Ivan Dudurych
Eirgrid
Real-time Dynamic
Modelling of the Irish
Power System
Manhattan: morning 14 August 2003
Photo by Mike Albans/NY Daily News Archive via Getty Images
Operational Security
WSAT Development Timeline
MAWAT Concept is proposed
Develop-ment the tool as WSAT jointly with Powertech Labs (Canada)
WSAT installed for testing and validation
On-line WSAT is officially launched in NCC
Official Launch AII-island WSAT in NCC and CHCC
Official Launch 5-min, new EMS-based AII-island WSAT in NCC and CHCC
Sep 2008 May 2009 Sep 2010 Nov 2016 Nov 2012
WSAT – Software Structure
Near real-time Wind limits
Security violation details
Results Display
WSAT Manager
On-line VSAT
On-line TSAT
Study WSAT
Real-time system
snapshot
Wind ForecastP
yth
on
Inte
rfa
ce
Other information
Input data
Security AssessmentReal-time
Contingencies
WSAT Calculations
TSA includes
transient period;
automatics operate
VSA – quasi steady state; time period before
manual actions
20 s 5 min
WSAT – Hardware Architecture
System Model of Time Domain
Simulation
Elements of an Excitation System
Ref To Grid
Limiters protective circuits
Voltage Transducer &
Load Compensator
Regulator Exciter Generator
Power System
Stabilizer
Detailed and Equivalent WF Model
110 kV
20 kV
RTr
XTr BTr
GTr
MVAbase=100 MVA
Rtr
Xtr RG
XG
MVAbase=∑Machine MVA
Second Generation Wind Models (WECC)
Model Validation (Stage 1)
Model Validation (Stage 2)
Model Validation (Stage 3)
Model Validation (Stage 3)
Original response (MW) PMU response (MW) Tuned response (MW)
North-West Wind Farm Model v Reality
WSAT Monitor – base case
TSAT Calculations
TSAT Applies faults on each line cleared in accordance to
the installed protection (TSAT Contingencies)
• Monitors machine rotor angles
• Computes Transient Stability
index for all islands
• Attempts to calculate a preventative control measure
(PCM), i.e. a recommendation from WSAT on how the
instability can be prevented.
Total generation
Source Sink
Wind - Conventional generation
Power Transfer
Transfer increase
Base level First
Stability
limit
Second
Stability
limit
All dispatchable
reserves are
exhausted
SecureVoltage
violationsCollapse
Wind MW
Initial
Value
WSAT
Limit
Power Transfer: Example of stages
WSAT monitor - transfers
WSAT Secure Wind graph
WSAT Frequency and RoCoF Summary Table
Transient Insecurity Example
Frequency Insecurity Example
WSAT Conclusion
Combined Real-time and Forecast WSAT
Up to 6 hr ahead
Up to 24 hr ahead
2-D Transfers
Two-dimensional transfer
Secure area
Questions?