70 NTE Electronics, Inc. Voice (973) 748−5089 FAX (973) 748−6224 http://www.nteinc.com Features 8 Programmable Timing Modes (4 on 8−Pin Type) 0.1 sec to 100 min. Programmable Timing Range Universal (24−240VAC/VDC) 10A Output Relay with DPDT Contacts DIP Switch Selection of Timing Mode and Range Knob and Dial Scale for Setting Actual Delay Time DPDT, 2 Form “C” + 7 6 2 3 4 8 9 10 11 5 1 INPUT* External Control Switch ** DPDT, 2 Form “C” * Note input polarity for DC operation. For most reliable operation on AC, connect high side to “+” and low side to “−”. ** IMPORTANT: A dry circuit switch is recommended. A “dry circuit” switch is one rated to reliably switch currents of less than 50mA. Use of a switch rated for other than dry circuit may result in failure of the time delay relay to function properly. (11−Pin Type) (8−Pin Type) 4 3 5 7 1 2 8 6 + INPUT* AC or DC OPERATED NTE Type No. No. of Pins Timing Adj Range Contact Arr. Nom Vltg AC/DC Nom Power Max. Contact Cur. @ 30VDC 277VAC Diag No. R64−11AD10−4 8 0.1 Sec. to 100 Min. DPDT 24 to 240 1W@24V 5W@120V 10W@240V 10A D58 R64−11AD10−8 11 0.1 Sec. to 100 Min. DPDT 24 to 240 1W@24V 5W@120V 10W@240V 10A D58 Note: R64−11AD10−X where “X” indicates the number of timing functions. ACCESSORIES MOUNTING STYLES DESCRIPTION NTE TYPE NO. SURFACE MOUNT 8−PIN OCTAL 11−PIN OCTAL R95−101 R95−104 PANEL MOUNT 8−PIN OCTAL 11−PIN OCTAL R95−118 R95−119 DIN RAIL MOUNT 8−PIN OCTAL 8−PIN OCTAL 11−PIN OCTAL 11−PIN OCTAL R95−113 R95−181 R95−114 R95−182 R64 Series Programmable, DPDT, 10 Amp, AC or DC, Multifunctional Time Delay Relay. D58 2.830 (71.9) .320 (8.1) 3.150 (80.0) 1.880 (47.8) 1.880 (47.8) .650 (16.5) .640 (16.3) Electrical Specifications Contact Rating: 10 Amps @ 30VDC or 277VAC, resistive; 1/2 HP @ 250VAC; 1/3 HP @ 120VAC Life: 100,000 operations at minimum rated load Mechanical Life: 10,000,000 operations Input Nominal Input Voltage: 24 − 240V ±15%, 50/60Hz AC or DC Nominal Power: See Chart Timing Timing Ranges: 0.1 to 1.0 / 1.0 to 10 / 10 to 100 sec.; 0.1 to 1.0 / 1.0 to 10 / 10 to 100 min. Timing Adjustments: Knob adjustable within selected range Tolerance: −0, +20% of max. specified at high end timing range; min. specified, or less, at low end Delta Time (for AC units add ±1 cycle 60Hz): ± 10% Repeatability (for AC units add ±1 cycle 60Hz): ± 2% − including first cycle of operation Reset Time (power interruption): 45mS, typ; 60 mS, max Minimum Pulse Width, Control: 50mS Recycle Time: 45mS, typ; 60mS, max Protection Transient: yes Dielectric Strength Between Open Contacts: 1000V rms , 60Hz Between All Other Conductors: 1500V rms , 60Hz Environmental Characteristics Operating: −10°C to +55°C Storage: −20°C to +70°C Humidity: 85% relative humidity, non−condensing Weight Std: 4.3 oz (122 grams) approx.

R64 Series Relay | NTE Electronics, Inc. · 8−Pin Type: Output relay will begin cycling at a 50% duty cycle with the application of input power. The initial state of the relay will

  • Upload
    others

  • View
    5

  • Download
    0

Embed Size (px)

Citation preview

Page 1: R64 Series Relay | NTE Electronics, Inc. · 8−Pin Type: Output relay will begin cycling at a 50% duty cycle with the application of input power. The initial state of the relay will

70 NTE Electronics, Inc. Voice (973) 748−5089 FAX (973) 748−6224 http://www.nteinc.com

Features• 8 Programmable Timing Modes (4 on 8−Pin Type)• 0.1 sec to 100 min. Programmable Timing Range• Universal (24−240VAC/VDC)• 10A Output Relay with DPDT Contacts• DIP Switch Selection of Timing Mode and Range• Knob and Dial Scale for Setting Actual Delay Time

DPDT, 2 Form “C”

+ −

76

2

3

4 8

9

1011

5

1

INPUT*

ExternalControlSwitch **

DPDT, 2 Form “C”

* Note input polarity for DC operation. For most reliable operation on AC,connect high side to “+” and low side to “−”.

** IMPORTANT: A dry circuit switch is recommended. A “dry circuit” switchis one rated to reliably switch currents of less than 50mA. Use of a switchrated for other than dry circuit may result in failure of the time delay relayto function properly.

(11−Pin Type)(8−Pin Type)

4

3

5

7

1

2

8

6

+ −INPUT*

AC or DC OPERATED

NTE Type No.

No.of

Pins

TimingAdj

RangeContact

Arr.

NomVltg

AC/DCNom

Power

Max.ContactCur. @30VDC277VAC

DiagNo.

R64−11AD10−4 8 0.1 Sec.to

100 Min.

DPDT 24to

240

1W@24V5W@120V10W@240V

10A D58

R64−11AD10−8 11 0.1 Sec.to

100 Min.

DPDT 24to

240

1W@24V5W@120V10W@240V

10A D58

Note: R64−11AD10−X where “X” indicates the number of timingfunctions.

ACCESSORIES

MOUNTINGSTYLES DESCRIPTION

NTETYPE NO.

SURFACE MOUNT 8−PIN OCTAL11−PIN OCTAL

R95−101R95−104

PANEL MOUNT 8−PIN OCTAL11−PIN OCTAL

R95−118R95−119

DIN RAIL MOUNT 8−PIN OCTAL8−PIN OCTAL11−PIN OCTAL11−PIN OCTAL

R95−113R95−181R95−114R95−182

R64 Series

Programmable, DPDT, 10 Amp, AC orDC, Multifunctional Time Delay Relay.

D58

2.830(71.9)

.320(8.1)

3.150(80.0)

1.880(47.8)

1.880 (47.8)

.650(16.5)

.640(16.3)

Electrical SpecificationsContactRating: 10 Amps @ 30VDC or 277VAC, resistive;1/2 HP @ 250VAC; 1/3 HP @ 120VACLife: 100,000 operations at minimum rated loadMechanical Life: 10,000,000 operations

InputNominal Input Voltage: 24 − 240V ±15%, 50/60Hz AC or DCNominal Power: See Chart

TimingTiming Ranges: 0.1 to 1.0 / 1.0 to 10 / 10 to 100 sec.;

0.1 to 1.0 / 1.0 to 10 / 10 to 100 min.Timing Adjustments: Knob adjustable within selected rangeTolerance: −0, +20% of max. specified at high end timing range;

min. specified, or less, at low endDelta Time (for AC units add ±1 cycle 60Hz): ± 10%Repeatability (for AC units add ±1 cycle 60Hz): ± 2% − includingfirst cycle of operationReset Time (power interruption): 45mS, typ; 60 mS, maxMinimum Pulse Width, Control: 50mSRecycle Time: 45mS, typ; 60mS, max

ProtectionTransient: yesDielectric Strength

Between Open Contacts: 1000Vrms, 60HzBetween All Other Conductors: 1500Vrms, 60Hz

Environmental CharacteristicsOperating: −10°C to +55°CStorage: −20°C to +70°CHumidity: 85% relative humidity, non−condensing

WeightStd: 4.3 oz (122 grams) approx.

Page 2: R64 Series Relay | NTE Electronics, Inc. · 8−Pin Type: Output relay will begin cycling at a 50% duty cycle with the application of input power. The initial state of the relay will

71NTE Electronics, Inc. Voice (973) 748−5089 FAX (973) 748−6224 http://www.nteinc.com

R64 Series (Continued)DIP Switch Layout

On

1 2 3 4 5 6 7

Function Setting Time Setting

Timing Function Switch Settings Timing Range Switch Settings

DIP SwitchSetting Function

DIP SwitchSetting Function

Delay On Operate Delay On Release

Interval On(Input Controller)

Inverted DelayOn Release

Recycler(Initially Off)

Interval On(Switch Controlled)

Recycler(Initially On) Interval Off

DIP SwitchSetting Timing Range

DIP SwitchSetting Timing Range

0.1 − 1.0 Seconds 0.1 − 1.0 Minutes

1.0 − 10 Seconds 1.0 − 10 Minutes

10 − 100 Seconds 10 − 100 Minutes

Note: The solid blocks in the DIP switch diagrams indicate the switch positions.For example, all the switches are “off” in the diagram above.

Timing Function DescriptionsDelay On Operate8−Pin Type: Output relay is energized at the completion of the timeinterval which is initiated by the application of input voltage.11−Pin Type: Same as above except, closing the control switch aftertime out will de−energize the relay and reset the timer. Opening theswitch will initiate another time interval. Closing the control switchduring timing will reset the time to zero and inhibit timing until openedagain.

Interval On (Input Controlled)8−Pin Type: Output relay is energized by the application of inputvoltage. The time interval is initiated at the sme time with the relayde−energize at the completion of the time interval.11−Pin Type: Same as above. Closing the control switch will have noeffect on timing or the state of the relay.

Recycler (Initially Off)8−Pin Type: Output relay will begin cycling at a 50% duty cycle withthe application of input power. The initial state of the relay will bede−energized.11−Pin Type: Same as above except, closing the control switch willde−energize the relay and inhibit timing until it is once again opened,at whice time it will start from zero time.

Recycler (Initially On)8−Pin Type: Output relay will begin cycling at a 50% duty cycle withthe application of input power. The initial state of the relay will beenergized.11−Pin Type: Same as above except, closing the control switch willenergize the relay and inhibit timing until it is once again opened, atwhich time it will start from zero time.

Delay On Release11−Pin Only: Output relay is energized by the closing of the controlswitch with the input applied or the application of input voltage with thecontrol switch already closed. The time interval will be initiated by theopening of the control switch with the relay de−energized at thecompletion of the time interval. Closing the control switch after time outwill energize the relay in preparation for another time interval. Closingthe switch during timing will reset the time to zero and inhibit timing untilopened again.

Inverted Delay On Release8−Pin Type: No Time Delay − Instantly On11−Pin Type: Output relay will energize with the application of the inputvoltage when the control switch is open. Control switch closing willde−energize the relay. A timing interval will be initiated with the openingof the control switch, at the completion of which the relay will energize.With the control switch closed upon application of input voltage, therelay will wait until the control switch is opened to initiate a time intervalafter which the relay will energize. Closing of the control switch duringtiming will reset the time to zero and inhibit timing until opened again.

Interval On (Switch Controlled)11−Pin Only: Output relay is energized by the application of inputvoltage with the control switch closed or the closing of the control switchwith the input applied. Immediately upon either, timing is initiated withthe relay de−energized at the completion of the time interval. Closingthe control switch after time out will reset the timer, energize the relay,and initiate another time interval. Closing the control switch duringtiming will have no effect on timing or the state of the relay.

Interval Off11−Pin Only: Output relay will initially be energized with the applicationof the input voltage when the control switch is open. Control switchclosing will de−energize the relay and start a time interval. At thecompletion of the time interval, the relay will energize. With the controlswitch closed upon application of input voltage, a time interval will beinitiated after which the relay will energize. Closing of the contol switchduring timing will have no effect on timing or the state of the relay.