2
FRENIC - Ace Quick Reference Guide Orange = Outputs, Yellow = Analog Inputs, Blue = Digital Inputs Control Card Terminals FRENIC - Ace Control Wiring *1 Install a recommended molded case circuit breaker (MCCB) or residual-current-operated protective device (RCD)/earth leakage circuit breaker (ELCB) (with overcurrent protection function) in the primary circuit of the inverter to protect wiring. Ensure that the circuit breaker capacity is equivalent to or lower than the recommended capacity. *2 Install a magnetic contactor (MC) for each inverter to separate the inverter from the power supply, apart from the MCCB or RCD/ELCB, when necessary. Connect a surge absorber in parallel when installing a coil such as the MC or solenoid near the inverter. *3 The R0 and T0 terminals are provided for inverters of type 0059 or above(460V class) and type 0088 or above(230V class). To retain an alarm output signal ALM issued on inverter's programmable output terminals by the protective function or to keep the keypad alive even if the main power has shut down, connect these terminals to the power supply lines. Even if without connecting the power supply to these terminals, the inverter can run as long as connecting the power supply to the terminals L1/R, L2/S, L3/T. *4 Normally no need to be connected. Use these terminals when the inverter is equipped with a high power-factor, regenerative PWM converter (RHC series). (Type 0203 or above/460V only) *5 When connecting an optional DC reactor (DCR), remove the jumper bar from the terminals P1 and P(+). For types 0139 (ND spec.), 0168 (HD/ND spec.) and 0203 or bigger capacity types, it is required to connect the DCR (460V only). Use a DCR when the capacity of the power supply transformer exceeds 500 kVA and is 10 times or more the inverter rated capacity, or when there are thyristor-driven loads in the same power supply line. *6 Inverters of type 0072 or below(460V class) and type 0115 or below(230V class) have a built-in braking chopper between the terminals P(+) and DB. *7 For inverters of type 0085 or above (460V class), need to use a braking unit to connect the braking resistor in order to upgrade the braking capability of inverters. Be sure to connect the braking unit (option) to terminals P(+) and N(-). Auxiliary terminals [1] and [2] have polarity. Be sure to connect as this figure. *8 A grounding terminal for a motor. Use this terminal if needed. *9 For control signal wires, use twisted or shielded-twisted wires. When using shielded-twisted wires, connect the shield of them to the common terminals of the control circuit. To prevent malfunction due to noise, keep the control circuit wiring away from the main circuit wiring as far as possible (recommended: 10 cm(3.9 inches) or more). Never install them in the same wire duct. When crossing the control circuit wiring with the main circuit wiring, set them at right angles. *10 The connection diagram shows factory default functions assigned to digital input terminals [X1] to [X5], [FWD] and [REV], transistor output terminals [Y1] and [Y2], and monitor contact output terminals [FM] . *11 The power switching connectors (CN UX) and the fan power supply switching connectors (CN R and CN W) are for type 0203(460 V class) or above. *12 Slide switches on the control printed circuit board (control PCB). Use these switches to customize the inverter operations. *13 Use auxiliary contacts of the thermal relay (manually restorable) to trip the molded case circuit breaker (MCCB) or magnetic contactor (MC). *14 When using the Enable input function, be sure to remove the jumper wire from terminals [EN1],[EN2] and [PLC]. *15 and are separated and insulated FRENIC-Ace (E2) Keypad SD DX- DX+ CMY Y1 Y2 CM X1 X2 X3 X4 X5 PLC 30A 30B 30C CM FWD REV PLC EN1 EN2 C1 11 FM1 FM2 11 11 12 13 • FWD, Rev, plus 5 Digital inputs. Configurable for Source or Sink. • 0-10VDC analog input. • 4-20mA, 0-20mA or 0-10VDC analog input. • 2 Transistor outputs. • Form C contact relay o (250VAC 0.3A, cosØ=0.3), (48VDC, .5A). • 1 0-10VDC, 4-20mA, 0-20mA or 25-32kp/s analog output. • 1 0-10VDC, 4-20mA or 0-20mA analog output. • 24VDC max 100mA DC output power. • 10VDC output power for potentiometer. • 2 Source only, safe torque off Enable Inputs. • RS-485 wire terminals. Min. Max. On level 0V 2V Olevel 22V 27V On level 22V 27V Olevel 0V 2V Operang Voltage (Sink) Operang Voltage (Sink) Item Max. On level 2v Olevel 22V Maximum Current at on 50mA Item Operang Voltage (Sink) A. LED Display B. Remote/Local Indicator C. Monitoring Display Indicator D. Program Reset Key E. Function Data Key F. Shift Key G. Menu Navigation Keys H. Local Mode Control Operators DBR Option DCR Option DB N(-) P(+) P1 U V W U V W M C L1/R L2/S L3/T MC MCCB or RCD /ELCB G Grounding terminal * 1 * 2 * 5 ( * 6 ) DB 2 1 (CM) (THR) (G) N(-) P(+) DB 2 1 (CM) (G) 2 1 (THR) (+) N(-) DBR Option Brake nit ( Option (G) (+) R DB * 7 TH1 THC PTC [11] [C1] Thermal ) R1 T1 R0 T0 * 3 Auxiliary control power supply Auxiliary fan power supply * 4 * 11 DC/DC (PLC) (FWD) (REV) (X1) (X2) (X3) (X4) (X5) (CM) (EN1) SINK SOURCE (EN2) 0V +24VDC Run forward command Run reverse command Select multi-frequency (0 to 1 step) Select multi-frequency (0 to 3 step) Select multi-frequency (0 to 7 step) Coast to a stop <Y1> <Y2> <CMY> Inverter running Motor overload early warning [FM] [11] 0V G E Output frequency 1 SW1 * 12 * 8 * 9 Digital input Common terminal for digital i nputs Contact outputs Transistor outputs * 10 * 10 Common terminal for analog output Analog/Pulse train output Common terminal for transistor outputs ( SINK/SOURCE) Safety switch SW5 (* 12 ) 30C 30B 30A Alarm output ( for any alarm) 30 Current output ( 4(0) 20mADC) Voltage output ( 0 +10VDC) Pulse train output ( 25 32kp/s) Power switching connector CN UX Fan power supply switching connector CN R / CN W * 10 * 9 * 14 (PLC) Charging indicator RJ45 connector SW2 *12 Connector for option card FMI FMV FMP FU FV FW FM * 13 Transformer Motor In case of the motor with built-in cooling fan Thermal Communication port 1 ( RS-485) Keypad(standard) Detachable terminal block Voltage input V2 ( 0 +10VDC) 11 12 13 * 9 +10VDC Current input C1 ( 4(0) 20mADC) Current/voltage input for setting + 4(0) to 20mADC / 0 to +10VDC Voltage input for setting 0 to + 10VDC (0 to ±10VDC) 0V Analog input 3 2 1 PTC input C 1 * 9 (+) (-) Voltage input 12 ( 0 +10VDC) ( 0 ±10VDC) SW4 PTC AI * 12 * 12 SW3 C1 V2 0V 0V 0V Enable input DBR: Dynamic Braking Resistor DCR : DC reactor RCD : Residual-current-operated protective device ELCB : Earth leakage circuit breaker MC : Magnetic contactor MCCB : Molded case circuit breaker Grounding terminal Potentiometer power supply Common terminal for analog inputs Communication port 2 ( RS - 485 ) [FM2] SW7 (* 12 ) FMI FMV Output current (DX+) (DX-) SW6 * 12 (SD) * 9 Current output ( 4(0) 20mADC) Voltage output ( 0 +10VDC) * 10 [11] 0V Common terminal for analog output * 15 * 15 * 15 * 15 * 15 U1 U2 CN UX FAN NC CN R CN W Power supply 400V series 380 to 480V 50/60Hz 200V series 200 to 240V 50/60Hz * 13

Quick Reference Guide - Instrumart · Quick Reference Guide Orange = Outputs, ... (MCCB) or residual-current-operated protective device ... Fuji Electric Corp. of America

  • Upload
    lycong

  • View
    242

  • Download
    0

Embed Size (px)

Citation preview

FRENIC - AceQuick Reference Guide

Orange = Outputs, Yellow = Analog Inputs, Blue = Digital Inputs

Control Card TerminalsFRENIC - Ace Control Wiring

*1 Install a recommended molded case circuit breaker (MCCB) or residual-current-operated protective device (RCD)/earth leakage circuit breaker (ELCB) (with overcurrent protection function) in the primary circuit of the inverter to protect wiring. Ensure that the circuit breaker capacity is equivalent to or lower than the recommended capacity.*2 Install a magnetic contactor (MC) for each inverter to separate the inverter from the power supply, apart from the MCCB or RCD/ELCB, when necessary. Connect a surge absorber in parallel when installing a coil such as the MC or solenoid near the inverter.*3 The R0 and T0 terminals are provided for inverters of type 0059 or above(460V class) and type 0088 or above(230V class).To retain an alarm output signal ALM issued on inverter's programmable output terminals by the protective function or to keep the keypad alive even if the main power has shut down, connect these terminals to the power supply lines. Even if without connecting the power supply to these terminals, the inverter can run as long as connecting the power supply to the terminals L1/R, L2/S, L3/T.*4 Normally no need to be connected. Use these terminals when the inverter is equipped with a high power-factor, regenerative PWM converter (RHC series). (Type 0203 or above/460V only)*5 When connecting an optional DC reactor (DCR), remove the jumper bar from the terminals P1 and P(+).For types 0139 (ND spec.), 0168 (HD/ND spec.) and 0203 or bigger capacity types, it is required to connect the DCR (460V only). Use a DCR when the capacity of the power supply transformer exceeds 500 kVA and is 10 times or more the inverter rated capacity, or when there are thyristor-driven loads in the same power supply line.*6 Inverters of type 0072 or below(460V class) and type 0115 or below(230V class) have a built-in braking chopper between the terminals P(+) and DB. *7 For inverters of type 0085 or above (460V class), need to use a braking unit to connect the braking resistor in order to upgrade the braking capability of inverters. Be sure to connect the braking unit (option) to terminals P(+) and N(-). Auxiliary terminals [1] and [2] have polarity. Be sure to connect as this figure.*8 A grounding terminal for a motor. Use this terminal if needed.*9 For control signal wires, use twisted or shielded-twisted wires. When using shielded-twisted wires, connect the shield of them to the common terminals of the control circuit. To prevent malfunction due to noise, keep the control circuit wiring away from the main circuit wiring as far as possible (recommended: 10 cm(3.9 inches) or more). Never install them in the same wire duct. When crossing the control circuit wiring with the main circuit wiring, set them at right angles.*10 The connection diagram shows factory default functions assigned to digital input terminals [X1] to [X5], [FWD] and [REV], transistor output terminals [Y1] and [Y2], and monitor contact output terminals [FM] .*11 The power switching connectors (CN UX) and the fan power supply switching connectors (CN R and CN W) are for type 0203(460 V class) or above.*12 Slide switches on the control printed circuit board (control PCB). Use these switches to customize the inverter operations.*13 Use auxiliary contacts of the thermal relay (manually restorable) to trip the molded case circuit breaker (MCCB) or magnetic contactor (MC).*14 When using the Enable input function, be sure to remove the jumper wire from terminals [EN1],[EN2] and [PLC].*15 and are separated and insulated

FRENIC-Ace (E2) Keypad

SD DX- DX+ CMY Y1 Y2 CM X1 X2 X3 X4 X5 PLC

30A 30B 30C CM FWD REV PLC EN1 EN2

C1 11 FM1 FM2 11 11 12 13

• FWD, Rev, plus 5 Digital inputs. Con�gurable for Source or Sink.

• 0-10VDC analog input.• 4-20mA, 0-20mA or 0-10VDC analog input.• 2 Transistor outputs.

• Form C contact relay o (250VAC 0.3A, cosØ=0.3), (48VDC, .5A).• 1 0-10VDC, 4-20mA, 0-20mA or 25-32kp/s analog

output. • 1 0-10VDC, 4-20mA or 0-20mA analog output. • 24VDC max 100mA DC output power.• 10VDC output power for potentiometer.• 2 Source only, safe torque off Enable Inputs.• RS-485 wire terminals.

Min. Max.

On level 0V 2V

Off level 22V 27V

On level 22V 27V

Off level 0V 2V

Operating Voltage

(Sink)Operating

Voltage (Sink)

Item

Max.

On level 2v

Off level 22V

Maximum Current at on 50mA

ItemOperating

Voltage (Sink)

A. LED DisplayB. Remote/Local IndicatorC. Monitoring Display IndicatorD. Program Reset KeyE. Function Data KeyF. Shift KeyG. Menu Navigation KeysH. Local Mode Control Operators

DBR(Option )

DCR(Option )

DB N(-)P(+)P1

UVW

UVW

M3~

C

L1/RL2/SL3/T

MC

MCCBor

RCD/ELCB

GGrounding terminal

(* 1 )

(* 2 )

(* 5 )

( * 6 )

P DB

21 (CM)

(THR)

(G)

N(-)P(+)

P DB

21 (CM)

(G)

2

1 (THR)P(+) N(-)

DBR(Option )

Brake Unit( Option )

(G)P(+) R

DB

(* 7 )

TH1THC

PTC

[11][C1]

Thermal

)

R1T1

R0T0(* 3 )

Auxiliary control power supply

Auxiliary fan power supply

(* 4 ){

(* 11 )

DC/DC

(PLC)

(FWD)

(REV)

(X1)

(X2)

(X3)

(X4)

(X5)(CM)

(EN1)

SINK

SOURCE

(EN2)

0V+24VDC

Run forward command

Run reverse command

Select multi-frequency (0 to 1 step)

Select multi-frequency (0 to 3 step)

Select multi-frequency (0 to 7 step)

Coast to a stop

<Y1>

<Y2>

<CMY>

Inverter running

Motor overload early warning

[FM]

[11]0V

G

E

Output frequency 1

SW1(* 12 )

(* 8 )

(* 9 )

Dig

ital

inpu

t

Common terminal for digital inputs

Con

tact

ou

tput

sTr

ansi

stor

ou

tput

s

(* 10 )

(* 10 )

Common terminal for analog output

Ana

log/

Pul

se tr

ain

outp

ut

Common terminal for transistor outputs( SINK/SOURCE)

Safety switch

SW5(* 12 )

30C

30B

30A

Alarm output( for any alarm)

30

Current output( 4(0) ~20mADC)

Voltage output( 0~+10VDC)

Pulse train output( 25~32kp/s)

・Power switching connector “CN UX ”・Fan power supply switching connector “CN R ”  / “CN W ”

(* 10 )

(* 9 )

(* 14 )

(PLC)

Chargingindicator

RJ45 connector

SW2(*12 )

Con

nect

or fo

r op

tion

card

FMI

FMV

FMP

FUFVFW FM

(* 13 )

Transformer

Motor

In case of the motor with built-in cooling fan

Thermal

Communication port 1

( RS-485)

Keypad(standard)

Detachable terminal block

Voltage input V2( 0~+10VDC)

〔11 〕

〔12 〕

〔13 〕(* 9 ) +10VDC

Current input C1( 4(0) ~20mADC)

Current/voltage input for setting + 4(0) to 20mADC / 0 to +10VDC

Voltage input for setting 0 to

+ 10VDC (0 to ±10VDC) 0V

Ana

log

inpu

t

3

2

1

PTC input〔C1〕(* 9 )

(+)

(-)

Voltage input 12( 0~+10VDC)( 0~±10VDC)

SW4PTCAI

(* 12 )

(* 12 )SW3

C1

V2

0V

0V0V

Enable input

DBR: Dynamic Braking ResistorDCR : DC reactorRCD : Residual-current-operated protective deviceELCB : Earth leakage circuit breakerMC : Magnetic contactorMCCB: Molded case circuit breaker

Grounding terminal

Potentiometer power supply

Common terminal for analog inputs

Communication port 2

( RS-485 )

[FM2]

SW7(* 12 )

FMI

FMVOutput current

(DX+)

(DX-)SW6(* 12 ) (SD)

(* 9 )

Current output( 4(0) ~20mADC)

Voltage output( 0~+10VDC)

(* 10 )

[11]0V

Common terminal for analog output

(* 15 )

(* 15 )

(* 15 )

(* 15 )

(* 15 )

U1U2

CN UX

FAN NC

CN R CN W

Power supply 400V series 380 to 480V 50/60Hz 200V series 200 to 240V 50/60Hz

(* 13 )

Fuji Electric Corp. of America47520 Westinghouse Drive, Fremont, CA 94539Phone: 510-440-1060www.americas.fujielectric.com

4. I_O (I/O Check)

4_00 I/O Signals on the Control Card Terminals

4_01 I/O Signals on the Control Card Terminals

under Communications.

4_02 Input Voltage on Terminal 12

4_03 Input Current on Terminal C1

4_04 Output Voltage on Terminal FMV

4_05 Output Voltage on Terminal FM2

4_06 Output Frequency on Terminal FMP

4_07 Input Voltage on Terminal C1

4_08 Output Current on Terminal FMI

4_09 Output Current on Terminal FM2

4_24 Cutomizable Logic Timer

1.F _ _

1.E _ _

1.C _ _

1.P _ _

1.H _ _

1.H1 _ _

1.A _ _

1.J _ _

1.J1 _ _

1.d _ _

1.U _ _

1.U1 _ _

1.Y _ _

1.k _ _

2. rEP

3. oEP

4. I_O

5. CHE

6. AL

5. CHE (Maintenacne Info)

5_00 Accumulated Run Time

5_01 DC Link Bus Voltage

5_03 Max Temperature of Heat Sink

5_04 Max Effectice Current

5_07 Accumulated Run Time of Cooling Fan

5_08 Number of Starts (Drive)

5_09 Input Watt-Hour

5_10 Input Watt-Hour Data

5_05 Capacitance of the DC Link Bus

Capacitance

5_06 Accumutated Run Time of Electolytic

Capacitors on the PCB

6. AL (Alarm Info)

6_00 Output Frequency

6_01 Output Current

6_02 Output Voltage

6_03 Calculated Torque

6_04 Reference Frequency

6_05 Rotational Ditection

6_06 Running Status

6_07 Accumulated Running Time

6_08 Number of Startups

6_09 DC Link Bus Voltage

6_10 Temperature Inside the Inverter

6_11 Max. Temperature of Heat Sink

6_12 Terminal I/O Status

6_13 Terminal Input Signal Status in HEX6_14 Terminal Output Status in Hex6_15 Number of Consecutice Occurrces

6_16 Overlapping Alarm 1

6_17 Overlapping Alarm 2

6_18 Communication Terminal Status I/0

6_19 Communication Terminal Status Input

6_20 Communication Terminal Status Output

6_21 Sub-Code

6_22 Running Status 2

6_23 Detected Speed

6_24 Running Status 3

6_25 Multiple Alarm Sub-Code

Quick Start Menus

1.F Fundamental Functions

1.E Extension Terminal Functions

1.C Control Functions of Frequency

1.P Motor 1 Parameters

1.H High Performance Functions

1.H1 High Performance Functions

1.A Motor 2 Functions

1.J Application Functions

1.J1 PID Functions

1.d Application Functions 2

1.U Customizable Logic

1.U1 Customizable Logic

1.Y Link Functions

1.k Keypad Functions

2. rEP (Data Check)

Displays function codes that

have been changed from

factory default

3. oPE (Operations Monitor)

3_00 Output frequency Before Slip

3_01 Output frequency After Slip

3_02 Output Current

3_03 Output Voltage

3_04 Calculated Torque

3_05 Reference Frequency

3_06 Rotation Direction

3_07 Running Status

3_08 Motor Speed r/min

3_09 Load Shaft speed

3_10 PID SV

3_11 PID PV

3_12 Torque Limit Value A

3_13 Torque Limit Value B

3_14 Ratio Setting

3_15 Line Speed r/min

First Power ON.

Upon powering the drive on for the �rst time you must set the region in Menu 8.des, for Americas by setting the value to amerAfter initial start-up you may change the region by setting the value of H101. See page 4-4 of FRENIC-ACE Instructional Manual INR-SI47-1733f-E For more details.

Changing the regional from default value asia to amer requires pressing and holding key while pressing

jpn

asia

chn

eu

amer

kor

savue+

To access menus 2-6 change function code E52-2