Upload
quivivesukesh
View
303
Download
0
Embed Size (px)
Citation preview
POWER TRANSFORMERS
PROTECTION
Rating of Some Power transformers used.
1. 220/132 KV 262A,437A 100MVA YNyn0 Auto
2. 132/11.5 KV 350A,2008A 80MVA YNyn0yn0
3. 132/11.5 70A,803A 16MVA YNyn0
The types of faults that the transformers are subjected to
are classified as :-
• Through Faults:- These are due to overload conditions
and external short circuits. Time graded O/C & E/F
relays are employed for external short circuit conditions.
Fuses are provided for Distribution transformers.
• Internal Faults:-
1) Electrical Faults : - Faults which cause immediate
serious damage such as phase to earth or phase to
phase faults, short circuits between turns of HV&LV
windings, etc.
2) Incipient Faults: - Which are initially minor faults,
causing slowly developing damage, such as a poor
electrical connection of conductors or breakdown of
insulation, etc.
The following relays are employed to protect the transformer against internal faults.
i) Differential relays
ii) REF relays
iii) Bucholz Relay
iv) Over fluxing relays
Differential Relays :-
Two basic requirements that the differential relay connections are to be satisfied are :
a) It must not operate for load or external faults.
b) It must operate for internal faults.
Differential Relay Improvement • Differential Relay has improved a lot with
the introduction of numerical relay
• Numerical relays use techniques such as harmonic
blocking, wave shape recognition • In case of electromagnetic and static
relays, in a typical delta-wye power transformer, the current transformer would be connected as wye-delta.
Setting Of 87T
Alarm
Delay Trip Delay
Start Up
10% 10 sec 20% 0 sec
ST 10% 10 sec 20% 0 sec
MT 10% 10 sec 20% 0 sec
Restricted Earth Fault Protection (REF) : -
This relay is operative only for the internal faults of the transformer and thus fast operating time can be achieved.
1. An external fault on the star side will result in current flowing in the line CT of the affected phase and a balancing current in the neutral CT and current in the relay is zero and hence relay is stable. During an internal fault, the line current on the line CT gets reversed and hence relay operates.
2. The arrangement of residually connected CTs on the delta side of a transformer is only sensitive to earth faults on the delta side because zero sequence currents are blocked by the delta winding.
For external faults no current flows through REF unless a CT gets saturated. Hence minimum pickup current setting is adopted (10% or 20% In) on REF relay. Based on the through fault current, the stabilizing resistor is set such that the relay will not operate for external fault when a CT gets saturated. This relay operates only for internal earth faults, instantaneously.
Setting Of 64R
Type Alarm Delay
Trip
Delay
ROA
Start Up HV
Low imp
10%
0 sec
60
ST HV High imp
2 V 5 sec 11V 0 sec
ST LV1&LV2
High imp
10V 5 sec 50V 0sec
MT HV High imp
4V 5 sec 21V 0 sec
MT LV High imp
13V 5 sec 64V 0 sec
Overcurrent Protection:
Step 1 Delay Step 2 Delay
Start up HV
150% 1.4sec 900% 0 sec
Start up LV
150% 1.2 sec 800% 0sec
ST HV 150% 1.4 sec 900% 0sec
MT HV 145% 1 sec 1200% 0sec
Earth fault Protection:
Step 1 Delay
Start up HV
20% 1.4sec
Start up LV
20% 1.2 sec
ST SEF
30A 1 sec
MT SEF LV
20% 1sec
Overfluxing Protection:
1. Overfluxing condition in a transformer can occur during system over voltage and/or under frequency.
Alarm
Delay
Trip Delay
Start up
237.16 KV
5sec 242KV
2000 sec
352KV
.143 sec
Other Protective devices employed
• Pressure Relief Value (PRV) • Winding Temperature• Oil Temperature • OLTC Buchholz
Buchholz Relays : -Whenever a fault in transformer develop slowly,heat is produced locally, which begins todecompose solid or liquid insulated materialsand thus to produce inflammable gas and oilflow. This phenomenon has been used in the gasprotection relay or popularly known as Buchholzrelay. This relay is applicable only to the so-calledconservator type transformer in which the
transformertank is completely filled with oil, and a pipe
connectsthe transformer tank to an auxiliary tank or
“Conservator” which acts as an expansion chamber.
Conservator Alarm
Trip
Transformer Tank
Figure shown as Bucholz relay connected into the pipe leading to the conservator tank and arrange to detect gas produced in the
transformer tank. As the gas accumulates for a minor fault
the oil level falls and, with it a float `F' which operates a
mercury switch sounding an alarm. When a more serious
fault occurs within the transformer during which intense
heating takes place, an intense liberation of gases results.
These gases rush towards the conservator and create a rise in
pressure in the transformer tank due to which the oil is forced
through the connecting pipe to the conservator. The oil flow
develops a force on the lower float shown as "V" in the figure
and overtrips it causing it contacts to complete the trip circuit of
the transformer breaker. Operation of the upper float indicates
an incipient fault and that of the lower float a serious fault.
THANK YOU