basic air conditioning system in a building

Citation preview

  • AIR-CONDITIONING

    Compiled by

    Mohd. Rodzi IsmailSchool of Housing Building & Planning

  • INTRODUCTION

  • Definitions

    The cooling of air (simple definition) The process of treating air in an internal environment to

    establish and maintain required standards of temperature, humidity, cleanliness and motion. Temperature (air temperature) is controlled by cooling

    (the removal of heat) the air Humidity, the water vapour content of the air, is controlled

    by adding or removing water vapour from the air (humidification or dehumidification)

    Cleanliness or air quality is controlled by either filtration or by ventilation. Often both are used in an installation

    Motion refers to air velocity and to where the air is distributed. It is controlled by appropriate air distributing equipment

  • Why do we need air-conditioning? Comfort Work performance and production Process Health Conservation of equipment and material Symbol of status

  • Air-conditioning & comfort Comfort temperature range from 23 oC to 27 oC (25 oC 2) Effective humidity form 40% to 60% Air velocity less than 0.2 ms-1 Sufficient clean air Noise from equipment and ductwork should be avoided

  • HEAT & REFRIGERATION

  • What is ................ ?

    Heat A form of energy. Every object

    contains heat energy in both quantity and intensity.

    Refrigeration The process of removing heat from

    one substance and transferring it to another substance.

  • Heat intensity is measured by its temperature, commonly in either F or C

    The quantity of heat is not the same as intensity of heat

    Quantity and Intensity of Heat

    Dessert Candle

    High in quantity of

    heat

    High in intensity of

    heat

  • 43.3C (110F)15.6C (60F)

    same quantity of heat

    contains more heat per unit of mass

    (the heat energy is more concentrated)

  • Measuring Heat Quantity

    60F 61F

    15C 16C

    1 Btu

    1 kcal

    1 lbwater

    1 kgwater

    (kilocalorie)

    Btu - the quantity of heat energy required to raise the temperature of 1 lb of water by 1F.

    (British Thermal Unit)

    kcal - the amount of heat energy required to raise the temperature of 1 kg of water by 1C

  • Principles of Heat Transfer

    Heat energy cannot be destroyed Heat always flows from a higher temperature substance

    to a lower temperature substance Heat can be transferred from one substance to another

  • Heat can only be transferred to another substance - the principle of conservation of energy.

    Heat energy cannot be destroyed

    As heat is transferred from the beverage to the ice, the temperature of the beverage is lowered. The heat transferred/removed is not destroyed but instead is absorbed by the ice, changing the ice from a solid to a liquid.

  • Heat flows from hot to cold

    Heat always flows from a higher temperature substance to a lower temperature substance

  • Three basic methods of heat transfer Conduction is the process of transferring heat through a

    solid

    RADIATIONRADIATION

    hotwater

    hotwater CONDUCTIONCONDUCTION

    CONVECTIONCONVECTION

    cool aircool air

    warm airwarm air

    Heat can be transferred from one substance to another

    Convection is the process of transferring heat as the result of the movement of air caused by temperature (density) differences

    Radiation is the process of transferring heat by means of electromagnetic waves, emitted due to the temperature difference between two objects

  • The quantity of heat that flows from one substance to another within a given period of time

    Commonly expressed in terms of Btu/hrthe quantity of heat, in Btus, that flows from one substance to another over a period of 1 hour

    In the SI metric system of units, it is expressed in terms of kilowatts (kW), which are equivalent to kJ/sec - the quantity of heat, in kJ, that flows from one substance to another over a period of 1 second

    A larger and more convenient measure of the rate of heat flow in English system of units called a ton of refrigeration (TR) 1TR is defined as the transfer of heat at the rate of 12,000 Btu/hr (3.517 kW).

    Heat Flow Rate

  • REFRIGERANTS

  • Icemelts at 32oF [0oC]

    Dry ice evaporates at -109.4F [-78.6C]

    Refrigerant-22 (R-22) boils at -41.4F [-40.8C]

    Coolant

    Each of these three substances (pure ice, dry ice, and R-22) absorbs heat and changes phase at its own fixed temperature

  • Effect of Transferring Heat

    60F 61F

    15C 16C

    1 Btu

    1 kcal

    1 lbwater

    1 kgwater

    By adding or subtracting heat energy, the temperature is raised or lowered

  • Effect of Transferring Heat

    60F 212F

    15C 100C

    + 152 Btu =

    + 85 kcal =

    1 lbwater

    1 kgwater

    The amount of energy added will raise the water temperature to its boiling point

  • Effect of Transferring Heat

    212F

    100C

    + 970.3 Btu =

    + 244.5 kcal =

    1 lbsteam

    1 kgsteam

    1 lbwater

    1 kgwater

    212F

    100CAt its boiling point, with the amount of energy added, water will completely transform into steam at the same temperature

  • Effect of Transferring Heat

    212F

    100C

    1 lbwater

    1 kgwater

    1 lbsteam

    1 kgsteam

    - 970.3 Btu =

    - 244.5 kcal =

    212F

    100C

    Condensation

  • Latent Heat

    212F

    100C

    970.3 Btu

    244.5 kcal

    1 lbsteam

    1 kgsteam

    1 lbwater

    1 kgwater

    212F

    100CLatent heat - the energy involved in changing the phase of a substance (e.g. from a liquid to a vapor)The temperature during the phase change remain the same

  • Sensible Heat

    60F 61F

    15C 16C

    1 Btu

    1 kcal

    1 lbwater

    1 kgwater

    Sensible heat - heat energy that, when added to or removed from a substance, results in a measurable change in temperature.

  • AA BB

    Specific Heat140F[60C]

    200F[93.3C]

    The specific heat of a substance is defined as the quantity of heat, in Btus, required to raise the

    temperature of 1 lb of that substance 1F the quantity of heat, in kJs, required to raise the

    temperature of 1 kg of that substance 1C

    Higher capacity for absorbing

    heat

  • 25

    Modern Refrigerants Refrigerants are substances that are used to absorb

    and transport heat for the purpose of cooling. When selecting a refrigerant to use for a given

    application, in addition to these heat transfer properties the manufacturer considers;

    EfficiencyOperating pressuresCompatibility with materialsStabilityToxicity

    FlammabilityCostAvailabilitySafety, andEnvironmental impact.

  • 26

    Historically, space cooling systems have relied on chlorofluorocarbon (CFC) refrigerants (R-11, R-12) and hydrochlorofluorocarbon (HCFC) refrigerant (R-22)

    Refrigerant-22 has been the most widely used refrigerant in residential, commercial, and industrial applications since the 1940s

    The most common refrigerants used in mechanical refrigeration systems today are Refrigerant-123 (or R-123), R-134a, and R-22

    Ammonia (R-717) and, under certain operating pressures, even water (R-718) and carbon dioxide (R-744) can be used as refrigerants

  • 27

    Example of Types of Refrigerants and Their Use

    Refrigerant Name Equipment Use

    HCFC-22 (R-22) residential air conditioning (central and window)commercial rooftop air conditioning, residential and commercial heat pumpslarge air conditioning equipment (chillers)commercial refrigeration equipment for supermarkets, food storage, beverage coolers, etc.

    HCFC-123 (R-123) large air conditioning equipment (chillers)

    HCFC Blends (R-401 A&B, 402A&B, 405A, 406A, 408A, 409A, 411A&B, 414A&B and 416A

    commercial refrigeration equipment (e.g. supermarkets, food processing, storage & distribution)beverage & large commercial coolersice machinesice drinks

  • 28

    These refrigerants will be phased out due to environmental concern (ozone layer depletion) & to comply with the world CFC reduction standards (Montreal Protocol)

    The most widely accepted replacement option for HCFCs is the use of hydrofluorocarbons (HFCs)

    Ammonia is also a replacement option in the large commercial air conditioning and refrigeration sectors

    These refrigerants do not deplete the ozone layer and can replace both CFC and HCFC uses

  • 29

    Phase-out schedule for HCFCs based on the terms of the Montreal Protocol

    Jan. 1, 1996 baseline annual allowable amount of HCFCs based on Montreal Protocol

    Jan. 1, 2004 annual allowable amount of HCFCs reduced by 35%

    Jan. 1, 2010 annual allowable amount of HCFCs reduced by 65%

    Jan. 1, 2010 no new R-22 equipment manufactured or imported

    Jan. 1, 2015 annual allowable amount of HCFCs reduced by 90%

    Jan. 1, 2020 annual allowable amount of HCFCs reduced by 99.5% except HCFC-123, which can be imported or manufactured until 2030 to service large air conditioning units (chillers) under the remaining .5% allowance. No new HCFC equipment to be manufactured or imported

    Jan. 1, 2030 HCFCs no longer permitted to be imported or manufactured

    The HCFC Phase-out Schedule

  • REFRIGERATION CYCLE

  • Basic Refrigeration System

    compressor

    condenser

    evaporator

    expansion device

    dischargeline

    suctionline

    liquidline

    A

    B

    C

    D

  • Cooling equipment moves heat from cool indoor spaces to warmer outdoor locations. It moves heat by causing a refrigerant to evaporate and condense. Refrigerants capture a lot of heat when they evaporate, and the captured heat is released when refrigerant vapour condenses.

    4 cooling cycles components

    A compressor circulates refrigerantthrough the loop and an expansion valve maintains low pressure on the suction side of the compressor and high pressure on the discharge side.

  • AIR-CONDITIONING SYSTEMS & COMPONENTS

  • Air-Conditioning System Common Components Condenser

    Part of the system that pressurizes refrigerant to cool it by changing it from a vapor to a liquid

    CompressorMotorised equipment that circulates coolant through the system.

    EvaporatorA system of coils that, when filled with cold refrigerant, cools the air around it

    Expansion valve/DeviceControlling pressure

    Air handlerShort for air-handling unit (AHU), the blower equipment designed for circulating cooled air through a central air-conditioning system.

  • Vapor-Compression Refrigeration

    expansiondevice

    condenser

    compressor

    evaporator

  • Large Air-Conditioning Equipment

    SCHEMATIC COOLING COMPONENTS

    PHYSICAL COOLING COMPONENTS

    AHUChiller

    Cooling tower

  • Types of Air-Conditioning Systems

    AIR-CONDITIONING SYSTEM

    UNITARY SYSTEM

    PLANT SYSTEM

    LOCAL CONTROL SYSTEM

    PACKAGE UNIT

    SPLIT UNIT

    WINDOW UNIT

    CENTRAL HANDLING PLANT SYSTEM

    CHILLED WATER PLANT SYSTEM

    SELF-CONTAINED PACKAGED UNIT

    AIR COOLED PACKAGE UNIT

    WATER COOLED PACKAGE UNIT

    SPLIT SYSTEM WITHOUT OUTSIDE AIR

    SPLIT SYSTEM WITH OUTSIDE AIR

    INDUCTION UNIT SYSTEM

    FAN COIL UNIT SYSTEM

    VARIABLE AIR VOLUME UNIT SYSTEM

    Classification based on layout arrangement, equipment and components

  • 38

    Classification based on air handling and distribution: Low velocity system High velocity system Constant volume system Variable air volume system

    Classification based on air cooled method prior to distribution into space: Direct expansion system All air system Water to air system All water system

  • 39

    Classification based on services to the cooled area: Single zone system Multi zone system Terminal Reheat system Dual-duct system

  • Room Air-ConditionerRoom air conditioner are a sensible cooling solutionfor situations where you only want to cool one or two rooms. Like central air conditioners, room air conditioners extract heat and moisture from the room air, cool it, and return the air to the room. A blower pulls warm room air through a filter.

    The main difference between a room and a central air conditioner is that a room air conditioner is a single, self-contained unit with evaporator or cooling coils, a condenser, and refrigerant-filled tubing all in one box.

  • Split Air-ConditionerEvaporator

    (indoor)

    Condenser(outdoor)

    Insulated refrigerant piping & wiring

    TThermostat

  • 42Cassette type

    Split unit chiller

  • 43

    Package Air Conditioners

    They are bigger versions of the room air conditioners and available in nominal capacities of 3, 5, 7, 10 and 15 tons.

    Like the room air conditioners, the package unit also houses:i. Air filteringii. Cooling-humidifyingiii. Air handling components

    The package air conditioners are usually factory assembled and condensers can be air-cooled or water-cooled type.

  • 44

    Water-cooled package units

  • 45

    Indoor self-contained units (Capacity: 10 105 TR)

    Single package units

  • Variable Refrigerant Volume (VRV)

  • Central Air-ConditionerIn a typical air conditioning system, a refrigerant circulates through a loop of copper tubing that runs between an outdoor coil (the condenser) and an indoor coil (the evaporator).

    Refrigerant travels between the two coils, absorbing heat from the room and releasing it outside. In the process, the refrigerant cools the evaporator coils. A blower sends the chilled air into the room. The cooling effect causes the warm air to release its moisture, which drops into a drain pan and is carried away.

  • Centralised air-conditioning system

    Air handling unit

  • 50

    AC SYSTEM SELECTION CRITERIA

    Air-conditioning design and selection criteria can be classified as follows: Comfort criteria

    These criteria include noise considerations, accuracy of control space conditions, amount of fresh air and air filtration, and tolerance of the effects of failure in the AC system.

    Space considerations AC systems occupy substantial space and AC components

    may require special support from structure. Space considerations include space required to house the

    equipment and the distribution ductwork and pipework. AHU room - 3% of total floor area cooled by that unit Plant room - 5% of total cooled floor area

    Another major considerations is the accessibility of the equipment for maintenance purposes.

  • 51

    First cost An important consideration in the design and selection of AC

    systems. There is a tendency for owners to prefer low first cost. Careful consideration should be given to the expandability of

    the system as well as to implications on the operating costs. Operating cost

    One of the most important considerations in the design selection of air-conditioning systems.

    The energy cost should be calculated and competing systems should be compared in terms of their life cycle cost which takes into account capital, energy and maintenance costs over the whole life of the systems.

  • 52

    Flexibility & maintenance The system should be flexible enough to meet changes in the

    use of building. The reliability, maintainability and the cost of maintenance

    contracts as well as the cost of replacement of major components should be considered in deciding between alternative systems.

    Others Fire protection & smoke control, interior & exterior appearance and

    environmental effects

    The final choice lies on the owner of the building/financier of the projects. This choice should be based on the recommendations of the consultants who should provide justifications for the recommended design solution against the requirements of the owner/financier.

  • 53

    LOCATION OF PLANT ROOM

    Top floorAdvantage Disadvantage

    Main spaces at ground level are fully utilised for other purposes (no waste of spaces)

    Load on building frame increased

    Piping distance of chilled water from cooling tower to plant room could be reduced if located on the same floor

    Noise from vibration of equipment

    Good ventilation at the top Accessibility challenge for maintenance personnel

  • 54

    Middle floorAdvantage Disadvantage

    No waste of main spaces Increase load on building frame

    Piping distance of chilled water from cooling tower to plant room could be reduced if located on the same floor

    Noise from vibration of equipment

    Good ventilation at this level

    Zoning for air distribution could easily be done

  • 55

    Ground floorAdvantage Disadvantage

    Easy accessibility for maintenance personnel

    Waste of valuable space on ground floor

    Reduce load on building structure

    Longer piping installation to connect the plant room to cooling tower at roof top

    Good ventilation at this level

    Ventilation problem occurs if the cooling tower is located on the ground floor since it emits heat

    Zoning for air distribution could easily be done

  • 56

    UndergroundAdvantage Disadvantage

    No waste of valuable space

    Longer piping installation to connect the plant room to cooling tower at roof top

    Reduce load on building structure

    The equipment would be at risk if flood occurs

    Easy accessibility for maintenance personnel

    Reduce space for parking

    Reduce noise and vibration

    Ventilation is very critical

  • 57

    It could also be explained as follows.

    Away from building Suitable to avoid noise to the

    user

    Alleviate in getting water supply, ventilation and maintenance work

    Plant room

    SECTION

    PLAN

  • 58

    Scattered and in between spaces For provisions of air-

    conditioning requirements for multiple uses and various cooling load between spaces

    Also acts as boundaries between buildings (but it is expensive to have many plant rooms as compared to just one huge plant room with similar capacity)

    PLAN

    PLAN

    PLAN

  • 59

    AIR HANDLING UNIT (AHU) ROOM

    Location of AHU room Should be near to facility zone or noise zone (to assist in

    maintenance work) Must consider fresh air intake Not too close to toilet to avoid contaminated air (minimum

    around 6 m) Not too close to parking area (especially closed parking area) Should be in one line vertically As close as possible to the cooling area

  • 60

    LOCATION OF COLING TOWER

    Roof top Advantage DisadvantageAlleviate in getting optimum ventilation

    Could be a problem for maintenance work

    Valuable spaces can be fully utilised

    Increase of load on buildings main frames

    No eyesore view Vibration to building structure

    Heat can be directly discharged outside

  • 61

    Podium Advantage DisadvantageAlleviate in getting optimum ventilation

    Eyesore view from the tower building

    Valuable spaces can be fully utilised

    Condensation of discharged heat will happen and move upward increase in building cooling load

  • 62

    Ground level

    Advantage Disadvantage

    Alleviate in maintenance work

    Waste of valuable spaces at this level

    Load on buildings main frames could be reduced

    Increase of heat to the surrounding

    Location of cooling tower could be far from the building

    Eyesore and vibration

  • COOLING LOAD

  • Space Heat Gain Components

    The space cooling load is the rate at which heat must be removed from a space in order to maintain the desired conditions in the space, generally a dry-bulb temperature and relative humidity

    Cooling load from external heat gainsi. Solar heat gain through the fenestration areas of the buildingii. Conduction heat gains through the fenestration areas, walls and roofiii. Conduction heat gains through internal partitions, ceilings and floorsiv. Heat gains through infiltration and ventilation air

    Cooling load from internal heat gainsi. Peopleii. Lightingiii. Electrical equipment and appliances

  • roof

    lights

    equipment

    floor

    exteriorwall

    glass solar

    glassconduction

    infiltrationpeople

    partitionwall

  • Cooling Load Components

    sensibleload

    latentload

    conduction through roof, walls, windows,and skylights

    solar radiation through windows, skylightsconduction through ceiling, interior

    partition walls, and floorpeoplelightsequipment/appliancesinfiltrationventilationsystem heat gains

    spaceload

    coilloadcooling load components

  • Cooling Load Estimation

    Rule of thumb Cooling capacity for an enclosed area

    = Area (ft2) x Cooling load factor (Btu/hr ft2)

    Capacity of A/C:

    1 HP (horsepower) = 9,000 Btu/hr1 TR (Ton refigerant) = 12,000 Btu/hr1 kW= 3,412 Btu/hr1 kcal= 3.968 Btu/hr

  • Detail estimation based on ASHRAEs recommendation

  • PSYCHROMETRICS

  • Psychrometry

    Psychrometry the science of studying the thermodynamic properties of

    moist air and the use of these properties to analyze conditions and processes involving moist air

    The air condition can be determined by using a Psychrometric Chart.

    Use of psychrometric chart determination of comfort zone prediction of condensation problems calculation of HVAC capacity/design

  • Common properties used in the psychrometric chart includesi. dry-bulb temperature (Tdb) ii. wet-bulb temperature (Twb)iii. relative humidity (RH) iv. humidity ratio (w) (moisture content/absolute humidity)v. specific volume (v)vi. dew point temperature (Tdp)vii. enthalpy (h)

    With two known properties it is possible to characterise the air in the intersection of the property lines, the state-point. With the intersection point located on the chart or diagram, other air properties can be read directly.

  • DefinitionsDry Bulb Temperature (Tdb):

    The air temperature measured with a standard thermometer , oC

    Dew Point Temperature (Tdp): The temperature at which water vapor in the air will condense

    from a gas to liquid if cooled at constant pressure and humidity ratio (w), oC

    Examples: Condensation on cold window, cloud formationWet Bulb Temperature (Twb):

    The temperature at which water vapour is evaporated into air bringing it to saturation conditions at the same temperature, oC

    Temperature measured by the wetted thermometer in a psychrometer

    Indirect measure of how saturated the air is

  • Humidity Ratio (w): The amount (mass) of water in the air, kg/water/kg/air

    Relative Humidity (RH or ): A measure of the actual amount of water vapor in the air

    compared to the saturated conditions, %

    w

    ws

    w

    ws

    Pactual vapor pressure of water in the air

    vapor pressure of water in the air @ saturation P

    xmole fraction of water in the air

    mole fraction of water in the air @ saturation x

  • Enthalpy (h): The total energy content of the water vapor mixture,

    kJkgdry air

    Specific Volume (): Inverse of the air density, m3

    kgdry air

  • Related Physical Laws

    Ideal Gas Law: A law that describes the relationships between measurable

    properties of an ideal gas

    pV = mRT

    where

    p = absolute pressure (N/m2)V = volume (m3)m = mass (kg)R = individual gas constant* (J/kg.oK)T = absolute temperature (oK)

    * The Individual Gas Constant depends on the particular gas and is related to the molecular weight of the gas. The value is independent of temperature.

  • Daltons Law of Partial Pressures: Total pressure is sum of the partial pressures of the components

    Ptotal = Pdry air + Pwater vapour

  • Psycrometric Chart

    ASHRAE

  • CIBSE

  • Structure

  • 80

    PSYCHROMETRIC CHART

  • Psychrometric Chart Applications

  • Obtaining conditions based on two known conditions, e.g. Given

    Temperatures of 15Cdb and 10Cwb

    Obtained from the chart The RH or percentage of

    saturation is 52% The moisture content is 5.4

    g/kg of air

  • Exercise

    Given: T = 27C, RH = 40%Find: h _________

    w _________ _________Twb _________Tdp _________

  • Psychrometric Process

    1. Sensible heating and cooling Heat addition or removal

    without moisture change

    HEATING

    COOLING

  • 2. Evaporative cooling Adiabatic process

    (constant h) Move along constant h

    or Twb line toward saturation

    Air loses sensible heat to gain latent heat from water added COOLING 1

    2

  • 3. Heating and humidification (of the air) Typical of ventilation air

    that circulates through a building space

    Air picks up both sensible and latent heat from entry to exit

    HEATING + HUMDIFICATION

    1

    2

  • 4. Adiabatic mixing Two separate conditions

    of air mixing together to form a third final condition without exchange of energy to the environment

    Addition of 1 and 2 in proportion to mass flow of each. Final condition will lie in straight line between the two on psychrometric chart.

    x

  • Using the enthalpy/humidity protractor Protractor in upper left hand side of psychrometric chart is

    useful in getting final conditions of complicated mixing problems

    Example: Define supply conditions necessary for air conditioning air into a space

    Outside: Enthalpy h

    = Humidity Ratio W

    S

    T

    QSensible Heat =

    Total Heat Q

  • PSYCHROMETRICS & SYSTEM DESIGN

  • Air Mixing Recirculating ductwork containing air at 21Cdb and

    15Cwb, mixing with fresh air at 36Cdb and 25Cwb before processing in an air-handling unit. If the ratio of mixed air is 3:1, i.e. 75% recirculated to 25% fresh. Find the state of mixed air:

    Tdb Twb RH Moisture content

  • Plant Sizing

    An air-conditioning is used to supply air at 27Cdb and 20Cwb to 20Cdb and 14Cwb, in a factory of 1500 m3volume requiring 5 air changes per hour.

    Find: Chiller rating Reheater rating

  • Q = Volume x air changes

    3600= 1500 x 5 = 2.1 m3/s

    3600

    Convert m3/s to kg/s by establishing specific volume plant commencing conditions:

    At 27Cdb and 20Cwb = 0.87 m3/kg (chiller)At 10Cdb and 10Cwb = 0.81 m3/kg (reheater)

  • Therefore

    2.1 m3/s = 2.4 kg/s (chiller)0.87 m3/kg

    and2.1 m3/s = 2.6 kg/s (reheater)

    0.81 m3/kg

    Enthalpy values for chilling and reheating:

    Chilling 57 45 kJ/kg = 12 kJ/kg

    Reheating 39 29.5 kJ/kg = 9.5 kJ/kg

  • The chiller rating is

    2.4 kg/s x 12 kJ/kg = 28.8 kW

    The reheater rating is

    2.6 kg/s x 9.5 kJ/kg = 24.7 kW

  • REFERENCES

  • Greeno, R.(1997). Building Services, Technology and Design. Essex: Longman.

    Hall, F. & Greeno, R. (2005). Building Services Handbook. Oxford: Elsevier.

    Trane Air-Conditioning Company. Mohamed Rashid Embi & Sulaiman Shariff (1996).

    Pengudaraan dan Sistem Penyamanan Udara. Kuala Lumpur: Dewan Bahasa dan Pustaka.

  • Quiz

    What is cooling load?

    List down the components of heat gains.