PSEG Internal Use Only Page 1 of 1 PSEG NUCLEAR L.L.C. SALEM/OPERATIONS S2.OP-AR.ZZ-0003(Q) - REV. 17 OVERHEAD ANNUNCIATORS WINDOW C Ë Biennial Review Performed: Yes ____ No T Ë DCP Packages and Affected Document Numbers incorporated into this revision: None Ë OTSC(s) were incorporated into this revision: None Ë OPEX(s) were incorporated into this revision: None REVISION SUMMARY: Ë Pg. 45, OHA C-38, CFCU Leak Detection High, Step 3.5.D - Added step INITIATE SC.OP-DG.SW-0005, Service Water Spill Response in Containment. (70103767) IMPLEMENTATION REQUIREMENTS Effective Date: 01/21/10 None

PSEG Internal Use Only Page 1 of 1 SALEM/OPERATIONS …s2.op-ar.zz-0003(q) salem 2 page 3 of 57 rev. 17 c waste disposal leak detect aux cooling containment 1 1 gas anly trbl m 2 cntmtsump

  • Upload
    others

  • View
    3

  • Download
    0

Embed Size (px)

Citation preview

  • PSEG Internal Use Only Page 1 of 1

    PSEG NUCLEAR L.L.C.SALEM/OPERATIONS

    S2.OP-AR.ZZ-0003(Q) - REV. 17

    OVERHEAD ANNUNCIATORS WINDOW C

    Ë Biennial Review Performed: Yes ____ No T Ë DCP Packages and Affected Document Numbers incorporated into this revision: NoneË OTSC(s) were incorporated into this revision: NoneË OPEX(s) were incorporated into this revision: None

    REVISION SUMMARY:

    Ë Pg. 45, OHA C-38, CFCU Leak Detection High, Step 3.5.D - Added stepINITIATE SC.OP-DG.SW-0005, Service Water Spill Response in Containment. (70103767)

    IMPLEMENTATION REQUIREMENTS Effective Date: 01/21/10

    ‚ None

  • S2.OP-AR.ZZ-0003(Q)

    Salem 2 Page 1 of 57 Rev. 17

    OVERHEAD ANNUNCIATORS WINDOW C

    TABLE OF CONTENTS

    SECTION PAGE

    Table of Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

    Window C Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

    Text . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

    WINDOW SECTION

    C-1 GAS ANLY TRBL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

    C-2 CNTMT SUMP PMP START . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

    C-3 21 CC HX IN TEMP HI . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

    C-4 21 CFCU AIRFLO TRBL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

    C-5 21 CFCU WTRFLO TRBL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

    C-6 CNTMT PRESS HI-HI . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

    C-7 21 H2 RECOMB TRBL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

    C-8 N A CNTMT ISOL ACT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

    C-9 104 PNL TRBL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

    C-10 CNTMT SUMP OVRFLO . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

    C-11 22 CC HX IN TEMP HI . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

    C-12 22 CFCU AIRFLO TRBL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

    C-13 22 CFCU WTRFLO TRBL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

    C-14 CNTMT PRESS HI . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

    C-15 22 H2 RECOMB TRBL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

    C-16 N B CNTMT ISOL ACT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

    C-17 21-23 CVCS HUT LVL HI . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

    C-18 RX SUMP OVRFLO . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

    C-19 SFP TEMP HI . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23

    C-20 23 CFCU AIRFLO TRBL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

    C-21 23 CFCU WTRFLO TRBL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26

    C-22 CNTMT SPRY ACT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27

  • S2.OP-AR.ZZ-0003(Q)

    Salem 2 Page 2 of 57 Rev. 17

    TABLE OF CONTENTS (Continued)

    WINDOW SECTION PAGE

    C-23 CNTMT H2 LVL HI . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28

    C-24 SPARE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29

    C-25 BA EVAP TRBL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30

    C-26 21 RHR SUMP OVRFLO . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31

    C-27 SFP LVL HI . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32

    C-28 24 CFCU AIRFLO TRBL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33

    C-29 24 CFCU WTRFLO TRBL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34

    C-30 CFCU LK DET HI-HI . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35

    C-31 SPARE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37

    C-32 SPARE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38

    C-33 RWST/PWST OVRFLO . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39

    C-34 22 RHR SUMP OVRFLO . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40

    C-35 SFP LVL LO . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41

    C-36 25 CFCU AIRFLO TRBL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42

    C-37 25 CFCU WTRFLO TRBL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43

    C-38 CFCU LK DET HI . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44

    C-39 SPARE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46

    C-40 SPARE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47

    C-41 SPARE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48

    C-42 SPARE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49

    C-43 SPARE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50

    C-44 SPARE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51

    C-45 SPARE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52

    C-46 PERSONNEL ACCESS DOOR OPEN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53

    C-47 SPARE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54

    C-48 SPARE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55

    References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56

  • S2.OP-AR.ZZ-0003(Q)

    Salem 2 Page 3 of 57 Rev. 17

    C

    WA

    STE

    DIS

    POSA

    LLE

    AK

    DET

    ECT

    AU

    XC

    OO

    LIN

    GC

    ON

    TAIN

    MEN

    T

    1

    1

    GA

    S A

    NLY

    TRB

    L

    M

    2

    CN

    TMT

    SUM

    P PM

    PST

    AR

    T

    3

    21 C

    C H

    XIN

    TEM

    PH

    I

    4

    21 C

    FCU

    AIR

    FLO

    TRB

    L

    5

    21 C

    FCU

    WTR

    FLO

    TRB

    L

    6

    CN

    TMT

    PRES

    SH

    I - H

    I

    7

    21 H

    2R

    ECO

    MB

    TRB

    L

    8

    N A

    CN

    TMT

    ISO

    LA

    CT

    8

    9

    9

    104

    PNL

    TRB

    L

    10

    CN

    TMT

    SUM

    PO

    VR

    FLO

    11

    22 C

    C H

    XIN

    TEM

    PH

    I

    12

    22 C

    FCU

    AIR

    FLO

    TRB

    L

    13

    22 C

    FCU

    WTR

    FLO

    TRB

    L

    14

    CN

    TMT

    PRES

    SH

    I

    15

    22 H

    2R

    ECO

    MB

    TRB

    L

    16

    N B

    CN

    TMT

    ISO

    LA

    CT

    16

    17

    17

    21 -

    23 C

    VC

    SH

    UT

    LVL

    HI

    M

    18

    RX

    SUM

    PO

    VR

    FLO

    19

    SFP

    TEM

    PH

    I

    20

    23 C

    FCU

    AIR

    FLO

    TRB

    L

    21

    23 C

    FCU

    WTR

    FLO

    TRB

    L

    22

    CN

    TMT

    SPR

    YA

    CT

    23

    CN

    TMT

    H2 L

    VL

    HI

    24

    24

    25

    25

    BA

    EV

    AP

    TRB

    L

    26

    21 R

    HR

    SUM

    PO

    VR

    FLO

    27

    SFP

    LVL

    HI

    28

    24 C

    FCU

    AIR

    FLO

    TRB

    L

    29

    24 C

    FCU

    WTR

    FLO

    TRB

    L

    30

    CFC

    ULK

    DET

    HI -

    HI

    M

    3132

    32

    3333

    RW

    ST /

    PWST

    OV

    RFL

    O

    34

    22 R

    HR

    SUM

    PO

    VR

    FLO

    35

    SFP

    LVL

    LO

    36

    25 C

    FCU

    AIR

    FLO

    TRB

    L

    37

    25 C

    FCU

    WTR

    FLO

    TRB

    L

    38

    CFC

    ULK

    DET

    HI

    M

    3940

    40

    41

    4142

    4344

    4546

    PER

    SON

    NEL

    AC

    CES

    SD

    OO

    R O

    PEN

    4748

    48

  • S2.OP-AR.ZZ-0003(Q)

    Salem 2 Page 4 of 57 Rev. 17

    ALARM

    C-11

    GAS ANLYTRBL

    M

    DEVICES: N/A

    SETPOINT: N/A

    1.0 CAUSE(S):

    1.1 Cover Gas Low Flow

    1.2 AC Power failure

    1.3 Hydrogen Low

    1.4 DC Power Failure

    1.5 WGDT Low Flow

    1.6 Recorder Trouble

    1.7 Oxygen High/Low

    2.0 AUTOMATIC ACTION:

    None

    3.0 OPERATOR ACTIONS:

    3.1 SEND Operator to Waste Disposal Gas Analyzer PNL 110 to determine cause of alarm.

    3.2 GO TO S2.OP-AR.WG-0001(Q), Waste Disposal Gas Analyzer PNL 110.

    Page 1 of 1 C-1References:

  • S2.OP-AR.ZZ-0003(Q)

    Salem 2 Page 5 of 57 Rev. 17

    ALARM

    C-22

    CNTMTSUMP PMP

    START

    DEVICES: N/A

    SETPOINT: N/A

    1.0 CAUSE(S):

    21 or 22 Containment Sump Pumps started

    2.0 AUTOMATIC ACTION:

    None

    3.0 OPERATOR ACTIONS:

    3.1 IF any indication of an RCS leak or an interconnecting ECCS leak affecting RCS inventory,THEN GO TO S2.OP-AB.RC-0001(Q), Reactor Coolant System Leak.

    3.2 DETERMINE a leakrate IAW S2.OP-SO.RC-0004(Q),Identifying and Measuring Leakage.

    A. IF leakrate is $ 1 gpm,THEN REFER to Technical Specifications.

    B. IF leakrate is trending up,THEN:

    1. SEND an Operator into Containment to determine source of leak.

    2. INITIATE a NOTF IAW LS-AA-120, Issue Identification and Screening Process

    3.3 MONITOR the WHUT levels.

    Page 1 of 1 C-2References: Dwg. 220972

  • S2.OP-AR.ZZ-0003(Q)

    Salem 2 Page 6 of 57 Rev. 17

    ALARM

    C-33

    21 CC HXIN TEMP

    HI

    DEVICES: 2TIC627A

    SETPOINT: $ 170°F

    1.0 CAUSE(S):

    Inlet temperature is $ 170°F

    2.0 AUTOMATIC ACTION:

    None

    3.0 OPERATOR ACTIONS:

    3.1 IF alarm is due to loss of Service Water pressure,THEN GO TO S2.OP-AB.SW-0001(Q), Loss of Service Water Header Pressure.

    3.2 IF alarm is due to loss of Component Cooling Water,THEN GO TO S2.OP-AB.CC-0001(Q), Component Cooling Abnormality.

    3.3 SEND an operator to perform the following:

    Ë INVESTIGATE the cause of the alarm.

    Ë ALIGN CCHXs as directed IAW S2.OP-SO.CC-0002(Q), 21 & 22 Component Cooling Heat Exchanger Operation.

    3.5 REFER to Technical Specifications 3.7.3 and 3.7.4.

    Page 1 of 1 C-3References: Dwg. 205331, 211522

  • S2.OP-AR.ZZ-0003(Q)

    Salem 2 Page 7 of 57 Rev. 17

    ALARM

    C-44

    21 CFCUAIRFLO

    TRBL

    DEVICES: N/A

    SETPOINT: N/A

    1.0 CAUSE(S):

    1.1 Roughing Filter Dampers not fully OPEN

    1.2 HEPA Filter Inlet Damper not fully CLOSED

    1.3 HEPA Filter Outlet Damper not fully CLOSED

    2.0 AUTOMATIC ACTION:

    None

    3.0 OPERATOR ACTIONS:

    3.1 IF 21 Containment Fan Coil Unit is operating in low speed,THEN no further Operator action is required.

    3.2 VERIFY positions of 21 Containment Fan Coil Filter Dampers

    on Control Console bezels.

    3.3 IF damper malfunction is indicated,THEN:

    A. STOP 21 Containment Fan Coil Unit.

    B. INITIATE a NOTF IAW LS-AA-120, Issue Identification and Screening Process.

    3.4 REFER to Technical Specification 3.6.2.3.

    Page 1 of 1 C-4References: Dwg. 205338, 203568

  • S2.OP-AR.ZZ-0003(Q)

    Salem 2 Page 8 of 57 Rev. 17

    ALARM

    C-5

    5

    21 CFCUWTRFLO

    TRBL

    DEVICES: N/A

    SETPOINT: N/A

    1.0 CAUSE(S):

    Any SW Valve misaligned with the CFCU running:

    ‚ 21SW58, 21 FAN COIL UNIT INLET WATER VALVE not fully OPEN

    ‚ 21SW72, 21 FAN COIL UNIT OUTLET WATER VALVE not fully OPEN

    ‚ 21SW223, 21 FAN COIL UNIT OUTLET WATER FLOW CONTROL VALVE is CLOSED

    2.0 AUTOMATIC ACTION:

    None

    3.0 OPERATOR ACTIONS:

    3.1 CONFIRM alarm by observing flow indication on 21 CFCU bezel.

    3.2 OPEN the following valves:

    A. 21SW58, 21 FAN COIL UNIT INLET WATER VALVE

    B. 21SW72, 21 FAN COIL UNIT OUTLET WATER VALVE

    3.3 IF a valve malfunction is suspected,THEN:

    A. STOP 21 Containment Fan Coil Unit.

    B. INITIATE a NOTF IAW LS-AA-120, Issue Identification and Screening Process

    C. REFER to Technical Specification 3.6.2.3

    Page 1 of 1 C-5References: Dwg. 205342, 203570

  • S2.OP-AR.ZZ-0003(Q)

    Salem 2 Page 9 of 57 Rev. 17

    ALARM

    C-66

    CNTMTPRESSHI-HI

    DEVICES: 2PC948A, 2PC948B, 2PC948C, 2PC948G

    SETPOINT: $ 15 psig

    1.0 CAUSE(S):

    Containment pressure channel $ 15 psig.

    2.0 AUTOMATIC ACTION:

    None

    3.0 OPERATOR ACTIONS:

    3.1 CONFIRM alarm by verifying indication.

    3.2 IF alarm is due to testing,THEN no further action is required.

    3.3 IF instrument failure is suspected,THEN:

    A. REMOVE affected channel from service IAW S2.OP-SO.RPS-0005(Q),Placing Containment Pressure Channel In Tripped Condition.

    B. INITIATE a NOTF IAW LS-AA-120, Issue Identification and Screening Process

    3.4 REFER to Technical Specification 3.3.2.1.

    Page 1 of 1 C-6References: Dwg. 221057

  • S2.OP-AR.ZZ-0003(Q)

    Salem 2 Page 10 of 57 Rev. 17

    ALARM

    C-77

    21 H2RECOMB

    TRBL

    DEVICES: N/A

    SETPOINT: # 350V input voltage

    1.0 CAUSE(S):

    Input voltage is # 350V

    2.0 AUTOMATIC ACTION:

    None

    3.0 OPERATOR ACTIONS:

    3.1 IF alarm is due to testing,THEN no further Operator action is required.

    3.2 ENSURE CLOSED breaker 2AX1AX15X at 2A 460V Vital Bus.

    3.3 REFER to Technical Specification 3.6.4.2.

    3.4 INITIATE a NOTF IAW LS-AA-120, Issue Identification and Screening Process

    Page 1 of 1 C-7References: Dwg. 203653

  • S2.OP-AR.ZZ-0003(Q)

    Salem 2 Page 11 of 57 Rev. 17

    ALARM

    C-88

    N ACNTMT ISOL

    ACT

    DEVICES: N/A

    SETPOINT: N/A

    1.0 CAUSE(S):

    1.1 Containment Isolation Phase A manual actuation

    1.2 Safety Injection signal

    2.0 AUTOMATIC ACTION:

    Phase A valves displayed on Panel 2RP4 CLOSE.

    3.0 OPERATOR ACTIONS:

    3.1 IF alarm is due to an SI,THEN GO TO 2-EOP-TRIP-1, Reactor Trip or Safety Injection.

    3.2 CONFIRM alarm by observing Panel 2RP4 or actual valve position indicationon Control Room Console.

    3.3 IF alarm is due to a failure,

    THEN:

    A. EVALUATE components affected.

    B. INITIATE a NOTF IAW LS-AA-120, Issue Identification and Screening Process.

    C. When notified of corrective action completion by Maintenance,RESET the alarm.

    3.4 REFER to Technical Specification 3.3.2.1.

    Page 1 of 1 C-8References: Dwg. 221057, 232015

  • S2.OP-AR.ZZ-0003(Q)

    Salem 2 Page 12 of 57 Rev. 17

    ALARM

    C-99

    104 PNL

    TRBL

    DEVICES: N/A

    SETPOINT: N/A

    1.0 CAUSE(S):

    An alarm on Panel 104, Waste Disposal-Boron Recycle Panel

    2.0 AUTOMATIC ACTION:

    None

    3.0 OPERATOR ACTIONS:

    3.1 SEND an Operator to Panel 104, Waste Disposal-Boron Recycle Panelto perform the following:

    A. DETERMINE cause of the alarm.

    B. INITIATE corrective action IAW S2.OP-AR.ZZ-0016(Q), Panel 104 Alarms.

    Page 1 of 1 C-9References: Dwg. 226513

  • S2.OP-AR.ZZ-0003(Q)

    Salem 2 Page 13 of 57 Rev. 17

    ALARM

    C-10

    10

    CNTMTSUMP

    OVRFLO

    DEVICES: 2LD2067

    SETPOINT: $ 75 feet 1 inch 1.0 CAUSE(S):

    Containment Sump level $ 75 feet 1 inch 2.0 AUTOMATIC ACTION:

    None 3.0 OPERATOR ACTIONS:

    3.1 IF Containment Sump Overflow is due to "N A Isolation" THEN RETURN to procedure in effect.

    3.2 ENSURE OPEN the following valves:

    A. 2WL16, CONT SUMP DISCH TO WHUT

    B. 2WL17, CONT SUMP DISCH TO WHUT

    3.3 IF Containment Sump Pump(s) failed to start,THEN VERIFY CLOSED:

    Ë Breaker 2GY1AX6J, 21 Containment Sump Pump

    Ë Breaker 2EY3AX6J, 22 Containment Sump Pump

    3.4 ENSURE Containment Sump Pumps have started.

    3.5 IF any indication of an RCS leak or an interconnecting ECCS leak

    affecting RCS inventory,THEN GO TO S2.OP-AB.RC-0001(Q), Reactor Coolant System Leak.

    3.6 DETERMINE a leakrate IAW S2.OP-ST.RC-0008(Q), RCS Water Inventory Balance.

    A. IF leakrate is trending up,

    THEN SEND an Operator into Containment to determine source of leak.

    B. IF leakrate is $ 1 gpm,THEN REFER to Technical Specifications.

    Page 1 of 1 C-10

    References: Dwg. 205326, 220972, 211514

  • S2.OP-AR.ZZ-0003(Q)

    Salem 2 Page 14 of 57 Rev. 17

    ALARM

    C-1111

    22 CC HXIN TEMP

    HI

    DEVICES: 2TIC627B

    SETPOINT: $ 170°F

    1.0 CAUSE(S):

    Inlet temperature is $ 170°F

    2.0 AUTOMATIC ACTION:

    None

    3.0 OPERATOR ACTIONS:

    3.1 IF alarm is due to loss of Service Water pressure,THEN GO TO S2.OP-AB.SW-0001(Q), Loss of Service Water Header Pressure.

    3.2 IF alarm is due to loss of Component Cooling Water,

    THEN GO TO S2.OP-AB.CC-0001(Q), Component Cooling Abnormality.

    3.3 SEND an operator to perform the following:

    Ë INVESTIGATE the cause of the alarm.

    Ë ALIGN CCHXs as directed IAW S2.OP-SO.CC-0002(Q), 21 & 22 Component Cooling Heat Exchanger Operation.

    3.5 REFER to Technical Specifications 3.7.3 and 3.7.4.

    Page 1 of 1 C-11References: Dwg. 205331, 211523

  • S2.OP-AR.ZZ-0003(Q)

    Salem 2 Page 15 of 57 Rev. 17

    ALARM

    C-1212

    22 CFCUAIRFLO

    TRBL

    DEVICES: N/A

    SETPOINT: N/A

    1.0 CAUSE(S):

    1.1 Roughing Filter Dampers not fully OPEN

    1.2 HEPA Filter Inlet Damper not fully CLOSED

    1.3 HEPA Filter Outlet Damper not fully CLOSED

    2.0 AUTOMATIC ACTION:

    None

    3.0 OPERATOR ACTIONS:

    3.1 IF 22 Containment Fan Coil Unit is operating in low speed,THEN no further Operator action is required.

    3.2 ENSURE the positions of 22 Containment Fan Coil Filter Dampers

    on the Control Console bezels.

    3.3 IF damper malfunction is indicated,THEN:

    A. STOP 22 Containment Fan Coil Unit.

    B. INITIATE a NOTF IAW LS-AA-120, Issue Identification and Screening Process

    3.4 REFER to Technical Specification 3.6.2.3.

    Page 1 of 1 C-12References: Dwg. 205338, 203572

  • S2.OP-AR.ZZ-0003(Q)

    Salem 2 Page 16 of 57 Rev. 17

    ALARM

    C-1313

    22 CFCUWTRFLO

    TRBL

    DEVICES: N/A

    SETPOINT: N/A

    1.0 CAUSE(S):

    Any SW Valve misaligned with the CFCU running:

    ‚ 22SW58, 22 FAN COIL UNIT INLET WATER VALVE not fully OPEN

    ‚ 22SW72, 22 FAN COIL UNIT OUTLET WATER VALVE not fully OPEN

    ‚ 22SW223, 22 FAN COIL UNIT OUTLET WATER FLOW CONTROL VALVE,is CLOSED

    2.0 AUTOMATIC ACTION:

    None

    3.0 OPERATOR ACTIONS:

    3.1 CONFIRM alarm by observing flow indication on 22 CFCU bezel.

    3.2 ENSURE OPEN the following valves:

    A. 22SW58, 22 FAN COIL UNIT INLET WATER VALVE

    B. 22SW72, 22 FAN COIL UNIT OUTLET WATER VALVE

    3.3 IF a valve malfunction is suspected,THEN:

    A. STOP 22 Containment Fan Coil Unit.

    B. INITIATE a NOTF IAW LS-AA-120, Issue Identification and Screening Process

    3.4 REFER to Technical Specification 3.6.2.3.

    Page 1 of 1 C-13References: Dwg. 205342, 203574

  • S2.OP-AR.ZZ-0003(Q)

    Salem 2 Page 17 of 57 Rev. 17

    ALARM

    C-1414

    CNTMTPRESS

    HI

    DEVICES: 2PC948D, 2PC948E, 2PC948F

    SETPOINT: $ 4 psig

    1.0 CAUSE(S):

    Containment pressure channel $ 4 psig

    2.0 AUTOMATIC ACTION:

    None

    3.0 OPERATOR ACTIONS:

    3.1 CONFIRM alarm by verifying indication.

    3.2 IF alarm is due to testing,THEN no further action is required.

    3.3 IF instrument failure is suspected,THEN:

    A. REMOVE affected channel from service IAW S2.OP-SO.RPS-0005(Q),Placing Containment Pressure Channel In Tripped Condition.

    B. INITIATE a NOTF IAW LS-AA-120, Issue Identification and Screening Process

    3.4 REFER to Technical Specification 3.3.2.1.

    Page 1 of 1 C-14References: Dwg. 221057

  • S2.OP-AR.ZZ-0003(Q)

    Salem 2 Page 18 of 57 Rev. 17

    ALARM

    C-1515

    22 H2RECOMB

    TRBL

    DEVICES: N/A

    SETPOINT: # 350V input voltage

    1.0 CAUSE(S):

    Input voltage is # 350V

    2.0 AUTOMATIC ACTION:

    None

    3.0 OPERATOR ACTIONS:

    3.1 IF alarm is due to testing,THEN no further action is required.

    3.2 ENSURE CLOSED breaker 2BX1AX15X on 2B 460V Vital Bus

    for No. 22 Hydrogen Recombiner

    3.3 REFER to Technical Specification 3.6.4.2.

    3.4 INITIATE a NOTF IAW LS-AA-120, Issue Identification and Screening Process.

    Page 1 of 1 C-15References: Dwg. 203654

  • S2.OP-AR.ZZ-0003(Q)

    Salem 2 Page 19 of 57 Rev. 17

    ALARM

    C-1616

    N BCNTMT ISOL

    ACT

    DEVICES: 2PC948A, 2PC948B, 2PC948C, 2PC948G

    SETPOINT: $ 15 psig

    1.0 CAUSE(S):

    1.1 Two out of four Containment pressure channels are $ 15 psig

    1.2 Manual Actuation

    2.0 AUTOMATIC ACTION:

    2.1 N B valves on Panel 2RP4 CLOSE.

    2.2 Containment Spray Valves on Panel 2RP4 OPEN

    2.3 Containment Spray Pumps START (if SEC permissive exists)

    3.0 OPERATOR ACTIONS:

    3.1 CONFIRM alarm by verifying coincidence on Panel 2RP4OR valve indications on Control Console.

    3.2 IF Containment pressure is $ 15 psig,THEN:

    A. TRIP the Reactor.

    B. GO TO 2-EOP-TRIP-1, Reactor Trip or Safety Injection.

    3.3 IF Containment pressure is # 15 psig,THEN:

    A. Attempt to RESET AND OPEN the Phase B Containment Isolation Valves.

    B. IF unable to reset Phase B Containment Isolation,THEN GO TO S2.OP-AB.RCP-0001(Q), RCP Abnormality,for loss of CCW flow to all RCP Motors.

    Page 1 of 1 C-16References: Dwg. 221057, 232016

  • S2.OP-AR.ZZ-0003(Q)

    Salem 2 Page 20 of 57 Rev. 17

    ALARM

    C-1717

    21-23 CVCSHUT LVL

    HIM

    DEVICES: 2LT167, 2LT168, 2LT170

    SETPOINT: $ 90%

    1.0 CAUSE(S):

    Any CVCS HUT level $ 90%

    2.0 AUTOMATIC ACTION:

    None

    3.0 OPERATOR ACTIONS:

    3.1 DETERMINE which CVCS HUT is causing the alarm from the Annunciator CRT:

    CRT Point Description

    173 21 CVCS HOLDUP TANK LEVEL HIGH

    180 22 CVCS HOLDUP TANK LEVEL HIGH

    188 23 CVCS HOLDUP TANK LEVEL HIGH

    3.2 SEND an operator to PLACE an unaffected tank in service IAWS2.OP-SO.CVC-0004(Q), CVCS Holdup Tank System Operations.

    Page 1 of 1 C-17References: Dwg. 205329

  • S2.OP-AR.ZZ-0003(Q)

    Salem 2 Page 21 of 57 Rev. 17

    ALARM

    C-1818

    RXSUMP

    OVRFLO

    DEVICES: 2LD7752

    SETPOINT: $ 54 feet

    1.0 CAUSE(S):

    Reactor Sump level $ 54 feet

    2.0 AUTOMATIC ACTION:

    None

    3.0 OPERATOR ACTIONS:

    3.1 IF in Modes 1-5,THEN:

    A. IF Reactor Sump Pump has not started,THEN VERIFY CLOSED breaker 2EY3AX6G for 2 Reactor Sump Pump

    B. ENSURE Reactor Sump Pump has started.

    C. IF any indication of an RCS leak or an interconnecting ECCS leak affecting RCS inventory,THEN GO TO S2.OP-AB.RC-0001(Q), Reactor Coolant System Leak.

    D. DETERMINE a leakrate IAW S2.OP-ST.RC-0008(Q),RCS Water Inventory Balance.

    E. INITIATE a NOTF IAW LS-AA-120, Issue Identification and Screening Process, as required.

    (Continued)

    Page 1 of 2 C-18

  • S2.OP-AR.ZZ-0003(Q)

    Salem 2 Page 22 of 57 Rev. 17

    3.2 IF in Mode 6,THEN:

    A. IF Reactor Cavity level is decreasing,THEN GO TO S2.OP-AB.FUEL-0002(Q),Loss of Refueling Cavity or Spent Fuel Pool Level.

    B. IF Reactor Cavity level is stable,THEN:

    1. VERIFY CLOSED breaker 2EY3AX6G for 2 Reactor Sump Pump.

    2. SEND an operator to determine the source of the leakage.

    3. INITIATE a NOTF IAW LS-AA-120, Issue Identification and Screening Process, as required.

    Page 2 of 2 C-18References: Dwg. 205326, 220972, 240698

  • S2.OP-AR.ZZ-0003(Q)

    Salem 2 Page 23 of 57 Rev. 17

    ALARM

    C-1919

    SFPTEMP

    HI

    DEVICES: 2TIC651

    SETPOINT: 125°F OR a temporary alarm setpoint may be in effect to supportrefueling outages (specifically reactor core off-loads).

    NOTE

    This alarm is expected during refueling outages during core off-load. The alarm setpoint mayhave to be raised to meet the commitment to maintain a loss of SFP cooling alarm.

    1.0 CAUSE(S):

    1.1 Spent Fuel Pit temperature $125°F.

    1.2 Spent Fuel Pit temperature is greater than the temporary alarm setpoint during refueling.

    2.0 AUTOMATIC ACTION:

    None

    3.0 OPERATOR ACTIONS:

    3.1 SEND operator to validate cause of alarm.

    3.2 REMOVE the Spent Fuel Demineralizer from service IAW S2.OP-SO.SF-0002(Q),Spent Fuel Cooling System Operation prior to reaching a Spent Fuel Pit temperature(TIC651) of 130°F.

    (continued on next page)Page 1 of 2 C-19

  • S2.OP-AR.ZZ-0003(Q)

    Salem 2 Page 24 of 57 Rev. 17

    3.0 OPERATOR ACTIONS (continued)

    3.3 IF the Spent Fuel Pit temperature is >125°FAND reactor core off-load is either in progress or completely off-loaded,THEN:

    A. INITIATE a continuous watch to monitor SFP temperature until the alarm setpoint is adjusted, as applicable, and the alarm is clear.

    1. INITIATE Temporary readings IAW SH.OP-DL.ZZ-0027 AND RECORD Spent Fuel Pit temperature (TIC651) every half hour until alarm setpoint has been changed, AND the Spent Fuel Demineralizer has been removed from service.

    2. IF the Alarm is adjusted,AND the Spent Fuel Demineralizer is out of service,THEN RECORD the Spent Fuel Pit temperature (TIC651) every four hours until the alarm setpoint has been returned to normal (125°F).

    B. INITIATE a NOTF to Maintenance to adjust the alarm setpointas provided by Outage Engineering (Refer to S-C-SF-MDC-1800).

    3.4 IF SFP cooling cannot be maintained below the alarm setpoint(

  • S2.OP-AR.ZZ-0003(Q)

    Salem 2 Page 25 of 57 Rev. 17

    ALARM

    C-2020

    23 CFCUAIRFLO

    TRBL

    DEVICES: N/A

    SETPOINT: N/A

    1.0 CAUSE(S):

    1.1 Roughing Filter Dampers not fully open

    1.2 HEPA Filter Inlet Damper not fully closed

    1.3 HEPA Filter Outlet Damper not fully closed

    2.0 AUTOMATIC ACTION:

    None

    3.0 OPERATOR ACTIONS:

    3.1 IF 23 Containment Fan Coil Unit is operating in low speed,THEN no further action is required.

    3.2 VERIFY positions of 23 Containment Fan Coil Filter Dampers

    on Control Console bezels.

    3.3 IF damper malfunction is indicated,THEN:

    A. STOP 23 Containment Fan Coil Unit.

    B. INITIATE a NOTF IAW LS-AA-120, Issue Identification and Screening Process

    3.4 REFER to Technical Specification 3.6.2.3.

    Page 1 of 1 C-20References: Dwg. 205338, 203576

  • S2.OP-AR.ZZ-0003(Q)

    Salem 2 Page 26 of 57 Rev. 17

    ALARM

    C-2121

    23 CFCUWTRFLO

    TRBL

    DEVICES: N/A

    SETPOINT: N/A 1.0 CAUSE(S):

    Any SW Valve misalignment with the CFCU running:

    ‚ 23SW58, 23 FAN COIL UNIT INLET WATER VALVE not fully OPEN

    ‚ 23SW72, 23 FAN COIL UNIT OUTLET WATER VALVE not fully OPEN

    ‚ 23SW223, 23 FAN COIL UNIT OUTLET WATER FLOW CONTROL VALVE,is CLOSED

    2.0 AUTOMATIC ACTION:

    None

    3.0 OPERATOR ACTIONS:

    3.1 CONFIRM alarm by observing flow indication on 23 CFCU bezel.

    3.2 ENSURE OPEN the following valves:

    A. 23SW58, 23 FAN COIL UNIT INLET WATER VALVE

    B. 23SW72, 23 FAN COIL UNIT OUTLET WATER VALVE

    3.3 IF a valve malfunction is suspected,THEN:

    A. STOP 23 Containment Fan Coil Unit.

    B. INITIATE a NOTF IAW LS-AA-120, Issue Identification and Screening Process

    3.4 REFER to Technical Specification 3.6.2.3.

    Page 1 of 1 C-21 References: Dwg. 205342, 203578

  • S2.OP-AR.ZZ-0003(Q)

    Salem 2 Page 27 of 57 Rev. 17

    ALARM

    C-2222

    CNTMTSPRYACT

    DEVICES: 2PC948A, 2PC948B, 2PC948C, 2PC948G

    SETPOINT: $ 15 psig

    1.0 CAUSE(S):

    1.1 Two out of four Containment pressure channels are $ 15 psig

    1.2 Manual actuation

    2.0 AUTOMATIC ACTION:

    2.1 Containment Spray Valves OPEN

    2.2 Containment Spray Pumps START (if SEC permissives exists)

    2.3 Containment Isolation Phase B

    2.4 Containment Ventilation Isolation (manual signal only)

    2.5 Main Steamline Isolation (automatic signal only)

    3.0 OPERATOR ACTIONS:

    3.1 IF alarm due to testing,THEN no further Operator action required.

    3.2 CONFIRM alarm by verifying coincidence on Panel 2RP4AND Main Control Console indications.

    3.3 GO TO 2-EOP-TRIP-1, Reactor Trip or Safety Injection.

    Page 1 of 1 C-22References: Dwg. 221057

  • S2.OP-AR.ZZ-0003(Q)

    Salem 2 Page 28 of 57 Rev. 17

    ALARM

    C-2323

    CNTMTH2 LVL

    HI

    DEVICES:

    SETPOINT: $ 2% hydrogen

    1.0 CAUSE(S):

    Hydrogen concentration in Containment atmosphere is $ 2%

    2.0 AUTOMATIC ACTION:

    None

    3.0 OPERATOR ACTIONS:

    3.1 IF alarm is due to testing,THEN no further Operator action is required.

    3.2 CONFIRM alarm by observing Control Room charts and H2 monitors (2RP5).

    3.3 IF alarm is valid,THEN:

    A. NOTIFY Chemistry for a confirming sample.

    B. PLACE Recombiner in service IAW S2.OP-SO.CAN-0001(Q),Hydrogen Recombiner Operation.

    C. REFER to Event Classification Guide.

    3.4 REFER to Technical Specifications 3.6.4.1.

    Page 1 of 1 C-23References: Dwg. 252310

  • S2.OP-AR.ZZ-0003(Q)

    Salem 2 Page 29 of 57 Rev. 17

    ALARM

    C-2424

    SPARE

    DEVICES:

    SETPOINT:

    Page 1 of 1 C-24References: Dwg.

  • S2.OP-AR.ZZ-0003(Q)

    Salem 2 Page 30 of 57 Rev. 17

    ALARM

    C-2525

    BA EVAPTRBL

    DEVICES: N/A

    SETPOINT: N/A

    1.0 CAUSE(S):

    An alarm at Panel 301, Gas Stripper & Boron Concentrate Panel

    2.0 AUTOMATIC ACTION:

    None

    3.0 OPERATOR ACTIONS:

    3.1 SEND an Operator to Panel 301-2, Gas Stripper & Boron Concentrate Panel,to perform the following:

    A. DETERMINE cause of the alarm.

    B. INITIATE corrective action.

    Page 1 of 1 C-25References: Dwg. 222875

  • S2.OP-AR.ZZ-0003(Q)

    Salem 2 Page 31 of 57 Rev. 17

    ALARM

    C-2626

    21 RHRSUMP

    OVRFLO

    DEVICES: 2LD7753, 2LD7754

    SETPOINT: $ 42 feet

    1.0 CAUSE(S):

    21 RHR Sump level $ 42 feet

    2.0 AUTOMATIC ACTION:

    None

    3.0 OPERATOR ACTIONS:

    3.1 IF RHR Sump Pumps have not started,THEN VERIFY CLOSED breakers:

    Ë 2CY2AX5A, #21 RHR Sump Pump

    Ë 2BY2AX5A, #22 RHR Sump Pump

    3.2 SEND an Operator to the RHR Pump room and 84 ft elevation to determine source of leak.

    3.3 ESTABLISH conditions required to isolate leak.

    3.4 IF RHR System must be isolated,THEN GO TO one of the following procedures, as applicable:

    Ë S2.OP-AB.RHR-0001(Q), Loss of RHR

    Ë S2.OP-AB.RHR-0002(Q), Loss of RHR At Reduced Inventory

    3.5 REFER to Technical Specifications 3.4.1.3, 3.4.1.4, 3.5.2, 3.5.3, 3.9.8.1, and 3.9.8.2.

    Page 1 of 1 C-26References: Dwg. 205326, 231035

  • S2.OP-AR.ZZ-0003(Q)

    Salem 2 Page 32 of 57 Rev. 17

    ALARM

    C-2727

    SFPLVLHI

    DEVICES: 2LC650

    SETPOINT: $ 129 feet 2 inches

    1.0 CAUSE(S):

    Pool level $ 129 feet 2 inches

    2.0 AUTOMATIC ACTION:

    None

    3.0 OPERATOR ACTIONS:

    3.1 IF alarm due to testing,THEN no further action required.

    3.2 SEND Operator to confirm that a high level exists in the Spent Fuel Pool.

    3.3 ENSURE CLOSED the following makeup valves:

    A. 2SF44, PRIMARY WATER MAKEUP VALVE

    B. 2SF58, DEMIN WATER MAKEUP

    C. 2SF71, SPENT FUEL PIT FILL FROM HUT

    3.4 IF alarm due to Cross-Connect Operations,THEN MONITOR level closely to prevent overfill of Spent Fuel Pool.

    3.5 REDUCE level in Spent Fuel Pool to clear alarm IAW S2.OP-SO.SF-0001(Q),Fill and Transfer of the Spent Fuel Pool.

    3.6 IF a failed instrument is indicated,THEN INITIATE a NOTF IAW LS-AA-120, Issue Identification and Screening Process

    Page 1 of 1 C-27References: Dwg. 205333, 231100

  • S2.OP-AR.ZZ-0003(Q)

    Salem 2 Page 33 of 57 Rev. 17

    ALARM

    C-2828

    24 CFCUAIRFLO

    TRBL

    DEVICES: N/A

    SETPOINT: N/A

    1.0 CAUSE(S):

    1.1 Roughing Filter Dampers not fully OPEN

    1.2 HEPA Filter Inlet Damper not fully CLOSED

    1.3 HEPA Filter Outlet Damper not fully CLOSED

    2.0 AUTOMATIC ACTION:

    None

    3.0 OPERATOR ACTIONS:

    3.1 IF 24 Containment Fan Coil Unit is operating in low speed,THEN no further Operator action is required.

    3.2 VERIFY positions of 24 Containment Fan Coil Filter Dampers

    on Control Console bezels.

    3.3 IF damper malfunction is indicated,THEN:

    A. STOP 24 Containment Fan Coil Unit.

    B. INITIATE a NOTF IAW LS-AA-120, Issue Identification and Screening Process

    3.4 REFER to Technical Specification 3.6.2.3.

    Page 1 of 1 C-28References: Dwg. 205338, 203580

  • S2.OP-AR.ZZ-0003(Q)

    Salem 2 Page 34 of 57 Rev. 17

    ALARM

    C-2929

    24 CFCUWTRFLO

    TRBL

    DEVICES: N/A

    SETPOINT: N/A

    1.0 CAUSE(S):

    Any SW Valve misalignment with the CFCU running:

    ‚ 24SW58, 24 FAN COIL UNIT INLET WATER VALVE not fully OPEN

    ‚ 24SW72, 24 FAN COIL UNIT OUTLET WATER VALVE not fully OPEN

    ‚ 24SW223, 24 FAN COIL UNIT OUTLET WATER FLOW CONTROL VALVE,is CLOSED

    2.0 AUTOMATIC ACTION:

    None

    3.0 OPERATOR ACTIONS:

    3.1 CONFIRM alarm by observing flow indication on 24 CFCU bezel.

    3.2 OPEN the following valves:

    A. 24SW58, 24 FAN COIL UNIT INLET WATER VALVE

    B. 24SW72, 24 FAN COIL UNIT OUTLET WATER VALVE

    3.3 IF a valve malfunction is suspected,THEN:

    A. STOP 24 Containment Fan Coil Unit.

    B. INITIATE a NOTF IAW LS-AA-120, Issue Identification and Screening Process

    3.4 REFER to Technical Specification 3.6.2.3.

    Page 1 of 1 C-29References: Dwg. 205342, 203582

  • S2.OP-AR.ZZ-0003(Q)

    Salem 2 Page 35 of 57 Rev. 17

    ALARM

    C-3030

    CFCULK DET

    HI-HIM

    DEVICES: 2LT730, 2LT731, 2LT732, 2LT733, 2LT734

    SETPOINT: $ 15.2 feet of water

    1.0 CAUSE(S):

    Leak detector level $ 15.2 feet of water

    2.0 AUTOMATIC ACTION:

    None

    3.0 OPERATOR ACTIONS:

    3.1 DETERMINE which CFCU is causing the alarm from the Annunciator CRT:

    CRT Point Description

    497 CONTAINMENT FAN COIL UNIT 21LEAK DETECTOR HIGH-HIGH

    498 CONTAINMENT FAN COIL UNIT 22LEAK DETECTOR HIGH-HIGH

    499 CONTAINMENT FAN COIL UNIT 23LEAK DETECTOR HIGH-HIGH

    500 CONTAINMENT FAN COIL UNIT 24LEAK DETECTOR HIGH-HIGH

    501 CONTAINMENT FAN COIL UNIT 25LEAK DETECTOR HIGH-HIGH

    (Continued)

    Page 1 of 2 C-30

  • S2.OP-AR.ZZ-0003(Q)

    Salem 2 Page 36 of 57 Rev. 17

    3.2 ENSURE OPEN 21-25WD50, CFCU CONDENSATE SHUTOFF, at 2RP1.

    3.3 IF there is indication of leakage other than Service Water,THEN INITIATE a leakrate IAW S2.OP-SO.RC-0004(Q),Identifying and Measuring Leakage.

    3.4 IF there is indication of a Service Water leak,THEN:

    A. STOP the affected CFCU.

    CAUTION

    Isolating a CFCU from the control room with the SW58 and SW72 valves also isolatesSW overpressure protection for the CFCU. These valves should only be used whenthere is a SW leak requiring immediate isolation.

    B. ISOLATE the affected CFCU IAW S2.OP-SO.SW-0005(Q),Service Water System Operation.

    C. INITIATE a NOTF IAW LS-AA-120, Issue Identification and Screening Process.

    3.5 REFER to Technical Specification 3.6.1.1 and 3.6.2.3.

    Page 2 of 2 C-30Reference Dwg. 205327, 220061, 240690

  • S2.OP-AR.ZZ-0003(Q)

    Salem 2 Page 37 of 57 Rev. 17

    ALARM

    C-3131

    DEVICES:

    SETPOINT:

    SPARE

    Page 1 of 1 C-31References: Dwg.

  • S2.OP-AR.ZZ-0003(Q)

    Salem 2 Page 38 of 57 Rev. 17

    ALARM

    C-3232

    DEVICES:

    SETPOINT:

    SPARE

    Page 1 of 1 C-32References: Dwg.

  • S2.OP-AR.ZZ-0003(Q)

    Salem 2 Page 39 of 57 Rev. 17

    ALARM

    C-3333

    RWST/PWSTOVRFLO

    DEVICES: 1LD8040

    SETPOINT: N/A

    1.0 CAUSE(S):

    1.1 Overflow from Unit 1 RWST or PWST

    1.2 Overflow from Unit 2 RWST or PWST

    2.0 AUTOMATIC ACTIONS:

    None

    3.0 OPERATOR ACTIONS:

    3.1 DETERMINE which tank causing alarm.

    A. STOP MAKEUP to affected tank.

    B. SEND an operator to drain the dike area around 13 CVCS HUT as follows:.

    1. Throttle OPEN 1WD7, 13 CVCS HUT DIKE DRAIN VALVE.

    2. MONITOR Auxiliary Building Sump Tank level.

    3. WHEN draining is completed,THEN CLOSE 1WD7, 13 CVCS HUT DIKE DRAIN VALVE.

    3.2 WHEN dike is drained and affected tank level restored,THEN:

    A. ESTABLISH communications with the control room.

    B. Throttle OPEN 1WD54, RWST & PWST TO WHT DRN VALVE, to drain level detector 1LD8040 AND clear alarm.

    Page 1 of 1 C-33References: Dwg. 205234

  • S2.OP-AR.ZZ-0003(Q)

    Salem 2 Page 40 of 57 Rev. 17

    ALARM

    C-3434

    22 RHRSUMP

    OVRFLO

    DEVICES: 2LD7755, 2LD7756

    SETPOINT: $ 42 feet

    1.0 CAUSE(S):

    22 RHR Sump level $ 42 feet

    2.0 AUTOMATIC ACTION:

    None

    3.0 OPERATOR ACTIONS:

    3.1 IF RHR Sump Pumps have not started,THEN VERIFY CLOSED breakers:

    Ë 2CY2AX6A, #23 RHR Sump Pump

    Ë 2BY2AX6A, #24 RHR Sump Pump

    3.2 SEND Operator to RHR Pump room and 84 ft elevation to determine source of leak.

    3.3 ESTABLISH conditions required to isolate leak.

    3.4 IF RHR System must be isolated,THEN GO TO one of the following procedures, as applicable:

    Ë S2.OP-AB.RHR-0001(Q), Loss of RHR

    Ë S2.OP-AB.RHR-0002(Q), Loss of RHR At Reduced Inventory

    3.5 REFER to Technical Specifications 3.4.1.3, 3.4.1.4, 3.5.2, 3.5.3, 3.9.8.1, and 3.9.8.2.

    Page 1 of 1 C-34References: Dwg. 205326, 231036

  • S2.OP-AR.ZZ-0003(Q)

    Salem 2 Page 41 of 57 Rev. 17

    ALARM

    C-3535

    SFPLVLLO

    DEVICES: 2LC650

    SETPOINT: # 128 feet 2 inches

    1.0 CAUSE(S):

    Spent Fuel Pit level is # 128 feet 2 inches

    2.0 AUTOMATIC ACTION:

    None

    3.0 OPERATOR ACTIONS:

    3.1 IF alarm is due to testing,THEN no further Operator action is required.

    3.2 IF in Modes 1-5,THEN:

    A. CONFIRM the alarm.

    B. DETERMINE source of the leak.

    C. INITIATE makeup to Spent Fuel Pit IAW S2.OP-SO.SF-0001(Q), Fill and Transfer of the Spent Fuel Pool.

    3.3 IF in Mode 6,THEN:

    A. SEND Operator to confirm the alarm.

    B. IF Spent Fuel Pool level is decreasing,THEN GO TO S2.OP-AB.FUEL-0002(Q),Loss of Refueling Cavity or Spent Fuel Pool Level.

    Page 1 of 1 C-35References: Dwg. 205333, 231100

  • S2.OP-AR.ZZ-0003(Q)

    Salem 2 Page 42 of 57 Rev. 17

    ALARM

    C-3636

    25 CFCUAIRFLO

    TRBL

    DEVICES: N/A

    SETPOINT: N/A

    1.0 CAUSE(S):

    1.1 Roughing Filter Dampers not fully OPEN

    1.2 HEPA Filter Inlet Damper not fully CLOSED

    1.3 HEPA Filter Outlet Damper not fully CLOSED

    2.0 AUTOMATIC ACTION:

    None

    3.0 OPERATOR ACTIONS:

    3.1 IF 25 Containment Fan Coil Unit is operating in low speed,THEN no further Operator action is required.

    3.2 ENSURE positions of 25 Containment Fan Coil Filter Dampers

    on Control Console bezels.

    3.3 IF damper malfunction is indicated,THEN:

    A. STOP 25 Containment Fan Coil Unit.

    B. INITIATE a NOTF IAW LS-AA-120, Issue Identification and Screening Process

    3.4 REFER to Technical Specification 3.6.2.3.

    Page 1 of 1 C-36References: Dwg. 205338, 203584

  • S2.OP-AR.ZZ-0003(Q)

    Salem 2 Page 43 of 57 Rev. 17

    ALARM

    C-3737

    25 CFCUWTRFLO

    TRBL

    DEVICES: N/A

    SETPOINT: N/A

    1.0 CAUSE(S):

    Any SW Valve misaligned with the CFCU running:

    ‚ 25SW58, 25 FAN COIL UNIT INLET WATER VALVE not fully OPEN

    ‚ 25SW72, 25 FAN COIL UNIT OUTLET WATER VALVE not fully OPEN

    ‚ 25SW223, 25 FAN COIL UNIT OUTLET WATER FLOW CONTROL VALVE,is CLOSED

    2.0 AUTOMATIC ACTION:

    None

    3.0 OPERATOR ACTIONS:

    3.1 CONFIRM alarm by observing flow indication on 25 CFCU bezel.

    3.2 ENSURE OPEN the following valves:

    A. 25SW58, 25 FAN COIL UNIT INLET WATER VALVE

    B. 25SW72, 25 FAN COIL UNIT OUTLET WATER VALVE

    3.3 IF a valve malfunction is suspected,THEN:

    A. STOP 25 Containment Fan Coil Unit.

    B. INITIATE a NOTF IAW LS-AA-120, Issue Identification and Screening Process

    3.4 REFER to Technical Specification 3.6.2.3.

    Page 1 of 1 C-37References: Dwg. 205342, 203586

  • S2.OP-AR.ZZ-0003(Q)

    Salem 2 Page 44 of 57 Rev. 17

    ALARM

    C-3838

    CFCULK DET

    HIM

    DEVICES: 2LT730, 2LT731, 2LT732, 2LT733, 2LT734

    SETPOINT: $ 0.8 feet of water

    1.0 CAUSE(S):

    Any Containment Fan Coil Unit leak detector level $ 0.8 feet of water

    2.0 AUTOMATIC ACTION:

    None

    3.0 OPERATOR ACTIONS:

    3.1 DETERMINE which CFCU is causing the alarm from the Annunciator CRT:

    CRT Point Description

    492 CONTAINMENT FAN COIL UNIT 21 LEAK DETECTOR HIGH

    493 CONTAINMENT FAN COIL UNIT 22 LEAK DETECTOR HIGH

    494 CONTAINMENT FAN COIL UNIT 23 LEAK DETECTOR HIGH

    495 CONTAINMENT FAN COIL UNIT 24 LEAK DETECTOR HIGH

    496 CONTAINMENT FAN COIL UNIT 25 LEAK DETECTOR HIGH

    (Continued)

    Page 1 of 2 C-38

  • S2.OP-AR.ZZ-0003(Q)

    Salem 2 Page 45 of 57 Rev. 17

    3.2 ENSURE OPEN 21-25WD50, CFCU CONDENSATE SHUTOFF, at 2RP1.

    3.3 IF the alarm is due to suspected clogging of the drain line,THEN:

    A. SELECT the CFCU for LEAK DETECTION indication (LI730) at 2CC1.

    B. CLOSE the associated WD50 valve at 2RP1.

    C. WAIT until the LEAK DETECTION indication (LI730) at 2CC1 is at a maximum value to facilitate flushing any sediment from the drain line.

    D. OPEN the associated WD50 valve at 2RP1.

    E. IF the alarm condition does NOT clear,THEN INITIATE an NOTF IAW LS-AA-120, Issue Identification and Screening Process.

    3.4 IF there is indication of leakage other than Service Water,THEN INITIATE leakrate IAW S2.OP-SO.RC-0004(Q),Identifying and Measuring Leakage.

    3.5 IF there is indication of Service Water leakage,THEN:

    A. STOP the affected CFCU.

    CAUTION Isolating a CFCU from the control room with the SW58 and SW72 valves also isolatesSW overpressure protection for the CFCU. These valves should only be used whenthere is a SW leak requiring immediate isolation.

    B. ISOLATE the affected CFCU IAW S2.OP-SO.SW-0005(Q),Service Water System Operation.

    C. INITIATE a NOTF IAW LS-AA-120, Issue Identification

    and Screening Process.

    D. INITIATE SC.OP-DG.SW-0005, Service Water Spill Response in Containment. *

    3.6 REFER to Technical Specification 3.6.1.1 and 3.6.2.3.

    Page 2 of 2 C-38References Dwg. 205327, 220061, 240690

  • S2.OP-AR.ZZ-0003(Q)

    Salem 2 Page 46 of 57 Rev. 17

    ALARM

    C-3939

    DEVICES:

    SETPOINT:

    SPARE

    Page 1 of 1 C-39References: Dwg.

  • S2.OP-AR.ZZ-0003(Q)

    Salem 2 Page 47 of 57 Rev. 17

    ALARM

    C-4040

    DEVICES:

    SETPOINT:

    SPARE

    Page 1 of 1 C-40References: Dwg.

  • S2.OP-AR.ZZ-0003(Q)

    Salem 2 Page 48 of 57 Rev. 17

    ALARM

    C-4141

    DEVICES:

    SETPOINT:

    SPARE

    Page 1 of 1 C-41References:

  • S2.OP-AR.ZZ-0003(Q)

    Salem 2 Page 49 of 57 Rev. 17

    ALARM

    C-4242

    DEVICES:

    SETPOINT:

    SPARE

    Page 1 of 1 C-42References: Dwg.

  • S2.OP-AR.ZZ-0003(Q)

    Salem 2 Page 50 of 57 Rev. 17

    ALARM

    C-4343

    DEVICES:

    SETPOINT:

    SPARE

    Page 1 of 1 C-43References: Dwg.

  • S2.OP-AR.ZZ-0003(Q)

    Salem 2 Page 51 of 57 Rev. 17

    ALARM

    C-4444

    DEVICES:

    SETPOINT:

    SPARE

    Page 1 of 1 C-44References: Dwg.

  • S2.OP-AR.ZZ-0003(Q)

    Salem 2 Page 52 of 57 Rev. 17

    ALARM

    C-4545

    DEVICES:

    SETPOINT:

    SPARE

    Page 1 of 1 C-45References: Dwg.

  • S2.OP-AR.ZZ-0003(Q)

    Salem 2 Page 53 of 57 Rev. 17

    ALARM

    C-46

    46

    PERSONNELACCESS

    DOOR OPEN

    DEVICES: N/A

    SETPOINT: N/A

    1.0 CAUSE(S):

    Any personnel airlock in use to or from Containment at the locations listed:

    ‚ Elevation 100

    ‚ Elevation 130

    2.0 AUTOMATIC ACTION:

    None

    3.0 OPERATOR ACTIONS:

    3.1 IF an authorized Containment entry is being made,THEN:

    A. RECORD Containment Airlocks and Loose Debris Inspection informationIAW S2.OP-DL.ZZ-0001(Q), Control Room Logs.

    B. No further action required.

    3.2 SEND Operator to ENSURE CLOSED airlock door(s).

    3.3 IF unable to clear alarm,THEN:

    A. REFER to Technical Specification 3.6.1.3.

    B. INITIATE a NOTF IAW LS-AA-120, Issue Identification and Screening Process

    C. PERFORM S2.OP-ST.CAN-0004(Q),Containment Air Lock Local Leak Rate Test.

    Page 1 of 1 C-46References: Dwg. 231096

  • S2.OP-AR.ZZ-0003(Q)

    Salem 2 Page 54 of 57 Rev. 17

    ALARM

    C-4747

    DEVICES:

    SETPOINT:

    SPARE

    Page 1 of 1 C-47References: Dwg.

  • S2.OP-AR.ZZ-0003(Q)

    Salem 2 Page 55 of 57 Rev. 17

    ALARM

    C-4848

    DEVICES:

    SETPOINT:

    SPARE

    Page 1 of 1 C-48References: Dwg.

  • S2.OP-AR.ZZ-0003(Q)

    Salem 2 Page 56 of 57 Rev. 17

    OVERHEAD ANNUNCIATORS WINDOW C

    REFERENCES

    1.0 Plant Documents:

    ‚ Technical Specifications Unit 2‚ Event Classification Guide

    2.0 Commitments:

    C0551, LER 272/94-013-00

    3.0 Procedures:

    None

    4.0 PSBPs:

    None

    5.0 Other:

    ‚ 2EC-3228, Provide reflash capability to C-1 window‚ ECA 80004565, OHA C-24 CBV ISOL SIGNAL PRESENT spared‚ INPO SER 40-86, Spent Fuel Pool Leakage‚ 2EC-1707A, Reset setpoint of LS-2067‚ MM S97-0095, Hydrogen Recombiner HI-KW Alarm Relay Removal‚ S-C-SF-MDC-1800, Decay Heatup Rates and Curves

    6.0 Cross-References:

    ‚ 2-EOP-TRIP-1, Reactor Trip or Safety Injection‚ S2.OP-AB.CC-0001(Q), Component Cooling Abnormality‚ S2.OP-AB.FUEL-0002(Q), Loss of Refueling Cavity or Spent Fuel Pool Level‚ S2.OP-AB.RC-0001(Q), Reactor Coolant System Leak.‚ S2.OP-AB.RCP-0001(Q), RCP Abnormality‚ S2.OP-AB.RHR-0001(Q), Loss of RHR‚ S2.OP-AB.RHR-0002(Q), Loss of RHR At Reduced Inventory‚ S2.OP-AB.SF-0001(Q), Loss of Spent Fuel Pool Cooling‚ S2.OP-AB.SW-0001(Q), Loss of Service Water Header Pressure‚ S2.OP-AR.WG-0001(Q), Waste Disposal Gas Analyzer PNL 110‚ S2.OP-SO.RC-0004(Q), Identifying and Measuring Leakage‚ S2.OP-SO.RPS-0005(Q), Placing Containment Pressure Channel In Tripped Condition‚ S2.OP-SO.SF-0001(Q), Filling the Spent Fuel Pool‚ S2.OP-ST.CAN-0004(Q), Containment Air Lock Local Leak Rate Test

  • S2.OP-AR.ZZ-0003(Q)

    Salem 2 Page 57 of 57 Rev. 17

    7.0 Drawings:

    ‚ 203568, No. 1 & 2 Units-Containment Ventilation No.11 & 21 Fan-Coil Units‚ 203570, No. 1 & 2 Units-Containment Ventilation No.11 & 21 Fan-Coil Units‚ 203572, No. 1 & 2 Units-Containment Ventilation No.12 & 22 Fan-Coil Units‚ 203574, No. 1 & 2 Units-Containment Ventilation No.12 & 22 Fan-Coil Units‚ 203576, No. 1 & 2 Units-Containment Ventilation No.13 & 23 Fan-Coil Units‚ 203578, No. 1 & 2 Units-Containment Ventilation No.13 & 23 Fan-Coil Units‚ 203580, No. 1 & 2 Units-Containment Ventilation No.14 & 24 Fan-Coil Units‚ 203582, No. 1 & 2 Units-Containment Ventilation No.14 & 24 Fan-Coil Units‚ 203584, No. 1 & 2 Units-Containment Ventilation No.15 & 25 Fan-Coil Units‚ 203586, No. 1 & 2 Units-Containment Ventilation No.15 & 25 Fan-Coil Units‚ 203653, No. 1 & 2 Units-Containment Ventilation No.11 & 21 Hydrogen Recombiners‚ 203654, No. 1 & 2 Units-Containment Ventilation No.12 & 22 Hydrogen Recombiners‚ 203683, No. 1 & 2 Units-Waste Disposal System Gas Analyzer Panel 110‚ 205234, No. 1 Unit Safety Injection‚ 205326, No. 2 Unit Floor Drains Contaminated‚ 205327, No. 2 Unit Equipment Vents & Drains-Contaminated‚ 205329, No. 2 Unit-Chemical & Volume Control Boric Acid Recovery‚ 205331, No. 2 Unit Component Cooling‚ 205333, No. 2 Unit Spent Fuel Cooling‚ 205338, No. 2 Unit Reactor Containment-Ventilation‚ 205342, No. 2 Unit Service Water Nuclear Header‚ 211514, No. 1 & 2 Units-RHR Sys. Containment Sump Level LT-939‚ 211522, No. 1 & 2 Units-CC System Surge Tank, No.11&21 CC Hdr Press Alarms‚ 211523, No. 1 & 2 Units-CC System Surge Tank, No.12&22 CC Hdr Press Alarms‚ 217142, No. 1 & 2 Units-Safety Injection System Spray Additive Tk & RWST Level Alarms‚ 220061, No. 1 & 2 Units Reactor Prot. & Process Cont. Systems Leak Detection‚ 220972, No. 1 & 2 Units-Reactor Containment Reactor & Containment Sump Pumps‚ 221057, No. 1 & 2 Units Reactor Protection System Safeguards Actuation Signals‚ 222875, No. 1 & 2 Units-CVCS Gas Stripper & Boron Control Panel No.301‚ 226513, No. 1 & 2 Units-Aux. Building 64 Waste Disposal-Boron Recycle Panel 104‚ 227977, No. 1 & 2 Units-Control Room Area SSPS System Train A Interface Cab.32‚ 231035, No. 1 & 2 Units-Auxiliary Building RHR No.11 & 12 Sump Pumps‚ 231036, No. 1 & 2 Units-Auxiliary Building RHR No.13 & 14 Sump Pumps‚ 231096, No. 1 & 2 Units- Cont Area Personnel Access Hatch indication & Alarms‚ 231100, No. 1 & 2 Units-Spent Fuel Pit Cooling Spent Fuel Pit Level & Temperature‚ 232015, No. 1 & 2 Units-Control Room Area SSPS System Train A Output Test‚ 232016, No. 1 & 2 Units-Control Room Area SSPS Train A Output Test‚ 240690, No. 2 Unit Equipment Vents & Drains Contaminated‚ 240698, No. 2 Unit Sump and Flood Pumps-Contaminated‚ 252310, No. 1 & 2 Units-Containment Ventilation Hydrogen Monitoring System