En-1 English Multi Air Conditioning System for Buildings (VRF System) INSTALLATION MANUAL (PART NO. 9369021053-03) This air conditioner uses new refrigerant HFC (R407C). For authorized service personnel only. WARNING This mark indicates procedures which, if improperly performed, might lead to the death or serious injury of the user. CAUTION This mark indicates procedures which, if improperly performed, might possibly result in personal harm to the user, or damage to property. WARNING 1 For the air conditioner to operate satisfactorily, install it as outlined in this installation manual. 2 Connect the indoor unit and outdoor unit with the air conditioner piping and cords available from our standard parts. This installation manual describes the correct connections using the installation set avail- able from our standard parts. 3 Installation work must be performed in accordance with national wiring standards by authorized personnel only. 4 If refrigerant leaks while work is being carried out, ventilate the area. If the refrigerant comes in contact with a flame, it produces a toxic gas. 5 Do not turn on the power until all installation work is complete. 6 During installation, make sure that the refrigerant pipe is attached firmly before you run the compressor. Do not operate the compressor under the condition of refrigerant piping not attached properly with 2-way or 3-way valve open. This may cause abnormal pressure in the refrigeration cycle that leads to breakage and even injury. 7 During the pump-down operation, make sure that the compressor is turned off before you remove the refrigerant piping. Do not remove the connection pipe while the compressor is in operation with 2-way or 3-way valve open. This may cause abnormal pressure in the refrigeration cycle that leads to breakage and even injury. 8 When installing and relocating the air conditioner, do not mix gases other than the specified refrigerant to enter the refrigerant cycle. If air or other gas enters the refrigerant cycle, the pressure inside the cycle will rise to an abnormally high value and cause breakage, injury, etc. Be careful not to scratch the air conditioner when handling it. After installation, explain correct operation to the customer, using the operating manual. Let the customer keep this installation manual because it is used when the air conditioner is serviced or moved. The maximum length of the piping is shown in page 9. If the units are further apart than this, correct opera- tion cannot be guaranteed. Refrigerant R407C

Refrigerant Multi Air Conditioning System R407C for ......Multi Air Conditioning System for Buildings (VRF System) INSTALLATION MANUAL (PART NO. 9369021053-03) This air conditioner

  • Upload
    others

  • View
    14

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Refrigerant Multi Air Conditioning System R407C for ......Multi Air Conditioning System for Buildings (VRF System) INSTALLATION MANUAL (PART NO. 9369021053-03) This air conditioner

En-1

En

gli

sh

Multi Air Conditioning System

for Buildings (VRF System)

INSTALLATION MANUAL(PART NO. 9369021053-03)

This air conditioner uses new refrigerant HFC (R407C).For authorized service personnel only.

WARNING This mark indicates procedures which, if improperly performed, might lead to the death or serious injury ofthe user.

CAUTION This mark indicates procedures which, if improperly performed, might possibly result in personal harm to theuser, or damage to property.

WARNING

1 For the air conditioner to operate satisfactorily, install it as outlined in this installation manual.

2 Connect the indoor unit and outdoor unit with the air conditioner piping and cords available from ourstandard parts. This installation manual describes the correct connections using the installation set avail-able from our standard parts.

3 Installation work must be performed in accordance with national wiring standards by authorized personnelonly.

4 If refrigerant leaks while work is being carried out, ventilate the area. If the refrigerant comes in contactwith a flame, it produces a toxic gas.

5 Do not turn on the power until all installation work is complete.

6 During installation, make sure that the refrigerant pipe is attached firmly before you run the compressor.Do not operate the compressor under the condition of refrigerant piping not attached properly with 2-wayor 3-way valve open. This may cause abnormal pressure in the refrigeration cycle that leads to breakageand even injury.

7 During the pump-down operation, make sure that the compressor is turned off before you remove therefrigerant piping. Do not remove the connection pipe while the compressor is in operation with 2-way or3-way valve open. This may cause abnormal pressure in the refrigeration cycle that leads to breakageand even injury.

8 When installing and relocating the air conditioner, do not mix gases other than the specified refrigerantto enter the refrigerant cycle. If air or other gas enters the refrigerant cycle, the pressure inside the cyclewill rise to an abnormally high value and cause breakage, injury, etc.

• Be careful not to scratch the air conditioner when handling it.• After installation, explain correct operation to the customer, using the operating manual.• Let the customer keep this installation manual because it is used when the air conditioner is serviced or

moved.• The maximum length of the piping is shown in page 9. If the units are further apart than this, correct opera-

tion cannot be guaranteed.

Refrigerant

R407C

9369021053-03_IM_en.p65 1/26/11, 10:25 AM1

Page 2: Refrigerant Multi Air Conditioning System R407C for ......Multi Air Conditioning System for Buildings (VRF System) INSTALLATION MANUAL (PART NO. 9369021053-03) This air conditioner

En-2

STANDARD PARTS

The following installation parts are supplied. Use them as required.

Description

Flange jointassembly

Coupler heatinsulation

Gasket

Q’ty

1

2

1

Application

For connecting the piping

For outdoor side pipejoint

Installation betweenflange joint assembly andlarge valve

Description

Bolt

Drain pipe

Auxiliary pipe assembly

TERMINAL RESISTOR

Q’ty

2

3

1

1

Application

For fixing the flange jointassembly

For outdoor unit drainpiping work (Reversecycle model only)

For connecting the piping

For installation to theoutdoor unit circuit board

Product mass

305 kg

Protective boards

CONVEYANCE METHOD AND PRODUCT MASS

Fig. 1

Rope suspension area

• If you are suspending the unit and conveying it to its installationlocation, place the ropes under the bottom, using the two placeson the front and rear provided for suspending it.

• Be sure to suspend the unit with ropes from 4 places and becareful not to subject it to impacts.

• Place protective boards on the unit so the rope doesn’t makecontact with the bell mouth.

• Use 2 ropes which are 7 m in length or longer.

9369021053-03_IM_en.p65 11/15/10, 1:06 PM2

Page 3: Refrigerant Multi Air Conditioning System R407C for ......Multi Air Conditioning System for Buildings (VRF System) INSTALLATION MANUAL (PART NO. 9369021053-03) This air conditioner

En-3

SELECTING THE MOUNTING POSITION

Decide the mounting position together with the customer as follows:

WARNING

1 Install the unit where it will not be tilted by more than 5°.

2 When installing the outdoor unit it may be exposed to strong wind, fasten it securely.

(1) If possible, do not install the unit where it will be exposed todirect sunlight. (If necessary, install a blind that does not inter-fere with the air flow.)

(2) Install the outdoor unit in a place where it will be free frombeing dirty or getting wet by rain as much as possible.

(3) Install the unit where connection to the indoor unit is easy.

(4) During heating operation, drain water flows from the outdoorunit. Therefore, install the outdoor unit in a place where drainwater flow will not be obstructed. (Reverse cycle model only)

(5) Do not place animals and plants in the path of the warm air.

(6) Take the air conditioner weight into account and select a placewhere noise and vibration are small.

(7) Select place so that the warm air and noise from the air condi-tioner do not disturb neighbors.

(8) Install inlet and outlet ducts in order to maintain stable opera-tion in cold or snowy regions.

(9) Provide the space shown in Fig. 2 so that the air flow is notblocked.

• Installing the unit individually

Fig. 2

10 mm or more

10 mm or more

Front side

500 mmor more

300 mmor more

• Installing continuous units

Fig. 3

Side

Front side

10 mmor more

10 mmor more

300 mmor more

10 mmor more

500 mmor more

10 mmor more

Side

9369021053-03_IM_en.p65 11/15/10, 1:06 PM3

Page 4: Refrigerant Multi Air Conditioning System R407C for ......Multi Air Conditioning System for Buildings (VRF System) INSTALLATION MANUAL (PART NO. 9369021053-03) This air conditioner

En-4

H (

1,20

0 m

m o

r le

ss)

L1 Top bloweroutlet

L2

h h

H (

1,20

0 m

m o

r le

ss)

Frontair

intake

Rearairin-

take

• There is no limit to the height of the side wall.• The height of the wall (H) on the front side and rear side should

be 1,200 mm or less (Fig. 4).• If the wall height exceeds 1,200 mm, add dimension (h) to the

respective service space dimensions L1 and L2 (Fig. 4).H 1,200 : L1 500, L2 300H > 1,200 : L1 > 500+h, L2 > 300+h

• The dimensions shown above are minimum required limit toprevent a decline in performance. The space provided shouldbe increased in consideration of passageways and room formaintenance.

Fig. 4

CONNECTION PIPE REQUIREMENT

(1) Connected to outdoor unit

* Capacity: The number displayed on the model name for the indoor and outdoor units.

• Use pipe with water-resistant heat insulation.• Use pipe that can withstand a pressure of 3,040 kPa.• The discharge gas pipe is only connected on heat recovery models.

(3) Connected to indoor unit

Table 1unit : mm

Capacity of Suction Dischargeoutdoor unit Gas Pipe Gas Pipe

Liquid Pipe

90 ø28.58 (1.2) ø19.05 (1.0) ø12.7 (0.8)

( ) : thickness

(2) Connected between two immediately adjacent refrigerant branch kits

Table 2unit : mm

Total capacity Suction Dischargeof indoor unit Gas Pipe Gas Pipe

Liquid Pipe

Less than 30 ø15.88 (1.0) ø12.7 (0.8) ø9.53 (0.8)

31 or more to 60 ø19.05 (1.0) ø15.88 (1.0) ø9.53 (0.8)

61 or more ø28.58 (1.2) ø19.05 (1.0) ø12.7 (0.8)

( ) : thickness

Table 3unit : mm

Capacity ofindoor unit

Gas Pipe Liquid Pipe

7, 9 ø9.53 (0.8) ø6.35 (0.8)

12, 14 ø12.7 (0.8) ø6.35 (0.8)

18, 20, 24, 25 ø15.88 (1.0) ø6.35 (0.8)

30 ø15.88 (1.0) ø9.53 (0.8)

36, 45, 54, 60 ø19.05 (1.0) ø9.53 (0.8)

( ) : thickness

9369021053-03_IM_en.p65 11/15/10, 1:06 PM4

Page 5: Refrigerant Multi Air Conditioning System R407C for ......Multi Air Conditioning System for Buildings (VRF System) INSTALLATION MANUAL (PART NO. 9369021053-03) This air conditioner

En-5

ELECTRICAL REQUIREMENTTable 4

Power supply Maximum 8.0

cord (mm2) Minimum 6.0

Transmission Maximum 1.25

cord (mm2) Minimum 0.75

Remote control Maximum 1.25

cord (mm2) Minimum 0.75

Outdoor unit fuse capacity (A) 40

Shield cord(LONWORKS

compatible part)

Type245 IEC57or equivalent

Sheathed vinylcord cable

INSTALLATION PROCEDURE

Install the air conditioner as follows.

1. OUTDOOR UNIT INSTALLATION

1. OUTDOOR UNIT PROCESSING

When the outdoor unit will be exposed to strong wind, fasten itwith anchor bolts at the four places indicated by the arrows(Fig. 5).

(1) Anchor Bolt Positions

• The distance between the left and right anchor bolts should beat least 850 mm.

• Set the unit on a strong stand, such as concrete blocks to mini-mize shock and vibration.

• Do not set the unit directly on the ground because it will causeproblems.

Fig. 5

Drain pipe

Rear panel

Knockout hole

Drain pipe mounting holes Rear panel

Hose

Drain pan

(2) Drain Processing

• Remove the rear panel.• Since the drain water flows out of the outdoor unit during heat-

ing operation, install the drain pipe and connect it to an com-mercial 16 mm hose. (When heating the outdoor temperatureis 0 °C or less, construct so that drain water from the outdoorunit will not freeze in the drain pipe.)

• Always use a drain pipe at three places.

Fig. 6

• Install the disconnection device with a contact gap of at least 3mm nearby the units. (Both indoor unit and outdoor unit)

NOTE: Install in accordance with local rules and regulations.

1,300 mm

1,000 mm850 mm

703

mm

650

mm

678

mm

9369021053-03_IM_en.p65 11/15/10, 1:06 PM5

Page 6: Refrigerant Multi Air Conditioning System R407C for ......Multi Air Conditioning System for Buildings (VRF System) INSTALLATION MANUAL (PART NO. 9369021053-03) This air conditioner

En-6

2. OUTDOOR UNIT CONNECTION CORD AND PIPE CONNECTION PREPARATIONS

(1) Piping and connection cord mounting direction (4-way mounting possible).• If a mounting bracket is installed at the knockout hole section in the base, do not connect the piping from the bottom.• If the piping is connected from the rear, be sure that there is enough space around the unit to make connections.

Fig. 7 Fig. 8

(2) Remove the front panel right.

Fig. 9

Bottom piping

Rear piping

Front piping Right piping

75

Unit: mm

Knockout hole210 30 36

Outdoor unit

CAUTION

Drain water will leak from the bottom of the outdoor unit during cooling/heating operation, even if the drainpipe is connected. To prevent the area surrounding the outdoor unit from getting wet, install a gutter surround-ing the outdoor unit as shown in the figure below for drain water.

1/1001/100Gutter

50 mmor more

10 mm or more

Gutter

Front panel right

9369021053-03_IM_en.p65 11/15/10, 1:06 PM6

Page 7: Refrigerant Multi Air Conditioning System R407C for ......Multi Air Conditioning System for Buildings (VRF System) INSTALLATION MANUAL (PART NO. 9369021053-03) This air conditioner

En-7

(3) Before connecting flange joint assembly to ball valve.Remove bolts, valve plate and gasket.

Fig. 10

(4) Open the piping and connection cord knockout holes of the desired direction with nippers, etc.After opening a hole in the center of bush, pierce with connection cord. (Rear, Right and Left wiring)

Fig. 11

(5) Connect the piping and connection cord from the mounting holes.

Fig. 12

(Example)

Valve plate

Ball valve

Gasket

Bolt

Washer

Transmission cord(Indoor unit and outdoorunit connection cord)

Bush

Power supply cord

Coupler heat insulation Small pipe Middle pipe (Heat recovery model only)

Large pipe

9369021053-03_IM_en.p65 11/15/10, 1:06 PM7

Page 8: Refrigerant Multi Air Conditioning System R407C for ......Multi Air Conditioning System for Buildings (VRF System) INSTALLATION MANUAL (PART NO. 9369021053-03) This air conditioner

En-8

2. CONNECTING THE PIPING

CAUTION

1 Do not use mineral oil on flared part.Prevent mineral oil from getting into the system as this would reduce the lifetime of the units.

2 Never use piping which has been used for previous installations. Only use parts which are delivered withthe unit.

3 While welding the pipes, be sure to blow nitrogen gas through them.

• If nitrogen gas is not blown through the pipes while they are being welded, an oxidized layer may form onthe inside of the pipes. If this occurs, the cooling efficiency may decrease and the air conditioner unit(compressor, valves, etc.) may malfunction.

1. FLARE PROCESSING

(1) Cut the connection pipe with pipe cutters so that the pipe isnot deformed.

(2) Holding the pipe downwards so that cuttings cannot enter thepipe and remove the burrs.

(3) Remove the flare nut from the indoor unit pipe and outdoorunit and assemble as shown in (Table 5) and insert the flarenut onto the pipe, and flare with a flaring tool.

(4) Check if the flared part “L” (Fig. 13) is spread uniformly andthat there are no cracks.

Table 5

Fig. 13

Pipe

Small pipe(ø12.7 mm)

Middle pipe(ø19.05 mm)

Flare nut

width across flats24 mm

with across flats36 mm

L dimension

1.9 to 2.2 mm

2.6 to 3.0 mm

Width across flats

2. BENDING PIPES

The pipes are shaped by your hands. Be careful not to collapsethem.Do not bend the pipes in an angle more than 90°.When pipes are repeatedly bent or stretched, the material willharden, making it difficult to bend or stretch them any more. Donot bend or stretch the pipes more than three times.

Fig. 14

When bending the pipe, there is a possibility to collapse. In thiscase, cut the heat insulating pipe with a sharp cutter as shown inFig. 15, and bend it after exposing the pipe. After bending thepipe as you want, be sure to put the heat insulating pipe back onthe pipe, and secure it with tape.

Fig. 15

Pipe

Heat insulatingpipe

Cutter

Cut line

CAUTION

1 To prevent breaking of the pipe, avoid sharp bends.Bend the pipe with a radius of curvature of 150 mm or over.

2 If the pipe is bent repeatedly at the same place, it will break.

9369021053-03_IM_en.p65 11/15/10, 1:06 PM8

Page 9: Refrigerant Multi Air Conditioning System R407C for ......Multi Air Conditioning System for Buildings (VRF System) INSTALLATION MANUAL (PART NO. 9369021053-03) This air conditioner

En-9

3. PERMISSIBLE LENGTH OF CONNECTION PIPING

• The RB unit is only used on heat recovery models.• Keep the length of straight portion of pipe between two branch kits longer than roughly 0.5 m.• Don’t use separation tube in the downstream of header.• Install separation tube and header in the correct direction specified in installation manual.

Fig. 16 EXAMPLE 1(Branch kit: Header)

b

a

Outdoorunit

H1

RBunit

Indoorunit

d

RBunit

Indoorunit

e

RBunit

Indoorunit

c

RBunit

Indoorunit H2 H4, f

H3

Fig. 17 EXAMPLE 2(Branch kit: Separation tube)

Fig. 18 EXAMPLE 3(Branch kit: Separation tube + Header)

Maximum permissible length (actual pipe length)

Between outdoor unit and farthest indoor unit

Total pipe length

Between outdoor unit and 1st branch kit

Between 1st branch kit and farthest indoor unit

Between RB unit and indoor unit (heat recovery models only)

100 m

200 m

70 m

40 m

10 m

EXAMPLE 1

a+b

a+c

a+d

a+e

a+b+c+d+e

b

c

d

e

f

EXAMPLE 2

a+g

a+b+h

a+b+c+i

a+b+c+d+j

a+b+c+d+e+k

a+b+c+d+e+f

a+b+c+d+e+f

+g+h+i+j+k

a

g

b+h

b+c+i

b+c+d+j

b+c+d+e+k

b+c+d+e+f

R

EXAMPLE 3

a+g+h

a+g+i

a+b+c

a+b+d

a+b+e

a+b+f

a+b+c+d+e

+f+g+h+i

g+h

g+i

b+c

b+d

b+e

b+f

c, d, e, f

Outdoorunit

RBunit

Indoorunit

RBunit

Indoorunit

H2

H3

H4,R

f

e

RBunit

Indoorunit

d

RBunit

Indoorunit

c

RBunit

Indoorunit

b

H1

RBunit

Indoorunit

a

kjihg

Table 6

EXAMPLE 1 EXAMPLE 2

H1

H2

H3

H4

EXAMPLE 3Maximum permissible height difference

Between outdoor Outdoor unit installed higher than indoor unitunit and indoor unit Outdoor unit installed lower than indoor unit

Between indoor units

Between RB units (heat recovery models only)

Between RB unit and indoor unit (heat recovery models only)

50 m

40 m

15 m

15 m

5 m

Outdoorunit

b

RBunit

Indoorunit

RBunit

Indoorunit

i

a

H1

h

gc

Indoorunit

Indoorunit

RB unit4 branch

e f

Indoorunit

d

IndoorunitH2

H3 H4

9369021053-03_IM_en.p65 11/15/10, 1:06 PM9

Page 10: Refrigerant Multi Air Conditioning System R407C for ......Multi Air Conditioning System for Buildings (VRF System) INSTALLATION MANUAL (PART NO. 9369021053-03) This air conditioner

En-10

5. CONNECTION PIPES

(1) Tighten the flare nut of the connection pipe at the outdoor unitvalve connector.

(2) Seal with the accessory putty so that water does not enter atthe top of the pipe insulation installed to the connection pipe.

(3) After connecting the pipes, an air tightness test must be per-formed. To perform the test, close the valve and increase thepressure of the nitrogen gas to 30 kg/cm2 G.

CAUTION

Be sure to apply the pipe against the port on the indoor unit correctly. If the centering is improper, the flare nutcannot be tightened smoothly. If the flare nut is forced to turn, the threads will be damaged.

When the flare nut is tightened properly by your hand, hold thebody side coupling with a separate spanner, then tighten with atorque wrench (Fig. 20).

Holding spanner

Body side

Torque wrench

Fig. 20

4. SELECTING A BRANCH KIT

A. Header selection

Table 7

B. Separation tube selection

Table 8

C. RB unit selection (Heat recovery models only)

Table 9

Number of branches(Number of indoor units connected)

1 unit

1 to 4 units

Model name of RB unit to be used

UTF-Y54A1A

UTF-Y90A4A

Fig. 19

Flare nutFlare nut

Connection pipe

Connection pipe (Heat recoverymodel only)

Flange joint assembly

Washer

Bolt (Accessory)

Gasket (Accessory)

Number of branches(Number of indoor units connected)

6 units or less

7 to 8 units

UTR-HD906R

UTR-HD908R

Model name of header to be used

Total capacity of indoor units

Less than 60

61 or more

Model name of separation tube to be used

UTR-BP54MA

UTR-BP90MA

9369021053-03_IM_en.p65 11/15/10, 1:06 PM10

Page 11: Refrigerant Multi Air Conditioning System R407C for ......Multi Air Conditioning System for Buildings (VRF System) INSTALLATION MANUAL (PART NO. 9369021053-03) This air conditioner

En-11

Installation angle• Separation tubeInstall the separation tube so that it branches either horizontally or vertically.

Fig. 22 Fig. 23

• HeaderInstall the header so that it branches horizontally.When connecting the connection pipes from the indoor units, connect them to the header branch pipes in the order 1, 2, 3, etc. (Fig. 24)

Fig. 24

Horizontal

Horizontal line±30°

Vertical

CAUTION

Hold the torque wrench at its grip, keeping it in the right angle with the pipe as shown in Fig. 21, in order totighten the flare nut correctly.

Table 10: Flare nut tightening torque

Pipe Tightening torque

Small pipe (ø12.7 mm) 500 to 550 kgf · cm (49 to 53.9 N · m)

Middle pipe (ø19.05 mm) 800 to 1,000 kgf · cm (78.4 to 98 N · m)

Large pipe (Bolt) (ø28.58 mm) 350 to 400 kgf · cm (34.3 to 39.2 N · m)

• Connecting the flange joint pipe.

Fig. 21

Torque wrench

Flangejoint pipe

Gas pipe Liquid pipe

Outdoorunit side Outdoor

unit side

or

12

34

...

12

34

...

CAUTION

Use a level to make sure that the header is positioned as shown in the following figure, and then secure it in place.Fig. 25

A

H1α1

β1

B

H2α2

β2

Brazingpoint

HorizontalLine

VIEW A

Outdoorunit side

H1 = 0 mm – 10 mm(α1 : 0° – 1°)β1: -10° – 10°

Gas pipe Liquid pipe

Brazingpoint

HorizontalLine

VIEW B

Outdoorunit side

H2 = 0 mm – 10 mm(α2 : 0° – 1°)β2: -10° – 10°

VerticalLine

HorizontalLine

9369021053-03_IM_en.p65 11/15/10, 1:06 PM11

Page 12: Refrigerant Multi Air Conditioning System R407C for ......Multi Air Conditioning System for Buildings (VRF System) INSTALLATION MANUAL (PART NO. 9369021053-03) This air conditioner

En-12

Fig. 26

4. VACUUM PROCESS

CAUTION

1 Do not purge the air with refrigerants but use a vacuum pump to vacuum the installation! There is no extrarefrigerant in the outdoor unit for air purging!

2 Use a vacuum pump for R407C exclusively. Using the same vacuum pump for different refrigerant maydamage the vacuum pump or the unit.

3. SEALING TEST

After the piping has been installed, perform a sealing test. Charge the piping with nitrogen to within the sealing test pressure(2.94 MPa). After 24 hours, check that the pressure has not fallen.

1. VACUUM

(1) Remove the cap, and connect the gauge manifold and thevacuum pump to the charging valve by the service hoses.

(2) Vacuum the indoor unit and the connecting pipes until the pres-sure gauge indicates -76 cmHg.

(3) When -76 cmHg is reached, operate the vacuum pump for atleast 1 hour.

(4) After vacuuming inside the indoor unit and connecting pipes,remove the cap of the three valves. See Fig. 26.(Remove the large and small valves on the cooling and heatpump models.)

(5) Open the handle (spindle) of the Large and Middle valves.Open the spindle of the Small valve with a hexagon wrench.See Table 12.(Open the Large and Small valves on the cooling and heatpump models.)

(6) Tighten the cap of the three valves to the specified torque.See Table 11.(Tighten the Large and Small valves on the cooling and heatpump models.)

Table 11

Tightening torque

Large valve and Middle valve Small valve

Spindle15 kgf·cm (1.47 N·m) or less

100 to 120 kgf·cm(handle) (9.8 to 11.7 N·m)

Cap150 to 200 kgf·cm 200 to 250 kgf·cm (14.7 to 19.6 N·m) (19.6 to 24.5 N·m)

Table 12

Middle valve

Open valve state Closed valve state

Large valve

Open valve state Closed valve state

∗ If the spindle (handle) is not fully open, perfor-mance will drop and an abnormal sound will begenerated.

Open

Close

Hexagon wrench

SpindleSmall valve

Small pipeMiddle pipe(Heat recovery model only)

Large pipeCharging valve

Cap

9369021053-03_IM_en.p65 11/15/10, 1:06 PM12

Page 13: Refrigerant Multi Air Conditioning System R407C for ......Multi Air Conditioning System for Buildings (VRF System) INSTALLATION MANUAL (PART NO. 9369021053-03) This air conditioner

En-13

2. ADDITIONAL CHARGE

Fig. 27

Vacuum pump.

Pressure gauge Pressure reduction valve

Refrigerantcontainer

R407C

ScaleNitrogen

Connected on heat recovery models only.∗ When conducting the vacuuming process from two pipes, use the Middle pipe and Small pipe.

B = + +

Total length of

ø12.70 mm

liquid pipe

mkg

× 0.136kg/m

Total length of

ø9.52 mm

liquid pipe

mkg

× 0.063kg/m

Total length of

ø6.35 mm

liquid pipe

mkg

× 0.025kg/m

ADDITIONAL CHARGE CALCULATION FORMULA• Additional refrigerant charge amount is calculated according to calculated value from its pipe length of liquid pipe and additional

amount for outdoor unit.• Round up the calculated result to two decimal places.

Calculation of additional refrigerant charge amount

1. Additional amount for outdoor unitA = 1.20 (kg)

2. Calculation of additional amount for pipe length

3. Calculation of additional refrigerant charge amount

C = A + B

Example: When the liquid pipe length are 20 m (ø12.70 mm), 15 m (ø9.52 mm), and 20 m (ø6.35 mm), respectively.1. Additional amount for outdoor unit:

A = 1.20 kg2. Calculation of additional amount for pipe length:

B = 20 (m) × 0.136 (kg/m) + 15 (m) × 0.063 (kg/m) + 20 (m) × 0.025 (kg/m)= 4.17 (kg)

3. Calculation of additional refrigerant charge amount:C = 1.20 kg + 4.17 kg

= 5.37 kg

AO 90MPCMF 11.80 1.20

ModelFactory charged

amount (kg)

AAdditionalamount for

outdoor unit (kg)

6.35 0.0259.52 0.06312.70 0.136

Diameter ofliquid pipe (mm)

BAdditional

amount for pipelength (kg/m)

9369021053-03_IM_en.p65 11/15/10, 1:06 PM13

Page 14: Refrigerant Multi Air Conditioning System R407C for ......Multi Air Conditioning System for Buildings (VRF System) INSTALLATION MANUAL (PART NO. 9369021053-03) This air conditioner

En-14

HOW TO CONNECT WIRING TO THE TERMINALS

A. For solid core wiring (or F-cable)

(1) Cut the wire end with a wire cutter or wire-cutting pliers, thenstrip the insulation to about 15/16" (25 mm) to expose the solidwire.

(2) Using a screwdriver, remove the terminal screw(s) on the ter-minal board.

(3) Using pliers, bend the solid wire to form a loop suitable for theterminal screw.

(4) Shape the loop wire properly, place it on the terminal boardand tighten securely with the terminal screw using a screw-driver.

5. ELECTRICAL WIRING

WARNING

1 Before starting work, check that power is not being supplied to the outdoor unit.

2 Match the terminal board numbers and connection cord colors with those of the outdoor unit.Erroneous wiring may cause burning of the electric parts.

3 Connect the connection cord firmly to the terminal board. Imperfect installation may cause a fire.

4 Always fasten the outside covering of the connection cord with the cord clamp. (If the insulator is chafed,electric leakage may occur.)

5 Always connect the ground wire.

Fig. 28

A. Solid wire

Str

ip 1

5/16

"(2

5 m

m)

Insulation

Loop

B. Strand wire

CAUTION

1 When charging the refrigerant R407C, always use an electronic balance for refrigerant charging (to meas-ure the refrigerant by weight).

2 When charging the refrigerant, take into account the slight change in the composition ofthe gas and liquid phases, and always charge from the liquid phase side whose composi-tion is stable.

3 Add refrigerant from the charging valve after the completion of the work.

4 The maximum length of the piping is 100 m (actual pipe length). If the units are further apart than this,correct operation can not be guaranteed.

B. For strand wiring

(1) Cut the wire end with a wire cutter or wire-cutting pliers, then strip the insulation to about 3/8" (10 mm) to expose the strand wiring.(2) Using a screwdriver, remove the terminal screw(s) on the terminal board.(3) Using a round terminal fastener or pliers, securely clamp a round terminal to each stripped wire end.(4) Position the round terminal wire, and replace and tighten the terminal screw using a screwdriver.

Wire

Screw withspecial washer

Roundterminal

Terminalboard

Terminal block

Screw withspecial washer

Wire

RoundterminalS

trip

3/8

"(1

0 m

m)

Round terminal

Gas

Liquid

R407C

9369021053-03_IM_en.p65 11/15/10, 1:06 PM14

Page 15: Refrigerant Multi Air Conditioning System R407C for ......Multi Air Conditioning System for Buildings (VRF System) INSTALLATION MANUAL (PART NO. 9369021053-03) This air conditioner

En-15

(1) Remove the front panel right.

Fig. 30

(2) Remove control box metal cover and connect the power supply cord and transmission cord.

Fig. 31 Fig. 32

Terminal board

Cable crip

Power supply cord Transmission cord

Insulation tube

Cord clamp

Control box metal

Front panel right

Control box metal cover

HOW TO FIX THE CONNECTION CORD AND POWER SUPPLY CORD AT THE CORD CLAMP

After passing the transmission cord and power supply cord through the insulation tube, fasten it with the cord clamp.

Use VW-1, 0.5 to 1.0 mm thick, PVC tube as the insulation tube.

Fig. 29

9369021053-03_IM_en.p65 11/15/10, 1:06 PM15

Page 16: Refrigerant Multi Air Conditioning System R407C for ......Multi Air Conditioning System for Buildings (VRF System) INSTALLATION MANUAL (PART NO. 9369021053-03) This air conditioner

En-16

R S TPOWER

N 2TRANSMISSION

1

12

RE

MO

TE

CO

NT

RO

L31

21

2TR

ANS

MIS

SIO

NPO

WER

SUPP

LY

12

RE

MO

TE

CO

NT

RO

L31

21

2TR

ANS

MIS

SIO

NPO

WER

SUPP

LY

Fig. 33

(Example)

Outdoor unit wiring

RB unit cord Power supply cord

Transmissioncord

Remote control cord

Remote control unit

Indoor unit wiring

Power supplycord

Refrigerant branch unit(Heat recovery model only)

CAUTION

1 Use care to wire properly. (Miswiring will result in damage.)

2 Never bundle the power supply cord, transmission cord and remote controller cord together. Bundlingthese cords together will cause misoperation.

3 The total length of the transmission cord should not exceed 500 meters. Note that the total length of thetransmission cord can be extended to 2,000 meters if the optional signal amplifier is used.

4 The power source capacity must be the sum of the air conditioner current and the current of other electricalappliances. When the current contracted capacity is insufficient, change the contracted capacity.

5 When the voltage is low and the air conditioner is difficult to start, contact the power company the voltageraised.

380-415 V 3ø 50 Hz220-240 V 1ø 50 Hz

Transmissioncord

9369021053-03_IM_en.p65 11/15/10, 1:06 PM16

Page 17: Refrigerant Multi Air Conditioning System R407C for ......Multi Air Conditioning System for Buildings (VRF System) INSTALLATION MANUAL (PART NO. 9369021053-03) This air conditioner

En-17

(3) Install the control box metal cover and front panel right. Fig. 34

WARNING

1 [1 phase TYPE]The rated voltage of this product is 220-240 V A.C. 50 Hz.Before turning on verify that the voltage is within the 198 V to 264 V range.

[3 phase TYPE]The rated voltage of this product is 380-415 V 3ø 50 Hz.Before turning on verify that the voltage is within the 342 V to 457 V range.

2 Always use a special branch circuit and install a special receptacle to supply power to the air conditioner.

3 Use a circuit breaker and receptacle matched to the capacity of the air conditioner.

4 Perform wiring work in accordance with standards so that the air conditioner can be operated safely andpositively.

5 Install a leakage circuit breaker in accordance with the related laws and regulations and electric companystandards.

Control box metal cover

9369021053-03_IM_en.p65 11/15/10, 1:06 PM17

Page 18: Refrigerant Multi Air Conditioning System R407C for ......Multi Air Conditioning System for Buildings (VRF System) INSTALLATION MANUAL (PART NO. 9369021053-03) This air conditioner

En-18

6. CIRCUIT BOARD SETTING

1. OUTDOOR UNIT SETTINGS

(1) Refrigerant circuit addressRotary switch (SW8) - - - Factory setting “0”Rotary switch (SW9) - - - Factory setting “0”In the case of multiple refrigerant systems, set SW8 and SW9 as shown in the Table 14 for each refrigerant system.Do not use a nonexistent switch setting conbination.Example: When SW9 is set to “1” and SW8 is set to “14”, the refrigerant circuit address will be “30”.

(2) Model settingsSet the DIP switch to the corresponding system type as shownin the Table 15.

Table 15

Heat pump Cooling Heat recovery

SW7-1 OFF ON OFF

SW7-2 OFF OFF ON

Table 14

Refrigerant Rotary Refrigerant Rotary Refrigerant Rotary Refrigerant Rotary Refrigerant Rotary

circuit Switch Setting circuit Switch Setting circuit Switch Setting circuit Switch Setting circuit Switch Setting

address OUTDOOR UNIT address OUTDOOR UNIT address OUTDOOR UNIT address OUTDOOR UNIT address OUTDOOR UNIT

SW9 SW8 SW9 SW8 SW9 SW8 SW9 SW8 SW9 SW8

0 0 0 20 1 4 40 2 8 60 3 12 80 5 0

1 0 1 21 1 5 41 2 9 61 3 13 81 5 1

2 0 2 22 1 6 42 2 10 62 3 14 82 5 2

3 0 3 23 1 7 43 2 11 63 3 15 83 5 3

4 0 4 24 1 8 44 2 12 64 4 0 84 5 4

5 0 5 25 1 9 45 2 13 65 4 1 85 5 5

6 0 6 26 1 10 46 2 14 66 4 2 86 5 6

7 0 7 27 1 11 47 2 15 67 4 3 87 5 7

8 0 8 28 1 12 48 3 0 68 4 4 88 5 8

9 0 9 29 1 13 49 3 1 69 4 5 89 5 9

10 0 10 30 1 14 50 3 2 70 4 6 90 5 10

11 0 11 31 1 15 51 3 3 71 4 7 91 5 11

12 0 12 32 2 0 52 3 4 72 4 8 92 5 12

13 0 13 33 2 1 53 3 5 73 4 9 93 5 13

14 0 14 34 2 2 54 3 6 74 4 10 94 5 14

15 0 15 35 2 3 55 3 7 75 4 11 95 5 15

16 1 0 36 2 4 56 3 8 76 4 12 96 6 0

17 1 1 37 2 5 57 3 9 77 4 13 97 6 1

18 1 2 38 2 6 58 3 10 78 4 14 98 6 2

19 1 3 39 2 7 59 3 11 79 4 15 99 6 3

9369021053-03_IM_en.p65 11/15/10, 1:06 PM18

Page 19: Refrigerant Multi Air Conditioning System R407C for ......Multi Air Conditioning System for Buildings (VRF System) INSTALLATION MANUAL (PART NO. 9369021053-03) This air conditioner

En-19

(3) Terminal resistor installationWhen connecting multiple outdoor units together with transmission cords, install the terminal resistor to terminal CN22 of oneoutdoor unit only.* When installing the signal amplifier (UTR-YRP❋), refer to the installation instruction sheet for the signal amplifier.

Fig. 35

CAUTION

Install the terminal resistor as specified.

If the terminal resistor is not installed as specified, the following malfunctions may occur.

1) When multiple terminal resistors are installed

The entire communication system may be damaged.

2) When no terminal resistor is installed

Communication errors may occur.

CN

22C

N2

ACIN

E1

SW1SW2SW8SW9 SW7 SW3

CN22

OUTDOOR BOARD

OUTDOOR UNIT

TERMINALRESISTOR

INDOOR UNIT

TERMINALRESISTOR

NO TERMINAL RESISTOR

TRANSMISSION CORD

9369021053-03_IM_en.p65 11/15/10, 1:06 PM19

Page 20: Refrigerant Multi Air Conditioning System R407C for ......Multi Air Conditioning System for Buildings (VRF System) INSTALLATION MANUAL (PART NO. 9369021053-03) This air conditioner

En-20

Fig. 36

Example If 4 indoor units are connected.

1 2

Indoor unit 0

3

1 2 3

1 2

Indoor unit 1

3 1 2

Indoor unit 2

3 1 2

Indoor unit 3

3

Remote controller

Bus wire

Remotecontrollercord

2. INDOOR UNIT SETTINGS

(1) Indoor unit addressesRotary switch (SW5) - - - Factory setting “0”When connecting multiple indoor units to one refrigerant system, set the address at SW5 in sequence from 0.

(2) Refrigerant circuit addressRotary switch (SW7) - - - Factory setting “0”Rotary switch (SW8) - - - Factory setting “0”In the case of multiple refrigerant systems, set SW7 and SW8 as shown in the Table 14 for each refrigerant system. Set to the samerefrigerant circuit address as the outdoor unit.

(3) Remote controller addressRotary switch (SW9) - - - Factory setting “0”When connecting multiple indoor units to one standard wired remote controller, set the address at SW9 in sequence from 0.

(4) Performance switchingSet the DIP switch (SW4) according to the model type of the indoor unit as shown below.

Table 16

Capacity 90 60 54 45 36 30 25·24 20 18 14 12 9 7

SW4-1 OFF ON OFF ON OFF ON OFF ON OFF ON OFF ON OFF

SW4-2 OFF ON ON OFF OFF ON ON OFF OFF ON ON OFF OFF

SW4-3 ON OFF OFF OFF OFF ON ON ON ON OFF OFF OFF OFF

SW4-4 ON ON ON ON ON OFF OFF OFF OFF OFF OFF OFF OFF

9369021053-03_IM_en.p65 11/15/10, 1:06 PM20

Page 21: Refrigerant Multi Air Conditioning System R407C for ......Multi Air Conditioning System for Buildings (VRF System) INSTALLATION MANUAL (PART NO. 9369021053-03) This air conditioner

En-21

(2) Standard wireless remote controller

• Press the remote control unit test run button while the air condi-tioner is running.

• At the end of test running, press the remote control unit start-stop button (Fig. 39).

Operation can be checked by lighting and flashing of the displaysection OPERATION and TIMER lamps.Perform judgement in accordance with the following.

• Test running

When the air conditioner is run by pressing the remote controlunit test run button, the OPERATION and TIMER lamps flashslowly at the same time.

TEST RUN buttonSTART

STOP

A B C D

START/STOP button

• When EE : EE blinks at the current time display, there is an error inside the air conditioner. If the SET TIME button ( ) and SETTEMP./DAY button ( ) are pressed simultaneously for more than three seconds, the self diagnosis check will start and the errorcontents will be displayed at the current time display. In addition, the remote controller address will be displayed below. When theoperation lamp lights, press the START/STOP button and after operation lamp goes off, perform the same operation (Fig. 38).

Fig. 38

7. TEST OPERATION

Supply power to the crankcase heater for 12 hours prior to the start of operation in the winter.The following is the procedure for the test operation.

1. TEST OPERATION USING CIRCUIT BOARD (OUTDOOR UNIT)

If the test operation is to be done for cooling operation, set DIP switch (SW1-1) to on. If the test operation is to be done for heating, setDIP switch (SW1-2) to on.

2. TEST OPERATION USING REMOTE CONTROLLER

(1) Standard wired remote controller• For test running, when the remote controller FAN CONTROL

button and MASTER CONTROL button are pressed simulta-neously for more than three seconds when the air conditioneris not running, the air conditioner starts and TEST is displayedon the remote controller display.However, the SET TEMP./DAY setting button does not function,but all other buttons, displays, and protection functions operate(Fig. 37).

Fig. 39

Fig. 37

MASTERCONTROL

FANCONTROL

TIMERMODE

TEMP./DAYSET TIME

CLOCK ADJUST

START/STOPSET DAY OFF

ZONE ENERGY SAVE

COOL

FANDRY

HEAT

AUTOAUTOCLOCKOFF

OFF

ON

ON

CF

NEXT DAY

DAYTIMER

NON STOPOFFONTIMERWEEKLY

ANTI FREEZE

CENTRAL

DAY OFFDEFROST TEST1 2

MASTERCONTROL

FANCONTROL

TIMERMODE

TEMP./DAYSET TIME

CLOCK ADJUST

START/STOPSET DAY OFF

ZONE ENERGY SAVE

COOL

FANDRY

HEAT

AUTOAUTOCLOCKOFF

OFF

ON

ON

CF

NEXT DAY

DAYTIMER

NON STOPOFFONTIMERWEEKLY

ANTI FREEZE

CENTRAL

DAY OFFDEFROST TEST1 2

MASTERCONTROL

FANCONTROL

TIMERMODE

TEMP./DAYSET TIME

CLOCK ADJUST

START/STOPSET DAY OFF

ZONE ENERGY SAVE

COOL

FANDRY

HEAT

AUTOAUTOCLOCKOFF

OFF

ON

ON

CF

NEXT DAY

DAYTIMER

NON STOPOFFONTIMERWEEKLY

ANTI FREEZE

CENTRAL

DAY OFFDEFROST TEST1 2

• To stop test running, press the START/STOP button.• For the operation method, refer to the operating manual and perform operation check.• Check that there are no abnormal sounds or vibration sounds during test running.

9369021053-03_IM_en.p65 11/15/10, 1:06 PM21

Page 22: Refrigerant Multi Air Conditioning System R407C for ......Multi Air Conditioning System for Buildings (VRF System) INSTALLATION MANUAL (PART NO. 9369021053-03) This air conditioner

En-22

8. AN ERROR DISPLAY

Operation can be checked by lighting and flashing of the LED lamps.Perform judgment in accordance with the following.

Table 17

Normal operating mode

LED 1Display Type

Not operatingCooling operationHeating operationCooling main operationHeating main operationSame performance operation

Compressor output STEP 0Compressor output STEP 1Compressor output STEP 2Compressor output STEP 3Compressor output STEP 4Compressor output STEP 5Compressor output STEP 6

Heat exchanger usage capacity STEP 0Heat exchanger usage capacity STEP 1Heat exchanger usage capacity STEP 2Heat exchanger usage capacity STEP 3Heat exchanger usage capacity STEP 4Heat exchanger usage capacity STEP 5Heat exchanger usage capacity STEP 6

Oil recoveryDefrostingTest operation

Medium pressure → Low pressure by-passHigh pressure → Low pressure by-pass

Under initialization of expansion value

LED 2

(1) (2) (3) (4) (5)

LED 3

(1) (2) (3) (4) (5) (6)

LED 4

(1) (2) (3) (4) (5) (6)

LED 5

(1) (2) (3)

LED 6

(1) (2)

: Lighted continuouslyDisplay Method : 0.5sec ON/0.5sec OFF flashing

( ) : Flashing times{

OFF

ON

LED 1

LED 2-6

OFF

ON

0.5 sec2 sec

0.5 sec

Operation display

9369021053-03_IM_en.p65 11/15/10, 1:06 PM22

Page 23: Refrigerant Multi Air Conditioning System R407C for ......Multi Air Conditioning System for Buildings (VRF System) INSTALLATION MANUAL (PART NO. 9369021053-03) This air conditioner

En-23

CAUTION

ERROR LED DISPLAY LAYOUT

LED

4

LED

1

LED

5

LED

2

LED

6

LED

3IC

Abnormal Mode

LED 1Display Type

Compressor 1 errorCompressor 2 errorCompressor 3 errorDischarge temperature 1 errorDischarge temperature 2 errorDischarge temperature 3 errorHigh-pressure errorLow-pressure errorPump down error

Discharge temperature thermistor 1 errorDischarge temperature thermistor 2 errorDischarge temperature thermistor 3 errorHeat exchange inlet thermistor 1 errorHeat exchange inlet thermistor 2 errorHeat exchange inlet thermistor 3 errorHeat exchange outlet thermistor 1 errorHeat exchange outlet thermistor 2 errorHeat exchange outlet thermistor 3 errorSuction temperature thermistor errorOutdoor temperature thermistor error

Discharge pressure sensor errorLiquid pressure sensor errorSuction pressure sensor errorOil sensor errorOil recovery error

Reverse phase blocker errorPower supply frequency abnormalModel information abnormalEEPROM access errorEEPROM deletion errorOutdoor unit circuit board error 1Outdoor unit circuit board error 2Transmission errorNode setting error

Indoor unit error

LED 2

(1) (2) (3) (4) (5) (6) (7) (8) (9)

LED 3

(1) (2) (3) (4) (5) (6) (7) (8) (9) (10) (11)

LED 4

(1) (2) (3) (4) (7)

LED 5

(1) (2)

(3) (4) (6) (7) (8) (9)

LED 6

(1)

Display Method : 0.1sec ON/0.1sec OFF flashing: 0.3sec ON/0.3sec OFF flashing

( ) : Flashing times

9369021053-03_IM_en.p65 11/15/10, 1:07 PM23

Page 24: Refrigerant Multi Air Conditioning System R407C for ......Multi Air Conditioning System for Buildings (VRF System) INSTALLATION MANUAL (PART NO. 9369021053-03) This air conditioner

En-24

9. INFORMATION

Label

Main contents of label

Item Detail

1. Model name Model name

2. Serial number Serial number

3. Electric characteristics Phase, rated voltage, and frequency

4. Capacity Cooling/heating capacity

5. Current Electric current during cooling/heating operation

6. Input power Input during cooling/heating operation

7. Max. Over Current Maximum electric current

8. Max. pressure (HP/LP) Means pressure of High Pressure side/Low Pressure side

9. Refrigerant Refrigerant type and initial charging amount

10. Weight Product weight

11. Protection Protection level against dust and water