10
Relay Connection For 1. 4G Reader 2. 4G Lite Reader 3. Sigma Reader 4. Sigma Lite Reader 1. 4G Relay Connection 4G’s has 170 Ma ability Relay needs to be turn on via Software (Single door Access Control in Secure Admin) ***If you don’t have a door connect then tie 20( Blue/Brown) and 25(White/Green) together**

Relay Connection For - MorphoTrakservice.morphotrak.com/content/Documents/Connection of... · 2016. 10. 26. · Relay Connection For 1. 4G Reader 2. 4G Lite Reader 3. Sigma Reader

  • Upload
    others

  • View
    8

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Relay Connection For - MorphoTrakservice.morphotrak.com/content/Documents/Connection of... · 2016. 10. 26. · Relay Connection For 1. 4G Reader 2. 4G Lite Reader 3. Sigma Reader

Relay Connection For

1. 4G Reader

2. 4G Lite Reader

3. Sigma Reader

4. Sigma Lite Reader

1.

4G Relay Connection

4G’s has 170 Ma ability

Relay needs to be turn on via Software (Single door Access Control in Secure Admin)

***If you don’t have a door connect then tie 20( Blue/Brown) and 25(White/Green) together**

Page 2: Relay Connection For - MorphoTrakservice.morphotrak.com/content/Documents/Connection of... · 2016. 10. 26. · Relay Connection For 1. 4G Reader 2. 4G Lite Reader 3. Sigma Reader

1.

4G with a External Relay

4G’s has 170 Ma ability

Relay needs to be turn on via Software (Single door Access Control in Secure Admin)

***If you don’t have a door connect then tie 20(Blue/Brown) and 25(White/Green) together***

***The External relay and 4G device needs to be on separate power supply***

Page 3: Relay Connection For - MorphoTrakservice.morphotrak.com/content/Documents/Connection of... · 2016. 10. 26. · Relay Connection For 1. 4G Reader 2. 4G Lite Reader 3. Sigma Reader

1.

4G Relay Connection with Motion Detector or Push Button

***If you don’t have a door connect then tie 20(Blue/Brown) and 25(White/Green) together***

18(yellow\Blue) and 21(yellow\Black) for your Motion Detector or Push button

Relay needs to be turn on via Software (Single door Access Control in Secure Admin)

Page 4: Relay Connection For - MorphoTrakservice.morphotrak.com/content/Documents/Connection of... · 2016. 10. 26. · Relay Connection For 1. 4G Reader 2. 4G Lite Reader 3. Sigma Reader

2.

4G Lite Relay Connection

4G Lite has 1 amp ability

Relay needs to be turn on via Software (Single door Access Control in Secure Admin or Access Control in Secure Admin Lite)

***If you don’t have a door connect then tie 13( Yellow/Blue) and 9(White/Red) together***

Page 5: Relay Connection For - MorphoTrakservice.morphotrak.com/content/Documents/Connection of... · 2016. 10. 26. · Relay Connection For 1. 4G Reader 2. 4G Lite Reader 3. Sigma Reader

2.

4G Lite with a External Relay

4G Lite has 1 amp ability

Relay needs to be turn on via Software (Single door Access Control in Secure Admin or Access Control in Secure Admin Lite)

***If you don’t have a door connect then tie 13( Yellow/Blue) and 9(White/Red) together***

***The External relay and 4G Lite device needs to be on separate power supply***

Page 6: Relay Connection For - MorphoTrakservice.morphotrak.com/content/Documents/Connection of... · 2016. 10. 26. · Relay Connection For 1. 4G Reader 2. 4G Lite Reader 3. Sigma Reader

2.

4G Lite with Motion Detector or Push Button

4G Lite has 1 amp ability

Relay needs to be turn on via Software (Single door Access Control in Secure Admin or Access Control in Secure Admin Lite)

Wire 15, Blue/Brown and Wire 9, White/Red for Push button or Motion dectector

Page 7: Relay Connection For - MorphoTrakservice.morphotrak.com/content/Documents/Connection of... · 2016. 10. 26. · Relay Connection For 1. 4G Reader 2. 4G Lite Reader 3. Sigma Reader

3.

Sigma Reader Relay

Please use an External power supply for your deadbolt or Door strike

Internal Relay not active from Factory and would need to be turn on via LCD screen or software (Biometric Device Profile in Morpho Manager)

Internal relay is rated for 2 Amps

Relay_1 and Relay_2 for Door strike

If no door contact being used GPI1 and GPO1 needs to connected together

Page 8: Relay Connection For - MorphoTrakservice.morphotrak.com/content/Documents/Connection of... · 2016. 10. 26. · Relay Connection For 1. 4G Reader 2. 4G Lite Reader 3. Sigma Reader

3.

Sigma Reader Sigma with Push Button and Door Contact

Relay_1 and Relay_2 for Door strike

GPO0 and GPI0 for push Button

Internal Relay not active from Factory and would need to be turn on via LCD screen or software for any control (Biometric Device Profile in Morpho Manager)

If no door contact being used GPI1 and GPO1 needs to connected together

Page 9: Relay Connection For - MorphoTrakservice.morphotrak.com/content/Documents/Connection of... · 2016. 10. 26. · Relay Connection For 1. 4G Reader 2. 4G Lite Reader 3. Sigma Reader

4.

Sigma Lite Relay

Please use an External power supply for your deadbolt or Door strike

Internal Relay not active from Factory and would need to be turn on via software (Biometric Device Profile in Morpho Manager)

Internal relay is rated for 1 Amps

19-Relay_NO Yellow

21-Relay_NC Orange

22-Relay_Comm Grey

If no door contact being used GPI_2(Orange/Red) and GPO_2 (Yellow/Red) needs to be connected together

Page 10: Relay Connection For - MorphoTrakservice.morphotrak.com/content/Documents/Connection of... · 2016. 10. 26. · Relay Connection For 1. 4G Reader 2. 4G Lite Reader 3. Sigma Reader

4.

Sigma Lite Relay (with Push Button)

Relay_1 and Relay_2 for Door strike

GPI_0 (yellow)and GPO_0 (yellow)for push Button

Internal Relay not active from Factory and would need to be turn on via software (Biometric Device Profile in Morpho Manager)

Label and documenation are incorrect for push button and door contact

If no door contact being used wire 10(Orange/Red) and wire 12 (Yellow/Red) needs to be connected together

Wire 9 (Orange) and Wire 11 (Yellow) are for the push button