Rectifiers
for stationary battery systems
Range ADC II
8/11/2019 Rectifier for Stationary Adc_ii_07-02
http://slidepdf.com/reader/full/rectifier-for-stationary-adcii07-02 2/4
AC-input
• Input voltage: 230V ± 15 %, 47 - 63 Hz
• Power factor: > 0,98 at nom. load
• Efficiency: 82 - 90 % depending on
the output voltage
• mains input fuse
•soft start
DC-output
• 4 possible output voltages
• constant power characteristic with current limiting
• output voltage accuracy < 0,5 %
• ripple < 0,05 % eff
• phosmetric noise voltage ≤ 1 bzw 2 mV acc.to CCITT
• short-circuit-proof
• parallel switchable
• blockable equalizing• automatic charging possible
• output relay for "power failure"
• output relay for "common alarm"
General
his rectifier range is suitable for boost and float-charging
of stationary installations. The low power ranges, are also
suitable for charging starter-batteries for diesel motors or gas
turbines.
Because the ADC has a very low output ripple current, it is ideal-
ly suited to be used with sealed batteries. The ADC can also be
connected to loads without batteries because of its excellent
dynamic performance.
These units can be supplied as a wall-mounted version (see pic-
ture 3) or as module (see picture 2) in a 19" plug-in version (see
picture 1).
Integrated function
he ADC is equipped with an active filter for sinusoidal
current consumption on the mains input. Using this tech-
nology a power factor of nearly 1 can be reached. This means
that only actual power is taken from the supply to feed the ADC.
The output is accurate, with constant power characteristic and
equipped with 3 different voltage levels as well as a current
limiting.
For optimizing the battery service life of sealed batteries tempe-
rature compensated charging voltage regulation is possible.
The unit is cooled with a fan which is temperature controlled
and superviced by a max. temperature guard.
T T
Monitoring functions
• mains fault
• rectifier fault
• monitoring of the adjusted constant voltage
• fuse alarm
• over temperature alarm
battery temperature monitoring with compensation charging
(temperature sensor necessary)
Standard display CL 20 (see picture 4)
The display unit is microprossesor controlled and supplied via
DC-DC-converter from the output voltage during mains failure
from the battery.
• push button for ON/OFF with LED indication
• push button for boost with LED indication
• push button for reset
• LCD display with push button and LED’s for indication of out-
put voltage and current also the adjusted limits• LED "operation"
• LED "Failure"
• LED "voltage deviation"
Picture 2: Module Picture 1: 19“-plug in
TECHNICAL DATA
ADC II
8/11/2019 Rectifier for Stationary Adc_ii_07-02
http://slidepdf.com/reader/full/rectifier-for-stationary-adcii07-02 3/4
8/11/2019 Rectifier for Stationary Adc_ii_07-02
http://slidepdf.com/reader/full/rectifier-for-stationary-adcii07-02 4/4
7 8 4 1 3 5 . 0
0
0 2 / 2 0 0 2
p a u s D e s i g n & M e d i e n ,
B o c h o l t
S u b j e c t t o a l t e r a t i o n s .
P r i n t e d
o n c h l o r i n e f r e e p a p e r .
Type Input voltage Input current Output voltage Output current Dimensions Weight
( V ) ( A ) ( V ) ( A ) H x W x D kgE 230 G 12/ 20 BWru - ADC/M 230 0,9 12 20 190 x 250 x 170 5
E 230 G 24/ 12 BWru - ADC/M 230 1,6 24 12 190 x 250 x 170 5
E 230 G 24/ 20 BWru - ADC/M 230 3,2 24 20 190 x 250 x 170 6
E 230 G 48/ 6 BWru - ADC/M 230 1,6 48 6 190 x 250 x 170 5E 230 G 48/ 12 BWru - ADC/M 230 3,2 48 12 190 x 250 x 170 6
E 230 G 60/ 4,8 BWru - ADC/M 230 1,6 60 4,8 190 x 250 x 170 5
E 230 G 60/ 9,5 BWru - ADC/M 230 3,2 60 9,5 190 x 250 x 170 6
E 230 G 110/ 5 BWru - ADC/M 230 3,2 110 5 190 x 250 x 170 6
MODULE VERSION
CABINET VERSION
275
4
1 0
2 2
9
1 9 0
230247
5,5 7
1
7 5
1
9 0
ø 5,5 (4x)
8
ø 10 (2x)
1 5 5
16,5140
172,5
482,6465,18,75
5,9
8 8
7 6 ,
2
210220,5241 41
1 5
Typetable ADC II range
19“PLUG IN VERSION
DIMENSION DIAGRAMS
Module version Wall mounted cabinet
19“-plug in version
ADC II
Benning GmbH & Co. KG Tel. +49 (0)2871 93 - 0 Fax 93 - 380
Münsterstraße 135 – 137 • D-46397 Bocholt E-Mail: [email protected]
Type Input voltage Input current Output voltage Output current Dimensions Weight
( V ) ( A ) ( V ) ( A ) H x W x D kg
E 230 G 12/ 20 BWru - ADC/G 230 0,9 12 20 410 x 275 x 190 9
E 230 G 24/ 12 BWru - ADC/G 230 1,6 24 12 410 x 275 x 190 9
E 230 G 24/ 20 BWru - ADC/G 230 3,2 24 20 410 x 275 x 190 10
E 230 G 48/ 6 BWru - ADC/G 230 1,6 48 6 410 x 275 x 190 9
E 230 G 48/ 12 BWru - ADC/G 230 3,2 48 12 410 x 275 x 190 10
E 230 G 60/ 4,8 BWru - ADC/G 230 1,6 60 4,8 410 x 275 x 190 9E 230 G 60/ 9,5 BWru - ADC/G 230 3,2 60 9,5 410 x 275 x 190 10
E 230 G 110/ 5 BWru - ADC/G 230 3,2 110 5 410 x 275 x 190 10
Type Input voltage Input current Output voltage Output current Dimensions Weight
( V ) ( A ) ( V ) ( A ) H x W x D kg
E 230 G 12/ 20 BWru - ADC/E 230 0,9 12 20 89 x 483 x 240 5
E 230 G 24/ 12 BWru - ADC/E 230 1,6 24 12 89 x 483 x 240 5
E 230 G 24/ 20 BWru - ADC/E 230 3,2 24 20 89 x 483 x 240 6
E 230 G 48/ 6 BWru - ADC/E 230 1,6 48 6 89 x 483 x 240 5
E 230 G 48/ 12 BWru - ADC/E 230 3,2 48 12 89 x 483 x 240 6
E 230 G 60/ 4,8 BWru - ADC/E 230 1,6 60 4,8 89 x 483 x 240 5
E 230 G 60/ 9,5 BWru - ADC/E 230 3,2 60 9,5 89 x 483 x 240 6
E 230 G 110/ 5 BWru - ADC/E 230 3,2 110 5 89 x 483 x 240 6