Upload
others
View
4
Download
0
Embed Size (px)
Citation preview
PROTECTION SYSTEM DESIGN
SHIP AND OFFSHORE VESSELS-AN OVERVIEW
Copyright Material IEEE Paper No. PCIC-2013-22
Moni Islam Chairman IEEE 45DOT President, M&R Global Trading 36 Madera Ct Kenner, LA 70065, USA [email protected]
Kamal Garg, PE Supervisor, Protection Schweitzer Engineering Laboratories, Inc. 2350 NE Hopkins Court Pullman, WA 99163, USA [email protected]
Pat Patel Development Manager Schweitzer Engineering Laboratories, Inc. 2350 NE Hopkins Court Pullman, WA 99163, USA [email protected]
Saurabh Shah Regional Manager Schweitzer Engineering Laboratories, Inc. 2350 NE Hopkins Court Pullman, WA 99163, USA [email protected]
Abstract—Offshore vessels and ships are islanded power
systems. Maintaining the operation during the adverse system
operating conditions is a challenge. This paper reviews the
concepts to improve the protection and operation using the
advanced system protection and new developments of the
simulating process.
Index Terms—Offshore, DP, common mode protection,
PMS, VFD, harmonics, blackout, modal analysis, load flow,
short circuit, relay coordination, real time digital simulations.
I. INTRODUCTION
Offshore vessels and ships are islanded power systems
operating in adverse system conditions. With the
advancement in technology in protection and controls, there is
a need to review the protection design and application for
ships and the Offshore Industry. This paper reviews some of
the concepts that can be applied to improve the protection
and control system for ships and the offshore industry
vessels. This paper will focus on the protection of generators,
transformers, drives, and motors as follows, in view of
reliability and redundancy:
a) System Design
b) Future System, Protection, and Control
c) Adjustable speed drive ASD Protection and
Challenges
d) PMS and Blackout Recovery
e) Common Mode Generator Protection
f) Design Verification
In most vessels, electromechanical relays containing single
function relays are installed. However, with the advancement
in technology digital relays can be employed more
economically with the added benefit of low maintenance front
panel indication and display, communications, event recording
and reporting, time synchronization, and high mean time
between failures (MTBF). The system depicted in Figure 1
shows an example of typical power generation and distribution
system with the digital relays. These relays are capable of
protection functions, as well as providing automation, control,
and monitoring functions. Many other functions which are
performed using programmable logic controllers (PLCs) can
also be integrated into these relays. In addition, functions like
blackout recovery and some
functions of the Power Management System (PMS) can
also be integrated and supported with minimal cost and effort
in digital relays.
A discussion of the details of design studies required for
load flow, short circuit, and coordination follows in addition to
and providing an insight into the properly designed protection
and control system. This paper also proposes that there is a
need for design verification using real time closed-loop digital
simulation before the system is implemented in the field.
II. SYSTEM DESIGN
The one-line of the system for an offshore vessel is shown
in Figure 1. A typical system includes four to six generators,
four to six thrusters, propulsion, drilling loads and hotel/local
loads [1]. A properly designed protection and control system
should be able to operate for the closed bus and open bus
operations in order to maintain the minimum system
requirements during fault conditions. The system design
should also meet the class requirement, such as DP2 and
DP3 [2][10]. For an accurate system design, proposed studies
are listed in the system design verification [3].
G1 G2 G3 G4
TH2 TH4
TF3 TF4
TD1 TD2
BUS 1A
11kV
BUS 1B
11kV
BUS 1C
11kV
BUS 1D
11kV
DRILL BUS A
DISTRIBUTION BUS
690/480V
To PMS
Panel
G1
Relay
G2
Relay
G3
Relay
G4
Relay
TH1
T1
RelayF1
Relay
F2
Relay
T3
Relay
T1
F5
Relay
F6
Relay
F7
Relay
F10
Relay
F4
Relay
9212kVA/
11kV
9212kVA/
11kV
9212kVA/
11kV
9212kVA/
11kV
T2 T4
4.5MW
3.3 kV
4.5MW
3.3 kV
4.5MW
3.3 kV
F9
Relay
F8
Relay
11/1.65kV
6MVA11/1.65kV
6MVA
TH3
F3
Relay
T3
4.5MW
3.3 kV
11/1.65kV
6MVA
11/1.65kV
6MVA
11/0.72/0.72kV
5MVA
11/0.72/0.72kV
5MVA 11/0.69/0.48kV
3.5MVA3.5MVA
TF1 TF2
11/0.69/0.48kV
3.5MVA
3.5MVA
T2
Relay
Figure 1: Example Protection System
III. INTELLIGENT DIGITAL RELAYS & DESIGN
The proposed solution includes protection for generators,
motors, and buses and will be able to detect any system
disturbance, and faults, using the properly designed and
coordinated protection system. The system also includes GPS
time synchronization, along with high resolution event
recording capability for the system operation analysis and
investigation.
A. Generator Protection
This solution can provide multiple protection functions in
one digital relay. Typical generator protection elements
included in a single digital relay may consist of the protection
elements shown in Figure 2.
52
46/50/
51G
24 27/59 81
49T 67G BF
50P 87
32 40 51V/C
60
LOP
Figure 2: Standard Features of the Generator Protection Relay
Generator protection protects the generator from the
internal faults. The 51V/C element is backup protection for the
external system faults if the faults are not cleared by the
primary protection elements. The Offshore Industry still uses
one protection relay. However, it is recommended that dual
protection be employed, similar to the protection applied in
other areas (i.e. generation, transmission, and distribution),
since the cost of new digital relays is very economical
compared to that of electromechanical relays.
B. Motor Protection
The digital relays can control, monitor, and protect induction motors, synchronous motors, ASD motors, and special applications such as high inertia motors. The motor thermal element provides integrated protection for all of the following motor operating conditions:
• Locked Rotor Starts
• Running Overload
• Unbalanced Current/Negative-Sequence Current Heating
• Repeated or Frequent Starts
The digital relay dynamically calculates motor slip to precisely track motor temperature using the thermal model. The rotor resistance changes depending on slip and generates heat
especially during starting when the current and slip are highest. By correctly calculating the rotor temperature, the thermal model reduces the time between starts. It also gives the motor more time to reach its rated speed before tripping. The advanced digital relays provide comprehensive metering and monitoring functions so that the motor can be maintained and serviced at regular intervals. The monitoring and reporting
functions offer the following:
• Motor Start Reports and Trends
• Load-Profile Monitoring
• Motor Operating Statistics
• Event reports (Four or 32 samples/cycle resolution)
• Sequential Events Recorder (SER) (As many as 1024 time-tagged, most recent input, output, and element transitions.
Typical motor protection elements included in a single digital
relay may consist of the protection elements shown in
Figure 3. The relays offer communications/integration support with multiple protocols and programmable automation features.
Figure 3: Standard Features of the Motor Protection Relay
C. Power Management & Blackout Recovery
The Power Management System (PMS) is the overall
control and monitoring system of the vessel [8][10]. The
main tasks include system configuration, maintaining
power generation and power factor (PF), avoiding
blackouts, start and stop generators, and supporting
blackout recovery. The proposed PMS is shown in
Figure 4. Protection relays provide the system critical
information to the PMS. The dual redundant PMS system
includes a generator control system (GCS), load sharing
processor (LSP), and front-end processors (FEPs) [4],[5].
Control command can be sent via the same
communications network either by controlling the loads or
by generation, as required. The key features of the LSP
and GCS are customized to meet the system requirements
of the end-user. This system is self-monitored, hence any
communications failure is reported in real time. In addition,
separate transducers, such as those existing in the present
system for metering and control functions, are not required
for the future system. New digital protection devices are
capable of providing all the information required for the
PMS system. The communications protocol can be either
DNP/Modbus® or IEC 61850 GOOSE. The main functions
of the PMS are:
• System operation/maintain power generation
• Load dependant start/stop
• Load sharing
• Frequency control
• Bus-tie breaker control
• Synchronization
• Generator and load breakers
• Power limiting thruster/drilling
• Blackout prevention
• Load shedding (underfrequency/overload)
• Harmonic monitoring
• Oscillation detection
• Data acquisition and event collection
• Graphical display (HMI) of the system
• Alarming
• System reconfiguration
Figure 4: Typical PMS Architecture
The blackout recovery will be programmed in the automation
controller and the digital intelligent relays. Most of the
information available in relays can be utilized to perform
blackout recovery logic. Figure 5 shows an example blackout
recovery system for Bus A. Similar logic can be applied to the
other buses. Bus-tie breaker, and any other system,
information is collected from the existing relays. The logic will
first detect the blackout conditions then based upon
generation in service during the bus recovery detection, a
blackout recovery sequence will be initiated. The critical loads
are auxiliary buses and thrusters, in order to maintain the
station.
D. Common Mode Generator Protection
Common modes of failure are defined as faults that affect the overall system operation and cause multiple redundant elements to react adversely. For normal operating conditions, all of the generators operate in parallel droop mode. In case of a fault on one generator exciter and governor, or any other common-mode fault, properly detecting and isolating the faulty generator from the system as soon as possible is desired [8] [10] [11]. It is also necessary to evaluate the response time of the controls (e.g., exciter and governor controls) before making decisions regarding any system isolation or islanding. Otherwise, undesirable system operations may result in additional faults or failures. This common-mode protection solution correctly detects and islands all of the common-mode faults, which are classified into the following categories:
• Governors
• Fuel or Actuator
• Exciters
Figure 5: System Blackout Recovery
Figure 6: Low kW and Droop Mode
Figure 6 shows the slope and three percent droop
characteristics for the generator prime mover operating in
parallel. Curve A is selected if the generators are operating
normally around 100 percent of load. Curve B is selected if
the unit normally operates around 50 percent of load. For this
analysis, Curve B is selected when the normal operating load
is 50 percent.
E. Small Signal Oscillations & Modal Analysis
Small signal oscillation monitoring and control is very
important for weak islanded systems i.e. offshore and drill
vessels. Without proper remedial actions, inter-area
oscillations can result in power system separation or major
blackouts. The solution is capable of monitoring these
oscillations. Usually local oscillation modes range in frequency
from 0.7 to 2 Hz system. Figure 7 shows the 60 Hz system
with subharmonics. It is proposed to monitor the system
oscillation and provide real time data for visualization and
analysis. [6] [7]
Figure 7: The 60 Hz Signal with Subharmonics
The real part, σ, gives the damping of the amplitude of the
oscillations and the imaginary component, ω, gives the
frequency of oscillations. Negative real part signifies that the
oscillations are decreasing, whereas the positive real part
indicates growing oscillations. The frequency, f, of oscillations
in hertz and damping ratio (ζ) is as given in the following
equation.
� ��
�� (1)
�� � ��
√������� ���� �
IV. ASD PROTECTION
ASD protection may include converter, inverter,
current-source inverter (CSI) and voltage-source inverter
(VSI), current-source converter and voltage-source converter,
and pulse-width modulation (PWM). ASDs, by definition,
operate over a variable frequency range. This is in contrast to
the fixed 50 or 60 Hz operation of across-the-line-operated
motors. A fixed frequency system can no longer be assumed.
The overload protection device must be able to operate
correctly at any allowed operating frequency of the motor.
Since the motor can be subjected to abnormal frequency
levels, overfrequency protection should be provided. Digital
intelligent relays are capable of operating on root-mean-
squared (rms) current measurement. ASDs also produce
significant harmonics in both current and voltage outputs. As a
result, the thermal model is more accurate for ASD operation
when true rms measurements are used instead of
fundamental frequency sequence components. True rms
measurements include both fundamental and harmonic
content.
A. Power Electronics (Drives Equipment)
The over- or under-voltages and voltage unbalances will be addressed in this section. Some drives may also include dc-link reactor overvoltage protection. Overcurrent protection is provided for the converter electronics and interconnected bus or wiring. Short-circuit protection is
provided by fuses in front of the thyristors. • dc Overvoltage
• dc Undervoltage – Loss-of-control power
• Over Temperature – This includes the rectifier and
inverter heat sinks as well as the enclosure
temperature
B. Motors, Propulsion and Thrusters
Motors should be provided with the same protection as constant speed motors of the same size. Motor protection should also include overfrequency and overvoltage, or overexcitation, protection. This protection is typically provided by the drive control system but could be provided by discreet or multifunction relays, as follows:
• Motor Ground Fault
• Motor Overcurrent
• Motor Overload I²t
• Motor Stall
• Motor Overspeed
• Current Unbalance
• Underload – May indicate a process malfunction and
will protect the machinery and the process in this fault
condition
• External Fault – An external relay input
When motors are applied to ASDs, certain operating characteristics of the motor are modified. The operating frequency impacts how the motor behaves during operation, both starting and running, as well as during abnormal operation and fault conditions. The areas that will be discussed are pertinent to the protection of the motor and drive system.
1) Reduced Frequency Operation Effect
The frequency of the source to the motor dictates the operating speed. At lower speed operation, the motor is not cooled as efficiently as it is at rated speed. Therefore, this must be taken into consideration with regard to motor thermal overload protection. Actual motor full load current (Full Load Amperes or FLA) is a function of the frequency, because lower FLA is drawn at lower frequency. The actual FLA must be used in the overload protection.
2) Harmonics
Harmonics in the motor current will cause additional heating in the motors and other connected elements. This additional heating needs to be considered when sizing and protecting the equipment. At near rated load, a typical value to accommodate the additional heating can be up to a 15 percent increase above the
fundamental heating effects.
3) Voltage & Dielectric Stress
State-of-the-art control algorithms used in ASDs keep the motor flux constant over the entire speed/frequency range. The voltage is proportional to the frequency
(V/f = constant) in the upper frequency range.
C. Input Transformer
The input transformer relay provides differential and
overcurrent protection. Based upon the transformer
connection, ground overcurrent and neutral overvoltage can
be enabled. A time overcurrent (51) element that operates on
the fundamental frequency (i.e., not rms) may be set with a
lower pickup, as it will not respond to the harmonic
components of the load current. An instantaneous ground
element (50N) and differential (87) element can be applied for
the input transformer. The feeder, 51, can provide
conventional time-delayed protection. For ASD drives, if using
capacitors for power factor correction, resonances can occur
which must be taken under consideration. Following is the
summary of protection proposed.
• Short-Circuit/Overcurrent – Fuse, CB, or OC relay
• Overload – Overcurrent protection with time delay
• Voltage Unbalance – Loss-of-input phase
• Ground Fault Overcurrent
• Direct current (dc) interconnection and protection
V. DESIGN VALIDATION
A properly designed and validated system with digital
multifunction relays using the validation tools, such as real-
time digital simulations can result in significant savings during
the on-site installation and commissioning [11]. This can be
used to develop proof of concept of design, leading to final
design. Figure 9 shows an example for the real-time digital
simulation, where the actual power system is modeled in real-
time software and the designed system is tested in a closed
loop. For the properly design protection system, the following
studies are required:
a. Load Flow
b. Short Circuit and Equipment Evaluation
c. Relay Coordination
d. Harmonic Analysis
e. Real-Time Digital Simulations
Load flow, short circuit, and equipment evaluation studies
will determine the proper size of cables, transformers, circuit
breakers, and trip devices. The properly designed system will
be able to operate for normal and abnormal operating system
conditions, and meet the system requirements. Properly
performed Coordination Studies will determine the correct
operation and fault clearing in a reasonable time. Figure 8
shows the coordination margin of more than 0.3 second
between the devices. For some system operation conditions,
some miscoordination may be tolerated in order to
accommodate either the system stability or the arc-flash
requirements. For new systems, arc–flash protection and
studies should also be performed.
Figure 8: Overcurrent Coordination
Figure 9: Real Time Test System and Closed Loop Test
VI. CONCLUSION
Offshore vessels and ships are islanded power systems.
Robust protection and control systems are required to operate
these vessels and ships under adverse system conditions.
This paper provides designs for a proposed future system
using the latest technology available. With the availability of
many new features and technologies, it is possible to integrate
many solutions in the protection relays and to improve the
system’s operability and reliability.
VII. REFERENCES
[1] C. Craig and M. Islam, “Integrated Power System
Design for Offshore Energy Vessels & Deep Water
Drilling Rigs,” proceedings of the 57th Annual Petroleum
and Chemical Industry Committee Technical
Conference, San Antonio, TX, September 2010.
[2] Maritime Safety Committee Circular 645, Guidelines for
Vessels With Dynamic Positioning Systems, June 1994.
[3] A. Jain and K. Garg, “System Planning and Protection
Engineering—An Overview,” proceedings of the 3rd
International Conference of Power Systems, Kharagpur,
India, December 2009.
[4] B. Cho, H. Kim, M. Almulla, and N. Seeley, “The
Application of a Redundant Load-Shedding System for
Islanded Power Plants,” proceedings of the 35th Annual
Western Protective Relay Conference, Spokane, WA,
October 2008.
[5] D. Miller, R. Schloss, S. Manson, S. Raghupathula, and
T. Maier, “PacifiCorp’s Jim Bridger RAS: A Dual Triple
Modular Redundant Case Study,” proceedings of the
11th Annual Western Power Delivery Automation
Conference, Spokane, WA, April 2009.
[6] E. O. Schweitzer, III, D. Whitehead, H. Altuve,
D. Tziouvaras, D. Costello, and D. Escobedo, “Line
Protection: Redundancy, Reliability, and Affordability,”
proceedings of the 37th Annual Western Protective
Relay Conference, Spokane, WA, October 2010.
[7] E. O. Schweitzer, III, D. Whitehead, A. Guzmán,
Y. Gong, and M. Donolo, “Advanced Real-Time
Synchrophasor Applications,” proceedings of the 35th
Annual Western Protective Relay Conference, Spokane,
WA, October 2008.
[8] L. Weingarth, S. Manson, S. Shah, and K. Garg, “Power
Management Systems for Offshore Vessels,”
proceedings of the Dynamic Positioning Conference,
Houston, TX, October 2009.
[9] P. Whatley, M. Lanier, L. Underwood, and S. Zocholl,
“Enhanced Motor Protection With the Slip-Dependent
Thermal Model: A Case Study,” proceedings of the 34th
Annual Western Protective Relay Conference, Spokane,
WA, October 2007.
[10] S. Shah and K. Garg, “DP Power Plant Open Bus
Redundancy With Reliable Closed Bus Operation,”
proceedings of the Dynamic Positioning Conference,
Houston, TX, October 2010.
[11] A. Al-Mulla, K. Garg, S. Manson, and A. El-Hamaky,
“Case Study: A Dual-Primary Redundant Automatic
Decoupling System for a Critical Petrochemical
Process,” proceedings of the 2009 PCIC Europe
Technical Conference, Barcelona, Spain, May 2009.
.
VIII. VITAE
Moni Islam -Marine electrical engineering subject matter expert consultant for commercial, Offshore Industry, and Office of Naval Research (ONR). Moni has forty years diversified experience with electrical power systems, particularly electrical propulsion systems. Chair-Central Coordinating Committee for developing IEEE-45 Standards, provides coordinating support for developing IEEE-45 DOT Standards for standardizing electrical design practice for the marine industry. Authored many technical papers on power system design architecture for the marine industry and authored “Handbook to IEEE-45, A Guide to Electrical Installation on Shipboard-2004”. Moni received his bachelor of electrical engineering (Valedictorian) in 1975 from Fort Schuyler, Maritime College, State University of New York.
Kamal Garg is a Protection Supervisor in the Engineering
Services division of Schweitzer Engineering Laboratories, Inc.
(SEL). He received his MSEE from Florida International
University and IIT, Roorkee, India, and a BSEE from KNIT,
Avadh University, India. Kamal worked for POWERGRID India
for seven years and B&V,USA for five years at various
positions before joining SEL, USA in 2006. He has experience
in protection system design, system planning, substation
design, operation, RAS schemes, Synchrophasors, testing,
and maintenance. Kamal is a licensed professional engineer
in six US states.
Pat Patel received his PhD in electrical engineering from the
University of Missouri-Columbia in 1971, after which he
served in the US Army for two years. He worked in various
positions for GE and CEGELEC(France) in the field of HVDC
and SVC systems and projects for 23 years. He has served
13 years at SEL as Manager and Product Engineer in
research and development and is currently actively involved in
industrial applications and product development.
Saurabh Shah is a Regional Manager in the Engineering
Services division of Schweitzer Engineering Laboratories, Inc.
(SEL). He received his AS (1991) and BS (1995) in computer
systems from Lewis-Clark State College. He has a broad
range of experience in the fields of power system operations,
protection, automation, and integrated systems. He has
served nearly 19 years at SEL, where he has worked in relay
testing, sales, business development, and engineering project
management.