SCHOOL OF ELECTRICAL ENGINEERING
1
Power System Simulation Lab (Experiment No: Six) Relay Co-ordination for a Sample Distribution System (radial)
System Details: 5 Buses, 4 transmission line section, a Generator and 4relays (IDMT-directional)
The relay make is as follow s Relay rated current = 5 Amps Plug setting = 50% to 250% in steps of 25% Time setting multiplier = 0.05 to 1.0 in steps of 0.01 Relay details
Relay Name R1 R2 R3 R4Primary Rating (1,2,3,4) 800 400 200 100Secondary Rating 5 5 5 5Load Current 800 400 200 100Relay type 3sec 3sec 3sec 3sec
Transmission line details on 100 MVA base: Bus - code Impedance Zpq Line charging
p-q Zpq Y'pq/21-2 0.00 + j0.1 02-3 0.00 + j0.1 03-4 0.00 + j0.1 04-5 0.00 + j0.1 0
Generator Details : G1 = 100 MVA, 11kV Maximum fault level = 1000 MVA. Interpretation according to MiPower :
Observe transmission line details. You find that all lines have similar parameters. Therefore no. oftransmission line libraries = 1
No of generator libraries = 1 As all the relays are of 3 sec type, no of relay libraries = 1
Procedure to enter the data for performing studies using MiPower.
MiPower - Database Configuration Open power system network editor. Select menu option Database Configure . Configure Database dialog is popped up as shown below. Click Browse button.
SCHOOL OF ELECTRICAL ENGINEERING
2
SCHOOL OF ELECTRICAL ENGINEERING
3
SCHOOL OF ELECTRICAL ENGINEERING
4
SCHOOL OF ELECTRICAL ENGINEERING
5
SCHOOL OF ELECTRICAL ENGINEERING
6
Procedure to Draw Relay Click on Directional IDMT Relay icon provided on tool bar or from main menu select
Power system Relays Directional IDMT Put it on the transmission line as shown below
SCHOOL OF ELECTRICAL ENGINEERING
7
Then hold ctrl and click on Bus 1, which invokes database manager
Select menu option Libraries Protection Relay Database Points to Note: Relay rated current = 5 Amps Current setting Max = 250 % of % 5 amps = 2.5 x 5 = 12.5 Min = 50 % of % 5 amps = 0.5 x 5 = 2.5 Uniform variation step = 0.25
SCHOOL OF ELECTRICAL ENGINEERING
8
Enter time dial setting as below
Time setting multiplier = 0.05 to 1.0 in steps of 0.01 Relay Element Details From main menu select Element Relays Over Current Relay Click “ADD “button And enter the details
SCHOOL OF ELECTRICAL ENGINEERING
9
Enter all the four relays details. Click on To Network button which takes control to Network Editor. Executing Over Current Relay Co - ordination Select the menu option Solve Over Current Relay Co-ordination
SCHOOL OF ELECTRICAL ENGINEERING
10
SCHOOL OF ELECTRICAL ENGINEERING
11
SCHOOL OF ELECTRICAL ENGINEERING
12
The relay co - ordination will be executed. Go to graph and plot Current in X - axis and Time in Y - Axis.
Inference: