Upload
lamque
View
220
Download
4
Embed Size (px)
Citation preview
Radiant cooling and thermal comfort
Dr Simos Oxizidis [email protected]
University College Dublin Meeting01 / 12 /2010
Heating and Cooling Terminal Units
High temperature cooling hydronicradiant systems are mainly building integrated (embedded) systems, in the form of radiant building surfaces like walls, floors or ceilings.
Heating & Cooling Terminal Units
Heating Mode TemperatureThermal Energy
Carrier
Radiant systems
Convective systems
Hybrid systems
Low Temperature
systems
Medium Temperature
systems
High Temperature
systems
Air systems
Steam systems
Water systems
(hydronic)
Refrigerant systems
Electric systems
Direct fired systems
High Temperature Cooling Hydronic Radiant Systems
Provision of better thermal comfort conditions by removing heat mainly by means of radiation.
Elimination of the local thermal discomfort causes which are usually related to the operation of convection cooling systems.
Absence of noise and draughts due to fan operation, resulting in discrete conditioning of spaces.
Comfort can be achieved with higher air temperatures (by decreasing the mean radiant temperature) thus, limiting air exchange heat gains.
Use of high temperature cooling enables the efficient use of plant equipment (air to water heat pumps) with increased overall energy efficiency.
By thermally activating the building elements, the thermal mass of the building’s envelope can be utilised for cooling, resulting in lower peak loads and lower equipment capacity. In addition, the building’s thermal mass can be used as thermal energy storage facility.
Thermal Comfort
There are two distinct ways of estimating comfort in a space:
(a) The deterministic route of Fanger’s PMV-PPD model and all its successors, derived from laboratory based research and
(b) the stochastic approach described by the adaptive comfort models that arose from field based research. The latter is more suited for evaluating thermal comfort conditions in free running, naturally ventilated buildings, where no mechanical cooling is used.
Thermal Comfort – The Deterministic Route
0 Neutral (Comfort)
+1 Slightly Warm
+3 Hot
+2 Warm
-1 Slightly Cool
-2 Cool
-3 Cold
1
10
100
-2 -1.5 -1 -0.5 0 0.5 1 1.5 2
PP
D (
%)
PMV
PMV (Predicted Mean Vote) is a function of
Air temperature
Human activity
Clothing type
Radiant temperature
Relative humidity
Air speed
Related with PMV is the PPD index (PPD –
Predicted Percent of Dissatisfied people)
Thermal Comfort – The Deterministic Route
PMV index in a room (limits for 10% of dissatisfied people – -0.5≤PMV≤
+0.5)
-1
-0.75
-0.5
-0.25
0
0.25
0.5
0.75
1
10 13 16 19 22 25 28 31 34 37 40
PM
V
Ambient Air Temperature (oC]
.
ASHRAE Standard 55 comfort area (limits for 10% of
dissatisfied people)
0
0.004
0.008
0.012
0.016
0.02
22 23 24 25 26 27 28 29 30
Hu
mid
ity
Rat
io
Operative temperature (oC)
0.5 clo (clothinginsulation
of occupants)
Thermal Comfort – The Stochastic Approach
The fundamental assumption of the adaptive approach is expressed by the adaptive principle: If a change occurs such as to produce discomfort, people react in ways which tend to restore their comfort.
There is a comfort indoor temperature that is linearly correlated with the outdoor temperature
16
18
20
22
24
26
28
30
32
5 10 15 20 25 30 35
Mean Monthly Outdoor Temperature [oC]
Ind
oo
r O
pe
rative
Te
mp
era
ture
[oC
]
90% acceptability limits
80% acceptability limits
ASHRAE Standard 55 acceptable operative temperature ranges for naturally conditioned
spaces
Test Cell Simulations
A model of an test cell was simulated for a four month cooling period (June to September) under the climatic data of Thessaloniki, Greece.
Simulation Conditions – Climatic Data
Daily Average Global Horizontal Radiation [Wh/m2]
Monthly Average Global Horizontal Radiation [Wh/m2]
Simulation Conditions – Climatic Data
Hourly Dry Bulb Temperature for the cooling period [oC]
Simulation Conditions
The U-values of walls, floor, roof and window are 0.33, 0.3, 0.26 and 2.75 W/m2K respectively
For the cell was assumed a constant ventilation of 0.9 ACH. It is occupied by two men who emit 126 W (1.2 met) each, 60% by radiation. The insulation of their clothing is 0.5 clo.
The internal heat gains by electric equipment are 5 W/m2.
For the thermal comfort (PMV index) calculations the air velocity in the cell was assumed 0.15 m/s during the heating season and 0.25 during the cooling season.
The temperature of the thermostatic control was set to 25oC.
Systems Compared
The following terminal units were compared:
Ideal conditioned air (PA)
Fan Coil (FC)
Radiant floor
Heavyweight construction (RF)
Lightweight construction (RFG)
Radiant ceiling (RC)
Radiant wall (RW) – south and north wall only
Heavyweight radiant floor and fan coil (RF FC)
Systems Compared – Radiant Units
a) Radiant Floor Heavyweight construction (RF)
b) Radiant Floor Lightweight construction (RFG)
c) Radiant ceiling (RC)
d) Radiant wall (RW) –south and north wall only
a) b)
c)
d)
Control Strategy for the radiant systems
Chiller
Pump
Supply
Mixing valve
Shut off valves
Return
Limiter
Central
control
unitOutside
temperature
Temperature -
Humidity
Room
sensor
Room
sensor
Local control
unit
Valve
ManifoldFloor
temperature
Control of the Systems
Control of the Systems
Temperature control of the supply water for the fan coil
6
7
8
9
10
11
12
13
15 20 25 30 35 40
Sup
ply
co
ld w
ater
te
mp
erat
ure
[οC
]
Outdoor Temperature [οC]
10
12
14
16
18
20
22
15 20 25 30 35 40
Sup
ply
co
ld w
ater
te
mp
erat
ure
[οC
]
Outdoor Temperature [οC]
0
20
40
60
80
100
24.5 25 25.5 26 26.5
Sup
ly c
old
wat
er f
low
[%
]
Zone Temperature [οC]
Temperature control of the supply water for the radiant surfaces
Flow control of the supply water for the radiant surfaces
Scenarios
Beyond the comparison determined by the above simulation conditions (reference scenario DBT) four other scenarios were investigated:
Controlling the indoor operative temperature (scenario OPT)
Controlling the internal thermal conditions by using the PMV (according to Fanger) index (scenario PMV). In that case it is assumed that the occupants are turning on and off the cooling system depending on their subjective sense of comfort, as quantified by the PMV index. The control value was set to PMV = 0.
Increased ventilation, with ventilation rates set at 1.5 ACH, and control of the operative temperature (scenario OPT VENT)
Increased insulation, with a thickness of 200 mm, and control of the operative temperature (scenario INS)
Results – Cooling load
Accumulative cooling load
Breakout of heat gains
Cooling load
0
10
20
30
40
50
60
Pu
rch
ase
d C
oo
ling
Rat
e [W
/m2]
Time [h]
473.29, 31%
330.35, 21%
64.08, 4%
675.54, 44%
WINDOW OPAQUE VENTILATION INTERNAL
0
10
20
30
40
50
60
10 20 30 40
Pu
rch
ase
d C
oo
ling
Rat
e [W
/m2]
Ambient Air Temperature [oC]
Results – PMV Index
PMV index in a room (limits for 10% of
dissatisfied people – -0.5≤PMV≤ +0.5)
Results – ASHRAE Standard 55
ASHRAE Standard 55 comfort area (limits
for 10% of dissatisfied people)
Results – Energy & Load
0 250 500 750 1000 1250 1500 1750
PA
FC
RF FC
RF
RFG
RC
RW
Purchased Cooling [kWh]
0 10 20 30 40 50 60
PA
FC
RF FC
RF
RFG
RC
RW
Maximum Purchased Cooling Load [W/m2]
Cooling energy consumption [kWh]
Maximum cooling load [W/m2]
Results – Scenarios
0 250 500 750 1000 1250 1500 1750
PA
FC
RF …
RF
RFG
RC
RW
Purchased Cooling [kWh] - 10 OPT0 250 500 750 1000 1250 1500 1750
PA
FC
RF …
RF
RFG
RC
RW
Purchased Cooling [kWh] - 10 OPT VENT
0 250 500 750 1000 1250 1500 1750
PA
FC
RF …
RF
RFG
RC
RW
Purchased Cooling [kWh] - 10 PMV0 250 500 750 1000 1250 1500 1750
PA
FC
RF …
RF
RFG
RC
RW
Purchased Cooling [kWh] - 20 INS
Discussion
Radiant building surfaces present two disadvantages:
They cannot face the latent loads and
have limited capacity.
Radiant systems offer satisfactory cooling with lower thermal energy consumption only when humidity is not an issue.
The hybrid system was offering for all scenarios considered the best thermal comfort conditions with lower energy consumption than the exclusive air system.
Discussion – The Stochastic Approach
If radiant floors can be assumed as non mechanical cooling systems, due to their extremely discrete operation:
absence of draughts and noise due to fan operation,
very limited radiant temperature asymmetry,
mild surface temperatures and
absence of vertical air temperature differences
then why not be assessed by applying the adaptive comfort models (which are based on the psychological expectation of occupants that in their space there is no artificial cooling offered)?
Discussion – The Stochastic Approach
In the adaptive approach the comfort, and therefore also the operative temperature in buildings cooled by radiant floors can be estimated by:
Tcomf = 0.33Trm + 18.8 (1)
Trm = (1 – α)Tod-1 + αTrm-1 (2)
where,
Trm, the exponentially weighted running mean temperature for a day
α, a constant (= 0.8)
Tod-1, the 24-h daily mean temperatures of the previous day
Trm-1, the exponentially weighted running mean temperature for the previous day
Tcomf, the neutral or comfort temperature (operative temperature at which the average person will be thermally neutral)
Results – The Stochastic Approach
Accepting again 10% dissatisfaction, a ±2 K limit range from the comfort temperature can be determined.
20
22
24
26
28
30
32
15 18 21 24 27 30
Co
mfo
rt (
op
era
tive
) te
mp
era
ture
Tco
mf(o
C)
Running mean outdoor temperature Trm [oC]
10 DBT RF
20
22
24
26
28
30
32
15 18 21 24 27 30
Co
mfo
rt (
op
era
tive
) te
mp
era
ture
Tco
mf(o
C)
Running mean outdoor temperature Trm [oC]
10 OPT RF
THANK YOU