DDC Controller Quick Start Guide

Quick Start Guide-01C · 1 Section 1: Goodman DDC Controller Quick Start Guide (Using Computer) Note: This Quick Start Guide is only for reference to make the startup process faster

  • Upload
    others

  • View
    7

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Quick Start Guide-01C · 1 Section 1: Goodman DDC Controller Quick Start Guide (Using Computer) Note: This Quick Start Guide is only for reference to make the startup process faster

DDC Controller Quick Start

Guide

Page 2: Quick Start Guide-01C · 1 Section 1: Goodman DDC Controller Quick Start Guide (Using Computer) Note: This Quick Start Guide is only for reference to make the startup process faster

WattMaster Controls Inc.8500 NW River Park Drive · Parkville, MO 64152DAIKIN® is a registered trademark of Daikin Industries, LTD

WattMaster Form: DK-QS-DDC-TGD-01AAll rights reserved. © June 2016 WattMaster Controls, Inc. Neither WattMaster Controls, Inc. nor Daikin Industries, Ltd. assumes any responsibility for errors or omissions in this document and are separate companies. This document is subject to change without notice.

Table of Contents

Section 1: DDC Controller Quick Start Guide (Using Computer) .................................................1

Part 1: Initial Computer and PrismD Setup ..............................................................................1 Part 2: Controller Con iguration ....................................................................................................5Part 3: Schedules ..................................................................................................................................8

.

Section 2: DDC Controller Quick Start Guide (Using LCD Display) ......................................... 10

Part 1: Controller Setup Using On-Board LCD Display ..................................................... 10

Appendix: Optional Sensor Descriptions ........................................................................................... 14

Troubleshooting ............................................................................................................................................. 15

Page 3: Quick Start Guide-01C · 1 Section 1: Goodman DDC Controller Quick Start Guide (Using Computer) Note: This Quick Start Guide is only for reference to make the startup process faster

Section1:GoodmanDDCControllerQuickStartGuide(UsingComputer)

Note:This Quick Start Guide is only for reference to make the startup process faster.  If more information is required on any of 

the features or wiring, please refer to the DDC Controller Technical Guide and the PrismD Technical Guide. 

 

Part1:InitialComputerandPrismDSetup

1. Install PrismD software and the USB drivers on your computer.  PrismD and the USB drivers can be downloaded 

at www.daikin.wattmaster.com.  You can also find installation instructions there for both of these items. 

 

2. After PrismD and the USB drivers have been successfully installed on your computer, you can then connect a 

standard USB cable between the computer and controller.  See Figure 1. 

 

  

Figure 1:  USB Cable Connection  

 

 

 

 

   

USB Cable

Connect to Computer with PrismD Software Installed For Stand-Alone Programming

DDC Controller

Page 4: Quick Start Guide-01C · 1 Section 1: Goodman DDC Controller Quick Start Guide (Using Computer) Note: This Quick Start Guide is only for reference to make the startup process faster

3. Verify that the CommLink jumpers are installed on the DDC Controller as shown in Figure 2.  Note: If you are 

using an external CommLink 5, remove the jumpers. Cycle power to the controller if making jumper changes. 

 

  

Figure 2:  On‐Board CommLink Jumper Setting 

 

4. Open the Prism2 program.  If you did not create a shortcut to your desktop described in the on‐line PrismD 

instructions or place the program on the Start menu, you can find the program at c:\PrismD\PrismD.exe. 

 

5. Once PrismD is open, click the  <Login> icon and use the following default user name and Password  

(see Figure 3):  User Name:  admin;  Password:  admin 

  

Figure 3:  Login Icon and Login Window 

DDC Controller

USE ON-BOARDCOMMLINK

Both Jumpers ON (Default)

RSLOO"R""T""SH

AN

BI5

BI7

BI1

BI2

BI3

BI4

BI8

BI6

AI1

AI2AI3

AI4

AI5

AI6

AI7

AI8

BINAR

O

24

POLA

BE

C

Wa#S

ENTER

UP

DOWN

ALARM

MENU

RELAY CONTACTRATING IS 1 AMP

MAX @ 24 VAC

RS-485 COMM

LOOP WIRE

“R” TO “R”,“T” TO “T”“SHLD” TO “SHLD”

24 VAC POWERONLY

WARNING!

POLARITY MUST

BE OBSERVED

OR THE

CONTROLLER

WILL BE

DAMAGED

ANALOG INPUTS

AI1:

A 2:I

A 3:I

A 6:I

A 7:I

A 8:I

BI1:

BI2:

BI3:

BI4:

BI5:

BI6:

BI7:

AO1

AO2

AO3

SPACE TEMP

CO2 SENSOR

OUTDOOR AIR TEMP

ECONOMIZER FEEDBACK

OUTDOOR AIR HUMIDITY

SPACE HUMIDITY

REMOTE START/STOP

FAN PROVING SWITCH

CLOGGED FILTER SWITCH

EMERGENCY SHUTDOWN

COMP PRESSURE SW 1

DEFROST SWITCH (ES)

LOAD SHEDDING

ECONOMIZER DAMPER:

MOD HGRH:

EXHAUST FAN (SSR):

A 4:I

A 5:I

BI8:

BINARY INPUTS (24V)

G OUTPUTSANALO

WattMaster Label#S 000067W

Rev.: 1G

E-BUSEXPANSION

E-BUSEXPANSION

+24 VAC

GND

HEAT STG2: RLY6

REV. VALVE(S): RLY8

www.wattmaster.com

COMP2/STG2: RLY2

OE377-26B-00001 PCBCG100

24V RLY2: COM2

BLOWER STG2: RLY4

COND FAN: RLY7

24V RLY: COM3-8

USB

AO4ALARM (SSR):

M

BINARY OUTPUTS

24V 3-8RLY: COM

HEAT STG1: RLY5

BLOWER STG1: RLY3

24V RLY1: COM1

COMP1/STG1: RLY1

SPACE SLIDE ADJUST

SUPPLY AIR TEMP

COMP PRESSURE SW 2

Page 5: Quick Start Guide-01C · 1 Section 1: Goodman DDC Controller Quick Start Guide (Using Computer) Note: This Quick Start Guide is only for reference to make the startup process faster

6. Click the <Jobsite> icon (see Figure 4). Once the Job Sites Window opens, create a name for your jobsite in the 

“Selected Location” field and press <Enter>. Your new jobsite name should appear in the “Job Site Selection” 

window.  Note: When entering data in PrismD, you must always press the <Enter> key after each entry in order 

for the program to save the data. 

 

7. Click the “Down Arrow” next to the Serial Port drop down list and choose the listing as shown in Figure 4.  Note:  

The number following “COM” may be different on your computer. It should still start with “Silicon Labs CP210x 

USB to UART Bridge”.  See the Troubleshooting Section at the end of this guide if you do not see this selection. 

  

Figure 4:  Job‐Site Icon and Job Sites Window 

8. In the Network Configuration Window, click Multiple Loop Configuration if using one or more MiniLinks. 

Otherwise, select Single Loop Configuration.  Once selected, click <Exit> to close the Job Sites Window. 

 

   

Page 6: Quick Start Guide-01C · 1 Section 1: Goodman DDC Controller Quick Start Guide (Using Computer) Note: This Quick Start Guide is only for reference to make the startup process faster

 

9. Click on the <Communications> menu item and then choose “Search for Units”.  See Figure 5. 

  

Figure 5:  Communications Menu ‐ Search For Units 

 

10. In the Search For Units Window that opens, click the menu option <Start Search>.  When completed you should 

see one small green square as shown in Figure 6. 

  

Figure 6:  Search For Units 

 

11. Close the Search For Units Window by clicking <Exit>. If you wish to save your search results, select <Yes> when 

prompted to do so. 

 

Page 7: Quick Start Guide-01C · 1 Section 1: Goodman DDC Controller Quick Start Guide (Using Computer) Note: This Quick Start Guide is only for reference to make the startup process faster

Part2:ControllerConfiguration

1. On the left‐hand side of the PrismD screen in the Unit Selection column, double‐click on the controller labeled 

“Daikin RTU”.   See Figure 7. 

 

Figure 7:  Unit Selection 

2. The Status Screen for the controller will display as shown in Figure 8. 

  

Figure 8:  Controller Status Screen 

 

Daikin RTU

Daikin RTU 

Page 8: Quick Start Guide-01C · 1 Section 1: Goodman DDC Controller Quick Start Guide (Using Computer) Note: This Quick Start Guide is only for reference to make the startup process faster

3. At the top of the Status Screen next to Daikin RTU, you will see a blank time of 00.00 AM. Click on this time field 

to broadcast the real time to the Controller.  See Figure 9. 

 

                       

Figure 9:  Broadcast Time 

 

4. From here, you can view the current status of the unit as well as access the settings by clicking the menu option 

<Setpoints> located at the top of the window. See Figure 10. 

 

 

Figure 10:  Setpoints Selection 

   

Daikin RTU

Daikin RTU

Page 9: Quick Start Guide-01C · 1 Section 1: Goodman DDC Controller Quick Start Guide (Using Computer) Note: This Quick Start Guide is only for reference to make the startup process faster

5. As shown below in Figure 11, you can select the setpoint category by clicking on one of the buttons at the 

bottom of the screen.  When initially setting up a controller, it is important to verify the configurations first.  

Click on the <Configuration> category. Note: When entering data in PrismD, you must always press the <Enter> 

key after each entry in order for the program to save the data. 

  

Figure 11:  Controller Setpoints Screen and Setpoint Categories 

 

6. In the Configuration Screen, there are 5 Sensor settings identified by the red arrows that are field options and 

they need to be set correctly in order for the controller to operate.  These options are shown with arrows in 

Figure 12.  However, you should still verify the other settings even though they should be set correctly at the 

factory. 

  

Figure 12:  Configuration Screen 

Page 10: Quick Start Guide-01C · 1 Section 1: Goodman DDC Controller Quick Start Guide (Using Computer) Note: This Quick Start Guide is only for reference to make the startup process faster

Part3:Schedules

1. The internal schedule can be changed by clicking on the <Schedules> icon located on the Controller Status 

Screen as shown in Figure 13. 

  

Figure 13:  Schedules Icon 

 

2. Once the Schedules Screen opens, modify the schedule as necessary.  See Figure 14.    

  

Figure 14:  Schedules Window 

3. When you enter a time in any field, you must type in 3 or 4 characters for each field and you must designate AM or PM and press <Enter>. For example, 500 PM, <Enter> or 1100 PM, <Enter>.  Note: You MUST press <Enter> to have the system accept your entry. If you do not press <Enter>, the bar graph to the right will either not display or will not change.  

Page 11: Quick Start Guide-01C · 1 Section 1: Goodman DDC Controller Quick Start Guide (Using Computer) Note: This Quick Start Guide is only for reference to make the startup process faster

4. To eliminate a schedule from any event, simply type a zero and press <Enter> for the Start and Stop time for that day. The screen will display 12:00 AM for both the Start and Stop times, indicating that the equipment will not activate for that day.  

5. If you want the controller to run the full 24 hours, type a zero and press  <Enter> to set 12:00 AM for the Start time and type 11:59 PM and press <Enter> for the Stop time. This ensures the full 24‐hour period will remain in the occupied mode without interruption.  

6. Select < Save> to save your schedule. Select < Restore> to restore a previously saved schedule. Select < Copy to All> to copy the schedule to all like controllers, and select < Erase Schedules> to completely erase the schedule appearing in the window.  WARNING: <Erase Schedules> will clear ALL entered. 

7. Select the <Holidays> button at the bottom left of the Schedules Window to schedule Holidays. The Holidays Window will appear (see Figure 15). Click on each date you wish to select as a Holiday. All Holidays will follow the daily Holiday schedule that is set in the Schedules Window.  The holiday start and stop times will override the standard operating hours. Note: You can only select holidays for the current year.

 

Figure 15:  Holidays Window

 

Page 12: Quick Start Guide-01C · 1 Section 1: Goodman DDC Controller Quick Start Guide (Using Computer) Note: This Quick Start Guide is only for reference to make the startup process faster

10 

Section2:GoodmanDDCControllerQuickStartGuide(UsingLCDDisplay)

Note:This Quick Start Guide is only for reference to make the startup process faster.  If more information is required on any of 

the features or wiring, please refer to the DDC Controller Technical Guide and the PrismD Technical Guide.   

 

Part1:ControllerSetupUsingOn‐BoardLCDDisplay

1. The  first  LCD  screen  is  the  initialization  screen. To  scroll  through  the  rest of  the  screens, press  the <MENU> 

button. Press the <MENU> button until you get to the TIMER / DELAYS Screen. Then press the <ENTER> button 

to scroll through the TIMER / DELAYS Screens. Follow the directions  in Step 1. Then press the <MENU> button 

until you get to the CONFIG SETPTS Screen. Then press the <ENTER> button to scroll through the Configuration 

Setpoints Screens. Follow the directions in Step 3. 

 

 

 

 

Page 13: Quick Start Guide-01C · 1 Section 1: Goodman DDC Controller Quick Start Guide (Using Computer) Note: This Quick Start Guide is only for reference to make the startup process faster

11 

2. There are 5 Timer settings that are field options and they need to be set correctly in order for the controller to 

operate properly.  They are shown below: 

 

                                                     

                                                        

Page 14: Quick Start Guide-01C · 1 Section 1: Goodman DDC Controller Quick Start Guide (Using Computer) Note: This Quick Start Guide is only for reference to make the startup process faster

12 

3. There are 7 Configuration settings that are field options and they need to be set correctly in order for the 

controller to operate properly.  However, you should still verify the accuracy of all other configuration settings 

even though they should be set correctly at the factory.  

 

4. The Configuration Settings that need to be set correctly are as follows:  

a.  Space Sensor Installed:  Analog or Digital 

b.  Humidity Space Sensor Installed or Not Installed 

c.  Humidity Space Sensor Installed:  Analog or Digital 

d.  Economizer: Economizer Only, CO2or None 

e.  Economizer Enable Source: Drybulb, Dewpoint, or Enthalpy 

f.  CO2 Sensor Installed or Not Installed 

g.  CO2 Sensor Installed:  Analog or Digital 

 

Use the <UP> and <DOWN> buttons to change screen values.  

 

                                    

 

 

 

Page 15: Quick Start Guide-01C · 1 Section 1: Goodman DDC Controller Quick Start Guide (Using Computer) Note: This Quick Start Guide is only for reference to make the startup process faster

13 

  

                                                                      

 

Page 16: Quick Start Guide-01C · 1 Section 1: Goodman DDC Controller Quick Start Guide (Using Computer) Note: This Quick Start Guide is only for reference to make the startup process faster

14 

Appendix:OptionalSensorDescriptionsIf the optional sensors are purchased from Daikin, the following pictures will help you determine the type of sensor that 

you have.   However, some of the optional sensor types are not provided by Daikin, such as the Analog Space Humidity 

Sensor (not shown).  

 

 

 

 

 

 

        

 

               

 

 

 

 

 

 

 

   

 

Analog Space Sensor 

OVR

RELO

C

REMR

O

AW

 

Digital Space Sensor 

with LCD Display 

 

Analog CO2 Sensor 

 

Digital CO2 Sensor 

 

Digital Space Sensor 

without LCD Display 

Page 17: Quick Start Guide-01C · 1 Section 1: Goodman DDC Controller Quick Start Guide (Using Computer) Note: This Quick Start Guide is only for reference to make the startup process faster

15 

Troubleshooting

What Can I Do If I Cannot Find Silicon Labs Under Serial Ports In PrismD? 

 

1. As shown in the Figure above, the serial port “Silicon Labs CP210x USB” should be an option under <Serial Port>. 

If this option is not shown, you will need to check your computer’s internal ports for the correct COM number.  

 

2. Go to the <Control Panel> in your computer and click on <Device Manager>.  This will open your computer’s 

Device Manager Window.  Find and click on <Ports (COM & LPT)>. 

 

3. Under Ports (COM & LPT), look for Silicon Labs and verify the COM number it is installed on. With this 

information, go back to PrismD and under JobSite, select the correct Serial Port. In this example, COM3. 

Page 18: Quick Start Guide-01C · 1 Section 1: Goodman DDC Controller Quick Start Guide (Using Computer) Note: This Quick Start Guide is only for reference to make the startup process faster

16 

Troubleshooting

What If I Forget My Password? 

If you have changed the administrator access username and password from its default username “admin” and password 

“admin” and you forgot one or both, you may reset the administrator access to factory default mode by following the 

steps below. 

1.  Under the C: drive, find and open your PrismD folder. In this folder you will find an internal folder named, 

“Configuration.”  Double‐click to open the folder.   

 

2. Inside this folder you will find multiple files. Look for a file named “ULData.cfg.”  Right click on this file and select 

<Delete>. 

 

 

3. This will reset the Username and Password to “admin”  