
MARSHAL'S OFFICE
EXIT 76"
781 SF
STORAGE (EXISTINGBOILER)
1,020 SF
STORAGE (EXISTINGAIR HANDLER)
USE OCCUPANCY
BUSINESS
STORAGE
UNEXCAVATED
STAIRS LEADING UP TO GRADE
EX
IT
76"
EX
IT
76"
EXIT 76"
EXIT 33" EXIT33"
1,671 SF
COMMUNITY ROOM
829 SF
SENIOR'S ROOM
1,040 SF
LIBRARY (STACK)
440 SF
KITCHEN
359 SF
OFFICE1,258 SF
CONFERENCE
2,962 SF
GYMNASIUM
494 SF
CONFERENCE
160 SF
MENS 151 SF
WOMENS
2,182 SF
CORRIDOR
TEMP. OFFICE SPACE TO BE DEMOLISHED(FUTURE DEMOLITON - NOT IN SCOPE OF WORK)
RAMP
RAMP
EX
IT
33"
ROUTE TO ACCESSIBLE PARKING
LEVEL 2 ALTERATION WORK AREA: 54 SF
64 SF
STORAGE
273 SF
STORAGE
151 SF
DISHES
USE OCCUPANCY
ASSEMBLY (EXERCISE ROOM)
ASSEMBLY(UNCONCENTRATED)
BUSINESS
KITCHEN
LIBRARY (READING)
LIBRARY (STACK)
STORAGE
633 SF
LIBRARY (READING)
173 SF
CLOSETS
179 SF
CLOSETS
223 SF
STORAGE
54 SF
ELECTRICALCLOSET
121 SF
OFFICE
830 SF
OFFICE
649 SF
OFFICE1,143 SF
OFFICE
612 SF
OFFICE
OPEN TO BELOW
USE OCCUPANCY
BUSINESS
STORAGE
ARCHITECTUREENGINEERINGINTERIOR DESIGN
MADISON, WI | WAUKESHA, WI
SHEET NAME
PROJECT TITLE
COPYRIGHT STRANG, INC.
DRAWING SET
DATE
PROJECT NO.
SHEET NO.
2021
9/23
/202
1 12
:34:
37 P
M
09/20/2021
208 JARVIS STRIDGEWAY, WI 53582
RIDGEWAYCOMMUNITY CENTERRENOVATIONS
2021046
CD
LIFE SAFETY PLAN &CODE INFORMATION
G003
GENERAL LIFE SAFETY PLAN NOTES
1 ALL DOOR LEAVES ARE 36" WIDE WITH 33" CLEAR EGRESS WIDTH, UNLESS NOTEDOTHERWISE.
2 WIDTHS NOTED ON LIFE SAFETY PLANS ARE CLEAR EGRESS WIDTHS
3 SEE SITE PLAN FOR ACCESSIBLE ROUTE TO ACCESSIBLE PARKING STALLS.
PN
TNSCALE: 1/16" = 1'-0"G003
1 BASEMENT LIFE SAFETY PLAN
PN
TNSCALE: 1/16" = 1'-0"G003
2 FIRST FLOOR LIFE SAFETY PLAN
SCALE: NTS
PN
TN
G003
3 SECOND FLOOR LIFE SAFETY PLAN
6"
4 1/4"
3 5/8" LIGHT GAUGE METAL FRAMING AT 16" O.C.
ONE LAYER 5/8" TYPE X GWB
CEILING AS SCHED
PROVIDE ACOUSTIC SEALANT AT PERIMETER
B01
RESILIENT FLOORING
RESILIENT REDUCER, SEE SCHEDULE OF INTERIOR FINISHES FOR ADDITIONAL INFORMATION
EXISTING CONCRETE FLOOR OR OTHER EXISTING MATERIAL
ARCHITECTURE
ENGINEERING
INTERIOR DESIGN
MADISON, WI | WAUKESHA, WI
SHEET NAME
PROJECT TITLE
COPYRIGHT STRANG, INC.
DRAWING SET
DATE
REVISIONS
PROJECT NO.
SHEET NO.
2021
No. DESCRIPTION DATE
#
9/23
/202
1 12
:34:
18 P
M
09/20/2021
208 JARVIS STRIDGEWAY, WI 53582
RIDGEWAYCOMMUNITY CENTERRENOVATIONS
2021046
CD
SCHEDULES ANDDETAILS
A001
SCALE: 1" = 1'-0"A001
1 PARTITION TYPES
ROOM FINISH SCHEDULE
NO. NAME
FINISHES CEILING
REMARKSFLOOR BASE TYPE
001 MARSHAL'S OFFICE
002 STORAGE LVT-1 WB-1
003 STORAGE (EXISTING BOILER)
004 STORAGE (EXISTING AIR HANDLER)
101 OFFICE
101A OFFICE
102A LIBRARY (READING)
102B LIBRARY (STACK)
103 SENIOR'S ROOM
103A CLOSETS
103B TOILET
104 COMMUNITY ROOM LVT-1 WB-1 ACP-2
104A CLOSETS LVT-1 WB-1
104B ELECTRICAL CLOSET LVT-1 WB-1
105 KITCHEN EPOX-1 WB-1
105A DISHES
111 STORAGE
111A MENS
111B OFFICE
111C STORAGE
111D SHOWER
112 GYMNASIUM
113 STORAGE
113A JANITOR
113B WOMENS
113C STORAGE
114 ENTRY
115 CONFERENCE
116 CONFERENCE
118 STORAGE SHED
190 CORRIDOR
201 OFFICE
202 OFFICE
203 STORAGE
204 OFFICE
205 OFFICE
206 WOMENS
207 JAN.
208 MENS
209 CLOSET
290 CORRIDOR
ROOM FINISH SCHEDULE GENERAL NOTES
1 REFER TO REFLECTED CEILING PLANS FOR CEILING HEIGHTS
2 ALL BLANK CELLS ARE "EXISTING TO REMAIN"
3
ROOM FINISH SCHEDULE LEGEND
ACP ACOUSTICAL CEILING PANEL
CG CORNER GUARD
CPT BROADLOOM CARPET
CPTL CARPET TILE
CT CERAMIC TILE
EC EXPOSED CONCRETE
ES EXPOSED STRUCTURE
ETR EXISTING TO REMAIN
FRP FIBERGLASS REINFORCED PANELS
G GROUT
GWB GYPSUM WALL BOARD
LVT LUXURY VINYL TILE
PLAM PLASTIC LAMINATE
PT PAINT
RB RESILIENT BASE
SSM SOLID SURFACE MATERIAL
ST INTERIOR STONE
SV SHEET VINYL
WD WOOD
INTERIOR FINISHES SCHEDULE
IFS Category ABBR DESCRIPTION MANUFACTURER PATTERN COLOR NUMBER SIZE REMARKS
06 61 16 SOLID SURFACING FABRICATIONS
06 61 16 SOLID SURFACING FABRICATIONS SSM-1 SOLID SURFACE CORIAN NEUTRALCONCRETE
09 30 00 TILING
09 30 00 TILING LVT-1 VINYL TILE INTERFACE A00406 ANTIQUELIGHT OAK
A004 5"x36"
09 51 00 ACOUSTICAL CEILINGS
09 51 00 ACOUSTICAL CEILINGS ACP-1 ACOUSTIC CEILINGPANEL
ARMSTRONG OPTIMA WHITE 2X4
09 51 00 ACOUSTICAL CEILINGS ACP-2 ACOUSTIC CEILINGPANEL
ARMSTRONG OPTIMA WHITE 2X2
09 65 00 RESILIENT FLOORING
09 65 00 RESILIENT FLOORING RB-1 RESILIENT FLOOR BASE TARKETT BLACK MAGIC TG4 4"
09 67 23 RESINOUS FLOORING
09 67 23 RESINOUS FLOORING EPOX-1 EPOXY TSR SLATESTONE
09 91 00 PAINTING
09 91 00 PAINTING PT-2 MATCH EXISTING MATCH EXIST.
GENERAL FINISH NOTES
1 REFER TO SHEET A001 FOR STANDARD FLOOR TRANSITION DETAILS.
2 REFER ALSO TO INTERIOR ELEVATIONS FOR ADDITIONAL INFORMATION.
3 INSTALL FLOORING UNDER EQUIPMENT AND MILLWORK.
4 FOR FLOORING TRANSITIONS OCCURRING AT A DOORWAY, CENTER TRANSITION ONDOOR UNLESS NOTED OTHERWISE.
5 ALL TOUCH UP AND REPAIR PAINT TO BE PT-2 (MATCH EXISTING).
SCALE: 6" = 1'-0"A001
2 TRANSITION, LVT-CONCRETE
FACP
UP
UP
UP
UP
STORAGE
MARSHAL'S OFFICE
STORAGE (EXISTINGBOILER)
DEMOLISH AIR HANDLING UNITS. REMOVE PIPING AS REQUIRED TO CAP AND ENCLOSE WITHIN THE WALL AND ABANDON IN PLACE.
REMOVE WALL BASE IN AREA
COMMUNITY ROOM
KITCHEN
DISHES
CLOSETS
TOILET
CLOSETS SENIOR'S ROOM LIBRARY (STACK)
CORRIDOR
DEMOLISH AIR HANDLING UNITS. REMOVE PIPING AS REQUIRED TO CAP AND ENCLOSE WITHIN THE WALL AND ABANDON IN PLACE.
DEMOLISH ACOUSTIC CEILING PANELS AND GRID IN AREA. SALVAGE ACP FOR RE-USE.
DEMOLISH SILLS AT WINDOWS IN THE COMMUNITY ROOM
DEMOLISH CERAMIC TILE WALL BASE IN ROOM.
KEY PLAN
A
N
ARCHITECTUREENGINEERINGINTERIOR DESIGN
MADISON, WI | WAUKESHA, WI
SHEET NAME
PROJECT TITLE
COPYRIGHT STRANG, INC.
DRAWING SET
DATE
PROJECT NO.
SHEET NO.
2021
9/23
/202
1 12
:34:
19 P
M
09/20/2021
208 JARVIS STRIDGEWAY, WI 53582
RIDGEWAYCOMMUNITY CENTERRENOVATIONS
2021046
CD
DEMOLITION PLANS -AREA A
A101A
GENERAL DEMOLITION PLAN NOTES
1 MAINTAIN CONTINUOUS UTILITY SERVICE TO ALL SPACES IN THE BUILDING.COORDINATE DISRUPTIONS IN SERVICE WITH OWNER.
2 PROTECT IN PLACE DURING ENTIRE CONSTRUCTION PROCESS: ALL FLOORING,SURFACES AND ITEMS TO REMAIN.
3 COORDINATE THE AVAILABILITY OF AREAS REQUIRING DEMOLITION WITH OWNER.SEQUENCE WORK ACCORDINGLY AND COORDINATE W/ ALL TRADES.
4 EXISTING CONSTRUCTION TO REMAIN IS SHOWN SCREENED. CONSTRUCTION ANDEQUIPMENT TO BE REMOVED IS SHOWN WITH DASHED LINES.
5 PATCH, PREPARE, REPAIR AND / OR RESTORE SURFACES SCHEDULED TO REMAININTACT THAT ARE DAMAGED AS A RESULT OF DEMOLITION WORK.
6 VISIT THE SITE PRIOR TO SUBMITTING A BID TO BECOME FAMILIAR WITH EXISTINGCONDITIONS.
7 DEMOLITION PLANS ARE NOT NECESSARILY INCLUSIVE OF ALL ITEMS NEEDINGREMOVAL. COORDINATE WITH ALL OTHER DRAWINGS AND FIELD VERIFY EXISTINGCONDITIONS.
8 COORDINATE DEMOLITION DIMENSIONS ON THIS PLAN WITH OTHER DRAWINGS ANDEXISTING CONDITIONS.
9 REFER TO HVAC, ELECTRICAL, PLUMBING, AND FIRE PROTECTION DRAWINGS FORADDITIONAL DEMOLITION AND MODIFICATIONS REQUIRED FOR HVAC, ELECTRICAL,PLUMBING, AND FIRE PROTECTION SYSTEMS.
10 REMOVE EXISTING ACOUSTIC CEILING PANELS AS REQUIRED FOR CONSTRUCTIONOF ABOVE-CEILING ELECTRICAL AND MECHANICAL WORK. RETURN CEILING PANELSTO GRID AFTER COMPLETION OF ABOVE-CEILING WORK.
PN
TNSCALE: 1/8" = 1'-0"A101A
1 BASEMENT FLOOR PLAN
PN
TNSCALE: 1/8" = 1'-0"A101A
2 FIRST FLOOR DEMOLITION PLAN
UP
UP
UP
UP
DN
DN
2,962 SF
GYMNASIUM
151 SF
WOMENS
64 SF
STORAGE
175 SF
ENTRY
494 SF
CONFERENCE
1,258 SF
CONFERENCE359 SF
OFFICE
273 SF
STORAGE
160 SF
MENS
146 SF
STORAGE
2,182 SF
CORRIDOR
830 SF
OFFICE
649 SF
OFFICE
1,143 SF
OFFICE
612 SF
OFFICE
731 SF
CORRIDOR
KEY PLAN
B
N
ARCHITECTURE
ENGINEERING
INTERIOR DESIGN
MADISON, WI | WAUKESHA, WI
SHEET NAME
PROJECT TITLE
COPYRIGHT STRANG, INC.
DRAWING SET
DATE
PROJECT NO.
SHEET NO.
2021
9/23
/202
1 12
:34:
21 P
M
09/20/2021
208 JARVIS STRIDGEWAY, WI 53582
RIDGEWAYCOMMUNITY CENTERRENOVATIONS
2021046
CD
DEMOLITION PLAN -AREA B
A101B
PN
TNSCALE: 1/8" = 1'-0"A101B
1 FIRST FLOOR DEMOLITION PLAN
PN
TNSCALE: 1/8" = 1'-0"A101B
2 SECOND FLOOR DEMOLITION PLAN
GENERAL DEMOLITION PLAN NOTES
1 MAINTAIN CONTINUOUS UTILITY SERVICE TO ALL SPACES IN THE BUILDING.COORDINATE DISRUPTIONS IN SERVICE WITH OWNER.
2 PROTECT IN PLACE DURING ENTIRE CONSTRUCTION PROCESS: ALL FLOORING,SURFACES AND ITEMS TO REMAIN.
3 COORDINATE THE AVAILABILITY OF AREAS REQUIRING DEMOLITION WITH OWNER.SEQUENCE WORK ACCORDINGLY AND COORDINATE W/ ALL TRADES.
4 EXISTING CONSTRUCTION TO REMAIN IS SHOWN SCREENED. CONSTRUCTION ANDEQUIPMENT TO BE REMOVED IS SHOWN WITH DASHED LINES.
5 PATCH, PREPARE, REPAIR AND / OR RESTORE SURFACES SCHEDULED TO REMAININTACT THAT ARE DAMAGED AS A RESULT OF DEMOLITION WORK.
6 VISIT THE SITE PRIOR TO SUBMITTING A BID TO BECOME FAMILIAR WITH EXISTINGCONDITIONS.
7 DEMOLITION PLANS ARE NOT NECESSARILY INCLUSIVE OF ALL ITEMS NEEDINGREMOVAL. COORDINATE WITH ALL OTHER DRAWINGS AND FIELD VERIFY EXISTINGCONDITIONS.
8 COORDINATE DEMOLITION DIMENSIONS ON THIS PLAN WITH OTHER DRAWINGS ANDEXISTING CONDITIONS.
9 REFER TO HVAC, ELECTRICAL, PLUMBING, AND FIRE PROTECTION DRAWINGS FORADDITIONAL DEMOLITION AND MODIFICATIONS REQUIRED FOR HVAC, ELECTRICAL,PLUMBING, AND FIRE PROTECTION SYSTEMS.
10 REMOVE EXISTING ACOUSTIC CEILING PANELS AS REQUIRED FOR CONSTRUCTIONOF ABOVE-CEILING ELECTRICAL AND MECHANICAL WORK. RETURN CEILING PANELSTO GRID AFTER COMPLETION OF ABOVE-CEILING WORK.
FACP
41' -
9"
21' -
4"
33' -
4"
8' -
5"
19' - 5" 44' - 10" 28' - 1"
1' - 11"
DEMOLISH ROOFING MEMBRANE AND INSULATION AS REQUIRED FOR INSTALLATION OF STEEL AND CURBING FOR RTU'S
DEMOLISH ROOFING MEMBRANE AND INSULATION AS REQUIRED FOR INSTALLATION OF STEEL AND CURBING FOR RTU'S
DEMOLISH ROOFING MEMBRANE AS REQUIRED FOR THE REPAIR OF LEAKING ROOF IN HATCHED AREA.
DEMOLISH ROOFING MEMBRANE AND INSULATION AS REQUIRED FOR INSTALLATION OF STEEL AND CURBING FOR FCU'S
KEY PLAN
A B
N
ARCHITECTURE
ENGINEERING
INTERIOR DESIGN
MADISON, WI | WAUKESHA, WI
SHEET NAME
PROJECT TITLE
COPYRIGHT STRANG, INC.
DRAWING SET
DATE
PROJECT NO.
SHEET NO.
2021
9/23
/202
1 12
:34:
22 P
M
09/20/2021
208 JARVIS STRIDGEWAY, WI 53582
RIDGEWAYCOMMUNITY CENTERRENOVATIONS
2021046
CD
DEMOLITION PLAN -ROOF
A150
PN
TNSCALE: 1/8" = 1'-0"A150
1 DEMOLITION PLAN - ROOF
GENERAL DEMOLITION PLAN NOTES
1 MAINTAIN CONTINUOUS UTILITY SERVICE TO ALL SPACES IN THE BUILDING.COORDINATE DISRUPTIONS IN SERVICE WITH OWNER.
2 PROTECT IN PLACE DURING ENTIRE CONSTRUCTION PROCESS: ALL FLOORING,SURFACES AND ITEMS TO REMAIN.
3 COORDINATE THE AVAILABILITY OF AREAS REQUIRING DEMOLITION WITH OWNER.SEQUENCE WORK ACCORDINGLY AND COORDINATE W/ ALL TRADES.
4 EXISTING CONSTRUCTION TO REMAIN IS SHOWN SCREENED. CONSTRUCTION ANDEQUIPMENT TO BE REMOVED IS SHOWN WITH DASHED LINES.
5 PATCH, PREPARE, REPAIR AND / OR RESTORE SURFACES SCHEDULED TO REMAININTACT THAT ARE DAMAGED AS A RESULT OF DEMOLITION WORK.
6 VISIT THE SITE PRIOR TO SUBMITTING A BID TO BECOME FAMILIAR WITH EXISTINGCONDITIONS.
7 DEMOLITION PLANS ARE NOT NECESSARILY INCLUSIVE OF ALL ITEMS NEEDINGREMOVAL. COORDINATE WITH ALL OTHER DRAWINGS AND FIELD VERIFY EXISTINGCONDITIONS.
8 COORDINATE DEMOLITION DIMENSIONS ON THIS PLAN WITH OTHER DRAWINGS ANDEXISTING CONDITIONS.
9 REFER TO HVAC, ELECTRICAL, PLUMBING, AND FIRE PROTECTION DRAWINGS FORADDITIONAL DEMOLITION AND MODIFICATIONS REQUIRED FOR HVAC, ELECTRICAL,PLUMBING, AND FIRE PROTECTION SYSTEMS.
10 REMOVE EXISTING ACOUSTIC CEILING PANELS AS REQUIRED FOR CONSTRUCTIONOF ABOVE-CEILING ELECTRICAL AND MECHANICAL WORK. RETURN CEILING PANELSTO GRID AFTER COMPLETION OF ABOVE-CEILING WORK.
UP
UP
UP
UP
UP
UP
UP
1,671 SF
COMMUNITY ROOM
440 SF
KITCHEN
1,040 SF
LIBRARY (STACK)829 SF
SENIOR'S ROOM
2,182 SF
CORRIDOR
151 SF
DISHES2,962 SF
GYMNASIUM
1,258 SF
CONFERENCE494 SF
CONFERENCE
359 SF
OFFICE
151 SF
WOMENS
160 SF
MENS
PROVIDE CONCRETE TRANSFORMER PAD
PROVIDE RAISED CONCRETE PAD FOR MECHANICAL EQUIPMENT
PROVIDE BOLLARD
STORAGE SHED
PROVIDE RAISED CONCRETE PAD FOR MECHANICAL EQUIPMENT
ACCESSIBLE ENTRY
AREA OF SITE WORK
AREA OF SITE WORK
AREA OF SITE WORK
PATCH PAVEMENT OVER NEW ELECTRICAL SERVICE
ACCESSIBLE PARKING
TEMP. OFFICE SPACE
NOTE: TEMP. OFFICE SPACE WILL BE AVAILABLE FOR USE AS JOBSITE TRAILER.
PROVIDE CONCRETE CURB
16' -
0"
18' - 0"
6"
6"
CONCRETE FILLED POST HOLE
6"
6"
AS
PH
ALT
4'-0
" B
EL
OW
SUBSOIL
ASPHALT
TROWEL FINISH TOP OF CONCRETE BASE
COMPACTED DRAINAGE FILL @ CONCRETE SLAB LOCATION
4" DIA. PIPE FILLED W/ CONCRETE PAINTED
DOMED CONCRETE FILL AT POST TOP
AS
PH
ALT
3'-0
" B
EL
OW
1"
R2 1/2"
R3"
7"
6" COMPACTED SUBBASE
ASPHALT PAVEMENT
SIDEWALK WHERE OCCURS SEE PLAN
6"
1' -
1"
1' - 0"5 255/256"
KEY PLAN
A B
N
ARCHITECTUREENGINEERINGINTERIOR DESIGN
MADISON, WI | WAUKESHA, WI
SHEET NAME
PROJECT TITLE
COPYRIGHT STRANG, INC.
DRAWING SET
DATE
REVISIONS
PROJECT NO.
SHEET NO.
2021
No. DESCRIPTION DATE
#
9/23
/202
1 12
:34:
24 P
M
09/20/2021
208 JARVIS STRIDGEWAY, WI 53582
RIDGEWAYCOMMUNITY CENTERRENOVATIONS
2021046
CD
ARCHITECTURAL SITEPLAN
A200
PN
TNSCALE: 1" = 10'-0"A200
1 ARCHITECTURAL SITE PLAN
SCALE: 3/4" = 1'-0"A200
2 BOLLARD DETAILSCALE: 1 1/2" = 1'-0"A200
3 CURB W/O GUTTER
UP
UP
UP
UP
UP
UP
UP
A
1
C
B
2
830 SF
002
STORAGE
845 SF
001
MARSHAL'S OFFICE
781 SF
STORAGE (EXISTINGBOILER)
INFILL WITH LAYER OF RIGID INSULATION SEALED TO PERIMETER OF OPENING WITH PARTITION TYPE B-01 AS REQUIRED TO PATCH AND INFILL WALL WHERE UNIT VENTILATORS WERE REMOVED.
A
1
C
B
2 3
/- ---
/- ---
100' - 0" 9' - 0"
1671.22 SF
104
COMMUNITY ROOM 440 SF
KITCHEN
1039.82 SF
102B
LIBRARY (STACK)
828.57 SF
103
SENIOR'S ROOM
2,182 SF
CORRIDOR
151 SF
DISHESINFILL WITH LAYER OF RIGID INSULATION SEALED TO PERIMETER OF OPENING WITH PARTITION TYPE B-01 AS REQUIRED TO PATCH AND INFILL WALL WHERE UNIT VENTILATORS WERE REMOVED.
LVT-1
632.94 SF
102A
LIBRARY (READING)
54 SF
ELECTRICALCLOSET
SSM-1 TYP. FOR ALL WINDOW SILLS IN COMMUNITY ROOM. FIELD VERIFY DIMENSION
2' - 4" VIF
VIF
11 1
/2"
PROVIDE EXPANSION JOINT COVER AT BUILDING EXPANSION JOINT TO TRANSITION LVT FLOORING
EPOX-1
PATCH CONCRETE WHERE OUTLET REMOVED
KEY PLAN
A
N
ARCHITECTUREENGINEERINGINTERIOR DESIGN
MADISON, WI | WAUKESHA, WI
SHEET NAME
PROJECT TITLE
COPYRIGHT STRANG, INC.
DRAWING SET
DATE
PROJECT NO.
SHEET NO.
2021
9/23
/202
1 12
:34:
25 P
M
09/20/2021
208 JARVIS STRIDGEWAY, WI 53582
RIDGEWAYCOMMUNITY CENTERRENOVATIONS
2021046
CD
FLOOR PLANS - AREAA
A201A
GENERAL FLOOR PLAN NOTES
1 ALL DRAWINGS ARE OF EQUAL IMPORTANCE IN DEFINING THE WORK OF THECONTRACT DOCUMENTS. CAREFULLY STUDY AND COMPARE ALL DRAWINGSDURING THE BIDDING PERIOD AND BEFORE INSTALLATION OF WORK. PROMPTLYREPORT INCONSISTENCIES IN THE DRAWINGS TO THE ARCHITECT FORCLARIFICATION.
2 DO NOT SCALE DRAWINGS. THE DRAWINGS ARE NOT NECESSARILY TO SCALE - USEGIVEN DIMENSIONS. VERIFY ALL CONDITIONS AND DIMENSIONS AT THE PROJECTSITE PRIOR TO THE START OF CONSTRUCTION. ANY INCONSISTENCIESDISCOVERED BY THE CONTRACTOR SHALL BE REPORTED PROMPTLY TO THEARCHITECT FOR CLARIFICATION BEFORE COMMENCING THE WORK. DIMENSIONSARE GIVEN FROM FACE TO FACE OF WALLS. SEE WALL SECTIONS AND PARTITIONTYPES FOR EXACT CONSTRUCTION DETAILS.
3 WHERE SPECIFIC DIMENSIONS, DETAILS OR DESIGN INTENT CANNOT BEDETERMINED FROM DOCUMENTS CONSULT THE ARCHITECT BEFORE PROCEEDINGWITH WORK.
4 PATCH, PREPARE AND / OR RESTORE WORK SCHEDULED TO REMAIN THAT ISDAMAGED AS A RESULT OF DEMOLITION WORK. RESTORATION AND PATCHINGWORK SHALL BE DONE IN A MANNER THAT MAINTAINS FIRE RATING OF RATEDBUILDING COMPONENTS.
5 PROTECT WORK IN PLACE DURING CONSTRUCTION
6 COORDINATE THE AVAILABILITY OF AREAS REQUIRING WORK WITH THE OWNER.
7 REFER TO HVAC, ELECTRICAL, PLUMBING, AND FIRE PROTECTION DRAWINGS FORADDITIONAL WORK AND MODIFICATIONS REQUIRED FOR HVAC, ELECTRICAL,PLUMBING AND FIRE PROTECTION SYSTEMS.
PN
TNSCALE: 1/8" = 1'-0"A201A
1 BASEMENT FLOOR PLAN
PN
TNSCALE: 1/8" = 1'-0"A201A
3 FIRST FLOOR PLAN
UP
UP
A
1
C
B
2 3 4 5 6
D
PATCH AND REPAIR EXISTING BUILT-UP ROOFING AS REQUIRED FOR RTU, CURB AND SUPPORT INSTALLATION. SEE MECHANICAL, STRUCTURAL DRAWINGS FOR MORE INFO.
PATCH AND REPAIR EXISTING BUILT-UP ROOFING AS REQUIRED FOR RTU, CURB AND SUPPORT INSTALLATION. SEE MECHANICAL, STRUCTURAL DRAWINGS FOR MORE INFO.
PATCH, REPAIR AND RE-GRADE EXISTING BUILT-UP ROOFING IN HATCHED AREA
PATCH AND REPAIR EXISTING BUILT-UP ROOFING AS REQUIRED FOR FCU, CURB AND SUPPORT INSTALLATION. SEE MECHANICAL, STRUCTURAL DRAWINGS FOR MORE INFO.
KEY PLAN
A B
N
ARCHITECTURE
ENGINEERING
INTERIOR DESIGN
MADISON, WI | WAUKESHA, WI
SHEET NAME
PROJECT TITLE
COPYRIGHT STRANG, INC.
DRAWING SET
DATE
REVISIONS
PROJECT NO.
SHEET NO.
2021
No. DESCRIPTION DATE
#
9/23
/202
1 12
:34:
27 P
M
09/20/2021
208 JARVIS STRIDGEWAY, WI 53582
RIDGEWAYCOMMUNITY CENTERRENOVATIONS
2021046
CD
ROOF PLAN
A250A
GENERAL ROOF PLAN NOTES
1 REFER TO OTHER DRAWINGS IN PLAN SET FOR ADDITIONAL INFORMATION ANDCOORDINATION.
2 VERIFY EXISTING CONDITIONS AT THE START OF ROOFING WORK TO CONFIRMDESIGN INTENT SHOWN ON PLANS.
3 NOTIFY ARCHITECT OF ANY FIELD DISCREPANCIES PRIOR TO THE START OFCONSTRUCTION SHOWN ON PLAN.
4 PROVIDE TAPERED INSULATION CRICKETS AT EQUIPMENT CURBS FOR POSITIVEDRAINAGE TO ROOF DRAINS AND SCUPPERS.
5 REFER TO MECHANICAL, ELECTRICAL AND PLUMBING DRAWINGS FOR LOCATIONSOF PLUMBING VENTS, STACKS, AND OTHER ROOF PENETRATIONS.
6 COMPLETE ROOFING WORK PER ROOFING MANUFACTURER'S STANDARD DETAILSTO MAINTAIN ROOFING MANUFACTURER'S WARRANTY.
8 ARROWS INDICATE DIRECTION OF DOWNWARD SLOPE, U.N.O.
PN
TNSCALE: 1/8" = 1'-0"A250A
1 ROOF PLAN
DH
DH DH
L1L1
L1L1L1
L1
L1
L1
L1L1L1
CEILING PLAN MATERIAL LEGEND
GYPSUM BOARD CEILING
2' X 2' ACOUSTICAL CEILING PANELS
2' X 4' ACOUSTICAL CEILING PANELS
A
1
C
B
2 3
PATCH AND REPAIR CEILING AS REQUIRED FOR RTU AND DUCTWORK WORK
9' - 9"
A
1
C
B
KEY PLAN
A
N
ARCHITECTURE
ENGINEERING
INTERIOR DESIGN
MADISON, WI | WAUKESHA, WI
SHEET NAME
PROJECT TITLE
COPYRIGHT STRANG, INC.
DRAWING SET
DATE
PROJECT NO.
SHEET NO.
2021
9/23
/202
1 12
:34:
29 P
M
09/20/2021
208 JARVIS STRIDGEWAY, WI 53582
RIDGEWAYCOMMUNITY CENTERRENOVATIONS
2021046
CD
REFLECTED CEILINGPLAN - AREA A
A301A
GENERAL CEILING PLAN NOTES
1 REFER TO ROOM FINISH SCHEDULE FOR ADDITIONAL INFORMATION.
2 MECHANICAL, ELECTRICAL, AND PLUMBING FIXTURES SHOWN FOR COORDINATIONONLY. REFER TO M.E.P. DRAWINGS FOR ADDITIONAL INFORMATION.
3 ALL NEW AND EXISTING GWB CEILINGS AND SOFFITS TO BE PT-1 UNLESS NOTEOTHERWISE.
4 ALL CEILINGS ARE EXISTING TO REMAIN UNLESS NOTED WITH CEILING HEIGHT.
5 REMOVE AND STORE ALL ACOUSTIC CEILING PANEL AND REPLACE AT END OFCONSTRUCTION. REPLACE DAMAGED ACP WITH ACP SALVAGED FROM ROOMS TORECIEVE NEW CEILING.
PN
TNSCALE: 1/8" = 1'-0"A301A
2 FIRST FLOOR REFLECTED CEILING PLAN - AREA A
PN
TNSCALE: 1/8" = 1'-0"A301A
1 BASEMENT REFLECTED CEILING PLAN
L1
L1
CEILING PLAN MATERIAL LEGEND
GYPSUM BOARD CEILING
2' X 2' ACOUSTICAL CEILING PANELS
2' X 4' ACOUSTICAL CEILING PANELS
A
C
B
2 3 4 5 6
D
PATCH AND REPAIR CEILING AS REQUIRED FOR RTU AND DUCTWORK WORK
C
B
2 3 4 5 6
D
PATCH AND REPAIR EXISTING WOOD DECKING AS REQUIRED FOR RTU AND DUCTWORK WORK
PATCH AND REPAIR CEILING AS REQUIRED FOR RTU AND DUCTWORK INSTALL
PATCH AND REPAIR CEILING AS REQUIRED FOR RTU AND DUCTWORK INSTALL
KEY PLAN
B
N
ARCHITECTURE
ENGINEERING
INTERIOR DESIGN
MADISON, WI | WAUKESHA, WI
SHEET NAME
PROJECT TITLE
COPYRIGHT STRANG, INC.
DRAWING SET
DATE
PROJECT NO.
SHEET NO.
2021
9/23
/202
1 12
:34:
31 P
M
09/20/2021
208 JARVIS STRIDGEWAY, WI 53582
RIDGEWAYCOMMUNITY CENTERRENOVATIONS
2021046
CD
REFLECTED CEILINGPLAN - AREA B
A301B
GENERAL CEILING PLAN NOTES
1 REFER TO ROOM FINISH SCHEDULE FOR ADDITIONAL INFORMATION.
2 MECHANICAL, ELECTRICAL, AND PLUMBING FIXTURES SHOWN FOR COORDINATIONONLY. REFER TO M.E.P. DRAWINGS FOR ADDITIONAL INFORMATION.
3 ALL NEW AND EXISTING GWB CEILINGS AND SOFFITS TO BE PT-1 UNLESS NOTEOTHERWISE.
4 ALL CEILINGS ARE EXISTING TO REMAIN UNLESS NOTED WITH CEILING HEIGHT.
5 REMOVE AND STORE ALL ACOUSTIC CEILING PANEL AND REPLACE AT END OFCONSTRUCTION. REPLACE DAMAGED ACP WITH ACP SALVAGED FROM ROOMS TORECIEVE NEW CEILING.
PN
TNSCALE: 1/8" = 1'-0"A301B
2 FIRST FLOOR REFLECTED CEILING PLAN
PN
TNSCALE: 1/8" = 1'-0"A301B
3 SECOND FLOOR REFLECTED CEILING PLAN
SA OR OA DUCT RISER
MD MOTORIZED CONTROL DAMPER
BD BALANCE DAMPER
FD FIRE DAMPER
HVAC SYMBOL LEGEND
AIR DEVICE LEGEND & TAGS
SD SUPPLY DIFFUSERSDG SPIRAL DUCT SUPPLY GRILLEEG EXHAUST GRILLERG RETURN GRILLE
ABBREVIATIONS
AD ACCESS DOORALUM ALUMINUMDN DOWNEC ELECTRICAL CONTRACTOREXH EXHAUSTFD FIRE DAMPERG GASGC GENERAL CONTRACTORMC MECHANICAL CONTRACTOROA OUTSIDE AIROED OPEN END DUCTPC PLUMBING CONTRACTORRA RETURN AIRSA SUPPLY AIRTYP TYPICAL
SUPPLY AIR DEVICE
RETURN AIR DEVICE
EXHAUST AIR DEVICE
AIR DEVICE TAGTAGCFM
CONNECT TO EXISTING
TEMPERATURE SENSORT
FD
MD
AIR DEVICE TAG ABBREVIATIONS
MISC SYMBOL LEGEND
1" LINED DUCT
2" LINED DUCT
SA OR OA DUCT DROP
RA DUCT RISER
RA DUCT DROP
EA DUCT RISER
EA DUCT DROP
TURNING VANES
ARCHITECTUREENGINEERINGINTERIOR DESIGN
MADISON, WI | WAUKESHA, WI
SHEET NAME
PROJECT TITLE
COPYRIGHT STRANG, INC.
DRAWING SET
DATE
PROJECT NO.
SHEET NO.
2021
9/22
/202
1 3:
12:0
2 P
M
09/20/2021
208 JARVIS STRIDGEWAY, WI 53582
RIDGEWAYCOMMUNITY CENTERRENOVATIONS
2021046
CD
HVAC SCHEDULES
M001
GENERAL HVAC NOTES
1 PROVIDE MANUAL BALANCING DAMPERS AT EACH DIFFUSER, GRILLE AND BRANCHTAKE-OFF IN ALL SUPPLY, RETURN AND EXHAUST DUCTWORK. LOCATE BALANCINGDAMPERS AS CLOSE TO THE BRANCH TAKE-OFF AS POSSIBLE.
2 DUCT SIZE TO DIFFUSERS, REGISTERS AND GRILLES SHALL BE SAME SIZE AS NECKSIZE UNLESS NOTED OR DETAILED OTHERWISE.
3 INLET DUCT SIZE TO SUPPLY AIR TERMINAL SHALL BE SAME AS INLET UNLESSOTHERWISE NOTED.
4 OUTLET DUCT SIZE TO EXHAUST AIR TERMINALS SHALL BE THE SAME AS OUTLETUNLESS OTHERWISE NOTED.
5 COORDINATE DIFFUSER, REGISTER, GRILLE AND ACCESS PANEL LOCATIONS WITHREFLECTED CEILING PLAN.
6 PROVIDE FLEXIBLE DUCTWORK FOR FINAL CONNECTIONS TO DIFFUSERS,REGISTERS AND GRILLES UNLESS NOTED OTHERWISE IN SPECIFICATIONS.FLEXIBLE DUCT SIZE SHALL BE SAME AS NECK SIZE OF DIFFUSER, REGISTER ORGRILLE. REFER TO SPECIFICATIONS FOR FLEXIBLE DUCT REQUIREMENTS.FLEXIBLE DUCTS ARE NOT ALLOWED ABOVE NON-ACCESSIBLE CEILINGS.
8 CONTRACTOR TO VERIFY LOCATIONS AND FIELD CONDITIONS PRIOR TO START OFWORK.
9 NO SERVICE SHALL BE INTERRUPTED OR CHANGED WITHOUT WRITTEN PERMISSIONFROM OWNER.
10 WHERE WORK INTERFERES WITH OWNER’S USE OF PREMISES, SCHEDULE WORKTHROUGH OWNER TO MINIMIZE INCONVENIENCE TO OWNER. OWNER MUSTAPPROVE SCHEDULE IN WRITING BEFORE CONTRACTOR BEGINS ANY SUCH WORK.
11 PROVIDE ROOM THERMOSTAT FOR EACH ROOM UNLESS INDICATED OTHERWISE.
12 PROVIDE BALANCING DAMPERS FOR ALL BRANCH MAIN TAKE-OFFS SERVING TWOOR MORE AIR TERMINAL BOXES, DIFFUSERS, ETC.
13 CONTRACTOR SHALL FIELD VERIFY LAYOUT AND MANUFACTURE’S INSTALLATIONREQUIREMENTS FOR ACTUAL EQUIPMENT PROVIDED.
14 MISCELLANEOUS STEEL FOR EQUIPMENT AND PIPE SUPPORTS SHALL BE PROVIDED.REFER TO ARCHITECTURAL SPECIFICATIONS FOR FINISHING OF MISCELLANEOUSSTEEL. ALL STEEL SHALL BE PAINTED.
15 CONTRACTOR SHALL COORDINATE LOCATIONS OF HVAC MAINS, BRANCHES, PIPING,ETC WITH ALL OTHER TRADES PRIOR TO INSTALLATION.
16 ALL ELEVATIONS NOTED ARE RELATIVE TO FINISHED FLOOR ELEVATION.
17 NO PIPING OR DUCTS SHALL BE INSTALLED ABOVE ELECTRICAL EQUIPMENT,UNLESS OTHERWISE NOTED. REFER TO ELECTRICAL DRAWINGS FOR ELECTRICALEQUIPMENT LOCATIONS. COORDINATE WITH EC FOR EXACT LOCATIONS.
18 COORDINATE THE LOCATIONS OF DIFFUSERS, REGISTERS AND GRILLES WITHELECTRICAL LIGHT FIXTURES, LIGHT FIXTURE SUPPORT RODS AND FIRE SPRINKLERHEADS FOR FREE INTERFERENCE.
19 ALL WALL-MOUNTED GRILLES SHALL BE ALIGNED VERTICALLY AND HORIZONTALLYWHENEVER POSSIBLE. FOR DISCREPANCIES, CONTACT THE ARCHITECT.
20 INSTALL ALL PIPING WITH PITCHES NOTED IN SPECIFICATIONS UNLESS NOTED ORSHOWN OTHERWISE.
21 ECCENTRIC REDUCERS SHALL BE USED UNLESS NOTED OTHERWISE.
22 UNLESS OTHERWISE NOTED, CENTER THERMOSTAT DEVICES ABOVE OUTLETS ANDSWITCHES IF WITHIN CLOSE PROXIMITY AND APPLICABLE. COORDINATE EXACTLOCATIONS WITH ARCHITECT.
23 REFER TO DIVISION 1 DOCUMENT FOR ALTERNATES.
24 PROVIDE FLEXIBLE DUCT CONNECTIONS AT ALL DUCTWORK CONNECTIONS TO AIRHANDLING UNITS, RETURN FANS AND EXHAUST FANS.
25 REFER TO ARCHITECTURAL ROOF PLANS FOR LOCATIONS OF PENETRATIONSTHROUGH ROOF.
GENERAL HVAC NOTES
PACKAGED ROOFTOP UNITS (OWNER PRE-PURCHASED)
RTU SERVES
UNIT HEATING SECTION COOLING SECTION DESIGN DIMENSIONS UNIT ELECTRICAL
MANUF. MODEL REMARKS
SUPPLY FAN EXT. S.P.IN IN.
WATER
SUPPLY FAN
FILTER TYPEENT. AIR
TEMP.LV. AIRTEMP.
INPUTBTU
OUTPUTBTU
BURNERTYPE GAS TYPE
GASPRESS.
INCH W.C.NOM.TONS REF. TYPE
ENT. AIRTEMP.
ENT. AIR TEMP.
COIL LV.AIR TEMP. WIDTH LENGTH HEIGHT
WEIGHTLBS. VOLT PH MCA MOCP
CFM OFSTD. AIR
MIN. CFMOF O.A.
MOTORHP FAN WHEEL TYPE DB (°F) WB (°F)
1 COMMUNITY ROOM 1 1,400 295 0.80 1 CENTRIFUGAL 2" PLEATED 52 °F 95 °F 120000 96000 1 STAGE NG 7 4.0 R-410 81 °F 77 61 52 °F 4' - 5" 7' - 5" 3' - 5" 980 208 3 30 40 TRANE YHC047E3RHA 1,2,3
2 COMMUNITY ROOM 1 1,400 295 0.80 1 CENTRIFUGAL 2" PLEATED 52 °F 95 °F 120000 96000 1 STAGE NG 7 4.0 R-410 81 °F 77 61 52 °F 4' - 5" 7' - 5" 3' - 5" 980 208 3 30 40 TRANE YHC047E3RHA 1,2,3
3 SENIOR'S ROOM 8 1,500 330 0.80 1 CENTRIFUGAL 2" PLEATED 52 °F 95 °F 120000 96000 1 STAGE NG 7 4.0 R-410 86 °F 77 61 53 °F 4' - 5" 7' - 5" 3' - 5" 980 208 3 30 40 TRANE YHC047E3RHA 1,2,3
4 LIBRARY 9 1,400 365 0.80 1 CENTRIFUGAL 2" PLEATED 52 °F 95 °F 120000 96000 1 STAGE NG 7 4.0 R-410 89 °F 77 61 52 °F 4' - 5" 7' - 5" 3' - 5" 980 208 3 30 40 TRANE YHC047E3RHA 1,2,3
5 HALLWAY 1,050 290 0.80 3/4 CENTRIFUGAL 2" PLEATED 52 °F 95 °F 100000 80000 1 STAGE NG 7 3.0 R-410 80 °F 77 61 53 °F 3' - 8" 5' - 10" 3' - 5" 770 208 3 24 30 TRANE YHC037E3RHA 1,2,3
6 GYMNASIUM 17 3,700 890 0.80 2 3/4 PLENUM 2" PLEATED 52 °F 95 °F 200000 160000 2 STAGE NG 7 10.0 R-410 85 °F 77 61 53 °F 5' - 3" 8' - 4" 4' - 3" 1610 208 3 48 60 TRANE YHC120F3MA 1,2,3
DIFFUSER, REGISTER, GRILLEMIN AIRFLOW
(CFM)MAX AIRFLOW
(CFM) SERVICE FACE SIZE NECK SIZE MOUNTING MANUF. MODEL REMARKS
RG-1
120 210 RETURN 24"x24" 8" LAY-IN PRICE 80
450 700 RETURN 24"x24" 16" LAY-IN PRICE 80
700 1600 RETURN 24"x24" LAY-IN
RG-2
0 700 RETURN 24"x12" SIDEWALL PRICE 530
SD-1
0 120 SUPPLY 24"x24" 6" LAY-IN PRICE SPD
121 210 SUPPLY 24"x24" 8" LAY-IN PRICE SPD
SDG-1
0 100 SUPPLY 10"x4" DUCT MOUNT PRICE SDG
101 150 SUPPLY 10"x4" DUCT MOUNT PRICE SDG
151 500 SUPPLY 22"x8" DUCT MOUNT PRICE SDG
ELECTRIC WALL HEATERS (OWNER PRE-PURCHASED)
EWH SERVES
CABINET
CAP. WATTS CAP BTU RECESSINTEGRAL
STAT
ELECTRICAL
MANUF. MODEL REMARKSW H D VOLT PH FLA
1 ENTRY 111 1' - 2" 1' - 6" 0' - 4" 3000 10240 NO YES 208 1 14.4 QMARK AWH4404F
2 ENTRY 111 1' - 2" 1' - 6" 0' - 4" 3000 10240 NO YES 208 1 14.4 QMARK AWH4404F
3 MENS 111A 1' - 2" 1' - 6" 0' - 4" 3500 11950 NO YES 208 1 19.2 QMARK AWH4408F
4 WOMENS 113B 1' - 2" 1' - 6" 0' - 4" 3500 11950 NO YES 208 1 19.2 QMARK AWH4408F
5 MENS 208 1' - 2" 1' - 6" 0' - 4" 2500 8530 NO YES 208 1 14.4 QMARK AWH4404F
6 WOMENS 206 1' - 2" 1' - 6" 0' - 4" 2500 8530 NO YES 208 1 14.4 QMARK AWH4404F
1. PROVIDE WITH SINGLE ZONE VAV CONROLS.2. PROVIDE WITH VARIABLE SPEED, DIRECT DRIVE FAN.3. BASED ON 87° DB/75°WB SUMMER AND -15° DB WINTER DESIGN CONDITIONS
ELECTRIC BASEBOARD RADIATION
EBB LOCATION SERVICECAP.
WATTS LENGTH VOLT PH FLA MANUF. MODEL REMARKS
1 001 MARSHAL'S OFFICE 001 MARSHAL'S OFFICE 2500 8' - 0" 208 1 12 QMARK QMKC25008W 1
1. PROVIDE INTEGRAL THERMOSTAT.
HEAT PUMP UNIT (OWNER PRE-PURCHASED)
ACCU
COMPRESSOR ELECTRICAL
MANUF. MODEL REMARKSSERVICE LOCATION NOM. CAP. TONS SEER VOLT PH MCA MOCP
1 FCU-1 ROOF 2.0 15 208 1 17 27 TRANE/MITSUBISHI NTXSKH24A112AA
2 FCU-2 ROOF 2.0 15 208 1 17 27 TRANE/MITSUBISHI NTXSKH24A112AA
3 FCU-3 ROOF 2.0 15 208 1 17 27 TRANE/MITSUBISHI NTXSKH24A112AA
4 FCU-4 ROOF 2.0 15 208 1 17 27 TRANE/MITSUBISHI NTXSKH24A112AA
5 FCU-5 ROOF 2.0 15 208 1 17 27 TRANE/MITSUBISHI NTXSKH24A112AA
6 FCU-6 ROOF 2.0 15 208 1 17 27 TRANE/MITSUBISHI NTXSKH24A112AA
7 FCU-7 ROOF 2.0 15 208 1 17 27 TRANE/MITSUBISHI NTXSKH24A112AA
8 FCU-8 ROOF 2.0 15 208 1 17 27 TRANE/MITSUBISHI NTXSKH24A112AA
9 FCU-9 ROOF 2.0 15 208 1 17 27 TRANE/MITSUBISHI NTXSKH24A112AA
10 FCU-10 ROOF 2.0 15 208 1 17 27 TRANE/MITSUBISHI NTXSKH24A112AA
FAN COIL UNIT (OWNER PRE-PURCHASED)
FCU LOCATION SERVES TYPE CFM OF STD. AIR MIN. CFM OF O.A.COOLING CAP.
(BTU)HEATING CAP. @
-13°F (BTU)
ELECTRICAL
MANUF, MODEL REMARKSVOLT PH
1 CEILING 002 STORAGE HORIZ. DUCTED 600 100 CFM 24000 20000 208 1 TRANE/MITSUBISHI TPEADA0241AA70A POWERED BY OUTDOOR UNIT
2 CEILING 001 MARSHAL'S OFFICE HORIZ. DUCTED 600 90 CFM 24000 20000 208 1 TRANE/MITSUBISHI TPEADA0241AA70A POWERED BY OUTDOOR UNIT
3 CEILING 101 OFFICE HORIZ. DUCTED 600 90 CFM 24000 20000 208 1 TRANE/MITSUBISHI TPEADA0241AA70A POWERED BY OUTDOOR UNIT
4 CEILING 116 CONFERENCE HORIZ. DUCTED 600 115 CFM 24000 20000 208 1 TRANE/MITSUBISHI TPEADA0241AA70A POWERED BY OUTDOOR UNIT
5 CEILING 116 CONFERENCE HORIZ. DUCTED 600 115 CFM 24000 20000 208 1 TRANE/MITSUBISHI TPEADA0241AA70A POWERED BY OUTDOOR UNIT
6 CEILING 115 CONFERENCE HORIZ. DUCTED 600 150 CFM 24000 20000 208 1 TRANE/MITSUBISHI TPEADA0241AA70A POWERED BY OUTDOOR UNIT
7 CEILING 205 OFFICE HORIZ. DUCTED 600 60 CFM 24000 20000 208 1 TRANE/MITSUBISHI TPEADA0241AA70A POWERED BY OUTDOOR UNIT
8 CEILING 204 OFFICE HORIZ. DUCTED 600 55 CFM 24000 20000 208 1 TRANE/MITSUBISHI TPEADA0241AA70A POWERED BY OUTDOOR UNIT
9 CEILING 204 OFFICE HORIZ. DUCTED 600 55 CFM 24000 20000 208 1 TRANE/MITSUBISHI TPEADA0241AA70A POWERED BY OUTDOOR UNIT
10 CEILING 202 OFFICE HORIZ. DUCTED 600 55 CFM 24000 20000 208 1 TRANE/MITSUBISHI TPEADA0241AA70A POWERED BY OUTDOOR UNIT
REMOVE EXISTING UNIT VENTILATOR, ASSOCIATED PIPING AND CONTROL. CAP PIPING BELOW FLOOR.
REMOVE EXISTING UNIT VENTILATOR, ASSOCIATED PIPING AND CONTROL. CAP PIPING BELOW FLOOR.
104A
CLOSETS
104
COMMUNITY ROOM
105A
DISHES
105
KITCHEN
190
CORRIDOR
102B
LIBRARY (STACK)103
SENIOR'S ROOM
103A
CLOSETS
?
?
103B
TOILET
111C
STORAGE
REMOVE EXISTING UNIT VENTILATOR, ASSOCIATED PIPING AND CONTROL. CAP PIPING BELOW FLOOR.
REMOVE EXISTING UNIT VENTILATOR, ASSOCIATED PIPING AND CONTROL. CAP PIPING BELOW FLOOR. 001
MARSHAL'S OFFICE
002
STORAGE
003
STORAGE (EXISTING BOILER)
KEY PLAN
A
N
ARCHITECTUREENGINEERINGINTERIOR DESIGN
MADISON, WI | WAUKESHA, WI
SHEET NAME
PROJECT TITLE
COPYRIGHT STRANG, INC.
DRAWING SET
DATE
PROJECT NO.
SHEET NO.
2021
9/22
/202
1 3:
11:3
6 P
M
09/20/2021
208 JARVIS STRIDGEWAY, WI 53582
RIDGEWAYCOMMUNITY CENTERRENOVATIONS
2021046
CD
MECHANICALDEMOLITION PLANAREA A
M101A
SCALE: 1/8" = 1'-0"M101A
1 FIRST FLOOR MECHANICAL DEMOLITION PLAN
SCALE: 1/8" = 1'-0"M101A
2 BASEMENT MECHANICAL DEMOLITION PLAN
0" 4' 8' 16'
0" 4' 8' 16'
REMOVE EXISTING UNIT VENTILATOR, ASSOCIATED PIPING AND CONTROL. CAP PIPING BELOW FLOOR.
REMOVE EXISTING UNIT VENTILATOR, ASSOCIATED PIPING AND CONTROL. CAP PIPING BELOW FLOOR.
111
STORAGE
111B
OFFICE
111C
STORAGE
111D
SHOWER
111A
MENS
190
CORRIDOR
101
OFFICE
116
CONFERENCE 115
CONFERENCE
190
CORRIDOR
114
ENTRY
113
STORAGE
113C
STORAGE
113B
WOMENS
112
GYMNASIUM
KEY PLAN
B
N
ARCHITECTURE
ENGINEERING
INTERIOR DESIGN
MADISON, WI | WAUKESHA, WI
SHEET NAME
PROJECT TITLE
COPYRIGHT STRANG, INC.
DRAWING SET
DATE
PROJECT NO.
SHEET NO.
2021
9/22
/202
1 3:
12:0
5 P
M
09/20/2021
208 JARVIS STRIDGEWAY, WI 53582
RIDGEWAYCOMMUNITY CENTERRENOVATIONS
2021046
CD
MECHANICALDEMOLITION PLANAREA B
M101B
SCALE: 1/8" = 1'-0"M101B
1 FIRST FLOOR MECHANICAL DEMOLITION PLAN
0" 4' 8' 16'
30"x
8" S
A
30"x
8" R
A
20"x
8" S
A
30"x
8" S
A
30"x
8" R
A
30"x
8" S
A
30"x
8" R
A
20"x
8" S
A
30"x8" SA
30"x8" RA
20"x
8" S
A
200
SD-1
200
SD-1 200
SD-1
200
SD-1
200
SD-1
200
SD-1
200
SD-1
200
SD-1
200
SD-1200
SD-1
200
SD-1
200
SD-1
200
SD-1
200
SD-1
200
SD-1
200
SD-1
200
SD-1
200
SD-1
200
SD-1
200
SD-1
200
SD-1
200
SD-1
200
SD-1200
SD-1
200
SD-1
200
SD-1
200
SD-1
200
SD-1
8"ø SA (TYP) 8"ø SA (TYP)
700
RG-1
750
RG-1
700
RG-1
16"ø SA DN FROM RTU-516"ø RA UP TO RTU-5 500
RG-2
12"ø SA UP12"ø RA DN
10"ø SA
8"ø SA
50
SDG-1
50
SDG-1
50
SDG-1 6"ø SA
50
SDG-1
190
CORRIDOR
111C
STORAGE
FD
FD
105
KITCHEN
105A
DISHES
104
COMMUNITY ROOM104A
CLOSETS
103B
TOILET
103A
CLOSETS
103
SENIOR'S ROOM
102B
LIBRARY (STACK)
190
CORRIDOR30"x32" SA DN FROM RTU-1
30"x32" RA UP TO RTU-1
30"x32" SA DN FROM RTU-2
30"x32" RA UP TO RTU-2
20"x
8" S
A8"ø SA (TYP)
100
SD-1
100
SD-18"ø SA
30"x32" SA DN FROM RTU-3
30"x32" RA UP TO RTU-3
30"x32" SA DN FROM RTU-4
30"x32" RA UP TO RTU-4
750
RG-1 700
RG-1
700
RG-1
700
RG-1
700
RG-1
TRTU-2
TRTU-1
TRTU-3
TRTU-4
TRTU-5
ACCU-1
ACCU-2
200
SD-1
200
SD-1
200
SD-1
510
RG-1
200
SD-1
200
SD-1
200
SD-1
EWH-1
002
STORAGE
003
STORAGE (EXISTING BOILER)
001
MARSHAL'S OFFICE
EBB-1
EBB-1
4"ø
OA
500
RG-1
4"ø OA
MOTORIZED DAMPER
3/4" COND. DOWN ALONG WALL. SPILL ON GRADE.
3/4" COND. DOWN ALONG WALL. SPILL ON GRADE.
WALL CAP
REF. PIPING INSTALL PER MANUF. RECOMM.
REF. PIPING DOWN ALONG WALL.
REF. PIPING INSTALL PER MANUF. RECOMM.
TFCU-1
TFCU-2
16"x
8" S
A
FCU-1
FCU-2
WALL CAP
3/4" C
16"x8" SA
16"x8" RA
16"x8" RA
3/4"
C
SLO
PE
SLOPE
REF. PIPING DOWN ALONG WALL.
MOTORIZED DAMPER
KEY PLAN
A
N
ARCHITECTUREENGINEERINGINTERIOR DESIGN
MADISON, WI | WAUKESHA, WI
SHEET NAME
PROJECT TITLE
COPYRIGHT STRANG, INC.
DRAWING SET
DATE
PROJECT NO.
SHEET NO.
2021
9/22
/202
1 3:
11:4
0 P
M
09/20/2021
208 JARVIS STRIDGEWAY, WI 53582
RIDGEWAYCOMMUNITY CENTERRENOVATIONS
2021046
CD
MECHANICAL PLANAREA A
M201A
SCALE: 1/8" = 1'-0"M201A
1 FIRST FLOOR MECHANICAL PLAN AREA A
SCALE: 1/8" = 1'-0"M201A
2 BASEMENT MECHANICAL PLAN AREA A
0" 4' 8' 16'
0" 4' 8' 16'
EWH-2
12"ø SA UP12"ø RA DN
10"ø SA
50
SDG-150
SDG-1
50
SDG-1
50
SDG-150
SDG-1
50
SDG-1
450
RG-1
485
RG-1
485
RG-1
200
SD-1
200
SD-1
200
SD-1
200
SD-1
200
SD-1
200
SD-1
200
SD-1
200
SD-1
200
SD-1
510
RG-1
10"ø SA
10"ø SA 10"ø SA200
SD-1
200
SD-1
200
SD-1
22"ø SA
500
SDG-1
500
SDG-1
500
SDG-1
500
SDG-1
500
SDG-1
500
SDG-1
500
SDG-1
500
SDG-1
500
SDG-1
500
SDG-1
34"x18" RA TURNED UP
101
OFFICE
190
CORRIDOR
111
STORAGE
111C
STORAGE
111B
OFFICE
111A
MENS111D
SHOWER
112
GYMNASIUM
116
CONFERENCE
115
CONFERENCE
113C
STORAGE113B
WOMENS
113A
JANITOR
114
ENTRY
1 1/4" COND. DOWN ALONG WALL. SPILL ON GRADE.
REF. PIPING INSTALL PER MANUF. RECOMM.
REF. PIPING UPREF. PIPING UP
TRTU-6
TFCU-3
FCU-3
REF. PIPING INSTALL PER MANUF. RECOMM.
REF. PIPING INSTALL PER MANUF. RECOMM.
8"ø OA
6"ø 6"
ø
6"ø8"ø OA
REF. PIPING INSTALL PER MANUF. RECOMM.
TFCU-4
TFCU-5
TFCU-6
REF. PIPING INSTALL PER MANUF. RECOMM.
16"x
8"
FCU-4
16"x8" SA16"x8" SA
16"x
8" S
A
FCU-5 FCU-6
200
RG-1
200
RG-1
FD
FD
190
CORRIDOR
3/4" C1 1/4" C1 1/4" C1" C3/4" C
3/4" C
16"x8" RA
16"x8" RA 16"x8" RA 16"x8" RA
EWH-3EWH-4
3/4" COND. DOWN ALONG WALL. SPILL ON GRADE.
18"x34" SA FROM RTU-6 ABOVE
18"x34" RA UP TO RTU-6 ABOVE
1" COND. DOWN FROM ABOVE
SLOPE SLOPE SLOPE
REF. PIPING UP
MOTORIZED DAMPER
MOTORIZED DAMPER
8"ø SA 6"ø SA
12"ø RA DN
12"ø SA UP
700
RG-2
12"ø SA150
SDG-110"ø SA
100
SDG-1
100
SDG-1100
SDG-1
8"ø SA
6"ø SA
540
RG-1
545
RG-1
545
RG-1
120
SD-1
120
SD-1
120
SD-1120
SD-1
120
SD-1
120
SD-1
120
SD-1
120
SD-1
120
SD-1
545
RG-1200
SD-1
200
SD-1
200
SD-1
208
MENS
206
WOMENS
205
OFFICE
204
OFFICE
290
CORRIDOR
112
GYMNASIUM
202
OFFICE
203
STORAGE
201
OFFICE
829.63 SF
8"ø OA
6"ø 6"ø
6"ø
16"x
8" S
A
FCU-9
16"x
8" S
A
FCU-8FCU-7
16"x
8" S
A
REF. PIPING UP WITHIN PIPE CURB ASSEMBLY
REF. PIPING UP WITHIN PIPE CURB ASSEMBLY
REF. PIPING INSTALL PER MANUF. RECOMM.
6"ø
OA
FCU-10
REF. PIPING INSTALL PER MANUF. RECOMM.
REF. PIPING INSTALL PER MANUF. RECOMM.
REF. PIPING INSTALL PER MANUF. RECOMM.
120
SD-1
120
SD-1
120
SD-1
120
SD-1
120
SD-1
120
SD-1
FD
FD
8"Ø OED. BALANCE TO 300 CFM
12"ø RA
REF. PIPING UP WITHIN PIPE CURB ASSEMBLY
REMOVE BACKDRAFT DAMPER IN EXISTING BUILDING RELEIF. CONNECT NEW OA DUCT TO EXISTING DUCT ABOVE CEILING.
3/4" COND. DOWN TO LEVEL 1
REMOVE BACKDRAFT DAMPER IN EXISTING BUILDING RELEIF. CONNECT NEW OA DUCT TO EXISTING DUCT ABOVE CEILING.
SLOPE SLOPE SLOPE
1" COND DOWN TO LEVEL 1
EWH-5 EWH-6
REF. PIPING UP WITHIN PIPE CURB ASSEMBLY
KEY PLAN
B
N
ARCHITECTURE
ENGINEERING
INTERIOR DESIGN
MADISON, WI | WAUKESHA, WI
SHEET NAME
PROJECT TITLE
COPYRIGHT STRANG, INC.
DRAWING SET
DATE
PROJECT NO.
SHEET NO.
2021
9/22
/202
1 3:
11:4
9 P
M
09/20/2021
208 JARVIS STRIDGEWAY, WI 53582
RIDGEWAYCOMMUNITY CENTERRENOVATIONS
2021046
CD
MECHANICAL PLANAREA B
M201BSCALE: 1/8" = 1'-0"M201B
1 FIRST FLOOR MECHANICAL PLAN AREA B
SCALE: 1/8" = 1'-0"M201B
2 SECOND FLOOR MECHANICAL PLAN AREA B
0" 4' 8' 16'
0" 4' 8' 16'
RTU-3
RTU-2
RTU-5
RTU-4
DROP
1" NG
3/4" NG
3/4"
NG
3/4"
NG
3/4" NG
LOOP SEAL
LOOP SEAL
LOOP SEAL
LOOP SEAL
LOOP SEAL
INSTALL GAS PIPING ON PIPE SUPPORT BLOCKS 8'-0" O.C. (MAX)
3/4"
NG
RTU-1
RTU-6
3/4" NG
1 1/4" NG UP FROM EXISTING GAS METER (1000 CFH @ 2 PSIG). VERIFY LOCATION AND PRESSURE WITH LOCAL UTILITY.
1 1/4" NG
1" NG
1" TEE, CAP FOR FUTURE (300 CFH)
1" NGDROP
1" NG
ACCU-3 ACCU-4 ACCU-5 ACCU-6ACCU-7 ACCU-8 ACCU-9
ACCU-10
REF. PIPING INSTALL PER MANUF. RECOMM.
REF. PIPING INSTALL PER MANUF. RECOMM.
REF. PIPING INSTALL PER MANUF. RECOMM.
EXISTING ROOF CAP
EXISTING ROOF CAP
INSTALL GAS PIPING ON PIPE SUPPORT BLOCKS 8'-0" O.C. (MAX)
INSTALL REF. PIPE SUPPORT BLOCKS 8'-0" O.C. (MAX.) TYP
REF PIPING FROM BELOW (TYP)
LOOP SEAL
KEY PLAN
A B
N
ARCHITECTURE
ENGINEERING
INTERIOR DESIGN
MADISON, WI | WAUKESHA, WI
SHEET NAME
PROJECT TITLE
COPYRIGHT STRANG, INC.
DRAWING SET
DATE
PROJECT NO.
SHEET NO.
2021
9/22
/202
1 3:
11:5
5 P
M
09/20/2021
208 JARVIS STRIDGEWAY, WI 53582
RIDGEWAYCOMMUNITY CENTERRENOVATIONS
2021046
CD
ROOF MECHANICALPLAN
M202SCALE: 1/8" = 1'-0"M202
1 ROOF MECHANICAL PLAN AREA A
SCALE: 1/8" = 1'-0"M202
2 ROOF MECHANICAL PLAN AREA B
0" 4' 8' 16'
0" 4' 8' 16'
DESCRIPTION DOUBLE LINE SINGLE LINE
BRANCH TAKE-OFF SUPPLY, RETURN OR
EXHAUST
CONVERGING
TEE
ELBOW
TRANSITION FITTINGS
OR
6"
MIN
1/4
W
45.0
0°
W
R
W
DIVERGING
FLOW
FLOW
20° MAX
30° MAX
R / W = 1.5
45° TYP
L
W
MIN DIM = 2W
OPPOSED BLADE DAMPER AS PER SPECIFICATIONS
NOTE:
L = 1/4W (4" MIN)
AIRFLOW 45° BOOT TAP
AIRFLOW
AIRFLOW
SELF-SEALING GASKET DUCT CONNECTION (LINLAB SPIROSAFE OR EQUAL)
SPIRAL DUCTBALANCE DAMPER
45° TAKE-OFF, RECT TO ROUND AS REQUIRED
FLEX DUCT, 48" MAX LENGTH
FLEX ELBOW, SUPPORT TO MAINTAIN RADIUS
SUPPLY DIFFUSER
CONDENSING UNIT, MOUNT WITH VIBRATION ISOLATORS
PENETRATE UP
RUN IN CEILING SPACE
COIL CONNECTION
DRAIN TO OUTSIDE
EXPANSION VALVE
AIR CONDSIGHT GLASS
FILTER DRYER AIRFLOWL S
L
S
SLOPE PIPE DOWN
CLAMPS
STAINLESS STEEL WASHER EMBEDDED IN CONST. SEALANT.
LAG SCREW
ROOF CURB BY MECH. CONTR.
RUBBER FLASHING BY GEN. CONTR.
INSULATION
ROOF DECK
ROOFING
WOOD NAILER BY MECH.
CONTR.
COVER
BOOT
GAS PIPE
GALVANIZED STEEL STRAP
"DURA-BLOK" ROOF SUPPORT BY MECHANICAL CONTACTOR
INSULATION
ROOF DECK
ROOFING
SRCURE DUCT TO UNIT IN ACCORDANCE WITH MANUF. INSTRUCTIONS
GASKET ALL AROUND BY MECH. CONTR.
WOOD NAILER BY MECH. CONTR.
ROOF CURB BY MECH. CONTR.
RUBBER FLASHING BY
ROOFING CONTR.
ROOFING
INSULATION
ROOF DECK
"D.O."
CAULK AROUND CLOSURE PLATE
SHEET METAL DUCT
FLEXIBLE CONNECTION
ACOUSTIC SEALANT AT ALL EDGES
2 LAYERS OF 5/8" MOLD RESISTANT PAPERLESS GYP. BD. BY MECH CONTR.
6" ROCKWOOL INSULATION BY MECH. CONTR.
SHEET METAL CLOSURE PLATE BY MECH. CONTR.
ROOF OPENING TO ACCOMMODATE DUCT-WORK ONLY
ACOUSTIC INSULATION
GALV. STEEL CHANNEL
GALV. METAL ANGLE1
2"
MIN
ARCHITECTURE
ENGINEERING
INTERIOR DESIGN
MADISON, WI | WAUKESHA, WI
SHEET NAME
PROJECT TITLE
COPYRIGHT STRANG, INC.
DRAWING SET
DATE
PROJECT NO.
SHEET NO.
2021
9/22
/202
1 3:
11:5
9 P
M
09/20/2021
208 JARVIS STRIDGEWAY, WI 53582
RIDGEWAYCOMMUNITY CENTERRENOVATIONS
2021046
CD
MECHANICAL DETAILS
M801
SCALE: NTSM801
1 DUCT FITTINGSSCALE: NTSM801
2 BRANCH DUCT TAKE-OFF AND DAMPERSCALE: NTSM801
3 SPIRAL DUCT TEE TAP DETAILSCALE: NTSM801
4 CEILING DIFFUSER CONNECTION
SCALE: NTSM801
5 SPLIT SYSTEM AIR CONDITIONERSCALE: NTSM801
6 PIPE CURB ASSEMBLYSCALE: NTSM801
7 GAS PIPING RUN ABOVE ROOFSCALE: NTSM801
8 ROOFTOP UNIT CURB DUCT CONN.
J
LINE VOLTAGE DIGITAL COUNTDOWN TIMER SWITCH
JUNCTION BOX
ELECTRICAL ABBREVIATIONS
OS
LV#WALL OCCUPANCY SENSOR, DUAL TECHNOLOGY. REFER TO SPECIFICATIONS FOR REQUIREMENTS.
DAYLIGHT HARVESTING SENSOR.
ACT ACOUSTICAL CEILING TILEAFF ABOVE FINISH FLOORAFG ABOVE FINAL GRADEAIC AMPERE INTERRUPTING CAPACITYALT ALTERNATEAPPROX APPROXIMATELYAMP AMPEREARCH ARCHITECT, ARCHITECTURALATS AUTOMATIC TRANSFER SWITCHAUX AUXILIARYAV AUDIO VISUALAWG AMERICAN WIRE GAUGE
BFG BELOW FINAL GRADEBLDG BUILDINGBSC BIOSAFETY CABINET
C CONDUITCB CIRCUIT BREAKERCCTV CLOSED CIRCUIT TELEVISIONCFCI CONTR FURNISHED, CONTR
INSTALLEDCKT CIRCUITCLG CEILINGCONT CONTINUOUS, CONTINUATIONCONTR CONTRACTORCT CABLE TRAYCTP CLEAN TECHNICAL POWERCTR CENTERCU COPPER
DAS DISTRIBUTED ANTENNA SYSTEMDED DEDICATEDDISC DISCONNECTDIST DISTRIBUTIONDIV DIVISIONDWG DRAWING
EBU EMERGENCY BATTERY UNITEC ELECTRICAL CONTRACTOREGB EQUIPMENT GROUND BUSELCU EMERGENCY LIGHTING CONTROL
UNITELEC ELECTRICALELEV ELEVATOREM EMERGENCYEMT ELECTRICAL METAL TUBINGEQUIP EQUIPMENTER ELEVATOR RECALLETR EXISTING TO REMAINEWC ELECTRIC WATER COOLER
F FUSEFA FIRE ALARMFB FLOOR BOXFL FLOORFPC FIRE PROTECTION CONTRACTOR
GC GENERAL CONTRACTORGD GARBAGE DISPOSALGFCI GROUND FAULT CKT INTERRUPTERGND GROUNDGYP GYPSUM
HOA HAND-OFF-AUTOMATIC SWITCHHORIZ HORIZONTALHP HORSEPOWERHT HEIGHT
IG ISOLATED GROUNDIT INFORMATION TECHNOLOGY
JB JUNCTION BOX
KV KILOVOLTKVA KILOVOLT-AMPEREKW KILOWATTKWH KILOWATT HOUR
LTS LIGHTSLV LOW VOLTAGE
BASIC LIGHTING CONTROL DEVICE SYMBOLS
MISCELLANEOUS SYMBOLS
MC MECHANICAL/HVAC CONTRACTORMCB MAIN CIRCUIT BREAKERMCC MOTOR CONTROL CENTERMEGB MAIN EQUIPMENT GROUNDING BUSMIN MINIMUMMISC MISCELLANEOUSMLO MAIN LUG ONLYMMS MANUAL MOTOR STARTERMFR MANUFACTURERMTR MOTORMTS MANUAL TRANSFER SWITCHMW MICROWAVE
N.C. NORMALLY CLOSEDNEC NATIONAL ELECTRICAL CODENEMA NATIONAL ELECTRICAL MFR ASSOC.NFSS NON-FUSED SAFETY SWITCHNIC NOT IN CONTRACTNL NIGHTLIGHTN.O. NORMALLY OPENNTS NOT TO SCALENU NEAR UNIT
OFCI OWNER FURNISHED, CONTR INSTALLED
OFOI OWNER FURNISHED, OWNER INSTALLED
OU ON UNIT
P POLEPBC PLUMBING CONTRACTORPDO POWER DOOR OPERATORPH PHASEPNL PANELPP POWER POLEPRI PRIMARYPRV POWER ROOF VENTILATORPVC POLYVINYL CHLORIDE
SHT SHEETSPEC SPECIFICATIONSPKR SPEAKERSP SPARESPD SURGE PROTECTIVE DEVICESTD STANDARDSUSP SUSPENDEDSW SWITCHSWBD SWITCHBOARDSWGR SWITCHGEARSYM SYMMETRICALSYS SYSTEM
TR TAMPER RESISTANTTCP TEMPERATURE CONTROL PANELTEL TELEPHONEXFMR TRANSFORMERTV TELEVISIONTYP TYPICAL
UG UNDERGROUNDUH UNIT HEATERUNO UNLESS NOTED OTHERWISE
V VOLTVA VOLT AMPEREVDP VIDEO DISPLAY PANELVERT VERTICALVFD VARIABLE FREQUENCY DRIVEVSD VARIABLE SPEED DRIVE
W WATTW/ WITHWC WATER CLOSETW/O WITHOUTWP WET LOCATION/WEATHERPROOF
XP EXPLOSION PROOF
LINETYPE EXPLANATION
SOLID DEVICES, LUMINAIRES, AND EQUIPMENT SHOWN WITH A HALF-TONE LINETYPE ARE EXISTING AND SHALL REMAIN IN PLACE.
DASHED DEVICES, LUMINAIRES, AND EQUIPMENT ARE TO BE DEMOLISHED AS PART OF THIS WORK.
SOLID DEVICES, LUMINAIRES, AND EQUIPMENT SHOWN WITH A DARK LINETYPE ARE NEW AND ARE BEING INSTALLED AS PART OF THIS WORK.
MOTOR OR ELECTRICAL CONNECTION TO EQUIPMENT.SEE ELECTRICAL CONNECTION SCHEDULE (UNO)
PANELBOARD
WHERE RECEPTACLES OR DATA DEVICES ARE NOTED AS "ABOVE COUNTER" THEY SHALL BE MOUNTED 6" ABOVE COUNTER OR 46" AFF WHERE NOT LOCATED ABOVE A COUNTER, UNLESS OTHERWISE NOTED ON PLANS, DETAILS, OR AS SHOWN ON ARCHITECTURAL ELEVATIONS.
DUPLEX RECEPTACLEABOVE COUNTER
DOUBLE DUPLEX RECEPTACLEABOVE COUNTER
PNL XXX
RECEPTACLE DEVICE SYMBOLS
SIMPLEX RECEPTACLENEMA DESIGNATION AS NOTED ON PLANSABOVE COUNTER
POWER DISTRIBUTION SYMBOLS
ELECTRICAL CONNECTION - SEE SCHEDULE (UNO)
NON-FUSED SAFETY DISCONNECT SWITCH
FUSED SAFETY DISCONNECT SWITCH
COMBINATION STARTER/DISCONNECT SWITCH
T TRANSFORMER
LINE VOLTAGE TOGGLE SWITCH WITH PILOT LIGHTP
LIGHTING CONTROL BUTTON STATION. REFER TO SPECIFICATIONS FOR REQUIREMENTS.
LV#
LIGHTING IS REPRESENTED BY SHAPES WHICH REPRESENT THE APPROXIMATE SIZEAND SHAPE OF THE LUMINIARES SPECIFIED. THE ACTUAL FIXTURE SPECIFICATION ANDLOCATION (WALL, CEILING, FLOOR, ETC.) IS BASED ON THE DATA IN THE LUMINAIRESCHEDULE FOR THE LISTED FIXTURE TYPE AND OTHER DOCUMENTATION.
F1X-##,a
FIXTURE ID(SEE LUMINAIRE SCHEDULE)
CIRCUIT DESIGNATION, CONTROL ZONE DESIGNATION
SWITCH ZONE DESIGNATIONS ON FIXTURES CORRESPOND WITH CONTROL DEVICES(I.E. SWITCHES, SENSORS, ETC) WITH THE SAME DESIGNATION
LIGHTING SYMBOLS
ROUND RECESSED DOWNLIGHT, ROUND PENDANT LUMINAIRE,ROUND GROUND MOUNTED UPLIGHT.
SQUARE RECESSED DOWNLIGHT, SQUARE WALL MOUNTED LUMINAIRE, SQUARE GROUND MOUNTED UPLIGHT.
2'x2' RECESSED, SURFACE, PENDANT LUMINAIRE.
1'x4' CEILING MOUNTED, LINEAR DIRECT/INDIRECT, LINEAR WALL WASH, WALL MOUNTED LUMINAIRE
2'x4' RECESSED, SURFACE, PENDANT LUMINAIRE.
WALL MOUNTED LUMINAIRE
POLE MOUNTED LUMINAIRE
POLE MOUNTED POST-TOP LUMINAIRE, BOLLARD LUMINAIRE
CEILING MOUNTED SPOT-TYPE EMERGENCY BATTERY UNIT
WALL MOUNTED SPOT-TYPE EMERGENCY BATTERY UNIT
CEILING MOUNTED EXIT OR AREA OF RESCUE ASSISTANCE SIGN.
WALL MOUNTED EXIT OR AREA OF RESCUE ASSISTANCE SIGN.
T
BASIC SLIDE DIMMER WITH POSITIVE OFF SWITCH. MATCH DIMMING TECHNOLOGY TO LOAD CONTROLLED
D
LOW VOLTAGE LIGHTING CONTROL DEVICE SYMBOLS
DEVICE CONFIGURATION NOTATION (TYP). REFER TO SPECIFICATIONS FOR ALL SEQUENCES OF OPERATIONS AND ADDITIONAL REQUIREMENTS.
4' INDUSTRIAL LUMINAIRE
L1
LINE VOLTAGE TOGGLE SWITCH
DH
LINE VOLTAGE WALL OCCUPANCY SENSOR.INDICATES SWITCHING DESIGNATION
#
MEDIAL LINES DENOTE TROFFER ORIENTATION
FEEDER AND BRANCH CIRCUIT DESIGNATIONS
SYSTEM DESCRIPTION(2G) 1ø, 2W + GND(3G) 3ø, 3W + GND(4G) 3ø, 4W + GND(5G) 3ø, 3W + 200%N + GND(5G+IG) 3ø, 3W + 200%N + GND + ISOLATED GND
CONDUCTOR AMPACITY(SEE FEEDER SCHEDULE)
200-4G
NOTE:2G DESIGNATION SHALL HAVE AN EQUAL PHASE, NEUTRAL, AND GROUND CONDUCTOR SIZE AS 3G DESIGNATION. CONDUIT SIZE PER SPECIFICATION AND CODE.
ONE-LINE DIAGRAM SYMBOLS
M
GROUND ELECTRODE
NON-FUSED SWITCHAMPERAGE/PHASE
FUSED SWITCH
METER ENCLOSURE WITH SOCKET
400/3
SWITCH AMPERE/POLE
FUSE AMPERE
400/3300
AMPERE, POLE, SETTINGS, VOLTAGES, IDENTIFICATION, AND SIZES BELOW ARE EXAMPLES AND ARE NOT REPRESENTATIVE OF ACTUAL VALUES, REFER TO ONE-LINE DIAGRAM, RISER DIAGRAM, PANEL SCHEDULES, MOTOR SCHEDULES, EQUIPMENT SCHEDULES, AND DETAILS FOR ACTUAL VALUES.
MDPPANEL
ELECTRICAL PANELBOARD (REFER TO PANELBOARD SCHEDULE) IDENTIFICATION TAG
FACP
FIRE ALARM PULL STATION
WALL AUDIBLE/VISUAL NOTIFICATION APPLIANCE
SMOKE DETECTOR
FIRE ALARM REMOTE ANNUNCIATOR PANEL
FIRE ALARM CONTROL PANEL
A CEILING MOUNTED AUDIBLE-ONLY NOTIFICATION APPLIANCE
WALL MOUNTED VISUAL-ONLY NOTIFICATION APPLIANCE
CM FIRE ALARM ADDRESSABLE CONTROL MODULE
MM FIRE ALARM ADDRESSABLE MONITOR MODULE
DUCT SMOKE DETECTORSD
AV
V CEILING MOUNTED VISUAL-ONLY NOTIFICATION APPLIANCE
HEAT DETECTORH
WALL AUDIBLE-ONLY NOTIFICATION APPLIANCE
CEILING MOUNTED AUDIBLE/VISUAL NOTIFICATION APPLIANCE
AUDIBLE NOTIFICATION APPLIANCES SHALL BE TEMPORAL TYPE, UNLESS OTHERWISE NOTED.
PROVIDE POLYCARBONATE TAMPER COVER (WITH LOCAL ALARM)TR
INDICATES MINIMUM VISUAL APPLIANCE CANDELA RATING (TYP.)#
FIRE ALARM DEVICE SYMBOLS
RI REMOTE TEST AND INDICATOR STATION
#
#
#
NAC FIRE ALARM NAC PANEL
FAAP
MINOR MOTION COVERAGE CEILING OCCUPANCY SENSOR, DUAL TECHNOLOGY. REFER TO SPECIFICATIONS FOR REQUIREMENTS.
ARCHITECTURE
ENGINEERING
INTERIOR DESIGN
MADISON, WI | WAUKESHA, WI
SHEET NAME
PROJECT TITLE
COPYRIGHT STRANG, INC.
DRAWING SET
DATE
PROJECT NO.
SHEET NO.
2021
9/20
/202
1 1:
49:2
3 P
M
09/20/2021
208 JARVIS ST.RIDGEWAY, WI 53582
RIDGEWAYCOMMUNITY CENTERRENOVATIONS
2021046
CD
ELECTRICALSYMBOLS,ABBREVIATIONS ANDGENERAL NOTES
E001
1 MOUNT EQUIPMENT AT NOMINAL MOUNTING HEIGHT INDICATED ON THE DRAWINGS OR DETAILEDON ARCHITECTURAL ELEVATIONS.
2 INSTALL INSULATED GREEN GROUND CONDUCTOR WITH ALL BRANCH CIRCUIT AND FEEDERCONDUCTORS, SIZE PER NEC TABLE 250.122.
3 ELECTRICAL CONTRACTOR SHALL PROVIDE SLEEVED OPENING WHERE REQUIRED TO RUNCONDUITS AND CABLE SYSTEMS THROUGH SLABS, WALLS, CEILINGS, AND BRIDGING, EXCEPTWHERE OTHERWISE NOTED. SEE ARCHITECTURAL DRAWINGS FOR WALL TYPE AND SPEC SECTION07 84 13 FOR SPECIFIC FIRE STOP METHODS.
4 CONTRACTOR SHALL REFER TO ELECTRICAL SPECIFICATIONS FOR MATERIAL AND EXECUTION OFWORK.
5 CONTRACTOR SHALL VERIFY ALL SIZES AND LOCATIONS OF ALL EXISTING SERVICES AFFECTED BYTHIS PROJECT.
6 ALL HOME RUNS SHALL BE MINIMUM 3/4" EMT.
7 THE CONTRACTOR SHALL REFER TO DRAWINGS AND SPECIFICATIONS OF OTHER SECTIONS FORADDITIONAL/RELATED ELECTRICAL REQUIREMENTS AS LISTED IN THE RESPECTIVE DIVISIONS.
8 ALL WORK SHOWN IS DIAGRAMMATIC IN NATURE AND INTENDED TO ILLUSTRATE GENERAL INTENTONLY. ELECTRICAL CONTRACTOR SHALL PROVIDE ALL ADDITIONAL LABOR, MATERIALS,ACCESSORIES, EQUIPMENT, ETC. REQUIRED TO CREATE A FULLY FUNCTIONAL SYSTEM INACCORDANCE WITH THESE DRAWINGS, APPLICABLE CODES, AND INDUSTRY STANDARDS.
9 ELECTRICAL CONTRACTOR SHALL FULLY COORDINATE WITH ALL OTHER CONTRACTORS TO ENSURECONFLICTS DO NOT ARISE. ALL COORDINATION CONFLICTS BETWEEN CONTRACTORS SHALL BERESOLVED IN A MANNER THAT IS ACCEPTABLE TO OWNER, ARCHITECT, AND ENGINEER, AT NOCOST TO THE PROJECT.
10 ALL ELECTRICAL CONNECTIONS TO OTHER CONTRACTORS' EQUIPMENT SHALL BE FULLYCOORDINATED WITH THE PROVIDING CONTRACTOR PRIOR TO ROUGH-IN. ELECTRICALCONTRACTOR SHALL PROVIDE ALL ADJUSTMENTS NEEDED TO PROVIDE POWER TO EQUIPMENT.ANY ADJUSTMENTS REQUIRED SHALL BE AT NO COST TO THE PROJECT.
GENERAL ELECTRICAL NOTES
FACP
AA
BB
CC
1
1
2
2
3
3
E
1
001
MARSHAL'S OFFICE
002
STORAGE
003
STORAGE (EXISTINGBOILER)
UNEXCAVATED
2
3
4
4
E100BE100A
E100BE100A
KEY PLAN
A
N
ARCHITECTURE
ENGINEERING
INTERIOR DESIGN
MADISON, WI | WAUKESHA, WI
SHEET NAME
PROJECT TITLE
COPYRIGHT STRANG, INC.
DRAWING SET
DATE
PROJECT NO.
SHEET NO.
2021
9/20
/202
1 1:
49:2
3 P
M
09/20/2021
208 JARVIS ST.RIDGEWAY, WI 53582
RIDGEWAYCOMMUNITY CENTERRENOVATIONS
2021046
CD
LOWER LEVELDEMOLITION PLAN -AREA A
E100A
GENERAL DEMOLITION NOTES
# SPECIFIC DEMOLITION NOTES
1 EXISTING TO REMAIN 400AMP MAIN DISCONNECT CURRENTLY POWERED FROMAERIAL 120/240V SINGLE PHASE SERVICE. REMOVE VERTICAL CONDUIT ANDSERVICE CONDUCTORS FROM PANEL TO WEATHERHEAD.
2 REMOVE POWER TO THE BOILER.
3 REMOVE POWER FROM THE AIR COMPRESSOR.
4 REMOVE POWER TO THE UNIT VENTILATOR.
5 REMOVE POWER TO AIR HANDLER AND ASSOCIATED GAS BURNER.
1 NOT ALL EXISTING DEVICES ARE SHOWN.
2 REMOVE ALL DEMOLISHED CONDUIT, DEVICES, LUMINAIRES, ETC. INDICATED.EXISTING TO REMAIN SYSTEMS SHALL BE MAINTAINED IN SERVICE. REMOVE ALLABANDONED HANGERS.
3 WHERE EQUIPMENT, LUMINAIRES, DEVICES, ETC. ARE INDICATED TO BE REMOVED,DISCONNECT AND REMOVE THE BRANCH CIRCUIT BACK TO THE NEXT JUNCTIONPOINT. ALL ABANDONED BRANCH CIRCUITS WILL BE REMOVED BACK TO THE SOURCE.
4 EXISTING CONDUIT, BOXES, LUMINAIRES, CEILING SUPPORT SYSTEMS, ETC. THATMUST BE MODIFIED OR RELOCATED FOR INSTALLATION OF NEW WORK, SYSTEMS,ETC. SHALL BE INCLUDED WITHIN THE SCOPE OF WORK OF THIS PROJECT.
PN
TNSCALE: 1/8" = 1'-0"E100A
1 LOWER LEVEL DEMOLITION PLAN - AREA A
AA
BB
CC
2
2
3
3
4
4
5
5
6
6
004
STORAGE (EXISTINGAIR HANDLER)
UNEXCAVATED
5
E100BE100A
E100BE100A
003
STORAGE (EXISTINGBOILER)
KEY PLAN
B
N
ARCHITECTURE
ENGINEERING
INTERIOR DESIGN
MADISON, WI | WAUKESHA, WI
SHEET NAME
PROJECT TITLE
COPYRIGHT STRANG, INC.
DRAWING SET
DATE
PROJECT NO.
SHEET NO.
2021
9/20
/202
1 1:
49:2
3 P
M
09/20/2021
208 JARVIS ST.RIDGEWAY, WI 53582
RIDGEWAYCOMMUNITY CENTERRENOVATIONS
2021046
CD
LOWER LEVELDEMOLITION PLAN -AREA B
E100B
GENERAL DEMOLITION NOTES
# SPECIFIC DEMOLITION NOTES
1 EXISTING TO REMAIN 400AMP MAIN DISCONNECT CURRENTLY POWERED FROMAERIAL 120/240V SINGLE PHASE SERVICE. REMOVE VERTICAL CONDUIT ANDSERVICE CONDUCTORS FROM PANEL TO WEATHERHEAD.
2 REMOVE POWER TO THE BOILER.
3 REMOVE POWER FROM THE AIR COMPRESSOR.
4 REMOVE POWER TO THE UNIT VENTILATOR.
5 REMOVE POWER TO AIR HANDLER AND ASSOCIATED GAS BURNER.
1 NOT ALL EXISTING DEVICES ARE SHOWN.
2 REMOVE ALL DEMOLISHED CONDUIT, DEVICES, LUMINAIRES, ETC. INDICATED.EXISTING TO REMAIN SYSTEMS SHALL BE MAINTAINED IN SERVICE. REMOVE ALLABANDONED HANGERS.
3 WHERE EQUIPMENT, LUMINAIRES, DEVICES, ETC. ARE INDICATED TO BE REMOVED,DISCONNECT AND REMOVE THE BRANCH CIRCUIT BACK TO THE NEXT JUNCTIONPOINT. ALL ABANDONED BRANCH CIRCUITS WILL BE REMOVED BACK TO THE SOURCE.
4 EXISTING CONDUIT, BOXES, LUMINAIRES, CEILING SUPPORT SYSTEMS, ETC. THATMUST BE MODIFIED OR RELOCATED FOR INSTALLATION OF NEW WORK, SYSTEMS,ETC. SHALL BE INCLUDED WITHIN THE SCOPE OF WORK OF THIS PROJECT.
PN
TNSCALE: 1/8" = 1'-0"E100B
1 LOWER LEVEL DEMOLITION PLAN - AREA B
AA
BB
CC
1
1
2
2
3
3
44
4 4 4
105
KITCHEN
105A
DISHES
190
CORRIDOR
104
COMMUNITY ROOM
103
SENIOR'S ROOM
102B
LIBRARY (STACK)
6
KEY PLAN
A
N
ARCHITECTURE
ENGINEERING
INTERIOR DESIGN
MADISON, WI | WAUKESHA, WI
SHEET NAME
PROJECT TITLE
COPYRIGHT STRANG, INC.
DRAWING SET
DATE
PROJECT NO.
SHEET NO.
2021
9/22
/202
1 11
:45:
19 A
M
09/20/2021
208 JARVIS ST.RIDGEWAY, WI 53582
RIDGEWAYCOMMUNITY CENTERRENOVATIONS
2021046
CD
FIRST FLOORDEMOLITION PLAN -AREA A
E101A
GENERAL DEMOLITION NOTES
# SPECIFIC DEMOLITION NOTES
1 EXISTING TO REMAIN 400AMP MAIN DISCONNECT CURRENTLY POWERED FROMAERIAL 120/240V SINGLE PHASE SERVICE. REMOVE VERTICAL CONDUIT ANDSERVICE CONDUCTORS FROM PANEL TO WEATHERHEAD.
2 REMOVE POWER TO THE BOILER.
3 REMOVE POWER FROM THE AIR COMPRESSOR.
4 REMOVE POWER TO THE UNIT VENTILATOR.
5 REMOVE POWER TO AIR HANDLER AND ASSOCIATED GAS BURNER.
6 REMOVE FLOOR MOUNTED RECEPTACLE. CUT CONDUIT FLUSH WITH FLOOR,REMOVE CONDUCTORS AND MARK CIRCUIT BREAKER AS SPARE.
1 NOT ALL EXISTING DEVICES ARE SHOWN.
2 REMOVE ALL DEMOLISHED CONDUIT, DEVICES, LUMINAIRES, ETC. INDICATED.EXISTING TO REMAIN SYSTEMS SHALL BE MAINTAINED IN SERVICE. REMOVE ALLABANDONED HANGERS.
3 WHERE EQUIPMENT, LUMINAIRES, DEVICES, ETC. ARE INDICATED TO BE REMOVED,DISCONNECT AND REMOVE THE BRANCH CIRCUIT BACK TO THE NEXT JUNCTIONPOINT. ALL ABANDONED BRANCH CIRCUITS WILL BE REMOVED BACK TO THE SOURCE.
4 EXISTING CONDUIT, BOXES, LUMINAIRES, CEILING SUPPORT SYSTEMS, ETC. THATMUST BE MODIFIED OR RELOCATED FOR INSTALLATION OF NEW WORK, SYSTEMS,ETC. SHALL BE INCLUDED WITHIN THE SCOPE OF WORK OF THIS PROJECT.
PN
TNSCALE: 1/8" = 1'-0"E101A
1 FIRST FLOOR DEMOLITION PLAN - AREA A
LVDLV
2
DH
DH DH
LV2
LVDLV
2LV
D
LV2 LV
D
LV2
L1L1
L1L1L1
L1
L1
L1
L1L1L1
AA
BB
CC
1
1
2
2
3
3
103
SENIOR'S ROOM102B
LIBRARY (STACK)
104
COMMUNITY ROOM
105
KITCHEN
105A
DISHES
190
CORRIDOR
A, b
A, b
A, c
A, a A, a A, b
A, b
A, c
A, b
A, b
A, c
A, b
A, b
A, c
A, b
A, b
A, c
A, a
A, a
A, c
A, a
A, a
A, c
A, a
A, a
A, c
A, a
A, a
A, c
A, a
A, a A, a A, a
A, a
A, a
A, bA, b A, b A, b
A, b
A, b
A, c
A, a
A, a
A, c
A, a
A, a
A, c
A, a
A, a
A, c
A, a
A, a
A, c
c
b c
111C
STORAGE
?
?
103A
CLOSETS
103B
TOILET
104A
CLOSETS
a,b,c
a,b,c
a,b,c
a,b a,b
a,b,c a,b,c a,b,c
a,b,ca,b,ca,b,c
ab,cab,c
a,b ab,c ab,c
ON/OFF
ON/OFF
ON/OFF
LV2 LVD
KEY PLAN
A
N
ARCHITECTURE
ENGINEERING
INTERIOR DESIGN
MADISON, WI | WAUKESHA, WI
SHEET NAME
PROJECT TITLE
COPYRIGHT STRANG, INC.
DRAWING SET
DATE
PROJECT NO.
SHEET NO.
2021
9/20
/202
1 1:
49:2
6 P
M
09/20/2021
208 JARVIS ST.RIDGEWAY, WI 53582
RIDGEWAYCOMMUNITY CENTERRENOVATIONS
2021046
CD
FIRST FLOORLIGHTING PLAN -AREA A
E201A
1 SEE SPECIFICATIONS FOR ALL LIGHTING CONTROL SEQUENCES OF OPERATIONS.
2 COORDINATE FINAL LOCATIONS OF DEVICES, LUMINAIRES, ETC WITHARCHITECTURAL CEILING PLANS.
3 CONNECT NORMAL BRANCH LIGHTING CIRCUITS TO EXISTING LIGHTING BRANCHCIRCUITS.
4 ROOMS AND COMMON CORRIDORS WITH MULTIPLE OCCUPANCY SENSORS SHALLBE INTERCONNECTED TO ENERGIZE ALL LUMINAIRES SERVING AREA TOGETHER.
5 LUMINAIRE SCHEDULE LOCATED ON SHEET E901.
GENERAL LIGHTING NOTES
PN
TNSCALE: 1/8" = 1'-0"E201A
1 FIRST FLOOR LIGHTING PLAN - AREA A
SCALE: NTSE201A
2 LIGHTING CONTROL SYSTEM BUTTON LAYOUTS
FACP
AA
BB
CC
1
1
2
2
3
3
2
E300A
003
STORAGE (EXISTINGBOILER)
002
STORAGE
001
MARSHAL'S OFFICE
UNEXCAVATED
E
2.2
2.2
ACCU-1A-12,14
FCU-1
FCU-2
ACCU-2A-7,9
EWH-1A-8,10
2.6
WP,GFI2.3
WP,GFI
2.3
2.1 2.92.7
2.4
T
2.10
2.11
EBB-1AMDP-8
EBB-1BMDP-9
2.12
BASEMENT89' - 3"
FIRST FLOOR100' - 0"
SECOND FLOOR112' - 6"
1
2.7 2.9 2.1 2.11
KEY PLAN
A
N
ARCHITECTURE
ENGINEERING
INTERIOR DESIGN
MADISON, WI | WAUKESHA, WI
SHEET NAME
PROJECT TITLE
COPYRIGHT STRANG, INC.
DRAWING SET
DATE
PROJECT NO.
SHEET NO.
2021
9/20
/202
1 1:
49:2
7 P
M
09/20/2021
208 JARVIS ST.RIDGEWAY, WI 53582
RIDGEWAYCOMMUNITY CENTERRENOVATIONS
2021046
CD
LOWER LEVEL POWERPLAN - AREA A
E300A
GENERAL POWER NOTES
# SPECIFIC POWER NOTES
1 BRANCH CIRCUIT NUMBER SEQUENTIAL ORDER IS FOR BOOKKEEPING PURPOSESONLY AND MAY NOT REFLECT ACTUAL CIRCUIT BREAKER NUMBER SEQUENCE IN THEPANELBOARD. NUMBERS INDICATE WHICH DEVICES ARE CONNECTED TO A COMMONBRANCH CIRCUIT.
2 SEE MECHANICAL SHEETS FOR ADDITIONAL INFORMATION RELATED TO ELECTRICAL.
3 REFER TO SPECIFICATION SECTION 07 84 00 PENETRATION FIRE STOPPING FOR ALLFLOOR AND WALL PENETRATIONS THROUGH RATED WALLS. REFER TO THEARCHITECTURAL LIFE SAFETY PLAN SHEETS FOR FLOOR AND WALL RATINGS.
2.1 CT METER CABINET. ROUTE CONDUITS TO MDP INSIDE BUILDING,
2.2 INDOOR FAN COIL UNIT POWERED BY ASSOCIATED OUTDOOR UNIT. REFER TOMECHANICAL PLANS FOR ADDITIONAL INFORMATION.
2.3 CONNECT RECEPTACLE TO NEAREST CONVENIENCE RECEPTACLE CIRCUIT WITHCAPACITY.
2.4 UTILITY PAD MOUNTED SERVICE TRANSFORMER. ENSURE THAT THETRANSFORMER IS AT LEAST 5 FEET FROM THE ORIGINAL WINDOW SILL ON THESECOND FLOOR (AS MEASURED DIAGONALLY) PER PSC 114 REQUIREMENTS.
2.5 APPROXIMATE LOCATION OF EXISTING AERIAL SERVICE DROP ON ROOF. REFER TODEMO PLANS FOR ADDITIONAL REQUIREMENTS.
2.6 REPOWER EXISTING 400A SINGLE PHASE DISCONNECT FROM PANEL MDP.
2.7 FUTURE TENANT MULTIPLE METER CENTER.
2.8 PRE-WIRED INTEGRAL RECEPTACLE INSIDE RTU.
2.9 ELECTRICAL SERVICE TERMINATION CABINET.
2.10 ELECTRICAL CONTRACTOR TO PROVIDE TRENCH, CONDUIT FROM TRANSFORMERTO TERMINATION CABINET, AND SITE RESTORATION.
2.11 PROVIDE METER SOCKET AND 1" CONDUIT TO METER CABINET IN ACCORDANCEWITH ALLIANT ENERGY SERVICE RULES.
2.12 CONDUITS TO PANEL MDP IN INTERIOR OF BUILDING. MAXIMUM LENGTH OFCONDUCTORS INSIDE BUILDING 8 FEET PER WISCONSIN ELECTRICAL CODE.
PN
TNSCALE: 1/8" = 1'-0"E300A
1 LOWER LEVEL POWER PLAN - AREA ASCALE: 1/8" = 1'-0"E300A
2 EXTERIOR ELEVATION
AA
BB
CC
1
1
2
2
3
3
103
SENIOR'S ROOM
102B
LIBRARY (STACK)
190
CORRIDOR
104
COMMUNITY ROOM
105
KITCHEN
105A
DISHES
190
CORRIDOR
MDP
104A
CLOSETS
103A
CLOSETS
103B
TOILET
111C
STORAGE
111B
OFFICE
102A
LIBRARY (READING)
E301BE301A
E301BE301A
SPDMDP-7
KEY PLAN
A
N
ARCHITECTURE
ENGINEERING
INTERIOR DESIGN
MADISON, WI | WAUKESHA, WI
SHEET NAME
PROJECT TITLE
COPYRIGHT STRANG, INC.
DRAWING SET
DATE
PROJECT NO.
SHEET NO.
2021
9/20
/202
1 1:
49:2
8 P
M
09/20/2021
208 JARVIS ST.RIDGEWAY, WI 53582
RIDGEWAYCOMMUNITY CENTERRENOVATIONS
2021046
CD
FIRST FLOOR POWERPLAN - AREA A
E301A
GENERAL POWER NOTES
# SPECIFIC POWER NOTES
1 BRANCH CIRCUIT NUMBER SEQUENTIAL ORDER IS FOR BOOKKEEPING PURPOSESONLY AND MAY NOT REFLECT ACTUAL CIRCUIT BREAKER NUMBER SEQUENCE IN THEPANELBOARD. NUMBERS INDICATE WHICH DEVICES ARE CONNECTED TO A COMMONBRANCH CIRCUIT.
2 SEE MECHANICAL SHEETS FOR ADDITIONAL INFORMATION RELATED TO ELECTRICAL.
3 REFER TO SPECIFICATION SECTION 07 84 00 PENETRATION FIRE STOPPING FOR ALLFLOOR AND WALL PENETRATIONS THROUGH RATED WALLS. REFER TO THEARCHITECTURAL LIFE SAFETY PLAN SHEETS FOR FLOOR AND WALL RATINGS.
2.1 CT METER CABINET. ROUTE CONDUITS TO MDP INSIDE BUILDING,
2.2 INDOOR FAN COIL UNIT POWERED BY ASSOCIATED OUTDOOR UNIT. REFER TOMECHANICAL PLANS FOR ADDITIONAL INFORMATION.
2.3 CONNECT RECEPTACLE TO NEAREST CONVENIENCE RECEPTACLE CIRCUIT WITHCAPACITY.
2.4 UTILITY PAD MOUNTED SERVICE TRANSFORMER. ENSURE THAT THETRANSFORMER IS AT LEAST 5 FEET FROM THE ORIGINAL WINDOW SILL ON THESECOND FLOOR (AS MEASURED DIAGONALLY) PER PSC 114 REQUIREMENTS.
2.5 APPROXIMATE LOCATION OF EXISTING AERIAL SERVICE DROP ON ROOF. REFER TODEMO PLANS FOR ADDITIONAL REQUIREMENTS.
2.6 REPOWER EXISTING 400A SINGLE PHASE DISCONNECT FROM PANEL MDP.
2.7 FUTURE TENANT MULTIPLE METER CENTER.
2.8 PRE-WIRED INTEGRAL RECEPTACLE INSIDE RTU.
2.9 ELECTRICAL SERVICE TERMINATION CABINET.
2.10 ELECTRICAL CONTRACTOR TO PROVIDE TRENCH, CONDUIT FROM TRANSFORMERTO TERMINATION CABINET, AND SITE RESTORATION.
2.11 PROVIDE METER SOCKET AND 1" CONDUIT TO METER CABINET IN ACCORDANCEWITH ALLIANT ENERGY SERVICE RULES.
2.12 CONDUITS TO PANEL MDP IN INTERIOR OF BUILDING. MAXIMUM LENGTH OFCONDUCTORS INSIDE BUILDING 8 FEET PER WISCONSIN ELECTRICAL CODE.
PN
TNSCALE: 1/8" = 1'-0"E301A
1 FIRST FLOOR POWER PLAN - AREA A
E301BE301A
AA
BB
CC
DD
2
2
3
3
4
4
5
5
6
6
190
CORRIDOR
111C
STORAGE
111D
SHOWER
111A
MENS
111
STORAGE
111B
OFFICE
101
OFFICE
116
CONFERENCE
115
CONFERENCE
112
GYMNASIUM
113B
WOMENS
113A
JANITOR
113C
STORAGE
114
ENTRY
FCU-3
2.2
FCU-4
2.2
FCU-5
2.2
FCU-6
2.2
EWH-2A-32,34
113
STORAGE
EWH-3A-27,29
EWH-4A-31,33
E301BE301A
E301BE301A
KEY PLAN
B
N
ARCHITECTURE
ENGINEERING
INTERIOR DESIGN
MADISON, WI | WAUKESHA, WI
SHEET NAME
PROJECT TITLE
COPYRIGHT STRANG, INC.
DRAWING SET
DATE
PROJECT NO.
SHEET NO.
2021
9/20
/202
1 1:
49:2
9 P
M
09/20/2021
208 JARVIS ST.RIDGEWAY, WI 53582
RIDGEWAYCOMMUNITY CENTERRENOVATIONS
2021046
CD
FIRST FLOOR POWERPLAN - AREA B
E301B
GENERAL POWER NOTES
# SPECIFIC POWER NOTES
1 BRANCH CIRCUIT NUMBER SEQUENTIAL ORDER IS FOR BOOKKEEPING PURPOSESONLY AND MAY NOT REFLECT ACTUAL CIRCUIT BREAKER NUMBER SEQUENCE IN THEPANELBOARD. NUMBERS INDICATE WHICH DEVICES ARE CONNECTED TO A COMMONBRANCH CIRCUIT.
2 SEE MECHANICAL SHEETS FOR ADDITIONAL INFORMATION RELATED TO ELECTRICAL.
3 REFER TO SPECIFICATION SECTION 07 84 00 PENETRATION FIRE STOPPING FOR ALLFLOOR AND WALL PENETRATIONS THROUGH RATED WALLS. REFER TO THEARCHITECTURAL LIFE SAFETY PLAN SHEETS FOR FLOOR AND WALL RATINGS.
2.1 CT METER CABINET. ROUTE CONDUITS TO MDP INSIDE BUILDING,
2.2 INDOOR FAN COIL UNIT POWERED BY ASSOCIATED OUTDOOR UNIT. REFER TOMECHANICAL PLANS FOR ADDITIONAL INFORMATION.
2.3 CONNECT RECEPTACLE TO NEAREST CONVENIENCE RECEPTACLE CIRCUIT WITHCAPACITY.
2.4 UTILITY PAD MOUNTED SERVICE TRANSFORMER. ENSURE THAT THETRANSFORMER IS AT LEAST 5 FEET FROM THE ORIGINAL WINDOW SILL ON THESECOND FLOOR (AS MEASURED DIAGONALLY) PER PSC 114 REQUIREMENTS.
2.5 APPROXIMATE LOCATION OF EXISTING AERIAL SERVICE DROP ON ROOF. REFER TODEMO PLANS FOR ADDITIONAL REQUIREMENTS.
2.6 REPOWER EXISTING 400A SINGLE PHASE DISCONNECT FROM PANEL MDP.
2.7 FUTURE TENANT MULTIPLE METER CENTER.
2.8 PRE-WIRED INTEGRAL RECEPTACLE INSIDE RTU.
2.9 ELECTRICAL SERVICE TERMINATION CABINET.
2.10 ELECTRICAL CONTRACTOR TO PROVIDE TRENCH, CONDUIT FROM TRANSFORMERTO TERMINATION CABINET, AND SITE RESTORATION.
2.11 PROVIDE METER SOCKET AND 1" CONDUIT TO METER CABINET IN ACCORDANCEWITH ALLIANT ENERGY SERVICE RULES.
2.12 CONDUITS TO PANEL MDP IN INTERIOR OF BUILDING. MAXIMUM LENGTH OFCONDUCTORS INSIDE BUILDING 8 FEET PER WISCONSIN ELECTRICAL CODE.
PN
TNSCALE: 1/8" = 1'-0"E301B
1 FIRST FLOOR POWER PLAN - AREA B
AA
BB
CC
1
1
2
2
RTU-1MDP-5
RTU-3MDP-4
RTU-2MDP-6
RTU-5A-1,3,5
RTU-4A-2,4,6
2.5
2.8
2.8 2.8
2.8
2.8
A
209
CLOSET
WP,GFIWP,GFI
WP,GFIWP,GFI
E302BE302A
E302BE302A
WP,GFI
KEY PLAN
A
N
ARCHITECTURE
ENGINEERING
INTERIOR DESIGN
MADISON, WI | WAUKESHA, WI
SHEET NAME
PROJECT TITLE
COPYRIGHT STRANG, INC.
DRAWING SET
DATE
PROJECT NO.
SHEET NO.
2021
9/20
/202
1 1:
49:3
0 P
M
09/20/2021
208 JARVIS ST.RIDGEWAY, WI 53582
RIDGEWAYCOMMUNITY CENTERRENOVATIONS
2021046
CD
ROOF POWER PLAN -AREA A
E302A
GENERAL POWER NOTES
# SPECIFIC POWER NOTES
1 BRANCH CIRCUIT NUMBER SEQUENTIAL ORDER IS FOR BOOKKEEPING PURPOSESONLY AND MAY NOT REFLECT ACTUAL CIRCUIT BREAKER NUMBER SEQUENCE IN THEPANELBOARD. NUMBERS INDICATE WHICH DEVICES ARE CONNECTED TO A COMMONBRANCH CIRCUIT.
2 SEE MECHANICAL SHEETS FOR ADDITIONAL INFORMATION RELATED TO ELECTRICAL.
3 REFER TO SPECIFICATION SECTION 07 84 00 PENETRATION FIRE STOPPING FOR ALLFLOOR AND WALL PENETRATIONS THROUGH RATED WALLS. REFER TO THEARCHITECTURAL LIFE SAFETY PLAN SHEETS FOR FLOOR AND WALL RATINGS.
2.1 CT METER CABINET. ROUTE CONDUITS TO MDP INSIDE BUILDING,
2.2 INDOOR FAN COIL UNIT POWERED BY ASSOCIATED OUTDOOR UNIT. REFER TOMECHANICAL PLANS FOR ADDITIONAL INFORMATION.
2.3 CONNECT RECEPTACLE TO NEAREST CONVENIENCE RECEPTACLE CIRCUIT WITHCAPACITY.
2.4 UTILITY PAD MOUNTED SERVICE TRANSFORMER. ENSURE THAT THETRANSFORMER IS AT LEAST 5 FEET FROM THE ORIGINAL WINDOW SILL ON THESECOND FLOOR (AS MEASURED DIAGONALLY) PER PSC 114 REQUIREMENTS.
2.5 APPROXIMATE LOCATION OF EXISTING AERIAL SERVICE DROP ON ROOF. REFER TODEMO PLANS FOR ADDITIONAL REQUIREMENTS.
2.6 REPOWER EXISTING 400A SINGLE PHASE DISCONNECT FROM PANEL MDP.
2.7 FUTURE TENANT MULTIPLE METER CENTER.
2.8 PRE-WIRED INTEGRAL RECEPTACLE INSIDE RTU.
2.9 ELECTRICAL SERVICE TERMINATION CABINET.
2.10 ELECTRICAL CONTRACTOR TO PROVIDE TRENCH, CONDUIT FROM TRANSFORMERTO TERMINATION CABINET, AND SITE RESTORATION.
2.11 PROVIDE METER SOCKET AND 1" CONDUIT TO METER CABINET IN ACCORDANCEWITH ALLIANT ENERGY SERVICE RULES.
2.12 CONDUITS TO PANEL MDP IN INTERIOR OF BUILDING. MAXIMUM LENGTH OFCONDUCTORS INSIDE BUILDING 8 FEET PER WISCONSIN ELECTRICAL CODE.
PN
TNSCALE: 1/8" = 1'-0"E302A
1 ROOF POWER PLAN - AREA A
AA
BB
CC
DD
2
2
3
3
4
4
5
5
6
6
2.5
209
CLOSET
201
OFFICE
208
MENS
202
OFFICE
112
GYMNASIUM
201
OFFICE
206
WOMENS
207
JAN.
205
OFFICE
204
OFFICE
290
CORRIDOR
203
STORAGE
A
FCU-7
2.2
FCU-8
2.2
FCU-9
2.2
FCU-10
2.2
E302BE302A
E302BE302A
EWH-5A-35,37
EWH-6A-39,41
KEY PLAN
B
N
ARCHITECTURE
ENGINEERING
INTERIOR DESIGN
MADISON, WI | WAUKESHA, WI
SHEET NAME
PROJECT TITLE
COPYRIGHT STRANG, INC.
DRAWING SET
DATE
PROJECT NO.
SHEET NO.
2021
9/20
/202
1 1:
49:3
0 P
M
09/20/2021
208 JARVIS ST.RIDGEWAY, WI 53582
RIDGEWAYCOMMUNITY CENTERRENOVATIONS
2021046
CD
SECOND FLOORPOWER PLAN - AREA B
E302B
GENERAL POWER NOTES
# SPECIFIC POWER NOTES
1 BRANCH CIRCUIT NUMBER SEQUENTIAL ORDER IS FOR BOOKKEEPING PURPOSESONLY AND MAY NOT REFLECT ACTUAL CIRCUIT BREAKER NUMBER SEQUENCE IN THEPANELBOARD. NUMBERS INDICATE WHICH DEVICES ARE CONNECTED TO A COMMONBRANCH CIRCUIT.
2 SEE MECHANICAL SHEETS FOR ADDITIONAL INFORMATION RELATED TO ELECTRICAL.
3 REFER TO SPECIFICATION SECTION 07 84 00 PENETRATION FIRE STOPPING FOR ALLFLOOR AND WALL PENETRATIONS THROUGH RATED WALLS. REFER TO THEARCHITECTURAL LIFE SAFETY PLAN SHEETS FOR FLOOR AND WALL RATINGS.
2.1 CT METER CABINET. ROUTE CONDUITS TO MDP INSIDE BUILDING,
2.2 INDOOR FAN COIL UNIT POWERED BY ASSOCIATED OUTDOOR UNIT. REFER TOMECHANICAL PLANS FOR ADDITIONAL INFORMATION.
2.3 CONNECT RECEPTACLE TO NEAREST CONVENIENCE RECEPTACLE CIRCUIT WITHCAPACITY.
2.4 UTILITY PAD MOUNTED SERVICE TRANSFORMER. ENSURE THAT THETRANSFORMER IS AT LEAST 5 FEET FROM THE ORIGINAL WINDOW SILL ON THESECOND FLOOR (AS MEASURED DIAGONALLY) PER PSC 114 REQUIREMENTS.
2.5 APPROXIMATE LOCATION OF EXISTING AERIAL SERVICE DROP ON ROOF. REFER TODEMO PLANS FOR ADDITIONAL REQUIREMENTS.
2.6 REPOWER EXISTING 400A SINGLE PHASE DISCONNECT FROM PANEL MDP.
2.7 FUTURE TENANT MULTIPLE METER CENTER.
2.8 PRE-WIRED INTEGRAL RECEPTACLE INSIDE RTU.
2.9 ELECTRICAL SERVICE TERMINATION CABINET.
2.10 ELECTRICAL CONTRACTOR TO PROVIDE TRENCH, CONDUIT FROM TRANSFORMERTO TERMINATION CABINET, AND SITE RESTORATION.
2.11 PROVIDE METER SOCKET AND 1" CONDUIT TO METER CABINET IN ACCORDANCEWITH ALLIANT ENERGY SERVICE RULES.
2.12 CONDUITS TO PANEL MDP IN INTERIOR OF BUILDING. MAXIMUM LENGTH OFCONDUCTORS INSIDE BUILDING 8 FEET PER WISCONSIN ELECTRICAL CODE.
PN
TNSCALE: 1/8" = 1'-0"E302B
1 SECOND FLOOR POWER PLAN - AREA B
BB
CC
DD
2
2
3
3
4
4
5
5
6
6
RTU-6MDP-3
WP,GFI
ACCU-3A-16,18
ACCU-7A-11,13
ACCU-4A-20,22
ACCU-5A-15,17
ACCU-8A-24,26
ACCU-6A-19,21
ACCU-9A-28,30
ACCU-10A-23,25
2.8
WP,GFI WP,GFI2.3 2.3
KEY PLAN
B
N
ARCHITECTURE
ENGINEERING
INTERIOR DESIGN
MADISON, WI | WAUKESHA, WI
SHEET NAME
PROJECT TITLE
COPYRIGHT STRANG, INC.
DRAWING SET
DATE
PROJECT NO.
SHEET NO.
2021
9/20
/202
1 1:
49:3
1 P
M
09/20/2021
208 JARVIS ST.RIDGEWAY, WI 53582
RIDGEWAYCOMMUNITY CENTERRENOVATIONS
2021046
CD
ROOF POWER PLAN -AREA B
E303B
GENERAL POWER NOTES
# SPECIFIC POWER NOTES
1 BRANCH CIRCUIT NUMBER SEQUENTIAL ORDER IS FOR BOOKKEEPING PURPOSESONLY AND MAY NOT REFLECT ACTUAL CIRCUIT BREAKER NUMBER SEQUENCE IN THEPANELBOARD. NUMBERS INDICATE WHICH DEVICES ARE CONNECTED TO A COMMONBRANCH CIRCUIT.
2 SEE MECHANICAL SHEETS FOR ADDITIONAL INFORMATION RELATED TO ELECTRICAL.
3 REFER TO SPECIFICATION SECTION 07 84 00 PENETRATION FIRE STOPPING FOR ALLFLOOR AND WALL PENETRATIONS THROUGH RATED WALLS. REFER TO THEARCHITECTURAL LIFE SAFETY PLAN SHEETS FOR FLOOR AND WALL RATINGS.
2.1 CT METER CABINET. ROUTE CONDUITS TO MDP INSIDE BUILDING,
2.2 INDOOR FAN COIL UNIT POWERED BY ASSOCIATED OUTDOOR UNIT. REFER TOMECHANICAL PLANS FOR ADDITIONAL INFORMATION.
2.3 CONNECT RECEPTACLE TO NEAREST CONVENIENCE RECEPTACLE CIRCUIT WITHCAPACITY.
2.4 UTILITY PAD MOUNTED SERVICE TRANSFORMER. ENSURE THAT THETRANSFORMER IS AT LEAST 5 FEET FROM THE ORIGINAL WINDOW SILL ON THESECOND FLOOR (AS MEASURED DIAGONALLY) PER PSC 114 REQUIREMENTS.
2.5 APPROXIMATE LOCATION OF EXISTING AERIAL SERVICE DROP ON ROOF. REFER TODEMO PLANS FOR ADDITIONAL REQUIREMENTS.
2.6 REPOWER EXISTING 400A SINGLE PHASE DISCONNECT FROM PANEL MDP.
2.7 FUTURE TENANT MULTIPLE METER CENTER.
2.8 PRE-WIRED INTEGRAL RECEPTACLE INSIDE RTU.
2.9 ELECTRICAL SERVICE TERMINATION CABINET.
2.10 ELECTRICAL CONTRACTOR TO PROVIDE TRENCH, CONDUIT FROM TRANSFORMERTO TERMINATION CABINET, AND SITE RESTORATION.
2.11 PROVIDE METER SOCKET AND 1" CONDUIT TO METER CABINET IN ACCORDANCEWITH ALLIANT ENERGY SERVICE RULES.
2.12 CONDUITS TO PANEL MDP IN INTERIOR OF BUILDING. MAXIMUM LENGTH OFCONDUCTORS INSIDE BUILDING 8 FEET PER WISCONSIN ELECTRICAL CODE.
PN
TNSCALE: 1/8" = 1'-0"E303B
1 ROOF POWER PLAN - AREA B
SD
CM
RI
AA
BB
CC
DD
2
2
3
3
4
4
5
5
6
6
RTU-6
112
GYMNASIUM
RTU-6
3.1
3.1
102A
LIBRARY (READING)
190
CORRIDOR
111C
STORAGE
111B
OFFICE
111
STORAGE
111D
SHOWER
111A
MENS
101
OFFICE
116
CONFERENCE
115
CONFERENCE
113B
WOMENS
113A
JANITOR
113C
STORAGE
114
ENTRY
KEY PLAN
B
N
ARCHITECTURE
ENGINEERING
INTERIOR DESIGN
MADISON, WI | WAUKESHA, WI
SHEET NAME
PROJECT TITLE
COPYRIGHT STRANG, INC.
DRAWING SET
DATE
PROJECT NO.
SHEET NO.
2021
9/20
/202
1 1:
49:3
2 P
M
09/20/2021
208 JARVIS ST.RIDGEWAY, WI 53582
RIDGEWAYCOMMUNITY CENTERRENOVATIONS
2021046
CD
FIRST FLOORSYSTEMS PLAN -AREA B
E401
GENERAL SYSTEMS NOTES
# SPECIFIC SYSTEMS NOTES
1 ALL FIRE ALARM NOTIFICATION, DETECTION AND SIGNALING DEVICES SHALL MEETALL APPLICABLE CODES AND MANUFACTURER'S LISTING RECOMMENDATIONS.
2 DEVICE LOCATIONS ARE SHOWN TO INDICATE DESIGN INTENT ONLY.
3 INSTALL ALL FIRE ALARM CABLE IN CONDUIT.
4 REFER TO SPECIFICATION SECTION 07 84 00 PENETRATION FIRE STOPPING FOR ALLFLOOR AND WALL PENETRATIONS THROUGH RATED WALLS. REFER TO THEARCHITECTURAL LIFE SAFETY PLAN SHEETS FOR FLOOR AND WALL RATINGS.
5 EXISTING FIRE ALARM DEVICES NOT SHOWN.
3.1 CONNECT NEW FIRE ALARM DEVICES TO EXISTING FIRE ALARM PANEL LOCATED INAREA A LOWER LEVEL.
PN
TNSCALE: 1/8" = 1'-0"E401
1 FIRST FLOOR SYSTEMS PLAN - AREA B
2030405060708090100110125150175200225250300350400450500600700800
100012001600200025003000
FEEDER AMPACITY
*
Ø
CONDUCTOR SIZE (kcmil)
N GND
PARALLEL SETS
CONDUIT SIZE
111111111111111111222223345678
3G,4G
3#123#103#83#63#43#43#33#23#13#13#1
3#1/03#2/03#3/03#4/03#2503#3503#5003#3/03#4/03#2503#3503#5003#3003#4003#3503#4003#4003#5003#500
3G,4G
1#121#101#81#61#41#41#31#21#11#11#1
1#1/01#2/01#3/01#4/01#2501#3501#/5001#3/01#4/01#2501#3501#5001#3001#4001#3501#4001#4001#5001#500
4G
1#121#101#101#101#101#81#81#81#81#61#61#61#61#61#41#41#41#31#31#21#21#1
1#1/01#1/01#2/01#3/01#4/01#2501#3501#400
3G,4G 3G 4G3/4"3/4"3/4"1"1"
1 1/4"1 1/4"1 1/4"1 1/2"1 1/2"1 1/2"1 1/2"
2"2"2"
2 1/2"2 1/2"
3"2"2"
2 1/2"3"3"
2 1/2"3"3"3"3"
3 1/2"3 1/2"
3/4"3/4"1"1"
1 1/4"1 1/4"1 1/4"1 1/2"1 1/2"1 1/2"1 1/2"
2"2"
2 1/2"2 1/2"2 1/2"
3"3 1/2"2 1/2" 2 1/2"
3"3"
3 1/2"3"3"3"
3 1/2"3 1/2"3 1/2"3 1/2"
FEEDER SCHEDULE
********
1. NOT ALL FEEDER AMPACITY OR WIRING CONFIGURATION MAY BE UTILIZED.2. CONDUCTOR AMPACITIES PER NEC TABLE 310-15(B)(16), CU, XHHW-2. FEEDER AMPACITY NOTED WITH (*) ARE BASED ON 60ºC PER NEC 110.14(C).3. CONDUIT SIZES ARE PER NEC CHAPTER 9 TABLES, 40% FILL OF SCHEDULE 80 PVC.4. CONDUCTOR AND CONDUIT SIZES SHOWN ARE MINIMUM SIZES. FEEDERS ARE NOT DERATED PER NEC ART.310, AND MAY NOT CORRESPOND TO OCPD AMPACITIES SHOWN ON THE ONE-LINE OR RISER DIAGRAM.5. CONTRACTOR SHALL DERATE EACH FEEDER'S AMPACITY FOR VOLTAGE DROP AND AMBIENT TEMPERATURE. INCREASE THE CONDUCTOR AND RACEWAY SIZES PER THE NEC AND SPECIFICATIONS. SUBMIT CALCULATIONS AND REVISED SIZES TO THE ARCHITECT/ENGINEER.6. PARALLEL SETS: EACH CONDUIT SHALL HAVE CONDUCTOR GROUPINGS OF A-B-C PHASE CONDUCTORS, GROUNDING CONDUCTOR(S), AND OR NEUTRAL CONDUCTOR(S).
PANEL
MDP
208Y/120V
800A
208Y/120V, 3-PHASEPAD MOUNTEDUTILITY TRANSFORMER
800-
4G
T
SPD
EXTERIOR NEMA 3R METER CABINET
30-4G
M
2[(2
#3/
0, 1
#3/
0N, 1
#3G
) 2"
C]
PANEL A
208Y/120V
225A
225-
4G
1
NOTE:PROVIDE ALL EQUIPMENT IN ACCORDANCE WITH UTILITY REQUIREMENTS.
PANEL E
208/120V
1 PHASE
400A
208/120V400A-2P
400A
4
EXTERIOR NEMA 3R TERMINATION CABINET SIZED
TO ACCOMODATE NEW SERVICE AND FUTURE TAPS
TO POWER A TENANTMULTI-METER CENTER
5
5
6
7
240/120V, 1-PHASE POLE MOUNTEDUTILITY TRANSFORMER
T
PANEL E
240/120V
1 PHASE
400A
2
3
240/120V400A
M
ARCHITECTURE
ENGINEERING
INTERIOR DESIGN
MADISON, WI | WAUKESHA, WI
SHEET NAME
PROJECT TITLE
COPYRIGHT STRANG, INC.
DRAWING SET
DATE
PROJECT NO.
SHEET NO.
2021
9/20
/202
1 1:
49:3
3 P
M
09/20/2021
208 JARVIS ST.RIDGEWAY, WI 53582
RIDGEWAYCOMMUNITY CENTERRENOVATIONS
2021046
CD
ELECTRICAL ONE-LINEDIAGRAMS
E701
1 COMPLY WITH ALL ALLIANT ENERGY SERVICE RULES.
2 REFER TO EQUIPMENT SCHEDULES FOR SPECIFIC ELECTRICAL EQUIPMENTREQUIREMENTS.
3 SIZE OF GROUNDING ELECTRODE CONDUCTOR PER N.E.C. TABLE 250.86.
4 THE GROUNDING ELECTRODE CONDUCTOR SHALL BE UNSPLICED AND INSTALLEDIN NON-METALLIC (PVC SCHEDULE 40) CONDUIT TO PROTECT IT FROM DAMAGE.
1 PROVIDE METER BASE IN ACCORDANCE WITH ALLIANT ENERGY RULES.
2 REMOVE MAIN BONDING JUMPER.
3 REMOVE GROUNDING ELECTRODE CONDUCTOR.
4 PROVIDE NEW NAME PLATE FOR PANEL E INDICATING NEW VOLTAGE 208/120V.
5 SUBMIT PROPOSED EQUIPMENT TO ALLIANT ENERGY FOR APPROVAL PRIOR TOORDERING.
6 PROVIDE THREE 4" CONDUITS WITH PULL CORD. ALLIANT ENERGY WILL PROVIDETHE SERVICE CONDUCTORS.
7 PROVIDE PAD FOR SERVICE TRANSFORMER IN ACCORDANCE WITH ALLIANTENERGY RULES.
GENERAL ONE-LINE NOTES
# SPECIFIC ONE-LINE NOTES
SCALE: NONEE701
1 PARTIAL ONE-LINE DIAGRAMSCALE: NONEE701
2 PARTIAL DEMOLITION ONE-LINE DIAGRAM
ARCHITECTUREENGINEERINGINTERIOR DESIGN
MADISON, WI | WAUKESHA, WI
SHEET NAME
PROJECT TITLE
COPYRIGHT STRANG, INC.
DRAWING SET
DATE
PROJECT NO.
SHEET NO.
2021
9/20
/202
1 1:
49:3
5 P
M
09/20/2021
208 JARVIS ST.RIDGEWAY, WI 53582
RIDGEWAYCOMMUNITY CENTERRENOVATIONS
2021046
CD
ELECTRICALSCHEDULES
E901
SERVICE ENTRANCE RATED
Notes:
Total Adj. Demand Current: 533 A
Total Conn. Current: 521 A
HVAC Heating 23000 VA 100.00% 23000 VA Total Adj. Demand: 191918 VA
Other 70000 VA 100.00% 70000 VA Total Conn. Load: 187865 VA
Motor 94865 VA 104.27% 98918 VA
Load Classification Connected Load Demand Factor Adjusted Demand Switchboard Totals
GFI - GFCI BREAKER AFCI - AFCI BREAKER SD - SWITCHING DUTY F - FUSED ST - SHUNT TRIP MCS - MOLDEDCASE SWITCH ET - ELECTRONIC TRIP METER - ELECTRONIC METERING
Legend:
521 A
187865 VA
16 SPACE -- -- 0 VA --
15 SPACE -- -- 0 VA --
14 SPACE -- -- 0 VA --
13 SPARE BREAKER 3 200 A 0 VA
12 SPARE BREAKER 3 200 A 0 VA
11 SPARE BREAKER 2 20 A 0 VA
10 SPARE BREAKER 2 20 A 0 VA
9 EBB-1B 2 20 A 2500 VA
8 EBB-1A 2 20 A 2500 VA
7 SPD 3 30 A 0 VA
6 RTU-2 3 40 A 9727 VA
5 RTU-1 3 40 A 9727 VA
4 RTU-3 3 40 A 9727 VA
3 RTU-6 3 60 A 16212 VA
2 PANEL A 3 225 A 67472 VA
1 EXISTING 400AMP SINGLE PHASE DISCONNECT 2 400 A 70000 VA
CKT Circuit Description # of Poles Trip Rating Load Remarks
Enclosure: Type 1 Neutral Bus: 100%
Mounting: Surface Wires: 4 Mains Rating: 800
Supply From: Phases: 3 Mains Type: MCB
Location: ELECTRICAL CLOSET 104B Volts: 120/208 Wye A.I.C. Rating: 35,000 A
Main Panel: MDP
Notes:
GFI - GFCI BREAKER AFCI - AFCI BREAKER SD - SWITCHING DUTY F - FUSED ST - SHUNT TRIP MCS - MOLDED CASE SWITCH HT - HANDLE TIE
Options:
Total Adj. Demand Current: 194 A
Total Conn. Current: 187 A
Total Adj. Demand: 69903.8 VA
HVAC Heating 18000 VA 100.00% 18000 VA Total Conn. Load: 67472 VA
Motor 49472 VA 104.92% 51903.8 VA
Load Classification Connected Load Demand Factor Adjusted Demand Panel Totals
Total Amps: 194 A 195 A 177 A
Total Load: 23021 VA 23180 VA 21271 VA
55 SPARE BREAKER 20 A 1 0 VA 0 VA 1 20 A SPARE BREAKER 5653 SPARE BREAKER 20 A 1 0 VA 0 VA 1 20 A SPARE BREAKER 5451 SPARE BREAKER 20 A 1 0 VA 0 VA 1 20 A SPARE BREAKER 5249 SPARE BREAKER 20 A 1 0 VA 0 VA 1 20 A SPARE BREAKER 5047 SPARE BREAKER 20 A 1 0 VA 0 VA 1 20 A SPARE BREAKER 4845 SPARE BREAKER 20 A 1 0 VA 0 VA 1 20 A SPARE BREAKER 4643 SPARE BREAKER 20 A 1 0 VA 0 VA 1 20 A SPARE BREAKER 44
-- -- -- -- 1250 VA 0 VA 1 20 A SPARE BREAKER 4239,41 EWH-6 20 A 2 1250 VA 0 VA 1 20 A SPARE BREAKER 40
-- -- -- -- 1250 VA 0 VA 1 20 A SPARE BREAKER 3835,37 EWH-5 20 A 2 1250 VA 0 VA 1 20 A SPARE BREAKER 36
-- -- -- -- 1750 VA 1500 VA -- -- -- --31,33 EWH-4 25 A 2 1750 VA 1500 VA 2 20 A EWH-2 32,34
-- -- -- -- 1750 VA 1591 VA -- -- -- --27,29 EHW-3 25 A 2 1750 VA 1591 VA 2 30 A ACCU-9 28,30
-- -- -- -- 1591 VA 1591 VA -- -- -- --23,25 ACCU-10 30 A 2 1591 VA 1591 VA 2 30 A ACCU-8 24,26
-- -- -- -- 1591 VA 1591 VA -- -- -- --19,21 ACCU-6 30 A 2 1591 VA 1591 VA 2 30 A ACCU-4 20,22
-- -- -- -- 1591 VA 1591 VA -- -- -- --15,17 ACCU-5 30 A 2 1591 VA 1591 VA 2 30 A ACCU-3 16,18
-- -- -- -- 1591 VA 1591 VA -- -- -- --11,13 ACCU-7 30 A 2 1591 VA 1591 VA 2 30 A ACCU-1 12,14
-- -- -- -- 1591 VA 1500 VA -- -- -- --7,9 ACCU-2 30 A 2 1591 VA 1500 VA 2 20 A EWH-1 8,10
-- -- -- -- 2641.7 VA 3242.3 VA -- -- -- ---- -- -- -- 2641.7 VA 3242.3 VA -- -- -- --
1,3,5 RTU-5 30 A 3 2641.7 VA 3242.3 VA 3 40 A RTU-4 2,4,6
CKT Options Circuit Description Trip Poles A B C Poles Trip Circuit Description Options CKT
Enclosure: Type 1 Neutral Bus: 100.00%
Mounting: Surface Wires: 4 Mains Rating: 225 A
Supply From: MDP Phases: 3 Mains Type: MLO
Location: CLOSET 209 Volts: 120/208 Wye A.I.C. Rating: 10,000 A
Branch Panel: A
LUMINAIRE SCHEDULE NOTES
1 LUMINAIRE MOUNTING TO BE COORDINATED WITH CEILING OR WALL TYPE. ALL TRIM AND MOUNTING ACCESSORIES SHALL BE PROVIDED AND VERIFIED COMPATIBLE WITH MOUNTING SURFACE TYPE.
2 FINAL MOUNTING HEIGHTS FOR SUSPENDED AND WALL LUMINAIRES SHALL BE AS NOTED AND CONFIRMED WITH ARCHITECTURAL ELEVATIONS AND DETAILS, IF APPLICABLE. IF THIS INFORMATION IS NOT SHOWN, HEIGHTS SHALL BE CONFIRMED PRIOR TO SUSPENSION ORDERING AND ROUGH-IN.
3 FIXTURE MANUFACTURER AND MODEL LISTED IS THE BASIS FOR DESIGN. ANY REQUEST FOR SUBSTITUTIONS SHALL BE PROVIDED WITH DOCUMENTATION OF EQUIVALENCE, INCLUDING (BUT NOT LIMITED TO) PHOTOMETRIC COMPARISON.
4 PART NUMBERS/SERIES LISTED ARE TO ESTABLISH A MINIMUM QUALITY LEVEL ONLY. SUPPLIERS SHALL VERIFY THE LISTED LUMINAIRE MEETS ALL REQUIREMENTS LISTED IN THIS SCHEDULE AND SPECIFICATIONS. WHERE THE PART NUMBER LISTED DOES NOT MEET ALL THE REQUIREMENTS. LISTED SUPPLIER SHALL PROVIDE LUMINAIRE WITH EQUAL OR BETTER QUALITY THAT MEETS ALL THE REQUIREMENTS.
5 MAXIMUM LUMINAIRE POWER IS LISTED TO ENSURE COMPLIANCE WITH ENERGY CODE CALCULATIONS. EQUALS SHALL NOT USE MORE VA THAN LISTED.
6 FOR CONTINUOUS DIMMING LUMINAIRES BALLAST FACTOR COLUMN LISTS THE DIMMING RANGE DESIRED IN PERCENTAGE. I.E. 10%-100% INDICATES A LUMINAIRE DIMMABLE FROM FULL(100%) DOWN TO 10%
LUMINAIRE SCHEDULE
LUMINAIRE ID DESCRIPTION MANUFACTURER/SERIES LAMP QTY, TYPE, SIZE COLOR TEMP DRIVER TYPE DIMMING %INPUT
VOLT-AMPS VOLTAGE MOUNTING NOTES
A 2x4 FLAT PANEL SYLVANIA PANELF2B 026 UNVD840 24G WH LED, 4160LM 4000 K LED, 0-10V 10-100% 32 VA 120 V RECESSED
MECHANICAL EQUIPMENT CONNECTION SCHEDULE NOTES
MECHANICAL EQUIPMENT CONNECTION SCHEDULE
EQUIPMENT ID DESCRIPTIONLOCATION
MCALOAD VOLTAGE PHASE FEEDER
STARTER DISCONNECT
COMMENTSROOM NUMBER TYPE FURN / INST TYPE FURN / INST
ACCU-1 AIR COOLED CONDENSING UNIT EXTERIOR 17 A 3182 VA 208 V 1 (2#10, 1#10G) 3/4"C INTEGRAL MANUFACTURER FUSED DIV 26 / DIV 26 NEMA 3R FUSED DISCONNECT
ACCU-2 AIR COOLED CONDENSING UNIT EXTERIOR 17 A 3182 VA 208 V 1 (2#10, 1#10G) 3/4"C INTEGRAL MANUFACTURER FUSED DIV 26 / DIV 26 NEMA 3R FUSED DISCONNECT
ACCU-3 AIR COOLED CONDENSING UNIT ROOF 17 A 3182 VA 208 V 1 (2#10, 1#10G) 3/4"C INTEGRAL MANUFACTURER FUSED MANUFACTURER NEMA 3R FUSED DISCONNECT
ACCU-4 AIR COOLED CONDENSING UNIT ROOF 17 A 3182 VA 208 V 1 (2#10, 1#10G) 3/4"C INTEGRAL MANUFACTURER FUSED MANUFACTURER NEMA 3R FUSED DISCONNECT
ACCU-5 AIR COOLED CONDENSING UNIT ROOF 17 A 3182 VA 208 V 1 (2#10, 1#10G) 3/4"C INTEGRAL MANUFACTURER FUSED MANUFACTURER NEMA 3R FUSED DISCONNECT
ACCU-6 AIR COOLED CONDENSING UNIT ROOF 17 A 3182 VA 208 V 1 (2#10, 1#10G) 3/4"C INTEGRAL MANUFACTURER FUSED MANUFACTURER NEMA 3R FUSED DISCONNECT
ACCU-7 AIR COOLED CONDENSING UNIT ROOF 17 A 3182 VA 208 V 1 (2#10, 1#10G) 3/4"C INTEGRAL MANUFACTURER FUSED MANUFACTURER NEMA 3R FUSED DISCONNECT
ACCU-8 AIR COOLED CONDENSING UNIT ROOF 17 A 3182 VA 208 V 1 (2#10, 1#10G) 3/4"C INTEGRAL MANUFACTURER FUSED MANUFACTURER NEMA 3R FUSED DISCONNECT
ACCU-9 AIR COOLED CONDENSING UNIT ROOF 17 A 3182 VA 208 V 1 (2#10, 1#10G) 3/4"C INTEGRAL MANUFACTURER FUSED MANUFACTURER NEMA 3R FUSED DISCONNECT
ACCU-10 AIR COOLED CONDENSING UNIT ROOF 17 A 3182 VA 208 V 1 (2#10, 1#10G) 3/4"C INTEGRAL MANUFACTURER FUSED MANUFACTURER NEMA 3R FUSED DISCONNECT
EBB-1A ELECTRIC BASEBOARD MARSHAL'S OFFICE 001 14 A 2500 VA 208 V 1 (2#12, 1#12G) 1/2"C INTEGRAL MANUFACTURER INTEGRAL MANUFACTURER
EBB-1B ELECTRIC BASEBOARD MARSHAL'S OFFICE 001 14 A 2500 VA 208 V 1 (2#12, 1#12G) 1/2"C INTEGRAL MANUFACTURER INTEGRAL MANUFACTURER
EWH-1 ELECTRIC WALL HEATER WEST STAIR 14 A 3000 VA 208 V 1 (2#12, 1#12G) 1/2"C INTEGRAL MANUFACTURER INTEGRAL MANUFACTURER
EWH-2 ELECTRIC WALL HEATER ENTRY 114 14 A 3000 VA 208 V 1 (2#12, 1#12G) 1/2"C INTEGRAL MANUFACTURER INTEGRAL MANUFACTURER
EWH-3 ELECTRIC WALL HEATER MENS 111A 14 A 3500 VA 208 V 1 (2#10, 1#10G) 3/4"C INTEGRAL MANUFACTURER INTEGRAL MANUFACTURER
EWH-4 ELECTRIC WALL HEATER WOMENS 113B 14 A 3500 VA 208 V 1 (2#10, 1#10G) 3/4"C INTEGRAL MANUFACTURER INTEGRAL MANUFACTURER
EWH-5 ELECTRIC WALL HEATER MENS 208 14 A 2500 VA 208 V 1 (2#12, 1#12G) 1/2"C INTEGRAL MANUFACTURER INTEGRAL MANUFACTURER
EWH-6 ELECTRIC WALL HEATER WOMENS 206 14 A 2500 VA 208 V 1 (2#12, 1#12G) 1/2"C INTEGRAL MANUFACTURER INTEGRAL MANUFACTURER
FCU-1 FAN COIL UNIT STORAGE 002 2 A 400 VA 208 V 1 (2#12, 1#12G) 1/2"C INTEGRAL MANUFACTURER INTEGRAL MANUFACTURER POWER FROM RESPECTIVE OUTDOOR UNIT.
FCU-2 FAN COIL UNIT MARSHAL'S OFFICE 001 2 A 400 VA 208 V 1 (2#12, 1#12G) 1/2"C INTEGRAL MANUFACTURER INTEGRAL MANUFACTURER POWER FROM RESPECTIVE OUTDOOR UNIT.
FCU-3 FAN COIL UNIT OFFICE 101 2 A 400 VA 208 V 1 (2#12, 1#12G) 1/2"C INTEGRAL MANUFACTURER INTEGRAL MANUFACTURER POWER FROM RESPECTIVE OUTDOOR UNIT.
FCU-4 FAN COIL UNIT CONFERENCE 116 2 A 400 VA 208 V 1 (2#12, 1#12G) 1/2"C INTEGRAL MANUFACTURER INTEGRAL MANUFACTURER POWER FROM RESPECTIVE OUTDOOR UNIT.
FCU-5 FAN COIL UNIT CONFERENCE 116 2 A 400 VA 208 V 1 (2#12, 1#12G) 1/2"C INTEGRAL MANUFACTURER INTEGRAL MANUFACTURER POWER FROM RESPECTIVE OUTDOOR UNIT.
FCU-6 FAN COIL UNIT CONFERENCE 115 2 A 400 VA 208 V 1 (2#12, 1#12G) 1/2"C INTEGRAL MANUFACTURER INTEGRAL MANUFACTURER POWER FROM RESPECTIVE OUTDOOR UNIT.
FCU-7 FAN COIL UNIT OFFICE 205 2 A 400 VA 208 V 1 (2#12, 1#12G) 1/2"C INTEGRAL MANUFACTURER INTEGRAL MANUFACTURER POWER FROM RESPECTIVE OUTDOOR UNIT.
FCU-8 FAN COIL UNIT OFFICE 204 2 A 400 VA 208 V 1 (2#12, 1#12G) 1/2"C INTEGRAL MANUFACTURER INTEGRAL MANUFACTURER POWER FROM RESPECTIVE OUTDOOR UNIT.
FCU-9 FAN COIL UNIT OFFICE 204 2 A 400 VA 208 V 1 (2#12, 1#12G) 1/2"C INTEGRAL MANUFACTURER INTEGRAL MANUFACTURER POWER FROM RESPECTIVE OUTDOOR UNIT.
FCU-10 FAN COIL UNIT OFFICE 202 2 A 400 VA 208 V 1 (2#12, 1#12G) 1/2"C INTEGRAL MANUFACTURER INTEGRAL MANUFACTURER POWER FROM RESPECTIVE OUTDOOR UNIT.
RTU-1 PACKAGED ROOFTOP UNIT ROOF 30 A 9727 VA 208 V 3 (3#8, 1#10G) 3/4"C INTEGRAL MANUFACTURER INTEGRAL MANUFACTURER
RTU-2 PACKAGED ROOFTOP UNIT ROOF 30 A 9727 VA 208 V 3 (3#8, 1#10G) 3/4"C INTEGRAL MANUFACTURER INTEGRAL MANUFACTURER
RTU-3 PACKAGED ROOFTOP UNIT ROOF 30 A 9727 VA 208 V 3 (3#8, 1#10G) 3/4"C INTEGRAL MANUFACTURER INTEGRAL MANUFACTURER
RTU-4 PACKAGED ROOFTOP UNIT ROOF 30 A 9727 VA 208 V 3 (3#8, 1#10G) 3/4"C INTEGRAL MANUFACTURER INTEGRAL MANUFACTURER
RTU-5 PACKAGED ROOFTOP UNIT ROOF 24 A 7925 VA 208 V 3 (3#10, 1#10G), 3/4"C INTEGRAL MANUFACTURER INTEGRAL MANUFACTURER
RTU-6 PACKAGED ROOFTOP UNIT ROOF 48 A 16212 VA 208 V 3 (3#6, 1#10G) 3/4"C INTEGRAL MANUFACTURER INTEGRAL MANUFACTURER
1 CONDUIT AND WIRE SIZE SHOWN ARE BASED ON NEC TABLE 310.15 (B)(16). EC TO ADJUST CONDUIT AND WIRE SIZE FOR VOLTAGE DROP, TEMPERATURE, ETC.
2 EC TO CONFIRM MECHANICAL EQUIPMENT CONNECTION REQUIREMENTS WITH MC PRIOR TO START OF WORK.
333
100 A100 A100 A