5
Authorities Having Jurisdiction should be consulted before installation. System Overview: Radix Wire & Cable has been 2-hour, UL 2196 certified for use in Champion Fiberglass XW™ phenolic system conduit. This certification will allow for a non-metallic solution for alarm system applications where the use of metallic raceways are not desired. This Addendum to the DuraLife ® II FPLR/FPLR-CI Installation Guide will offer information as to the proper assembly of this unique system, as well as information as to the system components that have the 2-hour fire certification as listed for use in FHIT/FHIT7 28C. UL 2196 ADDENDUM DuraLife ® II FPLR FAS 90 Shielded/Unshielded Fire Resistive Cables 18AWG/2C, 16AWG/2C, 14AWG/2C, 12AWG/2C Phenolic System Guidelines FHIT/FHIT7 28C Item No. CTU CTS CAN/ULC S-139 September 2019

Radix Wire Cable - Champion Fiberglass

  • Upload
    others

  • View
    0

  • Download
    0

Embed Size (px)

Citation preview

Authorities Having Jurisdiction shouldbe consulted before installation.

System Overview:

RadixWire&Cablehasbeen2-hour,UL2196certifiedforuseinChampionFiberglassXW™phenolicsystemconduit.Thiscertificationwillallowforanon-metallicsolutionforalarmsystemapplicationswheretheuseofmetallicracewaysarenotdesired.ThisAddendumtotheDuraLife®IIFPLR/FPLR-CIInstallationGuidewillofferinformationastotheproperassemblyofthisuniquesystem,aswellasinformationastothesystemcomponentsthathavethe2-hourfirecertificationaslistedforuseinFHIT/FHIT728C.

UL 2196

ADDENDUMDuraLife®IIFPLRFAS90Shielded/UnshieldedFireResistiveCables

18AWG/2C,16AWG/2C,14AWG/2C,12AWG/2CPhenolicSystemGuidelines

FHIT/FHIT728C

Item No. CTUCTS

CAN/ULC S-139

September2019

DuraLife®IIFPLR/FAS90cableshavebeencertifiedtoUL2196for2-hourfirecomplianceinChampionFiberglassXW™phenolicconduitandsystemcomponents.Thecertifieditemnos.arelistedbelow:

System Certified Components

Straightsections;standardlengths ChampionFiberglassPartNos.

1.00”tradeI.D.(10ft.) 10EXW10S

1.25”tradeI.D.(20ft.) 12EXW10S

1.50”tradeI.D.(20ft.) 15EXW10S2.00”tradeI.D.(20ft.) 20FXW10S

A. Phenolic Conduit

Straightsections ChampionFiberglassPartNos.

1.00”tradeI.D. 10EXW42

1.25”tradeI.D. 12EXW42

1.50”tradeI.D. 15EXW422.00”tradeI.D. 20FXW42

B. Phenolic Conduit Couplers

90°sections;12”radius ChampionFiberglassPartNos.

1.00”tradeI.D. 10EXW90P

1.25”tradeI.D. 12EXW90P

1.50”tradeI.D. 15EXW90P2.00”tradeI.D. 20FXW90P

C. Phenolic Elbow Joints

Non-threaded;pinassembly;O-ring ChampionFiberglassPartNos.

1.00”tradeI.D. 10EXW30-2196

1.25”tradeI.D. 12EXW30-2196

1.50”tradeI.D. 15EXW30-21962.00”tradeI.D. 20FXW30-2196

D. Phenolic Box Fittings

DuraLife®IIFPLR/FAS90cablesareapprovedformultiplefillallowancesinChampionXWphenolicconduit.Seetablebelowformaximumcable-fill:

Phenolic Conduit Fill Allowances

Fill Allowances: Horizontal/VerticalConduit Size

Cable 1” 1.25” 1.5” 2”

18AWGUnshielded 3 6 9 X

18AWGShielded 3 5 7 X

16AWGUnshielded 2 4 6 10

16AWGShielded 2 4 6 10

14AWGUnshielded 2 3 4 10

14AWGShielded 1 3 4 10

12AWGUnshielded 2 3 4 9

DuraLife®IIFPLR/FAS90cables,bothshieldedandunshielded,canbemechanicallysplicedwhenusingapprovedNEMA1spliceboxes.Splicesareallowed(upto8conductors)inbothhorizontalandverticalinstallations.PleaserefertotheapprovedspliceprocedureforFHITSystem28C,andthecertifiedsplicecomponentsonpages7-9intheDuraLife®IIFPLR/FPLR-CIFAS90Dual-Rated Installation Instructions - Shielded and Unshielded,forbothapprovedsplicemethods.

Splice Allowance

• Onetotwocablescanusea8x8x4splicebox• Threeormorecablescanusea10x10x4splicebox• Verticalsplicingcanusea12x6x4splicebox

Requiredwallsupportmustbeamin12gauge,by1½in.wideor1-5/8in.wide,paintedorunpainted,slottedsteelchannelswithhemmedflangeedges.Channelbottomwithorwithoutholes.Lengthsofslottedsteelchannels5ft.andlessshallbesecuredtothewallorfloorwithaminoftwo¼in.diameter(orlarger)by2¼in.minlongconcretescrews,or¼in.diameter(orlarger)by1¾in.longminsteelmasonryanchors.Onescreworanchormustbelocatedateachendoftheslottedsteelchannel.Lengthsofslottedsteelchannelinexcessof5ft.requireaminofthreescrewsoranchors,oneateachendofthechannelandonecentrallylocatedwithinthelengthofthechannel.Forhorizontalcableinstallations,thesupportsshallbespacedatamaximumof5ft.OC.Forverticalcableinstallations,thesupportsshallbespacedamaximum6ft.OC.WheninstallingDuraLife® IIBrandcable(s)shieldedandunshieldedinverticalruns,themaximumverticalriseallowanceofcablewithinshallbe:

• 30ft.betweenterminatingpointsfor18AWG• 35ft.for16,14AWGand12AWG(unshieldedonly)

Phenolic System Support Requirements

Approvedphenolicconduitsupportclampsare:

PartNumber: ERICOER-CD2B(1”) ERICOER-CD3B(1.25”) ERICOER-CD4B(1.5”) ERICOER-CD5B(2”)

**NOTE-Duetothesystemassemblyrequirementofadhesiveforin-linecouplers,boxfittings,elbowjoints,asupportclampshouldbeusedwithin24”ofthelocationofthebondedjoint.Seeillustrationsbelow:

GeneralMethod:Thecomponentsofthephenolicsystemshouldbegluedbeforetheconduitisplacedonthewallsupports.Thismethodbelowwilldescribetheproperpracticetousetheepoxyadhesive:

• Thetwocomponentadhesivesystemwillbegintocurein3-7minutes,andrequiresapproximately30minutesofsettimebeforehandlingorpullingcables.Thetwocomponentsystemwillbesuppliedinadhesivetubeswithanaccompanyingmixertipthatwillmixthetwocomponentstogether.Theadhesivetubeshouldbeinsertedintotheapplicatordispenser(mustbepurchasedseparately).Themixertipshouldthenbeattachedtotheadhesivetubeanthentheadhesiveisreadytobeapplied.

PartNos.:ChampionFiberglassMixCM-2070• Epoxy---SuperFastGel#43558• Hardener---#43558• MixingTip---CM-MT-20• AdhesiveGun---CM-AG-20

• Theendsurfaceoftheconduit(approx.9”)shouldbelightlysandedtoremovethesheenfromthesurfacepriortoapplicationoftheadhesive(seeillustrationbelow).

• Whentheadhesiveapplicatortriggerisdepressed,theadhesivewillself-mixinthemixertip.Afewsquirtsofadhesiveshouldbeclearedfromthetubetogetthepropercomponentmixratio.Theadhesiveshouldbeliberallyspreadwithasteelspatulaleavinganapprox.10-15milthicknessoverthesandedsurfaceofconduitend.Theconduitendcanthenbeinsertedintothecorrespondingcoupling,orboxfitting,whileusingaslighttwistingmotion.Anyexcessadhesivecanbescrapedoffwiththesteelspatulaorwipedoffwitharag.Glovesandsafetyglassesarerecommendedwhenusingtheadhesive.

Adhesive Joint Application