Description Qty. (Nos) Voltage Rating (KW) Diversity factor Demand factor Induced draft fan motor 6 3.3 KV 430 2.0 80% Forced draft fan motor 6 3.3 KV 270 2.0 80% Cooling tower pump motor 4 3.3 KV 335 2.0 80% Boiler feed pump motor 2 3.3 KV 1800 2.0 80% Total HT Load(KW) Description Qty. (Nos) Voltage Rating (KW) Diversity factor Demand factor Makeup water pump motor 3 415 V 90 1.5 80% Air compressor motor 3 415 V 115 1.5 70% Air heater 2 415 V 30 1 90% Auxiliary water pump 2 415 V 75 1.5 80% CT fan motor 4 415 V 45 1 60% Condensate extraction pump 4 415 V 22 2 80% Chiller compressor 3 415 V 55 1.5 80% Air handling unit 3 415 V 45 1.5 80% Auxiliary oil pump 2 415 V 22 2 70% Air handling, cooling tower, and miscellaneous other load 6 415 V 17 2 80% NGL firing pump 6 415 V 55 3 70% NGL unloading pump 2 415 V 7.5 1.5 50% Lighting, UPS and miscellaneous others - 415V 15 1.8 I 80% Total LT Load (KW) The Loads of Industry are given in a Table Above. Find 1)The Capacity of Transformer Required 2)Fault current at 3.3 kV Bus and 0.415 kV Bus. The Primary of Transformer is supplied by 11 kV Bus. The Fault level at 11 kV is 750 MVA 3)Select CB/Fuse 4)Select Cables for 5% Regulation 5)Economic evaluation of Transformer

PSA Mini Project

Embed Size (px)

DESCRIPTION

1

Citation preview

DescriptionQty. (Nos)VoltageRating (KW)Diversity factorDemand factor

Induced draft fan motor63.3 KV4302.080%

Forced draft fan motor63.3 KV2702.080%

Cooling tower pump motor43.3 KV3352.080%

Boiler feed pump motor23.3 KV18002.080%

Total HT Load(KW)

DescriptionQty. (Nos)VoltageRating (KW)Diversity factorDemand factor

Makeup water pump motor3415 V901.580%

Air compressor motor3415 V1151.570%

Air heater2415 V30190%

Auxiliary water pump2415 V751.580%

CT fan motor4415 V45160%

Condensate extraction pump4415 V22280%

Chiller compressor3415 V551.580%

Air handling unit3415 V451.580%

Auxiliary oil pump2415 V22270%

Air handling, cooling tower, and miscellaneous other load6415 V17280%

NGL firing pump6415 V55370%

NGL unloading pump2415 V7.51.550%

Lighting, UPS and miscellaneous others-415V151.8I 80%

Total LT Load (KW)

The Loads of Industry are given in a Table Above. Find1)The Capacity of Transformer Required2)Fault current at 3.3 kV Bus and 0.415 kV Bus. The Primary of Transformer is supplied by 11 kV Bus. The Fault level at 11 kV is 750 MVA3)Select CB/Fuse 4)Select Cables for 5% Regulation5)Economic evaluation of Transformer

It is required to calculate the load for the residential as well as commercial set-up. There are two ways to accomplish the above task. One is to calculate the load as per the number of points provided, and the other is calculation of load based on covered area. In addition to the above, the housing complex has got two number of lifts in each block, area lighting, fire and drinking water pumps. The details are given belowFind Capacity of Transformer

Draw a single line diagram

Find cable sizes for 5% regulation

SISL Description No.No. of housesArea (sq. metre)5A socket (Nos)15A socket (Nos)40W lamp (Nos)Ceiling fan (Nos)100W lamp (Nos)Exhaust fan (Nos)

1BLOCK-1

Type-114801257541

Type-21410015710752

2 BLOCK-2

Type-31812518911953

Type-4181502011121063

3 BLOCK-3

Type-5121752213151283

Table 1.5

Sl.No. DescriptionQty (Nos)Rating (KW)

1Lifts (8 Passengers)65

2Fire pumps120

3Drinking water pumps210

4Common area lighting450.055

55. Street lighting250.15

The housing complex also has a commercial complex. The load details are given in Table 1.6.

Table 1.6

SL NO Description Nos. Area (sq. No. metre)5 A socket (Nos)15 A socket (Nos)40 W lamp (Nos)Ceiling fan(Nos)100 W lamp (Nos) Exhaust fan (Nos)

1Super market 1 125112520152510151

2Office rooms 5 1551512520550

3Shops 5 105101510101050

4Restaurant 1 100110015122012104

DescriptionQty. (Nos)VoltageRating (KW)Diversity factorDemand factor

Induced draft fan motor63.3 KV4302.080%

Forced draft fan motor63.3 KV2702.080%

Cooling tower pump motor43.3 KV3352.080%

Boiler feed pump motor23.3 KV18002.080%

Total HT Load(KW)

DescriptionQty. (Nos)VoltageRating (KW)Diversity factorDemand factor

Makeup water pump motor3415 V901.580%

Air compressor motor3415 V1151.570%

Air heater2415 V30190%

Auxiliary water pump2415 V751.580%

CT fan motor4415 V45160%

Condensate extraction pump4415 V22280%

Chiller compressor3415 V551.580%

Air handling unit3415 V451.580%

Auxiliary oil pump2415 V22270%

Air handling, cooling tower, and miscellaneous other load6415 V17280%

NGL firing pump6415 V55370%

NGL unloading pump2415 V7.51.550%

Lighting, UPS and miscellaneous others-415V151.8I 80%

Total LT Load (KW)