July 2021 Request for Quotations (RFQ) AVL Landfill Gas Flare RFQ Details The Alberni-Clayoquot Regional District (ACRD) invites quotations for the supply and installation of a Landfill Gas Flare according to the following requirements: Location The flare is to be installed and commissioned at the Alberni Valley Landfill (AVL) 7080 McCoy Lake Rd, Port Alberni, BC V9Y 9G1 The location is indicated on the following site plan and is shown in the attached photos. The site can be inspected during landfill opening hours by appointment with the landfill operator (Berry and Vale at [email protected]). Background The Landfill has accepted municipal solid waste since the 1970s. Waste placement is confined to the waste mound shown which is under intermediate soil cover. The location identified for this installation has experienced landfill gas emissions associated with two monitoring wells. These wells were sealed in place and have not been opened since that took place. The ACRD requires the flare to burn the LFG from this source rather than continue to emit the LFG. Emissions of landfill gas are within provincial requirements and gas collection system is not required for the AVL, nor is the need anticipated. The AVL is served by a SCADA system that monitors several systems on the site such as pumps and reservoir levels. The details of the service will be provided to the successful respondent. It is assumed instrumentation needs will be powered by solar panels and batteries to be installed as part of this RFQ. Scope of work The specified flare is to be purchased and connected to a new purpose-drilled well (casing minimum 200mm OD) to be installed adjacent to the existing monitoring wells. A borehole log from the drilling of those wells is also attached. The well casing and backfill materials are to be suitable to the intended purpose of landfill gas extraction over the next three decades. The purchased flare is to be connected to the new well and commissioned. It is to have connectivity to the SCADA system that is in place at the site. Flare temperature, battery condition, and up time are to be made available in real time via SCADA. The successful proponent is to also required to compile an operations and maintenance manual/checklist for the flare system, as well as record drawings of the installation.

Request for Quotations (RFQ) AVL Landfill Gas Flare

  • Upload
    others

  • View
    8

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Request for Quotations (RFQ) AVL Landfill Gas Flare

July 2021

Request for Quotations (RFQ) AVL Landfill Gas Flare RFQ Details The Alberni-Clayoquot Regional District (ACRD) invites quotations for the supply and installation of a Landfill Gas Flare according to the following requirements:

Location

The flare is to be installed and commissioned at the Alberni Valley Landfill (AVL) 7080 McCoy Lake Rd, Port Alberni, BC V9Y 9G1

The location is indicated on the following site plan and is shown in the attached photos. The site can be inspected during landfill opening hours by appointment with the landfill operator (Berry and Vale at [email protected]).

Background

The Landfill has accepted municipal solid waste since the 1970s. Waste placement is confined to the waste mound shown which is under intermediate soil cover. The location identified for this installation has experienced landfill gas emissions associated with two monitoring wells. These wells were sealed in place and have not been opened since that took place.

The ACRD requires the flare to burn the LFG from this source rather than continue to emit the LFG. Emissions of landfill gas are within provincial requirements and gas collection system is not required for the AVL, nor is the need anticipated.

The AVL is served by a SCADA system that monitors several systems on the site such as pumps and reservoir levels. The details of the service will be provided to the successful respondent. It is assumed instrumentation needs will be powered by solar panels and batteries to be installed as part of this RFQ.

Scope of work

The specified flare is to be purchased and connected to a new purpose-drilled well (casing minimum 200mm OD) to be installed adjacent to the existing monitoring wells. A borehole log from the drilling of those wells is also attached. The well casing and backfill materials are to be suitable to the intended purpose of landfill gas extraction over the next three decades.

The purchased flare is to be connected to the new well and commissioned. It is to have connectivity to the SCADA system that is in place at the site. Flare temperature, battery condition, and up time are to be made available in real time via SCADA.

The successful proponent is to also required to compile an operations and maintenance manual/checklist for the flare system, as well as record drawings of the installation.

Page 2: Request for Quotations (RFQ) AVL Landfill Gas Flare

July 2021

Flare

The following flare has been identified as suitable to the purpose. It does not include SCADA connectivity as supplied. Vendors are free to identify equivalent alternatives that may be substituted according to their expertise.

Site Viewing

The site is available for viewing by prior arrangement during regular facility hours,. Appropriate PPE is high vis vest and steel toe boots. Site COVID protocols current at the site are to be followed.

RFQ Submission Procedure All quotes are to be marked Quotation for AVL LFG Flare and be received by the ACRD representatives on or before 4:30pm on August 12th 2021 by email. A single email is to be addressed to: [email protected] and [email protected]

Enquiries Solid Waste Manager 3008 Fifth Avenue Port Alberni, BC V9Y 2E3 Email is the preferred means of communication.

Page 3: Request for Quotations (RFQ) AVL Landfill Gas Flare

"- SURFACE WATER 'C:::7 HEATH CREEK

*Mwo2-•

APR. 2018

MODIFIED JUNE 2021

MW98-9♦ +MW98-10

- - ..,, ...

.,SHOO-IA

ALBERNI CLAYOQUOT REGIONAL DISTRICT

ALBERNI VALLEY LANDFILL

SHOWING PROPOSED LOCATION OF FLARE

MW13-1S �/AW13-10

FIGURE 1

£

-®-w

Installation to be made at Location MW94-3

Page 4: Request for Quotations (RFQ) AVL Landfill Gas Flare
Page 5: Request for Quotations (RFQ) AVL Landfill Gas Flare
Page 6: Request for Quotations (RFQ) AVL Landfill Gas Flare

Norseman Engineering Ltd. Engineering Services #4-7551 Vantage Way Environmental Engineering Delta, B.C. V4G-1C9 Landfill Gas Utilization Phone: (604) 946-0111 Solid Waste Management Fax: (604) 946-6359 cell: (604) 644-5482

January 11, 2016 McGill and Associates Engineering Ltd. 4610 Elizabeth Street Port Alberni, B.C. V9Y-6L7 Attn: Brad West, P.Eng. Re: Report on field investigation and remedial measures taken to alleviate landfill gas venting of monitoring well MW94-3 at Alberni Valley Landfill. Len Hanson of Norseman Engineering Ltd. was contacted by Jennifer Mancer of Piteau Engineering concerning safety issues associated with the above monitoring well, in particular with large amounts of landfill gas being emitted from this well. Norseman was provided with all of the information needed to assess, test and perform corrective measures on the above well including the original drilling log, a photo of the well, a topographical site plan of the area and a description of the situation. Norseman was requested to analyze the landfill gas, including testing for hydrogen sulphide. A Gem 2000 Plus instrument was rented which had the capability of measuring that as well as methane, carbon dioxide, oxygen, carbon monoxide and carbon dioxide. The description of the well as presented to Norseman was that of a 152 mm (6”) steel casing rising out of the landfill surface vertically to a height of 1.8 m (5.9’). Inside of the protective steel pipe were two 51 mm (2”) PVC piezometers; a deep one with slotted screen at 12.2 to 15.2 meters below the surface, and a shallow one with slot screen at 5.2 to 6.7 m below the surface. It was thought that it would be prudent to be prepared to be able to contain the landfill gas being emitted from the well and at the same time maintain access to the piezometers.

Page 7: Request for Quotations (RFQ) AVL Landfill Gas Flare

The site was visited on January 4, 2016. Upon arrival, Norseman was escorted to the well in question by Earl, the landfill operator, and was provided with a description of the site. Large amounts of landfill gas were being emitted from the well. It was unknown whether the majority of the landfill gas was being emitted from the 152 mm pipe or from the 51 mm piezometers. These were capped, and it was observed that the flow of landfill gas did not decrease appreciably. Thus it was concluded that the steel pipe was providing a path of least resistance for the landfill gas to escape into the atmosphere. The large amount of landfill gas escaping from the well provided a good opportunity to test the landfill gas for its component parts. The results are as follows: Chemical Component Instrument Reading Methane (CH4) 55.9 % Carbon Dioxide (CO2) 36.5 % Oxygen (O2) 1.0 % Balance (mostly Nitrogen) 6.8 % Carbon Monoxide (CO) 10 ppm Hydrogen Sulphide (H2S) 28 ppm It was then decided to cap the steel pipe while still maintaining access to the piezometers if necessary. A 152 mm PVC Drain, Waste and Vent (DWV) cap was used since this type of cap is constructed in Iron Pipe Size (IPS), which was assumed to be the size of the steel pipe. This proved to be correct. A hole saw was used to cut two holes in the cap the size of the OD of the two piezometers. Couplings and 51 mm (2”) pipe were used to extent these above the top of the steel pipe. The cap was then fitted over the extended pipes and pounded in to place. It was observed at this point that landfill gas was still being emitted from the piezometers, but at a greatly reduced rate.

Page 8: Request for Quotations (RFQ) AVL Landfill Gas Flare

In order to stop all landfill gas emissions while still having access to test the piezometers, 51mm (2”) male threaded adapters were glued to the pipes, and were then topped off with threaded 51 mm (2”) caps tightened hand tight for easy access. These pipes can now be tested if necessary one at a time with minimal landfill gas exposure, while preventing any landfill gas from escaping during non test periods. Conclusion The steel pipe of MW94-3 provided a point of easy escape for landfill gas into the atmosphere. Capping it will force the landfill gas to migrate slowly through the soil and cover before emerging from the ground surface. As the landfill gas migrates through the soil, much of the methane and other components of landfill gas will be oxidized and will become less harmful. This will reduce the amount of emissions of concern from going into the atmosphere and also correcting a potential safety and health hazard. The fittings at the top will provide access for testing if necessary. If you have any questions, please contact me. Submitted by: Norseman Engineering Ltd. Len Hanson, P.Eng.

Page 9: Request for Quotations (RFQ) AVL Landfill Gas Flare

Manufacturer of Environmental and Industrial Solutions EPG Companies Inc.19900 County Rd. 81

Maple Grove MN 553111-800-443-7426 www.epgco.com

• SolarPoweredwithBatteryBackup

• 6VDCContinuousIgnitionSystem

• AllWeatherStainlessSteelSparkPilot

• StainlessSteelBallValve

• InlineFlameArrester

CF-5 Flow Range 2-90 SCFM

Bulletin 6555

Sold By:

StandardFeatures:

Height: 96”InlettoTopofFlareHead

ShipWeight: 75lbs.

Base: 4”MNPTBushingMatedtoSpecificFlangeAdapterRequiredforLocalApplication

DarkTimeEndurance: 21DaysinDarknesswithFullyChargedSystem

SparkInterval: 1.5SecondsContinuous

Flangeadapters,insulationkits,andothercustomcomponentsareavailabletomeetyourneeds.Forotherflaresizesandoptions,consultyourlocalsalesrep.

Solar Spark® Vent Flares are patented and registered trademark of LSC Environmental Products, LLC

Solar Spark® Passive Vent Flare

Sales and Service by EPG Companies Inc.

SolarSpark®PassiveVentFlaresare

suitableforalltypesoffugitivegas

vents.Theyprovideaneconomical

solutionforfugitivegasemmisionsand

odorcontrol.Theiruniquedesigncan

withstandcloudyandwindyconditions

forworry-freeoperation.

Page 10: Request for Quotations (RFQ) AVL Landfill Gas Flare

ZIRCO (1989) LTD5614A Burbank Rd SECalgary, Alberta T2H 1Z4Canada

QUOTE

Quote No.:Date:Page:

1278701/11/20211

Sold To:

Paul EvansAlberni Valley LandfillPort Alberni, BC V9Y 9G1

Alberni Clayoquot Regional District_CashShip To:

Alberni Clayoquot Regional District_CashPaul EvansAlberni Valley LandfillPort Alberni, BC V9Y 9G1Ph: 403-899-1477Ref: Passive Flare project

Comments

Business No.: 105792501

Ship Date:

Item No. Quantity Unit Description Tax Base Price Disc % Unit Price Amount

EPG-MISC 1 each 810010 B 10,470.74 10,470.74 10,470.74CF-10 Solar Spark vent flare (5-140 CFM). Includes2" gas riser, stainless steel ball valve, heat shield, 8" double expansion flare head, Model 78 Spark Pilot, in-line flame arrester, and 4" MPT connection.Includes:- P/N 800002: Solar Igniter with On/Off switch, 12 Volt battery, solar collector, and charger.- P/N 800093: Flame Shield, screens visibility of flame zone, stainless steel, includes mounting hardware.

- P/N 60098: Guy Wire Kit, includes three (3) 10' long stainlesssteel guy wire cables, eye bolts, turnbuckles, 3' fence posts, and (6) cable clamps- P/N 60430: 4" Base Mounting Kit. Includes (2) 4x9 steel flanges, gasket, bolt kit (bolts, washers, and nuts), 4" x close steel nipple, 4" tee with baffle, 4" x 3' steel pipe, 4 x 13 steel flange, and (4) expansion bolts for mounting in concrete. Inlet to flare to be a 4" FNPT connection.

Important Note: The CF-10 Solar Fare don't carry CSA certification. Minimun flow for CF-10 flare is 5 CFM and for CF-5 flare is 2 CFM.

Quote Notes: 1) Lead time is currently stock to three (3) weeks from date of approved order. Please keep in mind that if submittals are required, the lead time will remain stock to three (3) weeks after submittals are given final approval.

Continued...Continued...

Page 11: Request for Quotations (RFQ) AVL Landfill Gas Flare

ZIRCO (1989) LTD5614A Burbank Rd SECalgary, Alberta T2H 1Z4Canada

QUOTE

Quote No.:Date:Page:

1278701/11/20212

Sold To:

Paul EvansAlberni Valley LandfillPort Alberni, BC V9Y 9G1

Alberni Clayoquot Regional District_CashShip To:

Alberni Clayoquot Regional District_CashPaul EvansAlberni Valley LandfillPort Alberni, BC V9Y 9G1Ph: 403-899-1477Ref: Passive Flare project

Comments

Business No.: 105792501

Ship Date:

Item No. Quantity Unit Description Tax Base Price Disc % Unit Price Amount

Submittals are available 2-3 weeksafter approved order is received.2) All prices FCA Zirco Calgary Warehouse.3) All prices in CDN Dollar4) Please note that any changes, cancellations or returns are subject to an administration fee plus any additional cleanup or material costs; restocking fees upto 100% applicable for factory ordered products.5) Rev 1: Jan 11th, updated the flare to CF-10 flare per client request

Subtotal: 10,470.74

B - GS 5%, BC 7%GST 523.54BCTAX 732.95

ZIRCO (1989) LTD GST: #105792501ZIRCO (1989) LTD BCTAX: #105792501

Total Amount 11,727.23

Shipped by

Sold By: Humayun Humayun

Page 12: Request for Quotations (RFQ) AVL Landfill Gas Flare

Terms and Conditions of Proposals & Transactions

The following terms and conditions apply to proposals made by ZIRCO (1989) LTD., unless specifically modified in the main body of the proposal that they accompany. Proposals made by ZIRCO (1989) LTD. on behalf of our principal representatives will be subject to the terms and conditions of that principal at the time the order is accepted. 1. This proposal is firm for 30 days from date shown in proposal. 2. Delivery and delivery date shown is

contingent upon strike, stoppages of labour, accidents, fire, floods, acts of God or of the public enemy, riots, civil disturbances, martial law, acts of government, shortages of fuel and of raw material, delays or stoppages of transportation or other caused beyond our control and in the event of such occurrences, seller may at its election cancel this order or any part thereof.

3. Terms are net 30 days for approved accounts.

2% per month will be charged on all overdue accounts. Any account that is 60 days past due, will be subject to immediate credit hold.

4. Warranty: ZIRCO (1989) LTD. passes on the

manufacturer's warranty to the purchaser. ZIRCO (1989) LTD. does not in its own name underwrite the manufacturer's warranty. The liability of ZIRCO (1989) LTD. and purchaser's exclusive remedy in any cause of actions (whether in contract, tort, breach of warranty or otherwise) arising out of the sale of any products, supplies or materials is expressly limited to the manufacturer's warranty. In no event shall ZIRCO (1989) LTD. be liable for special, incidental, indirect, punitive or consequential damages.

5. Prices shown are in Canadian Dollars, FCA

ZIRCO (1989) LTD. warehouse in Calgary, AB. All applicable taxes are extra. Goods will be invoiced on the date they are ready to ship from our warehouse.

6. The purchaser is responsible for loss or

damage from the time of shipment from ZIRCO (1989) LTD. warehouse. Carrier insurance is available upon request.

7. Orders cannot be cancelled by purchaser under any circumstances without the seller's consent and upon terms, which will indemnify against all loss.

Order Cancellation: After PO submission – 10% After ordering materials – 25% When the order is ready to ship – 25-100% No cancellation will be allowed for Products

of special design, finish or size. 8. A service charge of 25-100% of the price will

be paid by Buyer to cover handling and inspection of any Products returned. Products returned without Seller’s written permission in the form of a Return Material Authorization (RMA) will not be accepted for credit. All returned Products must be new, in saleable condition, with transportation charges prepaid. No credit will be allowed for return of Products of special design, finish or size, or for any Products returned more than 50 days after shipment.

9. NO credit will be allowed for return of

products of special design, finish or size, or for any products returned more than 60 days after shipment. Parts and subassemblies may not be returned. Any product that is not a standard stock item is considered to be of special design.

10. All shipping costs, to and from our

warehouse and/or factory, on all returned products, whether for credit, repair, or warranty, will be the responsibility of the purchaser.

11. Title to materials in this contract shall remain

with the seller until all invoices for the goods supplied are paid in full.

12. Clerical or typographical errors are subject to

correction. 13. All orders are subject to acceptance by

ZIRCO (1989) LTD. or by the manufacturer. 14. All prepaid and charge freight is subject to a

minimum 25% administration fee. 15. A minimum charge of $25.00 applies to all

orders.

ZIRCO (1989) LTD. 5614 A Burbank Road SE Calgary, Alberta T2H 1Z4 Telephone(403)259-3303 Facsimile (403) 259-2814 Toll Free (800) 461-3120

Page 13: Request for Quotations (RFQ) AVL Landfill Gas Flare

EXCHANGE FLUCTUATION:

a) Quote to Order: If the USD/CAD exchange rate fluctuates by more than 2% between the date of quotation through the date of order acceptance, Seller reserves the right to adjust the prices for all goods manufactured in (or imported from) the United States. The adjustment will be determined using the value of all US goods, the Bank of Canada noon rate from day prior to the proposal date, and the Bank of Canada noon rate on the day prior to order acceptance. Seller will attempt to provide Buyer with confirmation, but it is not possible in all cases due to the urgency and time sensitive nature of our business.

b) Order to Shipment: If the USD/CAD exchange rate fluctuates by more than 2% between Order Acceptance and Product Shipment, Seller reserves the right to add a billable line to each invoice, adjusting the prices for all goods manufactured in (or imported from) the United States. The applicable rates to determine the value of the billable line will be the Bank of Canada noon rate from the day prior to Order Acceptance, and the Bank of Canada noon rate on the day prior to Invoice Date.