L O W  ACCUMULA TOR 1. Piping Abbreviation Identies the part of the system with text printed in black on an orange background. Abbreviations are recommended; see table of Piping  Abbreviations . If additional identifying information is needed, include it here. 2. Physical State For liquid ammonia, show “LIQ” in black on a yellow band • For vapor, show “VAP” in black on a sky blue band • If both states may be present, both elements may appear 3. Pipe Contents The word “AMMONIA” should be printed in black on an orange background. 4. Pressure Level For contents at 70 psig or less, show “LOW” in black on a green band • For contents above 70 psig, show “HIGH” in black on a red band 5. Flow Direction Show the direction of ow with directional arrows, printed in black on an orange background. The arrows may appear at one or both ends of the label, and may repeat around the circumference of the pipe if desired. Piping Abbreviations Piping Description Abbr. Booster Discharge BD Booster Suction BS Condenser Drain CD Economizer Suction ES High Pressure Liquid HPL High Stage Discharge HSD High Stage Suction HSS High Temperature Recirculated Liquid HTRL High Temperature Recirculated Suction HTRS High T emperature Suction HTS Hot Gas Defrost HGD Intermediate Pressure Liquid IPL Liquid Injection Cooling LIC Low Stage Suction LSS Low Temp eratur e R ecircu lated Liquid LTRL Low Temperature Recirculated Suction LTRS Low Temperature Suction LTS Medium Temperature Recirculated Liquid MTRL Medium Temperature Recirculated Suction MTRS Medium Temperature Suction MTS Oil Drain OD Pump Out PO Relief Vent RV Sub-Cooled Liquid SCL  Thermosyphon Return TSR  Thermosyphon Supply TSS  Thermosyphon Vent TSV Pipe Marker Dimensions Outside Pipe Diameter Including Covering Minimum Marker Height Minimum Marker Length Minimum Height of Letters Min. Width of State/Press. Bands Up to 1.25" 1.25" - 2" 2" - 7" 7" - 10" Over 10" 32 mm 32 - 51 mm 51 - 178 mm 178 - 254 mm Over 254 mm 1" 1.5" 2.5" 3.5" 4.5" 25 mm 38 mm 64 mm 89 mm 114 mm 8" 8" 12" 24" 32" 203 mm 203 mm 305 mm 610 mm 813 mm .5" .75" 1.25" 2.5" 3.5" 13 mm 19 mm 32 mm 64 mm 89 mm .5" .75" 1" 1.5" 2" 13 mm 19 mm 25 mm 38 mm 51 mm  Pipe Marker Locations Before and after any change in pipe direction. If the pipe ends at equipment or changes direction again within 24 inches (61cm), the label in the short space may be omitted. Before and after any wall, ceiling, or oor penetration. No farther than 40 feet (12m) apart on extended runs of pipe. At least once in each room or area through which the pipe passes. System Component Markers – Two-Part Labels  Ammonia Pipe Markers – Five-Part Labels 1. Component Identifer Name the component with black text on an orange background. Abbreviations are acceptable; see the table of Component  Abbreviations. If additional identifying information is needed, include it here. 2. Pressure Level • For contents at 70 psig or less, show “LOW” in black on a green band • For contents above 70 psig, show “HIGH” in black on a red band Component Marker Dimensions • At least 3.5 inches high Lettering at least 2.5 inches high Marker length will vary to allow for the length of the component name Pressure level band should be at least 1.5 inches wide Component Abbreviations Component/Equipment Abbr.  Accumulator (with/without int. coil) ACC  Air Cooled Condenser AC  Air Handling Unit AHU  Air Unit AU Booster Compressor BC Co ntrolled P re ssure Receiver CPR Evaporative Condenser EC Heat Exchanger HEX  High Pressure Receiver HPR High Stage Compressor HSC Hi gh Tempe ra tu re Rec ir cu la to r HT R Inter co oler (wi th/wit hout int. coil ) IC Liquid Transfer Unit LTU Low T empera ture Compressor LTC Lo w Te mpe ra t ur e Rec ir cu la to r LTR Low Low Temp Recirculator LLTR Oil Pot OP Oil Separator OS Pilot Receiver PR Purger Unit PRG Refrigerant Pump RP Re fr ig er at ed Mak e- Up Air Un it RMAU Rooftop Air Unit RTU Surge Drum SD Swing Compressor SWC  Thermosyphon Receiver TSR Water Cooled Condenser WC IIAR Suggested Pipe Color Scheme In addition to the detailed labels, it may be helpful to include a color code for refrigeration system pipes. These colors may be applied as paint over the length of the pipe, or as bands of color applied periodically, as sufcient for pipe recognition. IIAR Bulletin No. 114 suggests the color scheme shown at right. Colo r Pi pe De si gn at ion Ora nge Hig h P ressur e L iquid  Yellow High Pressure Vapor Sky Blue Low Pressu re, High Temper atur e Liquid/V apor Blue Low Pressure, Low Temperature Liquid/Vapor Purple Low Pressure, Very Low Temperature Liquid/Vapor Gr ay Pr e ss ure R el ie f Vent pi pi ng  Green Nonvolatile, Non-pressurized Process piping  This, or any other pipe coloring scheme, should only be used in conjunction with a clearly posted legend or key describing the color scheme in place. This guide is for general information purposes only. It is not a substitute for review of applicable  standards or regulations. © 2007, 2014 Graphic Products, Inc. All Rights Reserved. 1 1 2 2 4 5 3 L O W H I G H L O W H I G H L I Q  V  A P 877.534.5157 | DuraLabel.com AMMONIA PIPE MARKING GUIDE  This g uide follow s Inte rnatio nal Institu te of Ammo nia R efrige ration (IIAR) Bullet in No . 11 4, as revis ed in 201 4. Fa cilities using an older version of the st andard may continue to do so, as long as their usage is consistent and documented.

Qrg Pipe-Ammonia 06-13-14

Embed Size (px)

Citation preview

7/24/2019 Qrg Pipe-Ammonia 06-13-14

http://slidepdf.com/reader/full/qrg-pipe-ammonia-06-13-14 1/2

LOW ACCUMULATOR

1. Piping Abbreviation

Identies the part of the system with text printed in black on an orange

background. Abbreviations are recommended; see table of Piping

 Abbreviations. If additional identifying information is needed, include it here.

2. Physical State

•For liquid ammonia, show “LIQ” in black on a yellow band

• For vapor, show “VAP” in black on a sky blue band

• If both states may be present, both elements may appear

3. Pipe Contents

The word “AMMONIA” should be printed in black on an orange background.

4. Pressure Level

• For contents at 70 psig or less, show “LOW” in black on agreen band

• For contents above 70 psig, show “HIGH” in black on a red band

5. Flow Direction

Show the direction of ow with directional arrows, printed in black on an orange

background. The arrows may appear at one or both ends of the label, and may

repeat around the circumference of the pipe if desired.

Piping Abbreviations

Piping Description Abbr.

Booster Discharge BD

Booster Suction BS

Condenser Drain CD

Economizer Suction ES

High Pressure Liquid HPL

High Stage Discharge HSD

High Stage Suction HSS

High Temperature Recirculated

Liquid HTRL

High Temperature Recirculated

SuctionHTRS

High Temperature Suction HTS

Hot Gas Defrost HGD

Intermediate Pressure Liquid IPL

Liquid Injection Cooling LIC

Low Stage Suction LSS

Low Temperature Recirculated Liquid LTRL

Low Temperature Recirculated

SuctionLTRS

Low Temperature Suction LTS

Medium Temperature Recirculated

LiquidMTRL

Medium Temperature Recirculated

SuctionMTRS

Medium Temperature Suction MTS

Oil Drain OD

Pump Out PO

Relief Vent RV

Sub-Cooled Liquid SCL

 Thermosyphon Return TSR

 Thermosyphon Supply TSS

 Thermosyphon Vent TSV

Pipe Marker Dimensions

Outside Pipe Diameter

Including Covering 

Minimum

Marker Height

Minimum

Marker Length

Minimum

Height of Letters

Min. Width of

State/Press. Bands

Up to 1.25"1.25" - 2"

2" - 7"

7" - 10"

Over 10"

32 mm32 - 51 mm

51 - 178 mm

178 - 254 mm

Over 254 mm

1"1.5"

2.5"

3.5"

4.5"

25 mm38 mm

64 mm

89 mm

114 mm

8"8"

12"

24"

32"

203 mm203 mm

305 mm

610 mm

813 mm

.5"

.75"

1.25"

2.5"

3.5"

13 mm19 mm

32 mm

64 mm

89 mm

.5"

.75"

1"

1.5"

2"

13 mm19 mm

25 mm

38 mm

51 mm

 

Pipe Marker Locations

• Before and after any change in pipe direction. If the pipe ends at equipmentor changes direction again within 24 inches (61cm), the label in the shortspace may be omitted.

• Before and after any wall, ceiling, or oor penetration.

• No farther than 40 feet (12m) apart on extended runs of pipe.

• At least once in each room or area through which the pipe passes.

System Component Markers – Two-Part Labels 

Ammonia Pipe Markers – Five-Part Labels 

1. Component Identifer 

Name the component with black

text on an orange background.

Abbreviations are acceptable;

see the table of Component

 Abbreviations. If additional

identifying information is needed,

include it here.

2. Pressure Level• For contents at 70

psig or less, show“LOW” in black on agreen band

• For contents above 70 psig,show “HIGH” in black on a redband

Component Marker Dimensions

• At least 3.5 inches high

• Lettering at least 2.5 inches high

• Marker length will vary to allowfor the length of the componentname

• Pressure level band should be atleast 1.5 inches wide

Component Abbreviations

Component/Equipment Abbr.

 Accumulator (with/without int. coil) ACC

 Air Cooled Condenser AC

 Air Handling Unit AHU Air Unit AU

Booster Compressor BC

C ontrolled Pre ssure Receiver CPR

Evaporative Condenser EC

Heat Exchanger HEX  

High Pressure Receiver HPR

High Stage Compressor HSC

H ig h Te mp er at ure Re ci rc ul at or H TR

Intercooler (with/without int. coil) IC

Liquid Transfer Unit LTU

Low Temper ature Compressor LTC

L ow Te mpe ra tu re Re ci rc ul at or LT R

Low Low Temp Recirculator LLTR

Oil Pot OP

Oil Separator OS

Pilot Receiver PR

Purger Unit PRG

Refrigerant Pump RP

R ef ri ge ra te d Ma ke -U p Ai r U ni t R MAU

Rooftop Air Unit RTU

Surge Drum SD

Swing Compressor SWC

 Thermosyphon Receiver TSR

Water Cooled Condenser WC

IIAR Suggested Pipe Color Scheme

In addition to the detailed

labels, it may be helpful

to include a color code

for refrigeration system

pipes. These colors may

be applied as paint over

the length of the pipe, or

as bands of color applied

periodically, as sufcient

for pipe recognition. IIAR

Bulletin No. 114 suggests

the color scheme shown

at right.

Color P ipe Designation

Orange High Pressure Liquid

 Yellow High Pressure Vapor 

Sky Blue Low Pressure, High Temperature Liquid/Vapor 

Blue Low Pressure, Low Temperature Liquid/Vapor 

Purple Low Pressure, Very Low Temperature Liquid/Vapor 

Gray Pressur e Relief Vent piping 

Green Nonvolatile, Non-pressurized Process piping 

 This, or any other pipe coloring scheme, should only be used in conjunction with a

clearly posted legend or key describing the color scheme in place.

This guide is for general information purposes only. It is not a substitute for review of applicable

 standards or regulations. © 2007, 2014 Graphic Products, Inc. All Rights Reserved.

1

1 2

2 4 53

LOW

HIGH

LOW

HIGH

LIQ

 V AP

877.534.5157 | DuraLabel.com

AMMONIA PIPE MARKING GUIDE This guide follows International Institute of Ammonia Refrigeration (IIAR) Bulletin No. 114, as revised in 2014. Facilities

using an older version of the st andard may continue to do so, as long as their usage is consistent and documented.

7/24/2019 Qrg Pipe-Ammonia 06-13-14

http://slidepdf.com/reader/full/qrg-pipe-ammonia-06-13-14 2/2

06/14

Pipe Marking Accessories

Pipe Grabber™ Sleeves

Clear plastic pipe grabber sleeves

provide a clean surface for pipe marking

labels, enabling users to identify dirty,

oily, rusty pipes. Labels are applieddirectly on the sleeve, then the sleeve

curls tightly around the pipe.

Pipe Grabber Sleeve Sizes:

▪ 1" x 9" - Fits pipes with diameters 1" - 1.5"

▪ 1.5" x 9" - Fits pipes with diameters 1.5" - 2.3"

▪ 2" x 12" - Fits pipes with diameters 2" - 3"

▪ 3" x 12" - Fits pipes with diameters 3" - 4"

▪ 4" x 18" - Fits pipes with diameters 4" - 5.2"

DuraTagTM, Slot Puncher and Cable Ties

For difcult to label pipes or situationswhere adhesive labels are not

appropriate, we offer the Slot Puncher

and Cable Ties. Simply print your

custom label onto DuraTag TM Tag Stock,

use the Slot Puncher in each corner of

your label, and secure to pipe with our Cable Ties.

Heavy-Duty Valve Tags

Label pipes and valves easily with our

Heavy-Duty Valve Tags. Tags provide a rigid

base for your label, and have pre-drilled holes

to hang with cable ties. Great for small pipes

as pictured and color-coding valves.

Create Ammonia Pipe Markers with

THERMAL TRANSFER PRINTERS

Proper ammonia pipe marking is critical in facility safety and efficiency. Pipes containing ammonia

require specialized designs and a durable marker to comply with global industry standards.

DuraLabel offers industrial printers designed to print these labels for compliance and lasting

performance in industrial settings.

DuraLabel 9000 

Increase visibility

from a distance with

oversized labels.

Create labels and

signs up to 9" in width.

DuraLabel Toro is a portable, independent

label and sign printer capable of creating

labels up to 4" in width anywhere, anytime.

DuraLabel PRO 300 prints up to 3" per

second on supplies from ½" to 4" in

width. With more types of supplies than

any other printer, it assures you a lways

get your labeling jobs done right.

DuraLabel Lobo is a portable thermal transfer

printer that gives you the power to create

durable labels anywhere, anytime. The

Lobo’s label stock comes in easy-to-use

cartridges of ½" to 2" in width and can

be changed in seconds.

SAVE WITH KITS! Bundle a DuraLabel

printer, supplies, and DuraSuite™ labeling

software to make compliance easy!

Call Today! 877.534.5157

877.534.5157 | DuraLabel.com Scan here to learn more about

DuraLabel pipe marking solutions!