1 – 24 SM cable
to UNGC Fiber Loop
1 – 48 PCH 02U
SC Fiber Patch panel
for 24 SM fiber cable
from Fiber Loop
DWG # 1
Rack Elevation IT Equipment – Room 144D
11/03/2015
CA
DB
1 2 3 4 5 6
1 2 3 4 5 6
1 2 3 4 5 6
1 2 3 4 5 6
CA
DB
1 2 3 4 5 6
1 2 3 4 5 6
1 2 3 4 5 6
1 2 3 4 5 6
CA
DB
1 2 3 4 5 6
1 2 3 4 5 6
1 2 3 4 5 6
1 2 3 4 5 6
50 foot
Service
loop
OSP Entry
1 – 24 strand cable
Feed to TC-2 Rm 2081 – 24 strand cable
Feed to TC-3 Rm 3161 – 24 strand cable
Feed to Server Rm 310
Conduits to
TC-1
1 – 24 strand cable
Feed to TC-1 Rm 126
1 – 24 strand cable
to TC-1 Rm 126
1 – 24 strand cable
to TC-2 Rm 208
1 – 24 strand cable
to TC-3 Rm 316
1 – 24 strand cable
to Server Rm 310
Smart-UPS
5 0 0 0
Test
I
O
www.apcc.com
8000VA UPS
Smart-UPS
5 0 0 0
Test
I
O
www.apcc.com
2 – Core/Distribution
Routers
(Redundant)
2 – Firewall/IPS/Proxy/
Anti-Virus
(Redundant)
2 – 48 PCH 02U
SC Fiber Patch panel for four
(4) 24 SM fiber cable
As distribution to remote TCs
(Include a spare PCH)
8000VA UPS
SPARE EQUIPMENT
RACK/CABINET
SPACE FOR FUTURE
BUILDING
SPARE EQUIPMENT
RACK/CABINET
SPACE FOR FUTURE
BUILDING
· 3 – 2ru, 48 Port Fiber Patch Panel
· 1 – 2ru, Blank Panel
· 2 – 5ru, Core/Distribution Routers
· 2 – 2ru, Firewall/IPS
· 8 – 2ru, Cable Management
· (one below each device)
· 2 – 6ru 8000VA UPS
HDD1 Cisco ASA 5585-X SSP-20HDD0
EJECT
CONSOLEAUX
0123456789SFP/SFP+
0MGMT1 USB PW
RBOOT
ALA
RM
ACT
VPN
PS1
PS0
HDD1
DD0
HDD1 Cisco ASA 5585-X SSP-20HDD0
EJECT
CONSOLEAUX
0123456789SFP/SFP+
0MGMT1 USB PW
RBOOT
ALA
RM
ACT
VPN
PS1
PS0
HDD1
DD0
C6880-X-FAN
Fan StatusID
!
OI
C6880-X-3KW-AC IN OUT FAULT ID
100-240V ~ / 16A / 50 - 60Hz
OI
C6880-X-3KW-AC IN OUT FAULT ID
100-240V ~ / 16A / 50 - 60Hz
C6880-X
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
Status16 Port 10/1 GbE Supervisor
XL Tables Reset System ID
ConsoleUSBManagement
Management
CATALYST C6880-XC6880-X-FAN
Fan StatusID
!
OI
C6880-X-3KW-AC IN OUT FAULT ID
100-240V ~ / 16A / 50 - 60Hz
OI
C6880-X-3KW-AC IN OUT FAULT ID
100-240V ~ / 16A / 50 - 60Hz
C6880-X
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
Status16 Port 10/1 GbE Supervisor
XL Tables Reset System ID
ConsoleUSBManagement
Management
CATALYST C6880-X
Sample portrait rack
elevation drawing to
clarify the location, size,
quantity, placement and
association of the ISP,
Data Equipment, and
Audio/Video equipment.
DWG # 2
Rack Elevation TC-01 – Room 126
11/03/2015
CA
DB
1 2 3 4 5 6
1 2 3 4 5 6
1 2 3 4 5 6
1 2 3 4 5 6
Conduit
to TC-3
1 – 24 strand cable
Feed to TC-11 – 24 strand cable
to TC-2 Rm 208
1 – 24 strand cable
to TC-3 Rm 316
1 – 24 strand cable
to Server Rm 310
50 foot
Service
loop
Cable Home run to IT
Room 144D
Power 110V 20A
(NO Backup)
Panel 1RA-18
DATA/VoIP CAT-6 CABLE COUNT
· WAP – Wireless Access Point 25
· LAN – Tele/Data Outlets 51
· FB – Floor Box Data Outlets 14
· WB – Wall Box Data Outlets 21
· SIM – -
TOTAL 111
ConsoleMGMT 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 1 SFP+ 2
RPSSPEEDSTATSYST
MAST STACKMode Console
CATALYST C6800IA – 48FPD10G Uplink Catalyst 6800 Instant Access Series
ConsoleMGMT 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 1 SFP+ 2
RPSSPEEDSTATSYST
MAST STACKMode Console
CATALYST C6800IA – 48FPD10G Uplink Catalyst 6800 Instant Access Series 1 – 2ru, Fiber Patch Panel
3 – 2ru, CAT 6 Patch Panels
3 – 1ru, 48 Port Access Switches
6 – 1ru, Cable Management
(one below each device)
1 – 4ru, 4000VA UPS
4000VA UPS
ConsoleMGMT 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 1 SFP+ 2
RPSSPEEDSTATSYST
MAST STACKMode Console
CATALYST C6800IA – 48FPD10G Uplink Catalyst 6800 Instant Access Series
5125
25%
100%
Sample portrait rack
elevation drawing to
clarify the location, size,
quantity, placement and
association of the ISP,
Data Equipment, and
Audio/Video equipment.
DWG # 3
Rack Elevation TC-02 – Room 208
11/03/2015
CA
DB
1 2 3 4 5 6
1 2 3 4 5 6
1 2 3 4 5 6
1 2 3 4 5 6
Conduit
to TC-3
1 – 24 strand cable
Feed to TC-2 1 – 24 strand cable
to TC-3 Rm 316
1 – 24 strand cable
to Server Rm 31050 foot
Service
loop
Conduits From TC-1
Cable Home run to IT
Room 144D
Power 110V 20A
(NO Backup)
Panel 2RA-1
DATA/VoIP CAT-6 CABLE COUNT
· WAP – Wireless Access Point 20
· LAN – Tele/Data Outlets 145
· FB – Floor Box Data Outlets 66
· WB – Wall Box Data Outlets 18
· SIM -
TOTAL 249
ConsoleMGMT 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 1 SFP+ 2
RPSSPEEDSTATSYST
MAST STACKMode Console
CATALYST C6800IA – 48FPD10G Uplink Catalyst 6800 Instant Access Series
ConsoleMGMT 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 1 SFP+ 2
RPSSPEEDSTATSYST
MAST STACKMode Console
CATALYST C6800IA – 48FPD10G Uplink Catalyst 6800 Instant Access Series
ConsoleMGMT 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 1 SFP+ 2
RPSSPEEDSTATSYST
MAST STACKMode Console
CATALYST C6800IA – 48FPD10G Uplink Catalyst 6800 Instant Access Series
ConsoleMGMT 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 1 SFP+ 2
RPSSPEEDSTATSYST
MAST STACKMode Console
CATALYST C6800IA – 48FPD10G Uplink Catalyst 6800 Instant Access Series 1 – 2ru, Fiber Patch Panel
6 – 2ru, CAT 6 Patch Panels
6 – 1ru, 48 Port Access Switches
12 – 1ru, Cable Management
(one below each device)
1 – 4ru, 6000VA UPS
ConsoleMGMT 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 1 SFP+ 2
RPSSPEEDSTATSYST
MAST STACKMode Console
CATALYST C6800IA – 48FPD10G Uplink Catalyst 6800 Instant Access Series
ConsoleMGMT 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 1 SFP+ 2
RPSSPEEDSTATSYST
MAST STACKMode Console
CATALYST C6800IA – 48FPD10G Uplink Catalyst 6800 Instant Access Series
6000VA UPS
Smart-UPS
5 0 0 0
Test
I
O
www.apcc.com
Sample portrait rack
elevation drawing to
clarify the location, size,
quantity, placement and
association of the ISP,
Data Equipment, and
Audio/Video equipment.
1 – 24 strand cable
to Server Room
DWG # 4
Rack Elevation TC-03 – Room 316
11/03/2015
CA
DB
1 2 3 4 5 6
1 2 3 4 5 6
1 2 3 4 5 6
1 2 3 4 5 6
Cable Tray
To Server Room 310
Conduits From TC-2
Cable Home run to IT
Room 144D
1 – 24 strand cable
to TC-3
50 foot
Service
loop
Power 110V 20A
(NO Backup)
Panel 3RA-1
Cable Tray
DATA/VoIP CAT-6 CABLE COUNT
· WAP – Wireless Access Point 20
· LAN – Tele/Data Outlets 160
· FB – Floor Box Data Outlets -
· WB – Wall Box Data Outlets 02
· SIM -
TOTAL 182
ConsoleMGMT 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 1 SFP+ 2
RPSSPEEDSTATSYST
MAST STACKMode Console
CATALYST C6800IA – 48FPD10G Uplink Catalyst 6800 Instant Access Series
ConsoleMGMT 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 1 SFP+ 2
RPSSPEEDSTATSYST
MAST STACKMode Console
CATALYST C6800IA – 48FPD10G Uplink Catalyst 6800 Instant Access Series
ConsoleMGMT 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 1 SFP+ 2
RPSSPEEDSTATSYST
MAST STACKMode Console
CATALYST C6800IA – 48FPD10G Uplink Catalyst 6800 Instant Access Series 1 – 2ru, Fiber Patch Panel
4 – 2ru, CAT 6 Patch Panels
4 – 1ru, 48 Port Access Switches
9 – 1ru, Cable Management
(one below each device)
1 – 4ru, 4000VA UPS
4000VA UPS
ConsoleMGMT 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 1 SFP+ 2
RPSSPEEDSTATSYST
MAST STACKMode Console
CATALYST C6800IA – 48FPD10G Uplink Catalyst 6800 Instant Access Series
5125
25%
100%
Sample portrait rack
elevation drawing to
clarify the location, size,
quantity, placement and
association of the ISP,
Data Equipment, and
Audio/Video equipment.
Rack Elevation SERVER Room 310
DWG # 511/03/2015
www.apcc.com
Smart-UPS
5 0 0 0
Test
I
O
www.apcc.com
www.apcc.com
APC
9 6 2 6
PDU
CA
DB
1 2 3 4 5 6
1 2 3 4 5 6
1 2 3 4 5 6
1 2 3 4 5 6
4000VA UPS
Cable Tray
To TC-3 Room 316
1 – Data Center
Access Switches
1 – Blade Server
1 Storage Array
1 – 24 strand cable
to TC-03, Room 3161 – 48 PCH 02U
SC Fiber Patch panel
for 24 SM fiber cable
from Room 316
Conduits From 2nd
Floor Room 202
Health Assessment
37 - Cat-6
Audio and Video
Cables
AUDIO/VIDEO/CAMERA CAT-6 CABLE COUNT
2nd
3rd
· N1A/D - NETWORK OUTLET – FLOOR 10 56
· N5B - NETWORK OUTLET - ABOVE COUNTER 08· N8D - NETWORK OUTLET – STANDARD 16 84· N14 - NETWORK PULL BOX FOR CEILING CAMERA 20 150· N16 - NETWORK OUTLET - ON WIRE TRAY 24· N50A - NETWORK OUTLET - FLAT PANEL DISPLAY 11 21
Floor TOTAL 37 169
Ceiling 20 174
6 U
3 U
25 27 29 31
26 28 30 32
17 19 21 23
18 20 22 24
9 11 13 15
10 12 14 16
1 3 5 7
2 4 6 8
25 27 29 31
26 28 30 32
17 19 21 23
18 20 22 24
9 11 13 15
10 12 14 16
1 3 5 7
2 4 6 8
25 27 29 31
26 28 30 32
17 19 21 23
18 20 22 24
9 11 13 15
10 12 14 16
1 3 5 7
2 4 6 8
25 27 29 31
26 28 30 32
17 19 21 23
18 20 22 24
9 11 13 15
10 12 14 16
1 3 5 7
2 4 6 8
RESERVED
STATUS 9 10 11 12 13 14 15 16
1 2 3 4 5 6 7 8
100-
240V
~
50~60Hz
1.2A
Cable Tray
To All Video/Audio Rooms
169 - Cat-6
Audio and Video Cables
5125
25%
100%
1 – 2ru, Fiber Patch Panel
2 – 1ru, Data Center Access
1 – 2ru, CAT 6 Patch Panels
1 – 6ru, Blade Server
1 – 3ru, Raid Storage
4 – 1ru, Cable Management
(one below each device)
1 – 4ru, 4000VA UPS
Cisco Nexus 3064-T
ID
1 2 3 41 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48
STAT
Cisco Nexus 3064-T
ID
1 2 3 41 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48
STAT
1 – 1ru, Control Processor
2 – 4ru, Encoders
1 – 14ru, Matrix Switch
4 – 1ru, Midspan PoE Injectors
6 – 1ru, Cable Management
(one below each device)
1 – 4ru, 8000VA UPS
5 – 2ru, CAT 6 Patch Panels
Matrix Switch
Patch Panel count does not include
termination of the Ceiling mounted
Cat 6 terminations on 2nd
, 3rd
floor,
and above server cabinets.
(Add three addional panels)
Spare CabinetSpare CabinetSpare Cabinet
Sample portrait rack
elevation drawing to
clarify the location, size,
quantity, placement and
association of the ISP,
Data Equipment, and
Audio/Video equipment.
48" x 96"
fire treated
backboard
DWG # 6
Backboard Elevation
Storage, Time Warner Cable – Room 134
11/03/2015
TWC cable feed
Service
loop
Cable Home run to
Time Warner Cable
Junction Box
TWC Eq
Small
UPS
Power 110V 20A
(Generator Backup)
Panel 1SR-14
Cable Tray To
TC-3 Room 316 &
IT Room 144D
Sample portrait rack
elevation drawing to
clarify the location, size,
quantity, placement and
association of the ISP,
Data Equipment, and
Audio/Video equipment.
48" x 96"
fire treated
backboard
DWG # 7
Backboard Elevation
Storage, at&t – Room 132C
11/03/2015
at&t cable feed
Service
loop
Cable Home run to
at&t Cable
Junction Box
at&t Eq
Small
UPS
Power 110V 20A
(Generator Backup)
Panel 1SR-15
Cable Tray In Adjacent
Storage Room 134
Use J-Hooks as Pathway to Tray
Sample portrait rack
elevation drawing to
clarify the location, size,
quantity, placement and
association of the ISP,
Data Equipment, and
Audio/Video equipment.