2
RH-Cube 18 HH High Humidity Dehumidifier Legal: Copyright© 2019—DewAirCorporaon. All rights reserved. Specificaons and benefits believed correct at the me of release and may vary de- pending on specific condions and other circumstances. This brochure is subject to change without advanced noce. Product images may vary slightly. No warranes expressed or implied other than our product warranty. No DIY—must be installed by a cerfied HVAC contractor. Version release - Dec. 2019 www.DewAirCorp.com HVAC contractors and wholesalers in your area (attach business card here) DewAirproducts supplied by: Compared to other brands, RH-Cubehas: Raw capacity — our 2.0 ton system can remove more moisture than a 10 ton air conditioner More capacity than our CZ model for non- corrosive applications of high humidity & temp. Minimal ducting for simpler installation Less constrained electrical supply requirements Very low energy usage, very low cost of operation Optimized to pull more moisture where needed For applications such as greenhouses and industrial processing plants where temperatures and humidity levels are high, the RH- Cube 18 HH model is the ideal choice. In some cases, there can be a deployment of both the HH and CZ models to span a wider range of humidity and temperature where the CZ is only used at lower RH and temperatures by means of automation. The HH model may have its condenser outdoors to reduce heat such as industrial processing plants applications, or indoors to recover heat such as greenhouses for 25,000 BTUs of reheat. RH-Cube 18 HH application selection Compact | Capacity | Cost effective High humidity dehumidifier for select applications The higher capacity of the HH model needs to be aligned to applications where the range of indoor air temperature and range of humidity is within the recommended region for the HH model. Not ob- serving this will cause cycling that will reduce effi- ciency. Please refer to the capacity tables on our website for guidance or request technical support. Application example - Greenhouses Application example - Industrial Processing 80°F 80%RH→398 US pints/day 75°F 80%RH→425 US pints/day 70°F 80%RH→444 US pints/day (condenser is placed inside for greenhouses)

RH-Cube 18 HH High Humidity Dehumidifier · 2019. 12. 19. · Inspect every 1-2 months, replace every 3-4 months or as needed Alternative Air Filter (premium) Camfil 24x16x2 30/30

  • Upload
    others

  • View
    1

  • Download
    0

Embed Size (px)

Citation preview

  • RH-Cube 18 HH

    High Humidity Dehumidifier

    Legal: Copyright© 2019—DewAir™ Corporation. All rights reserved. Specifications and benefits believed correct at the time of release and may vary de-

    pending on specific conditions and other circumstances. This brochure is subject to change without advanced notice. Product images may vary slightly. No

    warranties expressed or implied other than our product warranty. No DIY—must be installed by a certified HVAC contractor. Version release - Dec. 2019

    www.DewAirCorp.com

    HVAC contractors and wholesalers in your area

    (attach business card here)

    DewAir™ products supplied by:

    Compared to other brands, RH-Cube™ has:

    • Raw capacity — our 2.0 ton system can remove more moisture than a 10 ton air conditioner

    • More capacity than our CZ model for non-corrosive applications of high humidity & temp.

    • Minimal ducting for simpler installation

    • Less constrained electrical supply requirements

    • Very low energy usage, very low cost of operation

    Optimized to pull more moisture where needed For applications such as greenhouses and industrial processing plants where temperatures and humidity levels are high, the RH-Cube 18 HH model is the ideal choice. In some cases, there can be a deployment of both the HH and CZ models to span a wider range of humidity and temperature where the CZ is only used at lower RH and temperatures by means of automation.

    The HH model may have it’s condenser outdoors to reduce heat such as industrial processing plants applications, or indoors to recover heat such as greenhouses for 25,000 BTUs of reheat.

    RH-Cube 18 HH application selection

    Compact | Capacity | Cost effective

    High humidity dehumidifier for select applications

    The higher capacity of the HH model needs to be

    aligned to applications where the range of indoor

    air temperature and range of humidity is within the

    recommended region for the HH model. Not ob-

    serving this will cause cycling that will reduce effi-

    ciency. Please refer to the capacity tables on our

    website for guidance or request technical support.

    Application example -

    Greenhouses

    Application example -

    Industrial Processing

    80°F 80%RH→398 US pints/day

    75°F 80%RH→425 US pints/day

    70°F 80%RH→444 US pints/day(condenser is placed inside for greenhouses)

  • Legal: Copyright© 2019—DewAir™ Corporation. All rights reserved. Specifications and benefits believed correct at the time of release and may vary de-

    pending on specific conditions and other circumstances. This brochure is subject to change without advanced notice. Product images may vary slightly. No

    warranties expressed or implied other than our product warranty. No DIY—must be installed by a certified HVAC contractor. Version release - Dec. 2019

    www.DewAirCorp.com

    Patents: CA2861757, US2016265805.

    Other patents pending.

    RH-Cube 18 HH is sold as a

    system of two components -

    the indoor dehumidifier unit

    and the outdoor condenser

    unit. Indoor unit should be

    installed in a noise tolerant

    area as like other HVAC

    equipment with blowers.

    See online installation

    manuals section.

    38.2” (97 cm)

    44.0” (112 cm)

    26.0” (66 cm)

    26.0” (66 cm)

    27.5” (70 cm)

    Dehumdifier unit (indoor) Part number: DA-900-0001

    Typical Power Consumption 340 Watts @ 80°F and 60% RH

    Blower power, STP performance

    336W (0.44 HP), 610 CFM @ 0" WG, 545 CFM@ 0.2"

    WG (50 Pascals), 500 CFM@ 0.35 WG (87 Pascals)

    Supply Voltage, Cord 120 V - 1 phase, 60 Hz, 6 foot cord (grounded)

    Power Circuit (Max Current Draw) 15 A breaker (Max draw 3.2A)

    Refrigerant / Liquid & Suction Lines R410A / Liquid 3/8" (9.5 mm) & Suction 3/4" (19 mm)

    Drain connection 3/4" (19 mm) NTP threaded female

    Refrigerant Maximum Length 82 feet (25m) distance

    Refrigerant Maximum Elevation 50 feet (15m) elevation

    Control Device (not included) dehumidistat

    Output Control Power 24 VAC up to 30 VA to power dehumidistat control

    Blower Switch Auto or always on

    Return Duct (air into RH-Cube)

    Minimum 3 foot duct (MANDATORY). Opening on

    top is 12" ( 30.5 cm) x 18" (46 cm)

    Supply Duct (air out of RH-Cube)

    Duct optional but recommended. Cutout choice on left,

    right, top, and back. 8" (20.5 cm) x 14" (35.6 cm)

    Other blower duct system connect Refer to installation manual for several options

    Service Access Left Side connection pipes, electrical control, blower switch

    Service Access Front evaporator coil, four heat exchangers, filter cover

    Service Access Top electrical components box

    Air Filter (standard recommended) Camfil 24x16x2 30/30 MERV 8 Part # 049880-016

    Filter Maintenance

    Inspect every 1-2 months, replace every 3-4 months or

    as needed

    Alternative Air Filter (premium) Camfil 24x16x2 30/30 Dual 9 Part # 0406331-016

    Equipment Weight, Ship Weight Equipment 260 lbs (117 Kg), Ship 300 lbs (136 Kg)

    Minimum maneuvering weight

    Approx 180 lbs (81 Kg) If needed, two front panel doors are easily opened so the 4 heat exchangers weighing 20 lbs each can be removed at client site to

    reduce final positioning weight, then reinserted.

    Equipment Dimensions (incl. pipes) 44.0"H (112 cm) x 28.4"W (72 cm) x 38.2"L (97 cm)

    Shipping Dimensions 47.0"H (120 cm) x 32.0"W (82 cm) x 44.0"L (112 cm)

    Dehumidification Performance Outdoor 80°F, total power usage = 1.86 kW

    Efficiency Capacity Capacity Sens. Cool.

    Indoor

    conditions

    US Pints /

    kWh

    US Pints /

    Day

    US Gal. /

    Day

    BTUs /

    Hour

    80F/60RH 7.5 319 39.9 3754

    75F/60RH 6.7 285 35.6 3970

    75F/50RH N/A N/A N/A N/A

    Outdoor 95°F, total power usage = 2.0 kW

    Efficiency Capacity Capacity Sens. Cool.

    Indoor

    conditions

    US Pints /

    kWh

    US Pints /

    Day

    US Gal. /

    Day

    BTUs /

    Hour

    80F/60RH 6.5 310 38.8 3376

    75F/60RH 5.6 268 33.5 3564

    75F/50RH N/A N/A N/A N/A

    Condenser unit (outdoor 2 ton) DewAir™ Part Number: DA-911-0002

    Typical Power Consumption 1526 Watts @ 80°F and 60% RH

    Supply Voltage (Max/Min V) 208/230 V - 1 phase, 60 Hz, (Min 193V/Max 255V)

    Power Circuit (Max Current Draw) 15 A breaker (Max draw 10.3A)

    Electrical Conduit 1/2" (12.7 mm) or 3/4" (19 mm)

    Refrigerant / Liquid & Suction Lines R410A / Liquid 3/8" (9.5 mm) & Suction 3/4" (19 mm)

    Operating Temperature Range 55°F (13°C) - 115°F (46°C) without add-ons

    Protection from Low Temperature add outdoor thermostat bimetal sensor

    Full Possible Operating

    Temperature Range with Add-ons

    10°F (-12°C) - 115°F (46°C), add condenser fan

    Equipment Weight, Ship Weight Equipment 126 lbs (57 Kg), Ship 141 lbs (64 Kg)

    Equipment Dimensions 27.5"H (70 cm) x 26.0"W (66 cm) x 26.0"L (66 cm)

    RH-Cube 18 HH Technical and Performance Data Performance measurements simulated and North American safety

    certification performed by Intertek in the USA.

    28.4” (72 cm)