Product Manual PM WHR-2

Group: Chiller

Effective: May 2000

Supersedes: PM WHR-1

© 1997 McQuay International

Reciprocating Chillers

WHR 017EW To WHR 210EW, Packaged Water-CooledWHR 017EA To WHR 210EA, Remote Condenser

17 to 210 Tons, 60 to 740 kWR-22, R134a

60 Hz

Page 2: Reciprocating Chillers - Daikin Applied

2 WHR 017E - 210E Product Manual WHR-2

Table of ContentsIntroduction ...................................................................................................................................... 3Features and Benefits ..................................................................................................................... 4Design Advantages .......................................................................................................................... 6Temperature Control ...................................................................................................................... 9

Standard Control .......................................................................................................................9Optional Control........................................................................................................................9Optional Network Master Panel............................................................................................12Optional Remote Monitoring and Sequence Panel............................................................12Monitor software .....................................................................................................................13Open Protocol..........................................................................................................................13MicroTech BACdrop Gateway..........................................................................................13

Selection Procedure......................................................................................................................14EW Water-Cooled, R-22 .........................................................................................................14EW Water-Cooled, R-134a .....................................................................................................15EA Remote Condenser, R-22 .................................................................................................15EA Remote Condenser, R-134a .............................................................................................17

Selection Adjustment Factors .....................................................................................................17Ethylene and Propylene Glycol Factors ...............................................................................17Evaporator and Condenser Delta-T Factors .......................................................................18Fouling Factor..........................................................................................................................18

Performance Data..........................................................................................................................19EW Water-Cooled ...................................................................................................................19Part Load Data (EW Only) .....................................................................................................25EA Remote Condenser ...........................................................................................................26

Pressure Drop Curves..................................................................................................................30Electrical Data................................................................................................................................33

Field Wiring Diagram..............................................................................................................44Physical Data..................................................................................................................................45

EW Water-Cooled ...................................................................................................................45EA Remote Condenser ...........................................................................................................50

Dimensional Data ..........................................................................................................................53EW Water-Cooled ...................................................................................................................53EA Remote Condenser ...........................................................................................................57

Sound Data......................................................................................................................................61Application Data.............................................................................................................................65Optional Features ..........................................................................................................................69

Optional Remote Monitoring and Sequencing Panel (RMS)............................................69Product Specifications..................................................................................................................71

Water-Cooled, WHR 017 through 030 .................................................................................71Water-Cooled, WHR 040E through WHR 210E..................................................................75Remote Condenser Chiller, WHR 017 through 030 ............................................................80Remote Condenser Chiller, WHR 040E - WHR 210E..........................................................84

Our Facility is

"McQuay" is a registered trademark of McQuay International1997 McQuay International

"Illustrations cover the general appearance of McQuay International products at the time of publication and wereserve the right to make changes in design and construction at anytime without notice"

ARI Certification Applies to EWWater-Cooled Units Only

Page 3: Reciprocating Chillers - Daikin Applied

Product Manual WHR-2 3

Introduction

McQuay International offers a complete line of water-cooled chillers from 17 to 2500 tons (60to 8800 kW) utilizing reciprocating and centrifugal compressors.

The WHR packaged reciprocating compressor chillers are a product of the McQuaycommitment to offer energy efficient equipment design. A design approach carefullycombining high quality compressors, efficient shell-and-tube heat exchangers, and state-of-the-art controls into a unit of uncompromised operating efficiency and reliability.

Model WHR-EW are equipped with factory-mounted water-cooled condensers.

Model WHR-EA have no condensers mounted and are intended for use with remoteevaporative or air-cooled condensers. See McQuay catalog PM ACAQ for a complete line ofmatching air-cooled condensers.

ARI Standard 550/590-98 Certified

The ARI Certification Program does not include chillers with remote condensers.Therefore, Model WHR-EA, Remote Condenser Chillers, ratings are not ARI certified.

Model WHR-EW, Water-Cooled Chillers are ARI certified.

Efficiency• WHR-EW are in compliance with ASHRAE 90.1• Cross-circuit compressor unloading• Liquid subcooling• Copeland DISCUS compressor• Maximum capacity reduction

Reliability• Rugged compressor design• Factory installed operating and safety controls

Flexibility• Complete factory assembly• 25 available sizes• Factory installed options

Serviceability• Semi-hermetic compressors• Suction and discharge service valves• Dual refrigerant circuits (WHR040 and above)

Full Factory Testing• Assures trouble-free start-up and operation

Page 4: Reciprocating Chillers - Daikin Applied

4 Product Manual WHR-2

Features and Benefits

EfficiencyWHR-EW Water-Cooled and WHR-EA Air-Cooled, (depending on remote condenser selection) meetASHRAE 90-1 efficiency levels - the world’s standard for chiller efficiency.

The “E” vintage WHR-EA reciprocating chillers offer some of the highest operating efficienciesavailable today through the use of highly efficient components and efficiency oriented packaging.

Operating economy at reduced load is increased by operating each refrigerant circuit partiallyunloaded, rather than one circuit off and the other circuit fully loaded. At unloaded conditions eachcompressor will operate at lower compression ratios with substantial power savings.

Optional steps of capacity reduction are accomplished by the most efficient method of cylinderunloading in the industry today.

To McQuay, operating economy means more than just energy efficiency. The WHR chillers reduceoperating costs not only through energy efficiency, but by offering high unit reliability, easyserviceability, full factory testing and the backing of a factory trained sales, service and partsorganization.

FlexibilityThe WHR chillers come in 25 sizes between 17 and 210 nominal tons (60 and 710 kW). The smallcapacity increments provide a selection that will closely match the required job capacity.

The WHR water chillers come completely factory assembled, piped, wired, and shipped in one piece;ready for water piping and wiring connections. The EA remote condenser models are ready for fieldpiping to the remote condenser. Single main supply power terminal block can be supplied by one fieldinstalled main supply power disconnect switch.

Many optional features can been added to fit your needs. A unit mounted non-fused disconnectswitch eliminates the need for a field installed disconnect. Phase failure/reversal protection, highreturn water unloading, and acoustical sound enclosures around compressor are all optional featuresthat can be factory installed.

ReliabilityThe McQuay WHR chillers use the most advanced and efficient reciprocating compressors in theindustry, the Copeland DISCUS valve compressors. These heavy-duty, industrial quality, semi-hermetic compressors are designed for R 22 or R-134a.

All WHR chillers are factory run tested to assure unit functionality. All safety and operating controlsare checked and calibrated. Chillers for remote condensers are connected to slave condensers fortesting purposes. This extensive testing assures trouble-free start-ups.

To protect the unit from abnormal operating conditions, a complete set of safety controls for eachcircuit is used. Safety controls include compressor crankcase heater(s), freeze protectionpressurestats (manual reset), oil switches (manual rest), high pressure safety switches (manual reset),and compressor motor overload protectors. Standard operating controls include time delay relays for20-second sequence starting of compressors, manual pumpdown switches, low pressure controls,compressor lead-lag switches (WHR-040EW-210EW) and chilled water temperature controller. Allcontrols and wiring are completely factory labeled for ease of service.

Page 5: Reciprocating Chillers - Daikin Applied

Product Manual WHR-2 5

ServiceabilitySemi-hermetic, 1750 rpm induction type motors are employed. The motors are refrigerant gas cooled.A finned motor housing helps dissipate motor heat. Solid-state modules in the motor terminal boxrespond to temperature sensors imbedded in all three motor windings to provide inherent thermaloverload protection for all run and start conditions.

Serviceable compressors offer reducedmaintenance costs because if problemsdevelop with components such as oilpumps, unloaders, and pistons, theycan be serviced in the field withoutreplacing the compressor. Both suctionand discharge service valves areprovided to allow isolation of thecompressor from the refrigerant circuit.

All multiple compressor units utilizetwo independent refrigerant circuits.Dual refrigerant circuits permitshutdown and routine maintenance andservice of one circuit while the secondcircuit maintains system operationwhere two or more compressors aresupplied.

RefrigerantsModels WHR 017 through WHR 210 utilize R-22 as the standard refrigerant. Models WHR 040through WHR 210 can be furnished with R-134a refrigerant.

Full factory testingExtensive quality control checks and individual performance tests assure that the units will meet therequirements of the application and start-up and perform reliably. EA remote condenser models areshipped with a holding charge of refrigerant, EW water-cooled units are shipped with a completeoperating charge.

Each unit is pressure tested, evacuated and charged with refrigerant for test purposes. Extensivequality control checks and individual unit performance tests, at full load, ensure that each control isproperly adjusted and operates correctly. EA remote condenser models are connected to factory slavecondensers for testing. Each unit is then rechecked for refrigerant leakage.

Code ApprovalsAll WHRhb units are constructed and/or rated with the latest ANSI/ASHRAE 15 Safety Code,National Electrical Code and ASME Boiler and Pressure Vessel Code. All models are ETL approved orcETL listed.

Page 6: Reciprocating Chillers - Daikin Applied

6 Product Manual WHR-2

Design Advantages

Unit ArrangementsThe McQuay water chillers are completely factory assembled, piped, wired and shipped in one piece,ready for field connection of refrigerant (EA models) and water piping. Each unit consists of motorcompressors, insulated DX cooler and centralized electrical control panel containing all necessarysafety and operating controls, and compressor starting controls. Arrangement “EW” units comecomplete with water-cooled condensers with integral subcooler circuits. Arrangement “EA” units areprovided without condensers to allow for remote installation of air-cooled or evaporative condensingequipment.

Compressors WHR chillers use Copeland DISCUS semi-hermetic compressors. These compressors are designedfor R 22 and R-134a.

Semi-hermetic, 1750 rpm induction type motors are used. The motors are refrigerant gas cooled. Solid-state modules in the motor terminal box respond to temperature sensors imbedded in all three motorwindings, providing inherent thermal overload protection for all run and start conditions.

The compressor housing is constructed from close grained, high nickel content, alloy cast-iron withno bolted joint between the motor and compressor. The housing includes a cast-iron cylinder headand stator cover, and a crankcase oil sightglass. A suction strainer built into the compressor in the gasstream between the suction service valve and the motor, filters out foreign and abrasive particles. Aninternal relief valve relieves discharge pressure to the suction side for safety protection at highcompression ratios as required by ANSI/ASHRAE 15 Safety Code.

Main bearings are solid cast bronze insert type with oversized bearing area resulting in ultra-lowbearing loading.

The crankshaft is die-forged, high strength iron alloy with integral counterweights, statically anddynamically balanced for smooth operation.

Connecting rods are lightweight aluminum with integral bearing surfaces on the crankshaft and pistonends. Pistons are close grain cast iron with oil and compression rings. Piston pins are full floatingtype for long life.

Compressors have a forced-feed lubrication system with positive oil displacement, a reversible oilpump, and an operating oil charge. The pump feeds oil through rifle-drilled passages in the crankshaftto all bearing surfaces. Magnetic plugs trap particles that enter the crankcase. The oil supply filtersthrough a large area oil strainer. During start-up, a crankcase heater minimizes oil being diluted byrefrigerant.

Factory Installed Liquid Line Components Each refrigerant circuit has a filter-drier, liquid line sightglass/moisture indicator, solenoid valve,manual liquid line shutoff valve and thermal expansion valve.

Short Circuit Protection (WHR 017 through 030, WHR 095 through 210)

Each compressor is individually protected against short circuit and locked rotor conditions by factoryinstalled circuit breakers. Separate fusing protects the control circuit. WHR-040 through 090 can havecircuit breakers factory installed as an option.

Page 7: Reciprocating Chillers - Daikin Applied

Product Manual WHR-2 7

Part Load Efficiencies Part load efficiencies and Integrated Part Load Values (IPLV) for EW units are calculated according tothe requirements of the latest ARI Standard 550/590-98 and meet or exceed ASHRAE EfficiencyStandard 90.1. Since most air conditioning systems operate at less than design full load a majority ofthe time, IPLV is an excellent method for comparing chillers' efficiencies.

Noise All McQuay WHR chillers are equipped with hot gas discharge line mufflers in each refrigerant circuitto reduce the overall sound levels. An optional insulated acoustical compressor enclosure to furtherreduce sound levels is also available for most units. Sound level ratings are contained in the SoundRating section of this manual.

Unit Base Designed for easy handling, the units are mounted on a compact, rugged formed steel base. Isolatormounting holes are provided.

Electrical Control Center Shipped with all operating and safety controls and motor starting equipment factory wired,operationally tested, and ready for operation. All controls are centrally located in a hinged controlcenter with keylocked doors.

Part-winding starters are standard on 208/230 volt applications and available as a special on 460/575volts. Across-the-line starters are standard on 380/460/575 volts.

A five-minute, solid-state lockout timer is provided to delay compressor restart after safety cutout orpower interruption, or under irregular cooling load demands. A lead lag switch is standard on all units(WHR 040 – WHR 210) not incorporating the single circuit hot gas bypass option.

Evaporator The evaporator is a direct expansion, shell-and-tube type with water flowing in the baffled shell sideand refrigerant flowing through the tubes.

The evaporator is constructed with a carbon steel shell and seamless high efficiency copper tubes,roller expanded into heavy carbon steel tube sheets. Water baffles are polypropylene to resistcorrosion.

Refrigerant heads are carbon steel with multi-pass baffles to ensure oil return and are removable topermit access to the tubes from either end. For water removal, 3/8" (10mm) vent and drain plugs areprovided on the top and bottom of the shell. Two 1/2” (12.7mm) couplings on each water nozzle allowfor easy field installation of sensor equipment.

The evaporator is wrapped with 3/4” (19.1mm) thick vinyl nitrate polymer sheet insulation. Theinsulation has a K factor of 0.28 at 75°F (24°C). The insulation is fitted and cemented in place, thenpainted with a resilient vinyl base paint to resist cracking.

The tube side maximum working pressure is 225 psig (1552kPa). The waterside working pressure is 175psig (1206kPa). All evaporators are designed, constructed, inspected and stamped according to therequirements of the ASME Boiler and Pressure Vessel Code.

Page 8: Reciprocating Chillers - Daikin Applied

8 Product Manual WHR-2

Water-Cooled Condensers All water-cooled condensers are cleanable shell and tube type with water in the tubes and refrigerantin the shell. Each condenser is capable of holding the circuit pumpdown capacity. Independentcondensers serve the dual refrigerant circuits.

Each condenser is constructed with a carbon steel shell and seamless integrally finned high efficiencycopper tubes roller expanded into steel tubesheets. Water heads have vent and drain connectionsand are removable. Also included is a liquid shutoff valve, purge valve, 450 psi (3104 kPa) relief valveper ANSI/ASHRAE Pressure Vessel Code, Section VIII.

Water side working pressure is 225 psi (1550 kPa), refrigerant side is 450 psi (3104 kPa).

Air-Cooled CondensersThe WHR-EA chillers are designed for use withproperly sized and configured remote air-cooled orevaporative condensers. The McQuay AC/AQ line ofair-cooled condensers are designed for use with thesechillers. The AC/AQ condensers are available withsingle or double row vertical discharge fans and arefully described and rated in Product Manual PMACAQ. They are packed with features offeringtangible benefits to owners.

• Complete range of capacities from 10 to 210 tons

• Circuits matched to WHR chillers

• Direct drive fan motors at 1140 and 830 RPM

• Patented floating tube design to eliminate tube sheet leaks

• High efficiency coil and fan motor design

• Internal baffles between all fan cells

• Weatherproof control panel with door mounted disconnect switch

• G90 painted galvanized steel cabinets

• Single point power connection

• Independent fusing and contactors for each fan motor

• Integral pre-piped subcooler circuit

Page 9: Reciprocating Chillers - Daikin Applied

Product Manual WHR-2 9

Temperature Control

The McQuay WHR-040EW through 210EW water chillers are available with any one of threedifferent temperature controls to satisfy your requirements: 1) the standard microprocessor leavingwater controller, 1a) the same controller but with an indicator light package, and 2) the MicroTechController.

Standard ControlWHR-017 - 030

A return water electromechanical temperature controller is supplied on the WHR-17 through 030when supplied with two stages. Three stage units are supplied with a solid state, return watertemperature controller.

On Model EA units for remote condensers this controller is equipped with terminals from which thefirst fan motor can be energized on compressor start. These sizes have a single refrigerant circuit.

WHR 040 - 210

The UNT-33 microprocessor leaving water temperature controller is standard on all units from size040 to 210 and provides precise temperature control based on leaving water temperature. Thecontrol is preset and calibrated and no other adjustment is required other than setpoint. There is a60 second interstage On Delay between stages. Each stage incorporates minimum on and off timerswith a maximum cycle rate of six cycles per hour. Reset of supply water temperature can beaccomplished from outside air temperature, zone temperature or a signal from an EMS system.

Condenser fan control (Model EA)Some means of controlling discharge pressure is required on condensers applied to the WHR-EAremote condenser units. The McQuay AC/AQ air-cooled condensers can be equipped withpressure activated fan cycling switches or with variable speed drives. Neither method requiresinterconnecting wiring between the chiller and condenser.

Optional Control

Optional Zone Terminal for use with the UNT ControlProvides for onboard (or remotely wired) monitoring or adjusting of certain functions.

• Monitoring

• Monitor up to three setting or sensed values

• Monitor 18 different on/off inputs

• Monitor alarm status via a flashing alarm light and flashing symbol

• Adjusting, allows adjustment of any flashing set points, three at a time, typically set up so thatthe relationship between values can be viewed simultaneously. For example:

• Display 1 = Lvg Water temp

• Display 2 = Lvg Water SP

• Display 3 = % Unit Load

Page 10: Reciprocating Chillers - Daikin Applied

10 Product Manual WHR-2

Figure 1, Zone Terminal Configuration

MONITORADJUSTTIME SCHEDULEPASSWORD

ENTER

Compressor 1Compressor 2Stage 3Stage 4

Solenoid #1

Frzstat#1AlmFrzstat#2AlmMinLowPres#1MinLowPres#2

OccupiedFlow FailureOA LockoutCir#2Lead=OnPmp/Stp #1=0

Lvg Water TempEvap Pres #1Evap Pres #2OA/AI3 Input

LvgWtr RBnd SPContrl Band SPActual Lvg SP

Unoccpd Lvg SPOA Lockout SP

Lvg Low Lim SPSoftSta Capcty

Cir #1 StartsCir #2 Starts

McQuay AGZ/AGR Global ChillerINSERT 10

ON OFF

Display Button 1

ModeSelector Panel

Mode SelectorButton

2

AGZ-AGR

Display Indicator Dot On/Off Status

3

Operating Mode Indicator

Up/Down Arrow Keys

Door

Display Item List Warning Signal

ALARM

OA/AI3 HiLimSPOA/AI3 ResetSP

Display Area 11

Display Area 21

Display Area 31

Alarm Light

Lvg Water SP

% Unit Load

SoftStart Time

Pmp/Stp #2=0

Solenoid #2

Stage 5 Opt.Stage 6 Opt.

Optional MicroTech Chiller ControllerWHR-040 – 210 Only

The MicroTech reciprocating chiller controller surpasses all other microprocessor-based chillercontrol systems available today. This powerful, user-friendly control system provides the flexibilityand performance needed for a stand-alone unit as well as multiple units tied into a network system.

MicroTech’s state-of-the-art design will not only permit your chiller to run more efficiently, but willalso simplify troubleshooting if a system failure occurs. Every MicroTech controller is programmedand tested prior to shipment to ensure a trouble-free start-up.

Condenser fan control (Model EA)Control of condenser fans is available through the MicroTech controller. The control stepscondenser fans or groups of fans based on discharge pressure. Field wiring is required betweenthe chiller and the remote condenser.

Page 11: Reciprocating Chillers - Daikin Applied

Product Manual WHR-2 11

Operator-friendlyThe 12-key, touch-sensitive, membrane keypad and 32-character display makes the MicroTechsystem especially user-friendly. Inch-pound or SI units are optionally available.

The MicroTech menu structure is separated into three distinct categories, which provide theoperator or service technician with a full description of current unit status, control parameters, andalarms. Security protection prevents unauthorized changing of the setpoints and controlparameters.

MicroTech continuously performs self-diagnostic checks, monitoring all system temperatures,pressures and safeties, and will automatically shutdown a compressor, a refrigerant circuit of theentire unit should a fault occur. The cause of the shutdown will be retained in memory and can beeasily displayed in plain English or metric units for operator review. The MicroTech chillercontroller can also retain and display the time the fault occurred and the operating conditions thatwere present at the time of the fault, which is an extremely useful feature for troubleshooting. Inaddition to displaying alarm diagnostics, the MicroTech chiller controller also provides the operatorwith a warning of pre-alarm conditions.

Ice storageThe MicroTech control easily changes the leaving fluid setpoint via a remote signal to thecontroller. The feature enables selection of chilled water or ice storage mode.

Enhanced chiller operating efficienciesThe MicroTech chiller controller offers many features to improve the operating efficiency of thereciprocating chiller. In addition to monitoring water temperature and air temperatures, refrigeranttemperatures and pressures, and unit amperage, MicroTech also offers the following energy savingfeatures:

Programmable setpoints

The MicroTech chiller controller offers precise digital settings of the leaving chilled watertemperature setpoint and all other control parameters. This is extremely important in the setting ofsafeties such as low leaving water temperature cutout, high pressure cutout, suction pressurecutout, and freeze protection.

Compressor soft loading

Soft loading limits the number of cooling stages to prevent unnecessary electrical demand andpossible overshoot of the leaving chilled water temperature setpoint.

Demand limit control

Based on a 4-20mA DC signal, the controller will determine the maximum number of stages permittedto operate, preventing additional demand charges during high usage periods.

Page 12: Reciprocating Chillers - Daikin Applied

12 Product Manual WHR-2

Automatic circuit lead-lag

With the keypad, the operator can manually select either refrigerant circuit for the lead position orthe controller will automatically select the lead circuit based on the circuit with the fewest operatinghours.

Time clock, daily and holiday start/stop control

The operator can program daily start/stop schedules including weekends and up to fourteenseparate holidays without the need of an external time clock or EMS interface. If desired, anexternal time clock can be used instead of the internal schedule.

Chilled water pump control

There is no need for an external time clock or EMS interface to control the pump start/stopoperation. The MicroTech chiller controller can accomplish this through a digital output. If analarm shuts down the chiller, the chilled water pump will remain on, providing any remaining coolingto the loads.

Optional Network Master PanelThe MicroTech Network Master Panel (NMP) allows multiple reciprocating chiller controllers to beincorporated into a building-wide network with other MicroTech units and auxiliary controllers. Inconjunction with a personal computer, it provides the building operator with the capability toperform advanced equipment control and monitoring from a central or remote location. Thefollowing features are provided by the optional NMP:

• Remote unit monitoring• Advanced scheduling features• Advanced alarm management features• Global operator override• Global unit shutdown input• Demand metering• Historical electrical data logging

Optional Remote Monitoring and Sequence PanelOne to three reciprocating chiller controllers can be incorporated into a network with the MicroTechremote monitoring and sequencing (RMS) panel. The optional RMS panel provides the followingfeatures:

• Remote chiller monitoring (up to 3)• Automatic or manual chiller sequencing• Automatic or manual lead-lag designation• Common chiller scheduling• Optimal start control• Chilled water reset by outdoor air temperature or external 4-20 mA signal• Chiller run time totalization by month, current year, and prior year• Cooling degree-day totalization by month, current year, and prior year

The RMS panel is equipped with a keypad/display that is identical to the chiller controller’skeypad/display. With a special keystroke combination, the RMS keypad/display can be interfacedwith any chiller controller. It then operates identical to the chiller-mounted keypad/display. Thusthe operator has full access to all networked chillers from a single remote location. Panel-mountedLED’s clearly indicate which controller the RMS panel keypad/display is currently interfaced with.

Page 13: Reciprocating Chillers - Daikin Applied

Product Manual WHR-2 13

Monitor softwareWhen properly equipped with MicroTech Monitor software, a direct or remote connected PC can beused for monitoring unit operation, changing setpoints, scheduling, trend logging, downloadingcontroller software, and diagnostics. For MicroTech network systems, the PC gives the operatoraccess to all unit and auxiliary controllers in the network. Specific controller or global data can bedisplayed as desired. All keypad status information and control capability is available at the PC in afull-screen format. Many additional unit control parameters, which are not available at the unitcontroller’s keypad, are also available. Monitor software provides the following features:

• High resolution, unit-specific graphic representations• One-touch function keys• Multiple unit display screen• Automatic screen refresher• Help text• Dial-up communications• Alarm monitoring and management• Scheduling• Trend logging• Downloading capability• Multi-level password protection• Controller Diagnostics

Open ProtocolMicroTech Open Protocol Master panel provides an interface between MicroTech unit controllersand virtually all building automation systems (BAS). A protocol is a set of rules governing dataexchange between microprocessors, thereby permitting communications between unlike controllers.As a result, building designers, owners and operators can obtain the advantages of McQuayequipment, and the control versatility MicroTech has to offer. A low cost site license covering anyand all McQuay product is required.

MicroTech BACdrop GatewayThe McQuay BACdrop Gateway panel allows any BACnet based building automation system(BAS) to communicate with MicroTech controllers. The panel translates between the standardBACnet protocol (ANSI/ASHRAE 135-1995) and the MicroTech protocol. No modifications to theMicroTech hardware or software are necessary. Since BACnet is a standard, public protocol nolicense agreement is necessary.

Page 14: Reciprocating Chillers - Daikin Applied

14 Product Manual WHR-2

Selection Procedure

EW Water-Cooled, R-221. Ratings are based and certified in accordance with ARI Standard 550/590-98.2. Ratings in Table 5 through Table 10 may be interpolated for any chiller water temperature

between 40°F and 50°F (4.4°C and 10.0°C) but cannot be extrapolated.3. Chilled water quantities - Ratings are based on a 10 degree F (5.6 degree C) chilled water range

(2.4 gpm/ton) and can be used for a delta-T range of 6 to 16 degrees F (3.3 to 8.8 degrees C) byadjustments from Table 3.

4. Figure 2 through Figure 4 give the evaporator water pressure drop data. Water flow ratesshould be maintained within these limits, which are based on minimum and maximum flow.

5. Ratings are based on 0.0001 fouling factor for the evaporator. For other fouling factors,multiply ratings by evaporator factors from Table 3. For applications using a glycol solution,see Table 1 and Table 2.

6. Ratings are based on condenser flow of 3 gpm/ton (10 degree F, 5.6 degree C delta-T) and0.00025 fouling factor. Corrections for other conditions are in the following ApplicationSection.

Selection ProcedureKnowing the required chiller capacity in tons, the leaving water temperature and either the chilledwater temperature range (Delta T) or the flow, determine the unknown quantity using the formula:

24 = Tons

TDeltaGPM ×

Knowing the required chiller capacity (tons), the entering condenser water temperature, and eitherthe condenser water temperature range-delta T, or the GPM, determine the unknown quantity usingthe formula:

aterRangeCondenserW30Capacity Cooling Tons Nominal

.Cond TDelta500THR

=GPM Condenser ×

With the above data, the appropriate unit can be selected from Table 5 through Table 10. Pressuredrop for evaporators and condensers can be found in Figure 2 through Figure 4.

Sample SelectionGiven: Cool 165 GPM of water from 54°F to 44°F with condenser water available at 85°F.Condenser water temperature rise to be 10 degrees. Fouling factor of 0.0001 in the evaporator and0.00025 in the condenser.

Find:

A. WHR packaged water chiller selectionB. Compressor power inputC. Condenser water flow rateD. Evaporator and condenser water pressure drop

Page 15: Reciprocating Chillers - Daikin Applied

Product Manual WHR-2 15

Solution:

1. Chilled water range: 54°F - 44°F = 10°F (Temperature Difference).

2. 24

Range Water ChilledGPM=Capacity

× = 68.8 tons165 10

24×

3. From Table 6, a model WHR-070EW has the capacity to meet the job requirement. For anevaporator leaving water temperature of 44°F and condenser water entering temperature of85°F with a 10 degree rise, the unit capacity rating table indicates:

Capacity: 70.5 Tons

Power: 62.4 kW

4. Determine condenser water from the following:

Condenser GPM = Tons Cooling Capacit y 30

Nominal Condenser Water Range×

GPM 211degrees 10

30 tons70.5 = =

×

5. From Figure 2 for the WHR-070EW, evaporator pressure drop at 165 GPM is 6.2 feet

6. From Figure 3, the condenser pressure drop at 210.6 GPM is 12.5 feet water.

EW Water-Cooled, R-134aUse the same selection procedures as with R-22 except multiply the values in the R-22 PerformanceTables as follows: Capacity x 0.68, Power x 0.65, EER x 1.05.

EA Remote Condenser, R-22

Selection MethodThe performance of the WHR chillers is listed by LWT (leaving chilled water temperature) and byCondensing Temperature . Tons, Power, and THR (Total Heat Rejection) are given. This data canthen be used to select any condenser from its own capacity data. For a McQuay AC/AQ air-cooledcondenser, use product manual PM ACAQ.

1. Ratings may be interpolated for any chiller water temperature between 42°F and 50°F butcannot be extrapolated (contact factory for ratings outside this range).

2. Chilled water quantities - Ratings are based on a 10 degree F chilled water range and areapplicable from a minimum of 6 degrees F to a maximum of 16 degrees F differential betweenentering and leaving chilled water temperatures.

3. Ratings are based on .00025 fouling factor for both condenser and evaporator. For otherfouling factors, multiply ratings by cooler factors from Table 3 and Table 4. For applicationsusing a glycol solution, see Table 1 and Table 2.

Selection ProcedureNormally the required chiller capacity in tons, the entering and leaving chilled water temperatureand flow and the design outdoor air temperature are known. Determine any unknown quantityusing the formula:

Tons = gpm x delta T / 24

Capacity data is in Table 12 and Table 13 for IP units and Table 14 and Table 15 for SI units. Ratingare based on:

• Leaving chilled water temperatures from 42°F to 50°F (6°C to 10°C) with a 10 degree delta-T.Selections can be interpolated between these leaving temperatures but not extrapolated.

Page 16: Reciprocating Chillers - Daikin Applied

16 Product Manual WHR-2

Correction factors for delta-Ts other than 10 degrees are in Table 3 and Table 4. Exceeding theDelta-T range of 6 to 16 degrees will cause problems controlling unit unloading.

• Condensing temperatures (CT) from 105°F to 125°F (40°C to 55°C).

• Total Heat Rejection (THR) is given and used to select the condenser, whether it be a dry air-cooled condenser or an evaporative condenser.

Several different size condensers can usually be matched to any given WHR-EA unit depending onthe condensing temperature that typically ranges from 20 to 30 degrees F above the design outdoortemperature. Increasing condensing temperatures will reduce the chiller capacity, increase its powerconsumption and result in a smaller condenser being required.

Normally a WHR-EA is selected to meet or exceed the required cooling capacity at somecondensing temperature and a condenser then selected with sufficient capacity to handle the heatrejection with the selected temperature difference (TD, difference between design outdoor dry bulbtemperature and condensing temperature).

A more accurate solution can be achieved by plotting the capacity of the chiller and the condenseras a function of the TD and observing the curves intersection that is the system balance point. Anexample is shown in the following "Selection Example" section.

Sample SelectionsGiven: Required capacity of 100 tons cooling 240 gpm of water from 54°F to 44°F with 95°F designdry bulb temperature. Evaporator fouling factor of .00025.

Find:

1. WHR water chiller and AC/AQ condenser selection

2. Compressor power input, chilled water pressure drop

Solution:

1) From Table 13, several WHR selections are possible:

a) WHR 110EA at 110°F CT; 102.5 tons, 107.3 kW, 1596.5 THR, 1.05 kW/ton

b) WHR 115EA at 115°F CT; 101.0 tons, 112.8 kW, 1597.3 THR, 1.12 kW/ton

c) WHR 120EA at 125°F CT; 103.4 tons, 135.1 kW, 1701.5 THR, 1.30 kW/ton

Note that the condensing temperature has significant influence on the chiller efficiency.Progressing from a) to c) above will require smaller condensers, offset by larger, moreexpensive chillers and lessening efficiency.

2) A condenser can be selected with the above information. For this example, a McQuay ModelACAQ air-cooled condenser will be selected using selection procedures and data contained inProduct Manual PM ACAQ. A model ACD (double row of fans, standard fan speed) will beused.

a) For the WHR 110EA at a TD of 15 degrees F (110°F - 95°F) no selection appears possiblebased on the simple selection method. However, it is close and the graphical method maygive a solution.

b) For the WHR 115EA at a TD of 20 degrees, a Model 175A will do the service.

c) For the WHR 120 EA at a TD of 30 degrees, a Model 115A will do the service.

Selection c) will prove to be considerably lower in first cost but carries a 16 percent efficiencypenalty.

Page 17: Reciprocating Chillers - Daikin Applied

Product Manual WHR-2 17

3) Graphical solution to Case a) is shown below.

d) The THR for the WHR110EA is plotted using twopoints; TD=10 degrees(105°F-95°F) and TD=25degrees (120°F-95°F).

e) The THR for the ACD 210Ais plotted using its capacityat TD+15 degrees andTD=18 degrees.

f) The curves intersect atTD=16.5 degrees or 111.5°Fcondensing temperature.

g) Extrapolating the WHRcapacity at 111.5°F gives101.5 tons which will meetthe job requirements. It willbe the highest cost butmost efficient unit.

EA Remote Condenser, R-134aUse the same selection procedures as with R-22 except multiply the values in the R-22 PerformanceTables as follows: Capacity x 0.68, Power x 0.65, EER x 1.05.

Selection Adjustment Factors

Ethylene and Propylene Glycol FactorsWHR units are designed to operate with a leaving chilled fluid temperature from 21°F (-6.1°C) to60°F (16°C). Leaving chilled fluid temperatures below 40°F (4.6°C) result in suction temperatures ator below the freezing point of water and a glycol solution is required. The use of glycol in theevaporator will reduce the performance of the unit. The reduction in performance depends uponthe glycol concentration. This should be taken into consideration during initial system design.

McQuay encourages a minimum concentration of 25% be provided on all glycol applications.Glycol concentrations below 25% are too diluted for long-term corrosion protection of ferrousmetals and corrosion inhibitors may need to be recalculated. Glycol in the condenser will have anegligible effect on performance because glycol at higher temperatures will perform withcharacteristics similar to water.

Table 1, Adjustment Factors for Ethylene GlycolFreeze PointPercent

E.G °F °CCap. Power Flow PD

10 26 -3 0.991 0.966 1.013 1.07020 18 -8 0.982 0.992 1.040 1.12930 7 -14 0.972 0.986 1.074 1.18140 -7 -22 0.961 0.976 1.121 1.26350 -28 -33 0.946 0.966 1.178 1.308

Table 2, Adjustment Factors for Propylene GlycolFreeze PointPercent

P.G °F °CCap. Power GPM PD

10 26 -3 0.987 0.992 1.010 1.06820 19 -7 0.975 0.985 1.028 1.14730 9 -13 0.962 0.978 1.050 1.248

Page 18: Reciprocating Chillers - Daikin Applied

18 Product Manual WHR-2

40 -5 -21 0.946 0.971 1.078 1.366NOTE: Glycol applications are not included in the ARI certification program.

Evaporator and Condenser Delta-T FactorsPerformance tables are based on a 10°F (5°C) temperature difference through the evaporator andcondenser. A temperature difference other than 10°F (5°C) will result in unit performance beingdifferent from what is shown. Adjustment factors for applications having temperature dropsbetween 6°F and 16°F (3.3°C to 8.9°C) can be found in Table 3 and Table 4.

Fouling FactorPerformance tables are based on water with a fouling factor of 0.0001 ft2 x hr x °F/BTU (0.0176 m2 x°C/kW) in the evaporator and 0.00025 ft2 x hr x °F/BTU (0.044 m2 x °C/kW) in water-cooledcondensers according to ARI 550/590-98. As fouling is increased, performance decreases. SeeTable 3 and Table 4 for performance with other fouling factors.

To ensure optimum unit operation, proper water treatment must be maintained. Scaling and dirt in asystem will vary significantly depending on local water conditions. Water treatment should bebased on characteristics of the area’s water. Improper or untreated water may lead to scale build up,erosion and corrosion in both the condenser and evaporator. McQuay will not acceptresponsibility for poorly or improperly treated water.

Table 3, Evaporator Adjustment FactorsFouling FactorChilled Water

Delta-T 0.0001 (0.0176) 0.00025 (0.044) 0.00075 (0.132)

°F °C Cap. Power Cap. Power Cap. Power

6 3.3 0.992 0.995 0.985 0.993 0.962 0.986

8 4.4 0.995 0.997 0.988 0.995 0.965 0.988

10 5.6 1.000 1.000 0.993 0.998 0.970 0.991

12 6.7 1.005 1.002 0.998 1.000 0.975 0.993

14 6.8 1.010 1.005 1.003 1.003 0.980 0.996

16 8.9 1.014 1.007 1.007 1.005 0.984 0.998

Table 4, Condenser Adjustment FactorsFouling FactorCondenser

Water Delta-T 0.00025 (0.044 0.00075 (0.132)

°° F °° C Cap. Power Cap. Power

6 3.3 1.003 0.999 0.984 1.035

8 4.4 1.002 1.000 0.982 1.037

10 5.5 1.000 1.000 0.980 1.038

12 6.6 0.984 0.973 0.977 1.042

14 7.7 0.976 0.960 0.963 1.067

16 8.8 0.968 0.946 0.948 1.092

Page 19: Reciprocating Chillers - Daikin Applied

Product Manual WHR-2 19

Performance Data

EW Water-CooledTable 5, WHR 017EW - WHR 060EW, 60 Hz, IP Units

Entering Condenser Water Temperature (10°F Delta T.)70°F 80°F 85°F 95°F 105°F

Cap. PWR Cap. PWR Cap. PWR Cap. PWR Cap. PWRWHRSIZE

LWT(°F)

Tons kWiEER

Tons kWiEER

Tons kWiEER

Tons kWiEER

Tons kWiEER

40.0 17.8 11.7 17.1 16.9 13.1 14.7 16.5 13.7 13.7 15.6 15.0 11.8 14.6 16.3 10.242.0 18.4 11.8 17.7 17.6 13.1 15.1 17.1 13.8 14.1 16.2 15.2 12.1 15.1 16.5 10.4

017EW 44.0 19.1 11.8 18.3 18.2 13.2 15.6 17.7 13.9 14.4 16.7 15.4 12.4 15.7 16.7 10.746.0 19.8 11.9 18.7 18.9 13.3 16.0 18.3 14.0 14.8 17.3 15.5 12.6 16.3 17.0 10.948.0 20.4 11.9 19.4 19.5 13.3 16.6 19.0 14.1 15.3 18.0 15.6 13.1 16.9 17.1 11.350.0 21.2 12.0 19.9 20.1 13.5 17.0 19.6 14.2 15.7 18.6 15.8 13.4 18.1 17.4 11.740.0 21.8 15.5 16.1 20.7 17.3 13.8 20.2 18.2 12.8 19.1 19.9 11.1 17.9 21.6 9.642.0 22.6 15.6 16.6 21.5 17.4 14.2 20.9 18.3 13.2 19.8 20.1 11.3 18.6 21.8 9.8

020EW 44.0 23.4 15.7 17.1 22.3 17.5 14.6 21.7 18.4 13.5 20.5 20.3 11.6 19.3 22.1 10.146.0 24.3 15.7 17.6 23.1 17.6 15.0 22.5 18.6 13.9 21.2 20.5 11.9 20.0 22.4 10.348.0 25.1 15.8 18.2 23.9 17.7 15.5 23.3 18.7 14.3 22.0 20.7 12.3 20.7 22.6 10.650.0 26.0 15.8 18.7 24.7 17.8 15.9 24.1 18.8 14.7 22.8 20.9 12.6 22.1 23.0 10.940.0 27.1 19.6 15.9 25.8 21.9 13.7 25.1 23.0 12.7 23.8 25.2 11.0 22.3 27.4 9.542.0 28.1 19.8 16.5 26.8 22.0 14.1 26.1 23.2 13.1 24.7 25.4 11.3 23.1 27.6 9.7

025EW 44.0 29.2 19.8 17.0 27.8 22.1 14.5 27.0 23.3 13.4 25.5 25.7 11.5 24.0 28.0 10.046.0 30.2 19.9 17.4 28.8 22.3 14.9 27.9 23.5 13.7 26.3 25.9 11.8 24.8 28.4 10.248.0 31.2 19.9 18.1 29.7 22.4 15.4 28.9 23.6 14.2 27.4 26.2 12.2 25.8 28.7 10.550.0 32.4 20.1 18.6 30.7 22.6 15.8 29.9 23.8 14.6 28.4 26.5 12.5 27.5 29.1 10.940.0 30.4 21.7 16.1 28.8 24.3 13.8 28.1 25.5 12.8 26.6 27.9 11.1 24.9 30.3 9.642.0 31.4 21.9 16.6 30.0 24.4 14.2 29.1 25.7 13.2 27.6 28.1 11.3 25.8 30.6 9.8

030EW 44.0 32.6 22.0 17.1 31.0 24.5 14.6 30.2 25.8 13.5 28.5 28.5 11.6 26.8 31.0 10.146.0 33.8 22.1 17.6 32.2 24.6 15.0 31.3 26.0 13.9 29.4 28.7 11.9 27.8 31.5 10.348.0 34.9 22.1 18.2 33.2 24.8 15.5 32.4 26.2 14.3 30.7 29.0 12.3 28.8 31.7 10.650.0 36.2 22.2 18.7 34.3 25.0 15.9 33.5 26.3 14.7 31.7 29.3 12.6 30.8 32.3 10.940.0 38.8 26.8 16.8 36.6 29.7 14.3 35.5 31.1 13.3 33.5 33.9 11.5 31.3 36.6 9.942.0 40.2 27.0 17.2 38.0 30.0 14.7 36.9 31.4 13.7 35.1 34.3 11.8 32.5 37.1 10.2

040EW 44.0 41.6 27.2 17.8 39.3 30.2 15.1 38.0 31.7 14.0 35.9 34.6 12.1 33.7 37.6 10.446.0 43.1 27.5 18.3 40.8 30.5 15.5 39.6 32.0 14.4 37.3 35.0 12.5 35.0 38.0 10.648.0 44.6 27.6 18.8 42.2 30.7 16.0 41.0 32.3 15.2 38.7 35.4 12.7 36.3 38.5 11.050.0 46.1 27.7 19.3 43.7 31.0 16.5 42.5 32.6 15.2 40.0 35.8 13.0 37.5 38.9 11.340.0 44.9 30.4 17.1 42.4 33.7 14.6 41.1 35.4 13.6 38.8 38.5 11.7 36.3 41.6 10.242.0 46.5 30.7 17.6 44.0 34.0 15.0 42.7 35.6 14.0 40.7 39.0 12.0 37.6 42.1 10.4

045EW 44.0 48.2 30.9 18.2 45.5 34.3 15.4 44.0 36.0 14.3 41.6 39.3 12.4 39.1 42.7 10.746.0 49.9 31.2 18.7 47.2 34.6 15.9 45.9 36.4 14.7 43.2 39.8 12.7 40.5 43.2 10.948.0 51.6 31.3 19.2 48.8 34.9 16.4 47.5 36.7 15.5 44.8 40.2 13.0 42.0 43.7 11.250.0 53.4 31.5 19.7 50.6 35.2 16.8 49.2 37.0 15.5 46.3 40.6 13.3 43.5 44.2 11.540.0 52.5 38.1 16.0 49.6 42.3 13.7 48.2 44.3 12.7 45.4 48.2 11.0 42.4 52.1 9.542.0 54.4 38.5 16.5 51.5 42.6 14.1 50.0 44.6 13.1 47.6 48.8 11.3 44.0 52.8 9.8

050EW 44.0 56.4 38.7 17.0 53.3 43.0 14.5 51.5 45.1 13.4 48.7 49.3 11.6 45.7 53.5 10.046.0 58.5 39.1 17.5 55.3 43.3 14.9 53.7 45.6 13.8 50.5 49.8 11.9 47.4 54.1 10.248.0 60.4 39.2 18.0 57.2 43.7 15.3 55.6 46.0 14.5 52.4 50.4 12.2 49.2 54.8 10.550.0 62.5 39.5 18.5 59.2 44.1 15.7 57.6 46.4 14.5 54.2 50.9 12.5 50.9 55.4 10.840.0 59.7 41.4 16.8 56.3 45.9 14.3 54.7 48.1 13.3 51.5 52.4 11.5 48.2 56.6 9.942.0 61.8 41.8 17.2 58.5 46.3 14.7 56.7 48.5 13.7 54.1 53.0 11.8 50.0 57.3 10.2

060EW 44.0 64.1 42.0 17.8 60.5 46.7 15.1 58.5 49.0 14.0 55.3 53.6 12.1 51.9 58.1 10.446.0 66.4 42.4 18.3 62.8 47.1 15.5 61.0 49.5 14.4 57.4 54.1 12.5 53.8 58.8 10.648.0 68.6 42.6 18.8 64.9 47.5 16.0 63.2 50.0 15.2 59.6 54.7 12.7 55.9 59.5 11.050.0 71.0 42.9 19.3 67.2 47.9 16.5 65.4 50.4 15.2 61.6 55.3 13.0 57.8 60.2 11.3

Notes:1. Bold box areas certified in accordance with ARI Standard 550/590-98.2. Ratings based on HCFC-22, evaporator fouling of 0.0001, 2.4 gpm/ton; condenser fouling of 0.00025, 3 gpm/ton.3. For 208V units multiply capacity and EER by 0.98.4. Ratings are based on circuit #1 in lead position and circuit #2 in lag position.5. Interpolation is allowed; extrapolation is not permitted. Consult McQuay for performance outside the ratings shown.6. For LWT of 40°F and below please refer to Application Adjustment Factors section.

Page 20: Reciprocating Chillers - Daikin Applied

20 Product Manual WHR-2

Table 6, WHR 070EW - WHR 120EW, 60 Hz, IP UnitsEntering Condenser Water Temperature (10°F Delta T.)

70°F 80°F 85°F 95°F 105°FCap. PWR Cap. PWR Cap. PWR Cap. PWR Cap. PWR

WHRSIZE

LWT(°F)

Tons kWiEER

Tons kWiEER

Tons kWiEER

Tons kWiEER

Tons kWiEER

40.0 71.9 52.8 16.0 67.9 58.5 13.7 65.9 61.3 12.7 62.1 66.7 11.0 58.1 72.1 9.542.0 74.5 53.2 16.5 70.5 59.0 14.1 68.4 61.8 13.1 65.1 67.5 11.3 60.3 73.0 9.8

070EW 44.0 77.2 53.5 17.0 73.0 59.5 14.5 70.5 62.4 13.4 66.7 68.2 11.6 62.6 74.0 10.046.0 80.0 54.0 17.5 75.6 60.0 14.9 73.5 63.0 13.8 69.2 69.0 11.9 64.9 74.9 10.248.0 82.7 54.3 18.0 78.3 60.5 15.3 76.1 63.6 14.5 71.8 69.7 12.2 67.3 75.8 10.550.0 85.5 54.6 18.5 81.0 61.0 15.7 78.8 64.2 14.5 74.2 70.4 12.5 69.7 76.6 10.840.0 78.0 57.4 15.9 73.7 63.6 13.6 71.5 66.7 12.6 67.4 72.6 10.9 63.0 78.4 9.442.0 80.9 57.9 16.4 76.5 64.2 14.0 74.2 67.2 13.0 70.7 73.5 11.2 65.4 79.4 9.7

080EW 44.0 83.8 58.2 16.9 79.2 64.8 14.4 76.5 67.9 13.3 72.4 74.2 11.5 67.9 80.6 9.946.0 86.8 58.8 17.4 82.1 65.3 14.8 79.8 68.6 13.7 75.0 75.0 11.8 70.4 81.5 10.148.0 89.7 59.1 17.8 84.9 65.9 15.2 82.6 69.3 14.4 77.9 75.8 12.1 73.1 82.5 10.450.0 92.8 59.4 18.4 87.9 66.4 15.6 85.5 69.9 14.4 80.6 76.6 12.4 75.6 83.4 10.740.0 86.7 61.4 16.6 81.9 68.0 14.2 79.5 71.3 13.2 74.9 77.6 11.4 70.0 83.9 9.942.0 89.8 61.9 17.1 85.0 68.6 14.6 82.5 71.9 13.6 78.5 78.6 11.7 72.7 84.9 10.1

085EW 44.0 93.1 62.2 17.7 88.0 69.3 15.0 85.0 72.6 13.9 80.4 79.4 12.0 75.5 86.1 10.446.0 96.5 62.9 18.1 91.2 69.8 15.4 88.7 73.3 14.3 83.4 80.2 12.4 78.2 87.1 10.648.0 99.7 63.2 18.6 94.4 70.4 15.9 91.8 74.1 15.1 86.5 81.1 12.6 81.2 88.2 10.950.0 103.1 63.5 19.2 97.7 71.0 16.3 95.0 74.7 15.1 89.5 81.9 12.9 84.0 89.2 11.240.0 93.3 64.6 17.0 88.1 71.6 14.5 85.6 75.0 13.5 80.6 81.7 11.6 75.4 88.2 10.142.0 96.7 65.2 17.5 91.5 72.2 14.9 88.8 75.6 13.9 84.5 82.7 11.9 78.2 89.4 10.4

090EW 44.0 100.2 65.5 18.0 94.7 72.9 15.3 91.5 76.4 14.2 86.6 83.5 12.3 81.3 90.6 10.646.0 103.9 66.2 18.5 98.2 73.4 15.8 95.4 77.2 14.6 89.8 84.4 12.6 84.2 91.7 10.848.0 107.3 66.5 19.0 101.6 74.1 16.3 98.8 77.9 15.4 93.1 85.3 12.9 87.4 92.8 11.150.0 111.0 66.9 19.6 105.1 74.7 16.7 102.3 78.6 15.4 96.3 86.2 13.2 90.4 93.8 11.440.0 96.9 68.4 16.7 91.8 76.3 14.2 89.2 80.2 13.2 84.3 87.9 11.3 79.2 95.5 9.842.0 100.3 68.7 17.2 95.2 76.7 14.7 92.5 80.7 13.6 87.5 88.7 11.6 82.2 96.5 10.1

095EW 44.0 104.0 68.9 17.9 98.7 77.2 15.1 96.0 81.3 14.0 90.6 89.5 12.0 85.0 97.4 10.446.0 107.6 69.1 18.5 102.1 77.5 15.6 99.5 81.8 14.4 94.0 90.2 12.4 88.5 98.5 10.648.0 111.5 69.3 19.0 105.8 77.9 16.0 103.6 82.1 15.1 97.2 90.9 12.7 92.6 98.8 11.050.0 115.2 69.3 19.7 109.4 78.2 16.5 106.4 82.7 15.3 100.7 91.5 13.0 95.0 99.6 11.340.0 102.9 72.7 16.7 97.5 81.0 14.2 94.8 85.3 13.2 89.6 93.4 11.3 84.1 101.5 9.842.0 106.6 73.0 17.2 101.2 81.6 14.7 98.3 85.8 13.6 92.9 94.3 11.6 87.3 102.6 10.1

100EW 44.0 110.5 73.2 17.9 104.9 82.0 15.1 102.0 86.4 14.0 96.3 95.1 12.0 90.3 103.6 10.446.0 114.3 73.4 18.5 108.5 82.3 15.6 105.7 86.9 14.4 99.9 95.8 12.4 94.0 104.6 10.648.0 118.4 73.6 19.0 112.4 82.8 16.0 110.1 87.3 15.1 103.3 96.6 12.7 98.4 105.0 11.050.0 122.4 73.7 19.7 116.3 83.1 16.5 113.0 87.9 15.3 107.0 97.3 13.0 101.0 105.8 11.340.0 112.5 80.7 16.5 106.6 90.0 14.0 103.6 94.7 13.0 97.9 103.7 11.2 91.9 112.7 9.742.0 116.5 81.0 17.0 110.6 90.5 14.5 107.5 95.2 13.4 101.6 104.6 11.5 95.4 113.8 9.9

110EW 44.0 120.8 81.2 17.6 114.6 91.0 14.9 111.5 95.9 13.8 105.3 105.6 11.8 98.7 114.9 10.246.0 125.0 81.5 18.2 118.6 91.4 15.4 115.5 96.5 14.2 109.2 106.4 12.2 102.8 116.1 10.548.0 129.5 81.7 18.8 122.9 91.9 15.8 120.4 96.9 14.9 112.9 107.2 12.5 107.6 116.6 10.850.0 133.8 81.8 19.4 127.1 92.3 16.3 123.5 97.5 15.1 116.9 108.0 12.8 110.4 117.5 11.240.0 114.5 80.7 16.7 108.5 90.0 14.2 105.5 94.8 13.2 99.7 103.8 11.3 93.6 112.8 9.842.0 118.6 81.1 17.2 112.6 90.6 14.7 109.4 95.3 13.6 103.4 104.7 11.6 97.2 114.0 10.1

115EW 44.0 122.9 81.3 17.9 116.7 91.1 15.1 113.5 96.0 14.0 107.1 105.7 12.0 100.4 115.1 10.446.0 127.2 81.6 18.5 120.8 91.5 15.6 117.6 96.6 14.4 111.1 106.5 12.4 104.6 116.3 10.648.0 131.8 81.8 19.0 125.1 92.0 16.0 122.5 97.0 15.1 115.0 107.3 12.7 109.5 116.7 11.050.0 136.2 81.9 19.7 129.4 92.4 16.5 125.8 97.6 15.3 119.0 108.1 13.0 112.4 117.6 11.340.0 123.1 88.6 16.5 116.6 98.8 14.0 113.4 103.9 13.0 107.1 113.8 11.2 100.6 123.7 9.742.0 127.5 89.0 17.0 121.0 99.4 14.5 117.6 104.6 13.4 111.1 114.9 11.5 104.4 125.0 9.9

120EW 44.0 132.1 89.2 17.6 125.4 99.9 14.9 122.0 105.3 13.8 115.2 115.9 11.8 108.0 126.2 10.246.0 136.8 89.5 18.2 129.8 100.4 15.4 126.4 105.9 14.2 119.4 116.8 12.2 112.5 127.5 10.548.0 141.6 89.7 18.8 134.4 100.9 15.8 131.7 106.4 14.9 123.6 117.7 12.5 117.7 128.0 10.850.0 146.4 89.8 19.4 139.1 101.3 16.3 135.2 107.1 15.1 128.0 118.6 12.8 120.8 129.0 11.2

Notes:1. Bold box areas certified in accordance with ARI Standard 550/590-98.2. Ratings based on HCFC-22, evaporator fouling of 0.0001, 2.4 gpm/ton; condenser fouling of 0.00025, 3 gpm/ton.3. For 208V units multiply capacity and EER by 0.98.4. Ratings are based on circuit #1 in lead position and circuit #2 in lag position.5. Interpolation is allowed; extrapolation is not permitted. Consult McQuay for performance outside the ratings shown.6. For LWT of 40°F and below please refer to Application Adjustment Factors section.

Page 21: Reciprocating Chillers - Daikin Applied

Product Manual WHR-2 21

Table 7, WHR 130EW - WHR 210EW, 60 Hz, IP UnitsEntering Condenser Water Temperature (10°F Delta T.)

70°F 80°F 85°F 95°F 105°F

Cap. PWR Cap. PWR Cap. PWR Cap. PWR Cap. PWRWHRSIZE

LWT°F

Tons kWiEER

Tons kWiEER

Tons kWiEER

Tons kWiEER

Tons kWiEER

40.0 133.2 98.4 16.0 126.2 109.7 13.6 122.7 115.5 12.6 115.9 126.5 10.9 108.8 137.5 9.442.0 137.9 98.9 16.5 130.9 110.4 14.1 127.2 116.2 13.0 120.3 127.6 11.1 113.0 138.9 9.6

130EW 44.0 143.0 99.1 17.1 135.7 111.0 14.5 132.0 117.0 13.4 124.6 128.8 11.5 116.8 140.2 9.9

46.0 148.0 99.5 17.7 140.4 111.5 14.9 136.8 117.7 13.8 129.2 129.8 11.9 121.7 141.7 10.248.0 153.3 99.7 18.2 145.5 112.1 15.3 142.5 118.2 14.5 133.7 130.8 12.1 127.4 142.2 10.550.0 158.4 99.8 18.8 150.5 112.6 15.8 146.3 119.0 14.7 138.4 131.7 12.5 130.7 143.3 10.9

40.0 145.3 101.8 17.0 137.7 113.6 14.4 133.8 119.5 13.3 126.4 130.9 11.5 118.7 142.3 9.942.0 150.5 102.3 17.5 142.8 114.3 14.9 138.8 120.3 13.8 131.2 132.1 11.8 123.3 143.7 10.2

145EW 44.0 156.0 102.6 18.1 148.0 114.9 15.3 144.0 121.1 14.2 135.9 133.3 12.1 127.4 145.1 10.5

46.0 161.4 102.9 18.7 153.2 115.4 15.8 149.2 121.8 14.6 141.0 134.3 12.6 132.8 146.7 10.848.0 167.2 103.2 19.3 158.7 116.0 16.3 155.4 122.3 15.3 145.9 135.4 12.9 139.0 147.2 11.150.0 172.8 103.3 20.0 164.2 116.5 16.8 159.6 123.2 15.5 151.0 136.4 13.2 142.6 148.3 11.5

40.0 151.9 109.9 16.4 143.9 122.6 13.9 139.9 129.0 12.9 132.1 141.3 11.1 124.1 153.6 9.642.0 157.3 110.4 16.9 149.3 123.4 14.4 145.1 129.8 13.3 137.1 142.6 11.4 128.8 155.1 9.9

155EW 44.0 163.0 110.7 17.5 154.7 124.0 14.8 150.5 130.7 13.7 142.1 143.9 11.7 133.2 156.6 10.1

46.0 168.7 111.1 18.1 160.1 124.6 15.3 155.9 131.5 14.1 147.3 144.9 12.1 138.8 158.3 10.448.0 174.7 111.4 18.6 165.9 125.2 15.7 162.5 132.0 14.8 152.5 146.1 12.4 145.2 158.9 10.850.0 180.6 111.5 19.2 171.6 125.7 16.2 166.8 132.9 15.0 157.8 147.2 12.7 149.0 160.1 11.1

40.0 164.5 118.8 16.5 155.8 132.5 14.0 151.5 139.5 13.0 143.1 152.7 11.2 134.4 166.0 9.742.0 170.3 119.4 17.0 161.7 133.4 14.5 157.1 140.3 13.4 148.5 154.2 11.5 139.5 167.7 9.9

165EW 44.0 176.5 119.7 17.6 167.6 134.1 14.9 163.0 141.3 13.8 153.9 155.6 11.8 144.3 169.3 10.2

46.0 182.7 120.1 18.2 173.4 134.7 15.4 168.9 142.1 14.2 159.6 156.7 12.2 150.3 171.1 10.548.0 189.2 120.4 18.8 179.6 135.4 15.8 176.0 142.7 14.9 165.1 158.0 12.5 157.3 171.8 10.850.0 195.6 120.5 19.4 185.8 135.9 16.3 180.6 143.7 15.1 171.0 159.1 12.8 161.4 173.1 11.2

40.0 178.6 130.3 16.3 169.2 145.3 13.8 164.5 152.9 12.8 155.4 167.4 11.0 145.9 182.0 9.542.0 185.0 130.9 16.7 175.6 146.2 14.3 170.6 153.8 13.2 161.2 169.0 11.3 151.5 183.9 9.8

175EW 44.0 191.7 131.2 17.3 182.0 147.0 14.7 177.0 154.9 13.6 167.1 170.5 11.6 156.6 185.6 10.1

46.0 198.4 131.7 18.0 188.3 147.6 15.2 183.4 155.8 14.0 173.3 171.8 12.0 163.2 187.6 10.348.0 205.5 132.0 18.5 195.1 148.4 15.6 191.1 156.4 14.7 179.3 173.2 12.3 170.8 188.3 10.750.0 212.4 132.1 19.1 201.8 149.0 16.0 196.1 157.5 14.9 185.6 174.4 12.6 175.2 189.8 11.0

40.0 186.7 130.4 17.0 176.9 145.4 14.4 172.0 153.0 13.3 162.4 167.6 11.5 152.5 182.1 9.942.0 193.3 131.0 17.5 183.5 146.3 14.9 178.3 153.9 13.8 168.5 169.1 11.8 158.4 184.0 10.2

185EW 44.0 200.4 131.3 18.1 190.2 147.1 15.3 185.0 155.0 14.2 174.6 170.7 12.1 163.7 185.8 10.5

46.0 207.4 131.8 18.7 196.8 147.7 15.8 191.7 155.9 14.6 181.1 171.9 12.6 170.6 187.7 10.848.0 214.8 132.1 19.3 203.9 148.5 16.3 199.7 156.6 15.3 187.4 173.3 12.9 178.5 188.4 11.150.0 222.0 132.2 20.0 210.9 149.1 16.8 205.0 157.6 15.5 194.0 174.5 13.2 183.2 189.9 11.5

40.0 198.8 141.4 16.7 188.3 157.7 14.2 183.1 165.9 13.2 173.0 181.7 11.3 162.4 197.5 9.842.0 205.9 142.0 17.2 195.4 158.7 14.7 189.9 166.9 13.6 179.5 183.4 11.6 168.6 199.5 10.1

195EW 44.0 213.4 142.4 17.9 202.5 159.5 15.1 197.0 168.1 14.0 186.0 185.1 12.0 174.3 201.5 10.4

46.0 220.8 142.9 18.5 209.6 160.2 15.6 204.1 169.1 14.4 192.9 186.4 12.4 181.6 203.6 10.648.0 228.7 143.2 19.0 217.1 161.0 16.0 212.7 169.8 15.1 199.6 187.9 12.7 190.1 204.3 11.050.0 236.4 143.4 19.7 224.6 161.7 16.5 218.3 171.0 15.3 206.6 189.3 13.0 195.0 205.9 11.3

40.0 212.9 150.7 16.8 201.7 168.1 14.3 196.1 176.9 13.3 185.3 193.7 11.4 174.0 210.6 9.942.0 220.5 151.4 17.3 209.3 169.2 14.8 203.4 177.9 13.7 192.2 195.5 11.7 180.6 212.7 10.2

210EW 44.0 228.5 151.8 18.0 216.9 170.1 15.2 211.0 179.2 14.1 199.2 197.3 12.1 186.7 214.8 10.4

46.0 236.5 152.3 18.6 224.5 170.8 15.7 218.6 180.3 14.5 206.6 198.7 12.5 194.5 217.0 10.748.0 245.0 152.7 19.2 232.5 171.7 16.1 227.8 181.0 15.2 213.7 200.3 12.8 203.6 217.8 11.150.0 253.2 152.9 19.8 240.5 172.4 16.6 233.8 182.2 15.4 221.3 201.8 13.1 208.9 219.5 11.4

Notes:1. Bold box areas certified in accordance with ARI Standard 550/590-98.2. Ratings based on HCFC-22, evaporator fouling of 0.0001, 2.4 gpm/ton; condenser fouling of 0.00025, 3 gpm/ton.3. For 208V units multiply capacity and EER by 0.984. Ratings are based on circuit #1 in lead position and circuit #2 in lag position.5. Interpolation is allowed; extrapolation is not permitted. Consult McQuay for performance outside the ratings shown.6. For LWT of 40°F and below please refer to Application Adjustment Factors section.

Page 22: Reciprocating Chillers - Daikin Applied

22 Product Manual WHR-2

Table 8, WHR 017EW - WHR 060EW, 60 Hz, SI UnitsEntering Condenser Water Temperature (°C)

20°C (68°F) 25°C (77°F) 30°C (86°F) 35°C (95°F) 40°C (104°F)

Cap. PWR Cap. PWR Cap. PWR Cap. PWR Cap. PWRWHRSIZE

LWT°C

kW kWiCOP

kW kWiCOP

kW kWiCOP

kW kWiCOP

kW kWiCOP

5.0 (41.0°F) 64.5 11.4 5.1 61.7 12.7 4.5 58.5 13.9 3.9 54.7 15.0 3.4 52.8 16.3 2.96.0 (42.8°F) 66.8 11.5 5.3 63.6 12.8 4.7 60.8 14.1 4.1 56.8 15.2 3.4 54.3 16.5 3.0

017EW 7.0 (44.6°F) 69.1 11.6 5.5 65.3 12.8 4.8 63.1 14.1 4.1 58.8 15.3 3.6 56.5 16.7 3.18.0 (46.4°F) 70.2 11.6 5.5 67.0 12.9 4.8 64.0 14.2 4.2 60.8 15.5 3.7 57.6 16.7 3.29.0 (48.2°F) 72.8 11.6 5.8 69.4 12.9 5.0 67.7 14.3 4.4 63.1 15.6 3.8 59.7 16.9 3.2

10.0 (50.0°F) 75.1 11.7 6.0 72.0 13.0 5.1 68.5 14.4 4.4 65.4 15.8 3.9 61.9 17.1 3.4

5.0 (41.0°F) 79.1 15.2 4.9 75.6 16.8 4.3 71.7 18.4 3.7 67.1 19.9 3.2 64.7 21.5 2.86.0 (42.8°F) 81.9 15.3 5.0 78.0 16.9 4.4 74.5 18.6 3.8 69.6 20.1 3.3 66.6 21.8 2.9

020EW 7.0 (44.6°F) 84.7 15.3 5.2 80.1 17.0 4.5 77.3 18.7 3.9 72.1 20.3 3.4 69.3 22.1 3.08.0 (46.4°F) 86.1 15.3 5.3 82.2 17.0 4.6 78.4 18.8 4.0 74.5 20.5 3.5 70.6 22.2 3.09.0 (48.2°F) 89.2 15.4 5.5 85.1 17.1 4.7 83.0 18.9 4.1 77.4 20.7 3.6 73.1 22.4 3.1

10.0 (50.0°F) 92.1 15.4 5.7 88.3 17.2 4.9 84.0 19.0 4.2 80.2 20.9 3.7 75.9 22.6 3.2

5.0 (41.0°F) 98.4 19.2 4.8 94.1 21.3 4.1 89.2 23.3 3.6 83.5 25.1 3.1 80.5 27.3 2.76.0 (42.8°F) 101.9 19.3 4.9 97.1 21.4 4.3 92.7 23.6 3.7 86.6 25.4 3.2 82.8 27.7 2.8

025EW 7.0 (44.6°F) 105.4 19.4 5.1 99.7 21.5 4.4 96.2 23.7 3.8 89.7 25.7 3.3 86.2 28.0 2.98.0 (46.4°F) 107.2 19.4 5.1 102.3 21.6 4.5 97.6 23.8 3.9 92.7 25.9 3.4 87.8 28.1 3.09.0 (48.2°F) 111.0 19.5 5.3 105.9 21.7 4.6 103.3 24.0 4.0 96.3 26.2 3.5 91.0 28.3 3.0

10.0 (50.0°F) 114.5 19.6 5.6 109.9 21.8 4.8 104.6 24.1 4.1 99.8 26.5 3.6 94.4 28.6 3.1

5.0 (41.0°F) 110.0 21.2 4.9 105.2 23.6 4.3 99.8 25.8 3.7 93.4 27.8 3.2 90.1 30.2 2.86.0 (42.8°F) 113.9 21.4 5.0 108.6 23.7 4.4 103.7 26.1 3.8 96.9 28.1 3.3 92.6 30.6 2.9

030EW 7.0 (44.6°F) 117.8 21.5 5.2 111.5 23.8 4.5 107.6 26.2 3.9 100.3 28.4 3.4 96.4 31.0 3.08.0 (46.4°F) 119.9 21.5 5.3 114.4 23.9 4.6 109.1 26.4 4.0 103.7 28.7 3.5 98.2 31.1 3.09.0 (48.2°F) 124.2 21.5 5.5 118.4 24.0 4.7 115.5 26.5 4.1 107.7 29.0 3.6 101.8 31.4 3.1

10.0 (50.0°F) 128.1 21.7 5.7 122.9 24.2 4.9 117.0 26.7 4.2 111.6 29.3 3.7 105.6 31.7 3.2

5.0 (41.0°F) 140.1 26.4 5.1 134.7 28.8 4.4 127.7 31.1 4.0 119.8 34.1 3.3 112.9 36.6 3.06.0 (42.8°F) 145.4 26.5 5.3 138.3 29.0 4.6 131.1 31.9 4.0 124.2 34.5 3.5 117.3 37.0 3.1

040EW 7.0 (44.6°F) 150.4 26.7 5.4 143.0 29.0 4.7 136.0 32.1 4.1 128.8 34.9 3.6 121.7 37.5 3.28.0 (46.4°F) 152.9 26.8 5.5 145.9 29.1 4.8 138.5 32.3 4.2 131.3 35.0 3.7 123.7 37.7 3.29.0 (48.2°F) 158.4 26.9 5.7 150.8 29.3 4.9 143.3 32.6 4.3 136.0 35.4 3.7 128.3 38.2 3.3

10.0 (50.0°F) 163.7 27.1 5.9 156.2 29.5 5.1 148.4 32.9 4.4 140.7 35.8 3.8 133.0 38.6 3.3

5.0 (41.0°F) 162.2 29.9 5.2 156.0 32.7 4.5 147.9 35.4 4.1 138.7 38.7 3.4 130.7 41.5 3.16.0 (42.8°F) 168.3 30.0 5.4 160.1 32.9 4.7 151.8 36.2 4.1 143.8 39.2 3.6 135.8 42.0 3.1

045EW 7.0 (44.6°F) 174.2 30.3 5.5 165.6 33.0 4.8 157.5 36.5 4.2 149.1 39.6 3.7 140.9 42.6 3.28.0 (46.4°F) 177.1 30.4 5.7 168.9 33.1 4.9 160.4 36.7 4.2 152.0 39.8 3.7 143.3 42.8 3.39.0 (48.2°F) 183.4 30.6 5.9 174.6 33.3 5.0 165.9 37.0 4.4 157.5 40.2 3.8 148.6 43.4 3.3

10.0 (50.0°F) 189.6 30.7 6.1 180.8 33.5 5.2 171.8 37.4 4.5 162.9 40.6 3.9 154.0 43.9 3.4

5.0 (41.0°F) 189.8 37.5 4.9 182.6 41.0 4.2 173.1 44.3 3.8 162.3 48.5 3.2 153.0 52.0 2.96.0 (42.8°F) 197.0 37.6 5.1 187.4 41.2 4.4 177.7 45.3 3.9 168.3 49.1 3.4 158.9 52.7 3.0

050EW 7.0 (44.6°F) 203.9 38.0 5.2 193.9 41.3 4.5 184.4 45.7 3.9 174.6 49.6 3.4 164.9 53.3 3.08.0 (46.4°F) 207.3 38.1 5.3 197.7 41.5 4.6 187.7 45.9 4.0 177.9 49.9 3.5 167.7 53.7 3.19.0 (48.2°F) 214.7 38.3 5.5 204.4 41.7 4.7 194.2 46.4 4.1 184.4 50.4 3.6 173.9 54.3 3.1

10.0 (50.0°F) 221.9 38.5 5.7 211.6 42.0 4.9 201.1 46.8 4.2 190.7 50.9 3.7 180.3 54.9 3.2

5.0 (41.0°F) 215.6 40.7 5.1 207.4 44.5 4.4 196.7 48.1 4.0 184.4 52.7 3.3 173.8 56.5 3.06.0 (42.8°F) 223.8 40.9 5.3 212.9 44.8 4.6 201.9 49.2 4.1 191.1 53.3 3.5 180.5 57.2 3.1

060EW 7.0 (44.6°F) 231.6 41.3 5.4 220.2 44.9 4.7 209.4 49.7 4.1 198.3 53.9 3.6 187.3 57.9 3.28.0 (46.4°F) 235.4 41.4 5.6 224.6 45.0 4.8 213.2 49.9 4.2 202.1 54.2 3.7 190.5 58.3 3.29.0 (48.2°F) 243.9 41.6 5.8 232.1 45.3 4.9 220.6 50.4 4.3 209.4 54.7 3.7 197.5 59.0 3.3

10.0 (50.0°F) 252.1 41.8 5.9 240.4 45.6 5.1 228.4 50.9 4.4 216.6 55.3 3.9 204.8 59.7 3.3

Notes:1. Ratings based on HCFC-22, evaporator fouling of 0.0176, 0.043 L/s; condenser fouling of 0.044.2. For 208V units multiply capacity and COP by 0.98.3. Ratings are based on circuit #1 in lead position and circuit #2 in lag position.4. Interpolation is allowed; extrapolation is not permitted. Consult McQuay for performance outside the ratings shown.5. For LWT of 5°C and below please refer to Application Adjustment Factors section.

Page 23: Reciprocating Chillers - Daikin Applied

Product Manual WHR-2 23

Table 9, WHR 070EW - WHR 120EW, 60 Hz, SI UnitsEntering Condenser Water Temperature (°C)

20°C (68°F) 25°C (77°F) 30°C (86°F) 35°C (95°F) 40°C (104°F)Cap. PWR Cap. PWR Cap. PWR Cap. PWR Cap. PWR

WHRSIZE

LWT°C

kW kWiCOP

kW kWiCOP

kW kWiCOP

kW kWiCOP

kW kWiCOP

5.0 (41.0°F) 259.8 51.9 4.9 249.9 56.7 4.2 237.0 61.3 3.8 222.2 67.1 3.2 209.5 72.0 2.96.0 (42.8°F) 269.7 52.1 5.1 256.6 57.0 4.4 243.3 62.7 3.8 230.3 67.9 3.3 217.6 72.9 2.9

070EW 7.0 (44.6°F) 279.1 52.6 5.2 265.4 57.2 4.5 252.4 63.3 3.9 239.0 68.6 3.4 225.7 73.8 3.08.0 (46.4°F) 283.7 52.7 5.3 270.7 57.4 4.5 257.0 63.6 4.0 243.5 69.0 3.5 229.6 74.3 3.09.0 (48.2°F) 293.9 53.0 5.5 279.8 57.7 4.7 265.8 64.2 4.1 252.4 69.7 3.6 238.0 75.2 3.1

10.0 (50.0°F) 303.8 53.3 5.6 289.7 58.1 4.8 275.3 64.8 4.2 261.0 70.4 3.7 246.8 76.0 3.25.0 (41.0°F) 282.0 56.4 4.9 271.2 61.7 4.2 257.2 66.7 3.8 241.1 73.0 3.1 227.3 78.4 2.86.0 (42.8°F) 292.7 56.7 5.1 278.4 62.0 4.4 264.0 68.2 3.8 250.0 73.9 3.3 236.1 79.3 2.9

080EW 7.0 (44.6°F) 302.9 57.2 5.2 288.0 62.2 4.5 273.9 68.9 3.9 259.3 74.7 3.4 244.9 80.3 3.08.0 (46.4°F) 307.9 57.4 5.3 293.7 62.4 4.5 278.8 69.2 4.0 264.3 75.1 3.5 249.1 80.8 3.09.0 (48.2°F) 318.9 57.7 5.5 303.6 62.8 4.7 288.5 69.8 4.1 273.9 75.8 3.5 258.3 81.8 3.1

10.0 (50.0°F) 329.6 58.0 5.6 314.4 63.2 4.8 298.7 70.5 4.2 283.2 76.6 3.7 267.8 82.7 3.15.0 (41.0°F) 313.3 60.4 5.1 301.3 65.9 4.4 285.7 71.3 3.9 267.9 78.0 3.3 252.5 83.8 3.06.0 (42.8°F) 325.2 60.6 5.3 309.3 66.3 4.6 293.3 73.0 4.0 277.7 79.0 3.5 262.3 84.8 3.0

085EW 7.0 (44.6°F) 336.5 61.2 5.4 320.0 66.5 4.6 304.3 73.6 4.0 288.1 79.8 3.5 272.2 85.8 3.18.0 (46.4°F) 342.1 61.3 5.5 326.3 66.7 4.7 309.8 73.9 4.1 293.6 80.3 3.6 276.8 86.4 3.29.0 (48.2°F) 354.3 61.7 5.7 337.3 67.2 4.9 320.5 74.6 4.3 304.3 81.1 3.7 287.0 87.5 3.2

10.0 (50.0°F) 366.2 62.0 5.9 349.3 67.6 5.0 331.9 75.3 4.3 314.7 81.9 3.8 297.5 88.4 3.35.0 (41.0°F) 337.2 63.5 5.2 324.4 69.4 4.5 307.6 75.1 4.0 288.4 82.1 3.3 271.9 88.2 3.06.0 (42.8°F) 350.1 63.8 5.4 333.0 69.8 4.7 315.7 76.8 4.1 299.0 83.2 3.5 282.4 89.2 3.1

090EW 7.0 (44.6°F) 362.2 64.4 5.5 344.4 70.0 4.8 327.6 77.5 4.1 310.1 84.0 3.6 293.0 90.3 3.28.0 (46.4°F) 368.2 64.5 5.6 351.3 70.2 4.8 333.5 77.8 4.2 316.1 84.5 3.7 297.9 90.9 3.29.0 (48.2°F) 381.4 64.9 5.8 363.1 70.7 5.0 345.0 78.6 4.4 327.6 85.3 3.8 309.0 92.0 3.3

10.0 (50.0°F) 394.3 65.2 6.0 376.0 71.1 5.1 357.3 79.3 4.4 338.8 86.2 3.9 320.3 93.1 3.35.0 (41.0°F) 350.2 66.9 5.1 334.0 74.2 4.4 317.8 81.3 3.9 301.8 88.3 3.3 285.5 95.1 3.06.0 (42.8°F) 363.0 67.2 5.3 346.0 74.5 4.6 329.8 81.8 3.9 312.8 89.1 3.5 296.3 96.2 3.1

095EW 7.0 (44.6°F) 375.7 67.3 5.5 358.6 74.8 4.7 341.7 82.4 4.1 324.4 89.8 3.6 307.7 97.1 3.18.0 (46.4°F) 382.3 67.4 5.6 365.0 75.0 4.8 347.8 82.6 4.1 330.4 90.2 3.6 313.2 97.6 3.29.0 (48.2°F) 395.7 67.5 5.8 377.1 75.2 4.9 362.4 83.1 4.3 342.1 90.9 3.7 324.7 98.5 3.2

10.0 (50.0°F) 409.2 67.6 6.0 390.9 75.6 5.1 372.7 83.5 4.4 354.0 91.5 3.8 336.1 99.4 3.35.0 (41.0°F) 372.1 71.1 5.1 354.8 78.9 4.4 337.7 86.4 3.9 320.7 93.9 3.3 303.4 101.1 3.06.0 (42.8°F) 385.7 71.4 5.3 367.7 79.2 4.6 350.4 87.0 3.9 332.4 94.7 3.5 314.8 102.2 3.1

100EW 7.0 (44.6°F) 399.2 71.6 5.5 381.0 79.5 4.7 363.0 87.6 4.1 344.7 95.4 3.6 326.9 103.2 3.18.0 (46.4°F) 406.2 71.6 5.6 387.8 79.7 4.8 369.6 87.8 4.1 351.0 95.8 3.6 332.7 103.7 3.29.0 (48.2°F) 420.4 71.7 5.8 400.6 80.0 4.9 385.1 88.3 4.3 363.5 96.6 3.7 345.0 104.7 3.2

10.0 (50.0°F) 434.7 71.8 6.0 415.3 80.4 5.1 396.0 88.8 4.4 376.1 97.3 3.8 357.1 105.7 3.35.0 (41.0°F) 406.8 78.9 5.1 387.9 87.5 4.4 369.1 95.9 3.9 350.6 104.2 3.3 331.6 112.2 2.96.0 (42.8°F) 421.6 79.3 5.2 401.9 87.9 4.5 383.0 96.5 3.9 363.3 105.1 3.4 344.1 113.5 3.0

110EW 7.0 (44.6°F) 436.4 79.4 5.4 416.5 88.2 4.6 396.8 97.2 4.0 376.8 105.9 3.5 357.4 114.6 3.18.0 (46.4°F) 444.1 79.5 5.5 423.9 88.4 4.7 404.0 97.5 4.1 383.7 106.4 3.6 363.7 115.1 3.19.0 (48.2°F) 459.6 79.6 5.7 437.9 88.8 4.9 421.0 98.0 4.2 397.3 107.2 3.7 377.1 116.2 3.2

10.0 (50.0°F) 475.2 79.7 5.9 454.0 89.2 5.0 432.9 98.5 4.3 411.2 108.0 3.8 390.4 117.3 3.35.0 (41.0°F) 414.1 79.0 5.2 394.9 87.6 4.5 375.7 96.0 3.9 356.8 104.3 3.3 337.6 112.3 3.06.0 (42.8°F) 429.2 79.3 5.3 409.1 88.0 4.6 389.9 96.6 4.0 369.9 105.2 3.5 350.3 113.6 3.1

115EW 7.0 (44.6°F) 444.2 79.5 5.5 424.0 88.3 4.7 403.9 97.3 4.1 383.5 106.0 3.6 363.8 114.7 3.28.0 (46.4°F) 452.0 79.6 5.6 431.5 88.5 4.8 411.2 97.6 4.2 390.6 106.5 3.7 370.2 115.2 3.29.0 (48.2°F) 467.8 79.7 5.8 445.8 88.9 5.0 428.5 98.2 4.3 404.4 107.3 3.7 383.8 116.3 3.2

10.0 (50.0°F) 483.7 79.8 6.0 462.2 89.3 5.1 440.6 98.6 4.4 418.5 108.1 3.8 397.4 117.4 3.35.0 (41.0°F) 445.1 86.7 5.1 424.4 96.1 4.4 403.9 105.3 3.8 383.6 114.4 3.3 362.8 123.2 2.96.0 (42.8°F) 461.3 87.0 5.2 439.8 96.5 4.5 419.1 106.0 3.9 397.6 115.4 3.4 376.6 124.6 3.0

120EW 7.0 (44.6°F) 477.5 87.2 5.4 455.7 96.9 4.6 434.2 106.7 4.0 412.2 116.3 3.5 391.0 125.8 3.18.0 (46.4°F) 485.9 87.3 5.5 463.8 97.1 4.7 442.0 107.0 4.1 419.8 116.8 3.6 398.0 126.4 3.19.0 (48.2°F) 502.8 87.4 5.7 479.2 97.5 4.9 460.6 107.7 4.2 434.7 117.7 3.7 412.6 127.6 3.2

10.0 (50.0°F) 520.0 87.5 5.9 496.8 97.9 5.0 473.6 108.2 4.3 449.9 118.6 3.8 427.2 128.8 3.3Notes:1. Ratings based on HCFC-22, evaporator fouling of 0.0176, 0.043 L/s; condenser fouling of 0.044.2. For 208V units multiply capacity and COP by 0.983. Ratings are based on circuit #1 in lead position and circuit #2 in lag position.4. Interpolation is allowed; extrapolation is not permitted. Consult McQuay for performance outside the ratings shown.5. For LWT of 5°C and below please refer to Application Adjustment Factors section.

Page 24: Reciprocating Chillers - Daikin Applied

24 Product Manual WHR-2

Table 10, WHR 130EW - WHR 210EW, 60 Hz, SI UnitsEntering Condenser Water Temperature (°C)

20°C (68°F) 25°C (77°F) 30°C (86°F) 35°C (95°F) 40°C (104°F)

Cap. PWR Cap. PWR Cap. PWR Cap. PWR Cap. PWRWHRSIZE

LWT°C

kW kWiCOP

kW kWiCOP

kW kWiCOP

kW kWiCOP

kW kWiCOP

5.0 (41.0°F) 481.6 96.3 4.9 459.2 106.8 4.3 437.0 117.0 3.7 415.0 127.1 3.2 392.6 136.9 2.96.0 (42.8°F) 499.1 96.7 5.1 475.8 107.2 4.4 453.4 117.8 3.8 430.2 128.2 3.3 407.4 138.5 2.9

130EW 7.0 (44.6°F) 516.6 96.9 5.3 493.1 107.6 4.5 469.8 118.6 3.9 446.0 129.2 3.4 423.1 139.8 3.08.0 (46.4°F) 525.7 97.0 5.3 501.9 107.9 4.6 478.2 118.9 4.0 454.2 129.8 3.5 430.6 140.4 3.09.0 (48.2°F) 544.1 97.1 5.5 518.4 108.3 4.7 498.3 119.6 4.1 470.4 130.8 3.6 446.4 141.8 3.1

10.0 (50.0°F) 562.6 97.2 5.8 537.5 108.8 4.8 512.5 120.2 4.2 486.8 131.7 3.7 462.2 143.1 3.2

5.0 (41.0°F) 525.3 99.7 5.2 501.0 110.5 4.5 476.7 121.1 3.9 452.7 131.6 3.4 428.3 141.7 3.06.0 (42.8°F) 544.5 100.1 5.3 519.1 111.0 4.6 494.6 121.9 4.0 469.3 132.7 3.5 444.5 143.3 3.1

145EW 7.0 (44.6°F) 563.6 100.3 5.6 537.9 111.4 4.7 512.5 122.7 4.1 486.6 133.8 3.6 461.6 144.7 3.28.0 (46.4°F) 573.5 100.4 5.6 547.5 111.7 4.8 521.7 123.1 4.2 495.5 134.3 3.7 469.7 145.4 3.29.0 (48.2°F) 593.5 100.5 5.8 565.6 112.1 5.0 543.6 123.8 4.3 513.1 135.4 3.8 487.0 146.7 3.3

10.0 (50.0°F) 613.7 100.6 6.1 586.3 112.6 5.1 559.0 124.4 4.4 531.0 136.4 3.9 504.2 148.1 3.4

5.0 (41.0°F) 549.0 107.6 5.0 523.6 119.3 4.4 498.2 130.7 3.8 473.2 142.0 3.3 447.6 152.9 2.96.0 (42.8°F) 569.1 108.0 5.2 542.5 119.8 4.5 517.0 131.6 3.9 490.4 143.2 3.4 464.5 154.7 3.0

155EW 7.0 (44.6°F) 589.1 108.2 5.4 562.2 120.2 4.6 535.6 132.5 4.0 508.5 144.4 3.5 482.4 156.1 3.18.0 (46.4°F) 599.4 108.3 5.4 572.2 120.5 4.7 545.3 132.8 4.1 517.9 145.0 3.6 490.9 156.9 3.19.0 (48.2°F) 620.3 108.5 5.6 591.1 121.0 4.8 568.2 133.6 4.2 536.3 146.1 3.6 509.0 158.4 3.2

10.0 (50.0°F) 641.4 108.6 5.9 612.8 121.6 5.0 584.3 134.3 4.3 555.0 147.2 3.8 527.0 159.8 3.3

5.0 (41.0°F) 594.6 116.3 5.0 567.1 129.0 4.4 539.6 141.3 3.8 512.5 153.5 3.3 484.8 165.3 2.96.0 (42.8°F) 616.3 116.8 5.2 587.6 129.5 4.5 559.9 142.2 3.9 531.2 154.8 3.4 503.1 167.2 3.0

165EW 7.0 (44.6°F) 638.0 117.0 5.4 608.9 130.0 4.6 580.1 143.2 4.0 550.8 156.1 3.5 522.5 168.8 3.18.0 (46.4°F) 649.2 117.1 5.5 619.7 130.3 4.7 590.6 143.6 4.1 560.9 156.7 3.6 531.7 169.6 3.19.0 (48.2°F) 671.8 117.3 5.6 640.2 130.8 4.8 615.4 144.5 4.2 580.8 158.0 3.6 551.2 171.2 3.2

10.0 (50.0°F) 694.7 117.4 5.9 663.7 131.4 5.0 632.8 145.2 4.3 601.1 159.1 3.8 570.7 172.8 3.3

5.0 (41.0°F) 645.7 127.5 5.0 615.8 141.4 4.3 585.9 154.8 3.8 556.5 168.3 3.2 526.4 181.2 2.96.0 (42.8°F) 669.3 128.0 5.1 638.0 142.0 4.5 608.0 155.9 3.8 576.8 169.7 3.4 546.3 183.3 3.0

175EW 7.0 (44.6°F) 692.8 128.3 5.4 661.2 142.5 4.5 629.9 157.0 3.9 598.1 171.1 3.5 567.3 185.1 3.18.0 (46.4°F) 704.9 128.4 5.4 672.9 142.8 4.6 641.3 157.4 4.0 609.1 171.8 3.5 577.4 185.9 3.19.0 (48.2°F) 729.5 128.5 5.6 695.2 143.4 4.8 668.2 158.4 4.2 630.7 173.2 3.6 598.6 187.7 3.1

10.0 (50.0°F) 754.4 128.7 5.8 720.7 144.1 4.9 687.2 159.2 4.2 652.7 174.4 3.7 619.7 189.4 3.2

5.0 (41.0°F) 674.9 127.6 5.2 643.6 141.5 4.5 612.4 154.9 4.0 581.6 168.4 3.4 550.2 181.3 3.06.0 (42.8°F) 699.5 128.1 5.4 666.9 142.1 4.7 635.5 156.0 4.0 602.9 169.8 3.5 571.0 183.4 3.1

185EW 7.0 (44.6°F) 724.1 128.4 5.6 691.1 142.6 4.7 658.4 157.1 4.1 625.1 171.2 3.6 593.0 185.2 3.28.0 (46.4°F) 736.8 128.5 5.6 703.4 142.9 4.8 670.3 157.5 4.2 636.6 171.9 3.7 603.5 186.0 3.29.0 (48.2°F) 762.5 128.6 5.8 726.6 143.5 5.0 698.4 158.5 4.4 659.2 173.3 3.8 625.6 187.8 3.3

10.0 (50.0°F) 788.5 128.8 6.1 753.3 144.2 5.1 718.2 159.3 4.4 682.2 174.5 3.9 647.8 189.5 3.4

5.0 (41.0°F) 718.7 138.4 5.1 685.3 153.4 4.4 652.1 168.0 3.9 619.4 182.7 3.3 585.9 196.7 3.06.0 (42.8°F) 744.9 138.9 5.3 710.1 154.1 4.6 676.7 169.2 3.9 642.0 184.2 3.5 608.0 198.9 3.1

195EW 7.0 (44.6°F) 771.1 139.2 5.5 735.9 154.6 4.7 701.1 170.4 4.1 665.6 185.7 3.6 631.4 200.8 3.18.0 (46.4°F) 784.6 139.3 5.5 749.0 155.0 4.7 713.7 170.8 4.1 677.9 186.4 3.6 642.6 201.8 3.29.0 (48.2°F) 812.0 139.5 5.7 773.7 155.6 4.9 743.7 171.9 4.3 702.0 188.0 3.7 666.2 203.7 3.2

10.0 (50.0°F) 839.6 139.7 6.0 802.1 156.3 5.0 764.8 172.7 4.4 726.5 189.3 3.8 689.8 205.6 3.3

5.0 (41.0°F) 769.8 147.5 5.1 734.0 163.5 4.5 698.5 179.1 3.9 663.4 194.7 3.3 627.5 209.6 3.06.0 (42.8°F) 797.8 148.1 5.3 760.6 164.2 4.6 724.8 180.4 4.0 687.6 196.3 3.5 651.3 212.1 3.1

210EW 7.0 (44.6°F) 825.9 148.4 5.5 788.2 164.9 4.7 750.9 181.6 4.1 713.0 197.9 3.6 676.3 214.1 3.18.0 (46.4°F) 840.3 148.5 5.6 802.2 165.3 4.8 764.5 182.1 4.1 726.1 198.8 3.6 688.3 215.1 3.29.0 (48.2°F) 869.7 148.7 5.8 828.7 165.9 5.0 796.6 183.2 4.3 751.9 200.4 3.7 713.6 217.1 3.2

10.0 (50.0°F) 899.3 148.9 6.0 859.2 166.7 5.1 819.2 184.1 4.4 778.1 201.8 3.8 738.8 219.1 3.3

Notes:1. Ratings based on HCFC-22 evaporator fouling of 0.0176, 0.043 L/s; condenser fouling of 0.044.2. For 208V units multiply capacity and COP by 0.98.3. Ratings are based on circuit #1 in lead position and circuit #2 in lag position.4. Interpolation is allowed; extrapolation is not permitted. Consult McQuay for performance outside the ratings shown.5. For LWT of 5°C and below please refer to Application Adjustment Factors section.

Page 25: Reciprocating Chillers - Daikin Applied

Product Manual WHR-2 25

Part Load Data (EW Only)Table 11, Part Load Performance

Unit Size % LoadCapacity

Tons

60 HzPower

Unit kWEER IPLV Unit Size % Load

CapacityTons

60 HzPower

Unit kWEER IPLV

100.00 17.7 14.7 14.4 100.00 96.0 82.0 14.0

017EW 75.00 13.3 9.1 17.5 20.3 095EW 75.00 72.1 47.6 18.2 19.950.00 8.8 4.5 23.5 50.00 48.0 26.3 21.925.00 4.4 2.9 18.2 25.00 24.0 15.1 19.1

100.00 21.7 19.3 13.5 100.00 102.0 87.2 14.0

020EW 75.00 16.2 11.7 16.6 18.9 100EW 75.00 76.5 49.6 18.5 20.250.00 10.8 6.0 21.6 50.00 51.0 28.0 21.925.00 5.4 3.7 17.5 25.00 25.5 15.0 20.4

100.00 27.0 24.2 13.4 100.00 111.5 96.8 13.8

025EW 75.00 20.3 14.4 16.9 18.4 110EW 75.00 83.6 56.8 17.7 20.150.00 13.6 8.1 20.1 50.00 55.7 29.9 22.425.00 6.7 4.7 17.1 25.00 28.0 16.3 20.6

100.00 30.0 26.7 13.5 100.00 113.5 97.0 14.0

030EW 75.00 22.6 16.1 16.8 18.7 115EW 75.00 85.0 57.5 17.7 19.950.00 15.1 8.7 20.8 50.00 56.7 30.4 22.425.00 7.5 5.1 17.6 25.00 28.5 18.7 18.3

100.00 38.0 32.6 14.0 100.00 122.0 106.1 13.8

040EW 75.00 28.5 19.6 17.4 19.2 120EW 75.00 91.5 62.1 17.7 19.950.00 19.0 11.1 20.5 50.00 61.0 33.0 22.225.00 9.5 5.5 20.7 25.00 30.5 18.9 19.4

100.00 44.0 36.8 14.3 100.00 132.0 118.0 13.4

045EW 75.00 33.1 22.6 17.6 19.2 130EW 75.00 98.9 69.6 17.1 19.750.00 22.1 12.8 20.7 50.00 65.9 35.7 22.225.00 11.0 6.8 19.4 25.00 32.9 19.3 20.5

100.00 51.5 46.0 13.4 100.00 144.0 122.0 14.2

050EW 75.00 38.9 28.0 16.7 18.1 145EW 75.00 107.9 73.8 17.5 20.050.00 25.9 15.9 19.5 50.00 71.9 38.8 22.225.00 12.9 8.5 18.2 25.00 35.9 21.2 20.3

100.00 58.5 50.3 14.0 100.00 150.5 131.5 13.7

060EW 75.00 44.6 29.5 18.1 18.6 155EW 75.00 112.8 78.2 17.3 19.750.00 29.7 18.7 19.1 50.00 75.2 40.5 22.325.00 14.7 9.3 19.0 25.00 37.6 23.5 19.2

100.00 70.5 63.3 13.4 100.00 163.0 142.1 13.8

070EW 75.00 53.2 37.2 17.2 19.2 165EW 75.00 122.6 85.4 17.2 19.750.00 35.4 19.8 21.5 50.00 81.7 44.6 22.025.00 17.7 11.8 18.0 25.00 40.8 24.6 19.9

100.00 76.5 68.8 13.3 100.00 177.0 155.8 13.6

080EW 75.00 57.3 41.0 16.8 18.7 175EW 75.00 134.8 94.3 17.2 19.850.00 38.2 22.0 20.8 50.00 89.9 48.1 22.425.00 19.1 13.1 17.5 25.00 44.3 26.4 20.1

100.00 85.0 73.2 13.9 100.00 185.0 155.9 14.2

085EW 75.00 63.7 43.9 17.4 19.2 185EW 75.00 139.0 96.1 17.4 19.750.00 42.5 24.1 21.2 50.00 92.6 50.2 22.125.00 21.2 14.0 18.2 25.00 46.3 29.1 19.1

100.00 91.5 77.5 14.2 100.00 197.0 168.9 14.0

090EW 75.00 68.8 46.6 17.7 18.9 195EW 75.00 150.3 101.9 17.7 19.450.00 45.8 26.8 20.5 50.00 100.2 57.1 21.125.00 22.9 16.1 17.1 25.00 49.5 30.9 19.2

Note: Part load data certified under ARI Standard 550/590-98 100.00 211.0 180.1 14.1

210EW 75.00 162.3 109.2 17.8 19.450.00 108.2 61.7 21.025.00 53.0 33.0 19.3

Page 26: Reciprocating Chillers - Daikin Applied

26 Product Manual WHR-2

EA Remote CondenserTable 12, R22, WHR 017EA – WHR 090EA, 60 Hz, IP Units

CONDENSING TEMPERATURE105°F 110°F 115°F 120°F 125°F

Cap. Power Cap. Power Cap. Power Cap. Power Cap. Power

WHRUNITSIZE

LWT(°F)

Tons kWiTHR

Tons kWiTHR

Tons kWiTHR

Tons kWiTHR

Tons kWiTHR

42 16.9 15.7 256.4 16.4 16.4 252.8 15.8 17.1 248.0 15.2 17.8 243.2 14.7 18.4 239.344 17.6 15.8 265.2 17.1 16.5 261.0 16.5 17.3 256.3 15.9 18.0 252.1 15.4 18.6 247.7

017EA 46 18.3 15.9 273.9 17.7 16.6 269.1 17.1 17.4 264.6 16.6 18.1 261.0 16.0 18.8 256.248 19.1 16.0 283.1 18.5 16.7 278.4 17.9 17.5 274.0 17.3 18.3 269.9 16.7 19.0 264.750 19.8 16.0 292.3 19.2 16.8 287.8 18.6 17.6 283.3 18.0 18.4 278.9 17.3 19.2 273.242 20.6 20.3 316.5 20.0 21.2 312.4 19.4 22.0 308.0 18.8 22.9 303.8 18.2 23.7 299.444 21.4 20.4 326.5 20.8 21.4 322.5 20.2 22.2 318.2 19.6 23.1 313.5 19.0 24.0 309.2

020EA 46 22.2 20.5 336.4 21.6 21.5 332.6 21.0 22.4 328.5 20.3 23.3 323.2 19.7 24.2 319.148 23.0 20.6 345.8 22.3 21.6 341.4 21.7 22.6 337.4 21.0 23.5 332.3 20.4 24.5 327.750 23.7 20.7 355.1 23.0 21.7 350.1 22.4 22.7 346.3 21.7 23.7 341.4 21.0 24.7 336.442 24.5 24.7 378.4 23.8 25.8 373.7 23.1 26.8 368.7 22.5 27.8 365.0 21.7 28.8 358.844 25.5 24.9 390.5 24.8 26.0 385.8 24.0 27.1 380.4 23.3 28.1 375.6 22.5 29.2 369.6

025EA 46 26.4 25.1 402.5 25.7 26.2 397.9 24.9 27.3 392.1 24.1 28.4 386.2 23.3 29.5 380.448 27.4 25.3 414.5 26.6 26.4 409.2 25.8 27.5 403.5 25.0 28.7 397.9 24.2 29.8 392.250 28.3 25.4 426.4 27.5 26.5 420.5 26.7 27.7 415.0 25.9 28.9 409.5 25.1 30.1 404.042 28.3 26.9 431.5 27.4 28.0 424.4 26.7 29.1 419.8 25.7 30.2 411.6 24.9 31.3 405.744 29.4 27.1 444.8 28.5 28.2 437.7 27.6 29.3 431.3 26.7 30.5 423.8 25.8 31.6 417.5

030EA 46 30.4 27.3 458.1 29.5 28.4 451.0 28.5 29.5 442.8 27.6 30.7 436.1 26.7 31.9 429.448 31.6 27.4 472.8 30.6 28.6 464.7 29.6 29.7 456.7 28.7 30.9 449.4 27.7 32.2 442.250 32.8 27.5 487.5 31.7 28.7 478.4 30.7 29.9 470.5 29.7 31.1 462.6 28.7 32.4 455.142 36.4 33.5 551.2 35.0 35.1 539.9 33.9 36.6 531.8 32.8 38.1 523.7 31.5 39.5 512.944 37.9 33.8 570.1 36.5 35.4 558.8 35.4 37.0 550.4 34.2 38.5 541.9 32.9 40.0 531.3

040EA 46 39.4 34.0 588.9 38.0 35.6 577.6 36.8 37.3 569.0 35.6 38.9 560.1 34.3 40.4 549.648 41.0 34.2 608.1 39.6 35.9 597.7 38.4 37.6 588.5 37.1 39.2 578.5 35.7 40.8 567.850 42.5 34.3 627.2 41.2 36.1 617.7 39.9 37.8 607.9 38.5 39.5 596.9 37.1 41.2 585.942 44.4 44.1 683.4 43.1 45.9 674.0 41.8 47.8 664.9 40.6 49.6 656.6 39.2 51.5 646.344 46.2 44.4 705.5 44.9 46.3 696.4 43.5 48.3 686.8 42.2 50.2 677.1 40.7 52.1 666.2

045EA 46 47.9 44.7 727.5 46.6 46.7 718.7 45.2 48.7 708.8 43.7 50.7 697.6 42.2 52.6 686.148 49.6 45.0 748.7 48.3 47.0 739.6 46.8 49.1 729.3 45.4 51.2 718.9 43.9 53.2 707.850 51.3 45.2 770.0 49.9 47.3 760.4 48.4 49.5 749.9 47.0 51.6 740.3 45.5 53.7 729.442 49.3 49.0 758.8 47.8 51.2 748.3 46.3 53.3 737.5 44.9 55.3 727.5 43.5 57.5 718.244 51.4 49.3 784.5 49.8 51.5 773.3 48.2 53.6 761.5 46.7 55.5 749.9 45.2 57.7 738.9

050EA 46 53.4 49.6 810.1 51.8 51.8 798.2 50.2 53.8 785.4 48.5 55.8 772.3 46.9 57.9 759.648 55.5 49.9 835.7 53.8 52.0 823.2 52.1 54.1 809.4 50.3 56.0 794.6 48.5 58.0 780.350 57.5 50.2 861.3 55.8 52.3 848.1 54.0 54.3 833.3 52.1 56.2 817.0 50.2 58.2 801.042 54.6 51.2 830.1 52.8 53.3 815.7 51.0 55.5 801.6 49.6 57.7 792.3 47.8 59.9 778.244 56.7 51.5 856.3 55.0 53.7 842.8 53.1 56.0 827.7 51.6 58.2 817.4 49.6 60.5 801.3

060EA 46 58.8 51.8 882.5 57.1 54.1 870.0 55.1 56.4 853.9 53.5 58.7 842.5 51.3 61.1 824.348 61.0 52.0 909.6 59.2 54.4 895.6 57.2 56.8 879.7 55.3 59.2 865.7 53.3 61.7 850.250 63.2 52.2 936.7 61.2 54.7 921.3 59.2 57.1 905.5 57.1 59.6 888.8 55.3 62.2 876.142 66.6 64.1 1018.2 64.6 67.0 1004.1 62.4 69.8 987.2 60.7 72.7 976.7 58.3 75.6 957.844 69.1 64.6 1049.3 66.9 67.6 1033.6 64.7 70.5 1017.2 62.8 73.5 1003. 60.5 76.5 987.2

070EA 46 71.5 65.1 1080.4 69.2 68.1 1063.0 67.0 71.2 1047.2 64.8 74.2 1031. 62.7 77.3 1016.548 74.1 65.5 1112.2 71.8 68.6 1095.3 69.7 71.8 1080.9 67.4 74.9 1064. 65.2 78.1 1049.050 76.6 65.8 1144.0 74.3 69.1 1127.6 72.3 72.3 1114.6 70.0 75.5 1097. 67.7 78.8 1081.642 72.8 70.9 1115.8 70.6 74.1 1100.3 68.4 77.2 1084.5 66.3 80.4 1070. 63.8 83.6 1051.244 75.4 71.5 1148.9 73.1 74.7 1132.4 70.9 78.0 1116.5 68.6 81.2 1100. 66.2 84.5 1082.5

080EA 46 78.0 72.0 1182.0 75.6 75.3 1164.4 73.3 78.7 1148.4 70.9 82.0 1130. 68.5 85.4 1113.748 80.8 72.5 1216.5 78.3 75.9 1198.7 75.9 79.4 1181.9 73.5 82.8 1164. 71.1 86.3 1147.250 83.5 72.9 1251.0 81.0 76.4 1233 78.5 80.0 1215.3 76.0 83.5 1197. 73.6 87.1 1180.742 78.1 79.4 1208.4 75.8 82.7 1192.1 73.6 86.0 1177.0 71.4 89.3 1161. 68.9 92.6 1142.844 81.0 80.1 1245.5 78.7 83.5 1228.9 76.4 86.8 1212.7 74.1 90.2 1196. 74.4 94.6 1215.4

085EA 46 83.9 80.7 1282.5 81.5 84.2 1265.6 79.1 87.6 1248.4 76.7 91.1 1231. 77.1 95.6 1251.248 86.9 81.3 1319.9 84.4 84.9 1302.0 81.9 88.4 1284.8 79.5 92.0 1268. 79.8 96.6 1287.650 89.8 81.9 1357.4 87.2 85.5 1338.5 84.7 89.2 1321.1 82.3 92.9 1304. 82.5 97.7 1323.742 86.7 82.8 1323.4 84.6 86.5 1310.6 82.0 90.1 1290.8 79.5 93.5 1272. 77.0 97.2 1255.644 87.3 83.3 1331.5 88.1 87.0 1354.8 85.3 90.6 1332.9 82.7 93.8 1312. 80.0 97.5 1292.9

090EA 46 87.8 83.8 1339.6 91.7 87.5 1399.0 88.9 90.9 1376.6 85.8 94.3 1352. 83.0 97.9 1330.148 88.3 84.3 1347.7 95.2 87.9 1442.6 92.2 91.4 1418.7 89.0 94.6 1391. 85.8 98.0 1364.750 88.9 84.8 1355.8 98.8 88.4 1486.9 95.6 91.8 1460.2 92.2 95.0 1430. 88.9 98.4 1401.9

Notes:1. Ratings based on HCFC-22, evaporator fouling of 0.0001, evaporator temperature drop of 10°F.2. For 208V units multiply capacity and EER by 0.98.3. Remote condenser units are not covered in the ARI Certification Program.4. Interpolation is allowed; extrapolation is not permitted. Consult McQuay for performance outside the cataloged ratings.5. For LWT of 41°F and below please refer to application considerations for reciprocating chillers.

Page 27: Reciprocating Chillers - Daikin Applied

Product Manual WHR-2 27

Table 13, R22, WHR 095EA – WHR 210EA, 60 Hz, IP UnitsCONDENSING TEMPERATURE

105°F 110°F 115°F 120°F 125°F Cap. Power Cap. Power Cap. Power Cap. Power Cap. Power

WHRUNITSIZE

LWT(°F)

Tons kWiTHR

Tons kWiTHR

Tons kWiTHR

Tons kWiTHR

Tons kWiTHR

42 88.5 87.3 1360.2 86.1 91.1 1344.4 83.6 94.8 1327.0 81.2 98.5 1310.9 78.3 102.2 1288.744 91.9 87.9 1403.1 89.4 91.9 1386.0 86.8 95.7 1367.9 84.2 99.5 1350.3 81.4 103.4 1329.8

095EA 46 95.3 88.5 1445.9 92.6 92.6 1427.5 89.9 96.6 1408.8 87.2 100.5 1389.7 84.5 104.5 1371.048 98.7 89.0 1488.4 96.0 93.2 1469.8 93.2 97.4 1450.9 90.4 101.5 1431.4 87.6 105.6 1411.850 102.1 89.5 1530.9 99.3 93.8 1512.0 96.5 98.1 1493.1 93.6 102.4 1473 90.7 106.6 1452.542 94.3 91.4 1443.8 91.6 95.2 1424.4 88.6 98.9 1401.0 85.9 102.7 1381.6 83.2 106.6 1362.544 97.7 92.0 1486.7 95.1 95.9 1468.8 92.2 99.8 1447.3 89.2 103.8 1424.2 86.3 107.8 1403.7

100EA 46 101.1 92.6 1529.5 98.6 96.6 1513.2 95.8 100.7 1493.6 92.4 104.8 1466.8 89.4 108.9 1444.848 104.8 93.1 1575.0 102.0 97.3 1555.6 99.0 101.5 1534.0 95.7 105.7 1509.3 92.7 110.0 1487.450 108.4 93.6 1620.5 105.3 97.9 1598.0 102.1 102.2 1574.3 99.0 106.5 1551.8 95.9 111.0 1530.042 101.7 101.4 1566.8 98.8 106.2 1548.4 95.8 110.9 1528.4 92.9 115.6 1509.7 90.0 120.1 1490.344 105.5 102.4 1615.6 102.5 107.3 1596.5 99.5 112.2 1576.7 96.4 117.1 1556.6 93.4 121.7 1535.9

110EA 46 109.3 103.3 1664.5 106.2 108.4 1644.7 103.1 113.5 1624.9 99.9 118.5 1603.6 96.7 123.3 1581.648 113.2 104.2 1713.6 110.0 109.4 1693.1 106.8 114.7 1672.6 103.5 119.8 1650.6 100.3 124.8 1629.350 117.0 105.0 1762.7 113.7 110.4 1741.5 110.4 115.8 1720.4 107.0 121.1 1697.7 103.8 126.3 1677.042 103.5 101.9 1590.1 100.5 106.7 1570.5 97.4 111.5 1549.7 94.1 116.2 1526.1 91.2 120.8 1507.144 107.4 102.9 1639.5 104.2 107.8 1618.6 101.0 112.8 1597.3 97.8 117.7 1574.9 94.7 122.4 1554.5

115EA 46 111.2 103.8 1689.0 107.9 108.9 1666.8 104.6 114.1 1645.0 101.4 119.1 1623.6 98.2 124.0 1602.048 115.1 104.6 1738.5 111.8 109.9 1716.4 108.4 115.2 1694.3 105.1 120.4 1672.5 101.8 125.5 1650.350 119.0 105.4 1788.0 115.6 110.9 1766.0 112.2 116.3 1743.7 108.8 121.7 1721.3 105.4 127.0 1698.642 112.9 113.2 1741.5 109.6 118.3 1719.3 106.3 123.3 1696.8 102.9 128.4 1673.4 99.5 133.4 1649.744 117.0 114.2 1793.5 113.6 119.5 1771.2 110.1 124.7 1747.0 106.8 129.9 1724.7 103.4 135.1 1701.5

120EA 46 121.0 115.2 1845.5 117.6 120.6 1823.2 113.9 126.0 1797.2 110.6 131.4 1776.1 107.2 136.7 1753.448 125.5 116.1 1902.0 121.8 121.7 1876.6 118.1 127.3 1851.3 114.6 132.8 1828.8 111.1 138.3 1805.050 129.9 117.0 1958.5 125.9 122.7 1929.9 122.2 128.5 1905.4 118.6 134.2 1881.6 114.9 139.9 1856.742 122.3 124.5 1892.9 118.7 129.8 1867.8 115.2 135.2 1844.2 111.7 140.6 1820.7 107.9 146.0 1793.544 126.6 125.6 1947.6 123.0 131.1 1923.7 119.2 136.6 1897.0 115.8 142.2 1874.6 112.1 147.8 1849.3

130EA 46 130.8 126.7 2002.4 127.3 132.3 1979.5 123.2 138.0 1949.8 119.8 143.7 1928.5 116.2 149.5 1905.148 135.8 127.6 2065.5 131.8 133.5 2036.9 127.7 139.3 2008.2 124.1 145.2 1985.0 120.3 151.2 1959.350 140.8 128.5 2128.6 136.2 134.6 2094.2 132.2 140.6 2066.7 128.4 146.6 2041.6 124.3 152.8 2013.642 133.2 129.9 2042.1 129.2 135.6 2013.6 125.4 141.4 1987.8 121.3 147.1 1958.1 117.5 152.9 1932.344 138.2 130.9 2105.0 134.1 136.8 2075.9 130.0 142.8 2047.6 125.9 148.7 2018.2 121.9 154.7 1990.5

145EA 46 143.1 131.9 2167.8 138.9 138.0 2138.2 134.6 144.1 2107.4 130.4 150.3 2078.2 126.2 156.4 2048.748 148.3 132.8 2232.5 143.9 139.1 2201.8 139.5 145.4 2169.9 135.1 151.7 2139.4 130.8 158.0 2108.750 153.4 133.6 2297.2 148.9 140.1 2265.4 144.3 146.6 2232.4 139.8 153.1 2200.6 135.3 159.6 2168.842 141.8 139.9 2179.5 137.6 146.1 2150.3 133.0 152.3 2116.3 128.9 158.6 2088.6 124.9 164.8 2061.844 147.2 141.0 2247.3 142.8 147.4 2216.9 138.2 153.8 2183.0 133.8 160.2 2152.8 129.6 166.6 2123.7

155EA 46 152.5 142.0 2315.1 148.0 148.6 2283.6 143.3 155.2 2249.8 138.7 161.8 2217.1 134.2 168.4 2185.748 157.7 143.0 2380.9 153.1 149.8 2348.7 148.4 156.5 2315.4 143.8 163.3 2282.8 139.2 170.1 2250.950 162.9 144.0 2446.7 158.2 150.9 2413.9 153.5 157.8 2381.0 148.8 164.8 2348.6 144.1 171.8 2316.142 150.9 158.1 2350.9 146.3 164.4 2317.2 142.5 170.8 2293.5 138.2 177.3 2264.1 134.0 183.9 2236.244 156.6 159.5 2424.1 152.2 166.0 2392.9 147.8 172.6 2362.6 143.4 179.3 2332.7 139.0 186.1 2303.5

165EA 46 162.3 160.9 2497.2 158.0 167.6 2468.5 153.0 174.4 2431.8 148.5 181.3 2401.3 144.0 188.2 2370.948 167.9 162.3 2568.4 163.4 169.1 2538.4 158.6 176.1 2504.0 154.0 183.1 2472.9 149.4 190.2 2441.950 173.4 163.6 2639.7 168.8 170.6 2608.4 164.1 177.7 2576.2 159.4 184.9 2544.4 154.7 192.2 2513.042 160.9 180.5 2547.4 155.9 187.1 2509.9 151.9 193.8 2484.8 147.5 200.6 2455.2 142.9 207.5 2423.644 166.7 182.2 2622.0 161.8 189.0 2587.1 157.6 195.8 2560.1 153.2 202.8 2530.4 148.3 209.9 2496.0

175EA 46 172.4 183.8 2696.7 167.7 190.8 2664.2 163.3 197.8 2635.3 158.8 204.9 2605.5 153.6 212.3 2568.448 178.6 185.3 2776.0 173.7 192.5 2741.2 169.0 199.7 2710.2 164.3 207.0 2678.7 159.3 214.6 2643.950 184.8 186.7 2855.4 179.6 194.1 2818.2 174.7 201.6 2785.1 169.8 209.1 2751.9 164.9 216.8 2719.442 168.3 178.4 2629 163.8 185.2 2598.2 158.4 192.1 2557.0 153.7 199.0 2524.2 149.1 205.9 2492.644 174.7 180.0 2710.5 170.0 187.0 2678.0 164.8 194.1 2639.9 159.9 201.2 2605.9 155.2 208.3 2573.2

185EA 46 181.0 181.5 2792.0 176.1 188.7 2757.8 171.1 196.0 2722.7 166.1 203.3 2687.7 161.2 210.6 2653.848 187.8 183.0 2878.7 182.8 190.4 2843.4 177.6 197.9 2807.2 172.5 205.5 2771.8 167.5 213.0 2736.850 194.6 184.5 2965.5 189.4 192.1 2929.0 184.1 199.8 2891.7 178.9 207.6 2856.0 173.7 215.3 2819.942 180.8 200.2 2853.5 175.0 207.4 2808.5 169.7 214.4 2768.8 164.3 221.4 2727.9 158.9 228.2 2686.344 187.6 202.0 2940.5 181.9 209.4 2897.9 176.4 216.6 2856.1 170.7 223.9 2812.5 165.0 231.0 2769.1

195EA 46 194.3 203.7 3027.4 188.8 211.3 2987.4 183.0 218.8 2943.4 177.0 226.3 2897.0 171.1 233.8 2851.948 201.5 205.4 3119.6 195.8 213.2 3077.9 189.9 221.0 3033.7 183.8 228.8 2986.4 177.6 236.5 2938.950 208.7 207.1 3211.9 202.8 215.1 3168.4 196.8 223.2 3124.1 190.5 231.2 3075.8 184.1 239.1 3026.042 192.8 221.8 3070.6 187.0 229.2 3026.3 180.9 236.4 2977.6 173.9 243.5 2917.9 167.4 250.4 2863.444 199.7 223.8 3160.2 193.6 231.5 3113.3 187.2 239.0 3062.1 181.0 246.3 3012.6 174.3 253.5 2956.8

210EA 46 207.7 225.7 3262.7 201.4 233.6 3214.1 195.0 241.4 3163.9 188.0 249.1 3106.2 180.6 256.6 3043.048 214.6 227.6 3352.0 208.4 235.8 3305.6 201.7 243.9 3252.8 194.7 251.8 3195.8 187.3 259.7 3134.050 222.4 229.5 3452.1 215.9 237.9 3402.8 209.0 246.2 3348.3 201.8 254.5 3290.2 194.3 262.6 3227.9

Notes:1. Ratings based on HCFC-22, evaporator fouling of 0.0001, evaporator temperature drop of 10°F.2. For 208V units multiply capacity and EER by 0.98.3. Remote condenser units are not included in the ARI Certification Program.4. Interpolation is allowed; extrapolation is not permitted. Consult McQuay for performance outside the cataloged ratings.5. For LWT of 41°F and below please refer to application considerations for reciprocating chillers.

Page 28: Reciprocating Chillers - Daikin Applied

28 Product Manual WHR-2

Table 14, R22, WHR 017EA – WHR 100EA, 60 Hz, SI UnitsCONDENSING TEMPERATURE (deg °C)

40°C 45°C 50°C 52°C 55°C Cap. Power THR Cap. Power THR Cap. Power THR Cap. Power THR Cap. Power THR

WHRUNITSIZE

LWT(°C)

kW kWi kW kW kWi kW kW kWi kW kW kWi kW kW kWi kW6 60.8 15.6 76.4 55.9 17.4 73.2 53.0 18.3 71.4 52.3 18.6 70.9 51.6 18.8 70.57 63.1 15.7 78.8 58.0 17.5 75.5 55.1 18.5 73.6 54.4 18.8 73.2 53.7 19.0 72.7

017EA 8 65.4 15.7 81.1 60.2 17.6 77.8 57.2 18.7 75.9 56.5 18.9 75.4 55.7 19.2 74.99 67.7 15.8 83.5 62.4 17.7 80.1 59.3 18.8 78.2 58.6 19.1 77.7 57.8 19.4 77.210 70.0 15.9 85.9 64.5 17.9 82.4 61.4 19.0 80.4 60.6 19.3 79.9 59.9 19.6 79.46 74.0 20.2 94.2 68.6 22.4 91.0 65.6 23.6 89.2 64.8 23.9 88.7 64.0 24.2 88.37 76.5 20.3 96.8 71.0 22.5 93.5 67.8 23.8 91.7 67.0 24.1 91.2 66.3 24.5 90.7

020EA 8 79.0 20.4 99.3 73.3 22.7 96.0 70.1 24.0 94.1 69.3 24.4 93.7 68.5 24.7 93.29 81.4 20.4 101.9 75.7 22.9 98.5 72.3 24.3 96.6 71.5 24.6 96.1 70.7 24.9 95.610 83.9 20.5 104.4 78.0 23.0 101.0 74.6 24.5 99.1 73.8 24.8 98.6 72.9 25.2 98.16 88.0 24.6 112.7 81.7 27.2 108.9 78.1 28.7 106.8 77.2 29.1 106.2 76.3 29.5 105.77 91.1 24.7 115.8 84.5 27.4 111.9 80.7 29.0 109.7 79.8 29.4 109.2 78.9 29.8 108.6

025EA 8 94.1 24.9 119.0 87.3 27.7 115.0 83.4 29.3 112.7 82.5 29.7 112.1 81.5 30.1 111.69 97.1 25.0 122.1 90.1 27.9 118.0 86.1 29.5 115.6 85.1 30.0 115.1 84.1 30.4 114.510 100.1 25.1 125.3 92.9 28.1 121.0 88.8 29.8 118.6 87.7 30.3 118.0 86.7 30.7 117.46 101.6 26.8 128.3 93.9 29.6 123.4 89.5 31.2 120.7 88.4 31.6 120.0 87.3 32.0 119.37 105.1 26.9 132.0 97.1 29.7 126.8 92.5 31.4 123.9 91.4 31.8 123.2 90.2 32.2 122.4

030EA 8 108.6 27.0 135.6 100.3 29.9 130.2 95.5 31.6 127.2 94.3 32.0 126.4 93.1 32.5 125.69 112.1 27.1 139.3 103.5 30.1 133.6 98.5 31.9 130.4 97.3 32.3 129.6 96.1 32.7 128.810 115.7 27.3 142.9 106.7 30.3 137.0 101.5 32.1 133.6 100.3 32.5 132.8 99.0 33.0 132.06 130.7 33.4 164.0 119.9 37.2 157.1 113.7 39.4 153.1 112.2 39.9 152.1 110.7 40.4 151.17 135.6 33.5 169.1 124.5 37.5 162.0 118.2 39.7 157.9 116.6 40.3 156.9 115.1 40.9 155.9

040EA 8 140.5 33.7 174.2 129.2 37.8 166.9 122.7 40.1 162.8 121.1 40.7 161.7 119.4 41.3 160.79 145.5 33.9 179.3 133.8 38.1 171.9 127.2 40.5 167.6 125.5 41.1 166.6 123.8 41.7 165.510 150.4 34.0 184.4 138.5 38.4 176.8 131.6 40.8 172.5 129.9 41.4 171.4 128.2 42.1 170.36 167.2 44.3 211.5 151.3 48.8 200.1 142.2 51.3 193.6 140.0 52.0 191.9 137.7 52.6 190.37 168.5 44.3 212.8 154.5 49.1 203.6 146.6 51.8 198.4 144.6 52.5 197.1 142.6 53.1 195.8

045EA 8 169.7 44.3 214.0 157.8 49.3 207.1 150.9 52.2 203.2 149.2 53.0 202.2 147.5 53.7 201.29 171.0 44.3 215.2 161.0 49.6 210.6 155.3 52.7 208.0 153.9 53.4 207.3 152.5 54.2 206.710 172.2 44.3 216.5 164.2 49.9 214.1 159.7 53.1 212.8 158.5 53.9 212.5 157.4 54.7 212.16 171.8 49.2 221.0 163.2 52.7 215.9 154.7 56.2 210.9 151.3 57.6 208.9 146.2 59.7 205.97 177.9 49.5 227.4 168.9 52.9 221.8 159.9 56.4 216.3 156.3 57.8 214.1 150.9 59.8 210.8

050EA 8 184.0 49.7 233.7 174.5 53.1 227.6 165.1 56.6 221.6 161.3 57.9 219.2 155.7 60.0 215.69 190.1 50.0 240.1 180.2 53.3 233.5 170.2 56.7 227.0 166.3 58.1 224.4 160.4 60.1 220.510 196.2 50.2 246.4 185.8 53.5 239.3 175.4 56.9 232.3 171.3 58.2 229.5 165.1 60.2 225.36 196.0 50.8 246.9 180.7 56.4 237.1 172.0 59.6 231.6 169.8 60.4 230.2 167.6 61.2 228.87 202.9 51.1 254.0 187.0 56.8 243.8 177.9 60.1 238.0 175.6 60.9 236.6 173.4 61.7 235.1

060EA 8 209.8 51.3 261.1 193.3 57.2 250.5 183.9 60.6 244.5 181.5 61.4 242.9 179.1 62.3 241.49 216.7 51.5 268.2 199.6 57.6 257.2 189.8 61.1 250.9 187.3 62.0 249.3 184.9 62.8 247.710 223.6 51.7 275.3 205.9 58.0 263.9 195.7 61.6 257.3 193.2 62.5 255.7 190.7 63.4 254.16 239.1 63.7 302.8 220.5 71.0 291.6 209.9 75.2 285.1 207.3 76.3 283.5 204.6 77.3 281.97 247.0 64.1 311.1 228.1 71.6 299.7 217.3 75.9 293.2 214.6 77.0 291.6 211.9 78.1 290.0

070EA 8 254.9 64.5 319.3 235.6 72.2 307.9 224.6 76.6 301.3 221.9 77.8 299.7 219.2 78.9 298.09 262.7 64.8 327.6 243.2 72.8 316.0 232.0 77.4 309.4 229.2 78.5 307.7 226.4 79.6 306.110 270.6 65.2 335.8 250.7 73.4 324.1 239.4 78.1 317.5 236.6 79.2 315.8 233.7 80.4 314.16 275.5 71.0 346.9 250.9 79.3 330.2 236.9 83.8 320.7 233.4 84.9 318.3 229.9 86.0 316.07 275.9 71.1 347.3 253.4 79.5 332.9 240.5 84.2 324.8 237.3 85.4 322.7 234.1 86.6 320.7

080EA 8 276.4 71.2 347.6 255.9 79.8 335.6 244.2 84.6 328.8 241.2 85.9 327.1 238.3 87.1 325.49 276.9 71.3 348.0 258.4 80.0 338.3 247.8 85.1 332.8 245.1 86.3 331.5 242.5 87.6 330.110 277.3 71.4 348.4 260.8 80.2 341.1 251.4 85.5 336.9 249.0 86.8 335.8 246.7 88.1 334.86 276.0 78.5 354.5 271.7 88.6 360.3 257.4 93.2 350.5 251.5 94.2 345.7 245.6 95.2 340.97 287.5 79.3 366.8 274.0 88.7 362.7 260.4 93.5 353.8 255.8 94.6 350.4 251.2 95.7 347.0

085EA 8 299.0 80.1 379.1 276.3 88.8 365.1 263.3 93.7 357.1 260.1 95.0 355.1 256.8 96.2 353.19 310.6 80.9 391.5 278.6 88.9 367.5 266.3 94.0 360.4 264.4 95.4 359.8 262.5 96.7 359.210 322.1 81.7 403.8 280.9 89.0 369.9 269.3 94.3 363.6 268.7 95.8 364.5 268.1 97.2 365.36 304.1 83.1 387.2 288.9 89.1 377.9 273.8 95.0 368.8 267.8 97.3 365.1 258.8 100.9 359.77 314.9 83.6 398.5 298.9 89.4 388.3 283.0 95.3 378.3 276.7 97.6 374.2 267.1 101.1 368.2

090EA 8 325.7 84.0 409.7 308.9 89.7 398.6 292.1 95.6 387.7 285.5 97.9 383.4 275.5 101.3 376.89 336.5 84.4 420.9 318.9 90.1 408.9 301.3 95.9 397.2 294.4 98.1 392.5 283.9 101.5 385.410 347.3 84.8 432.1 328.9 90.4 419.3 310.5 96.2 406.6 303.2 98.4 401.6 292.2 101.7 394.06 318.1 86.8 405.0 295.2 96.3 391.6 282.1 101.8 383.9 278.8 103.1 382.0 275.6 104.5 380.17 328.8 87.3 416.2 305.3 97.1 402.5 291.9 102.7 394.7 288.6 104.1 392.7 285.2 105.5 390.7

095EA 8 339.6 87.8 427.4 315.5 97.9 413.4 301.7 103.7 405.4 298.3 105.2 403.4 294.8 106.6 401.49 350.3 88.3 438.5 325.6 98.7 424.3 311.5 104.7 416.2 308.0 106.2 414.1 304.4 107.7 412.110 361.0 88.7 449.7 335.7 99.5 435.2 321.3 105.6 426.9 317.7 107.2 424.9 314.1 108.7 422.86 341.8 91.1 432.9 319.5 101.1 420.5 306.7 106.7 413.4 303.5 108.1 411.7 300.3 109.6 409.97 351.2 91.4 442.6 326.7 101.6 428.2 312.6 107.3 420.0 309.1 108.8 417.9 305.6 110.2 415.9

100EA 8 360.6 91.7 452.3 333.8 102.1 435.9 318.6 108.0 426.5 314.7 109.4 424.2 310.9 110.9 421.89 369.9 92.1 462.0 341.0 102.6 443.6 324.5 108.6 433.1 320.4 110.1 430.4 316.2 111.6 427.810 379.3 92.4 471.7 348.2 103.1 451.3 330.4 109.2 439.6 326.0 110.7 436.7 321.5 112.3 433.8

Notes:1. Ratings bases on HCFC-22, evaporator fouling of 0.044, evaporator temperature drop of 5.6°C and sea level altitude.2. For 208V units multiply capacity and EER by 0.983. Ratings are based on circuit #1 in lead position and circuit #2 in lag position.4. Interpolation is allowed; extrapolation is not permitted. Consult McQuay for performance outside the cataloged ratings.5. For LWT of 5°C and below please refer to application considerations for reciprocating chillers.6. Remote condenser units are not covered in the ARI Certification Program

Page 29: Reciprocating Chillers - Daikin Applied

Product Manual WHR-2 29

Table 15, R22, WHR110EA - WHR210EA, 60 Hz, SI UnitsCONDENSING TEMPERATURE (deg °C)

40°C 45°C 50°C 52°C 55°C Cap. Power THR Cap. Power THR Cap. Power THR Cap. Power THR Cap. Power THR

WHRUNITSIZE

LWT(°C)

kW kWi kW kW kWi kW kW kWi kW kW kWi kW kW kWi kW6 365.0 100.9 466.0 338.7 112.9 451.5 323.6 119.7 443.3 319.8 121.4 441.2 316.1 123.1 439.27 377.2 101.7 478.9 350.1 114.0 464.1 334.6 121.0 455.6 330.7 122.8 453.5 326.8 124.5 451.4

110EA 8 389.4 102.5 491.9 361.5 115.2 476.6 345.5 122.4 467.9 341.5 124.2 465.7 337.5 126.0 463.69 401.5 103.3 504.8 372.9 116.3 489.2 356.5 123.8 480.2 352.4 125.6 478.0 348.3 127.5 475.8

10 413.7 104.1 517.8 384.2 117.5 501.7 367.4 125.1 492.6 363.2 127.0 490.3 359.0 129.0 488.06 371.5 101.4 472.9 343.9 113.5 457.3 328.1 120.4 448.4 324.1 122.1 446.2 320.2 123.8 444.07 383.8 102.2 486.0 355.5 114.6 470.1 339.4 121.7 461.1 335.3 123.5 458.8 331.3 125.3 456.6

115EA 8 396.1 102.9 499.0 367.2 115.8 482.9 350.7 123.1 473.8 346.6 124.9 471.5 342.4 126.7 469.29 408.3 103.7 512.0 378.8 116.9 495.7 362.0 124.4 486.4 357.8 126.3 484.1 353.5 128.2 481.8

10 420.6 104.5 525.1 390.5 118.0 508.5 373.3 125.8 499.1 369.0 127.7 496.7 364.7 129.7 494.36 405.0 112.6 517.6 375.2 125.5 500.7 358.1 132.9 491.0 353.9 134.7 488.6 349.6 136.5 486.17 418.3 113.4 531.8 387.8 126.7 514.5 370.3 134.3 504.6 366.0 136.2 502.1 361.6 138.1 499.7

120EA 8 431.6 114.3 545.9 400.4 127.9 528.3 382.5 135.7 518.2 378.1 137.7 515.7 373.6 139.6 513.29 444.9 115.1 560.0 413.0 129.1 542.1 394.7 137.1 531.8 390.1 139.1 529.3 385.6 141.1 526.7

10 458.2 115.9 574.1 425.5 130.3 555.9 406.9 138.6 545.5 402.2 140.6 542.9 397.6 142.7 540.36 438.5 123.8 562.3 406.6 137.5 544.1 388.4 145.4 533.8 383.8 147.3 531.2 379.3 149.3 528.67 452.8 124.7 577.5 420.1 138.8 558.9 401.4 146.9 548.2 396.7 148.9 545.6 392.0 150.9 542.9

130EA 8 467.1 125.6 592.7 433.5 140.1 573.6 414.3 148.4 562.7 409.5 150.4 560.0 404.7 152.5 557.29 481.5 126.5 607.9 447.0 141.4 588.4 427.3 149.9 577.2 422.4 152.0 574.4 417.5 154.1 571.6

10 495.8 127.3 623.2 460.5 142.6 603.1 440.3 151.4 591.6 435.2 153.5 588.8 430.2 155.7 585.96 478.0 129.1 607.1 442.7 143.8 586.5 422.5 152.2 574.7 417.4 154.3 571.7 412.4 156.4 568.87 494.0 129.9 624.0 457.5 145.0 602.6 436.7 153.7 590.3 431.4 155.8 587.3 426.2 158.0 584.2

145EA 8 510.1 130.7 640.8 472.4 146.3 618.7 450.8 155.2 606.0 445.4 157.4 602.8 440.1 159.6 599.79 526.1 131.6 657.7 487.2 147.5 634.8 465.0 156.6 621.6 459.4 158.9 618.4 453.9 161.2 615.1

10 542.2 132.4 674.6 502.1 148.8 650.8 479.2 158.1 637.3 473.4 160.5 633.9 467.7 162.8 630.56 508.9 139.0 648.0 470.8 154.9 625.7 449.0 164.0 613.0 443.5 166.3 609.8 438.1 168.6 606.67 525.8 139.9 665.7 486.7 156.2 642.9 464.3 165.5 629.8 458.7 167.9 626.6 453.1 170.2 623.3

155EA 8 542.7 140.8 683.5 502.5 157.5 660.1 479.6 167.1 646.7 473.9 169.5 643.3 468.1 171.9 640.09 559.6 141.7 701.3 518.4 158.8 677.3 494.9 168.6 663.5 489.0 171.1 660.1 483.1 173.5 656.7

10 576.4 142.6 719.0 534.3 160.1 694.4 510.2 170.2 680.4 504.2 172.7 676.9 498.2 175.2 673.36 541.3 157.2 698.6 503.3 173.7 677.1 481.6 183.1 664.8 476.2 185.5 661.7 470.8 187.9 658.67 559.4 158.5 717.8 520.4 175.3 695.7 498.1 185.0 683.1 492.5 187.4 679.9 486.9 189.8 676.7

165EA 8 577.5 159.7 737.1 537.4 176.9 714.3 514.5 186.8 701.3 508.8 189.3 698.1 503.1 191.8 694.89 595.5 160.9 756.4 554.4 178.6 733.0 530.9 188.7 719.6 525.1 191.2 716.2 519.2 193.7 712.9

10 613.6 162.1 775.7 571.4 180.2 751.6 547.4 190.5 737.9 541.3 193.1 734.4 535.3 195.7 731.06 576.5 179.7 756.2 536.6 196.9 733.5 513.8 206.8 720.6 508.1 209.2 717.4 502.4 211.7 714.17 595.5 181.1 776.6 554.6 198.7 753.3 531.3 208.8 740.1 525.4 211.3 736.8 519.6 213.9 733.5

175EA 8 614.5 182.4 796.9 572.6 200.5 773.2 548.7 210.9 759.6 542.7 213.5 756.2 536.7 216.0 752.89 633.5 183.8 817.3 590.6 202.3 793.0 566.1 212.9 779.1 560.0 215.6 775.6 553.9 218.2 772.1

10 652.5 185.2 837.7 608.6 204.1 812.8 583.6 215.0 798.6 577.3 217.7 795.0 571.1 220.4 791.56 604.0 177.6 781.6 561.1 195.1 756.3 536.6 205.2 741.7 530.5 207.7 738.1 524.3 210.2 734.57 624.8 178.9 803.7 581.1 196.9 778.0 556.1 207.2 763.4 549.9 209.8 759.7 543.7 212.4 756.0

185EA 8 645.6 180.3 825.8 601.1 198.7 799.8 575.7 209.3 785.0 569.3 211.9 781.3 563.0 214.6 777.69 666.3 181.6 847.9 621.1 200.5 821.6 595.2 211.4 806.6 588.8 214.1 802.9 582.3 216.8 799.1

10 687.1 182.9 870.0 641.1 202.3 843.4 614.8 213.4 828.2 608.2 216.2 824.4 601.6 219.0 820.66 648.7 199.6 848.3 599.7 217.5 817.2 571.8 227.7 799.4 564.8 230.2 795.0 557.8 232.8 790.67 671.1 201.1 872.2 620.7 219.5 840.2 591.9 230.1 822.0 584.7 232.7 817.4 577.5 235.4 812.8

195EA 8 693.5 202.6 896.1 641.7 221.6 863.3 612.0 232.5 844.5 604.6 235.2 839.8 597.2 237.9 835.19 716.0 204.1 920.0 662.6 223.7 886.3 632.2 234.9 867.0 624.5 237.7 862.2 616.9 240.5 857.4

10 738.4 205.5 944.0 683.6 225.7 909.3 652.3 237.3 889.6 644.5 240.1 884.6 636.6 243.0 879.76 693.7 221.3 915.1 636.6 239.6 876.2 604.0 250.0 854.0 595.8 252.6 848.4 587.6 255.2 842.97 717.2 223.0 940.2 658.8 241.9 900.7 625.3 252.7 878.0 617.0 255.4 872.4 608.6 258.1 866.7

210EA 8 740.8 224.7 965.4 680.9 244.2 925.1 646.7 255.4 902.1 638.1 258.2 896.3 629.6 261.0 890.69 764.3 226.3 990.6 703.0 246.5 949.6 668.1 258.1 926.1 659.3 261.0 920.3 650.6 263.8 914.4

10 787.8 228.0 1015.7 725.2 248.8 974.0 689.4 260.8 950.2 680.5 263.7 944.2 671.5 266.7 938.3Notes:

1. Ratings based on HCFC-22, evaporator and condenser fouling of 0.044, evaporator and condenser temperature drop of 5.6°C.2. For 208V units multiply capacity and COP by 0.983. Ratings are based on circuit #1 in lead position and circuit #2 in lag position.4. Interpolation is allowed; extrapolation is not permitted. Consult McQuay for performance outside the cataloged ratings.5. kWi input is for compressors only. COP is for the entire unit, including compressors and control power.6. For LWT of 5°C and below please refer to application considerations for reciprocating chillers.

Page 30: Reciprocating Chillers - Daikin Applied

30 Product Manual WHR-2

Pressure Drop Curves

Figure 2, Evaporator Pressure Drop WHR 017 – WHR 210

Page 31: Reciprocating Chillers - Daikin Applied

Product Manual WHR-2 31

Figure 3, Condenser Pressure Drop WHR 017EW – WHR 090EW

Page 32: Reciprocating Chillers - Daikin Applied

32 Product Manual WHR-2

Figure 4, Condenser Pressure Drop WHR 095EW – WHR 210EW

Page 33: Reciprocating Chillers - Daikin Applied

Product Manual WHR-2 33

Electrical Data

Table 16, Compressor Amp Draw, WHR 017E - WHR 060ERated Load Amps (1) Locked Rotor Amps (2)

w/o SupplementalOverloads

w/ SupplementalOverloads

Across-The-LineStart

Part WindingStart

UnitSize

Voltage3-Phase

Freq(Hz)

Circuit 1 Circuit 2 Circuit 1 Circuit 2 Circuit 1 Circuit2

Circuit 1 Circuit 2

208 60 - - - 308 - 188 -

017 230 60 60 - - - 308 - 188 -

460 31 - - - 154 - 104 -

575 23 - - - 135 - 81 -

208 74 - - - 428 - 250 -

020 230 60 74 - - - 428 - 250 -

460 37 - - - 214 - 132 -

575 31 - - - 172 - 103 -

208 85 - - - 470 - 292 -

025 230 60 85 - - - 470 - 292 -

460 43 - - - 235 - 141 -

575 36 - - - 200 - 130 -

208 95 - - - 565 - 340 -

030 230 60 95 - - - 565 - 340 -

460 48 - - - 283 - 156 -

575 36 - - - 230 - 138 -

208 60 60 48 54 308 374 188 222

040 230 60 60 60 48 54 308 374 188 222

460 31 31 24 27 154 187 104 108

575 23 24 19 22 135 135 81 81

208 74 74 62 62 428 428 250 250

045 230 60 74 74 62 62 428 428 250 250

460 37 37 31 31 214 214 132 132

575 31 31 25 25 172 172 103 103

208 85 85 77 77 470 470 292 292

050 230 60 85 85 77 77 470 470 292 292

460 43 43 38 38 235 235 141 141

575 36 36 31 31 200 200 130 130

208 85 95 76 84 470 565 292 340

060 230 60 85 95 76 84 470 565 292 340

460 43 48 38 42 235 283 141 156

575 36 36 31 34 200 230 130 138

NOTES:1. Compressor RLA values are for wire sizing purposes only and do not reflect normal operating current draw.2. Compressor LRA values for part winding start are for the first winding.3. Unit wire sizing amps are equal to 125% of the largest compressor-motor RLA plus 100% of RLA of all other loads in the circuit

including control transformer. Wire size amps for separate 115V control circuit power is 11 amps.4. Single point power supply requires a single fused disconnect to supply electrical power to the unit.5. Supplemental overloads are used in conjunction with standard inherent overload protection. The supplemental overloads:

• Reduce wire sizing amps• Add additional protection• Lower compressor amperage

6. Part Winding Start is a special option on 460 and 575 volt units.

Page 34: Reciprocating Chillers - Daikin Applied

34 Product Manual WHR-2

Table 17, Compressor Amp Draw, WHR 070E - WHR 120ERated Load Amps (1) Locked Rotor Amps (2)

w/o SupplementalOverloads

w/ SupplementalOverloads

Across-The-Line Part WindingUnitSize

Voltage3-Phase

Freq.(Hz)

Circuit 1 Circuit 2 Circuit 1 Circuit 2 Circuit 1 Circuit 2 Circuit 1 Circuit 2

208 122 122 115 115 650 650 400 400

070 230 60 122 122 100 100 594 594 340 340

460 60 60 50 50 297 297 195 195

575 42 42 40 40 245 245 152 152

208 135 135 124 124 754 754 463 463

080 230 60 127 127 108 108 594 594 340 340

460 64 64 54 54 297 297 195 195

575 48 48 43 43 245 245 152 152

208 135 162 124 147 754 1070 463 654

085 230 60 127 162 108 147 594 1070 340 654

460 64 82 54 74 297 535 195 330

575 48 68 43 59 245 405 152 262

208 162 162 147 147 1070 1070 654 654

090 230 60 162 162 147 147 1070 1070 654 654

460 82 82 74 74 535 535 330 330

575 68 68 59 59 405 405 262 262

208 74 , 85 74 , 85 62 , 76 62 , 76 428 , 470 428 , 470 250 , 292 250 , 292

095 230 60 74 , 85 74 , 85 62 , 76 62 , 76 428 , 470 428 , 470 250 , 292 250 , 292

460 37 , 43 37 , 43 31 , 38 31 , 38 214 , 235 214 , 235 132 , 141 132 , 141

575 31 , 36 31 , 36 25 , 31 25 , 31 172 , 200 172 , 200 103 , 130 103 , 130

208 74 , 95 74 , 95 62 , 84 62 , 84 428 , 565 428 , 565 250 , 340 250 , 340

100 230 60 74 , 95 74 , 95 62 , 84 62 , 84 428 , 565 428 , 565 250 , 340 250 , 340

460 37 , 48 37 , 48 31 , 42 31 , 42 214 , 283 214 , 283 132 , 156 132 , 156

575 31 , 36 31 , 36 25 , 34 25 , 34 172 , 230 172 , 230 103 , 138 103 , 138

208 122 , 74 122 , 74 115 , 62 115 , 62 650 , 428 650 , 428 400 , 250 400 , 250

110 230 60 122 , 74 122 , 74 100 , 62 100 , 62 594 , 428 594 , 428 340 , 250 340 , 250

460 60 , 37 60 , 37 50 , 31 50 , 31 297 , 214 297 , 214 195 , 132 195 , 132

575 42 , 31 42 , 31 40 , 25 40 , 25 245 , 172 245 , 172 152 , 103 152 , 103

208 122 , 74 122 , 74 115 , 62 115 , 62 650 , 428 650 , 428 400 , 250 400 , 250

115 230 60 122 , 74 122 , 74 100 , 62 100 , 62 594 , 428 594 , 428 340 , 250 340 , 250

460 60 , 37 60 , 37 50 , 31 50 , 31 297 , 214 297 , 214 195 , 132 195 , 132

575 42 , 31 42 , 31 40 , 25 40 , 25 245 , 172 245 , 172 152 , 103 152 , 103

208 122 , 74 122 , 122 115 , 62 115 , 115 650 , 428 650 , 650 400 , 250 400 , 400

120 230 60 122 , 74 122 , 122 100 , 62 100 , 100 594 , 428 594 , 594 340 , 250 340 , 340

460 60 , 37 60 , 60 50 , 31 50 , 50 297 , 214 297 , 297 195 , 132 195 , 195

575 42 , 31 42 , 42 40 , 25 40 , 40 245 , 172 245 , 245 152 , 103 152 , 152

NOTES:1. Compressor RLA values are for wire sizing purposes only and do not reflect normal operating current draw.2. Compressor LRA values for part winding start are for the first winding.3. Unit wire sizing amps are equal to 125% of the largest compressor-motor RLA plus 100% of RLA of all other loads in the circuit

including control transformer. Wire size amps for separate 115V control circuit power is 11 amps.4. Single point power supply requires a single fused disconnect to supply electrical power to the unit.5. Supplemental overloads are used in conjunction with standard inherent overload protection. The supplemental overloads:

• Reduce wire sizing amps• Add additional protection• Lower compressor amperage

6. Part Winding Start is a special option on 460 and 575 volt units

Page 35: Reciprocating Chillers - Daikin Applied

Product Manual WHR-2 35

Table 18, Compressor Amp Draw, WHR 130E - WHR 210ERated Load Amps (1) Locked Rotor Amps (2)

w/o SupplementalOverloads

w/ SupplementalOverloads

Across-The-Line Part WindingUnitSize

Voltage3-Phase

Freq.(Hz)

Circuit 1 Circuit 2 Circuit 1 Circuit 2 Circuit 1 Circuit 2 Circuit 1 Circuit 2

208 122 , 122 122 , 122 115 , 115 115 , 115 650 , 650 650 , 650 400 , 400 400 , 463

130 230 60 122 , 122 122 , 122 100 , 100 100 , 100 594 , 594 594 , 594 340 , 340 340 , 340

460 60 , 60 60 , 60 50 , 50 50 , 50 297 , 297 297 , 297 195 , 195 195 , 195

575 42 , 42 42 , 42 40 , 40 40 , 40 245 , 245 245 , 245 152 , 152 152 , 152

208 122 , 122 122 , 135 115 , 115 115 , 124 650 , 650 650 , 754 400 , 400 400 , 463

145 230 60 122 , 122 122 , 127 100 , 100 100 , 108 594 , 594 594 , 594 340 , 340 340 , 340

460 60 , 60 60 , 64 50 , 50 50 , 54 297 , 297 297 , 297 195 , 195 195 , 195

575 42 , 42 42 , 48 40 , 40 40 , 43 245 , 245 245 , 245 152 , 152 152 , 152

208 135 , 135 135 , 135 124 , 124 124 , 124 754 , 754 754 , 754 463 , 463 463 , 463

155 230 60 127 , 127 127 , 127 108 , 108 108 , 108 594 , 594 594 , 594 340 , 340 340 , 340

460 64 , 64 64 , 64 54 , 54 54 , 54 297 , 297 297 , 297 195 , 195 195 , 195

575 48 , 48 48 , 48 43 , 43 43 , 43 245 , 245 245 , 245 152 , 152 152 , 152

208 135 , 162 135 , 162 124 , 147 124 , 147 754 , 1070 754 , 1070 463 , 654 463 , 654

165 230 60 127 , 162 127 , 162 108 , 147 108 , 147 594 , 1070 594 , 1070 340 , 654 340 , 654

460 64 , 82 64 , 82 54 , 74 54 , 74 297 , 535 297 , 535 195 , 330 195 , 330

575 48 , 68 48 , 68 43 , 59 43 , 59 245 , 405 245 , 405 152 , 262 152 , 262

208 135 , 202 135 , 202 124 , 176 124 , 176 754 , 1070 754 , 1070 463 , 654 463 , 654

175 230 60 127 , 202 127 , 202 108 , 176 108 , 176 594 , 1070 594 , 1070 340 , 654 340 , 654

460 64 , 93 64 , 93 54 , 88 54 , 88 297 , 535 297 , 535 195 , 330 195 , 330

575 48 , 75 48 , 75 43 , 71 43 , 71 245 , 405 245 , 405 152 , 262 152 , 262

208 162 , 162 162 , 162 147 , 147 147 , 147 1070 , 1070 1070 , 1070 654 , 654 654 , 654

185 230 60 162 , 162 162 , 162 147 , 147 147 , 147 1070 , 1070 1070 , 1070 654 , 654 654 , 654

460 82 , 82 82 , 82 74 , 74 74 , 74 535 , 535 535 , 535 330 , 330 330 , 330

575 68 , 68 68 , 68 59 , 59 59 , 59 405 , 405 405 , 405 262 , 262 262 , 262

208 162 , 202 162 , 202 147 , 176 147 , 176 1070 , 1070 1070 , 1070 654 , 654 654 , 654

195 230 60 162 , 202 162 , 202 147 , 176 147 , 176 1070 , 1070 1070 , 1070 654 , 654 654 , 654

460 82 , 93 82 , 93 74 , 88 74 , 88 535 , 535 535 , 535 330 , 330 330 , 330

575 68 , 75 68 , 75 59 , 71 59 , 71 405 , 405 405 , 405 262 , 262 262 , 262

208 202 , 202 202 , 202 176 , 176 176 , 176 1070 , 1070 1070 , 1070 654 , 654 654 , 654

210 230 60 202 , 202 202 , 202 176 , 176 176 , 176 1070 , 1070 1070 , 1070 654 , 654 654 , 654

460 88 , 93 88 , 93 88 , 88 88 , 88 535 , 535 535 , 535 330 , 330 330 , 330

575 72 , 75 72 , 75 71 , 71 71 , 71 405 , 405 405 , 405 262 , 262 262 , 262

NOTES:1. Compressor RLA values are for wire sizing purposes only and do not reflect normal operating current draw.2. Compressor LRA values for part winding start are for the first winding.3. Unit wire sizing amps are equal to 125% of the largest compressor-motor RLA plus 100% of RLA of all other loads in the circuit

including control transformer. Wire size amps for separate 115V control circuit power is 11 amps.4. Single point power supply requires a single fused disconnect to supply electrical power to the unit.5. Supplemental overloads are used in conjunction with standard inherent overload protection. The supplemental overloads:

• Reduce wire sizing amps• Add additional protection• Lower compressor amperage

6. Part Winding Start is a special option on 460 and 575 volt units.

Page 36: Reciprocating Chillers - Daikin Applied

36 Product Manual WHR-2

Table 19, Wire Sizing Amps, WHR 017E - WHR 080Ew/o Supplemental Overloads (1) w/ Supplemental Overloads (1)

Minimum Circuit Ampacity (MCA) Minimum Circuit Ampacity (MCA)

Multiple Point PowerSupply(3)

Multiple Point PowerSupply(3)

UnitSize

Voltage3-Phase

Freq.(Hz) Single Point

PowerSupply(2) Circuit 1 Circuit 2

SinglePointPower

Supply(2) Circuit 1 Circuit 2

208 75 - - 60 - -

017 230 60 75 - - 60 - -

460 39 - - 30 - -

575 29 - - 24 - -

208 93 - - 78 - -

020 230 60 93 - - 78 - -

460 46 - - 39 - -

575 39 - - 31 - -

208 106 - - 95 - -

025 230 60 106 - - 95 - -

460 54 - - 48 - -

575 45 - - 39 - -

208 119 - - 105 - -

030 230 60 119 - - 105 - -

460 60 - - 53 - -

575 45 - - 43 - -

208 135 75 75 116 60 68

040 230 60 135 75 75 116 60 68

460 70 39 39 58 30 34

575 53 29 30 47 24 28

208 167 93 93 140 78 78

045 230 60 167 93 93 140 78 78

460 83 46 46 70 39 39

575 70 39 39 56 31 31

208 191 106 106 173 96 96

050 230 60 191 106 106 173 96 96

460 97 54 54 86 48 48

575 81 45 45 70 39 39

208 204 106 105 183 95 105

060 230 60 204 106 105 183 95 105

460 103 54 53 91 48 53

575 81 45 45 74 39 43

208 275 153 153 259 144 144

070 230 60 254 141 141 225 125 125

460 135 75 75 113 63 63

575 95 53 53 90 50 50

208 304 169 169 279 155 155

080 230 60 286 159 159 243 135 135

460 144 80 80 122 68 68

575 108 60 60 97 54 54

NOTES:1. Unit wire sizing amps are equal to 125% of the largest compressor-motor RLA plus 100% of RLA of all other loads in the circuit including

control transformer. Wire size amps for separate 115V control circuit power is 11 amps.2. Single point power supply requires a single fused disconnect to supply electrical power to the unit.3. Multiple point power supply requires three independent power circuits with separate fused disconnects. (Two compressor circuits, one

control circuit.)4. Supplemental overloads are used in conjunction with standard inherent overload protection. The supplemental overloads:

• Reduce wire sizing amps• Add additional protection• Lower compressor amperage

Page 37: Reciprocating Chillers - Daikin Applied

Product Manual WHR-2 37

Table 20,Wire Sizing, WHR 085E - WHR 130Ew/o Supplemental Overloads (1) w/ Supplemental Overloads (1)

Minimum Circuit Ampacity (MCA) Minimum Circuit Ampacity (MCA)

Multiple Point PowerSupply(3)

Multiple Point PowerSupply(3)

UnitSize

Voltage3-Phase

Freq(Hz)

SinglePointPower

Supply(2) Circuit 1 Circuit 2

Single PointPower

Supply(2) Circuit 1 Circuit 2

208 338 169 203 308 155 184

085 230 60 330 159 203 292 135 184

460 167 80 103 147 68 93

575 133 60 85 117 54 74

208 365 203 203 331 184 184

090 230 60 365 203 203 331 184 184

460 185 103 103 167 93 93

575 153 85 85 133 74 74

208 339 180 180 297 158 158

095 230 60 339 180 180 297 158 158

460 171 91 91 148 79 79

575 143 76 76 120 64 64

208 362 193 193 313 167 167

100 230 60 362 193 193 313 167 167

460 182 97 97 157 84 84

575 143 76 76 127 68 68

208 423 227 227 383 206 206

110 230 60 402 215 215 349 187 187

460 209 112 112 175 94 94

575 157 84 84 140 75 75

208 471 227 227 383 206 206

115 230 60 441 215 215 349 187 187

460 232 112 112 175 94 94

575 168 84 84 140 75 75

208 519 227 275 436 206 259

120 230 60 480 215 255 387 187 225

460 255 112 135 194 94 113

575 179 84 95 155 75 90

208 535 275 275 498 259 259

130 230 60 498 255 255 425 225 225

460 260 135 135 213 113 113

575 186 95 95 170 90 90

NOTES:1. Unit wire sizing amps are equal to 125% of the largest compressor-motor RLA plus 100% of RLA of all other loads in the circuit

including control transformer. Wire size amps for separate 115V control circuit power is 11 amps.2. Single point power supply requires a single fused disconnect to supply electrical power to the unit.3. Multiple point power supply requires three independent power circuits with separate fused disconnects. (Two compressor

circuits, one control circuit) and is a factory special.4. Supplemental overloads are used in conjunction with standard inherent overload protection. The supplemental overloads:

• Reduce wire sizing amps• Add additional protection• Lower compressor amperage

Page 38: Reciprocating Chillers - Daikin Applied

38 Product Manual WHR-2

Table 21, Wire Sizing Amps, WHR 145E - WHR 210Ew/o Supplemental Overloads (1) w/ Supplemental Overloads (1)

Minimum Circuit Ampacity (MCA) Minimum Circuit Ampacity (MCA)

Multiple Point PowerSupply(3)

Multiple Point PowerSupply(3)

UnitSize

Voltage3-Phase

Freq.(Hz) Single Point

PowerSupply(2) Circuit 1 Circuit 2

Single PointPower

Supply(2) Circuit 1 Circuit 2

208 535 275 291 500 259 270

230 60 498 255 272 435 225 235

145 460 260 135 135 218 113 118

575 186 95 102 174 90 94

208 574 304 304 527 279 279

230 60 540 286 286 459 243 243

155 460 272 144 144 230 122 122

575 204 108 108 183 97 97

208 635 338 338 578 308 308

230 60 619 330 330 547 292 292

165 460 313 167 167 275 147 147

575 249 133 133 219 117 117

208 725 388 388 644 344 344

230 60 709 380 380 612 328 328

175 460 326 174 174 306 164 164

575 258 138 138 246 132 132

208 689 365 365 625 331 331

230 60 689 365 365 625 331 331

185 460 349 185 185 315 167 167

575 289 153 153 251 133 133

208 779 415 415 661 367 367

230 60 779 415 415 661 367 367

195 460 362 192 192 346 184 184

575 298 158 158 278 148 148

208 859 455 455 748 396 396

230 60 859 455 455 748 396 396

210 460 374 198 198 374 198 198

575 306 162 162 302 160 160

NOTES:1. Unit wire sizing amps are equal to 125% of the largest compressor-motor RLA plus 100% of RLA of all other loads in the circuit including

control transformer. Wire size amps for separate 115V control circuit power is 11 amps.2. Single point power supply requires a single fused disconnect to supply electrical power to the unit.3. Multiple point power supply requires three independent power circuits with separate fused disconnects. (Two compressor circuits,

one control circuit) and is a factory special.

Page 39: Reciprocating Chillers - Daikin Applied

Product Manual WHR-2 39

Table 22, Single Point Fuse Sizing, WHR 017E - WHR 080ERecommended Fuse Size(1) Maximum Fuse Size(2)

Single Point Power Single Point Power

w/o Supplemental w/ Supplemental w/o Supplemental w/Supplemental

UnitSize

Voltage3-Phase

Freq.(Hz)

Overloads Overloads Overloads Overloads

208 110 - 125 -

017 230 60 110 - 125 -460 50 - 70 -

575 40 - 50 -

208 125 - 150 -

020 230 60 125 - 150 -460 70 - 80 -

575 60 - 70 -

208 150 - 175 -

025 230 60 150 - 175 -460 80 - 90 -

575 70 - 80 -

208 175 - 200 -

030 230 60 175 - 200 -460 80 - 100 -

575 70 - 80 -

208 175 150 175 150

040 230 60 175 150 175 150460 90 80 100 80

575 70 60 70 60

208 200 175 225 200

045 230 60 200 175 225 200460 200 90 110 100

575 90 70 100 80

208 225 225 250 250

050 230 60 225 225 250 250460 110 100 125 110

575 100 90 110 100

208 250 225 250 250

060 230 60 250 225 250 250460 125 110 150 125

575 100 90 110 100

208 350 350 350 350

070 230 60 300 300 350 300460 175 150 175 150

575 110 110 125 125

208 400 350 400 400

080 230 60 350 300 400 350460 175 150 200 175

575 125 125 150 125

NOTES:1. "Recommended Fuse Size" are selected at approximately 150% of the largest compressor RLA, plus 100% of all other

loads in the circuit.2. "Maximum Fuse Sizes" are selected at approximately 225% of the largest compressor RLA, plus 100% of all other loads

in the circuit.3. Supplemental overloads are used in conjunction with standard inherent overload protection. The supplemental overloads:

• Reduce wire sizing amps• Add additional protection• Lower compressor amperage

Page 40: Reciprocating Chillers - Daikin Applied

40 Product Manual WHR-2

Table 23, Single Point Fuse Sizing, WHR 085E - WHR 145ERecommended Fuse Size(1) Maximum Fuse Size(2)

Single Point Power Single Point Power

w/o Supplemental w/ Supplemental w/o Supplemental w/Supplemental

UnitSize

Voltage3-Phase

Freq.(Hz)

Overloads Overloads Overloads Overloads

208 450 400 500 450

085 230 60 400 400 450 400460 200 200 225 200

575 175 150 200 175

208 450 400 500 450

090 230 60 450 400 500 450460 225 200 250 225

575 175 150 200 175

208 400 350 400 350

095 230 60 400 350 400 350460 200 175 200 175

575 175 150 175 150

208 450 350 450 350

100 230 60 450 350 450 350460 225 175 225 175

575 175 150 175 150

208 500 450 500 450110 230 60 450 400 500 400

460 225 200 250 225

575 175 175 175 175

208 500 450 500 450

115 230 60 450 400 500 400460 250 200 250 225

575 175 175 175 175

208 500 500 500 500

120 230 60 500 450 500 450460 250 225 250 225

575 200 175 200 175

208 600 600 600 600

130 230 60 500 500 500 500460 300 250 300 250

575 200 200 200 200

208 600 600 600 600

145 230 60 600 500 600 500460 300 250 300 250

575 225 200 225 200

NOTES:1. "Recommended Fuse Size" are selected at approximately 150% of the largest compressor RLA, plus 100%

of all other loads in the circuit.2. "Maximum Fuse Sizes" are selected at approximately 225% of the largest compressor RLA, plus 100% of all

other loads in the circuit.

Page 41: Reciprocating Chillers - Daikin Applied

Product Manual WHR-2 41

Table 24, Single Point Fuse Size, WHR 155E - WHR 210ERecommended Fuse Size(1) Maximum Fuse Size(2)

Single Point Power Single Point Power

w/o Supplemental w/ Supplemental w/o Supplemental w/Supplemental

UnitSize

Voltage3-Phase

Freq.(Hz)

Overloads Overloads Overloads Overloads

208 700 600 700 600

155 230 60 600 500 600 500

460 300 250 300 250

575 225 200 250 225

208 700 700 700 700

165 230 60 700 600 700 600

460 350 300 350 300

575 300 250 300 250

208 800 800 800 800

175 230 60 800 700 800 700460 400 350 400 350

575 300 300 300 300

208 800 700 800 700

185 230 60 800 700 800 700460 400 350 400 350

575 350 300 350 300

208 800 800 800 800

195 230 60 800 800 800 800460 400 400 450 400

575 350 300 350 300

208 1000 800 1000 800

210 230 60 1000 800 1000 800460 450 450 450 450

575 350 350 350 350

NOTES:1. "Recommended Fuse Size" are selected at approximately 150% of the largest compressor RLA, plus 100%

of all other loads in the circuit.2. "Maximum Fuse Sizes" are selected at approximately 225% of the largest compressor RLA, plus 100% of all

other loads in the circuit.

Page 42: Reciprocating Chillers - Daikin Applied

42 Product Manual WHR-2

Table 25, Multiple-Point Fuse Sizing, WHR 040E - WHR 145ERecommended Fuse Size(1)

Multiple Point PowerMaximum Fuse Size(2)Multiple Point Power

Circuit 1 Circuit 2 Circuit 1 Circuit 2UnitSize

Voltage3-Phase

Freq.(Hz) w/o

SupplementalOverloads

w/Supplemental

Overloads

w/oSupplemental

Overloads

w/Supplemental

Overloads

w/oSupplemental

Overloads

w/Supplemental

Overloads

w/oSupplemental

Overloads

w/Supplemental

Overloads

208 110 90 110 100 125 100 125 110040 230 60 110 90 110 100 125 100 125 110

460 60 45 60 50 70 50 70 60208 125 150 125 150 150 125 150 125

045 230 60 125 150 125 150 150 125 150 125460 70 80 70 80 80 70 80 70575 60 70 60 70 70 50 70 50208 150 125 150 125 175 150 175 150

050 230 60 150 125 150 125 175 150 175 150460 80 70 80 70 90 80 90 80575 70 60 70 60 80 70 80 70208 150 125 150 150 175 150 200 175

060 230 60 150 125 150 150 175 150 200 175460 80 70 90 80 90 80 100 90575 70 60 70 60 80 70 80 70208 225 200 225 200 250 250 250 250

070 230 60 225 175 225 175 250 225 250 225460 110 90 110 90 125 110 125 110575 80 70 80 70 90 90 90 90208 225 225 225 225 300 250 300 250

080 230 60 225 200 225 200 250 225 250 225460 110 100 110 100 125 110 125 110575 90 80 90 80 100 90 100 90208 250 225 300 250 300 250 350 300

085 230 60 225 200 300 250 250 225 350 300460 110 100 150 125 125 110 175 150575 90 80 125 100 100 90 150 125208 300 250 300 250 350 300 350 300

090 230 60 300 250 300 250 350 300 350 300460 150 125 150 125 175 150 175 150575 125 100 125 100 150 125 150 125208 225 200 225 200 250 225 250 225

095 230 60 225 200 225 200 250 225 250 225460 110 100 110 100 125 110 125 110575 100 80 100 80 110 90 110 90208 225 200 225 200 250 250 250 250

100 230 60 225 200 225 200 250 250 250 250460 110 100 110 100 125 125 125 125575 90 90 90 90 110 100 110 100208 300 250 300 250 300 300 300 300

110 230 60 250 225 250 225 300 250 300 250460 150 110 150 110 150 125 150 125575 100 90 100 90 125 110 125 110208 300 250 300 250 300 300 300 300

115 230 60 350 225 250 225 300 250 300 250460 150 110 150 110 150 125 150 125575 100 90 100 90 125 110 125 110208 300 250 350 300 300 300 350 350230 60 250 225 300 250 300 250 350 300

120 460 150 110 175 125 150 125 175 150575 110 90 110 110 125 110 125 125208 350 300 350 300 350 350 350 350

130 230 60 300 250 300 250 350 300 350 300460 175 125 175 125 175 150 175 150575 110 110 110 110 125 125 125 125208 350 300 400 350 350 350 400 350

145 230 60 300 250 350 300 350 300 350 300460 175 125 175 150 175 150 175 150575 110 110 110 110 125 125 125 125

NOTES: 1. "Recommended Fuse Size" are selected at approximately 150% of the largest compressor RLA, plus 100% of all other circuit loads. 2. "Maximum Fuse Sizes" are selected at approximately 225% of the largest compressor RLA, plus 100% of all other loads.

Page 43: Reciprocating Chillers - Daikin Applied

Product Manual WHR-2 43

3. Supplemental overloads are used in conjunction with standard inherent overload protection. The supplemental overloads:• Reduce wire sizing amps• Add additional protection• Lower compressor amperage

Table 26, Multiple Point Fuse Size, WHR 155E - WHR 210ERecommended Fuse Size(1) Multiple Point Power Maximum Fuse Size(2) Multiple Point Power

Circuit 1 Circuit 2 Circuit 1 Circuit 2UnitSize

Voltage3-Phase

Freq.(Hz) w/o

Supplemental

Overloads

w/Supplementa

lOverloads

w/oSupplementa

lOverloads

w/Supplementa

lOverloads

w/oSupplementa

lOverloads

w/Supplementa

lOverloads

w/oSupplementa

lOverloads

w/Supplementa

lOverloads

208 400 350 400 350 400 400 400 400

155 230 60 350 300 350 300 400 350 400 350

460 175 150 175 150 200 175 200 175

575 125 110 125 110 150 125 150 125

208 400 400 400 400 500 450 500 450

165 230 60 400 350 400 350 450 400 450 400

460 200 175 200 175 225 200 225 200

575 175 150 175 150 200 175 200 175

208 450 450 450 450 500 500 500 500

175 230 60 450 450 450 450 500 500 500 500

460 225 225 225 225 250 250 250 250

575 175 175 175 175 200 200 200 200

208 500 400 500 400 500 450 500 450

185 230 60 500 400 500 400 500 450 500 450

460 225 200 225 200 250 225 250 225

575 200 175 200 175 200 175 200 175

208 500 450 500 450 600 500 600 500

195 230 60 500 450 500 450 600 500 600 500

460 225 225 225 225 250 250 250 250

575 200 175 200 175 225 200 225 200

208 600 450 600 450 600 500 600 500

210 230 60 600 450 600 450 600 500 600 500

460 250 225 250 225 250 250 250 250

575 200 200 200 200 225 225 225 225

NOTES: 1. "Recommended Fuse Size" are selected at approximately 150% of the largest compressor RLA, plus 100% of all other circuit loads. 2. "Maximum Fuse Sizes" are selected at approximately 225% of the largest compressor RLA, plus 100% of all other loads. 3. Supplemental overloads are used in conjunction with standard inherent overload protection. The supplemental overloads:

• Reduce wire sizing amps• Add additional protection• Lower compressor amperage

Page 44: Reciprocating Chillers - Daikin Applied

44 Product Manual WHR-2

Field Wiring DiagramFigure 5, Field Wiring Diagram

WHR 017EW - 030EW only

WHR 040EW - 220EW only

Field connection terminal

Field wiring

Page 45: Reciprocating Chillers - Daikin Applied

Product Manual WHR-2 45

Physical Data

EW Water-CooledTable 27, WHR-017EW - WHR-030EWWHR UNIT SIZE 017EW 020EW 025EW 030EWUnit capacity @ ARI conditionstons, (kW) (1) 17.7 (62.3) 21.7 (76.4) 27.0 (95.0) 30.2 (106.3)No. Circuits 1 1 1 1COMPRESSORSNominal Horsepower 20 25 30 30Number 1 1 1 1Speed RPM 1750 1750 1750 1750No. of Cylinders 4 4 4 6Unloading Steps 100-50-0 100-50-0 100-50-0 100-67-33-0Oil Charge oz., (l) 135 (4.0) 130 (3.8) 140 (4.1) 140 (4.1)Discharge Valve In., (mm) 1 3/8 (35) 1 3/8 (35) 1 3/8 (35) 1 5/8 (41)CONDENSERSNumber 1 1 1 1Diameter, in., (mm) 8 5/8 (219) 8 5/8 (219) 8 5/8 (219) 8 5/8 (219)Tube Length, in., (mm) 96 (2438) 96 (2438) 96 (2438) 96 (2438)Design W.P.PSIG, (kPa): Refrigerant Side 450 (3104) 450 (3104) 450 (3104) 450 (3104) Water Side 225 (1550) 225 (1550) 225 (1550) 225 (1550)No. of Passes 2 2 2 2Pump-Out Capacity, lb., (kg) (2) 104 (47) 104 (47) 100 (45) 91 (41)Connections: Water Inlet & Outlet, in., (mm)(3)

2 (51) 2 (51) 2 (51) 2 (51)

Relief Valve, Flare In., (mm) 5/8 (16) 5/8 (16) 5/8 (16) 5/8 (16) Purge Valve, Flare In., (mm) 1/4 (6) 1/4 (6) 1/4 (6) 1/4 (6) Liquid Subcooling Integral Integral Integral IntegralEVAPORATORNo. Refrigerant Circuits 1 1 1 1Diameter, in., (mm) 8 (203) 8 (203) 8 (203) 8 (203)Tube Length, in., (mm) 60 (1524) 60 (1524) 72 (1829) 84 (2134)Water Volume, gallons, (l) 6.3 (.4) 6.3 (.4) 7.6 (.5) 9.0 (.6)Refrigerant Side D.W.P.Psig, (kPa)

200 (1379) 200 (1379) 200 (1379) 200 (1379)

Water Side D.W.P,. psig, (kPa) 175 (1207) 175 (1207) 175 (1207) 175 (1207)Water Connections: Inlet & Outlet, in., (mm) (3) 2 (51) 2 (51) 2 (51) 2 (51) Drain & Vent (NPT INT.) 3/4 (19)/1/4 (6) 3/4 (19)/1/4 (6) 3/4 (19)/1/4 (6) 3/4 (19)/1/4 (6)DIMENSIONSLength In., (mm) 104 1/4 (2648) 104 1/4 (2648) 104 1/2 (2578) 106 (2692)Width In., (mm) 26 1/4 (667) 26 1/4 (667) 29 1/2 (749) 29 1/2 (749)Height In., (mm) 46 1/2 (1181) 46 1/2 (1181) 47 1/2 (1207) 46 1/2 (1181)WEIGHTSOperating Weight, lb., (kg) 1478 (671) 1498 (680) 1654 (750) 1726 (783)Shipping Weight, lb., (kg) 1573 (714) 1590 (721) 1747 (792) 1806 (819)Operating Charge, lb., (kg) R-22 40 (18) 42 (19) 50 (23) 52 (24)Operating Charge, lb., (kg) R-134a 42 (19) 44 (20) 53 (24) 55 (25)Notes:1. Certified in accordance with ARI Standard 550/590-98.2. Full R-22 at 90°F (32°C) per refrigerant circuit.3. NPT external WHR017-030.

Page 46: Reciprocating Chillers - Daikin Applied

46 Product Manual WHR-2

Table 28, WHR-040EW - WHR-070EWWHR UNIT SIZE 040EW 045EW 050EW 060EW 070EWCapacity @ ARI conditionstons, (kW) 38.0 (133.8) 44.0 (154.9) 51.5 (181.3) 58.5 (205.9) 70.5 (248.2)No. Circuits 2 2 2 2 2COMPRESSORSNominal Horsepower 20 22 25 25 30 30 30 30 35 35Number 1 1 1 1 1 1 1 1 1 1Speed RPM 1750 1750 1750 1750 1750No. of Cylinders 4 4 4 4 4 4 4 6 6 6Unloading Steps 100-75-50-25-0 100-75-50-25-0 100-75-50-25-0 100-83-58-25-0 100-83-66-50-33-16-0Oil Charge oz., (l) 135 (4.0) 130 (3.8) 130 (3.8) 130 (3.8) 140 (4.1) 140 (4.1) 140 (4.1) 140 (4.1) 140 (4.1) 140 (4.1)Discharge Valve in. (mm) 1 3/8 (35) 1 3/8 (35) 1 3/8 (35) 1 3/8 (35) 1 3/8 (35) 1 3/8 (35) 1 3/8 (35) 1 5/8 (41) 1 5/8 (41) 1 5/8 (41)CONDENSERSNumber 2 2 2 2 2Diameter, in. (mm) 8 5/8 (219 8 5/8 (219 8 5/8 (219 8 5/8 (219 8 5/8 (219 8 5/8 (219 8 5/8 (219 8 5/8 (219 8 5/8 (219 8 5/8 (219Tube Length, in. (mm) 96 (2438) 96 (2438) 96 (2438) 96 (2438) 96 (2438) 96 (2438) 96 (2438) 96 (2438) 96 (2438) 96 (2438)Design W.P.PSIG, (kPa): Refrigerant Side 450 (3104) 450 (3104) 450 (3104) 450 (3104) 450 (3104) Water Side 225 (1550) 225 (1550) 225 (1550) 225 (1550) 225 (1550)No. of Passes 2 2 2 2 2 2 2 2 2 2Pump-Out Capacity, lb. (kg) (2) 130 (60) 130 (60) 125 (58) 125 (58) 125 (58) 125 (58) 116 (53) 116 (53) 116 (53) 116 (53)Connections : Water Inlet & Outlet, In. (mm)(3)

2 1/2 (64) 2 1/2 (64) 2 1/2 (64) 2 1/2 (64) 2 1/2 (64) 2 1/2 (64) 2 1/2 (64) 2 1/2 (64) 2 1/2 (64) 2 1/2 (64)

Relief Valve, Flare in. (mm) 1/2 (13) 1/2 (13) 1/2 (13) 1/2 (13) 1/2 (13) Purge Valve, Flare in. (mm) 1/4 & 1/2 1/4 & 1/2 1/4 & 1/2 1/4 & 1/2 1/4 & 1/2

(6) & (13) (6) & (13) (6) & (13) (6) & (13) (6) & (13) Liquid Subcooling Integral Integral Integral Integral IntegralEVAPORATORNo. Refrigerant Circuits 2 2 2 2 2Diameter, in., (mm) 10 3/4 (273) 10 3/4 (273) 10 3/4 (273) 12 3/4 (324) 12 3/4 (324)Tube Length, in. (mm) 96 (2438) 96 (2438) 96 (2438) 96 (2438) 96 (2438)Water Volume, gallons (l) 17.9 (1.1) 17.9 (1.1) 17.9 (1.1) 24.3 (1.5) 24.3 (1.5)Refrigerant Side D.W.P.PSIG, (kPa)

225 (1552) 225 (1552) 225 (1552) 225 (1552) 225 (1552)

Water Side D.W.P. psig (kPa) 175 (1207) 175 (1207) 175 (1207) 175 (1207) 175 (1207)Water Connections: Inlet & Outlet, in. (mm) (4) 4 (102) 4 (102) 4 (102) 5 (127) 5 (127) Drain & Vent, (NPT INT.) 3/8 (10) 3/8 (10) 3/8 (10) 3/8 (10) 3/8 (10)DIMENSIONSLength, in. (mm) 117 (2972) 117 (2972) 117 (2972) 117 (2972) 117 (2972)Width, in. (mm) 34 (864) 34 (864) 34 (864) 34 (864) 34 (864)Height, in. (mm) 62 1/4 (1581) 62 1/4 (1581) 62 1/4 (1581) 63 3/4 (1619) 63 3/4 (1619)WEIGHTSOperating Weight, lb. (kg) 3614 (1639) 3686 (1672) 3696 (1676) 3980 (1805) 4057 (1840)Shipping Weight, lb. (kg) 3644 (1653) 3716 (1686) 3726 (1690) 3925 (1780) 4002 (1815)Operating Charge, lb. (kg) R-22 45 (20) 45 (20) 50 (23) 50 (23) 50 (23) 50 (23) 55 (25) 55 (25) 60 (27) 60 (27)Operating Charge, lb. (kg) R-134a 47 (21) 47 (21) 52 (24) 52 (24) 52 (24) 52 (24) 58 (26) 58 (26) 63 (29) 63 (29)Notes:1. Certified in accordance with ARI Standard 550/590-98.2. 80% Full R-22 at 90°F (32°C) per refrigerant circuit.3. Victaulic WHR040-070.

Page 47: Reciprocating Chillers - Daikin Applied

Product Manual WHR-2 47

Table 29, WHR-080EW - WHR-110EWWHR UNIT SIZE 080EW 085EW 090EW 095EW 100EW 110WUnit capacity @ ARI conditionstons, (kW) (1) 76.5 (269.3) 85.0 (299.2) 91.5 (322.1) 96.0 (337.9) 102.0 (359.0) 111.5 (392.5)No. Circuits 2 2 2 2 2 2COMPRESSORSNominal Horsepower 40 40 40 50 50 50 30/25 30/25 30/25 30/25 35/25 35/25Number (2) 1 1 1 1 1 1 2 2 2 2 2 2Speed RPM 1750 1750 1750 1750 1750 1750No. of Cylinders 6 6 6 8 8 8 4/4 4/4 6/4 6/4 6/4 6/4

Unloading Steps100-83-66-50-

33-16-0100-87-70-58-

41-16-0100-97-75-62-

50-25-0100-87-75-62-58-37-25-12-0

100-91-83-6650-41-33-16-0

100-91-83-6650-41-33-16-0

Oil Charge oz. 255 255 255 255 255 255 140/130 140/130 140/130 140/130 140/130 140/130(l) (7.5) (7.5) (7.5) (7.5) (7.5) (7.5) (4.1)/(3.8) (4.1)/(3.8) (4.1)/(3.8) (4.1)/(3.8) (4.1)/(3.8) (4.1)/(3.8)CONDENSERSNumber 2 2 2 2 2 2

Diameter, in. (mm)8 5/8(219)

8 5/8(219)

10 3/4(273)

10 3/4(273)

10 3/4(273)

10 3/4(273)

10 3/4(273)

10 3/4(273)

10 3/4(273)

10 3/4(273)

10 3/4(273)

10 3/4(273)

Tube Length, in. (mm)96

(2438)96

(2438)96 (2438)

96(2438)

96(2438)

96(2438)

120(3048)

120(3048)

120(3048)

120(3048)

120 (3048) 120 (3048)

Design W.P.psig (kPa): Refrigerant Side 450 (3104) 450 (3104) 450 (3104) 450 (3104) 450 (3104) 450 (3104) Water Side 225 (1550) 225 (1550) 225 (1550) 225 (1550) 225 (1550) 225 (1550)No. of Passes 2 2 2 2 2 2 2 2 2 2 2 2

Pump-Out Cap., lb. (kg) (3)199(90)

199(90)

185(84)

185(84)

185(84)

185(84)

252 (114)

252(114)

252 (114)

252(114)

252(114)

252(114)

Connection:Water Inlet & Outlet, in (mm)(4)

2 1/2 (64) 2 1/2 (64) 3 (76) 3 (76) 3 (76) 3 (76) 3 (76) 3 (76) 3 (76) 3 (76) 3 (76) 3 (76)

Relief Valve, Flare in. (mm) 1/2 (13) 1/2 (13) 1/2 (13) 5/8 (16) 5/8 (16) 5/8 (16)Purge Valve, Flare in. 1/4 & 1/2 1/4 & 1/2 1/4 & 1/2 1/4 & 1/2 1/4 & 1/2 1/4 & 1/2 (mm) (6) & (13) (6) & (13) (6) & (13) (6) & (13) (6) & (13) (6) & (13) Liquid Subcooling Integral Integral Integral Integral Integral IntegralEVAPORATORNo. Refrigerant Circuits 2 2 2 2 2 2Diameter, in. (mm) 12 3/4 (324) 14 (356) 14 (356) 14 (356) 14 (356) 14 (356)Tube Length, in. (mm) 96 (2438) 96 (2438) 96 (2438) 120 (3048) 120 (3048) 120 (3048)Water Volume, gallons (l) 24.3 (1.5) 27.8 (1.8) 27.8 (1.8) 38.2 (2.4) 38.2 (2.4) 38.2 (2.4)Refrigerant Side D.W.P. PSIG,(kPa)

225 (1552) 225 (1552) 225 (1552) 225 (1552) 225 (1552) 225 (1552)

Water Side D.W.P. PSIG, (kPa) 175 (1207) 175 (1207) 175 (1207) 175 (1207) 175 (1207) 175 (1207)Water Connections : Inlet & Outlet(5) 5 (127) 6 (152) 6 (152) 6 (152) 6 (152) 6 (152) Drain & Vent(NPT INT.) 3/8 (10) 3/8 (10) 3/8 (10) 3/8 (10) 3/8 (10) 3/8 (10)DIMENSIONSLength In., (mm) 117 (2972) 115 3/4 (2940) 115 3/4 (2940) 142 3/4 (3626) 142 3/4 (3626) 142 3/4 (3626)Width In., (mm) 34 (864) 34 (864) 34 (864) 34 (864) 34 (864) 34 (864)Height In., (mm) 63 3/4 (1619) 66 1/4 (1683) 66 1/4 (1683) 77 (1956) 77 (1956) 77 (1956)WEIGHTSOperating Weight, Lb., (kg) 4242 (1924) 5316 (2411) 5626 (2552) 6090 (2762) 6170 (2799) 6170 (2799)Shipping Weight, Lb., (kg) 4187 (1899) 5176 (2348) 5486 (2488) 5900 (2676) 5980 (2713) 5980 (2713)Ref. Charge Lb, (kg) R-22 65 (29) 65 (29) 70 (32) 70 (32) 80 (36) 80 (36) 85 (39) 85 (39) 90 (41) 90 (41) 90 (41) 90 (41)Ref. Charge Lb, (kg) R-134a 68 (31) 68 (31) 74 (33) 74 (33) 84 (38) 84 (38) 89 (40) 89 (40) 94 (43) 94 (43) 94 (43) 94 (43)Notes:1. Certified in accordance with ARI Standard 550/590-98.2. Unit sizes WHR095 through 210 have two compressors per circuit in parallel.3. 80% Full R-22 at 90°F (32°C) per refrigerant circuit.4. NPT External WHR080 - 110.5. Victaulic connections, WHR080 - 110.

Page 48: Reciprocating Chillers - Daikin Applied

48 Product Manual WHR-2

Table 30, WHR-115EW - WHR-165EWWHR UNIT SIZE 115EW 120EW 130EW 145EW 155EW 165EWUnit capacity @ ARIconditionstons, (kW) (1) 113.5 (399.5) 122.0 (429.4) 132.0 (464.6) 144.0 (506.9) 150.5 (529.8) 163.8 (576.6)No. Circuits 2 2 2 2 2 2COMPRESSORSNominal Horsepower 35/25 35/25 35/25 35/35 35/35 35/35 35/35 35/40 40/40 40/40 40/50 40/50Number (2) 2 2 2 2 2 2 2 2 2 2 2 2Speed RPM 1750 1750 1750 1750 1750 1750No. of Cylinders 6/4 6/4 6/4 6/6 6/6 6/6 6/6 6/6 6/6 6/6 6/8 6/8Unloading Steps 100-91-83-66

50-41-33-16-0100-91-83-6650-41-33-16-0

100-91-83-6650-41-33-16-0

100-91-83-6650-41-33-16-0

100-91-83-6650-41-33-16-0

100-91-83-6650-41-33-16-0

Oil Charge oz. 140/130 140/130 140/130 140/140 140/140 140/140 140/140 140/255 225/255 225/255 225/255 225/255(l) (4.1)/(3.8

)(4.1)/(3.8

)(4.1)/(3.8

)(4.1)/(4.1

)(4.1)/(4.1

)(4.1)/(4.1

)(4.1)/(4.1

)(4.1)/(7.5

)(7.5)/(7.5

)(7.5)/(7.5

)(7.5)/(7.5

)(7.5)/(7.5

)CONDENSERSNumber 2 2 2 2 2 2Diameter, in. (mm) 10 3/4

(273)10 3/4(273)

10 3/4(273)

10 3/4(273)

10 3/4(273)

10 3/4(273)

10 3/4(273)

10 3/4(273)

10 3/4(273)

10 3/4(273)

10 3/4(273)

10 3/4(273)

Tube Length, in. (mm) 120(3048)

120(3048)

120(3048)

120(3048)

120(3048)

120(3048)

120(3048)

120(3048)

120(3048)

120(3048)

120(3048)

120(3048)

Design W.P, .psig, (kPa): Refrigerant Side 450 (3104) 450 (3104) 450 (3104) 450 (3104) 450 (3104) 450 (3104) Water Side 225 (1550) 225 (1550) 225 (1550) 225 (1550) 225 (1550) 225 (1550)No. of Passes 2 2 2 2 2 2 2 2 2 2 2 2Pump-Out Capacity, lb. (kg) 227 (103) 227 (103) 227 (103) 227 (103) 227 (103) 227 (103) 215

(97.5)215

(97.5)205 (93) 205 (93) 190

(86.2)190

(86.2)Connections : Water Inlet & Outlet, In.,(mm) (4)

3 (76) 3 (76) 3 (76) 3 (76) 3 (76) 3 (76) 3 (76) 3 (76) 3 (76) 3 (76) 3 (76) 3 (76)

Relief Valve, Flare in.(mm)

1/2 (13) 1/2 (13) 5/8 (16) 5/8 (16) 5/8 (16) 5/8 (16)

Purge Valve, Flare in. 1/4 & 1/2 1/4 & 1/2 1/4 & 1/2 1/4 & 1/2 1/4 & 1/2 1/4 & 1/2 (mm) (6) & (13) (6) & (13) (6) & (13) (6) & (13) (6) & (13) (6) & (13) Liquid Subcooling Integral Integral Integral Integral Integral IntegralEVAPORATORNo. Refrigerant Circuits 2 2 2 2 2 2Diameter, in. (mm) 14 (356) 14 (356) 14 (356) 16 (406) 16 (406) 16 (406)Tube Length, in. (mm) 120 (3048) 120 (3048) 120 (3048) 120 (3048) 120 (3048) 120 (3048)Water Volume, gallons, (l) 36.1 (2.3) 36.1 (2.3) 36.1 (2.3) 45.1 (2.9) 45.1 (2.9) 45.1 (2.9)Refrigerant Side D.W.P.,psig, (kPa)

225 (1552) 225 (1552) 225 (1552) 225 (1552) 225 (1552) 225 (1552)

Water Side D.W.P.Psig (kPa)

175 (1207) 175 (1207) 175 (1207) 175 (1207) 175 (1207) 175 (1207)

Water Connections: Inlet & Outlet, in. (mm)(5)

6 (152) 6 (152) 6 (152) 6 (152) 6 (152) 6 (152)

Drain & Vent, (NPT INT.) 3/8 (10) 3/8 (10) 3/8 (10) 3/8 (10) 3/8 (10) 3/8 (10)DIMENSIONSLength, in. (mm) 142 3/4 (3626) 142 3/4 (3626) 142 3/4 (3626) 142 3/4 (3626) 142 3/4 (3626) 142 3/4 (3626)Width, in. (mm) 34 (864) 34 (864) 34 (864) 34 (864) 34 (864) 34 (864)Height, in. (mm) 77 (1956) 77 (1956) 77 (1956) 77 (1956) 77 (1956) 77 (1956)WEIGHTSOperating Weight, lb. (kg) 6340 (2876) 6480 (2939) 6565 (2978) 7195 (3264) 7340 (3329) 7870 (3547)Shipping Weight, lb. (kg) 6150 (2790) 6290 (2853) 6375 (2892) 6895 (3128) 7020 (3148) 7470 (3388)Ref. Charge, lb. (kg) R-22 95 (43) 95 (43) 95 (43) 95 (43) 100 (45) 100 (45) 100 (45) 100 (45) 105(48) 105(48) 110(50) 110 (50)Ref. Charge, lb. (kg) R-134a

100 (45) 100 (45) 100 (45) 100 (45) 105 (48) 105 (48) 105 (48) 105 (48) 110 (50) 110 (50) 116 (52) 116 (52)

Notes:1. Certified in accordance with ARI Standard 550/590-98.2. Unit sizes WHR095 through 210 have two compressors per circuit in parallel.3. 80% Full R-22 at 90°F (32°C) per refrigerant circuit.4. NPT External WHR115 - 165.5. Victaulic connections, WHR115 - 165.

Page 49: Reciprocating Chillers - Daikin Applied

Product Manual WHR-2 49

Table 31, WHR-175EW - WHR-210EWWHR UNIT SIZE 175EW 185EW 195EW 210EWUnit capacity @ ARIconditions tons, (kW) (1)

177.0 (623.0) 185.0 (651.2) 197.0 (693.4) 211.9 (742.7)

No. Circuits 2 2 2 2COMPRESSORSNominal Horsepower 40/60 40/60 50/50 50/50 50/60 50/60 60/60 60/60Number (2) 2 2 2 2 2 2 2 2Speed RPM 1750 1750 1750 1750No. of Cylinders 6/8 6/8 8/8 8/8 8/8 8/8 8/8 8/8Unloading Steps 100-91-83-66

50-41-33-16-0100-87-75-62-50-37-25-12

100-87-75-62-50-37-25-12

100-87-75-62-50-37-25-12

Oil Charge oz. 255/255 255/255 255/255 255/255 255/255 255/255 255/255 255/255(l) (7.5)/(7.5) (7.5)/(7.5) (7.5)/(7.5) (7.5)/(7.5) (7.5)/(7.5) (7.5)/(7.5) (7.5)/(7.5) (7.5)/(7.5)CONDENSERSNumber 2 2 2 2Diameter, in. (mm) 10 3/4

(273)10 3/4(273)

12 3/4(323.9)

12 3/4(323.9)

12 3/4(323.9)

12 3/4(323.9)

12 3/4(323.9)

12 3/4(323.9)

Tube Length, in. (mm) 120(3048)

120(3048)

120(3048)

120(3048)

120(3048)

120(3048)

120(3048)

120(3048)

Design W.P., psig (kPa): Refrigerant Side 450 (3104) 450 (3104) 450 (3104) 450 (3104) Water Side 225 (1550) 225 (1550) 225 (1550) 225 (1550)No. of Passes 2 2 2 2 2 2 2 2Pump-Out Capacitylb., (kg) (3)

190(86.2)

190(86.2)

270(122.5)

270(122.5)

253(114.8)

253(114.8)

253(114.8)

253(114.8)

Connections : Water Inlet & Outlet in., (mm) (4)

3 (76) 3 (76) 4 (101.6) 4 (101.6) 4 (101.6) 4 (101.6) 4 (101.6) 4 (101.6)

Relief Valve, Flare in.,(mm)

5/8 (16) 5/8 (16) 5/8 (16) 5/8 (16)

Purge Valve, Flare in. 1/4 & 1/2 1/4 & 1/2 1/4 & 1/2 1/4 & 1/2 (mm) (6) & (13) (6) & (13) (6) & (13) (6) & (13) Liquid Subcooling Integral Integral Integral IntegralEVAPORATORNo. Refrigerant Circuits 2 2 2 2Diameter, in. (mm) 16 (406) 18 (457.2) 18 (457.2) 18 (457.2)Tube Length, in. (mm) 120 (3048) 120 (3048) 120 (3048) 120 (3048)Water Volume, gallons (l) 45.1 (2.9) 57.3 (3.6) 57.3 (3.6) 57.3 (3.6)Refrigerant Side D.W.P.,psig, (kPa)

225 (1552) 225 (1552) 225 (1552) 225 (1552)

Water Side D.W.P., psig,(kPa)

175 (1207) 175 (1207) 175 (1207) 175 (1207)

Water Connections: Inlet & Outlet, in. (mm) (5) 6 (152) 6 (152) 6 (152) 6 (152) Drain & Vent, (NPT INT.) 3/8 (10) 3/8 (10) 3/8 (10) 3/8 (10)DIMENSIONSLength, in. (mm) 142 3/4 (3626) 145 7/8 (3705) 145 7/8 (3705) 145 7/8 (3705)Width, in. (mm) 34 (864) 35 (889) 35 (889) 35 (889)Height, in. (mm) 77 (1956) 79 (2007) 79 (2007) 79 (2007)WEIGHTSOperating Weight, lb., (kg) 7870 (3547) 9195 (4171) 9290 (4214) 9300 (4218)Shipping Weight, lb. (kg) 7470 (3388) 8795 (3989) 8890 (4033) 8900 (4037)Ref. Charge, lb. (kg) R-22 110 (50) 110 (50) 125 (57) 125 (57) 130 (60) 130 (60) 130 (60) 130 (60)Ref. Charge, lb. (kg) R-134a 115 (52) 115 (52) 131 (59) 131 (59) 137 (62) 137 (62) 137 (62) 137 (62)Notes:

1. Certified in accordance with ARI Standard 550/590-98.2. Unit sizes WHR095 through 210 have two compressors per circuit in parallel.3. 80% Full R-22 at 90°F (32°C) per refrigerant circuit.4. NPT External WHR175. FPT Internal WHR185 - 210.5. Victaulic connections, WHR175 - WHR210

Page 50: Reciprocating Chillers - Daikin Applied

50 Product Manual WHR-2

EA Remote CondenserTable 32, WHR-017EA - WHR-030EA

WHR UNIT SIZE 017EA 020EA 025EA 030EACapacity @ 44 °F LWT, 120°F CT; tons, (kW) 15.9 (56.06) 19.6 (68.8) 23.3 (81.8)) 26.7 (93.7)No. Circuits 1 1 1 1COMPRESSORSNominal Horsepower 20 25 30 30Number 1 1 1 1Speed RPM 1750 1750 1750 1750No. of Cylinders 4 4 4 6Unloading Steps 100-50-0 100-50-0 100-50-0 100-50-0Oil Charge oz., (l) 135 (4.0) 130 (3.8) 140 (4.1) 140 (4.1)Discharge Valve In. (mm) 1 3/8 (35) 1 3/8 (35) 1 3/8 (35) 1 5/8 (41)EVAPORATORNo. Refrigerant Circuits 1 1 1 1Diameter, in, (mm) 8 (203) 8 (203) 8 (203) 8 (203)Tube Length, in. (mm) 60 (1524) 60 (1524) 72 (1829) 84 (2134)Water Volume, gallons (l) 6.3 (.4) 6.3 (.4) 7.6 (.5) 9.0 (.6)Refrigerant Side, D.W.P. psig (kPa) 200 (1379) 200 (1379) 200 (1379) 200 (1379)Water Side, D.W.P. psig, (kPa) 175 (1207) 175 (1207) 175 (1207) 175 (1207)Water Connections (1) Inlet & Outlet, in. (mm)(1) 2 (51) 2 (51) 2 (51) 2 (51) Drain & Vent, (NPT INT.) 3/4 (19)/1/4 (6) 3/4 (19)/1/4 (6) 3/4 (19)/1/4 (6) 3/4 (19)/1/4 (6)DIMENSIONSLength, in. (mm) 97 1/2 (2477) 97 1/2 (2477) 89 (2261) 99 1/2 (2527)Width, in.,, (mm) 25 1/2 (648) 25 1/2 (648) 28 3/4 (730) 24 (610)Height, in.,, (mm) 46 1/2 (1181) 46 1/2 (1181) 47 1/2 (1207) 46 1/2 (1181)WEIGHTSOperating Weight, lbs. (kg) 1106 (502) 1126 (571) 1314 (596) 1386 (1386)Shipping Weight, lbs. (kg) 1196 (543) 1209 (549) 1402 (636) 1454 (660)Operating Charge, lbs. (kg) R-22 (2) 25 (11) 16 912) 27 (12) 28 913)

Table 33, WHR-040EA - WHR-070EAWHR UNIT SIZE 040EA 045EA 050EA 060EA 070EACap. @ 44°F LWT, 120°F CT tons,(kW)

34.2 (120.0) 42.2 (148.1) 46.7 (163.8) 58.2 (204.6) 70.2 (246.8)

No. Circuits 2 2 2 2 2COMPRESSORSNominal Horsepower 20 22 25 25 30 30 30 30 35 35Number 1 1 1 1 1 1 1 1 1 1Speed RPM 1750 1750 1750 1750 1750Unloading Steps 100-75-50-25-0 100-75-50-25-0 100-75-50-25-0 100-83-58-25-0 100-83-66-50-33-16-0No. of Cylinders 4 4 4 4 4 4 4 6 6 6Oil Charge, oz.(l) 135 (4.0) 130 (3.8) 130 (3.8) 130 (3.8) 140 (4.1) 140 (4.1) 140 (4.1) 140 (4.1) 140 (4.1) 140 (4.1)Discharge Valve, in. (mm) 1 3/8

(35)1 3/8(35)

1 3/8(35)

1 3/8(35)

1 3/8(35)

1 3/8(35)

1 3/8(35)

1 5/8(41)

1 5/8(41)

1 5/8(41)

EVAPORATORNo. Refrigerant Circuits 2 2 2 2 2Diameter, in. (mm) 10 3/4 (273) 10 3/4 (273) 10 3/4 (273) 12 3/4 (324) 12 3/4 (324)Tube Length, in. (mm) 96 (2438) 96 (2438) 96 (2438) 96 (2438) 96 (2438)Water Volume, gallons (l) 17.9 (1.1) 17.9 (1.1) 17.9 (1.1) 24.3 (1.5) 24.3 (1.5)Refrigerant. Side D.W.P., psig, (kPa) 225 (1552) 225 (1552) 225 (1552) 225 (1552) 225 (1552)Water D.W.P., psig (kPa) 175 (1207) 175 (1207) 175 (1207) 175 (1207) 175 (1207)Water Connections: Inlet & Outlet, in. (mm) (1) 4 (102) 4 (102) 4 (102) 5 (127) 5 (127) Drain & Vent, (NPT INT.) 3/8 (10) 3/8 (10) 3/8 (10) 3/8 (10) 3/8 (10)DIMENSIONSLength, in. (mm) 116 (2940) 116 (2940) 116 (2940) 116 (2940) 116 (2940)Width, in. (mm) 34 (864) 34 (864) 34 (864) 34 (864) 34 (864)Height, in. (mm) 52 (1324) 52 (1324) 52 (1324) 52 (1324) 52 (1324)WEIGHTSOperating Weight, lbs. (kg) 2644 (1199) 2711 (1230) 2711 (1230) 2924 (1326) 3010 (1365)Shipping Weight, lbs. (kg) 2739 (1242) 2806 (1273) 2806 (1273) 2934 (1331) 3040 (1379)Operating Charge, lbs. (kg) R-22 22 (10) 24 (11) 24 (11) 24 (11) 24 (11) 24 (11) 28 (13) 28 (13) 28 (13) 28 (13)Notes:1. NPT external WHR-017-030.2. Condenser and field piping not included.

Page 51: Reciprocating Chillers - Daikin Applied

Product Manual WHR-2 51

Table 34, WHR-080EA - WHR-110EAWHR UNIT SIZE 080EA 085EA 090EA 095EA 100EA 110EACap. @ ARI conditions, tons, (kW)(1)

76.7 (269.7) 83.8 (294.6) 90.8 (319.3) 94.9 (333.7) 100.7 (354.1) 110.1 (387.1)

No. Circuits 2 2 2 2 2 2COMPRESSORSNominal Horsepower 40 40 40 50 50 50 30/25 30/25 30/25 30/25 35/25 35/25Number (4) 1 1 1 1 1 1 2 2 2 2 2 2Speed RPM 1750 1750 1750 1750 1750 1750No. of Cylinders 6 6 6 8 8 8 4/4 4/4 6/4 6/4 6/4 6/4Unloading Steps 100-83-66-50-

33-16-0100-87-70-58-

41-16-0100-97-75-62-

50-25-0100-87-75-62-58-37-25-12-0

100-91-83-6650-41-33-16-0

100-91-83-6650-41-33-16-0

Oil Charge, oz. 255 255 255 255 255 255 140/130 140/130 140/130 140/130 140/130 140/130(l) (7.5) (7.5) (7.5) (7.5) (7.5) (7.5) (4.1)/(3.8) (4.1)/(3.8) (4.1)/(3.8) (4.1)/(3.8) (4.1)/(3.8) (4.1)/(3.8)Discharge Valve, in. 1 5/8 1 5/8 1 5/8 1 5/8 1 5/8 1 5/8 1 3/8

1 3/81 3/81 3/8

1 3/81 3/8

1 3/81 3/8

1 3/81 3/8

1 3/81 3/8

(mm) (41) (41) (41) (41) (41) (41) (35) / (35) (35) / (35) (35) / (35) (35) / (35) (35) / (35) (35) / (35)EVAPORATORNo. Refrigerant Circuits 2 2 2 2 2 2Diameter, in. (mm) 12 3/4 (324) 14 (356) 14 (356) 14 (356) 14 (356) 14 (356)Tube Length, in. (mm) 96 (2438) 96 (2438) 96 (2438) 120 (3048) 120 (3048) 120 (3048)Water Volume, gallons (l) 24.3 (1.5) 27.8 (1.8) 27.8 (1.8) 38.2 (2.4) 38.2 (2.4) 38.2 (2.4)Refrigerant D.W.P., psig (kPa) 225 (1552) 225 (1552) 225 (1552) 225 (1552) 225 (1552) 225 (1552)Water D.W.P., psig (kPa) 175 (1207) 175 (1207) 175 (1207) 175 (1207) 175 (1207) 175 (1207)Water Connections : Inlet & Outlet, in. (mm) (2) 5 (127) 5 (127) 5 (127) 6 (152) 6 (152) 6 (152) Drain & Vent, (NPT INT.) 3/8 (10) 3/8 (10) 3/8 (10) 3/8 (10) 3/8 (10) 3/8 (10)DIMENSIONSLength, in. (mm) 115 3/4 (2940) 115 3/4 (2940) 115 3/4 (2940) 142 3/4 (3626) 142 3/4 (3626) 142 3/4 (3626)Width, in. (mm) 34 (864) 34 (864) 34 (864) 34 (864) 34 (864) 34 (864)Height, in. (mm) 53 1/8 (1349) 54 (1372) 54 (1372) 64 3/4 (1645) 64 3/4 (1645) 64 3/4 (1645)WEIGHTSOperating Weight, lbs. (kg) 3050 (1383) 3700 (1678) 3700 (1678) 4460 (2023) 4530 (2055) 4530 (2055)Shipping Weight, lbs. (kg) 3095 (1404) 3695 (1676) 3695 (1676) 4420 (2005) 4490 (2037) 4490 (2037)Operating Charge, lbs. (kg) R-22 28 (13) 28 (13) 34 (15) 34 (15) 34 (15) 34 (15) 35 (16) 35 (16) 35 (16) 35 (16) 35 (16) 35 (16)

Table 35, WHR-115EA through WHR-165EAWHR UNIT SIZE 115EA 120EA 130EA 145EA 155EA 165EACap.@ ARI condition tons, (kW) (1) 112.7 (396.3) 121.4 (426.8) 131.4 (462.0) 143.9 (505.9) 152.5 (536.2) 162.3 (570.6)No. Circuits 2 2 2 2 2 2COMPRESSORSNominal Horsepower 35/25 35/25 35/25 35/35 35/35 35/35 35/35 35/40 40/40 40/40 40/50 40/50Number (4) 2 2 2 2 2 2 2 2 2 2 2 2Speed RPM(60 Hz/50 Hz) 1750/1450 1750/1450 1750/1450 1750/1450 1750/1450 1750/1450No. of Cylinders 6/4 6/4 6/4 6/6 6/6 6/6 6/6 6/6 6/6 6/6 6/8 6/8Unloading Steps 100-91-83-66

50-41-33-16-0100-91-83-6650-41-33-16-0

100-91-83-6650-41-33-16-0

100-91-83-6650-41-33-16-0

100-91-83-6650-41-33-16-0

100-91-83-6650-41-33-16-0

Oil Charge oz. 140/130 140/130 140/130 140/140 140/140 140/140 140/140 140/255 225/255 225/255 225/255 225/255(l) 4.1/3.8 4.1/3.8 4.1/3.8 4.1/4.1 4.1/4.1 4.1/4.1 4.1/4.1 4.1/7.5 7.5/(.5 7.5/7.5 7.5/7.5 7.5/7.5Discharge Valve, in. 1 5/8

1 3/81 5/81 3/8

1 5/81 3/8

1 5/81 5/8

1 5/81 5/8

1 5/81 5/8

1 5/81 5/8

1 5/81 5/8

1 5/81 5/8

1 5/81 5/8

1 5/81 5/8

1 5/81 5/8

(mm) 41 / 35 41 / 35 41 / 35 41 / 41 41 / 41 41 / 41 41 / 41 41 / 41 41 / 41 41 / 41 41 / 41 41 / 41EVAPORATORNo. Refrigerant Circuits 2 2 2 2 2 2Diameter, in. (mm) 14 (356) 14 (356) 14 (356) 16 (406) 16 (406) 16 (406)Tube Length, in. (mm) 120 (3048) 120 (3048) 120 (3048) 120 (3048) 120 (3048) 120 (3048)Water Volume, gallons (L) 36.1 (2.3) 36.1 (2.3) 36.1 (2.3) 45.1 (2.9) 45.1 (2.9) 45.1 (2.9)Refrigerant Side D.W.P., psig (kPa) 225 (1552) 225 (1552) 225 (1552) 225 (1552) 225 (1552) 225 (1552)Water Side D.W.P., psig (kPa) 175 (1207) 175 (1207) 175 (1207) 175 (1207) 175 (1207) 175 (1207)Water Connections: Inlet & Outlet, in (mm) (2) 6 (152) 6 (152) 6 (152) 6 (152) 6 (152) 6 (152) Drain & Vent, (NPT INT.) 3/8 (10) 3/8 (10) 3/8 (10) 3/8 (10) 3/8 (10) 3/8 (10)DIMENSIONSLength, in. (mm) 142 3/4 (3626) 142 3/4 (3626) 142 3/4 (3626) 142 3/4 (3626) 142 3/4 (3626) 142 3/4 (3626)Width, in. (mm) 34 (864) 34 (864) 34 (864) 34 (864) 34 (864) 34 (864)Height, in. (mm) 64 3/4 (1645) 64 3/4 (1645) 64 3/4 (1645) 64 3/4 (1645) 64 3/4 (1645) 64 3/4 (1645)WEIGHTSOperating Weight, lbs. (kg) 4600 (2087) 4705 (2134) 4730 (2146) 5245 (2379) 5440 (2468) 5820 (2640)Shipping Weight, lbs. (kg) 4580 (2077) 4685 (2125) 4810 (2182) 5145 (2334) 5340 (2422) 5700 (2586)Operating Charge, lbs. (kg) R-22 38 (17) 38 (17) 38 (17) 38 (17) 42 (19) 42 (19) 46 (21) 46 (21) 48 (22) 48 (22) 48 9220 48 9220

Page 52: Reciprocating Chillers - Daikin Applied

52 Product Manual WHR-2

Notes:1. Condenser and field piping not included.2. Victaulic connections, WHR080 - 110.3. Unit sizes WHR095 thru 165 have two compressors per circuit in parallel.

Table 36, WHR-175EA - WHR-210EAWHR UNIT SIZE 175EA 185EA 195EA 210EAUnit capacity @ ARI conditionstons, (kW) (1) 176.1 (619.2) 182.0 (639.9) 196.0 (689.1) 209.0 (734.8)No. Circuits 2 2 2COMPRESSORSNominal Horsepower 40/60 40/60 50/50 50/50 50/60 50/60 60/60 60/60Number (4) 2 2 2 2 2 2 2 2Speed RPM 1750 1750 1750 1750No. of Cylinders 6/8 6/8 8/8 8/8 8/8 8/8 8/8 8/8Unloading Steps 100-91-83-66

50-41-33-16-0100-87-75-62-50-37-25-12

100-87-75-62-50-37-25-12

100-87-75-62-50-37-25-12

Oil Charge, oz. 255/255 255/255 255/255 255/255 255/255 255/255 255/255 255/255(l) (7.5)/(7.5) (7.5)/(7.5) (7.5)/(7.5) (7.5)/(7.5) (7.5)/(7.5) (7.5)/(7.5) (7.5)/(7.5) (7.5)/(7.5)Discharge Valve, in. 1 5/8/1 5/8 1 5/8/1 5/8 1 5/8/1 5/8 1 5/8/1 5/8 1 5/8/1 5/8 1 5/8/1 5/8 1 5/8/1 5/8 1 5/8/1 5/8(mm) (41) / (41) (41) / (41) (41) / (41) (41) / (41) (41) / (41) (41) / (41) (41) / (41) (41) / (41)EVAPORATORNo. Refrigerant Circuits 2 2 2 2Diameter, in. (mm) 16 (406) 18 (457.2) 18 (457.2) 18 (457.2)Tube Length, in. (mm) 120 (3048) 120 (3048) 120 (3048) 120 (3048)Water Volume, gallons, (l) 45.1 (2.9) 57.3 (3.6) 57.3 (3.6) 57.3 (3.6)Refrigerant. Side D.W.P., psig (kPa) 225 (1552) 225 (1552) 225 (1552) 225 (1552)Water Side D.W.P., psig (kPa) 175 (1207) 175 (1207) 175 (1207) 175 (1207)Water Connections: Inlet & Outlet, in (mm) (5) 6 (152) 6 (152) 6 (152) 6 (152) Drain & Vent, (NPT INT.) 3/8 (10) 3/8 (10) 3/8 (10) 3/8 (10)DIMENSIONSLength, in., (mm) 142 3/4 (3626) 145 7/8 (3705) 145 7/8 (3705) 145 7/8 (3705)Width, in., (mm) 34 (864) 35 (889) 35 (889) 35 (889)Height, in., (mm) 64 3/4 (1645) 64 3/4 (1645) 64 3/4 (1645) 64 3/4 (1645)WEIGHTSOperating Weight, lbs. (kg) 5820 (2640) 6880 (3121) 6890 (3125) 6900 (3130)Shipping Weight, lbs. (kg) 5700 (2586) 6740 (3057) 6750 (3062) 6760 (3066)Operating Charge, lbs. (kg) R-22 48 (22) 48 (22) 61 (28) 61 (28) 61 (28) 61 (28) 61 (28) 61 (28)Notes:1. Condenser and field piping not included.2. Victaulic connections, WHR175. through 2103. Unit sizes WHR175 thru 210 have two compressors per circuit in parallel.

Page 53: Reciprocating Chillers - Daikin Applied

Product Manual WHR-2 53

Dimensional Data

EW Water-CooledFigure 6, WHR 017EW through WHR 030EW

Maximum OverallDimensions

Chilled WaterConnections

Condenser WaterConnections

WHRModel

Number L W H SIZE A D N SIZE P

017EW104 1/4(2648)

26-1/4(667)

46-1/2(1181)

2 NPT (EXT)(51)

13-1/2(343)

17-3/4(451)

51(1295)

2 NPT (INT)(51)

1-1/2(38)

020EW104-1/4(2648)

26-1/4(667)

46-1/2(1181)

2 NPT (EXT)(51)

13-1/2(343)

17-3/4(451)

51(1295)

2 NPT (INT)(51)

1-2(38)

025EW101-1/2(2578)

29-1/2(749)

47-1/2(1207)

2 NPT (EXT)(51)

7-1/2(191)

18-3/4(476)

51(1295)

2 NPT (INT)(51)

1-3/4(44)

030EW106

(2692)29-1/2(749)

46-1/2(1181)

2 NPT (EXT)(51)

13-1/2(343)

18-3/4(476)

51(1295)

2 NPT (INT)(51)

1-3/4(44)

Page 54: Reciprocating Chillers - Daikin Applied

54 Product Manual WHR-2

Figure 7, WHR 040EW through WHR 090EW

Maximum OverallDimensions

Condenser WaterConnections (NPT)

WHRMODEL

NUMBER L W H E F G J P040EW 116-7/8 (2969) 34 (864) 62-1/4 (1581) 6-5/8 (168) 11-3/8 (289) 4-3/4 (121) 4-3/4 (121) 2-1/2 (64)045EW 116-7/8 (2969) 34 (864) 62-1/4 (1581) 6-5/8 (168) 11-3/8 (289) 4-3/4 (121) 4-3/4 (121) 2-1/2 (64050EW 116-7/8 (2969) 34 (864) 62-1/4 (1581) 6-5/8 (168) 11-3/8 (289) 4-34 (121) 4-34/ (121) 2-1/2 (64)060EW 116-7/8 (2969) 34 (864) 63-3/4 (1619) 6-5/8 (168) 11-3/8 (289) 4-3/4 (121) 4-3/4 (121) 2-1/2 (64)070EW 116-7/8 (2969) 34 (864) 63-3/4 (1619) 6-5/8 (168) 11-3/8 (289) 4-3/4 (121) 4-3/4 (121) 2-1/2 (64)080EW 116-7/8 (2969) 34 (864) 63-3/4 (1619) 6-5/8 (168) 11-3/8 (289) 4-3/4 (121) 4-3/4 (121) 2-1/2 (64)085EW 115-3/4 (2940) 34 (864) 66-1/4 (1683) 7-1/2 (191) 13-1/8 (333) 5-3/4 (146) 5-5/8 (143) 3 (76)090EW 115-3/4 (2940) 34 (864) 66-1/4 (1683) 7-1/2 (191) 13-1/8 (333) 5-3/4 (146) 5-5/8 (143) 3 (76)

Evaporator WaterConnections (Victaulic)

Center ofGravity

WHRMODEL

NUMBER A C D T U X Y Z040EW 2-3/4 (70) 23-3/8 (594) 4 (102) 19-5/8 (498) 58-1/8 (1476) 42-5/8 (1089) 23 (584) 13 (330)045EW 2-3/4 (70) 23-3/8 (594) 4 (102) 19-5/8 (498) 58-1/8 (1476) 42-5/8 (1089) 23 (584) 13 (330)050EW 2-3/4 (70) 23-3/8 (594) 4 (102) 19-5/8 (498) 58-1/8 (1476) 42-5/8 (1089) 23 (584) 13 (330)060EW 3-1/2 (89) 24-7/8 (632) 5 (127) 19 5/8 (498) 59-5/8 (1495) 43 (1092) 25-1/8 (638) 12-3/4 (324)070EW 3-1/2 (89) 24-7/8 (632) 5 (127) 19-5/8 (498) 59-5/8 (1495) 43 (1092) 25-1/8 (638) 12-3/4 (324)080EW 3-1/2 (89) 24-7/8 (632) 5 (127) 19-5/8 (498) 59-5/8 (1495) 43 (1092) 25-1/8 (638) 12-3/4 (324)085EW 3-1/2 (89) 27-1/8 (689) 6 (152) 18-1/2 (470) 62-1/8 (1578) 48 (1219) 23 (584) 13 (330)090EW 3-1/2 (89) 27-1/8 (689) 6 (152) 18-1/2 (470) 62-1/8 (1578) 48 (1219) 23 (584) 13 (330)

Note: Control box size: 76” (1930mm) L x 38½” (978mm) H x 7¼” (184mm) D.

Page 55: Reciprocating Chillers - Daikin Applied

Product Manual WHR-2 55

Figure 8, WHR 095EW through WHR 175EW

Maximum OverallDimensions

Center ofGravity

WHRMODELNUMBER L W H X Y Z

095EW 142-3/4 (3626) 34 (864) 77 (1956) 55-1/4 (1403) 32-5/8 (829) 13-5/8 (346)100EW 142-3/4 (3626) 34 (864) 77 (1956) 55-1/4 (1403) 32-5/8 (829) 13-5/8 (346)110EW 142-3/4 (3626 34 (864) 77 (1956) 55-1/4 (1403) 32-5/8 (829) 13-5/8 (346)115EW 142-3/4 (3626) 34 (864) 77 (1956) 55-7/8 (1419) 32-5/8 (829) 13-1/2 (343)120EW 142-3/4 (3626) 34 (864) 77 (1956) 56-1/8 (1419) 32-5/8 (829) 13-1/2 (343)130EW 142-3/4 (3626) 34 (864) 77 (1956) 56-1/8 (1426) 32-7/8 (835) 13-1/2 (343)145EW 142-3/4 (3626) 34 (864) 77 (1956) 56-5/8 (1438) 32-5/8 (835) 13-1/2 (343)155EW 142-3/4 (3626) 34 (864) 77 (1956) 56-1/4 (1429) 33-1/2 (845) 13-3/8 (340)165EW 142-3/4 (3626) 34 (864) 77 (1956) 56-1/4 (1429) 33-1/2 (845) 13-3/8 (340)175EW 142-3/4 (3626) 34 (864) 77 (1956) 56-1/4 (1429) 33-1/2 (845) 13-3/8 (340)

Note: Control box size: 76” (1930mm) L x 38½” (978mm) H x 7¼” (184mm) D.

Page 56: Reciprocating Chillers - Daikin Applied

56 Product Manual WHR-2

Figure 9, WHR-185EW through WHR-210EW

Maximum OverallDimensions

Center ofGravity

WHRMODELNUMBER L W H X Y Z185EW 145-7/8 (3705) 35 (889) 79 (2007) 55 (1397) 36 (914) 13-1/2 (343)195EW 145-7/8 (3705) 35 (889) 79 (2007) 55 (1397) 36 (914) 13-1/2 (343)210EW 145-7/8 (3705) 35 (889) 79 (2007) 55 (1397) 36 (914) 13-1/2 (343)

Note: Control box size: 76” (1930mm) L x 38½” (978mm) H x 7¼” x (184mm) D.

Page 57: Reciprocating Chillers - Daikin Applied

Product Manual WHR-2 57

EA Remote CondenserFigure 10 Dimensions, WHR 017EA– WHR 030EA

Maximum OverallDimensions, in. (mm)

Chilled WaterConnections, in. (mm)

WHRMODEL

NO. L W H Size A D

Inlet LiquidConn. Size

In. (mm)

DischargeConn. size

In. (mm) B

017EA97 1/2(2477)

25 1/2(648)

46 1/2(1181)

2 NPT (EXT) (51)

13 1/2(343)

17 3/4(451)

7/8 O.D. (22)

1 3/8 O.D. (35)

43 3/4(1111)

020EA97 1/2(2477)

25 1/2(648)

46 1/2(1181)

2 NPT (EXT) (51)

13 1/2(343)

17 3/4(451)

7/8 O.D.(22)

1 3/8 O.D.(35)

43 3/4(1111)

025EA89

(2261)28 3/4(730)

47 1/2(1207)

2 NPT (EXT) (51)

7 1/2(191)

18 3/4(476)

7/8 O.D.(22)

1 3/8 O.D.(35)

38(965)

030EA99 1/2(2527)

24(610)

46 1/2(1181)

2 NPT (EXT) (51)

13 1/2(343)

18 3/4(476)

7/8 O.D.(22)

1 5/8 O.D.(41)

44(1118)

Page 58: Reciprocating Chillers - Daikin Applied

58 Product Manual WHR-2

Figure 11, Dimensions WHR 040EA – WHR 090EA

Refrig. ConnectionsMaximum OverallDimensions

Evaporator WaterConnections (Victualic) Liquid Discharge

Center of GravityWHRModel

NumberL W H A C D E G T U X Y Z

040EA115 3/4(2940)

34(864)

52 1/8(1324)

2 3/4(70)

13 1/4(337)

4(102)

7/8 O.D.(22)

1 3/8 O.D.(35)

19 5/8(498)

48(1219)

41 3/4(1060)

18 7/8(479)

14 1/8(359)

045EA115 3/4(2940)

34(864)

52 1/8(1324)

2 3/4(70)

13 1/4(337)

4(102)

7/8 O.D.(22)

1 3/8 O.D.(35)

19 5/8(498)

48(1219)

41 3/4(1060)

18 7/8(479)

14 1/8(359)

050EA115 3/4(2940)

34(864)

52 1/8(1324)

2 3/4(70)

13 1/4(337)

4(102)

7/8 O.D.(22)

1 3/8 O.D.(35)

19 5/8(498)

48(1219)

41 3/4(1060)

18 7/8(479)

14 1/8(359)

060EA115 3/4(2940)

34(864)

53 1/8(1349)

3 1/2(89)

14 1/4(362)

5(127)

7/8 O.D.(22)

1 5/8 O.D.(41)

19 5/8(498)

49 1/2(1257)

42(1067)

22 1/8(562)

13 3/4(349)

070EA115 3/4(2940)

34(864)

53 1/8(1349)

3 1/2(89)

14 1/4(362)

5(127)

7/8 O.D.(22)

1 5/8 O.D.(41)

19 5/8(498)

49 1/2(1257)

42(1067)

22 1/8(562)

13 3/4(349)

080EA115 3/4(2940)

34(864)

53 1/8(1349)

3 1/2(89)

14 1/4(362)

5(127)

1 1/8 O.D.(29)

1 5/8 O.D.(41)

19 5/8(498)

49 1/2(1257)

42(1067)

22 1/8(562)

13 3/4(349)

085EA115 3/4(2940)

34(864)

54(1372)

3 1/2(89)

14 1/4(362)

6(152)

1 1/8 O.D.(29)

1 5/8 O.D.(41)

18 1/2(470)

50 3/8(1280)

46 1/4(1175)

22 3/4(578)

13 1/2(343)

090EA115 3/4(2940)

34(864)

54(1372)

3 1/2(89)

14 1/4(362)

6(152)

1 1/8 O.D.(29)

1 5/8 O.D.(41)

18 1/2(470)

50 3/8(1280)

46 1/4(1175)

22 3/4(578)

13 1/2(343)

Page 59: Reciprocating Chillers - Daikin Applied

Product Manual WHR-2 59

Figure 12, Dimensions, WHR 120EA – WHR 175EA

Maximum OverallDimensions

Evap. Water Conn.(Victaulic)

Center of Gravity Refrigerant ConnectionsWHR

MODELNO. L W H A C D P T X Y Z Liquid Disc.

095EA 142 3/4 34 64 3/4 5 1/2 18 6 6 20 5/8 54 1/2 28 3/4 13 1/8 1 1/8 O.D. 1 5/8 O.D.100EA 142 3/4 34 64 3/4 5 1/2 18 6 6 20 5/8 54 1/2 28 3/4 13 1/8 1 1/8 O.D. 1 5/8 O.D.110EA 142 3/4 34 64 3/4 5 1/2 18 6 6 20 5/8 54 1/2 28 3/4 13 1/8 1 1/8 O.D. 1 5/8 O.D.115EA 142 3/4 34 64 3/4 5 1/2 18 6 6 20 5/8 55 1/2 28 3/4 13 1/8 1 1/8 O.D. 1 5/8 O.D.120EA 142 3/4 34 64 3/4 5 1/2 18 6 6 20 5/8 55 1/2 29 13 1/8 1 1/8 O.D. 1 5/8 O.D.130EA 142 3/4 34 64 3/4 5 1/2 18 6 6 20 5/8 55 3/8 29 1/8 13 1 1/8 O.D. 1 5/8 O.D.145EA 142 3/4 34 64 3/4 5 1/2 18 6 6 20 5/8 56 1/4 29 3/4 13 1 1/8 O.D. 1 5/8 O.D.155EA 142 3/4 34 64 3/4 5 1/2 18 6 6 20 5/8 55 3/4 29 3/4 12 7/8 1 1/8 O.D. 1 5/8 O.D.165EA 142 34 64 3/4 5 1/2 18 6 6 20 5/8 55 3/4 30 1/2 12 7/8 1 3/8 O.D. 1 5/8 O.D.175EA 142 34 64 3/4 5 1/2 18 6 6 20 5/8 55 3/4 30 1/2 12 7/8 1 3/8 O.D. 1 5/8 O.D.

Page 60: Reciprocating Chillers - Daikin Applied

60 Product Manual WHR-2

Figure 13, Dimensions WHR 185EA, 195EA, 210EA

Maximum OverallDimensions

Evap. Water Conn.(Victaulic)

Center of Gravity Refrigerant ConnectionsWHRMODEL

NO. L W H A C D P T X Y Z Liquid Disc.185EA 145 7/8 35 64 3/4 4 1/8 19 6 6 21 3/8 54 32 1/2 16 1 3/8 O.D 1 5/8 O.D.195EA 145 7/8 35 64 3/4 4 1/8 19 6 6 21 3/8 54 32 1/4 16 1 3/8 O.D 1 5/8 O.D.210EA 145 7/8 35 64 3/4 4 1/8 19 6 6 21 3/8 54 32 16 1 3/8 O.D 1 5/8 O.D.

Page 61: Reciprocating Chillers - Daikin Applied

Product Manual WHR-2 61

Sound Data

WHR Sound Pressure Charts

Table 37Octave Band Sound Pressure Levels Per ARI Standard 575 (dB)WHR "E"

Unit Size 63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 HzOverall "A"Weighted

017 46 48 54 58 60 60 60 60 68020 47 49 55 59 61 61 61 60 68025 47 49 55 60 61 62 63 62 69030 47 49 55 60 61 62 63 62 69040 50 51 57 60 64 64 64 64 71045 50 52 58 61 64 64 64 64 71050 51 53 58 61 65 64 65 64 72060 51 53 59 62 65 65 65 64 73070 52 54 61 64 67 67 67 65 74080 52 54 61 64 67 67 67 65 74085 54 56 63 66 69 69 69 66 76

Notes:1. Sound Pressure per ARI Standard 575.2. Sound pressure levels taken at a distance of 3 feet.3. Acoustical enclosure is not available on the following unit sizes: 085, 090, 165, 175, 185, 195 and 210.

Table 38Octave Band Sound Pressure Levels Per ARI Standard 575 (dB)WHR "E"

Unit Size 63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 HzOverall "A"Weighted

090 55 57 63 67 69 70 69 70 77095 68 69 72 73 75 69 66 65 78100 68 69 72 73 75 69 66 65 78110 69 70 73 74 76 70 66 65 79115 69 70 73 74 76 70 66 65 79120 69 70 73 74 76 70 66 65 79130 70 71 73 75 77 71 67 65 80145 70 72 74 75 77 72 68 65 80155 71 73 74 76 77 72 68 66 80165 72 74 75 77 78 73 69 67 81175 73 75 76 78 79 74 70 68 82185 73 75 76 78 79 74 70 68 82195 74 76 76 79 80 75 71 76 84210 74 76 76 79 80 75 71 76 84

Notes:1. Sound Pressure per ARI Standard 575.2. Sound pressure levels taken at a distance of 3 feet.3. Acoustical enclosure is not available on the following unit sizes: 085, 090, 165, 175, 185, 195 and 210.

Page 62: Reciprocating Chillers - Daikin Applied

62 Product Manual WHR-2

WHR with Acoustical Enclosure Sound Pressure Chart

Table 39Octave Band Sound Pressure Levels Per ARI Standard 575 (dB)WHR "E"

Unit Size 63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 HzOverall "A"Weighted

017 43 45 51 55 57 57 57 57 65020 44 46 52 56 58 58 58 57 65025 44 46 52 57 58 59 60 59 66030 44 46 52 57 58 59 60 59 66040 47 48 54 57 61 61 61 61 68045 47 49 55 58 61 61 61 61 68050 48 50 55 58 62 61 62 61 69060 48 50 56 59 62 62 62 61 69070 48 50 57 60 63 63 63 61 69080 48 50 57 60 63 63 63 61 69

Notes:1. Sound Pressure per ARI Standard 575.2. Sound values taken with units fully loaded with hot gas mufflers.3. Sound pressure levels taken at a distance of 3 feet.4. Acoustical enclosure is not available on the following unit sizes: 085, 090, 165, 175, 185, 195 and 210.

Table 40Octave Band Sound Pressure Levels Per ARI Standard 575 (dB)WHR "E"

Unit Size 63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 HzOverall "A"Weighted

100 64.2 65.2 68.2 69.2 71.2 65.2 62.2 61.2 74110 65 66 69 70 72 66 62 61 75115 65 66 69 70 72 66 62 61 75120 65 66 69 70 72 66 62 61 75130 66.2 67.2 69.2 71.2 73.2 67.2 63.2 61.2 76145 66.2 67.2 69.2 70.2 72.2 67.2 63.2 60.2 75155 66.2 68.2 69.2 71.2 72.2 67.2 63.2 61.2 75

Notes:1. Sound Pressure per ARI Standard 575.2. Sound values taken with units fully loaded with hot gas mufflers.3. Sound pressure levels taken at a distance of 3 feet.4. Acoustical enclosure is not available on the following unit sizes: 085, 090, 165, 175, 185, 195 and 210.

Page 63: Reciprocating Chillers - Daikin Applied

Product Manual WHR-2 63

WHR Sound Power

Table 41Octave Band Sound Power Levels Per ARI Standard 575 (dB)WHR "E"

Unit Size 63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 HzOverall "A"Weighted

017 54 56 62 66 68 68 68 68 75020 55 57 63 67 69 69 69 68 76025 55 57 63 68 69 69 70 69 77030 55 57 63 68 69 69 70 69 77040 58 59 65 68 72 72 72 72 78045 58 60 66 69 72 72 72 72 79050 59 61 66 69 73 72 73 72 80060 59 61 67 70 73 73 73 72 80070 60 62 68 71 75 74 75 73 82080 60 62 68 71 75 74 75 73 82085 62 64 70 74 77 77 77 74 84

Notes:1. Sound Power per ARI Standard 575.2. Sound values taken with units fully loaded with hot gas mufflers.3. Acoustical enclosure is not available on the following unit sizes: 085, 090, 165, 175, 185, 195 and 210.

Table 42Octave Band Sound Power Levels Per ARI Standard 575 (dB)WHR "E"

Unit Size 63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 HzOverall "A"Weighted

090 63 65 71 75 77 78 77 78 85095 76 77 80 81 83 77 74 73 86100 76 77 80 81 83 77 74 73 86110 77 78 81 82 84 78 74 73 87115 77 78 81 82 84 78 74 73 87120 77 78 81 82 84 78 74 73 87130 78 79 81 83 85 79 75 73 88145 78 80 82 83 85 80 76 73 88155 79 81 82 84 85 80 76 74 88165 80 82 83 85 86 81 77 75 89175 81 83 84 86 87 82 78 76 90185 81 83 84 86 87 82 78 76 90195 82 84 84 87 88 83 79 84 92210 82 84 84 87 88 83 79 84 92

Notes:1. Sound Power per ARI Standard 575.2. Sound values taken with units fully loaded with hot gas mufflers.3. Acoustical enclosure is not available on the following unit sizes: 085, 090, 165, 175, 185, 195 and 210.

Page 64: Reciprocating Chillers - Daikin Applied

64 Product Manual WHR-2

WHR with Acoustical Enclosure Sound Power Chart

Table 43Octave Band Sound Power Levels Per ARI Standard 575 (dB)WHR "E"

Unit Size 63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 HzOverall "A"Weighted

017 51 53 59 63 65 65 65 65 73020 52 54 60 64 66 66 66 65 73025 52 54 60 65 66 66 67 66 74030 52 54 60 65 66 66 67 66 74040 55 56 62 65 69 69 69 69 76045 55 57 63 66 69 69 69 69 76050 56 58 63 66 70 69 70 69 77060 56 58 64 67 70 70 70 69 77070 56 58 64 67 71 70 71 69 77080 56 58 64 67 71 70 71 69 77

Notes1. Sound Power per ARI Standard 575.2. Sound values taken with units fully loaded with hot gas mufflers.3. Acoustical enclosure is not available on the following unit sizes: 085, 090, 165, 175, 185, 195 and 210.

Table 44Octave Band Sound Power Levels Per ARI Standard 575 (dB)WHR "E"

Unit Size 63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 HzOverall "A"Weighted

095 72 73 76 77 79 73 70 69 82100 72 73 76 77 79 73 70 69 82110 73 74 77 78 80 74 70 69 83115 73 74 77 78 80 74 70 69 83120 73 74 77 78 80 74 70 69 83130 74 75 77 79 81 75 71 69 84145 73 75 77 78 80 75 71 68 83155 74 76 77 79 80 75 71 69 83

Notes:1. Sound Power per ARI Standard 575.2. Sound values taken with units fully loaded with hot gas mufflers.3. Acoustical enclosure is not available on the following unit sizes: 085, 090, 165, 175, 185, 195 and 210.

Page 65: Reciprocating Chillers - Daikin Applied

Product Manual WHR-2 65

Application Data

Location and Space RequirementsThe units are designed for indoor application and must be located in a space where the temperatureis 40°F (4.4°C) or above. Provide clearance of 2 to 3 ft. (609 to 914 mm) on each side and ends forpiping and to help when servicing unit.

Provide clearance at either end of the unit to permit cleaning of condenser tubes or for removal oftubes from condenser or cooler (see dimensional data). If a door or window is provided at one endof the unit, the tubes may be replaced through the opening provided.

FoundationMount the unit on a level concrete foundation. Floors must be strong enough to support the unitweight. If necessary, use structural supports to transfer the weight of the unit to the nearest beams.

Vibration IsolationVibration mounts are recommended for upper floor installations or where compressor noises mightbe objectionable (next to occupied spaces such as offices, meeting rooms, etc.).

Vibration eliminators may be used for water piping connected to the unit to avoid transmission ofwater or pump noise into occupied spaces.

System water volume considerations:All chillers need adequate time to recognize a load change, respond to the change and stabilizewithout short cycling the compressor. The water volume in the system and the size of the pipingloop is a critical consideration. Good engineering practice is to have a minimum water volume ofseven times the flow rate (GPM) for comfort cooling applications. For process applications wherethe load can change quickly, contact the factory for recommendations. A water storage tank(provided by others) may be required to increase the system water volume in some systems.

Typical Chilled Water PipingFlush the system water piping thoroughly before making connections to the unit evaporator. Installa 40 mesh strainer in the return water line before the inlet to the chiller. Design the water piping sothe chilled water circulating pump discharges into the evaporator inlet.

Connect chilled water return water line to evaporator inlet connection. And the supply water line toevaporator outlet connection.

Install a flow switch in the horizontal piping of the supply (evaporator outlet) water line.

Provide drain connections at low points in the system to permit complete drainage of the system.Air vents should be located at the high points in the system to purge air out of the system. A ventconnection on top of the evaporator vessel allows air to be purged. Purge air from the water systembefore unit start-up to ensure adequate flow through the evaporator.

Install pressure gauges in the inlet and outlet water lines to the evaporator. Measure pressure dropthrough the evaporator to calculate proper flow. Vibration eliminators are recommended in both thesupply and return water lines.

Chilled water piping should be insulated to reduce heat loss and prevent condensation. Chillers notrunning in the winter should have their water systems thoroughly drained to protect againstfreezing. If the chiller operates year round, or if the system is not drained for the winter, protect theoutdoor chilled water piping against freezing. Wrap the lines with a heater cable and add properamount of glycol to the system to further protect the system.

Page 66: Reciprocating Chillers - Daikin Applied

66 Product Manual WHR-2

Figure 14, Typical chilled water piping

Condenser Water (EW Units)Be certain the condenser water enters the bottom connection of the condenser. The condenserwater will exit the condenser from the top connection. Head pressure control must be provided ifthe entering condenser water can fall below 60°F. Fan cycling and modulating discharge damperson the cooling towers or a three-way bypass valve around the tower is often used. Consult thetower manufacturer for information on specific applications.

If city or well water is used for condensing, a two-way pressure actuated water regulating valveshould be installed in the outlet piping of each condenser. The condenser purge valve provides aconvenient pressure tap for the regulating valve. The valve can modulate in response to headpressure. When the compressor shuts down, this valve closes, preventing water from beingsiphoned out of the condenser.

Low Temperature ApplicationsCompressor unloading is acceptable for applications with 35°F or higher leaving fluid temperatures(LFT). For applications where the LFT is less than 35°F, only full load compressor operation isallowable. Due to reduced refrigerant flow, motor cooling can become a problem. If compressorpart load operation is required below 35°F LFT, contact the factory for additional requirements. It isacceptable to use UNT or MicroTech controls for applications with 35°F LFT or lower provided thatonly one LFT setpoint is needed.

Ice Storage ApplicationsIce storage applications must use Microtech controls. The Microtech has logic to changesetpoints from the low ice making mode to higher normal comfort cooling setpoints. It is importantthat the Microtech controller receive a signal to convert from ice mode to normal operating mode.Microtech includes the logic to keep compressors fully loaded when operating in the ice mode.The double insulation thickness option is recommend to prevent sweating.

Two Pipe SystemsWhen the same two pipes are used for both heating and cooling water, several limitations should beobserved. The maximum allowable temperature that the evaporator should experience in a non-operating mode is 100 degrees Fahrenheit. For unit operation and system changeover from heatingto cooling, the maximum allowable temperature entering the evaporator is 90 degrees Fahrenheit.System controls provided by others should prevent chiller operation until the loop temperaturedrops to 90 degrees. When the loop water temperature ranges between 75 and 90 degrees enteringthe evaporator, the high return water staging thermostat should be used to prevent compressoroverloading.

Page 67: Reciprocating Chillers - Daikin Applied

Product Manual WHR-2 67

Series or Parallel OperationConsider system pressure drop when designing the water piping. Parallel piped systems have halfof the total system flow going through the evaporator of each chiller, reducing the individual unitand total system pressure drop.

Series piped evaporators require that the total system water flows through both evaporators. Notonly is the pressure drop through each evaporator increased but the pressure drops must be addedtogether to obtain the total evaporator pressure drop. Series piped evaporators normally requirelarger circulating pumps for the chilled water system.

Electrical ConnectionEvery WHR chiller requires field installation of the main supply power plus flow switch and pumpstarter relay. A control circuit transformer installed at the factory eliminates the need for fieldinstallation of a separate 115V supply to the control circuit. A separate 115V field connection to thecontrol circuit can be substituted. A system time clock and remote on-off switch can also be fieldinstalled.

See Figure 5, Field Wiring Diagram, on page 44 for field electrical hookups. The diagram shownrepresent all WHR units; however, individual terminal numbers may vary between unit sizes. Eachunit is provided with its specific wiring diagram in the control panel. All wiring must be doneaccording to local and national codes.

Main Power Supply Disconnect SwitchEvery WHR unit uses a single factory installed main power supply terminal block as standard. Themain power supply terminal block will accept single or parallel power supply wiring.

A field installed non-fused disconnect switch with an optional thru-the-door handle (required tomeet NEC Code for disconnects) is available as an option on WHR 040 and above with single pointpower supply. The disconnect switch is properly sized for the model and voltage supplied.

A field supplied and installed remote disconnect switch can also be used.

Control CircuitA control power transformer is standard equipment on WHR units. Terminals are provided in theunit control center (terminals 1 and NB, typical field wiring diagram) for field connection to a remotecontrol circuit to a 115V power supply if desired.

Terminals are also provided for field connection of the chilled water flow switch, unit time clock,ambient thermostat and/or remote on/off switch.

Compressor Time LockoutA fixed 5-minute solid-state lockout time delays compressor restart after safety cutout or powerinterruption, or under irregular cooling load demands.

Interlock WiringThe condenser water pump should be interlocked to cycle with the compressor(s). This willprevent the refrigerant pressure from being overly depressed during the off cycle and allows theenergy savings of pump shutdown. Interlock terminals are provided in the unit control panel.

Page 68: Reciprocating Chillers - Daikin Applied

68 Product Manual WHR-2

Design Limitations1. Maximum allowable condenser water pressure is 225 psig (1550 kPa).

2. Maximum allowable evaporator water pressure is 175 psig (1206 kPa).

3. Maximum design saturated discharge temperature (SDT) is 140°F (60°C). SDT=Condensingtemperature + discharge line loss.

4. Maximum allowable water temperature to evaporator in a non-operating cycling is 100°F(37.8°C). Maximum entering water temperature for operating cycle is 90°F (32.2°C) (duringsystem changeover from heating to cooling cycle). An optional return water unloadingthermostat is required for return temperatures greater than 75°F (23.4°C).

5. Minimum design leaving water temperature from the evaporator without freeze protection is42°F (6°C).

6. Contact your McQuay representative for operation with tower condenser water entering thechiller below 70°F (21.1°C).

7. Compressor unloading is not allowed with leaving chilled fluid temperatures 35°F or less.

8. The optional Microtech control is required for ice storage applications.

9. The maximum altitude for air-cooled condensers is 6,000 feet.

10. Consult factory for ambient operation below 0°F (-17.8°C).

Remote Condenser Refrigerant Piping

GeneralCareful design of refrigerant piping is necessary for proper system operation. The refrigerantpiping should be designed to accomplish the following:

1. Assure proper refrigerant feed to the evaporator.

2. Provide practical and economical refrigerant line sizes without excess pressure drop.

3. Maintain uniform oil return to the compressor under all load conditions.

4. Refer to the latest version of the ASHRAE Handbook for recommended piping practice.

Limit the length of refrigerant piping by locating the condenser as close to the chiller as possible.Avoid all unnecessary changes in direction or elevation. On dual circuit units, the condensers mustbe selected with separate condenser sections so that the circuits are not combined and precautionstaken to avoid cross-connecting the circuits.

Liquid LineWhere there is a vertical lift from the condenser to the chiller, adequate subcooling must beprovided to prevent liquid flashing before the expansion valve. A shutoff valve should be installedin the liquid line to allow isolation of the remote condenser.

Discharge lineThe discharge line should be trapped at the compressor and looped at the condenser (inverted trap)to prevent liquid refrigerant from draining back onto the compressor heads. Pressure drop shouldbe held at a minimum.

Page 69: Reciprocating Chillers - Daikin Applied

Product Manual WHR-2 69

Optional Features

Hot Gas BypassFactory mounted hot gas bypass permits unit operation down to 10% of full load capacity andincludes a hot gas bypass valve, solenoid valve and manual shutoff valve. Hot gas bypass isprovided both refrigerant circuits.

Vibration IsolatorsSpring or rubber-in-shear vibration isolators are available as a kit for field installation to reducevibration transmission through the unit base.

GaugesIncludes high side and low side refrigerant pressure gauges per refrigerant circuit and oil pressuregauges per compressor. The gauges are factory mounted on service gauge connections.

Zone Terminal KitComplete description in the "Design Advantages" section.

MicroTech Chiller Controller (WHR 040 through 210)Complete description in the "Design Advantages" section.

Optional Network Master Panel (NMP)Complete description in the "Design Advantages" section.

Optional Remote Monitoring and Sequencing Panel (RMS)Complete description in the "Design Advantages" section.

Monitor SoftwareComplete description in the "Design Advantages" section.

Open ProtocolComplete description in the "Design Advantages" section.

MicroTech BACdrop GatewayComplete description in the "Design Advantages" section.

Water Flow SwitchA field installed water flow safety switch in the chilled water piping prevents evaporator freeze-upunder low or no flow conditions. Terminals are provided in the unit control center for field hookupof the water flow safety switch.

Disconnect Switch (WHR 040 through 210)A field installed non-fused disconnect switch with thru-the-door- handle is available as an optionwith single point power supply (requires modifications to the control panel door. The disconnectswitch is properly sized for model and voltage required. The optional thru-the-door handle kit isrequired if the disconnect switch is to meet disconnecting provisions of the NEC when a separateexternal disconnect is not used.

Page 70: Reciprocating Chillers - Daikin Applied

70 Product Manual WHR-2

Through-the-Door Handle KitsKits are available for 225, 250, 400, 600, 800 and 1200 amps. To select the proper kit, refer themaximum fuse data in the catalog for the desired chiller and voltage. Select the kit size that is equalto the maximum fuse size. If an exact match is not listed, it is acceptable to use the closest size kitthat exceeds the maximum fuse size.

Circuit BreakersFactory installed circuit breakers are available as an option of unit sizes WHR 040 through 090 withsingle point power supply. Circuit breakers are standard on unit sizes WHR 017 through 030 andWHR 095 through 210 with single point power. This option provides unit installed compressorshort circuit protection.

Alarm BellA field installed 24 volt alarm bell signals safety trip of the freeze protection pressurestat, highpressure cutout, oil failure cutout, or motor overload. The bell is factory mounted on the unitcontrol center. A time clock is also available with a spring carryover. During normal operation, thespring is wound to operate the clock for up to ten hours should the power be lost to the unit.

Short Circuit/Overload Protection (Supplemental Overloads)Factory mounted companion trip automatic circuit breakers are available per compressor. External(supplemental) overloads added per compressor (in addition to standard compressor internaloverload protection) is available on 40 tons and above.

Phase Loss/Voltage ProtectionA field installed option- phase loss with under/over voltage protection and multiple LED indicationof fault type.

High Return Water Unloading(WHR 040 through 210)

A field installed high return water unloading thermostat is available for applications where thereturn water temperature to the evaporator exceeds an adjustable setpoint for short periods of timeat startup.

Acoustical Compressor Enclosure(WHR 017 - WHR 080 and WHR 095 – WHR 155)

A factory installed acoustical compressor enclosure is available for all units when low sound levelsare a consideration. The sheet metal enclosure is acoustically lined with 1 inch fiberglassinsulation.

Page 71: Reciprocating Chillers - Daikin Applied

Product Manual WHR-2 71

Product Specifications

Water-Cooled, WHR 017 through 030

PART 1 - GENERAL

1.01 SUMMARY

Section includes design, performance criteria, refrigerants, controls, and installationrequirements for water-cooled reciprocating compressor packaged chillers.

1.02 REFERENCES

Comply with applicable Standards/Codes of ARI 550/590-98, ANSI/ASHRAE 15,ASHRAE 90.1, ASME Section VIII, NEC, and OSHA as adopted by the State.

1.03 SUBMITTALS

A. Submit shop drawings and product data in accordance with contractspecifications.

B. Submittals shall include the following:

1. Dimensioned plan and elevation view drawings, required clearances, andlocation of all field connections.

2. Summary of all auxiliary utility requirements such as: electricity, water,compressed air, etc. Summary shall indicate quality and quantity of eachrequired utility.

3. Single line schematic drawing of the power field hookup requirements,indicating all items which are furnished.

4. Schematic diagram of control system indicating points for fieldinterface/connection. Diagram shall fully delineate field and factorywiring.

5. Manufacturer’s certification of factory run test of chiller unit signed bycompany officer.

6. Installation manuals.

1.04 QUALITY ASSURANCE

A. Qualifications; Equipment manufacturer must specialize in the manufacture of theproducts specified and have five years experience with the equipment andrefrigerant offered.

B Regulatory Requirements: Comply with the codes and standards specified.

C Chiller manufacturer must be ISO 9002 registered.

Page 72: Reciprocating Chillers - Daikin Applied

72 Product Manual WHR-2

1.05 DELIVERY AND HANDLING

A. Chillers shall be delivered to the job site completely assembled and charged withrefrigerant and oil by the manufacturer.

B. Comply with the manufacturers instructions for rigging and handling equipment.

1.06 WARRANTY

The equipment manufacturer’s warranty shall be for a period of one year from date ofequipment start and acceptance but not more than 18 months from shipment. Thewarranty shall cover defective material and workmanship within the above period,excluding refrigerant.

PART 2--PRODUCTS

2.01 ACCEPTABLE MANUFACTURERS

A. McQuay International

B. (Approved Equal)

2.02 UNIT DESCRIPTION

Provide and install as shown on the plans factory assembled, factory charged, and factoryrun tested, water-cooled reciprocating compressor packaged chillers in the quantityspecified. Each chiller shall consist of hermetic reciprocating compressor, direct expansionevaporator, water-cooled condenser, control system and all components necessary forsafe and controlled unit operation.

2.03 DESIGN REQUIREMENTS

A. General: Provide a complete reciprocation packaged chiller as specified herein andas shown on the drawings. The unit shall be in accordance with the standardsreferenced in section 1.02 and any local codes in effect.

B. Performance: Refer to the schedule of performance on the drawings. Performanceshall be in accordance with applicable ARI Standard.

C. Acoustics: Sound pressure levels for the unit shall not exceed the followingspecified levels. The manufacturer shall provide the necessary sound treatmentto meet these levels if required. Sound data shall be provided with the quotation.Test shall be in accordance with ARI Standard 575.

Octave Band

63 125 250 500 1000 2000 4000 8000 dBA____ ____ ____ ____ ____ ____ ____ ____ ____

Page 73: Reciprocating Chillers - Daikin Applied

Product Manual WHR-2 73

2.04 CHILLER COMPONENTS

A. Compressor: The compressor shall be of the accessible hermetic reciprocatingtype with suction and discharge service valves, crankcase oil heater and suctionstrainer. Compressor shall have a forced feed lubrication system with a reversibleoil pump, oil sight glass, and oil charge. The compressor motor shall berefrigerant gas cooled, high torque, hermetic induction type, four-pole, withinherent thermal protection on all three phases and shall be mounted on rubbervibration isolators. Provide part-winding start on 208/230 volt units and across-the-line start on 380/460/575 volt units.

B. Evaporator: The evaporator shall be direct expansion type with steel shell,internal water baffles, and internally finned copper tubes roller expanded intocarbon steel tube sheets. Refrigerant heads shall be removable. The cooler shallbe insulated with a heavy layer of closed cell foamed insulation. It shall bedesigned, tested and stamped in accordance with ASME Code requirements.

C. Condenser: Horizontal shell and finned tube type with steel shell and integralfinned copper tubes rolled into steel tube sheets which are to be drilled, andmultiple grooved to facilitate gas-tight rolling. The condenser shall be equippedwith intermediate tube supports. Construct condenser in accordance with therequirements of ASME Section VIII Unfired Pressure Vessel Code. It shall bedesigned for 225 psi (1552 kPa) water side working pressure and 450 psig (3104kPa) refrigerant side pressure and be provided with an ASME, pressure reliefvalve.

D. Refrigerant Circuit: The refrigerant circuit shall include a liquid line shutoff valve,replaceable core filter-drier, sight glass with moisture indicator, liquid linesolenoid valve (no exceptions), thermal expansion valve, discharge gas muffler,insulated suction line and a 450 psig (3104 kPa) relief valve.

E. Control System: A centrally located control panel shall contain the field powerconnection points, control interlock terminals, and control system. Power andstarting components shall include automatic circuit breakers, fused control circuitwith transformer, a motor contactor, solid-state start timer, solid-state compressorthree-phase motor overload protection, and unit power terminal blocks forconnection to remote disconnect switch. Hinged access doors shall be lockable.Deadfront panels are required to protect against accidental contact with linevoltage when accessing the control system.

Safety and operating control shall include unit control stop switch, recyclingpumpdown control, oil safety switch, high and low pressure safety switch, watertemperature controller, freeze protection pressurestat. Unit shall provide limitedrecycling pumpdown protection at all times.

F. The following options are to be included:• Part winding start• Three phase power loss with under and over voltage protection• Refrigerant and oil pressure gauges• High return water thermostat to keep compressor unloaded with high

startup water temperatures. Contractor to field mount sensor and fieldwire to control panel.

• Hot gas bypass on all circuits• Chilled water flow switch to be field mounted by the contractor and field

wired to terminals in the control panel.• R-I-S or spring vibration isolators for field installation per plans.• Acoustic sound enclosure

Page 74: Reciprocating Chillers - Daikin Applied

74 Product Manual WHR-2

PART 3 - EXECUTION

3.01 INSTALLATION

A. Install in strict accordance with manufacturer’s requirements, shop drawings, andContract Documents.

B. Adjust and level chiller in alignment on supports.

C. Coordinate electrical installation with electrical contractor.

D. Coordinate controls with control contractor.

E. Provide all appurtenances required to insure a fully operational and functionalchiller.

3.02 START-UP

A. Insure proper charge of refrigerant and oil.

B. Provide testing, and starting of machine, and instruct the Owner in its properoperation and maintenance.

Page 75: Reciprocating Chillers - Daikin Applied

Product Manual WHR-2 75

Water-Cooled, WHR 040E through WHR 210EPART 1 - GENERAL

1.01 SUMMARY

Section includes design, performance criteria, refrigerants, controls, and installationrequirements for water-cooled reciprocating compressor packaged chillers.

1.02 REFERENCES

Comply with applicable Standards/Codes of ARI 550/590-98, ANSI/ASHRAE 15, ASHRAEStandard 90.1, ASME Section VIII, NEC, and OSHA as adopted by the State.

1.03 SUBMITTALS

A. Submit shop drawings and product data in accordance with contractspecifications.

B. Submittals shall include the following:

1. Dimensioned plan and elevation view drawings, required clearances, andlocation of all field connections.

2. Summary of all auxiliary utility requirements such as: electricity, water,compressed air, etc. Summary shall indicate quality and quantity of eachrequired utility.

3. Single line schematic drawing of the power field hookup requirements,indicating all items that are furnished.

4. Schematic diagram of control system indicating points for fieldconnection. Diagram shall fully delineate field and factory wiring.

5. Certification of factory run test of chiller unit signed by company officer.

6. Installation manual.

1.04 QUALITY ASSURANCE

A. Qualifications; Equipment manufacturer must specialize in the manufacture of theproducts specified and have five years experience with the equipment andrefrigerant offered.

B Regulatory Requirements: Comply with the codes and standards specified.

C Chiller manufacturer must be ISO 9002 registered.

Page 76: Reciprocating Chillers - Daikin Applied

76 Product Manual WHR-2

1.05 DELIVERY AND HANDLING

A. Chillers shall be delivered to the job site completely assembled and charged withrefrigerant and oil by the manufacturer.

B. Comply with the manufacturers instructions for rigging and handling equipment.

1.04 WARRANTY

The equipment manufacturer’s warranty shall be for a period of one year from date ofequipment start up but not more than 18 months from shipment. The warranty shall coverdefective material and workmanship within the above period, excluding refrigerant.

PART 2--PRODUCTS

2.01 ACCEPTABLE MANUFACTURERS

A. McQuay International

B. (Approved Equal)

2.02 UNIT DESCRIPTION

Provide and install as shown on the plans factory assembled, factory charged, and factoryrun tested water-cooled reciprocating compressor packaged chillers in the quantityspecified. Each chiller shall consist of multiple accessible-hermetic reciprocatingcompressors, multi-circuit direct expansion evaporator, water-cooled condensers, controlsystem and all components necessary for safe and controlled unit operation.

2.03 DESIGN REQUIREMENTS

A. General: Provide a complete reciprocating packaged chiller as specified herein andas shown on the drawings. The unit shall be in accordance with the standardsreferenced in section 1.02 and any local codes in effect.

B. Performance: Refer to the schedule of performance on the drawings. Performanceshall be in accordance with applicable ARI Standard.

C. Acoustics: Sound pressure levels for the unit shall not exceed the followingspecified levels. The manufacturer shall provide the necessary sound treatmentto meet these levels if required. Sound data shall be provided with the quotation.Test shall be in accordance with ARI Standard 575.

Octave Band

63 125 250 500 1000 2000 4000 8000 dBA____ ____ ____ ____ ____ ____ ____ ____ ____

Page 77: Reciprocating Chillers - Daikin Applied

Product Manual WHR-2 77

2.04 CHILLER COMPONENTS

A. Compressors: The compressors shall be accessible hermetic reciprocating typewith suction and discharge service valves, crankcase oil heaters and suctionstrainers. The compressors shall have a forced feed lubrication system with areversible oil pump, oil sight glass, and oil charge. The compressor motors shallbe refrigerant gas cooled, high torque, hermetic induction type, four-pole, withinherent thermal protection on all three phases and shall be mounted on rubbervibration isolators.

B. Evaporator: The evaporator shall be direct expansion type with steel shell,polypropylene water baffles, and internally finned copper tubes roller expandedinto carbon steel tube sheets. Refrigerant heads shall be removable. The coolershall be insulated with 3/4 inch (12.7mm) closed cell insulation and painted withresilient paint to resist cracking. It shall be designed, tested and stamped inaccordance with ASME Code requirements and have a 175 psi (1206 kPa)maximum water side working pressure.

C. Condensers: Horizontal shell and finned tube type with steel shell and integralfinned copper tubes rolled into steel tube sheets which are to be drilled, andmultiple grooved to facilitate gas-tight rolling. The chiller shall be equipped withintermediate tube supports. Construct condenser in accordance with therequirements of ASME Section VIII Unfired Pressure Vessel Code and ANSI B9.1Safety Code. It shall be designed for 225 psi (1550 kPa) water side workingpressure and 450 psig (3104 kPa) refrigerant side pressure and be provided withASME, ANSI B9.1 pressure relief valves.

D. Refrigerant Circuit: Each refrigerant circuit shall include a liquid line shutoff valve,replaceable core filter-drier, sight glass with moisture indicator, liquid linesolenoid valve (no exceptions), thermal expansion valve, and insulated suctionline. The discharge line shall be equipped with a discharge muffler.

E. Control System: A centrally located control panel shall contain the field powerconnection points, control interlock terminals, and control system. Power andstarting components shall include, fused control circuit with transformer, a motorcontactor, solid-state start timer, solid-state compressor three-phase motoroverload protection, and unit power terminal blocks for connection to remotedisconnect switch. Hinged access doors shall be lockable. Deadfront panels arerequired to protect against accidental contact with line voltage when accessingthe control system.

Safety and operating control shall include unit control stop switch, recyclingpumpdown control, oil safety switch, high and low pressure safety switch, watertemperature controller, freeze protection pressurestat. The unit shall unload eachrefrigerant circuit alternately. Unit shall provide recycling pumpdown protectionat all times.

--OR--

E. Microprocessor based control system: A centrally located control panel shallcontain the field power connection points, control interlock terminals, and controlsystem. Power and starting components shall include factory controltransformer, fusing of control circuit, solid-state start timer, solid-statecompressor three-phase motor overload protection, and unit power terminalblocks for connection to remote disconnect switch. Hinged access doors shall belockable. Deadfront panels are required to protect against accidental contact withline voltage when accessing the control system.

Page 78: Reciprocating Chillers - Daikin Applied

78 Product Manual WHR-2

The system shall stage the unit based on the leaving water temperature. Safetiescontrolled by the microprocessor include oil differential pressure, motorprotection, high pressure, loss of refrigerant, loss of water flow, freeze protection,and low refrigerant pressure. Controls shall include auto/stop switch, chilledwater setpoint adjustment, anti-recycle timer, and digital display with watertemperature and setpoint, operating temperatures and pressures, and diagnosticmessages. The following features and functions shall be included:

1. The LCD type display shall have a minimum of 32 characters with allmessages in plain English. Coded messages are not acceptable.

2. Critical parameters shall have their own section of control and bepassword protected.

3. Resetting chilled water temperature by either controlling the returnchilled water temperature or by a remote 4-20mA DC signal.

4. A soft load function to prevent the system from operating at full loadduring the chilled water pulldown period.

5. An electronic time clock to allow programming of a yearly scheduleaccommodating weekends and holidays.

6. Auto restart after a power failure, not requiring external battery back-upor auxiliary power for maintaining program memory.

7. Safety shutdowns shall be date and time stamped with systemtemperatures and pressures recorded. A minimum of six previousoccurrences shall be kept in a revolving memory.

8. Start-to-start and stop-to-start timers to provide minimum compressoroff-time with maximum motor protection.

9. Capability of communication with a PC or remote monitoring through atwisted pair RS-232 interface.

10. Lead-lag by manual selection or automatically by circuit run hours.

11. Continuous diagnostic checks of unit operation to provide a pre-alarmsignal in advance of a shutdown allowing time for remedial action to betaken.

F. The following options are to be included:

• Refrigerant and oil pressure gauges for non-microprocessor controls.

• High return water thermostat to keep compressor unloaded with highstartup water temperatures. Contractor to field mount sensor and fieldwire to control panel.

• Hot gas bypass on all circuits.

• Chilled water flow switch to be field mounted in the chilled water lineand field wired to terminals in the control panel.

• R-I-S or spring vibration isolators for field installation per plans.

• Disconnect switch field installed.

• Acoustical compressor enclosures.

Page 79: Reciprocating Chillers - Daikin Applied

Product Manual WHR-2 79

PART 3 - EXECUTION

3.01 INSTALLATION

A. Install in strict accordance with manufacturer’s requirements, shop drawings, andContract Documents.

B. Adjust and level chiller in alignment on supports.

C. Coordinate electrical installation with electrical contractor.

D. Coordinate controls with control contractor.

E. Provide all appurtenances required to insure a fully operational and functionalchiller.

3.02 START-UP

A. Ensure proper charge of refrigerant and oil.

B. Provide testing, and starting of machine, and instruct the Owner in its properoperation and maintenance.

Page 80: Reciprocating Chillers - Daikin Applied

80 Product Manual WHR-2

Remote Condenser Chiller, WHR 017 through 030

PART 1 - GENERAL

1.01 SUMMARY

Section includes design, performance criteria, refrigerants, controls, and installationrequirements for water-cooled reciprocating compressor packaged chillers.

1.02 REFERENCES

Comply with applicable Standards/Codes of ANSI/ASHRAE 15, ASHRAE 90.1, ASMESection VIII, NEC, and OSHA as adopted by the State.

1.03 SUBMITTALS

A. Submit shop drawings and product data in accordance with contractspecifications.

B. Submittals shall include the following:

1. Dimensioned plan and elevation view drawings, required clearances, andlocation of all field connections.

2. Summary of all auxiliary utility requirements such as: electricity, water,compressed air, etc. Summary shall indicate quality and quantity of eachrequired utility.

3. Single line schematic drawing of the power field hookup requirements,indicating all items which are furnished.

4. Schematic diagram of control system indicating points for fieldinterface/connection. Diagram shall fully delineate field and factorywiring.

5. Manufacturer’s certification of factory run test of chiller unit signed bycompany officer.

6. Installation manuals.

1.04 QUALITY ASSURANCE

A. Qualifications; Equipment manufacturer must specialize in the manufacture of theproducts specified and have five years experience with the equipment andrefrigerant offered.

B Regulatory Requirements: Comply with the codes and standards specified.

C Chiller manufacturer must be ISO 9002 registered.

Page 81: Reciprocating Chillers - Daikin Applied

Product Manual WHR-2 81

1.05 DELIVERY AND HANDLING

A. Chillers shall be delivered to the job site completely assembled and charged withrefrigerant and oil by the manufacturer.

B. Comply with the manufacturers instructions for rigging and handling equipment.

1.06 WARRANTY

The equipment manufacturer’s warranty shall be for a period of one year from date ofequipment start and acceptance but not more than 18 months from shipment. Thewarranty shall cover defective material and workmanship within the above period,excluding refrigerant.

PART 2--PRODUCTS

2.01 ACCEPTABLE MANUFACTURERS

A. McQuay International

B. (Approved Equal)

2.02 UNIT DESCRIPTION

Provide and install as shown on the plans factory assembled, and factory run tested,reciprocating compressor chiller(s) in the quantity specified. Each chiller shall consist ofhermetic reciprocating compressor, direct expansion evaporator, control system and bearranged for connection to a remote single circuit condenser specified elsewhere. Thecombined components shall contain everything necessary for safe and controlled unitoperation.

2.03 DESIGN REQUIREMENTS

A. General: Provide a complete reciprocation packaged chiller as specified herein andas shown on the drawings. The unit shall be in accordance with the standardsreferenced in section 1.02 and any local codes in effect.

B. Performance: Refer to the schedule of performance on the drawings. Performanceshall be in accordance with applicable ARI Standard.

C. Acoustics: Sound pressure levels for the unit shall not exceed the followingspecified levels. The manufacturer shall provide the necessary sound treatmentto meet these levels if required. Sound data shall be provided with the quotation.Test shall be in accordance with ARI Standard 575.

Octave Band

63 125 250 500 1000 2000 4000 8000 dBA____ ____ ____ ____ ____ ____ ____ ____ ____

Page 82: Reciprocating Chillers - Daikin Applied

82 Product Manual WHR-2

2.04 CHILLER COMPONENTS

A. Compressor: The compressor shall be of the accessible hermetic reciprocatingtype with suction and discharge service valves, crankcase oil heater and suctionstrainer. Compressor shall have a forced feed lubrication system with a reversibleoil pump, oil sight glass, and oil charge. The compressor motor shall berefrigerant gas cooled, high torque, hermetic induction type, four-pole, withinherent thermal protection on all three phases and shall be mounted on rubbervibration isolators.

B. Evaporator: The evaporator shall be direct expansion type with steel shell,internal water baffles, and internally finned copper tubes roller expanded intocarbon steel tube sheets. Refrigerant heads shall be removable. The cooler shallbe insulated with a heavy layer of closed cell foamed insulation. It shall bedesigned, tested and stamped in accordance with ASME Code requirements.

C. Refrigerant Circuit: The refrigerant circuit shall include a liquid line shutoff valve,replaceable core filter-drier, sight glass with moisture indicator, liquid linesolenoid valve (no exceptions), thermal expansion valve, discharge gas muffler,insulated suction line and a 450 psig (3104 kPa) relief valve.

D. Control System: A centrally located control panel shall contain the field powerconnection points, control interlock terminals, and control system. Power andstarting components shall include automatic circuit breakers, fused control circuitwith control transformer, a motor contactor, solid-state start timer, solid-statecompressor three-phase motor overload protection, and unit power terminalblocks for connection to remote disconnect switch. Hinged access doors shall belockable. Deadfront panels are required to protect against accidental contact withline voltage when accessing the control system.

Safety and operating control shall include unit control stop switch, recyclingpumpdown control, oil safety switch, high and low pressure safety switch, watertemperature controller, freeze protection pressurestat. Unit shall provide limitedrecycling pumpdown protection at all times.

E. The following options are to be included:• Three phase power loss with under and over voltage protection.• Refrigerant and oil pressure gauges.• High return water thermostat to keep compressor unloaded with high

startup water temperatures. Contractor to field mount sensor and fieldwire to control panel.

• Hot gas bypass.• Chilled water flow switch to be field mounted by the contractor in the

chilled water line and field wired to terminals in the control panel.• R-I-S or spring vibration isolators for field installation.• Acoustic compressor enclosure when available from manufacturer.

PART 3 - EXECUTION

3.01 INSTALLATION

A. Install in strict accordance with manufacturer’s requirements, shop drawings, andContract Documents. Field installed refrigerant piping design to be approved bythe chiller manufacturer.

B. Adjust and level chiller in alignment on supports.

Page 83: Reciprocating Chillers - Daikin Applied

Product Manual WHR-2 83

C. Coordinate electrical installation with electrical contractor.

D. Coordinate controls with control contractor.

E. Provide all appurtenances required to insure a fully operational and functionalchiller.

3.02 START-UP

A. Insure proper charge of refrigerant and oil.

B. Provide testing, and starting of machine, and instruct the Owner in its properoperation and maintenance.

Page 84: Reciprocating Chillers - Daikin Applied

84 Product Manual WHR-2

Remote Condenser Chiller, WHR 040E - WHR 210EPART 1 - GENERAL

1.01 SUMMARY

Section includes design, performance criteria, refrigerants, controls, and installationrequirements for water-cooled reciprocating compressor packaged chillers.

1.02 REFERENCES

Comply with applicable Standards/Codes of ANSI/ASHRAE 15, ASHRAE Standard 90.1,ASME Section VIII, NEC, and OSHA as adopted by the State.

1.03 SUBMITTALS

A. Submit shop drawings and product data in accordance with contractspecifications.

B. Submittals shall include the following:

7. Dimensioned plan and elevation view drawings, required clearances, andlocation of all field connections.

8. Summary of all auxiliary utility requirements such as: electricity, water,compressed air, etc. Summary shall indicate quality and quantity of eachrequired utility.

9. Single line schematic drawing of the power field hookup requirements,indicating all items that are furnished.

10. Schematic diagram of control system indicating points for fieldconnection. Diagram shall fully delineate field and factory wiring.

11. Certification of factory run test of chiller unit signed by company officer.

12. Installation manual.

1.04 QUALITY ASSURANCE

A. Qualifications; Equipment manufacturer must specialize in the manufacture of theproducts specified and have five years experience with the equipment andrefrigerant offered.

B Regulatory Requirements: Comply with the codes and standards specified.

C Chiller manufacturer must be ISO 9002 registered.

Page 85: Reciprocating Chillers - Daikin Applied

Product Manual WHR-2 85

1.05 DELIVERY AND HANDLING

A. Chillers shall be delivered to the job site completely assembled and charged withrefrigerant and oil by the manufacturer

B. Comply with the manufacturers instructions for rigging and handling equipment.

1.04 WARRANTY

The equipment manufacturer’s warranty shall be for a period of one year from date ofequipment start up but not more than 18 months from shipment. The warranty shall coverdefective material and workmanship within the above period, excluding refrigerant.

PART 2--PRODUCTS

2.01 ACCEPTABLE MANUFACTURERS

A. McQuay International

B. (Approved Equal)

2.02 UNIT DESCRIPTION

Provide and install as shown on the plans factory assembled, and factory run testedremote condenser reciprocating compressor packaged chiller(s) in the quantity specified.Each chiller shall consist of multiple accessible-hermetic reciprocating compressors, multi-circuit direct expansion evaporator, control system and, when completely installed with theremote condenser, constitute all components necessary for safe and controlled unitoperation.

2.03 DESIGN REQUIREMENTS

A. General: Provide a complete reciprocating packaged chiller as specified herein andas shown on the drawings. The unit shall be in accordance with the standardsreferenced in section 1.02 and any local codes in effect.

B. Performance: Refer to the schedule of performance on the drawings. Performanceshall be in accordance with applicable ARI Standard.

C. Acoustics: Sound pressure levels for the unit shall not exceed the followingspecified levels. The manufacturer shall provide the necessary sound treatmentto meet these levels if required. Sound data shall be provided with the quotation.Test shall be in accordance with ARI Standard 575.

Octave Band

63 125 250 500 1000 2000 4000 8000 dBA____ ____ ____ ____ ____ ____ ____ ____ ____

Page 86: Reciprocating Chillers - Daikin Applied

86 Product Manual WHR-2

2.04 CHILLER COMPONENTS

A. Compressors: The compressors shall be accessible hermetic reciprocating typewith suction and discharge service valves, crankcase oil heaters and suctionstrainers. The compressors shall have a forced feed lubrication system with areversible oil pump, oil sight glass, and oil charge. The compressor motors shallbe refrigerant gas cooled, high torque, hermetic induction type, four-pole, withinherent thermal protection on all three phases and shall be mounted on rubbervibration isolators.

B. Evaporator: The evaporator shall be direct expansion type with steel shell,polypropylene water baffles, and internally finned copper tubes roller expandedinto carbon steel tube sheets. Refrigerant heads shall be removable. The coolershall be insulated with 3/4 inch (12.7mm) closed cell insulation and painted withresilient paint to resist cracking. It shall be designed, tested and stamped inaccordance with ASME Code requirements and have a 175 psi (1206kPa)maximum water side working pressure.

C. Refrigerant Circuit: Each refrigerant circuit shall include a liquid line shutoff valve,replaceable core filter-drier, sight glass with moisture indicator, liquid linesolenoid valve (no exceptions), thermal expansion valve, and insulated suctionline. The discharge line shall be equipped with a discharge muffler.

D. Control System: A centrally located control panel shall contain the field powerconnection points, control interlock terminals, and control system. Power andstarting components shall include, fused control circuit with transformer, a motorcontactor, solid-state start timer, solid-state compressor three-phase motoroverload protection, and unit power terminal blocks for connection to remotedisconnect switch. Hinged access doors shall be lockable. Deadfront panels arerequired to protect against accidental contact with line voltage when accessingthe control system.

Safety and operating control shall include unit control stop switch, recyclingpumpdown control, oil safety switch, high and low pressure safety switch, watertemperature controller, freeze protection pressurestat. The unit shall unload eachrefrigerant circuit alternately. Unit shall provide recycling pumpdown protectionat all times.

--OR--

E. Microprocessor based control system: A centrally located control panel shallcontain the field power connection points, control interlock terminals, and controlsystem. Power and starting components shall include factory fusing of controlcircuit with control transformer, solid-state start timer, solid-state compressorthree-phase motor overload protection, and unit power terminal blocks forconnection to remote disconnect switch. Hinged access doors shall be lockable.Deadfront panels are required to protect against accidental contact with linevoltage when accessing the control system.

Page 87: Reciprocating Chillers - Daikin Applied

Product Manual WHR-2 87

The system shall stage the unit based on the leaving water temperature. Safetiescontrolled by the microprocessor include oil differential pressure, motorprotection, high pressure, loss of refrigerant, loss of water flow, freeze protection,and low refrigerant pressure. Controls shall include auto/stop switch, chilledwater setpoint adjustment, anti-recycle timer, and digital display with watertemperature and setpoint, operating temperatures and pressures, and diagnosticmessages. The following features and functions shall be included:

1. The LCD type display shall have a minimum of 32 characters with allmessages in plain English. Coded messages are not acceptable.

2. Critical parameters shall have their own section of control and bepassword protected.

3. Resetting chilled water temperature by either controlling the returnchilled water temperature or by a remote 4-20mA DC signal.

4. A soft load function to prevent the system from operating at full loadduring the chilled water pulldown period.

5. An electronic time clock to allow programming of a yearly scheduleaccommodating weekends and holidays.

6. Auto restart after a power failure, not requiring external battery back-upor auxiliary power for maintaining program memory.

7. Safety shutdowns shall be date and time stamped with systemtemperatures and pressures recorded. A minimum of six previousoccurrences shall be kept in a revolving memory.

8. Start-to-start and stop-to-start timers to provide minimum compressoroff-time with maximum motor protection.

9. Capability of communication with a PC or remote monitoring through atwisted pair RS-232 interface.

10. Lead-lag by manual selection or automatically by circuit run hours.

11. Continuous diagnostic checks of unit operation to provide a pre-alarmsignal in advance of a shutdown allowing time for remedial action to betaken.

F. The following options are to be included:

• Refrigerant and oil pressure gauges for non-microprocessor controls.

• High return water thermostat to keep compressor unloaded with highstartup water temperatures. Contractor to field mount sensor and fieldwire to control panel.

• Hot gas bypass on all circuits.

• Chilled water flow switch to be field mounted in the chilled water lineand field wired to terminals in the control panel.

• Spring vibration isolators for field installation.

• Disconnect switch field installed

• Acoustical compressor enclosures

Page 88: Reciprocating Chillers - Daikin Applied

88 Product Manual WHR-2

PART 3 - EXECUTION

3.01 INSTALLATION

A. Install chiller and remote condenser with interconnecting piping in strictaccordance with manufacturer’s requirements, shop drawings, and ContractDocuments. Chiller manufacturer must approve the refrigerant piping design.

B. Adjust and level chiller in alignment on supports.

C. Coordinate electrical installation with electrical contractor.

D. Coordinate controls with control contractor.

E. Install, pressure test, and evacuate field refrigerant piping.

F. Provide all appurtenances required to insure a fully operational and functionalchiller.

3.02 START-UP

A. Ensure proper charge of refrigerant and oil.

B. Provide testing, and starting of machine, and instruct the Owner in its properoperation and maintenance.