— A B B G R I D EDG E SO LUTI O NS
PS1000 utility-grade power conversion systemUp to 1250 VDC; scalable to three MW
With world-class power density
and an easy-to-install design,
your energy storage system will
be commissioned quickly and
easily. The energy storage power
conversion system (PCS) has never
been more flexible or straightforward.
ABB’s e-mesh™ ecosystem of solutions and products ensure power reliability and availability, grid stability, and the integration of renewable energy enabled by advanced automation technology.
The ABB PowerStore™ PS1000 480Vac scalable platform was specifically developed to offer a straightfor-ward and simple solution to developers of utility-grade energy storage systems. In ~1 MW blocks, the PS1000 offers a single modular system that is tailored to all application sizes. The scalable power conversion system also boasts high-performance controls and system redundancy.
—01 Power Conversion System
Return on investment• More than 98% efficiency • Low installation & commissioning costs • Modular 1 MW blocks • Monetizable dynamic performance
Modular / flexible configuration • 1 MW blocks, up to 1250 VDC • Configurable up to 3 MW
(See picture above)• Individual AC connections or
combined throat
Simple O&M–easily maintainable • Modular design with low
component count • Extended warranty available
Easily transportable • Standard freight =
low transportation cost • Movable with pallet jack or standard
forklift • No crane required • Separable building blocks
Advanced technology• Fully parameterizable grid support • Certified to global standards and grid
codes • ZVRT(1) / LVRT(2) / 4-quadrant high
bandwidth control• ABB proprietary VGM(3) & GSM(4)
functionalities with full integration of e-meshTM control & SCADA
2 P S10 0 0 4 8 0VAC U TI L IT Y- G R A D E P OW ER CO N V ER SI O N S Y S TEM
Model PS1000 480Vac
LINEUP QTY 1 … 3
AC AC port configuration 3-wire (3P3W)
AC voltages 360-400-440-480- 520 VRMS ±10%. Others on request
AC export capacity @ 40°C 1203ARMS 3609ARMS
AC export capacity @ 45°C 1150 ARMS 3450 ARMS
AC import capacity @ 40°C 1203ARMS 3609ARMS
AC import capacity @ 45°C 1150 ARMS 3450 ARMS
AC import / export power see charts
Converter Type 22-Level VSC (5) / CSI (6)
Nominal frequency 50 – 60 Hz
Harmonic distortion <2% TDDi per IEEE 519
Power factor/reactive power 0 leading … 0 lagging (full 4-quadrant operation)
Aux power consumption (Including ext. Cooling pump + Fan)
1500 W 6000 W
Efficiency: Max | CEC | Euro 98.6% (est.) >98% (est.) >98% (est.)
DC DC voltage range at nominal AC voltage (7) 600 - 1250 VDC
DC voltage range at 110% nominal AC voltage (8) 750-1250 VDC
Maximum DC current 1386 ADC 4258 ADC
Battery technology all battery types, fuel cells, other DC sources, etc.
Number of DC inputs 1 … 3
Enviromental Ambient temperature (operation) -20°C to 50°C
Ambient temperature (storage) -20°C to 60°C
Protection degree NEMA 3R/IP54
Relative humidity 5% - 100% condensing
Max elevation 2000 m [6500 ft.]
Airborne noise <75 dBA @ 5 m
Temperature de-rating Automatic; see charts below
Cabinet Maximum dimensions (H x W x D)mm: [2275x1004x1200]
in.: [89.6x39.5x47.2]mm: 3 x [2275x4931x1200]
in.: 3 x [89.6 x 194 x 47.2]
Weight ( est.) 1043 kg [2300 lb.] 3 x 1043 kg [3 x 2300 lb.]
Mounting Pad mounted
Cooling Hybrid liquid /air
Cooling fluid 30% - 50% EWG (9) or PWG (10)
Certification Safety UL 1741 | C22.2 No.107.1-16 & CE mark
(pending) Utility interconnect UL 1741:2010 R2.18 (SA) | IEEE 1547.1-2005 | CA Rule 21 No.16-06-052Hawaii Rule 14 No. 2014-0192
EU Grid codes: DE, FR, SE, PT & IT. Others on request.
Protections AC protection fuses
DC protection fuses (optional)
Humidity Internal cabinet heating
Safety features overvoltage, overcurrent, overtemperature
Ground fault detection optional
Control Control interface CAN, Modbus RS 485, or Modbus TCP
Basic control modes
Grid Following (On Grid) control modes External PQ (power) / DQ (Current) / Cos Phi (pf) references
Grid Connected / Off grid transition Seamless transition in both directions available for PQ control
Grid Forming (Off grid) control modes External PQ references
Black Start Capable Yes, includes DC pre-charge. Requires external auxiliary control power
Extended control modes
Grid Following control modes External f & V references for ABB’s GSM (4) primary control functionalities:− Fast Voltage & Frequency support based on droops & dead band
− Virtual Inertia
Grid Forming – Following transitions Seamless transition from VGM to GSM in grid connected and island
P S10 0 0 4 8 0VAC U TI L IT Y- G R A D E P OW ER CO N V ER SI O N S Y S TEM 3
[1] ZVRT: Zero Voltage Ride Through[2] LVRT: Low Voltage Ride Through[3] VGM: Virtual Generator Mode[4] GSM: Grid Support Mode[5] VSC: Voltage Source Converter[6] CSI: Current Source Inverter[7] DC voltage at nominal AC line voltage for 480Vac[8] Minimum DC voltage at nominal AC line voltage for 1.1 x 480Vac[9] EGW: Ethylene Glycol and Water[10] PGW: Propylene Glycol and Water
Model PS1000 480Vac
Grid Forming control modes External f & V references for ABB’s VGM (3) primary control functionalities:− Droop control with dead band
− Synthetic Inertia & Synthetic impedance− Current limiting during faults and inrush
Fully integrated with ABB’s e-meshTM secondary control
Auxiliary Control power options PCS 208 – 240 VAC | DC: 24 VDC
supply Auxiliary power cooling unit 480 VAC 3P3W
Full-function, independent blocksEach PS1000 contains fully independent AC & DC disconnects, fuses, utility-grade surge suppression, environmental con-trols, recharge, enabling an easy installation.
Keep the transformer simple, pleaseWhen connection several PS1000 in parallel internal busbar connection allows simple AC parallel connection and simplifies the coupling transformer connection. Note that each 1 MW block is designed to support connections to independent battery banks.
The MV transformer can be provided by ABB with pre-engineered units to suit your application’s power and voltage needs.
AC power charts versus temperature for different LV AC voltages:
A
B
C
D
123456
123456
A
B
C
D
2 / 52:25SHEETWEIGHTSCALE
D0485-100180BREVDRAWING NUMBERSIZE
CAB1000/AC LAYOUT DRAWING
TITLE
EPC POWER CORPORATION 13250 GREGG STREET, SUITE A-2 POWAY, CALIFORNIA 92064 1.858.748.5590
AC DISCONNECT SWITCH
DC DISCONNECT SWITCH
FUSE ACCESS WINDOW
DEAD FRONT
PEDESTAL ACCESS PANEL
CONTROLS DINRAIL PANEL
FRONT DOOR OPEN
REAR DOOR OPEN
AIR TO LIQUIDHEAT EXCHANGER
INTAKE BAFFLE
MAGNETICS
COOLING SKID ACCESS PANEL
A
B
C
D
123456
123456
A
B
C
D
5X 219.1 ENCLOSURE FRONT TO TERMINAL[8.6]
3X 599.1 AC TERMINAL[23.6]
2X 734 DC TERMINAL[28.9]
3 / 52:25 SHEETWEIGHTSCALE
D0485-100180BREVDRAWING NUMBERSIZE
CAB1000/AC LAYOUT DRAWING
TITLE
EPC POWER CORPORATION 13250 GREGG STREET, SUITE A-2 POWAY, CALIFORNIA 92064 1.858.748.5590
POWER STAGE
CAPACITOR BANK
FILTER FAN ASSEMBLY
SURGE PROTECTIVE DEVICE
AC FUSE
DC FUSE
GROUND BAR
COOLING PUMP SKID
CABLE ENTRY PANEL
AC TERMINAL
FRONT DOOR, DEAD FRONT, AND PEDESTAL ACCESS PANELREMOVED FOR CLARITY
FORKLIFT GUIDES
DC TERMINAL
COMMS(CAN / MODBUS)
UTILITY
THIS DOCUMENT IS FOR THE PURPOSE OF DISCUSSION ONLY
208VAC, 1PAUX POWER
TRANSFORMER
FIELD-INSTALLEDTHROAT CONNECTIONS
STORAGE
CAB1000 DCAC
DC SOURCE
GRIDFILTER
-K2
COOLINGSYSTEM
-MX1
CAB1000 DCAC
DC SOURCE
GRIDFILTER
-K2
COOLINGSYSTEM
-MX1
BUS BAR
STORAGE TRANSFORMER
UTILITY
CAB1000 DCAC
DC SOURCE
GRIDFILTER
-K2
COOLINGSYSTEM
-MX1
BUS BAR
STORAGE STORAGE
STORAGE
STORAGE
SYSTEM BLOCK DIAGRAM
3 MW*
* : SEE POWER RATINGTABLE FOR DETAILS
1 MW* 1 MW* 1 MW*
1 MW*
1 MW*
1 MW*DC / AC
DC / AC
DC / AC
1 MW*
1 MW*
1 MW*
DOCUMENT NUMBER
SHEET OF
DATE
OP CODE
EPC POWER CORP.GREGG ST SUITE A-2
POWAY, CA 92064
SHEET DESCRIPTION
ENG
REV
1 2 3 4 5 6 7 8 90
PROJECT DESCRIPTION
60-100168
03 06
08-28-20193x UNITS R01
CAB1000 LINEUP
4 P S10 0 0 4 8 0VAC U TI L IT Y- G R A D E P OW ER CO N V ER SI O N S Y S TEM
4C
AE
00
08
62
—We reserve the right to make technical changes or modify the contents of this document without prior notice. With regard to purchase orders, the agreed particulars shall prevail. ABB AG does not accept any responsibility whatsoever for potential errors or possible lack of information in this document.
We reserve all rights in this document and in the subject matter and illustrations contained therein. Any reproduction, disclosure to third parties or utilization of its contents – in whole or in parts – is forbidden without prior written consent of ABB AG. Copyright © 2020 ABBAll rights reserved.
—ABB Power GridsBruggerstrasse 72CH-5400 BadenSwitzerland
abb.com/distributed-energy-microgrids