reliability and temperature evaluation of boilers

Embed Size (px)

Citation preview

  • 8/11/2019 reliability and temperature evaluation of boilers

    1/91

    1

    CHAPTER 1

    INTRODUCTION

  • 8/11/2019 reliability and temperature evaluation of boilers

    2/91

    2

    INTRODUCTION

    The common causes of the metallurgical failure of the tubes in water tube boiler are due

    to tube temperature higher than expected in the original design. A major challenge for the

    maintenance activities which are to be performed now a days in industries is not only to learn the

    available techniques, but to decide which are suitable for the particular industries. The new

    developments include: Decision support tools, such as hazard studies, failure modes and effects

    analysis and expert systems, new maintenance techniques, such as condition monitoring and

    designing equipment with a much greater emphasis on reliability and maintainability analysis of

    the systems in the industries.

    The primary problem associated with reliability assessment is the selection and

    specification of the most appropriate reliability model. This requires the collection and analysis

    of failure and repair data in order to empirically fit the model to the observed failure or repair

    process. The derivation of the reliability and maintainability models is an application of the

    probability theory, whereas the collection and analysis of the failure and repair data are primarily

    an application of descriptive and there are two general approaches to fitting reliability

    distributions to failure data. The first and usually preferred method is to fit a theoretical

    distribution such as normal, exponential, lognormal and weibull. The second is to derive directly

    from directly from the data an empirical reliability function or Probability density function

    function. The later method is also called as Distribution Free method and it is very easy toconduct for the analysis. The objective of this method is to derive directly from the failure and

    repair times, the failure and repair times, the failure distribution, reliability function and

    Probability density function functions.

    Tube temperature increases slowly over many years or rapidly caused either by loss of

    internal steam or water flow. Internal oxide scale or deposit formation usually results in long

    term overheating that gradually increases the temperature [1]. Although steam temperature

    occasionally measured in a boiler, local tube temperature and temperature distribution are rarely

    measured and some times impossible due to temperature range which is very high, load

    fluctuation and steam side oxide scale growth during operation [2]. However, the remaining life

    span of the boiler tubes that installed in a fossil fuelled power station can be predicted if the

    stress and average temperature of the tubes are known, together with the way the tubing is

    thinned or scarred as a result of erosion and corrosion processes [3]. Arguably, the average tube

  • 8/11/2019 reliability and temperature evaluation of boilers

    3/91

    3

    temperature plays a more significant role than stress does in determining the creep life of a boiler

    tube. In order to avoid the tube failure, detection of tube temperature distribution is necessary to

    take proper action. Therefore, temperature distribution in the tubes in water tube boiler needs to

    be analyzed numerically. Therefore, this paper presents the application of finite element method

    (FEM) to analyze the tube temperature distribution in a water tube boiler.

    1.1 INTRODUCTION TO VISAKHAPATNAM STEEL PLANT:

    The Visakhapatnam Steel Plant (VSP) is a 3Mt Integrated Steel Plant under the corporate

    entity, Rashtriya Ispat Nigam Limited (RINL). VSP is the first shore based integrated steel plant

    in country. The plant produces steel through the BF BOF route. VSP has the distinction of being

    the first integrated steel plant in the country to adopt 100% continuous casting. Currently the

    plant is operating at 4.0MT of hot metal, 3.56 MT liquid steel and 3.17 MT of saleable steel

    representing capacity utilization of over 115%.

    Steel industry being energy intensive in nature from raw material stage to finishing stage.

    About 470-480 KWH of electricity is used for every tonne of steel produced and steel industry

    requires about 250-260MW of electricity for running various drives in the plant .RINL realized

    that electrical energy demand in integrated steel works can be met through installation of captive

    power plant and support from grid. RINL has captive power plant of 247.5MW, and an

    additional 39MW installed capacity for waste energy recovery to meet energy recovery, to meetenergy requirements in VSP.

    1.2 INTRODUCTION ABOUT THERMAL POWER PLANT

    Integrated Steel Plants are major consumers of electricity, with specific

    consumption of power at around 600-650 MW Hrs/Ton of liquid steel. Power requirement of

    VSP is met through captive power plant generation as well as supply from APSEB grid. The

    captive capacity of 270MW is sufficient to meet all the plant needs in normal operation time. Incase of partial outage of captive generation capacity due to breakdown, shutdown or other

    reasons, the shortfall of power is availed from APSEB grid. Turbo generators of VSP normally

    operate in parallel with state grid. Excess generation over and above plant load is exported to

    APSEB. The following are the main objectives of Thermal Power Plant of Visakhapatnam Steel

    Plant.

  • 8/11/2019 reliability and temperature evaluation of boilers

    4/91

    4

    To supply uninterrupted cold blast to Blast Furnace as per furnace requirements.

    To supply uninterrupted Power to critical Category-1 loads of Steel Plant.

    To supply 13 ata process steam for other process units of Steel Plant.

    To supply DM water and soft water to meet both internal and external plant needs.

    To supply chilled water to meet both internal and external plant needs.

    To reduce dependency on State Power Grid by ensuring maximum internal in-house

    Power Generation.

    Thermal Power Plant has 5 Boilers each generating of 330 T/Hr steam at 101KSCA and 400C.

    the boilers are of BHEL make, capable of firing combination of fuels namely Coal, Coke Oven

    Gas, Blast Furnace Gas ands Oil. Crushed coal is conveyed from Raw Material Handling Plant to

    TPP through conveyors. The coal is pulverized in Bowl Mills and fired in the furnace. Normally,

    4 boilers are kept in full load operation to produce 247.5 MW of power, supply steam to 2 Turbo

    Blowers and process needs boilers outlet flue gas as it passes through Electro Static Precipitators

    to control air pollution. The Fly ash and bottom ash generated are pumped in slurry form to ash

    pond through on ground pipelines. The clarified water is recalculated back to ash system

    BOILERS:

    Thermal Power plant has 5 Boilers each generating 330 T/hr. steam at 101 KSCA and

    540oC. The boilers are of BHPL make, capable of firing combination of fuels namely Coal,

    Coke Oven Gas, Blast Furnace Gas and Oil. Crushed coal is conveyed from Raw Material

    Handling Plant to TPP through conveyors. The coal is pulverized in Bowl Mills and fired in the

    furnace. Normally 4 Boilers are kept in full load operation to produce 247.5 MW of Power,

    supply steam 2 turbo Blowers and process steam needs boiler outlet flue gas passes through

    electro Static Precipitators to control air pollution. The Fly ash and Bottom Ash Generated are

    pumped in slurry form to ash pond through on-ground pipe lines. The clarified water is

    recirculate back to ash system.

    TURBO GENERATORS:

    Thermal power plant has 4 Turbo Generators, three of 60MW capacity each and fourth

    67.5 MW. Special features of the turbo sets are: Electro hydraulic turbine Governing System

  • 8/11/2019 reliability and temperature evaluation of boilers

    5/91

    5

    controlling extractions at 13 ata and 4 ata for process steam needs in TG1, 2 and 3. Central

    admission of steam to reduce axial thrust.

    AIR COOLED GENERATORS:

    Power is generated and distributed at 11KV for essential loads. Remaining power from

    TG-1, 2 and 3 is transferred to plant grid.

    TURBO BLOWERS:

    VSP has two Blast Furnaces. To meet the blast air requirement 3 Turbo Blowers each

    of 6067 NM3/Min @ 6.5 Kg/ Cm2 capacity, are installed at TPP. These Blowers are of axial type

    and are the largest blowers installed in India. To meet the varying needs of Blast Furnace, the

    blowers are provided with adjustable stator guide blades in the low pressure compression stages.

    The Blowers are provided with suction filters, pre- coolers and intercoolers.

    AUXILIARIES OF TPP:

    These include coal conveyers; cooling towers and pump house No. 4 for cooling water

    system; pump house for ash water, ash slurry, fire water and fuel oil and HSD; air compressor

    station; emergency Diesel Generators; electric switch gear for power distribution; ventilation

    and air conditioning equipment etc.

    CHEMICAL WATER TREATMENT PLANT (CWTP):

    Chemical Water Treatment Plant located in TPP Zone produces high purity

    Demineralised Water and Soft Water. There are six streams of Demineralising units each

    capable of producing 125 cubic meters per hour and two softening units of 125 M 3/Hr each.

    DM water is supplied to Chilled Water Plant-I, II and SMS mould cooling. The return

    condensate from Thermal Power Plant, chilled water plant no. I and chilled water plant no. II is

    polished at CWTP in 2 streams, each of 100 M3/hr capacities. All the demineralised water

    produced/polished at CWTP is deareated and dosed with Ammonia before pumping for this

    purpose.

  • 8/11/2019 reliability and temperature evaluation of boilers

    6/91

    6

    CHILLED WATER PLANT:

    Chilled Water Plant No.2 located in TPP zone is having nine chillers, each having a chilling

    capacity of 337 cu.M of water per hour. The chillers operate on liquid absorption technique

    having Lithium Bromide cycle. The chilled water is supplied to TPP, Blast Furnace and sinter

    Plant for air conditioning Purpose of 70c. The return water temperature is 16oC. Steam and

    cooling water requirements are met by TPP and pump House No.4 respectively.

    COKE DRY COOLING PLANT (CDCP) BOILERS:

    In VSP, hot Coke produced in the coke Oven Batteries is cooled by circulating Nitrogen in

    Coke Dry Cooling Plant. The hot circulating gas is passed through waste Heat Boilers in which

    steam is produced at 40 KSCA pressure and 4400

    c temperature. There are four Waste HeatRecovery Boilers each of 25T/hr capacity in each Coke Dry Cooling Plant. There are three

    CDCP for 3 Coke Oven Batteries. These Boilers are forced circulation Boilers. Deaerators and

    Boiler feed pumps, serving all the three plants, are located at CDCP-1.

    BACK PRESSURE TURBINE CHILLED WATER PLANT:

    The 40 KSCP steam generated in CDCP Boilers is utilized for driving 2 Nos. of 7.5 MW

    Back Pressure Turbines for generation of power. The 2.5 ata exhaust steam is utilized for

    production of Chilled Water in CWP-1. The 7-ata-extraction steam is used for process

    requirements of CO7CCP zone. The CWP-1 has 5 chillers installed, each capable of cooling

    337m3 of water per hour from180c to 10

    oC. The Chilled Water is supplied to Gas Coolers and

    for air conditioning need s of CO&CCP zone. BPTS and CWP-1 are housed in a single building

    located near Batters No.3 of CO&CCP zone.

  • 8/11/2019 reliability and temperature evaluation of boilers

    7/91

    7

    CHAPTER 2

    LITERATURE SURVEY

  • 8/11/2019 reliability and temperature evaluation of boilers

    8/91

    8

    LITERATURE SURVEY:

    In water tube boilers, water is converted into steam inside the tubes, while hot gases pass

    over and around the outside of the tubes. Water tube boilers can operate at higher pressures than

    fire tube boilers. The flow of steam and water within a water tube boiler is called circulation.

    This circulation is critical in preventing tubes from overheating. When tubes are overheated,

    metal softens, weakens and may eventually rupture. In a simple water tube circuit, bubbles of

    steam form in the heated tubes or "risers". The resulting steam and water mixture is lighter than

    cooler water on the unheated side of the boiler, and rises to a steam drum at the top of the boiler.

    Here the bubbles rise to the surface and steam is released. The water then flows from the drum

    down through the cooler rubes, or "downcomers", completing and repeating the cycle.

    The Metallurgy Department of the Riley Stoker Corp. [1] that has many

    experiences for the 25 years period ending in 1980 gives the list of the breakdown between

    mechanical and corrosion failure and further classify the various kinds of failures, locations, and

    materials. 81% of the boiler tube failure is due to mechanical, consist of high temperature failure

    (short time) 65.8%, creep (high temperature/long time) 8.6%, and others 6.6%, while boiler

    failures caused by corrosion is 19%. Analysis of the North American Electric Reliability Council

    (NERC data) indicates that the coal fired boilers are among the highest economic risk

    components in any power plant. By far, the greatest number of forced outages in all types ofboiler is caused by failures [6]. Elimination of boiler tube failure could save the electric power

    industry about $5 billion a year [7]. Metallurgists from David N. French, Inc. [1] published data

    of the top 10 causes of failures where creep (long-term overheating) is 23.4%, followed by

    fatigue (13.9%) (thermal 8.6%, corrosion 5.3%), ash corrosion (12.0%), hydrogen damage

    (10.6%), weld failures (9.0%), high temperature (short-term overheating) (8.8%), erosion (6.5%),

    oxygen pitting (5.6%), caustic attack (3.5%) and stress corrosion cracking (2.6%). In general,

    30% of all tube failures in boilers and reformers are caused by creep [8].

    Dillon.AR et.al.,(2003), described that the prevention of the fast fracture damage of the

    mechanical equipment important for the safety of nuclear power plant by conducting the

    reliability analysis.

  • 8/11/2019 reliability and temperature evaluation of boilers

    9/91

    9

    Almeida.A.B and Ramos. H. M (2010) have conducted the diagnosis and reliability

    analysis in a pumping system. Weak points in the design and in the operation can then be

    detected and future accidents can also be avoided.

    Chapman, et.al.,(2010), have conducted the Structural lifetime, reliability and risk analysis

    for power plant components and systems.

    Deepika Garg et.al.,(2009), have described the reliability of a Pharmaceutical plant using

    MAT LAB. The purpose of paper is to compute reliability of a Pharmaceutical plant . A

    Pharmaceutical plant consists of nine sub-systems working in series. One subsystem namely

    Rotary Compression Machine is supported by stand-by units having perfect switch over devices

    and remaining eight subsystems are subjected to major failure only.

    Ray et.al., (2003) have conducted assessment of service exposed to boiler tube of the super

    heater and preheater made of 2.25 Cr-1 Mo steels in a120MW boiler of thermal power plant.

    Husain and habib et.al., (2008) have investigated the steel tubes failure in a super aterboiler

    at one of Kuwait electrical and power plants which suffered localized overheating.

    Baoyou et.al.,(2006) have analysed a boiler tube rupture through chemical analysis,

    scanning electron microscope and energy dispersive spectroscopy.

    Chattoraj et.al., (1997) have investigated the corrosive degradation and failures of vertical

    furnace wall tubes of a cogeneration boiler.The results showed that under isothermal condition,

    the creep damage depends only on the stress.

    Caligiuri et.al., (2006) have conducted simulation to identify the effect of thermal

    constraint in design of a heat recovery boiler. The finite element model using thermal and

    structural analysis was applied, and commercially available finite element software namely

    Ansys was used.

  • 8/11/2019 reliability and temperature evaluation of boilers

    10/91

    10

    CHAPTER 3

    INTRODUCTION TO BOILERS

  • 8/11/2019 reliability and temperature evaluation of boilers

    11/91

    11

    3.1 BOILER :

    A steam generator or boilers is usually, a closed vessel made of steel. Its

    functions is to transfer the heat produced by combustion fuel (liquids, solid or gaseous) to water

    and ultimately to generate steam. The steam produced may be supplied:

    To steam engines or turbines (turbo generators)

    At low pressures for industrial processes work

    For producing hot water which can be used in vapour absorption processes.

    In TPP,5 Boilers are installed with a capacity of 330 ton/hr each with 101 ata

    and 12 auxiliary waste heat recovery boilers installed capacity 25 ton/hr each 40ata,to supply

    steam to turbo generators for power generation and 13 ata,7 ata steam for different processes

    throughout the plant.

    GENERAL SPECIFICATIONS OF BOILER:

    Make : BHEL, Tiruchy

    Type of unit : Single drum, natural circulation, 3 stages super heated

    Balanced draught, multi fuel firing, non reheat

    Type of furnace : Fusion welded dry bottom

    Type of super heater : Radiant and convection

    Type of steam temperature

    Control : Spray

    AIR / FLUE GAS PATH:

    Air used for combustion of lignite or any other fuel applied in power generation, should

    be preferably hot. Air pre heaters are arranged in the flue gas ducts for preheating the air,

    utilizing the heat in waste gases. FD fans suck atmosphere air and pass it through ducts of rotary

    air heaters then temperature of air is raised up to 370 deg C.

    FUELS AND FIRING:

    A coal fired unit incorporates oil burners also to a firing capacity of 25% of boiler load

    for the reason of:

    1. To provide necessary ignition energy to light off coal burner

    2. To stabilize the coal flame at low boiler / burner loads

  • 8/11/2019 reliability and temperature evaluation of boilers

    12/91

    12

    3. As a safe start up fuel and controlled heat input during light off

    LIGHT FUEL OIL:

    The fuel for the igniter is light fuel oil. Normally LFO is used for cold start ups

    and it is sometimes referred as `warm-up fuel. Being a distillate, LFO burns clean ad completein a cold furnace without any un burnt oil conveyors. LFO has the advantage of being low

    viscous at ambient temperatures requiring no heating, and it can be air atomized.

    COKE OVEN GAS:

    Coke oven gas is supplied to the boiler from coke oven batteries. This gas can be

    used for warming up and for load carrying. This gas gives stable flame normally without any

    need for support by igniters. There are totally 32 COG gas spuds arranged in four elevations in

    the auxiliary air compartments.

    BLAST FURNACE GAS:

    This is supplied from Blast furnaces. The calorific value of the gas is low and

    hence needs support at low loads when the burnt separately. Also as no reliable flame scanning

    can be obtained with this gas flame, an auxiliary firing either oil or coal firing is resorted to

    whenever there is need for BFG firing. Also the gas is characterized by its high level of toxicity

    and hence utmost care should be taken for handling this gas.

    COMBUSTION IN FURNACE:

    Furnace is the place where combustion of the pulverized fuel and oil fuel takes place

    with the aid of air supplied. We can say that two processes occur in the furnace simultaneously.

    One process is that of a chemical reaction exothermic in nature which releases a lot of heat and

    the other process is the transfer of this heat to the medium inside the water walls. So the

    efficiency of the furnace depends on the utilization of heat energy for evaporation of water and inreduction of radiation and other losses. In our boilers the furnace is a dry bottom pulverized fuel

    furnace having suspension system of firing. Furnace is screened by water walls on all the four

    sides. Furnace bottom is hopper shaped and is immersed in water in the slag bath. The maximum

    temperature encountered in the furnace is 1250 C to 1300 C. Since the ash function temperature

    is 1450 C fly ash collects at the bottom of the furnace in solid state. 15% of ash below in the

  • 8/11/2019 reliability and temperature evaluation of boilers

    13/91

    13

    furnace into the slag. They are cooled by the water in the slag bath and removed by two slag

    conveyors.

    WATER WALL FURNACE:

    Furnace volume : 2300cu m

    Heat transfer area : 1230sq m

    Area of refractory exposed : nil

    Tube Outer Dia * thickness : 63.5 * 4.8 sq mm

    Tube material : SA 192

    Pitch : 76.2 mm

    No. of tubes in front and

    Rear walls each : 132

    No. of tubes in left and right

    Side walls each : 92

    Design metal temperature : 373 deg C

    Design pressure : 121 kg/sq cm

    WATER WALL PLATEN:

    Number off : 4

    Tube OD * thickness : 50.8 * 4.1 sq mm

    Heat transfer area : 120 sq.m

    Number of tubes/platen : 26

    Design metal temperature : 373 oC

    design pressure : 121 kg/sq.cm

    FEED WATER SYSTEM:

    Requirement of the boiler feed water is met by a DM plant. Feed water is deaerated

    and then pumped by a feed Pump into a common header from where the feed water is passed

    through two HP heaters. Feed water from HP heaters passes through a common header from

    where individual boilers are fed.

  • 8/11/2019 reliability and temperature evaluation of boilers

    14/91

    14

    Feed pump:

    Number off : 5+2 (stand by)

    Type of drive : motor driven through step up gear box

    Capacity : 375 m3/ hr

    Head : 1441 m/c

    Temperature of water : 142oC

    Density : 924.3 kg/m3

    Speed : 4305 rpm

    Power input : 1680 kw

    THE PRESSURE PARTS OF BOILER:

    The pressure parts of a boiler are the parts which are most prone to failure due to the

    acting of pressure and temperature and other factors such as corrosion due to natural causes

    which occur during operation.

    The pressure parts of a boiler are the tubing, header, boiler drum, and the pipe work

    which contain the steam that are the fundamental operating fluids of the thermodynamic cycle. In

    operation, these components are protected by avoiding large temperature differentials through

    the walls or gross heating by lack of coolant. The operating temperature plays an important role

    in the failure than the operating pressure. In addition to the long term aspects we also face short-

    term aspects such as boiler explosion, which take the unit off-load.

    BOILER DRUMS:-

    The boiler drum is usually the largest single piece of equipment in the boiler. It is also the

    most difficult to replace. Drum is basically a thick walled cylinder, made up of rolled plates

    welded together, susceptible from thermal shock due to operational error. The detailed inspection

    of the supporting structure can be carried out by detailed non-destructive testing.

    All inlet and outlet connections to the boiler are welded. In older designs, unfused land

    was included from which cracks propagated. A vast majority of these connections have site wells

    very close to the drum. If any of these fail, the escaping fluid may corrode the drum. Short term

    repairs to a drum are possible, but would require expensive heat treatment, making them

    expensive and time consuming.

  • 8/11/2019 reliability and temperature evaluation of boilers

    15/91

    15

    The bulk of drum inspection and repairs are concerned with the fitting inside the drum

    such as water distribution pipe work, sampling and dosing pipe work, steam separators, driers

    and baffles. They are bolted to the drum and there are some flanged connections. All these

    connections must be checked for any indications of corrosion and erosion. Failures of a number

    of fasteners indicate a fault or undue stress somewhere in the system. The most likely result of a

    bolt falling off in the drum is a blockage and tube leaks.

    Finally, the drum and its surrounding area must be checked to ensure that it is not being

    locally corroded by intermittent spillage from safety valve drains or airlocks.

    Fig 3.1 Boiler drum

    Headers:

    Header creep lives must be assessed by considering temperature, materials and dimensions.

    1. Based on the noral station instrument header temperature records, with correction

    for operating temperature spread along the header.

    2. Based on the actual header temperature, as part of the specific recording exercise

    with actual physical dimensions.

    3. Physical and NDT inspection of headers.

  • 8/11/2019 reliability and temperature evaluation of boilers

    16/91

    16

    TUBE ATTACHMENTS:

    Tube attachments are a general description of any device attached to the pressure tubing

    of the boiler. Attachment failure and subsequent loss of alignment can lead to tube heating or

    soot blower erosion, both leading to subsequent failure. Therefore attachment welding should be

    checked.

    MAIN PIPE WORK :

    The main pipe work of a boiler unit can be classified as the pipes linking the drums and

    headers within a boiler. Cole pipe work tends to present a few problems in actual operation of

    plant. Hot pipe works is often subject to defect which grow in size in service due to the elevated

    temperature of the boiler.

    3.2 TYPES OF BOILERS:

    This section describes the various types of Boilers:

    Fire tube boiler

    Water tube boiler

    Fluidized Bed Combustion Boiler

    Atmospheric Fluidized Bed Combustion Boiler

    Pressurized Fluidized Bed Combustion Boiler

    Fire Tube Boiler:

    In fire tube boiler, hot gases pass through the tubes and boiler feed water in the shell side

    is converted into steam. Fire tube boilers are generally used for relatively small steam capacities

    and low to medium steam pressures. As a guideline, fire tube boilers are competitive for steam

    rates up to 12,000 kg/hour and pressures up to 18 kg/cm2. Fire tube boilers are available for

    operation with oil, gas or solid fuels. For economic reasons, most fire tube boilers are nowadaysof packaged construction (i.e. manufacturers shop erected) for all fuels.

  • 8/11/2019 reliability and temperature evaluation of boilers

    17/91

    17

    WATER TUBE BOILER:

    In water tube boiler, boiler feed water flows through the tubes and enters the boiler

    drum. The circulated water is heated by the combustion gases and converted into steam at the

    vapor space in the drum. These boilers are selected when the steam demand as well as steam

    pressure requirements are high as in the case of process cum power boiler / power boilers. Most

    modern water boiler tube designs are within the capacity range 4,500 120,000 kg/hour of

    steam, at very high pressures. Many water tube boilers nowadays are of packaged construction

    if oil and /or gas are to be used as fuel. Solid fuel fired water tube designs are available but

    packaged designs are less common.

    The features of water tube boilers are:

    Forced, induced and balanced draft provisions help to improve combustion efficiency.

    Less tolerance for water quality calls for water treatment plant.

    Higher thermal efficiency levels are possible

    Fluidized Bed Combustion (FBC) Boiler:

    Fluidized bed combustion (FBC) has emerged as a viable alternative and has

    significant advantages over conventional firing system and offers multiple benefits compactboiler design, fuel flexibility, higher combustion efficiency and reduced emission of noxious

    pollutants such as SOx and NOx. The fuels burnt in these boilers include coal, washery rejects,

    rice husk, bagasse & other agricultural wastes. The fluidized bed boilers have a wide capacity

    range- 0.5 T/hr to over 100 T/hr.

    3.3 BOILER TUBE FAILURES CAUSES AND REMEDIES:

    The causes of failures of boiler tubes, while most of the causes of failures are attributed tooperational mistakes and malfunctions of boiler, a few can be attributed to defective design,

    material of workmanship. The details various causes of failures and the remedial measures to be

    adopted to avoid such failures are.

    The main causes of tube failure are:

    1. Overheating

  • 8/11/2019 reliability and temperature evaluation of boilers

    18/91

    18

    2. Erosion

    3. Corrosion

    4. Material

    5. Other defects

    1.OVERHEATING:

    Overheating can be localized, extensive, prolonged or of short duration. Metallographic

    analysis indicates the approximate temperature to which the tube was subjected before failure

    occurred. Observation of the grain growth and microstructure of failed tube material also

    indicates if the overheating was of prolonged or short duration. Water-wall tube failure results in

    a burst with a fish mouth opening. Occasionally cracks will also appear up to lengths of 2

    meters on either side of the burst. Bursting occurs due to excessive reactive force caused by

    change of state from water to steam. In the case of super heaters, tube failures take the form of a

    narrow opening with multiple satellite cracks. The reasons for overheating of waterfall or

    superheated tube are:

    a) Starvation due to

    (i) Improper circulation (ii) Insufficient flow

    b) Flame impingement

    c) Secondary burning of fuel

    d) Excessive air

    a) Starvation

    i) Due to improper circulation:

    Insufficient circulation in the water walls may lead to departure from onset of nucleate

    boiling and may lead to overheating, which in turn will result in tube failures. Where the failures

    are traced to improper circulation, the same can be improved in that region of water wall by

    providing additional down comers/spider tubes to the existing down comers.

    ii) Due to insufficient flow:

    Starvation can occur in super heater tubes due to an insufficient flow resulting in

    overheating. This is generally observed in the binder tubes of the platen super heater. These

    binder coils have a number of bents, and are longer in length than the other coils in the platen.

  • 8/11/2019 reliability and temperature evaluation of boilers

    19/91

    19

    The flow through these binder coils is, therefore inadequate. The prolonged overheating in such

    tubes results in creep failure.

    Such failures can be avoided by replacing the long binder tube with shorter tubes which

    in turn increases internal flow and prevents overheating Overheating can also be avoided by

    changing the material. The materials of the bottom portion of the outermost coils of platen can

    also be replaced by stainless steel to enhance their life since the bottom most portion faces direct

    radiation from the furnace.

    b) Flame impingement:

    Water wall failures occur mostly near the burners. This is due to the flame impingement

    from burners, which get distorted in service. To avoid such failures new burner nozzles such as

    the honeycomb type which resist distortion are now used.

    c) Secondary burning of fuel:

    In certain cases oil from the oil gun may flash on to the tubes. Even in coal fired boilers,

    the unburned fuel particles may catch at the top of the furnace or in the second pass cause in

    secondary combustion, explosion, or over heating of the tubes.

    This can be avoided by proper controlled of the atomization of oil, coal particle size and

    the firing rate.

    d) Excessive air:

    Too much of excess air leads to higher furnace temperature resulting in higher radiation,

    heat absorption and slagging problems. In oilfired boilers, too much of excess air is favorable to

    the formation of SO3due to the increased availability of O2, thereby promoting a higher rate of

    low temperature corrosion.

    To avoid such failure the O2content in flue gases should be measured periodically during

    operation and adjustments made to achieve design values as closely as possible. Further, to avoid

    condensation, the flue gas temperature in different zones should be closely monitored and kept

    within the design limits.

    2. EROSION:

    Erosion is the second major cause of tube failures. The tube wall thickness gets reduced

    due to erosion and when the thickness is not sufficient to withstand the operating pressure and

    temperature of the tube, the tube will fail.

    Erosion of the super heater and economizer tubes may be due to the following reasons:

  • 8/11/2019 reliability and temperature evaluation of boilers

    20/91

    20

    i) Flue gas erosion

    ii) Erosion due to steam or water

    i) Flue gas erosion:

    Since the rate of erosion is proportional to the cube of velocity, erosion may occur on the

    super heater and economizer tubes due to the high abrasive ash content of Indian coals if the

    velocity of the gases in the narrow gaps is high. Such insufficient gaps may occur between coils

    and walls, and super heater coils and ash hoppers blow them. Boilers, therefore, have to be

    designed with gas velocities limited to values below critical.

    ii) Erosion due to steam or water:

    Whenever there is a tube failure the water or steam from the faulty tube escapes in the

    form of a high velocity jet and when it impinges on the adjacent tubes they get eroded. If the

    boiler is not shut down immediately after detection of the failure and allowed to operate for a

    protracted period the damage due to steam or water erosion will be considerable.

    3. CORROSION:

    Corrosion is another cause of the tube failure. Corrosion can be on the gas side of the tubes the

    steam side. The gas side corrosion occurs in oil fired boilers. High temperature corrosion occurs

    due to the presence in oil of sodium and vanadium, the oxides of which form flux with the

    protective oxide of the material, thereby causing further attack on the material by the gas. This

    can be prevented by using low vanadium content oil or by employing certain additives like MgO

    powder in the oil. The MgO powder can be sprayed through a separate nozzle into the furnace or

    magnesium wires can be burnt in the furnace.

  • 8/11/2019 reliability and temperature evaluation of boilers

    21/91

    21

    Fig 3.2 Damage of boiler tube due to corrosion

    Low temperature or dew point corrosion occurs in oil fired boilers in the air heater

    or economizer if the flue gas temperature approaches the dew point temperature. Sulphur in the

    oil transforms to SO3 in the furnace and then to Sulphuric acid with the water vapour in the flue

    gas at low temperatures and causes corrosion. Low temperature corrosion can be avoided by

    controlling the inlet temperature of the feed water to the economizer.

    If the feed water contains dissolved oxygen or Carbon Dioxide, these gases will

    react with the tube material and cause corrosion inside the water wall or super heater tubes

    Water-side corrosion

    It is of the following three types:-

    Stress Corrosion Cracking (SCC)

    Symptoms: Failures from SCC are characterized by a thick wall, brittle-type crack

    May be found at locations of higher external stresses, such as near attachments.

    Causes: SCC most commonly is associated with austenitic (stainless steel) Super heater materials

    and can lead to either transgranular or intergranular crack propagation in the tube wall. It occurs

    where a combination of high-tensile stresses and a corrosive fluid are present. The dame results

    from cracks that propagate from the ID. The source of corrosive fluid may be carryover into the

    super heater from the steam drum or from contamination during boiler acid cleaning if the super

    heater is not properly protected.

  • 8/11/2019 reliability and temperature evaluation of boilers

    22/91

    22

    Hydrogen Damage:

    Symptoms: Inter granular micro-cracking. Loss of ductility or embrittlement of the tube material

    leading to brittle catastrophic rupture.

    Fig 3.3 hydrogen damage

    Causes: Hydrogen damage is most commonly associated with excessive Deposition on ID tube

    surfaces, coupled with a boiler water low pH excursion. Water chemistry is upset, such as what

    can occur from condenser leaks, particularly with salt water cooling medium, and leads to acidic

    (low pH) contaminants that can be concentrated in the deposit. Under-deposit corrosion releases

    atomic hydrogen which migrates into the tube wall metal, reacts with carbon in the steel

    (decarburization) and causes inter granular separation.

    Fire Side Corrosion:

    Fig 3.4 Fire side corrosion

    Tubes develop a series of cracks that initiate on the outside diameter surface and

    propagate into the tube walls. Since the damage develops over longer periods, tube surface tends

  • 8/11/2019 reliability and temperature evaluation of boilers

    23/91

    23

    to develop appearance known as iron hide, or craze cracking. Most commonly seen a s a series of

    circumferential cracks. Usually found on furnace wall tubes of coal- fired once- through boiler

    designs, but also has occurred to tubes in drum type boilers.

    Damage initiation and propagation results from corrosion in combination with thermal

    fatigue. Tube outer diameter experiences thermal fatigue stress cycle, which can occur from

    normal shedding of slag, soot blowing or from cyclic operation of boiler.

    It is mainly due to the following reasons:-

    (i) Low temperature

    (ii) Water wall

    (iii) Coal ash

    Water side Corrosion Fatigue:

    Symptoms: ID initiated, wide trans granular cracks which typically occur

    Adjacent to external attachments.

    Causes: Tube damage occurs due to the combination of thermal fatigue and Corrosion. Corrosion

    fatigue is influenced by boiler design, water chemistry, boiler water oxygen content and boiler

    operation. A combination of these effects leads to the breakdown of the protective magnetite on

    the ID surface of the boiler tube. The loss of this protective scale exposes tube to corrosion. The

    locations of attachments and external weldments, such as buck stay attachments, seal plates and

    scallop bars, are most susceptible. The problem is most likely to progress during boiler start-up

    cycles.

    4.MATERIAL DEFECTS:

    High-temperature Oxidation:

    Similar in appearance and often confused with fireside ash corrosion, high-

    temperature oxidation can occur locally in areas that have the highest outside surfacetemperature relative to the oxidation limit of the tube material. Determining the actual root cause

    between the mechanisms of ash corrosion or high-temperature oxidation is best done by tube

    analysis and evaluation of Both ID and OD scale and deposits.

  • 8/11/2019 reliability and temperature evaluation of boilers

    24/91

    24

    Drum Cracking:

    The durability of steam drums, relative to other boiler components, cannot be

    attributed to stable, low-stress operations: They operate in a very dynamic mode, especially

    during major transients. Aging, combined with cyclic duty, is beginning to take its tollthe

    incidence of cracking is increasing for units 30 years and older.

    Fig 3.5 Drum Cracking

    Grinding and localized weld repair can address initial cracking problems, but

    extensive drum cracking poses a threat to the structural integrity and continued safe and reliable

    operation of the unit. Pressure stresses and the environmental influence of corrosion fatigue play

    the dominant role in drum cracking for both types of boilers.

  • 8/11/2019 reliability and temperature evaluation of boilers

    25/91

    25

    CHAPTER 4

    INTRODUCTION TO FAILURE MODE

    EFFECTS AND CRITICALITY ANALYSIS

  • 8/11/2019 reliability and temperature evaluation of boilers

    26/91

    26

    INTRODUCTION TO FAILURE MODE EFFECTS AND CRITICALITY ANALYSIS

    CONDUCT FMECA :

    The next step is to conduct FMECA analysis on each boiler tubes of the thermal power

    plat, which can be done as follows:

    Failure Modes and Effects Analysis (FMEA) is a simple analysis method to reveal

    possible failures and to predict the failure effects on the system as a whole..If we describe or

    rank the criticality of the various failures in the FMEA, the analysis is often referred to as an

    FMECA (Failure Modes, Effects and Criticality Analysis). The criticality is a function of the

    failure effect and the frequency/probability as seen below. To ensure a systematic study of the

    system, a specific FMEA form is used. The FMEA form may for example include the following

    columns:

    IDENTIFICATION:

    Here the specific component is identified by a description and/or number. It is also

    common to refer to a system drawing or a functional diagram. The function of the component,

    i.e. its working tasks in the system, is briefly described. The state of the component when the

    system is in normal operation, is described.

    FAILURE ZONES:

    All the possible ways the components can fail to perform its function are listed in

    this column. Only the failure modes that can be observed from outside are included. The

    internal failure modes are to be considered as failure causes.

    Effect on other units in the system:In those cases where the specific failure mode affects

    other components in the system, this is stated in this column. Emphasis should be given to

    identification of failure propagation, which does not follow the functional chains of the

    functional diagrams.

    EFFECT ON SYSTEM:

    In this column, we describe how the system is influenced by the specific failure

    mode. The operational state of the system as a result of failure is to be expressed, for example,

    whether the system is in the operational state, changed to another operational mode, or not in an

    operational state.

  • 8/11/2019 reliability and temperature evaluation of boilers

    27/91

    27

    Corrective measures:

    Here we describe what has been done or what can be done to correct the failure,

    or possibly to reduce the consequences of the failure. We may also list measures that are aimed

    at reducing the probability that the failure will occur.

    FAILURE EFFECT RANKING:

    The failure is ranked according to its effect with respect to reliability and

    safety, the possibilities of mitigating the failure, the length of the repair time, the production loss,

    etc. We might for example use the following grouping of failure effects:

    Level C:A failure that does not reduce the functional ability of the system more than normally is

    accepted.

    Level B:A failure that reduces the functional ability of the system beyond the acceptable level,

    but the consequences can be corrected and controlled.

    Level A:A failure that reduces the functional ability of the system beyond the acceptable level

    and which creates an unacceptable condition, either operational or with respect to safety.

    Remarks: Here we state, for example, assumptions and suppositions. By combining the failure

    frequency (probability) and the failure effect (consequence), the criticality of the specific failure

    mode is determined.

    4.1FMECA FOR BOILER-1 TUBES:

    Boiler tubes are used to convert water into steam.It is havig we have conduct the

    FMECA and results are shown table

    Table 4.1 FMECA for Boiler-1 Tubes

    S.NO Failure

    zone

    Level of

    probability

    occurrence

    Failure

    cause

    Failure

    effect

    Remedies

    1 Near LHSwater wall

    screen tube

    B Overheatingof boilers

    Hazardousproblem

    Hard facingdone and

    tubechanged

    2 RHS

    economizer B Due to

    Fuction of

    economizer

    Replacement

    tubes

  • 8/11/2019 reliability and temperature evaluation of boilers

    28/91

    28

    upper bank

    lower tubes

    corrosion decreases

    3 Failure of

    water wall

    at 39 mtrs

    height

    A Continuous

    overheating

    Decreases

    efficiency

    Replacement

    with new

    tubes

    4 Economizer

    lower bank

    lower side

    C

    Due to

    erosion

    steam

    temperature

    decreases

    Economizer

    coil bends

    are changed

    After conducting the FMECA for boiler-1 tubes we found that the main causes to failure

    of tubes are water wall tubes and economizer tubes and remedies are shown in table 4.1.

    4.2

    FMECA FOR BOILER-2 TUBES:

    Boiler tubes are supply water to the boiler and converts steam.As like above we have

    conduct the FMECA and results are shown table

    Table 4.2 FMECA for Boiler-2 Tubes

    S.NO Failure

    zone

    Level of

    probability

    occurrence

    Failure

    cause

    Failure

    effect

    Remedies

    1 Water wall

    screen tube C

    Overheating

    of boilers

    Steam

    temperature

    increases

    Water wall

    screen tubes

    are replced

    2 Furnace

    area A Due to

    overheating

    Boiler may

    stops

    Hard facing

    done

    3 Economizer

    lower bank C

    Continuous

    overheating

    Economizer

    may stops

    Replacement

    with new

    tubes

    4 Super

    heater

    upper zone

    C

    Due to

    erosion

    Super

    heater may

    stops

    Replaced

    with new

    tubes

  • 8/11/2019 reliability and temperature evaluation of boilers

    29/91

    29

    After conducting the FMECA for boiler-2 tubes we found that the main causes to

    failure of tubes are water wall tubes and economizer tubes and remedies are shown in table 4.2.

    4.3FMECA FOR BOILER-3 TUBES:

    Boiler tubes supplies high temperature steam to superheater.As like above we have

    conduct the FMECA and results are shown table

    Table 4.3 FMECA for Boiler-3 Tubes

    S.NO Failure

    zone

    Level of

    probability

    occurrence

    Failure

    cause

    Failure

    effect

    Remedies

    1 Wall soot

    blower

    C Pin holes

    developed

    Leakage of

    flue gases

    Welding is

    done

    2

    Economizer A Due to

    erosion

    Parts

    damaged

    New tubes

    are placed

    3 Water wall

    buck stays B

    Due to

    high

    pressure

    Temperature

    decreases

    Pad welding

    done

    4 Super

    heater

    lower bank

    B

    Due to

    erosion

    Temperature

    of steam

    reduces

    Tubes were

    replaced

    After conducting the FMECA for boiler-3 tubes we found that the main causes to failure

    of tubes and remedies are shown in table 4.3

  • 8/11/2019 reliability and temperature evaluation of boilers

    30/91

    30

    4.4 FMECA FOR BOILER-4 TUBES:

    Boiler tubes are supply water to the boiler and converts steam.As like above we

    have conduct the FMECA and results are shown table

    Table 4.4 FMECA for Boiler-4 Tubes

    S.NO Failure

    zone

    Level of

    probability

    occurrence

    Failure

    cause

    Failure

    effect

    Remedies

    1 Tube

    leakages A

    Due to

    hydrogen

    damage

    Boiler

    functions

    decreases

    Replacement

    of tubes

    2 Water wall

    screen

    tubes fails

    B

    Due to

    erosion

    Temperature

    of steam

    decreases

    Window

    welding to

    failed tubes

    3 LHS super

    heater

    upper coil

    A Overheating

    of steam

    Tube

    efficiency

    decreases

    Tubes and

    coils was

    chaged

    After conducting the FMECA for boiler-4 tubes we found that the main causes to

    failure of tubes and remedies are shown in table 4.4

  • 8/11/2019 reliability and temperature evaluation of boilers

    31/91

    31

    4.5FMECA FOR BOILER-5 TUBES:

    Boiler tubes are supply water to the boiler and converts steam.As like above we

    have conduct the FMECA and results are shown table

    Table 4.5 FMECA for Boiler-5 Tubes

    S.NO Failure

    zone

    Level of

    probability

    occurrence

    Failure

    cause

    Failure

    effect

    Remedies

    1 Corner-4

    water wall

    Area

    A

    Due to

    power

    disturbance

    Boiler

    stops

    Power

    disturbance

    rectified

    2 Corner-4

    steam

    cooled

    waterwall

    header area

    B Due to high

    temperature

    Steam

    temperature

    increases

    Bend

    replaced

    3 Economizer

    inlet header A

    More

    supply of

    steam

    Tubes

    efficiency

    decreases

    All 3 tubes

    replaced

    4 Water wall

    sootblower

    failure

    C

    Due to

    high

    temperature

    Reduces

    steam

    temperature

    Window

    welding

    done

    After conducting the FMECA for boiler-5 tubes we found that the main causes

    to failure of tubes are water wall tubes and economizer tubes and remedies are shown in table

    4.5

  • 8/11/2019 reliability and temperature evaluation of boilers

    32/91

    32

    4.6 RESULTS FROM FMECA:

    After conducting FMECA analysis, the following failure modes have been found as

    critical and needs immediate action:

    1) In boiler-1 tubes have more failures has been found in water wall screen tubes due

    corrosion remedies for this problem is regularly check the boiler thoroughly and maintain

    constant temperature.

    2) In boiler-2 tubes the main failures are boiler tubes due to high temperature for this have

    to maintain the temperature.

    3) In boiler-3 tubes mostly failures occurs at super heater tubes and economizer tubes due

    corrosion and erosion of the parts the remedies for this problem replace the tubes.

    4) In boiler-4 tubes failures obtained due overheating of boilers and so the steam

    temperature increases then the leakages are raised. The remedy for this is the

    maintenance of boiler tubes the required temperature.

    5) In boiler-5 tubes water wall tubes are failed due to corrosion, erosion and scale formation

    remedy for this check water walls regularly.

  • 8/11/2019 reliability and temperature evaluation of boilers

    33/91

    33

    CHAPTER 5

    RELIABILITY EVALUATION OF

    BOILER TUBES

  • 8/11/2019 reliability and temperature evaluation of boilers

    34/91

    34

    RELIABILITY ANALYSIS OF BOILER TUBES:

    In the present chapter, reliability analysis has been performed for boiler tubes. In this

    work two methods namely empirical or non parametric and Weibull or parametric methods are

    employed. In this work, first empirical method is used for reliability assessment process.

    INTRODUCTION:

    The primary problem associated with reliability assessment is the selection and

    specification of the most appropriate reliability model. This requires the collection and analysis

    of failure and repair data in order to empirically fit the model to the observed failure or repair

    process. The derivation of the reliability and maintainability models is an application of the

    probability theory, whereas the collection and analysis of the failure and repair data are primarily

    an application of descriptive and there are two general approaches to fitting reliability

    distributions to failure data. The first and usually preferred method is to fit a theoretical

    distribution such as normal, exponential, lognormal and weibull. The second is to derive directly

    from directly from the data an empirical reliability function or Probability density function

    function. The later method is also called as Distribution Free method and it is very easy to

    conduct for the analysis. The objective of this method is to derive directly from the failure and

    repair times, the failure and repair times, the failure distribution, reliability function and

    Probability density function functions.

    5.1 Reliability analysis using empirical method:

    In the present study, initially the empirical method has been considered for the reliability

    assessment of the boiler tubes as follows:

    The generation or the observation of failure (or repair) times can be represented by

    t1,t2,t3,tn where ti represents the time of failure of the ithunit. It is assumed that each failure

    represents an independent sample from the same population. The population is the distribution of

    all possible failure time and may be represented by f(t),R(t),F(t) or (t).The basic problem is to

    determine the best failure distribution implied by the n failure times comprised in the sample. In

    all cases the sample is assumed to be a simple random(or probability) sample. A simple random

    sample is one in which the failure or repair rates are independent observations from a common

    population. If f(t) is the probability density function of the underlying population then f(ti) is the

  • 8/11/2019 reliability and temperature evaluation of boilers

    35/91

    35

    probability density function of the ith sample value. Therefore, if the sample consists of

    nindependent values, the joint probability distribution of the sample is the product of n identical

    and independent probability distributions, or

    ft1,t2,tn(t1,t2,.tn)=f(t1)f(t2)f(tn)

    Empirical methods of analysis are also referred to as nonparametric methods or

    distribution free methods. The objective is to derive directly from failure times, the failure

    distribution, reliability function and Probability density function function. Generally the

    parametric approach consisting of fitting a theoretical distribution is preferred. This method

    however is used in case when no theoretical distribution adequately fits the data. The data here is

    Grouped Complete Data.

    Grouped Complete Data:

    Failure times that have been placed into time intervals, their original values no longer

    available, let n1,n2,nk be the no. of units having survived at the ordered times t1,t2,..tk

    respectively. Then a logical estimate for R(t) is

    R(ti)=ni/n i=1,2,k

    When n is the no. of units at risk at the start of the test. Because of the larger sample size

    of the grouped data, it is generally unnecessary to obtain more precise estimates by considering

    plotting positions.

    Following are the terms associated with empirical method and data collection:

    (1)RELIABILITY: It is defined to be the probability that a component or system will

    perform a desired function for a given period of time when used under stated operating

    conditions. It is denoted by symbol R(t). and is expressed by the formula: R(ti)=ni/n

    (2)FAILURE DENSITY: The cumulative failure distribution or the probability density

    function of the failure of the component at that particular instant of time. It is denoted by

    symbol f(t) and is expressed by the formula: f(t)=(ni-ni+1)/{(ti+1-ti)*n}

    (3)

    PROBABILITY DENSITY FUNCTION FUNCTION: It is also known as instantaneous

    Probability density function function or failure rate function. It is denoted by (t) and

    provides an alternative way of describing the failure distribution. It is expressed by the

    formula:

  • 8/11/2019 reliability and temperature evaluation of boilers

    36/91

    36

    (t)=(ni-ni+1)/{(ti+1-ti)*ni}

    Data Collection And Analysis:

    In the present study, the data regarding failure rates of the boiler tubes in the processing

    industry has been collected from the maintenance log books. The failure rates have been

    analyzed both theoretically and graphically as follows:

    By using the above formulas and steps of empirical method, the reliability modeling and

    analysis using empirical method has been performed and results are shown as below.

    MODEL CALCULATIONS:

    Sample calculations for the BOILER-1 tubes have been conducted using formulas as follows:

    Reliability R(ti) = ni/n

    Failure density f(t) = (ni-ni+1)/(ti+1-ti).n

    Probability density function (t) = f(t)/R(t) = (ni-ni+1)/(ti+1-ti).ni

    Where ni (i= 1,2,..k) =no.of.units survived at time ti (i=1,2,.k)

    n = no.of.units at risk at the start of the test.

    Reliability R(3) = ni/n= 17/20 = 0.85

    Failure density f(3) = (ni-ni+1)/(ti+1-ti).n = (17-12)/(18-12).20 = 0.041666667

    Probability density function (3) = f(t)/R(t)= 0.04166667/0.85 = 0.049019608

    5.2 RELIABILITY ANALYSIS OF BOILER-1 TUBE:The boiler tubes are used to allow water to flow and by supplying heat outside of tubes

    the water converted into steam. The calculations of reliability, failure rate, probability density

    functions are listed in below table and graphs for variation of reliability, failure rate and f(t) are

    shown with respect to time as shown in table 5.1

    Table 5.1 Reliability analysis for boiler-1 tube

    Time

    No. of

    failures

    No. of

    survivals Reliability Failure rate Probability

    density

    function

    0 0 11 1 0.0075 0.0075

    12 1 10 0.9 0.0303 0.0336

  • 8/11/2019 reliability and temperature evaluation of boilers

    37/91

    37

    24 4 6 0.54 0.015 0.027

    36 2 4 0.36 0.0075 0.0208

    48 1 3 0.27 0.0075 0.0277

    After calculation of reliability, failure rate and f(t) for boiler-1 tubes, results are plotted.

    Reliabilty Graph:

    Fig 5.1:Reliabilty Graph for boiler tubes

    Fig 5.1 shows that the reliability of boiler-1 tube decreases with time.

    Failure Rate Graph:

    Fig 5.2: Failure rate graph of boiler-1 tube

    Fig 5.2 shows that the failure rate is increasing with time upto some time after that it decreases.

  • 8/11/2019 reliability and temperature evaluation of boilers

    38/91

    38

    Probability Density Function Graph:

    Fig 5.3: Probability density function graph for boiler-1 tube

    Fig 5.3 shows the variation of Probability density function with respect to time. Probability

    density function increases with time.

    5.3 RELIABILITY ANALYSIS OF BOILER-2 TUBES:

    Here we use water tube boilers it is a type of boiler in which water circulates in tubes heated

    externally by the fire. Fuel is burned inside the furnace, creating hot gas which heats water in the

    steam-generating tubes. In smaller boilers, additional generating tubes are separate in the

    furnace, while larger utility boilers rely on the water-filled tubes that make up the walls of the

    furnace to generates steam. The calculations of reliability, failure rate, probability density

    functions are listed in below table and graphs for variation of reliability, failure rate and f(t) are

    shown with respect to time as shown below.

    Table 5.2: Reliability analysis for boiler-2 tube

    Time No.of

    failures

    No.of

    Survivals Reliability Failure rate Probability

    density

    function

    0 0 15 1 0.0222 0.0222

    12 4 11 0.73 0.0277 0.0379

    24 5 6 0.4 0.00606 0.01515

    36 1 5 0.33 0.00606 0.0183

    48 1 4 0.26 0.0166 0.0638

  • 8/11/2019 reliability and temperature evaluation of boilers

    39/91

    39

    After calculation of reliability, failure rate and f(t) ,Probability density function for boiler-2 tubes

    results are plotted in graph.

    Reliabilty Graph:

    Fig 5.4: Reliabilty Graph for boiler-2 tube

    From fig 4.4 we found that reliability for boiler-2 tube decreases with time.

    Failure Rate Graph:

    Fig 5.5: Failure rate graph for boiler tube-2From Fig 5.5 we observe that failure rate increases for some time after that it decreases with

    time.

  • 8/11/2019 reliability and temperature evaluation of boilers

    40/91

    40

    Probability Density Function Graph:

    Fig 5.6: Failure density graph for Boiler-2 Tube

    Above figure shows that Probability density function increases with time.

    5.4 RELIABILITY ANALYSIS OF BOILER-3 TUBES:

    Table 5.3:Reliability analysis for Boiler-3 tube

    Time No.of

    Failures

    No.of

    survivals Reliability Failure rate Probability

    density

    function

    0 0 6 1 0.0277 0.0277

    12 2 4 0.666 0.0138 0.0207

    24 1 3 0.5 0.0138 0.0276

    36 1 2 0.333 0.0138 0.0414

    48 1 1 0.166 0.0138 0.0828

    After calculation of reliability, failure rate and f(t) ,Probability density function for boiler-3 tubes

    results are plotted

  • 8/11/2019 reliability and temperature evaluation of boilers

    41/91

    41

    Reliabilty Graph :

    Fig 5.7: Reliabilty Graph for boiler 3 tube

    From fig 5.7 we found that reliability for boiler tube decreases with time.

    Failure Rate Graph:

    Fig 5.8: Failure rate graph for Boiler-3 tube

    From fig 5.8 we found that failure rate for boiler tube decreases with time for some time period

    after that it is constant.

  • 8/11/2019 reliability and temperature evaluation of boilers

    42/91

    42

    Probability Density Function Graph:

    Fig 5.9: Probability density function graph for Boiler-3 tubeFrom fig 5.9 shows variations in rhe Probability density function with time and it is increases

    with time.

    5.5 RELIABILITY ANALYSIS OF BOILER-4 TUBES:

    Table 5.4 Reliability analysis for boiler-4 tube

    Time No. of

    failures

    No. of

    survivals

    Reliability Failure rate Probability

    density

    function

    0 0 11 1 0.0075 0.0075

    12 1 10 0.909 0.0151 0.0166

    24 2 8 0.727 0.0151 0.0207

    36 2 6 0.545 0.0378 0.0693

    48 5 1 0.0909 0.0075 0.0833

    After calculation of reliability, failure rate and f(t) ,Probability density function for

    boiler-4 tubes results are plotted in graphs.

  • 8/11/2019 reliability and temperature evaluation of boilers

    43/91

    43

    Reliabilty Graph:

    Fig 5.10: Reliabilty Graph for boiler-4 tube

    From fig 5.10 we found that Reliability for boiler tube decreases with time.

    Failure Rate Graph:

    Fig 5.11: Failure rate graph for boiler-4 tube

    From the fig 5.11 it is found that the failure rates are increases for some time period and after

    that it decreases.

  • 8/11/2019 reliability and temperature evaluation of boilers

    44/91

    44

    Probability Density Function Graph:

    Fig 5.12: Probability density function graph for Boiler-4 tube

    From the fig 5.12 it is found that the failure rate increases with time.

    5.6 RELIABILITY ANALYSIS OF BOILER-5 TUBES:

    Table 5.5: Reliability analysis for Boiler-5 tube

    Time No. of

    failures

    No.of

    survivals

    Reliability Failure rate Probability

    density

    function

    0 0 10 1 0.016 0.01612 2 8 0.8 0.025 0.031

    24 3 5 0.5 0.025 0.05

    36 3 2 0.2 0.0083 0.041

    48 1 1 0.1 0.0083 0.083

    After calculation of reliability, failure rate and f(t) ,Probability density function for

    boiler-5 tubes results are plotted in graphs.

  • 8/11/2019 reliability and temperature evaluation of boilers

    45/91

    45

    Reliabilty Graph:

    Fig 5.13: Reliabilty Graph for boiler -5 tubeFrom fig 5.13 we found that Reliability for boiler tubes decreases with time.

    Failure Rate Graph:

    Fig 5.14: Failure rate graph for boiler-5 tube

    From the fig 5.14 it is found that the failure rate increases with time for some period and after

    that it decreases.

  • 8/11/2019 reliability and temperature evaluation of boilers

    46/91

    46

    Probability Density FunctionGraph:

    Fig 5.15: Probability density function graph for boiler-5 tube

    Fig 5.15 shows the variation of Probability density function with respect to time and it is

    increases with time.

    5.7 SYSTEM RELIABILITY USING EMPERICAL METHOD:

    System Availability is calculated by modeling the system as an interconnection of parts

    in series and parallel. The following rules are used to decide if components should be placed in

    series or parallel:

    If failure of a part leads to the combination becoming inoperable, the two parts are

    considered to be operating in series

    If failure of a part leads to the other part taking over the operations of the failed part, the

    two parts are considered to be operating in parallel.

    (1) Reliability in Series

    As stated above, two parts X and Y are considered to be operating in series if failure of either of

    the parts results in failure of the combination. The combined system is operational only if both

    Part X and Part Y are available. From this it follows that the combined reliability is a product of

    the reliability of the two parts. The combined reliability is shown by the equation below:

  • 8/11/2019 reliability and temperature evaluation of boilers

    47/91

    47

    (2) Reliability in Parallel:

    Two parts are considered to be operating in parallel if the combination is considered

    failed when both parts fail. The combined system is operational if either is available. From this

    it follows that the combined reliability is 1 - (both parts are unavailable). The combined

    reliability is shown by the equation

    Combined series parallel Operation :

    In such systems where failure of a component leads to some users loosing service, system

    reliability has to be defined by considering the percentage of users affected by the failure. The

    reliability for this system can be computed by calculating A(p,q) as specified below:

    A(p,q) = C(q,p) * A^(q-p) * (1-A)^p

    Here pis the number of failed units and qis the total number of units.

    The present system is system of combined series and parallel systems and the Reliability Block

    Diagram for the present processing industry is as follows:

    Fig 5.13 Reliability Block Diagram for WATER TUBE BOILERS IN TPP using empiricalmethod.

  • 8/11/2019 reliability and temperature evaluation of boilers

    48/91

    48

    BOILER-1 BOILER-2 BOILER-3 BOILER-4

    BOILER-5

    Fig 5.16: boilers in series

    E1 = The event that component 1 does not fail

    E2 = The event that component 2 does not fail

    Then P(E1)=R1 and P(E2)=R2

    Where R1= The reliability of component 1

    Where R2= The reliability of component 2

    Therefore Rs = P(E1E2) = P(E1) P(E2) =R1 R2 assuming that the two components are

    independent.

    Generalizing to n mutually independent components in series, then

    Rs(T) = R1(t)*R2(t)**Rn(t) < min {R1(t),R2(t),,Rn(t)}

    Generalizing to n mutually independent components in parallel, then

    Rs=P(E1UE2) = 1- P(E1UE2)c

    = 1-P((E1cUE2

    c) = 1-P((E1

    c)P(E2

    c)) = 1-(1-R1)(1-R2)

    For combined series and parallel systems both these formulas are used.The System Reliability is calculated as follows:

    For boiler-1 tube:

    R(1)=0.614

    For boiler-2 tube:

    R(2)= 0.5464

    For boiler-3 tube:

    R(3)= 0.533

    For boiler-4 tube:

    R(4)= 0.654

    For boiler-5 tube:

    R(5)= 0.5234

  • 8/11/2019 reliability and temperature evaluation of boilers

    49/91

    49

    The complete system is now in combined series and parallel combination system. So, the system

    reliability is given as:

    R(s)= [R(1)R(5)]* [R(2)R(5)]*[R(3)R(5)]*[R(4)R(5)]

    =[1-(1-R(1))(1-R(5)]*[1-(1-R(2)(1-R(5)]*[1-(1-R(3))(1-R(5)]*[1-(1-R(4)(1-R(5)]

    =0.816*0.783*0.777*0.835 = 0.4113

    It is found from the above analysis by using empirical method the system reliability is 0.4113.

  • 8/11/2019 reliability and temperature evaluation of boilers

    50/91

    50

    CHAPTER 6

    RELIABILITY EVALUATION BY

    PARAMETRIC METHOD

  • 8/11/2019 reliability and temperature evaluation of boilers

    51/91

    51

    6.1 INTRODUCTION TO PARAMETRIC METHOD:

    In this work the next step is to evaluate the system reliability using parametric method.

    In parametric method there are four types of distributions which are explained as follows.1) Normal Distribution

    2) Lognormal Distribution

    3) Exponential Distribution

    4) Weibull method

    6.1.1 Introduction to Normal Distribution:

    In probability theory, the normal (or Gaussian) distribution is a continuous

    probability distribution that has a bell-shaped probability density function, known as the

    Gaussian function or informally the bell curve.

    Where parameter is the mean or expectation (location of the peak) and is the variance.

    is known as the standard deviation. The distribution with = 0 and 2 = 1 is called the

    standard normal distribution or the unit normal distribution. A normal distribution is often used

    as a first approximation to describe real-valued random variables that cluster around a single

    mean value. The normal distribution is considered the most prominent probability distribution in

    statistics. There are several reasons for this:[1] First, the normal distribution is very tractable

    analytically, that is, a large number of results involving this distribution can be derived in

    explicit form. Second, the normal distribution arises as the outcome of the central limit theorem,

    which states that under mild conditions the sum of a large number of random variables is

    distributed approximately normally. Finally, the "bell" shape of the normal distribution makes it

    a convenient choice for modelling a large variety of random variables.

    The probability density function (pdf) of a random variable describes the relative frequencies of

    different values for that random variable. The pdf of the normal distribution is given by the

    formula explained in detail in the previous section:

  • 8/11/2019 reliability and temperature evaluation of boilers

    52/91

    52

    This is a proper function only when the variance 2 is not equal to zero. In that case this

    is a continuous smooth function, defined on the entire real line, and which is called the

    "Gaussian function".

    Properties:

    Function f(x) is uni modal and symmetric around the point x = , which is at the same

    time the mode, the median and the mean of the distribution.

    The inflection points of the curve occur one standard deviation away from the mean (i.e., at x =

    and x = + ).

    Function f(x) is log-concave.

    The standard normal density (x) is an Eigen function of the Fourier transform.

    The function is super smooth of order 2, implying that it is infinitely differentiable. The first

    derivative of (x) is (x) = x(x); the second derivative is (x) = (x2 1)(x). More

    generally, the nth

    derivative is given by (n)(x) = (1)nH

    n(x)(x), where Hn is the Hermite

    polynomial of order n

    6.1.2 Introduction to Lognormal Distribution:

    In probability theory, a log-normal distribution is a continuous probability distribution of

    a random variable whose logarithm is normally distributed. If X is a random variable with a

    normal distribution, then Y = exp(X) has a log-normal distribution; likewise, if Y is log-normallydistributed, then X = log(Y) is normally distributed. (This is true regardless of the base of the

    logarithmic function: if log(Y) is normally distributed, then so is logb(Y), for any two positive

    numbers a, b 1.)Log-normal is also written log normal or lognormal. It is occasionally referred

  • 8/11/2019 reliability and temperature evaluation of boilers

    53/91

    53

    astheGaltondistributionor,Galton'sdistribution.

    6.1.3 Introduction to Exponential Distribution:

    In probability theory and statistics, the exponential distribution (a.k.a. negative

    exponential distribution) is a family of continuous probability distributions. It describes the time

    between events in a Poisson process, i.e. a process in which events occur continuously and

    independently at a constant average rate.

    Note that the exponential distribution is not the same as the class of exponential families ofdistributions, which is a large class of probability distributions that includes the exponential

    distribution as one of its members, but also includes the normal distribution, binomial

    distribution, gamma distribution, Poisson, and many others.

  • 8/11/2019 reliability and temperature evaluation of boilers

    54/91

    54

    6.1.4 Introduction to Weibull method:

    In probability theory and statistics, the Weibull distribution is a continuous probability

    distribution. It is named after WaloddiWeibull, who described it in detail in 1951, although itwas first identified by Frchet (1927) and first applied by Rosin &Rammler (1933) to describe

    the size distribution of particles.

    The probability density function of a Weibull random variable x is:

    where k > 0 is the shape parameter and > 0 is the scale parameter of the distribution. Its

    complementary cumulative distribution function is a stretched exponential function. The Weibull

    distribution is related to a number of other probability distributions; in particular, it interpolates

    between the exponential distribution (k = 1) and the Rayleigh distribution (k = 2).

  • 8/11/2019 reliability and temperature evaluation of boilers

    55/91

  • 8/11/2019 reliability and temperature evaluation of boilers

    56/91

    56

    Fig 6.1 :Probability Distribution fitting curve for boiler-1 tube

    The parameters obtained from the above figure are =0.5342, =2.0123by using

    these parameters reliability, failure rate and f(t) have been calculated according to Weibull

    distribution. And results have been shown in table.

    Table 6.1: Reliability of boiler-1 tube

    time number of

    failures

    reliability failure rate f(t)

    0 0 1 0.265 0.265

    12 1 0.873 0.100 0.115

    24 4 0.43 0.035 0.083

    36 2 0.32 0.022 0.069

    48 1 0.15 0.009 0.060

    By using the obtained results the graphs have been plotted for reliability, failure rate and

    probability distribution with respect to time.

  • 8/11/2019 reliability and temperature evaluation of boilers

    57/91

    57

    Reliability Graph:

    Fig 6.2: Reliabilty Graph for boiler tube using Parametric method

    Here from fig we can observe that reliability decreases with increase of time.

    Failure Rate Graph:

    We take the values from table and drawn the graph between failure rate and time.

    Fig 6.3 Failure rate graph for boiler tube using parametric method

    From figure 6.3 we can say that failure rate decreases with time increases.

  • 8/11/2019 reliability and temperature evaluation of boilers

    58/91

    58

    Probability Density Function Graph:

    Fig 6.4: Probability density function graph for boiler-1 tube using Parametricmethod

    From the above figure graphical analysis it is observed that reliability is decreases as the

    time increase.

    6.3 PARAMETRIC ANALYSIS OF BOILER-2 TUBES:

    Fig 6.5 :Probability Distribution fitting curve for boiler-2 tube

    The parameters obtained from the above figure are =0.4982, =2.6322 by using

    these parameters reliability, failure rate and f(t) have been calculated according to Weibull

    distribution. And results have been shown in table.

  • 8/11/2019 reliability and temperature evaluation of boilers

    59/91

    59

    Table 6.2 reliability analysis of boiler-2 tube using parametric method

    time number of

    failures

    reliability failure rate f(t)

    0 0 1 0.1891 0.1891

    12 3 0.75 0.0666 0.0883

    24 4 0.45 0.0280 0.0623

    36 2 0.35 0.0177 0.0508

    48 1 0.28 0.0123 0.0440

    By using the obtained results the graphs have been plotted for reliability, failure rate and

    probability distribution with respect to time.

    Reliability Graph:

    Fig 6.6 Reliabilty Graph for boiler-2 tube using parametric method

    Fig 6.6 shows the reliability decreases with increases in time.

  • 8/11/2019 reliability and temperature evaluation of boilers

    60/91

    60

    Failure Rate Graph:

    Fig6.7 Failure rate graph for boiler-2 tube using parametric method

    Here observe that failure rate decreases with time increases.

    Probability Density Function Graph:

    From table 6.2 drawn the graph between Probability density function and time in months.

    Fig 6.8: Probability density function graph for boiler-2 tube using Parametric method

    From the above graphical analysis it is observed that Probability density function is

    decreases as the time increase.

  • 8/11/2019 reliability and temperature evaluation of boilers

    61/91

    61

    6.4 PARAMETRIC ANALYSIS OF BOILER-3 TUBES:

    Fig 6.9 :Probability Distribution fitting curve for boiler-3 tube

    The parameters obtained from the above figure are =0.6598, =1.1129 by using these

    parameters reliability, failure rate and f(t) have been calculated according to Weibull distribution.

    And results have been shown in table.

    Table 6.3 reliability analysis of boiler-3 tube using parametric method

    Time number of

    failures

    reliability failure rate f(t)

    0 0 1 0.5921 0.5921

    12 2 0.69 0.1815 0.2631

    24 3 0.55 0.1142 0.2077

    36 2 0.37 0.0664 0.1809

    48 1 0.24 0.0328 0.1640

    By using the obtained results the graphs have been plotted for reliability, failure rate and

    Probability density function with respect to time.

  • 8/11/2019 reliability and temperature evaluation of boilers

    62/91

    62

    Reliabilty Graph:

    Fig 6.10 Reliabilty Graph for boiler-3 tube using parametric methodHere the reliability is decreases with time.

    Failure Rate Graph:

    Fig 6.11 Failure graph for boiler-3 tube using Parametric method

    Here failure rate decreases with time.

  • 8/11/2019 reliability and temperature evaluation of boilers

    63/91

    63

    Probability Density Function:

    Fig 6.12 Probability density function graph for boiler-3 tube using parametric method

    Here Probability density function decreases with increase in time.

    6.5 PARAMETRIC ANALYSIS OF BOILER-4 TUBES:

    Fig 6.13 :Probability Distribution fitting curve for boiler-4 tube

    The parameters obtained from the above figure are =0.5354, =1.947 by using these

    parameters reliability, failure rate and f(t) have been calculated according to Weibull distribution.

    And results have been shown in table.

  • 8/11/2019 reliability and temperature evaluation of boilers

    64/91

    64

    Table 6.4: Reliability analysis of boiler-4 tube

    time number of

    failures

    Reliability failure rate f(t)

    0 0 1 0.274 0.2741

    12 2 0.925 0.108 0.1178

    24 3 0.752 0.064 0.0854

    36 2 0.602 0.042 0.0707

    48 1 0.152 0.009 0.0619

    Reliabilty Graph:

    Fig 6.14 Reliabilty Graph for boiler-4 tube using parametric method

    Fig 6.14 shows the reliability decreases with time

    Failure Rate Graph :

  • 8/11/2019 reliability and temperature evaluation of boilers

    65/91

    65

    Fig 6.15 Reliabilty Graph for boiler-4 tube using parametric method

    Fig 6.15 shows failure rate decreases with time

    Probability Density Function Graph:

    Fig 6.16 Probability density function Graph for boiler-4 tube using parametric method

    Fig 6.16 shows the Probability density function decreases with time

    6.5 PARAMETRIC ANALYSIS OF BOILER-5 TUBES:

    Fig 6.17:Probability Distribution fitting curve for boiler-5 tube

    The parameters obtained from the above figure are =0.5536, =1.8559 by using these

    parameters reliability, failure rate and f(t) have been calculated according to Weibull distribution.

    And results have been shown in table.

  • 8/11/2019 reliability and temperature evaluation of boilers

    66/91

    66

    Table 6.4 Reliability of boiler-5 tube using parametric method

    Time Number of

    failures

    Reliability Failure rate Probability

    density function

    0 0 1 0.298 0.298

    12 2 0.87 0.112 0.129

    24 3 0.62 0.058 0.094

    36 3 0.26 0.020 0.079

    48 1 0.12 0.088 0.689

    From the table we have drawn the graphs between time and reliability,failure rate, hazard rate

    Reliabilty Graph:

    Fig6.18 Reliabilty Graph for boiler-5 tube using parametric method

    Here reliability decreases with time.

    Failure Rate Graph:

  • 8/11/2019 reliability and temperature evaluation of boilers

    67/91

    67

    Fig 6.19 failure rate Graph for boiler-5 tube using parametric method

    Here failure rate decreases with increase of time

    Probability Density Function Graph:

    Fig 6.20 Probability density function Graph for boiler-5 tube using parametric method

    Here Probability density function decreases and then increases with increase of time

    6.10 SYSTEM RELIABILITY USING PARAMETRIC METHOD:

    E1 = The event that component 1 does not fail

    E2 = The event that component 2 does not fail

    Then P(E1)=R1 and P(E2)=R2

    Where R1=the reliability of component 1

    Where R2=the reliability of component 2

    Therefore Rs = P(E1E2) = P(E1) P(E2) =R1 R2 assuming that the two components are

    independent.

    Generalizing to n mutually independent components in series, then

    Rs(T) = R1(t)*R2(t)**Rn(t) < min {R1(t),R2(t),,Rn(t)}

    Generalizing to n mutually independent components in parallel, then

    Rs=P(E1UE2) = 1- P(E1UE2)c = 1-P((E1cUE2c

    = 1-P((E1c)P(E2c)) = 1-(1-R1)(1-R2)

    For combined series and parallel systems both these formulas are used.

    The System Reliability is calculated as follows:

    For boiler-1 tubes

  • 8/11/2019 reliability and temperature evaluation of boilers

    68/91

    68

    R(1)=

    For boiler-2 tubes

    R(2)=0.4059

    For boiler-3 tubes

    R(3)=

    For boiler-4 tubes

    R(4)=Total system reliability R(s) = [R(1)R(5)]* [R(2)R(5)]*[R(3)R(5)]*[R(4)R(5)]

    =[1-(1-R(1))(1-R(5)]*[1-(1-R(2)(1-R(5)]*[1-(1-R(3))(1-R(5)]*[1-(1-R(4)(1-R(5)]

    =

    6.12 COMPARITIVE ANALYSIS BETWEEN EMPIRICAL AND PARAMETRIC

    METHODS:

    In this work a comparative analysis have been performed between empirical method and

    parametric method to identify which method is best suitable and all the machines reliabilities

    which are calculated as earlier are shown below.

    Comparison of reliability:

    Table 6.6 Comparison of Reliability by Empirical and Parametric methods

    S.NO

    NUMBER OF

    BOILER TUBES

    RELIABILITY BY

    EMPIRICAL

    METHOD

    RELIABILITY BY

    PARAMETRIC

    METHOD

    1 BOILER-1 TUBE 0.614 0.564

    2 BOILER-2 TUBE 0.5464 0.567

    3 BOILER-3 TUBE 0.5334 0.562

    4 BOILER-4 TUBE 0.654 0.686

    5 BOILER-5 TUBE 0.528 0.588

  • 8/11/2019 reliability and temperature evaluation of boilers

    69/91

    69

    Boiler tube-1:

    Fig 6.21 Comparison of reliability for boiler-1 tube

    Figure shows the reliability of boiler-1 tube. Here reliability by the empirical method is more

    than the reliability by parametric method.

    Boiler-2 tube:

    Fig 6.22 Comparison of reliability for boiler-2 tube

    Figure shows the reliability of boiler-2 tube. Here reliability by the parametric method is more

    empirical than the reliability by method.

  • 8/11/2019 reliability and temperature evaluation of boilers

    70/91

    70

    Boiler-3 Tube:

    Fig 6.23 Comparison of reliability for boiler-3 tube

    Figure shows the reliability of boiler-2 tube. Here reliability by the parametric method is more

    empirical than the reliability by method.

    Boiler-4 Tube:

    Fig 6.24 Comparison of reliability for boiler-1 tube

    Figure shows the reliability of boiler-2 tube. Here reliability by the parametric method is more

    empirical than the reliability by method.

  • 8/11/2019 reliability and temperature evaluation of boilers

    71/91

    71

    Boiler-5 Tube:

    Fig 6.25 Comparison of reliability for boiler-1 tube

    Figure shows the reliability of boiler-2 tube. Here reliability by the parametric method is more

    empirical than the reliability by method.

    Comparison of failure rates:

    Table 6.7 Comparison of Failure rates by Empirical and Parametric methods

    S.NO NUMBER OF THE

    BOILER TUBES

    FAILURE RATE BY

    EMPIRICAL

    METHOD

    FAILURE RATE BY

    PARAMETRIC

    METHOD

    1 BOILER-1 TUBE 0.01646 0.0552

    2 BOILER-2 TUBE 0.01663 0.0409

    3 BOILER-3 TUBE 0.0829 0.1188

    4 BOILER-4 TUBE 0.01662 0.05605

    5 BOILER-5 TUBE 0.01653 0.06158

    Table shows the failure rates of boiler tube by empirical and parametric methods and failure

    rates values more by the parametric method.

  • 8/11/2019 reliability and temperature evaluation of boilers

    72/91

    72

    Comparison of Probability density functions:

    Table 6.8 Comparison of Probability density functions Empirical and Parametric methods

    S.NO NUMBER OF THE

    BOILERS TUBES

    f(t) BY

    EMPIRICAL

    METHOD

    f(t)

    BY PARAMETRIC

    METHOD

    1 BOILER-1 TUBE

    2 BOILER-2 TUBE

    3 BOILER-3 TUBE

    4 BOILER-4 TUBE

    5 BOILER-5 TUBE

    Table shows the Probability density functions of boiler tube by using both empirical and

    parametric methods and it shows the values are high in parametric method.

    System reliability:Table 6.9 System reliability of boilers

    RELIABILITY ANALYSIS SYSTEM RELIABILITY

    Using Empirical method 0.4114

    Using parametric method 0.4722

    Table 6.9. shows that the system reliability of boiler tubes is more by the parametric method and

    from this it can conclude that the parametric method is the best method when compared to

    empirical method for system reliability evaluation process.

  • 8/11/2019 reliability and temperature evaluation of boilers

    73/91

    73

    CHAPTER 7

    INTRODUCTION TO ANSYS

  • 8/11/2019 reliability and temperature evaluation of boilers

    74/91

    74

    ANSYS:

    ANSYS is general-purpose finite element analysis (FEA) software package. Finite

    Element Analysis is a numerical method of deconstructing a complex system into very small

    pieces (of user-designated size) called elements. The software Implements equations that go