System Details 313470776.xls 1/42 LINE NAME : MYV-1 SUBSTATION : PONNAPURAM 230KV SS Select the Terminal REL670 NOTE: Open File by Enabling MACROS Fill in the BLUE Cells SYSTEM PARTICULARS A Line Parameters 1 Rated Line Voltage in KV 220 2 Line Length in kms 36.5 3 Max. Power Flow in the Line in MVA 165.00 433 4 Positive seqence Resistance in ohms/km 0.081 5 Positive Sequence Reactance in ohms/km 0.4 6 Zero sequence Resistance in ohms/km 0.275 7 Zero sequence reactance in ohms/km 1.275 8 Zero Sequence Mutual Impedance % 9 Zero Sequence Mutual Resistance in ohms/km 0 0 10 Zero Sequence Mutual Reactance in ohms/km 0 0 11 XC-Reactance of Series Capacitor B Adjoining Line Parameters a) Shortest Line 1 Length of shortest line in kms 6 2 Positive Sequence Resistance in ohms/km 0.081 3 Positive Sequence Reactance in ohms/km 0.4 4 Zero Sequence Resistance in ohms/km 0.275 5 Zero sequence Reactance in ohms/km 1.275 b) Longest Line 1 Length of longest line 132 2 Positive Sequence Resistance in ohms/km 0.081 3 Positive Sequence Reactance in ohms/km 0.4 4 Zero Sequence Resistance in ohms/km 0.275 5 Zero sequence Reactance in ohms/km 1.275 c) Transformer 1 Transformer MVA 0 2 Percentage Reactance in p.u. 0 3 Positive Sequence Reactance in ohms 0 4 Zero sequence Reactance in ohms 0 d) Shortest Line (Reverse) 1 Length of shortest line in kms 5 2 Positive Sequence Resistance in ohms/km 0.081 3 Positive Sequence Reactance in ohms/km 0.4 4 Zero Sequence Resistance in ohms/km 0.275 5 Zero sequence Reactance in ohms/km 1.275 C Source Impedance 1 FAULT MVA at Local-End 700 2 FAULT MVA at Remote-End 222 3 Source impedance angle in deg 80 (Assumed) 4 Angle in radians 1.397 5 Positive Sequence Resistance at local end, in ohms 11.968 6 Positive Sequence Reactance at local end, in ohms 68.099 7 Positive Sequence Resistance at remote end, in ohms 37.738 8 Positive Sequence Reactance at remote end, in ohms 214.727 9 Load Angle 30 (Assumed) D CT/PT Details 1 CT primary rating in A 800 2 CT secondary rating in A 1 3 PT primary rating in V 220000 4 PT secondary rating in V 110 E Relay Details 1 Rated Current in A 1 2 Rated Voltage in V 110 F System Particulars 1 Fault Resistance in primary for phase - earth faults 25.000 2 Fault Resistance in primary for phase - phase faults 20.000 3 zone 1 setting - % 80% of Protected Line 4 50% of Shortest Line 5 100% of Longest Line 6 100% of Reverse Line zone 2 setting - % (Choose option from D72) zone 3 setting - % (Choose option from D73) zone 4/5 setting- % (Z4 or Z5 set as Reverse Zone) Tick, if Line is Series Compe Tick, If in % of Zero Sequenc

Rel 670 Setting Tool -220kv Rajgarh

  • Upload
    karthik

  • View
    275

  • Download
    72

Embed Size (px)

DESCRIPTION

rel670

Citation preview

Page 1: Rel 670 Setting Tool -220kv Rajgarh

System Details

313470776.xls 1/42

LINE NAME : MYV-1SUBSTATION : PONNAPURAM 230KV SS

Select the Terminal REL670

NOTE: Open File by Enabling MACROS Fill in the BLUE CellsSYSTEM PARTICULARS

A Line Parameters

1 Rated Line Voltage in KV 2202 Line Length in kms 36.53 Max. Power Flow in the Line in MVA 165.00 4334 Positive seqence Resistance in ohms/km 0.0815 Positive Sequence Reactance in ohms/km 0.46 Zero sequence Resistance in ohms/km 0.2757 Zero sequence reactance in ohms/km 1.275

8 Zero Sequence Mutual Impedance %

9 Zero Sequence Mutual Resistance in ohms/km 0 010 Zero Sequence Mutual Reactance in ohms/km 0 0

11 XC-Reactance of Series Capacitor

B Adjoining Line Parameters

a) Shortest Line

1 Length of shortest line in kms 62 Positive Sequence Resistance in ohms/km 0.0813 Positive Sequence Reactance in ohms/km 0.44 Zero Sequence Resistance in ohms/km 0.2755 Zero sequence Reactance in ohms/km 1.275b) Longest Line

1 Length of longest line 1322 Positive Sequence Resistance in ohms/km 0.0813 Positive Sequence Reactance in ohms/km 0.44 Zero Sequence Resistance in ohms/km 0.2755 Zero sequence Reactance in ohms/km 1.275c) Transformer 1 Transformer MVA 02 Percentage Reactance in p.u. 03 Positive Sequence Reactance in ohms 04 Zero sequence Reactance in ohms 0d) Shortest Line (Reverse)

1 Length of shortest line in kms 52 Positive Sequence Resistance in ohms/km 0.0813 Positive Sequence Reactance in ohms/km 0.44 Zero Sequence Resistance in ohms/km 0.2755 Zero sequence Reactance in ohms/km 1.275C Source Impedance

1 FAULT MVA at Local-End 7002 FAULT MVA at Remote-End 2223 Source impedance angle in deg 80 (Assumed)4 Angle in radians 1.3975 Positive Sequence Resistance at local end, in ohms 11.9686 Positive Sequence Reactance at local end, in ohms 68.0997 Positive Sequence Resistance at remote end, in ohms 37.7388 Positive Sequence Reactance at remote end, in ohms 214.7279 Load Angle 30 (Assumed)D CT/PT Details

1 CT primary rating in A 8002 CT secondary rating in A 13 PT primary rating in V 2200004 PT secondary rating in V 110E Relay Details

1 Rated Current in A 12 Rated Voltage in V 110F System Particulars1 Fault Resistance in primary for phase - earth faults 25.0002 Fault Resistance in primary for phase - phase faults 20.0003 zone 1 setting - % 80% of Protected Line4 50% of Shortest Line5 100% of Longest Line6 100% of Reverse Line

zone 2 setting - % (Choose option from D72) zone 3 setting - % (Choose option from D73) zone 4/5 setting- % (Z4 or Z5 set as Reverse Zone)

Tick, if Line is Series Compensated

Tick, If in % of Zero Sequence

Page 2: Rel 670 Setting Tool -220kv Rajgarh

CALCULATIONS

313470776.xls 2/42

System Parameters

Fault Resistance in primary for phase - earth faults 25.000

20.000

Imp Ratio = CTR/PTR 0.400

1.000 #VALUE!

zone-1 setting - % of the protected line 80%

zone 2 setting - % of the shortest adjoining line 50% 2

zone 3 setting - % of the longest adjoining line 100% 3

Reach of Reverse Zone 100%

Line Impedance in secondary ZONE1

1 Positive seqence Resistance in ohms 2.957 2.957

2 Positive Sequence Reactance in ohms 14.600

3 Zero sequence Resistance in ohms 10.038

4 Zero sequence reactance in ohms 46.538

5 Zero Sequence Mutual Resistance in ohms 0.000

6 Zero Sequence Mutual Reactance in ohms 0.0007 Line Angle 78.522

Shortest Line (Forward) ZONE2

1 Positive Sequence Resistance in ohms 0.486 0.486

2 Positive Sequence Reactance in ohms 2.400 2.400

3 Zero Sequence Resistance in ohms 1.650 1.650

4 Zero sequence Reactance in ohms 7.650 7.650Shortest Line (Reverse)

1 Positive Sequence Resistance in ohms 0.405

2 Positive Sequence Reactance in ohms 2.000

3 Zero Sequence Resistance in ohms 1.375

4 Zero sequence Reactance in ohms 6.375

Longest line section ZONE31 Positive Sequence Resistance in ohms 10.692 10.6922 Positive Sequence Reactance in ohms 52.800 52.8003 Zero Sequence Resistance in ohms 36.300 36.300

4 Zero sequence Reactance in ohms 168.300 168.300

Fault Resistance in primary for phase - phase faults

Total Line Reactance to Permitted Covered Reactance Ratio

Page 3: Rel 670 Setting Tool -220kv Rajgarh

CALCULATIONS

313470776.xls 3/42

Zone-1 setting1 Positive sequence Resistance in ohms 2.3652 Positive Sequence Reactance in ohms 11.6803 Zero sequence Resistance in ohms 8.030 8.0304 Zero sequence reactance in ohms 37.230 37.2305 Fault Resistance (ph-ph) 44.7306 Fault Resistance (ph-e) 27.365

Zone-2 setting1 Positive seqence Resistance in ohms 3.2002 Positive Sequence Reactance in ohms 15.8003 Zero sequence Resistance in ohms 10.863 10.8634 Zero sequence reactance in ohms 50.363 50.3635 Fault Resistance (ph-ph) 46.3996 Fault Resistance (ph-e) 28.200

Zone-3 setting1 Positive seqence Resistance in ohms 13.6492 Positive Sequence Reactance in ohms 67.4003 Zero sequence Resistance in ohms 46.338 46.3384 Zero sequence reactance in ohms 214.838 214.8385 Fault Resistance (ph-ph) 67.2976 Fault Resistance (ph-e) 38.649

Reverse Zone SettingPositive seqence Resistance in ohms 0.405Positive Sequence Reactance in ohms 2.000Zero sequence Resistance in ohms 1.375Zero sequence reactance in ohms 6.375Fault Resistance (ph-ph) 12.000Fault Resistance (ph-e) 9.000

Load Impedance (primary) 237.600Load impedance (secondary) 95.040

The General Fault Criterion is an overall impedance measuring element with a very high reach and a long time delay for its tripping function.The GFC can be operated in two modes - the under impedance mode and the over current mode.In the under impedance mode, the GFC characteristic should, in general, cover all the impedance measuring zones used for distance protection, regardless of their directionality. Normally set to 2 times of zone-3 with a limit on the resistive direction so that the characteristics does not enter the load area.

Page 4: Rel 670 Setting Tool -220kv Rajgarh

CALCULATIONS

313470776.xls 4/42

General Fault Criterion

134.800

4.000

142.560

126.387

429.675

429.675

142.560Load Angle ARGLd 30.000

Power Swing Block Function

74.140

104.053

92.675

130.067

Positive sequence reactance for ph-ph & ph-e elements in the forward direction (2 * X3)

Positive sequence reactance for ph-ph & ph-e elements in the reverse direction(30% of forward reach)

Positive sequence Resistance for phase to phase faults for forward and Reverse reach (2[2*R3 + Rf])

Positive sequence Resistance for phase to earth faults for forward and Reverse reach (2[1/3(2R3 + R03)+Rf])

Zero sequence reactance for ph-e elements in the forward direction (2 * X03)

Zero sequence reactance for ph-e elements in the reverse direction (30% of forward reach)

RLd - the resistive reach in the load impedance area

The reach of the Inner characteristic in the resistive and reactive direction is set so that the inner characteristic covers completely all the distance protection zones, which are to be blocked by the PSD function. At least 10% of additional safety margin is considered

Reactive Reach of the Inner characteristic of the Power swing blocking element = 1.1*X3

Resistive Reach of the Inner characteristic of the Power swing blocking element=1.1(2R3+Rf)

Reactive Reach of the Outer characteristic of the Power swing blocking element

Resistive Reach of the Outer characteristic of the Power swing blocking element

Page 5: Rel 670 Setting Tool -220kv Rajgarh

313470776.xls PAGE:5

RECOMMENDED SETTINGS FOR REL670LINE NAME : MYV-1 Manual Entry to be made to BLUE cellsSUBSTATION : PONNAPURAM 230KV SS

PARAMETER SETTING SETTING RANGE RECOMMEND IN SECONDA DESCRIPTION

General setting Minimum operating current Ib (FLC/CT Primary) 0.541 Max. Load Current / CT Primary CurrentIminop (10-30) % of Ib 10 % of Ib

Line Reference Fault LocatorLength unit Km/mile km Unit for presentation of line lengthLine length (0-10000) 36.500 Length of protected lineX1 (0.001-1500) 14.600 5.840 Positive sequence reactance of lineR1 (0.001-1500) 2.957 1.183 Positive sequence resistance of lineX0 (0.001-1500) 46.538 18.615 Zero sequence reactance of lineR0 (0.001-1500) 10.038 4.015 Zero sequence resistance of lineX1SA (0.001-1500) 68.099 27.240 Positive sequence reactance of source at local endR1SA (0.001-1500) 11.968 4.787 Positive sequence resistance of source at local endX1SB (0.001-1500) 214.727 85.891 Positive source reactance at remote endR1SB (0.001-1500) 37.738 15.095 Positive source resistance at remote endXm0 (0.001-1500) 0.000 0.000 Zero sequence mutual reactance for double circuit linesRm0 (0.001-1500) 0.000 0.000 Zero sequence mutual resistance for double circuit lines

Disturbamce Report (Basic Settings)Operation On/Off On Disturbance reporting functionsDistance Unit %/(km/mi) km/mi Selection of presentation mode for the distance to fault*Next Sequence No 0-255 0 Select daily sequence NotPre 0.05-0.30 Seconds 0.30 Pre-Fault recording timetPost 0.1-5.0 Seconds 0.5 Post-Fault recording timetLim 0.5-6.0 Seconds 2.0 Fault recording time limitPost Retrig On/Off Off Retrigring during Post fault recording

Page 6: Rel 670 Setting Tool -220kv Rajgarh

313470776.xls PAGE:6

SETTING RANGE RECOMMEND IN SECONDARY DESCRIPTION

Settings of Phase to Phase measurement

Operation PP On/Off On Operation of distance protection zone 1 for Ph-Ph fault

X1PP 0.10-400 11.680 4.672 Positive sequence reactance of zone 1 for Ph-Ph fault

R1PP 0.10-400 2.365 0.946 Positive sequence resistance of zone 1 for Ph-Ph fault

RFPP 0.10-400 44.730 17.892 Resistive reach of distance protection for phase to phase faults

Timer t1PP Off,On On

t1PP (0 - 60) Seconds 0.000 Time delayed trip operation for the distance protection zone 1 for Ph-Ph faultsSettings for Phase to earth elementOperation PE On,Off On

Operation of distance protection zoneI for Ph-E faultX1PE 0.10-400 11.680 4.672R1PE 0.10-400 2.365 0.946 Positive sequence resistive reach of distance zone 1 for Ph-E faults

X0PEGroup-I 37.230 14.892

Zero sequence line reactance included in distance protection zone 1 for Ph-E faults Group-II 37.230 14.8920.10-1200

R0PEGroup-I 8.030 3.212

Zero sequence line resistance included in distance protection zone 1 for Ph-E faultsGroup-II 8.030 3.2120.10-1200

RFPE 0.10-400 27.365 10.946 Resistive Reach for zone1 for Ph-E faults

Timer t1PE Off,On On

t1PE (0 - 60) Seconds 0.000 Time delayed trip operation of the distance protection zone 1 for Ph-E faults.

Prepared by : SJR Description:REL670Setting Calculations

Issued by Dept. Year Wk Order Reference:

PTSY-SCUSTOMER TAMILNADU ELECTRICITY BOARDRev Year Wk 01 2006 45

Group 1 : Both the parallel feeders are in service.Group 2 : One feeder in service and the other feeder open and earthed at both the ends

PARAMETER SETTING

Operating mode of time delayed trip for the distance protection zone1 for Ph-Ph faults

Operating mode of time delayed trip for the distance protection zone 1 for Ph-E faults.

Page 7: Rel 670 Setting Tool -220kv Rajgarh

313470776.xls PAGE:7

SETTING RANGE RECOMMEND IN SECONDA DESCRIPTION

ZONE II Distance Protection Zone IIOperation Off,nondir,forward,reverseForward Operating mode and directionality of distance zone 2Settings of Phase to Phase measurementOperation PP On/Off On Operation of distance protection zone 2 for Ph – Ph fault X1PP 0.10-400 15.800 6.320 Positive sequence reactance of zone 2 for Phase to Phase faults R1PP 0.10-400 3.200 1.280 Positive sequence resistance of zone 2 for Phase to Phase faultsRFPP 0.10-400 46.399 18.560 Resistive reach of distance protection for phase to phase faults

Timer t2PP Off,On On

t12P (0 - 60) Seconds 0.400 Time delayed trip operation for the distance protection zone 2 for Ph-Ph faultsSettings of Phase to earth measurementOperation PE On,Off On Operating mode of distance protection zone 2 for Ph-E faultsX1PE 0.10-400 15.800 6.320 Positive sequence reactive reach of distance zone 2 for Ph-E faultsR1PE 0.10-400 3.200 1.280 Positive sequence resistive reach of distance zone 2 for Ph-E faults

X0PEGroup-I 50.363 20.145

Zero sequence line reactance included in distance protection zone 2 for Ph-E faultsGroup-II 50.363 20.1450.10-1200

R0PEGroup-I 10.863 4.345

Zero sequence line resistance included in distance protection zone 2 for Ph-E faultsGroup-II 10.863 4.3450.10-1200

RFPE 0.10-400 28.200 11.280 Resistive Reach for zone 2 for Ph-E faults

Timer t2PE Off,On On

t2PE (0 - 60) Seconds 0.400 Time delayed trip operation of the distance protection zone 2 for Ph-E faults.

Prepared by : SJR Description:REL670Setting Calculations

Issued by Dept. Year Wk Order Reference: 0

PTSY-SCUSTOMER TAMILNADU ELECTRICITY BOARDRev Year Wk 01 2006 45

PARAMETER SETTING

Operating mode of time delayed trip for the distance protection zone 2 for Ph-Ph faults

Operating mode of time delayed trip for the distance protection zone 2 for Ph-E faults.

Page 8: Rel 670 Setting Tool -220kv Rajgarh

313470776.xls PAGE:8

SETTING RANGE RECOMMEND IN SECONDA DESCRIPTION

Zone III Distance Protection Zone III

Operation Forward Operating mode and directionality of zone 3

Settings of Phase to Phase measurementOperation PP On/Off On Operation of distance protection zone 3 for Ph-Ph faultX1PP 0.10-400 67.400 26.960 Positive sequence reactance of zone 3 for Phase to Phase faultsR1PP 0.10-400 13.649 5.459 Positive sequence resistance of zone 3 for Phase to Phase faultsRFPP 0.10-400 67.297 26.919 Resistive reach of distance protection for phase to phase faults

Timer t3PP Off,On On

t3PP (0 - 60) Seconds 0.800 Time delayed trip operation for the distance protection zone 3 for Ph-Ph faultsSettings of Phase to earth measurementOperation PE On,Off On Operating mode of distance protection zone 3 for Ph-E faultsX1PE 0.10-400 67.400 26.960 Positive sequence reactive reach of distance zone 3 for Ph-E faultsR1PE 0.10-400 13.649 5.459 Positive sequence resistive reach of distance zone 3 for Ph-E faults

X0PEGroup-I 214.838 85.935

Zero sequence line reactance included in distance protection zone 3 for Ph-E faultsGroup-II 214.838 85.9350.10-1200

R0PEGroup-I 46.338 18.535

Zero sequence line resistance included in distance protection zone 3 for Ph-E faultsGroup-II 46.338 18.5350.10-1200

RFPE 0.10-400 38.649 15.459 Resistive Reach for zone3 for Ph-E faults

Timer t3PE Off,On On

t3PE (0 - 60) Seconds 0.800 Time delayed trip operation of the distance protection zone 3 for Ph-E faults.

Prepared by : SJR Description:REL670Setting Calculations

Issued by Dept. Year Wk Order Reference: 0

PTSY-SCUSTOMER TAMILNADU ELECTRICITY BOARDRev Year Wk 01 2006 45

PARAMETER SETTING

Off, nondir, forward, reverse

Operating mode of time delayed trip for the distance protection zone 3 for Ph-Ph faults

Operating mode of time delayed trip for the distance protection zone 3 for Ph-E faults.

Page 9: Rel 670 Setting Tool -220kv Rajgarh

313470776.xls PAGE:9

SETTING RANGE RECOMMEND IN SECONDA DESCRIPTION

Zone IV or Zone V (To be set in Reverse) Distance protection zone IV or Zone V

Operation Reverse Operating mode and directionality of zone 5

Settings of Phase to Phase measurement

Operation PP On/Off On Operation of distance protection zone for Ph-Ph faultX1PP 0.10-400 2.000 0.800 Positive sequence reactance of zone for Phase to Phase faultsR1PP 0.10-400 0.405 0.162 Positive sequence resistance of zone for Phase to Phase faults

RFPP 0.10-400 12.000 4.800 Fault resistance for Ph - Ph faults

Timer t5PP Off,On On

t5PP (0.0-60) 0.800 Time delayed trip operation for the distance protection zone for Ph-Ph faultsSettings of Phase to earth measurementOperation PE On,Off On Operating mode of distance protection zone for Ph-E faultsX1PE 0.10-400 2.000 0.800 Positive sequence reactive reach of distance zone for Ph-E faultsR1PE 0.10-400 0.405 0.162 Positive sequence resistive reach of distance zone for Ph-E faults

X0PE 0.01-1200 6.375 2.550 Zero sequence line reactance included in distance protection zone for Ph-E faults

R0PE 0.01-1200 1.375 0.550 Zero sequence line resistance included in distance protection zone for Ph-E faults

RFPE 0.10-400 9.000 3.600 Fault resistance for Ph - E faults

Timer t5PE Off,On On Operating mode of time delayed trip for the distance protection zone for Ph-E faults.

t5PE 0-60 0.800 Time delayed trip operation of the distance protection zone for Ph-E faults.

Prepared by : SJR Description:REL670Setting Calculations

Issued by Dept. Year Wk Order Reference: 0

PTSY-SCUSTOMER TAMILNADU ELECTRICITY BOARDRev Year Wk

PARAMETER SETTING

Off, nondir, forward, reverse

Operating mode of time delayed trip for the distance protection zone for Ph-Ph faults

Page 10: Rel 670 Setting Tool -220kv Rajgarh

313470776.xls PAGE:10

SETTING RANGE RECOMMEND IN SECONDA DESCRIPTION

ZDIR Directional Measuring ElementArgDir ( 5 - 45 ) Degrees 15 Lower angle of forward direction characteristic ( 4th Quadrant )

ArgNegRes ( 90 - 175 ) Degrees 115 Upper angle of forward direction characteristic ( 2nd Quadrant )

GFC General Fault Criteria

General settingsOperation On,Off On Operating mode of GFCTimer t PP On,Off Off Time delayed trip for phase to phase faults enabled or disabeledtPP (0 - 60) Seconds 2s Time delay set for trip for PH-PHTimer t PE On,Off Off Time delayed trip for phase to earth faults enabled or disabledtPE (0 - 60) Seconds 2s Time delay set for trip for PH-E faultsOver current operating modeOperation I> On,Off Off Operation of current based GFC enabled or disabledIP> 10-400 NA Operate value for phase currentsIn> 10-150 NA Operate value of residual currentI> (10-50)% of Ir 20 Operating level of current measuring elementGFC (Settings of Under Impedence Mode)Operation On,Off On Operation of under impedance based GFC measurementOperation<Z On,Off OnARGLd 5-45 deg 30.000 Load angle determining by the load impedance areaRLd 0.10-400 142.560 57.024 Limitation of resistive reach within the load impedance areaX1FwPP 0.10-400 134.800 53.920 Positive sequence reactive reach in forward direction for PH-PH faults.X1RvPP 0.10-400 4.000 1.600 Positive sequence reactive reach in Reverse direction for PH-PH faults.

RFPP 0.10-400 142.560 57.024 Resistive reach (forward & reverse) for PH-PH measurement

X1FwPE 0.10-400 134.800 53.920 Positive sequence reactive reach in forward direction for PH-E faults.X1RvPE 0.10-400 4.000 1.600 Positive sequence reactive reach in reverse direction for PH-E faults.X0FwPE 0.10-1200 429.675 171.870 Zero sequence reactive reach in forward direction for PH-E faults.X0RvPE 0.10-1200 429.675 171.870 Zero sequence reactive reach in reverse direction for PH-E faults.RFPE 0.10-400 126.387 50.555 Resistive reach (forward & reverse) for PH-E measurement

Prepared by : SJR Description:REL670Setting Calculations

Issued by Dept. Year Wk Order Reference: 0

PTSY-SCUSTOMER TAMILNADU ELECTRICITY BOARDRev Year Wk 01 2006 45

PARAMETER SETTING

Page 11: Rel 670 Setting Tool -220kv Rajgarh

313470776.xls PAGE:11

SETTING RANGE RECOMMEND IN SECONDA DESCRIPTION

PSB Powerswing BlockingOperation On,Off On Power swing function on/offDetection On,Off On Operating mode of internal PSD functionX1IN 0.10-400 74.140 29.656 Positive sequence reactive reach of the inner boundaryR1IN 0.10-400 104.053 41.621 Positive sequence resistive reach of the inner boundaryKX 120-200% 125 Reach multiplication for the outer reactive boundaryKR 120-200% 125 Reach multiplication for the outer resistive boundaryt P1 (0 - 60) Seconds 0.045 Initial PSD timer for the first swingt P2 (0 - 60) Seconds 0.015 Fast PSD timer for the consecutive swings within 't W't W (0 - 60) Seconds 0.250 Hold timer for activation of fast PSD timer. t H (0 - 60) Seconds 0.5 S Hold timer for PSD detectedt EF (0 - 60) Seconds 60.000 Timer overcoming 1-Ph reclosing dead timet R1 (0 - 60) Seconds 0.300 Timer to time delay block by the residual currentt R2 (0 - 60) Seconds 2.000 On delay timer for blocking of output signal at very slow swings.

Z Com Scheme Communication LogicOperation On, Off On No Scheme is selected since the carrier is not avalable.

Scheme type Permissive UR Operation mode

T coord (0 - 60) Seconds 0.050 s Coordination timerT sendmin (0 - 60) Seconds 0.1s Minimum duration of a carrier send signalUnblock Off, No restart, Restart Off Operation mode for an unblocking signalT security (0 - 60) Seconds 0.035 s Security timerCurrrev On,Off Off Operation mode of current reversal functionT pickup (0 - 60) Seconds NA Pickup time of current reversal functionT delay (0 - 60) Seconds NA Time delay for current reversalWEI Weak End Infeed FunctionOperation Off, trip, echo Off Operation mode of WEI functionTwei (0 - 60) Seconds 0.010 Coordination time for WEI functionUPN< 10-100 70 Voltage detection for Ph-E faultsUPP< 20-170 110 Voltage detection for Ph-Ph faults

Prepared by : SJR Description:REL670Setting Calculations

Issued by Dept. Year Wk Order Reference: 0

PTSY-SCUSTOMER TAMILNADU ELECTRICITY BOARDRev Year Wk 01 2006 45

PARAMETER SETTING

Inter trip, permissive UR, Permissive OR, Blocking

Page 12: Rel 670 Setting Tool -220kv Rajgarh

313470776.xls PAGE:12

SETTING RANGE RECOMMEND IN SECONDA DESCRIPTION

SOTF Switch Onto Fault FunctionOperation On/Off On Operation of SOTF functionFFR Fuse Failure FunctionZeroseq On,Off On FFR zero sequence function On/Off3U0> 10-50% 20 Operating value of voltage U0 - To be checked based on site conditions3Io< 10-50% 10 Operating value of current I0 BCS Broken Conductor SupervisionOperation On,Off On Broken conductor function On/OffIP> 10-100% 50 Minimum Operating current as a % of rated current.T (0 - 60) Seconds 10.000 Time delayDLD Dead Line DetectionOperation On,Off On dead line detection function ON/OFFU< 10-100% 40 Operating Phase voltageIP< 5-100% of Ib 10 Operating Phase currentI> OverloadOperation On.Off Off Overload function On/OffIP> 20-300% 110 Operating value of Phase currentT (0 - 9000) Seconds 500.000 Time delay

Prepared by : SJR Description:REL670Setting Calculations

Issued by Dept. Year Wk Order Reference: 0

PTSY-SCUSTOMER TAMILNADU ELECTRICITY BOARDRev Year Wk 01 2006 45

PARAMETER SETTING

Page 13: Rel 670 Setting Tool -220kv Rajgarh

313470776.xls PAGE:13

SETTING RANGE RECOMMENDED DESCRIPTION

AR Auto Recloser FunctionOperation Off, Stand-by, On Standby Auto-recloser Off/Stand-by/OnNo of Reclosing 1 to 4 1 Max. No. of Reclosing AttemptsFirst Shot 3 ph, 1/2/3 ph, 1/2 ph 1/2/3 Ph Restriction of fault type for reclosing attemptExtended t1 Off, On Off Extended dead time for loss of permissive channelt1 1ph (0 - 60) Seconds 1.000 Open time for auto-reclosing at Single phaset1 2ph (0 - 60) Seconds 1.000 Open time for auto-reclosing at Two phaset1 (0 - 60) Seconds 1.000 Open time for auto-reclosing at Three phasetSync (0 - 9000) Seconds 1.000 Auto-recloser Max. wait time for synctPulse (0 - 60) Seconds 0.200 Circuit Breaker closing pulse lengthCut Pulse Off, On Off Shorten closing pulse at a new triptReclaim (0 - 9000) Seconds 30.000 Auto-recloser reclaim timetInhibit (0 - 60) Seconds 0.500 Inhibit reset timeCB Ready CO, OCO CO Select type of circuit breaker ready signaltTrip (0 - 60) Seconds 0.300 Block auto-reclosing for long trip durationPriority None, Low, High None Priority selection between adjacement terminalstWait For-Master (0 - 9000) Seconds 60.000 Max. wait time for MasterAuto Cont Off, On Off Continue with next reclosing attempt if breaker not closesBlock Unsuc Off, On Off Block auto-reclosing at unsuccessful auto-reclosingtAutoWait (0 - 60) Seconds 2.000 Max. wait time between shootsUnsuc Mode No CB check, CB check No CB check Unsuccessful-Signal modetUnsuc (0 - 9000) Seconds 30.000 CB Check time before unsec

Prepared by : SJR Description:REL670Setting Calculations

Issued by Dept. Year Wk Order Reference: 0

PTSY-SCUSTOMER TAMILNADU ELECTRICITY BOARDRev Year Wk 01 2006 45

PARAMETER SETTING

Page 14: Rel 670 Setting Tool -220kv Rajgarh

313470776.xls PAGE:14

RECOMMENDED SETTINGS FOR REL670LINE NAME : MYV-1 Manual Entry to be made to BLUE cellsSUBSTATION : PONNAPURAM 230KV SS

SETTING RANGE RECOMMENDED DESCRIPTION

ZONE I Distance Protection Zone I

X(1) (-300 - 300) ohms/phase 11.680 Positive sequence reactance of zone 1 for Ph-Ph fault

R(1) (-300 - 300) ohms/phase 2.365 Positive sequence resistance of zone 1 for Ph-Ph fault

RR(1) (-300 - 300) ohms/phase 44.730 Resistive reach of distance protection for phase to phase faults

ko (01-08) 1.268 Zero sequence line reactance included in distance protection zone 1 for Ph-E faults

ko Angle (000-180.00) deg -1.054 Zero sequence line resistance included in distance protection zone 1 for Ph-E faults

RRE(1) (-300 - 300) ohms/phase 27.365 Resistive Reach for zone 1 for Ph-E faults

Delay(1) 0-10 Seconds 0.000 Time delayed trip operation of the distance protection zone 1 for Ph-E faults.

Prepared by : PSS - R Description:REL670Setting Calculations

Issued by Dept. Year Wk Order Reference: MSEB-2002

PSS - RCUSTOMER MSEBRev Year Wk 2002

PARAMETER SETTING

Page 15: Rel 670 Setting Tool -220kv Rajgarh

313470776.xls PAGE:15

SETTING RANGE RECOMMENDED DESCRIPTION

ZONE II Distance Protection Zone IIX(2) (-300 - 300) ohms/phase 15.800 Positive sequence reactance of zone 2 for Phase to Phase faults R(2) (-300 - 300) ohms/phase 3.200 Positive sequence resistance of zone 2 for Phase to Phase faultsRR(2) (-300 - 300) ohms/phase 46.399 Resistive reach of distance protection for phase to phase faults

ko (01-08) 1.268 Zero sequence line reactance included in distance protection zone 2 for Ph-E faults

ko Angle (000-180.00) deg -1.054 Zero sequence line resistance included in distance protection zone 2 for Ph-E faults

RRE(2) (-300 - 300) ohms/phase 28.200 Resistive Reach for zone 2 for Ph-E faults

Delay(2) 0-60 Seconds 0.400 Time delayed trip operation of the distance protection zone 2 for Ph-E faults.

Prepared by : PSS - R Description:REL670Setting Calculations

Issued by Dept. Year Wk Order Reference: MSEB-2002

PSS - RCUSTOMER MSEBRev Year Wk 2002

PARAMETER SETTING

Page 16: Rel 670 Setting Tool -220kv Rajgarh

313470776.xls PAGE:16

SETTING RANGE RECOMMENDED DESCRIPTION

Zone III Distance Protection Zone IIIX(3) (-300 - 300) ohms/phase 67.400 Positive sequence reactance of zone 3 for Phase to Phase faultsR(3) (-300 - 300) ohms/phase 13.649 Positive sequence resistance of zone 3 for Phase to Phase faultsRR(3) (-300 - 300) ohms/phase 67.297 Resistive reach of distance protection for phase to phase faults

ko (01-08) 1.268 Zero sequence line reactance included in distance protection zone 3 for Ph-E faults

ko Angle (000-180.00) deg -1.054 Zero sequence line resistance included in distance protection zone 3 for Ph-E faults

RRE(3) (-300 - 300) ohms/phase 38.649 Resistive Reach for zone 3 for Ph-E faults

Delay(3) 0-10 Seconds 0.800 Time delayed trip operation of the distance protection zone 3 for Ph-E faults.

Prepared by : PSS - R Description:REL670Setting Calculations

Issued by Dept. Year Wk Order Reference: MSEB-2002

PSS - RCUSTOMER MSEBRev Year Wk 2002

PARAMETER SETTING

Page 17: Rel 670 Setting Tool -220kv Rajgarh

313470776.xls PAGE:17

SETTING RANGE RECOMMENDED DESCRIPTION

STARTER Phase SelectionStart Mode UZ/OC UZPhase Sel Mode nondir/forward OR nondirGnd Fault Mode Io/Io OR Uo/Io(I2)/Io(I2) OR Uo IoI Start 4 x IN 4.000I Min (0.10-2.00) x IN 0.2003Io Min (0.10-2.00) x IN 0.2003Uo Min (0.00-2.00) x IN 0.000XA (0.10-999) ohms/phase 134.800XB (-999-0.00) ohms/phase -4.000RA (0.10-999) ohms/phase 126.387RB (-999-0.00) ohms/phase -142.560Rload (0-999) ohms/phase 142.560Angle Load (0-90) degree 30.000U Weak (0-2) x Un 0.000

Prepared by : PSS - R Description:REL670Setting Calculations

Issued by Dept. Year Wk Order Reference: MSEB-2002

PSS - RCUSTOMER MSEBRev Year Wk 2002

PARAMETER SETTING

Page 18: Rel 670 Setting Tool -220kv Rajgarh

313470776.xls PAGE:18

SETTING RANGE RECOMMENDED DESCRIPTION

PSB Powerswing Blocking

Time PS Block 0-10 Seconds 5.000

SOTF Switch Onto Fault FunctionSOTFMode nondir Operating mode of the switch-onto-fault functionSOTF10sec Off/On Off Enables the 10 s delay for the switch-onto-fault functionVT Supervision Fuse Failure Function

VTSupMode Off

VTSupBlkDel Off/On Off Delayed blocking of the Dist function (12 s) for operation of the v.t. supervision.VTSupDebDel Off/On On Delay (1 s) for resetting blocking by the v.t. supervision.U0min VTSup (0.01- 0.5) 0.20 Pick-up setting of the neutral voltage (Uo) for v.t. supervision referred to the v.t.I0min VTSup (0.01- 0.5) 0.07 Pick-up setting of the neutral current (I0) for v.t. supervision.U2min VTSup (0.01- 0.5) 0.20 Pick-up setting of the NegSeq voltage (U2) for v.t. supervision referred to the v.t.I2min VTSup (0.01- 0.5) 0.07 Pick-up setting of the NPS current (I2) for v.t. supervision.I> OverloadI O/C (0 -10) x In 0 Pick-up value of the definite time back-up overcurrent function.Delay O/C (0 - 10) Seconds 5.000 Time delay for the definite time back-up overcurrent function.

Prepared by : PSS - R Description:REL670Setting Calculations

Issued by Dept. Year Wk Order Reference: MSEB-2002

PSS - RCUSTOMER MSEBRev Year Wk 2002

PARAMETER SETTING

Maximum time during which the power-swing blocking function is effective. The function is disabled when set to zero.

Off/Zero Seq/Neg Seq/Zero *NegSeq/Spec

Page 19: Rel 670 Setting Tool -220kv Rajgarh

313470776.xls PAGE:19

SETTING RANGE RECOMMENDED DESCRIPTION

AR Auto Recloser FunctionAR Mode 1P3P-1P3P Type of first reclosure

4. AR Mode Off/2AR/3AR/4AR 2AR Maximum number of reclosure attempts (all three-phase)

Timers for ARt Dead1 1P (0.05 - 300) Seconds 1.200 Dead time for first single-phase reclosure.t Dead1 3P (0.05 - 300) Seconds 0.600 Dead time for first three-phase reclosure.

t Dead1 Ext. (0.05 - 300) Seconds 1.000

t Dead2 (0.05 - 300) Seconds 1.200 2nd. dead time.t Dead3 (0.05 - 300) Seconds 5.000 3rd. dead time.t Dead4 (0.05 - 300) Seconds 60.000 4th. dead time.t Oper (0.05 - 300) Seconds 0.500 Maximum duration of a fault for which a reclosure attempt is made.

t Inhibit (0.05 - 300) Seconds 5.000

t Close (0.05 - 300) Seconds 0.250 Duration of CB close signal.t Discrim.1P (0.10 - 300) Seconds 0.600 Evolving fault discrimination time for single-phase reclosure.t Discrim.3P (0.10 - 300) Seconds 0.300 Evolving fault discrimination time for three-phase reclosure.

t Timeout (0.05 - 300) Seconds 1.000

t AR Block (0.05 - 300) Seconds 5.000

Prepared by : PSS - R Description:REL670Setting Calculations

Issued by Dept. Year Wk Order Reference: MSEB-2002

PSS - RCUSTOMER MSEB

PARAMETER SETTING

1. 1P-1P -> single-phase trip and reclosure for earth faults (single-phase dead time), no reclosure for phase faults

2. 1P-3P -> single-phase trip followed by three phase trip after approx. 20 ms, three-phase reclosure for earth faults (three-phase dead time initiated by single-phase trip), no reclosure for -phase faults

3. 1P3P-3P -> three-phase trip and reclosure for earth and phase faults (three-phase dead time)

4. 1P3P-1P3P -> single-phase trip and reclosure for earth faults (single-phase dead time), threephase trip and reclosure for phase faults (three-phase dead time)

5. Ext. Wahl -> External selection by the binary inputs MD1_EXT_1P_1P, MD1_EXT_1P_3P, MD1_EXT_1P3P_3P and MD1_EX_1P3P_1P3P.

Extension of 1st. dead time for single or three-phase reclosure (effective as long as a logical ‘1’ (pulse or continous) is applied to the ‘Extend t1’ I/P before the dead time finishes (falling edge.)

Period (CB recovery time) from the falling edge of the last reclosure attempt during which the autoreclosure function is blocked and after which the function is reset. In the event of an evolving fault between discrimination and dead times, the period commences at the instant of another trip occurring between the two times.The reclaim timer is also started if the protection trips after the fault duration time ‘t Oper’ has elapsed.

Period following the dead time during which the CB close signal has to occur. If it does not, the ‘Def. Trip’ signal is generated.

Time during which reclosure is blocked. ‘t AR Block’ is started by every blocking signal (‘Ext.Blk AR’, ‘Cond.Blk. AR’, ‘Manual Close’, ‘Inhibit Inp’ and ‘MasternoSucc’).

Page 20: Rel 670 Setting Tool -220kv Rajgarh

313470776.xls PAGE:20

PSS - RRev Year Wk 2002

Page 21: Rel 670 Setting Tool -220kv Rajgarh

313470776.xls PAGE:21

RECOMMENDED SETTINGS FOR REL670LINE NAME : MYV-1 Manual Entry to be made to BLUE cellsSUBSTATION : PONNAPURAM 230KV SSPARAMETER SETTING SETTING RANGE RECOMMENDED DESCRIPTIONGeneral setting Minimum operating current Ib (FLC/CT Primary) 0.541 Max. Load Current / CT Primary CurrentIminop (10-30) % of Ib 20

Line Reference Fault LocatorLength unit Km/mile km Unit for presentation of line lengthLine length (0-10000) 36.500 Length of protected lineX1 (0.001-1500) 14.600 Positive sequence reactance of lineR1 (0.001-1500) 2.957 Positive sequence resistance of lineX0 (0.001-1500) 46.538 Zero sequence reactance of lineR0 (0.001-1500) 10.038 Zero sequence resistance of lineX1SA (0.001-1500) 27.240 Positive sequence reactance of source at local endR1SA (0.001-1500) 4.787 Positive sequence resistance of source at local endX1SB (0.001-1500) 85.891 Positive source reactance at remote endR1SB (0.001-1500) 15.095 Positive source resistance at remote endXm0 (0.001-1500) 0.000 Zero sequence mutual reactance for double circuit linesRm0 (0.001-1500) 0.000 Zero sequence mutual resistance for double circuit lines

Disturbamce Report (Basic Settings)Operation On/Off On Disturbance reporting functionsDistance Unit %/(km/mi) % Selection of presentation mode for the distance to fault*Next Sequence No 0-255 0 Select daily sequence NotPre 0.05-0.30 Seconds 0.05 Pre-Fault recording timetPost 0.1-5.0 Seconds 0.5 Post-Fault recording timetLim 0.5-6.0 Seconds 6.0 Fault recording time limitPost Retrig On/Off Off Retrigring during Post fault recording

Page 22: Rel 670 Setting Tool -220kv Rajgarh

313470776.xls PAGE:22

SETTING RANGE RECOMMENDED DESCRIPTION

Settings of Phase to Phase measurement

Operation PP On/Off On Operation of distance protection zone 1for Ph-Ph fault

X1PP 0.10-400 11.680 Positive sequence reactance of zone 1 for Ph-Ph fault

R1PP 0.10-400 2.365 Positive sequence resistance of zone 1 for Ph-Ph fault

RFPP 0.10-400 44.730 Resistive reach of distance protection for phase to phase faults

Timer t1PP Off,On On

t1PP (0.0-60) Seconds 0.000 Time delayed trip operation for the distance protection zone 1 for Ph-Ph faultsSettings for Phase to earth elementOperation PE On,Off On

Operation of distance protection zone 1 for Ph-E faultX1PE 0.10-400 11.680R1PE 0.10-400 2.365 Positive sequence resistive reach of distance zone 1 for Ph-E faults

X0PEGroup-I 37.230

Zero sequence line reactance included in distance protection zone 1 for Ph-E faults Group-II 37.2300.10-1200

R0PEGroup-I 8.030

Zero sequence line resistance included in distance protection zone 1 for Ph-E faultsGroup-II 8.0300.10-1200

RFPE 0.10-400 27.365 Resistive Reach for zone 1 for Ph-E faults

Timer t1PE Off,On On

t1PE 0-60 Seconds 0.000 Time delayed trip operation of the distance protection zone 1 for Ph-E faults.

Prepared by : SJR Description:REL670Setting Calculations

Issued by Dept. Year Wk Order Reference: TNEB-2006

PTSY-SCUSTOMER TNEB-2006Rev Year Wk 01 2006 45

Group 1 : Both the parallel feeders are in service.Group 2 : One feeder in service and the other feeder open and earthed at both the ends

PARAMETER SETTING

Operating mode of time delayed trip for the distance protection zone 1 for Ph-Ph faults

Operating mode of time delayed trip for the distance protection zone 1 for Ph-E faults.

Page 23: Rel 670 Setting Tool -220kv Rajgarh

313470776.xls PAGE:23

SETTING RANGE RECOMMENDED DESCRIPTION

ZONE II Distance Protection Zone IIOperation Off,nondir,forward,reverse Forward Operating mode and directionality of distance zone 2Settings of Phase to Phase measurementOperation PP On/Off On Operation of distance protection zone 2 for Ph – Ph fault X1PP 0.10-400 15.800 Positive sequence reactance of zone 2 for Phase to Phase faults R1PP 0.10-400 3.200 Positive sequence resistance of zone 2 for Phase to Phase faultsRFPP 0.10-400 46.399 Resistive reach of distance protection for phase to phase faults

Timer t2PP Off,On On

t12P (0.0-60) Seconds 0.400 Time delayed trip operation for the distance protection zone 2 for Ph-Ph faultsSettings of Phase to earth measurementOperation PE On,Off On Operating mode of distance protection zone 2 for Ph-E faultsX1PE 0.10-400 15.800 Positive sequence reactive reach of distance zone 2 for Ph-E faultsR1PE 0.10-400 3.200 Positive sequence resistive reach of distance zone 2 for Ph-E faults

X0PEGroup-I 50.363

Zero sequence line reactance included in distance protection zone 2 for Ph-E faultsGroup-II 50.3630.10-1200

R0PEGroup-I 10.863

Zero sequence line resistance included in distance protection zone 2 for Ph-E faultsGroup-II 10.8630.10-1200

RFPE 0.10-400 28.200 Resistive Reach for zone 2 for Ph-E faults

Timer t2PE Off,On On

t2PE 0-60 Seconds 0.400 Time delayed trip operation of the distance protection zone 2 for Ph-E faults.

Prepared by : SJR Description:REL670Setting Calculations

Issued by Dept. Year Wk Order Reference: TNEB-2006

PTSY-SCUSTOMER TNEB-2006Rev Year Wk 01 2006 45

PARAMETER SETTING

Operating mode of time delayed trip for the distance protection zone 2 for Ph-Ph faults

Operating mode of time delayed trip for the distance protection zone 2 for Ph-E faults.

Page 24: Rel 670 Setting Tool -220kv Rajgarh

313470776.xls PAGE:24

SETTING RANGE RECOMMENDED DESCRIPTION

Zone III Distance Protection Zone IIIOperation Off, nondir, forward, reverse Forward Operating mode and directionality of zone 3Settings of Phase to Phase measurementOperation PP On/Off On Operation of distance protection zone 3 for Ph-Ph faultX1PP 0.10-400 67.400 Positive sequence reactance of zone 3 for Phase to Phase faultsR1PP 0.10-400 13.649 Positive sequence resistance of zone 3 for Phase to Phase faultsRFPP 0.10-400 67.297 Resistive reach of distance protection for phase to phase faults

Timer t3PP Off,On On

t3PP (0.0-60) Seconds 0.800 Time delayed trip operation for the distance protection zone 3 for Ph-Ph faultsSettings of Phase to earth measurementOperation PE On,Off On Operating mode of distance protection zone 3 for Ph-E faultsX1PE 0.10-400 67.400 Positive sequence reactive reach of distance zone 3 for Ph-E faultsR1PE 0.10-400 13.649 Positive sequence resistive reach of distance zone 3 for Ph-E faults

X0PEGroup-I 214.838

Zero sequence line reactance included in distance protection zone 3 for Ph-E faultsGroup-II 214.8380.10-1200

R0PEGroup-I 46.338

Zero sequence line resistance included in distance protection zone 3 for Ph-E faultsGroup-II 46.3380.10-1200

RFPE 0.10-400 38.649 Resistive Reach for zone 3 for Ph-E faults

Timer t3PE Off,On On

t3PE 0-60 Seconds 0.800 Time delayed trip operation of the distance protection zone 3 for Ph-E faults.

Prepared by : SJR Description:REL670Setting Calculations

Issued by Dept. Year Wk Order Reference: TNEB-2006

PTSY-SCUSTOMER TNEB-2006Rev Year Wk 01 2006 45

PARAMETER SETTING

Operating mode of time delayed trip for the distance protection zone 3 for Ph-Ph faults

Operating mode of time delayed trip for the distance protection zone 3 for Ph-E faults.

Page 25: Rel 670 Setting Tool -220kv Rajgarh

313470776.xls PAGE:25

SETTING RANGE RECOMMENDED DESCRIPTION

Zone IV / ZoneV(To be set in Reverse) Distance protection Zone IV / ZoneVOperation Off, nondir, forward, reverse Reverse Operating mode and directionality of zone 5

Settings of Phase to Phase measurement

Operation PP On/Off On Operation of distance protection zone for Ph-Ph faultX1PP 0.10-400 2.000 Positive sequence reactance of zone for Phase to Phase faultsR1PP 0.10-400 0.405 Positive sequence resistance of zone for Phase to Phase faults

RFPP 0.10-400 12.000 Fault resistance for Ph - Ph faults

Timer t5PP Off,On On

t5PP (0.0-60) Seconds 0.250 Time delayed trip operation for the distance protection zone for Ph-Ph faultsSettings of Phase to earth measurementOperation PE On,Off On Operating mode of distance protection zone for Ph-E faultsX1PE 0.10-400 2.000 Positive sequence reactive reach of distance zone for Ph-E faultsR1PE 0.10-400 0.405 Positive sequence resistive reach of distance zone for Ph-E faults

X0PE 0.01-1200 6.375 Zero sequence line reactance included in distance protection zone for Ph-E faults

R0PE 0.01-1200 1.375 Zero sequence line resistance included in distance protection zone for Ph-E faults

RFPE 0.10-400 9.000 Fault resistance for Ph - E faults

Timer t5PE Off,On On Operating mode of time delayed trip for the distance protection zone for Ph-E faults.

t5PE 0-60 Seconds 0.250 Time delayed trip operation of the distance protection zone for Ph-E faults.

Prepared by : SJR Description:REL670Setting Calculations

Issued by Dept. Year Wk Order Reference: TNEB-2006

PTSY-SCUSTOMER TNEB-2006

Rev Year Wk

PARAMETER SETTING

Operating mode of time delayed trip for the distance protection zone for Ph-Ph faults

Page 26: Rel 670 Setting Tool -220kv Rajgarh

313470776.xls PAGE:26

SETTING RANGE RECOMMENDED DESCRIPTION

ZDIR Directional Measuring Element

ArgDir ( 5 - 45 ) Degrees 15 Lower angle of forward direction characteristic ( 4th Quadrant )

ArgNegRes ( 90 - 175 ) Degrees 115 Upper angle of forward direction characteristic ( 2nd Quadrant )PHS Phase SelectionOperation On/Off On Operation of Phase Selection X1PP (0.10-400) ohm/phase 134.800 Positive Sequence Reactive Reach for ph-ph loop measurmentRFPP (0.10-400) ohm/loop 149.768 Resistive Reach for ph-ph loop measurmentX1PE (0.10-400) ohm/phase 134.800 Positive Sequence Reactive Reach for ph-e loop measurmentX0PE (0.10-1200)ohm/phase 429.675 Zero Sequence Reactive for ph-e loop measurmentRFPE (0.10-400) ohm/loop 126.387 Resistive Reach for ph-e loop measurment

Prepared by : SJR Description:REL670Setting Calculations

Issued by Dept. Year Wk Order Reference: TNEB-2006

PTSY-SCUSTOMER TNEB-2006Rev Year Wk 01 2006 45

PARAMETER SETTING

Page 27: Rel 670 Setting Tool -220kv Rajgarh

313470776.xls PAGE:27

SETTING RANGE RECOMMENDED DESCRIPTION

PSB Powerswing BlockingOperation On,Off On Power swing function on/offDetection On,Off On Operating mode of internal PSD functionX1IN 0.10-400 74.140 Positive sequence reactive reach of the inner boundaryR1IN 0.10-400 104.053 Positive sequence resistive reach of the inner boundaryKX 120-200% 125 Reach multiplication for the outer reactive boundaryKR 120-200% 125 Reach multiplication for the outer resistive boundaryt P1 0-60 0.045 Initial PSD timer for the first swingt P2 0-60 Seconds 0.015 Fast PSD timer for the consecutive swings within 't W't W 0-60 Seconds 0.250 Hold timer for activation of fast PSD timer. t H 0-60 Seconds 0.5 S Hold timer for PSD detectedt EF 0-60 Seconds 3 S Timer overcoming 1-Ph reclosing dead timet R1 0-60 Seconds 0.300 Timer to time delay block by the residual currentt R2 0-60 Seconds 2.000 On delay timer for blocking of output signal at very slow swings.

Z Com Scheme Communication LogicOperation On, Off Off No Scheme is selected since the carrier is not avalable.

Scheme type Permissive UR Operation mode

T coord 0-60 Seconds 0.050 s Coordination timerT sendmin 0-60 Seconds 0.1s Minimum duration of a carrier send signalUnblock Off, No restart, Restart Off Operation mode for an unblocking signalT security 0-60 Seconds 0.035 s Security timerCurrrev On,Off Off Operation mode of current reversal functionT pickup 0-60 Seconds NA Pickup time of current reversal functionT delay 0-60 Seconds NA Time delay for current reversalWEI Weak End Infeed FunctionOperation Off, trip, echo Off Operation mode of WEI functionTwei 0-60 Seconds 0.010 Coordination time for WEI functionUPN< 10-100 70 Voltage detection for Ph-E faultsUPP< 20-170 110 Voltage detection for Ph-Ph faults

Prepared by : SJR Description:REL670Setting Calculations

Issued by Dept. Year Wk Order Reference: TNEB-2006

PTSY-SCUSTOMER TNEB-2006Rev Year Wk 01 2006 45

PARAMETER SETTING

Inter trip, permissive UR, Permissive OR, Blocking

Page 28: Rel 670 Setting Tool -220kv Rajgarh

313470776.xls PAGE:28

SETTING RANGE RECOMMENDED DESCRIPTION

SOTF Switch Onto Fault FunctionOperation On/Off On Operation of SOTF functionFFR Fuse Failure FunctionZeroseq On,Off On FFR zero sequence function On/Off3U0> 10-50% 20 Operating value of voltage U0 - To be checked based on site conditions3Io< 10-50% 10 Operating value of current I0 BRC Broken Conductor SupervisionOperation On,Off On Broken conductor function On/OffIP> 10-100% 10 Minimum Operating current as a % of rated current.T 0-60 Seconds 20.000 Time delayDLD Dead Line DetectionOperation On,Off On dead line detection function ON/OFFU< 10-100% 50 Operating Phase voltageIP< 5-100% of Ib 10 Operating Phase currentI> OverloadOperation On.Off On Overload function On/OffIP> 20-300% 110 Operating value of Phase currentT 0-9000 Seconds 20 s Time delay

Prepared by : SJR Description:REL670Setting Calculations

Issued by Dept. Year Wk Order Reference: TNEB-2006

PTSY-SCUSTOMER TNEB-2006Rev Year Wk 01 2006 45

PARAMETER SETTING

Page 29: Rel 670 Setting Tool -220kv Rajgarh

313470776.xls PAGE:29

SETTING RANGE RECOMMENDED DESCRIPTION

AR Auto Recloser FunctionOperation Off, Stand-by, On On Auto-recloser Off/Stand-by/OnNo of Reclosing 1 to 4 1 Max. No. of Reclosing AttemptsFirst Shot 3 ph, 1/2/3 ph, 1/2 ph 1/2/3 Ph Restriction of fault type for reclosing attemptExtended t1 Off, On Off Extended dead time for loss of permissive channelt1 1ph 0-60 Seconds 0.500 Open time for auto-reclosing at Single phaset1 2ph 0-60 Seconds 0.500 Open time for auto-reclosing at Two phaset1 0-60 Seconds 0.500 Open time for auto-reclosing at Three phasetSync 0.0 - 9000.0 Seconds 0.500 Auto-recloser Max. wait time for synctPulse 0-60 Seconds 0.200 Circuit Breaker closing pulse lengthCut Pulse Off, On Off Shorten closing pulse at a new triptReclaim 0.0 - 9000.0 Seconds 30.000 Auto-recloser reclaim timetInhibit 0-60 Seconds 0.500 Inhibit reset timeCB Ready CO, OCO CO Select type of circuit breaker ready signaltTrip 0-60 Seconds 0.300 Block auto-reclosing for long trip durationPriority None, Low, High None Priority selection between adjacement terminalstWait For-Master 0.0 - 9000.0 Seconds 60.000 Max. wait time for MasterAuto Cont Off, On Off Continue with next reclosing attempt if breaker not closesBlock Unsuc Off, On Off Block auto-reclosing at unsuccessful auto-reclosingtAutoWait 0-60 Seconds 2.000 Max. wait time between shootsUnsuc Mode No CB check, CB check No CB check Unsuccessful-Signal modetUnsuc 0.000 - 9000.0 Seconds 30.000 CB Check time before unsec

Prepared by : SJR Description:REL670Setting Calculations

Issued by Dept. Year Wk Order Reference: TNEB-2006

PTSY-SCUSTOMER TNEB-2006Rev Year Wk 01 2006 45

PARAMETER SETTING

Page 30: Rel 670 Setting Tool -220kv Rajgarh

313470776.xls PAGE:30

RECOMMENDED SETTINGS FOR REL670LINE NAME : MYV-1 Manual Entry to be made to BLUE cells ONLYSUBSTATION : PONNAPURAM 230KV SSPARAMETER SETTING SETTING RANGE RECOMMENDED DESCRIPTIONGeneral setting Minimum operating current Ib (FLC/CT Primary) 0.541 Max. Load Current / CT Primary CurrentIminop (10-30) % of Ib 20

Line Reference Fault LocatorLength unit Km/mile km Unit for presentation of line lengthLine length (0-10000) 36.500 Length of protected lineX1 (0.001-1500) 14.600 Positive sequence reactance of lineR1 (0.001-1500) 2.957 Positive sequence resistance of lineX0 (0.001-1500) 46.538 Zero sequence reactance of lineR0 (0.001-1500) 10.038 Zero sequence resistance of lineX1SA (0.001-1500) 27.240 Positive sequence reactance of source at local endR1SA (0.001-1500) 4.787 Positive sequence resistance of source at local endX1SB (0.001-1500) 85.891 Positive source reactance at remote endR1SB (0.001-1500) 15.095 Positive source resistance at remote endXm0 (0.001-1500) 0.000 Zero sequence mutual reactance for double circuit linesRm0 (0.001-1500) 0.000 Zero sequence mutual resistance for double circuit lines

Disturbamce Report (Basic Settings)Operation On/Off On Operation of Disturbance reporting functionsDistance Unit %/(km/mi) % Selection of presentation mode for the distance to fault*Next Sequence No 0-255 0 Select daily sequence NotPre 0.05-0.30 Seconds 0.05 Pre-Fault recording timetPost 0.1-5.0 Seconds 0.5 Post-Fault recording timetLim 0.5-6.0 Seconds 6.0 Fault recording time limitPost Retrig On/Off Off Retrigring during Post fault recording

Page 31: Rel 670 Setting Tool -220kv Rajgarh

313470776.xls PAGE:31

SETTING RANGE RECOMMENDED DESCRIPTION

ZONE I Distance Protection Zone 1

Operation Off,nondir,forward,reverse Forward Operating mode and directionality of zone 1Settings of Phase to Phase measurement

Operation PP On/Off On Operation of distance protection zone 1for Ph-Ph fault

X1PP 0.10-400 11.680 Positive sequence reactance of zone 1 for Ph-Ph fault

R1PP 0.10-400 2.365 Positive sequence resistance of zone 1 for Ph-Ph fault

RFPP 0.10-400 44.730 Resistive reach of distance protection for phase to phase faults

Timer t1PP Off,On On

t1PP (0.0-60) 0.000 Time delayed trip operation for the distance protection zone 1 for Ph-Ph faultsSettings for Phase to earth elementOperation PE On,Off On

Operation of distance protection zone 1 for Ph-E faultX1PE 0.10-400 11.680R1PE 0.10-400 2.365 Positive sequence resistive reach of distance zone 1 for Ph-E faults

X0PEGroup-I 37.230

Zero sequence line reactance included in distance protection zone 1 for Ph-E faults Group-II 37.2300.10-1200

R0PEGroup-I 8.030

Zero sequence line resistance included in distance protection zone 1 for Ph-E faultsGroup-II 8.0300.10-1200

RFPE 0.10-400 27.365 Resistive Reach for zone 1 for Ph-E faults

Timer t1PE Off,On On

t1PE 0-60 0.000 Time delayed trip operation of the distance protection zone 1 for Ph-E faults.

Prepared by : PTUA - R Description:REL670Setting Calculations

Issued by Dept. Year Wk Order Reference: MSEB-2002

PTUA - RCUSTOMER MSEBRev Year Wk 2002

Group 1 : Both the parallel feeders are in service.Group 2 : One feeder in service and the other feeder open and earthed at both the ends

PARAMETER SETTING

Operating mode of time delayed trip for the distance protection zone 1 for Ph-Ph faults

Operating mode of time delayed trip for the distance protection zone 1 for Ph-E faults.

Page 32: Rel 670 Setting Tool -220kv Rajgarh

313470776.xls PAGE:32

SETTING RANGE RECOMMENDED DESCRIPTION

ZONE II Distance Protection Zone IIOperation Off,nondir,forward,reverse Forward Operating mode and directionality of distance zone 2Settings of Phase to Phase measurementOperation PP On/Off On Operation of distance protection zone 2 for Ph – Ph fault X1PP 0.10-400 15.800 Positive sequence reactance of zone 2 for Phase to Phase faults R1PP 0.10-400 3.200 Positive sequence resistance of zone 2 for Phase to Phase faultsRFPP 0.10-400 46.399 Resistive reach of distance protection for phase to phase faults

Timer t2PP Off,On On

t12P (0.0-60) 0.400 Time delayed trip operation for the distance protection zone 2 for Ph-Ph faultsSettings of Phase to earth measurementOperation PE On,Off On Operating mode of distance protection zone 2 for Ph-E faultsX1PE 0.10-400 15.800 Positive sequence reactive reach of distance zone 2 for Ph-E faultsR1PE 0.10-400 3.200 Positive sequence resistive reach of distance zone 2 for Ph-E faults

X0PEGroup-I 50.363

Zero sequence line reactance included in distance protection zone 2 for Ph-E faultsGroup-II 50.3630.10-1200

R0PEGroup-I 10.863

Zero sequence line resistance included in distance protection zone 2 for Ph-E faultsGroup-II 10.8630.10-1200

RFPE 0.10-400 28.200 Resistive Reach for zone 2 for Ph-E faults

Timer t2PE Off,On On

t2PE 0-60 0.400 Time delayed trip operation of the distance protection zone 2 for Ph-E faults.

Prepared by : PTUA - R Description:REL670Setting Calculations

Issued by Dept. Year Wk Order Reference: MSEB-2002

PTUA - RCUSTOMER MSEBRev Year Wk 2002

PARAMETER SETTING

Operating mode of time delayed trip for the distance protection zone 2 for Ph-Ph faults

Operating mode of time delayed trip for the distance protection zone 2 for Ph-E faults.

Page 33: Rel 670 Setting Tool -220kv Rajgarh

313470776.xls PAGE:33

SETTING RANGE RECOMMENDED DESCRIPTION

Zone III Distance Protection Zone IIIOperation Off, nondir, forward, reverse Forward Operating mode and directionality of zone 3Settings of Phase to Phase measurementOperation PP On/Off On Operation of distance protection zone 3 for Ph-Ph faultX1PP 0.10-400 67.400 Positive sequence reactance of zone 3 for Phase to Phase faultsR1PP 0.10-400 13.649 Positive sequence resistance of zone 3 for Phase to Phase faultsRFPP 0.10-400 67.297 Resistive reach of distance protection for phase to phase faults

Timer t3PP Off,On On

t3PP (0.0-60) 0.800 Time delayed trip operation for the distance protection zone 3 for Ph-Ph faultsSettings of Phase to earth measurementOperation PE On,Off On Operating mode of distance protection zone 3 for Ph-E faultsX1PE 0.10-400 67.400 Positive sequence reactive reach of distance zone 3 for Ph-E faultsR1PE 0.10-400 13.649 Positive sequence resistive reach of distance zone 3 for Ph-E faults

X0PEGroup-I 214.838

Zero sequence line reactance included in distance protection zone 3 for Ph-E faultsGroup-II 214.8380.10-1200

R0PEGroup-I 46.338

Zero sequence line resistance included in distance protection zone 3 for Ph-E faultsGroup-II 46.3380.10-1200

RFPE 0.10-400 38.649 Resistive Reach for zone 3 for Ph-E faults

Timer t3PE Off,On On

t3PE 0-60 0.800 Time delayed trip operation of the distance protection zone 3 for Ph-E faults.

Prepared by : PTUA - R Description:REL670Setting Calculations

Issued by Dept. Year Wk Order Reference: MSEB-2002

PTUA - RCUSTOMER MSEBRev Year Wk 2002

PARAMETER SETTING

Operating mode of time delayed trip for the distance protection zone 3 for Ph-Ph faults

Operating mode of time delayed trip for the distance protection zone 3 for Ph-E faults.

Page 34: Rel 670 Setting Tool -220kv Rajgarh

313470776.xls PAGE:34

SETTING RANGE RECOMMENDED DESCRIPTION

Zone IV / ZoneV(To be set in Reverse) Distance protection Zone IV / ZoneVOperation Off, nondir, forward, reverse Reverse Operating mode and directionality of zone 5

Settings of Phase to Phase measurement

Operation PP On/Off On Operation of distance protection zone for Ph-Ph faultX1PP 0.10-400 2.000 Positive sequence reactance of zone for Phase to Phase faultsR1PP 0.10-400 0.405 Positive sequence resistance of zone for Phase to Phase faults

RFPP 0.10-400 12.000 Fault resistance for Ph - Ph faults

Timer t5PP Off,On On

t5PP (0.0-60) 0.250 Time delayed trip operation for the distance protection zone for Ph-Ph faultsSettings of Phase to earth measurementOperation PE On,Off On Operating mode of distance protection zone for Ph-E faultsX1PE 0.10-400 2.000 Positive sequence reactive reach of distance zone for Ph-E faultsR1PE 0.10-400 0.405 Positive sequence resistive reach of distance zone for Ph-E faults

X0PE 0.01-1200 6.375 Zero sequence line reactance included in distance protection zone for Ph-E faults

R0PE 0.01-1200 1.375 Zero sequence line resistance included in distance protection zone for Ph-E faults

RFPE 0.10-400 9.000 Fault resistance for Ph - E faults

Timer t5PE Off,On On Operating mode of time delayed trip for the distance protection zone for Ph-E faults.

t5PE 0-60 0.250 Time delayed trip operation of the distance protection zone for Ph-E faults.

Prepared by : PTUA - R Description:REL670Setting Calculations

Issued by Dept. Year Wk Order Reference: MSEB-2002

PTUA - RCUSTOMER MSEB

Rev Year Wk

PARAMETER SETTING

Operating mode of time delayed trip for the distance protection zone for Ph-Ph faults

Page 35: Rel 670 Setting Tool -220kv Rajgarh

313470776.xls PAGE:35

SETTING RANGE RECOMMENDED DESCRIPTION

ZDIR Directional Measuring Element

ArgDir ( 5 - 45 ) Degrees 15 Lower angle of forward direction characteristic ( 4th Quadrant )

ArgNegRes ( 90 - 175 ) Degrees 115 Upper angle of forward direction characteristic ( 2nd Quadrant )

PHS Phase SelectionOperation On/Off On Operation of Phase Selection X1PP (0.10-400) ohm/phase 134.800 Positive Sequence Reactive Reach for ph-ph loop measurmentRFPP (0.10-400) ohm/loop 149.768 Resistive Reach for ph-ph loop measurmentX1PE (0.10-400) ohm/phase 134.800 Positive Sequence Reactive Reach for ph-e loop measurmentX0PE (0.10-1200)ohm/phase 429.675 Zero Sequence Reactive for ph-e loop measurmentRFPE (0.10-400) ohm/loop 126.387 Resistive Reach for ph-e loop measurment

Prepared by : PTUA - R Description:REL670Setting Calculations

Issued by Dept. Year Wk Order Reference: MSEB-2002

PTUA - RCUSTOMER MSEBRev Year Wk 2002

PARAMETER SETTING

Page 36: Rel 670 Setting Tool -220kv Rajgarh

313470776.xls PAGE:36

SETTING RANGE RECOMMENDED DESCRIPTION

PSB Powerswing BlockingOperation On,Off On Power swing function on/offDetection On,Off On Operating mode of internal PSD functionX1IN 0.10-400 74.140 Positive sequence reactive reach of the inner boundaryR1IN 0.10-400 104.053 Positive sequence resistive reach of the inner boundaryKX 120-200% 125%. Reach multiplication for the outer reactive boundaryKR 120-200% 125%. Reach multiplication for the outer resistive boundaryt P1 0-60 0.045 Initial PSD timer for the first swingt P2 0-60 0.015 Fast PSD timer for the consecutive swings within 't W't W 0-60 0.250 Hold timer for activation of fast PSD timer. t H 0-60 0.5 S Hold timer for PSD detectedt EF 0-60 3 S Timer overcoming 1-Ph reclosing dead timet R1 0-60 0.300 Timer to time delay block by the residual currentt R2 0-60 2.000 On delay timer for blocking of output signal at very slow swings.

Z Com Scheme Communication LogicOperation On, Off Off No Scheme is selected since the carrier is not avalable.

Scheme type Permissive UR Operation mode

T coord 0-60 0.050 s Coordination timerT sendmin 0-60 0.1s Minimum duration of a carrier send signalUnblock Off, No restart, Restart Off Operation mode for an unblocking signalT security 0-60 0.035 s Security timerCurrrev On,Off Off Operation mode of current reversal functionT pickup 0-60 NA Pickup time of current reversal functionT delay 0-60 NA Time delay for current reversalWEI Weak End Infeed FunctionOperation Off, trip, echo Off Operation mode of WEI functionTwei 0-60 0.010 Coordination time for WEI functionUPN< 10-100 70 Voltage detection for Ph-E faultsUPP< 20-170 110 Voltage detection for Ph-Ph faults

Prepared by : PTUA - R Description:REL670Setting Calculations

Issued by Dept. Year Wk Order Reference: MSEB-2002

PTUA - RCUSTOMER MSEBRev Year Wk 2002

PARAMETER SETTING

Inter trip, permissive UR, Permissive OR, Blocking

Page 37: Rel 670 Setting Tool -220kv Rajgarh

313470776.xls PAGE:37

SETTING RANGE RECOMMENDED DESCRIPTION

SOTF Switch Onto Fault FunctionOperation On/Off On Operation of SOTF functionFFR Fuse Failure FunctionZeroseq On,Off On FFR zero sequence function On/Off3U0> 10-50% 10 Operating value of voltage U0 - To be checked based on site conditions3Io< 10-50% 10 Operating value of current I0 BCS Broken Conductor SupervisionOperation On,Off On Broken conductor function On/OffIP> 10-100% 10 Minimum Operating current as a % of rated current.T 0-60 20.000 Time delayDLD Dead Line DetectionOperation On,Off On dead line detection function ON/OFFU< 10-100% 50 Operating Phase voltageIP< 5-100% of Ib 10 Operating Phase currentI> OverloadOperation On.Off On Overload function On/OffIP> 20-300% 110 Operating value of Phase currentT 0-9000 20 s Time delayFault LocatorLength unit Km/mile km Unit for presentation of line lengthLine length 0-10000 36.500 Length of protected lineX1 0.001-1500 14.600 Positive sequence reactance of lineR1 (0.001-1500) 2.957 Positive sequence resistance of lineX0 (0.001-1500) 46.538 Zero sequence reactance of lineR0 (0.001-1500) 10.038 Zero sequence resistance of lineX1SA (0.001-1500) 68.099 Positive sequence reactance of source at local endR1SA (0.001-1500) 11.968 Positive sequence resistance of source at local endX1SB (0.001-1500) 214.727 Positive source reactance at remote endR1SB (0.001-1500) 37.738 Positive source resistance at remote end

Xm0 Group-I 0.000

Zero sequence mutual reactance for double circuit lines(0.001-1500) Group-II 0.000

Rm0 Group-I 0.000

Zero sequence mutual resistance for double circuit lines(0.001-1500) Group-II 0.000

Distance unit km/mile Selection of presentation mode for the distance to fault*

Prepared by : PTUA - R Description:REL670Setting Calculations

Issued by Dept. Year Wk Order Reference: MSEB-2002

PTUA - RCUSTOMER MSEB

PARAMETER SETTING

%/Km/mile

Page 38: Rel 670 Setting Tool -220kv Rajgarh

313470776.xls PAGE:38

PTUA - RRev Year Wk 2002

SETTING RANGE RECOMMENDED DESCRIPTION

AR Auto Recloser FunctionOperation Off, Stand-by, On On Auto-recloser Off/Stand-by/OnNo of Reclosing 1 to 4 1 Max. No. of Reclosing AttemptsFirst Shot 3 ph, 1/2/3 ph, 1/2 ph 1/2/3 Ph Restriction of fault type for reclosing attemptExtended t1 Off, On Off Extended dead time for loss of permissive channelt1 1ph 0.000 - 60.000 0.500 Open time for auto-reclosing at Single phaset1 2ph 0.000 - 60.000 0.500 Open time for auto-reclosing at Two phaset1 0.000 - 60.000 0.500 Open time for auto-reclosing at Three phasetSync 0.0 - 9000.0 0.500 Auto-recloser Max. wait time for synctPulse 0.0 - 60.000 0.200 Circuit Breaker closing pulse lengthCut Pulse Off, On Off Shorten closing pulse at a new triptReclaim 0.0 - 9000.0 30.000 Auto-recloser reclaim timetInhibit 0.0 - 60.000 0.500 Inhibit reset timeCB Ready CO, OCO CO Select type of circuit breaker ready signaltTrip 0.0 - 60.000 0.300 Block auto-reclosing for long trip durationPriority None, Low, High None Priority selection between adjacement terminalstWait For-Master 0.0 - 9000.0 60.000 Max. wait time for MasterAuto Cont Off, On Off Continue with next reclosing attempt if breaker not closesBlock Unsuc Off, On Off Block auto-reclosing at unsuccessful auto-reclosingtAutoWait 0.000 - 60.000 2.000 Max. wait time between shootsUnsuc Mode No CB check, CB check No CB check Unsuccessful-Signal modetUnsuc 0.000 - 9000.0 30.000 CB Check time before unsec

Prepared by : PTUA - R Description:REL670Setting Calculations

Issued by Dept. Year Wk Order Reference: MSEB-2002

PTUA - RCUSTOMER MSEBRev Year Wk 2002

PARAMETER SETTING

Page 39: Rel 670 Setting Tool -220kv Rajgarh

-40 -30 -20 -10 0 10 20 30 40 50 60

-40

-20

0

20

40

60

80

REL 5xx Zone char

Resistance(R)

Re

ac

tan

ce

(X)

Page 40: Rel 670 Setting Tool -220kv Rajgarh

-40 -30 -20 -10 0 10 20 30 40 50 60

-20

-10

0

10

20

30

40

50

60

70

80

REL5xx Ph-Ph Char

Resistance(R)

Re

ac

tan

ce

(X)

Page 41: Rel 670 Setting Tool -220kv Rajgarh

Revision Status:Last edited on 25/11/2004

Instructions for Using the Setting Calculation Toolfor REL 5xx Numerical Line Protection Terminals

Always remember the following steps:

1. Open file by enabling macros. If by mistake you disabled the macros, reopen

the file by enabling macros..

2. This excel sheet is a read only file. Don’t remove the restriction, so that you

will not loose the original file

3. Once the data entry is over, use Save As command for saving your file.

4. In first sheet, choose the terminal (REL 511, REL 521 & REL 531), for

which setting calculation is to be done.

5. Fill in the blue coloured cells only.

6. Remember you are not allowed to put any data, in cells other than the blue

cells.

7. In first sheet (System Details) you have to Tick in cell B17, if the terminal is

REL 531 and is used for series compensated line.

8. User has to feed only “recomm_setting REL5..” sheet data into the relay.

Note: Suggestions on Improvement are Welcome. This excel sheet may contain

errors (may be zero errors). Request to report the errors to PTUA-RT.

THIS EXCEL SHEET IS INTENDED FOR INTERNAL USE OF ABB

PERSONALS.

This Setting Tool may change without prior notice. So its advised always use

latest Tool from PTUA-R database.

Page 42: Rel 670 Setting Tool -220kv Rajgarh

Instructions for Using the Setting Calculation Toolfor REL 5xx Numerical Line Protection Terminals

Always remember the following steps:

1. Open file by enabling macros. If by mistake you disabled the macros, reopen

the file by enabling macros..

2. This excel sheet is a read only file. Don’t remove the restriction, so that you

will not loose the original file

3. Once the data entry is over, use Save As command for saving your file.

4. In first sheet, choose the terminal (REL 511, REL 521 & REL 531), for

which setting calculation is to be done.

5. Fill in the blue coloured cells only.

6. Remember you are not allowed to put any data, in cells other than the blue

cells.

7. In first sheet (System Details) you have to Tick in cell B17, if the terminal is

REL 531 and is used for series compensated line.

8. User has to feed only “recomm_setting REL5..” sheet data into the relay.