Protection Coordination Analysis

Embed Size (px)

Citation preview

  • 8/9/2019 Protection Coordination Analysis

    1/60

    1

    Power System Protection Coordinationwith Redundant Relay Application

    in Switchgear and MCCPresenter

    Shefian Bin Md Dom (HGE120021)

    SupervisorDr. Ab Halim Bin Abu Bakar

  • 8/9/2019 Protection Coordination Analysis

    2/60

    :: Presentation Outlines::

    Introduction

    Problem Statement

    Research Objectives

    Result & Discussion

    Conclusion

    2

  • 8/9/2019 Protection Coordination Analysis

    3/60

    :: Introduction ::

    The operation of the protection system should be fast and shouldisolate only the faulty section in the shortestpossible time to achieveminimumdisturbance to the system.

    Failure of a protective relay can result in devastating equipment

    damage and prolonged downtime as fault travel further deep intopowersystem structure fromthe actual faultlocation.

    This can be prevented by having optimum protectioncoordinationbetweenprotectionequipment.

    3

  • 8/9/2019 Protection Coordination Analysis

    4/60

    :: Introduction ::4

  • 8/9/2019 Protection Coordination Analysis

    5/60

    :: Introduction ::5 Old-TimerTools !

  • 8/9/2019 Protection Coordination Analysis

    6/60

    :: Introduction ::6 Old-TimerTools !

  • 8/9/2019 Protection Coordination Analysis

    7/60

    :: Introduction ::7 Old-TimerTools !

  • 8/9/2019 Protection Coordination Analysis

    8/60

    :: Introduction ::8 Old-TimerTools !

  • 8/9/2019 Protection Coordination Analysis

    9/60

    :: Introduction ::9 TodayTools !

  • 8/9/2019 Protection Coordination Analysis

    10/60

    ::Problem Statement ::

    Generally, optimum protection coordination study will ensurenearest protection devices to response against fault in shortestpossible time withinacceptable grading margin.

    Protection coordination study require complicated analysis and

    long duration of time will involved as short-circuit analysis andprotectiongrading mustbe complete together.

    In the even of faulty on main protection relay, there must be aredundant relay with proper protection coordination to ensurecomplete isolation of fault from travel further into power systemnetwork.

    10

  • 8/9/2019 Protection Coordination Analysis

    11/60

    :: Research Objectives::11

    1. To describe methodology required to achieve protectioncoordinationinpowersystem network.

    2. To perform full analysisusing SKMsoftware inorderto achieveprotectioncoordinationbetween protectiondevices.

    3.To evaluate the suitability of introducing redundant relay in

    the existing power system network from the aspect of properprotectioncoordination.

  • 8/9/2019 Protection Coordination Analysis

    12/60

    :: Methodology ::

    1 • Study Protection Coordination Concept

    2• Familiarization of Power System Analysis Software

    3• Technical Data Collection

    4• Perform Protection Coordination Analysis

    5• Review with Industrial Expert & Professional

    6• Produce Protection Coordination Report

    12

  • 8/9/2019 Protection Coordination Analysis

    13/60

    :: Result& Discussion ::

    Network Modelling

    Coordination Basis

    Fault Level Analysis

    Device Plug Setting

    Protection Coordination

    13

  • 8/9/2019 Protection Coordination Analysis

    14/60

     The network modelling is replication of actual network

    parameters from few different projects.Lynas Phase 2 (LampsUp), Onshore Malaysia.

    PKN PTA, Wloclawek, Onshore Poland.

    Petrofac FPSO Berantai & Wellhead, OffshoreMalaysia

    Petronas Platform Bekok C, Offshore Malaysia

     The analysis approach consist of real parameters fromlisted projects dedicate for conceptual study purposeand no commercial value.

    Divide into Upstream (Switchgears) and Downstream(MCC)

    14 Network Modelling

  • 8/9/2019 Protection Coordination Analysis

    15/60

    15 Network Modelling

  • 8/9/2019 Protection Coordination Analysis

    16/60

    bbb16 Network Modelling (Upstream 33/11kV)

  • 8/9/2019 Protection Coordination Analysis

    17/60

    17 Network Modelling (Upstream 33kV)

  • 8/9/2019 Protection Coordination Analysis

    18/60

    18 Network Modelling (Upstream 11kV)

  • 8/9/2019 Protection Coordination Analysis

    19/60

    19 Network Modelling (Downstream 0.4kV)

  • 8/9/2019 Protection Coordination Analysis

    20/60

    20 Network Modelling (Downstream 0.4kV)

  • 8/9/2019 Protection Coordination Analysis

    21/60

    21 Network Modelling (Downstream 0.4kV)

  • 8/9/2019 Protection Coordination Analysis

    22/60

    22 Network Modelling (Downstream 0.4kV)

  • 8/9/2019 Protection Coordination Analysis

    23/60

    23 Network Modelling (Downstream 0.4kV)

  • 8/9/2019 Protection Coordination Analysis

    24/60

    24 Network Modelling (Downstream 0.4kV)

  • 8/9/2019 Protection Coordination Analysis

    25/60

    Coordination basis is set of information to show initial criteria and

    assumption of respective power network under discussion.

    Sample of Coordination Basis:

    “The coordination margin between relays in series will be minimum

    0.30s”

    25 Coordination Basis

  • 8/9/2019 Protection Coordination Analysis

    26/60

    26 Coordination Basis

    CoordinationBasis

    General

    CoordinationMargin

    Plug Setting Discrimination

    MCCModules

    Load Type StartingMethod

    Protections

     Transformer

    Apparent(VA) Loaded Discrimination

  • 8/9/2019 Protection Coordination Analysis

    27/60

    27

    Fault LevelAnalysis

    ANSI IEC

    IEC60909 IEC61363

    Comprehensive

    Fault Level Analysis (Comprehensive)

  • 8/9/2019 Protection Coordination Analysis

    28/60

    28 Fault Level Analysis (Comprehensive)

    Sources ofFault Current

    Utility

    Generator

    SynchronousMotor

    InductionMotor

  • 8/9/2019 Protection Coordination Analysis

    29/60

     The maximum fault levels will be used in coordination asdiscrimination margin point.

     The definition of maximum fault levels condition includes full loadcapac ity, bus tie momentary close during synchronization betweenall busesunder Auto Transfer Switch (ATS) and generatoroperated.

    29 Fault Level Analysis (Comprehensive)

    Switchboard

    Maximum Fault DesignFault

     Three-Phase RMS

    Fault (kA)

     Three-Phase RMS

    Fault (kA)

    2LV8551A 62.121 80kA

    2LV8551B 58.729 80kA

    4MV8552 10.327 25kA

    4MV8501 9.743 25kA

  • 8/9/2019 Protection Coordination Analysis

    30/60

    30

    SKM

    Device Plug Setting (ANSI 51 OC IDMT)

  • 8/9/2019 Protection Coordination Analysis

    31/60

    31 Device Plug Setting (ANSI 51 OC IDMT)

    SKM

  • 8/9/2019 Protection Coordination Analysis

    32/60

    32 Device Plug Setting (ANSI 50 OC DT)

    SKM

  • 8/9/2019 Protection Coordination Analysis

    33/60

    Protection Coordination (LV/MCC)33

    MNSiSStarter

  • 8/9/2019 Protection Coordination Analysis

    34/60

    Protection Coordination (LV/MCC)34

    Protection: ANSI 49 Thermal Overload

     This function is used to protect equipment suchmotors and transformers against overloads basedon measurement of the c urrent consumed.

    MNSiSStarter

  • 8/9/2019 Protection Coordination Analysis

    35/60

    Protection Coordination (LV/MCC)35

    The cold curve defines the

    protection tripping time based onzero heat rise.

    MNSiSStarter

  • 8/9/2019 Protection Coordination Analysis

    36/60

    Protection Coordination (LV/MCC)36

  • 8/9/2019 Protection Coordination Analysis

    37/60

    Protection Coordination (LV/MCC)37

    The hot curve defines the

    protection tripping time based on100 % nominal heat rise.

    MNSiSStarter

  • 8/9/2019 Protection Coordination Analysis

    38/60

    Protection Coordination (LV/MCC)38

  • 8/9/2019 Protection Coordination Analysis

    39/60

    Protection Coordination (LV/MCC)39

    MNSiSStarter

  • 8/9/2019 Protection Coordination Analysis

    40/60

    Protection Coordination (LV/MCC)40

    MNSiSStarter

  • 8/9/2019 Protection Coordination Analysis

    41/60

  • 8/9/2019 Protection Coordination Analysis

    42/60

  • 8/9/2019 Protection Coordination Analysis

    43/60

  • 8/9/2019 Protection Coordination Analysis

    44/60

    Protection Coordination (LV/MCC)44

    MNSiSFeeder

  • 8/9/2019 Protection Coordination Analysis

    45/60

    Protection Coordination (LV/MCC)45

    Protection: ANSI 50/51 Phase Overcurrent The phase overcurrent protection function is

    three-pole. It picks up if one, two or three of thephase currents reach the operation set point.

    REF542+ R-2LV8551A

  • 8/9/2019 Protection Coordination Analysis

    46/60

    Protection Coordination (LV/MCC)46

    REF542+ R-2LV8551A

  • 8/9/2019 Protection Coordination Analysis

    47/60

    Protection Coordination (LV/MCC)47

  • 8/9/2019 Protection Coordination Analysis

    48/60

    REF542+ R-2LV8551A REF542+ 4TR8560

    Protection Coordination (LV/MV)48

    Protection Grading withFull Discrimination Technique

  • 8/9/2019 Protection Coordination Analysis

    49/60

    49

    0.4kV LV SWGR

    6.6kV MV SWGR

    WellheadPlatform FPSO Berantai Vessel

    FPSO VesselA floating production, storage and offloading (FPSO)unit is a floating vessel used by the offshore oil and

    gas industry for the production, processingof hydrocarbonsand for storage of oil

    Protection Grading withFull Discrimination Technique

    Protection Coordination (LV/MV)

    REF542+ R-2LV8551A

    0.4kV LV SWGR

  • 8/9/2019 Protection Coordination Analysis

    50/60

    50

    Protection Grading withNo Discrimination Technique

    REF542+ 4TR8560REF542+ R-2LV8551A

    Protection Coordination (LV/MV)

  • 8/9/2019 Protection Coordination Analysis

    51/60

    51

    Protection Grading withNo Discrimination Technique

    Substation 1

    Substation 2

    Substation 3

    Substation 4

    Protection Coordination (LV/MV)

  • 8/9/2019 Protection Coordination Analysis

    52/60

    52

    Full Discrimination No Discrimination

    1) Suitable for implementation whereMV and LV substation location veryfar from each other.

    1) Suitable for implementation whereMV or LV substation exist in thesame building or area.

    2) Total time margin will be longer 2) Total time margin will be shorter

    3) Fault isolation on either transformerprimary or secondary with respectto fault location.

    3) Fault isolation on both transformerprimary and secondary regardlessfault location.

    Protection Coordination (LV/MV)

  • 8/9/2019 Protection Coordination Analysis

    53/60

    Self-supplied (No external power required)

    Use microprocessor with Rogowsky Coil Sensor Simulation secondary injection using 5V USB EKIP CB Remote Open / Close using Modbus RTU Robust Design and Compact in size

    53

    Redundant Relay of ABB SACE PR123/P

    Protection Coordination (LV/MV)

  • 8/9/2019 Protection Coordination Analysis

    54/60

  • 8/9/2019 Protection Coordination Analysis

    55/60

    55

    Protection Grading withMix Discrimination Technique

    Protection Coordination (LV/MV)

  • 8/9/2019 Protection Coordination Analysis

    56/60

    56

    Protection Grading withMix Discrimination Technique

    Protection Coordination (LV/MV)

  • 8/9/2019 Protection Coordination Analysis

    57/60

    57 Protection Coordination (LV/MV)

  • 8/9/2019 Protection Coordination Analysis

    58/60

  • 8/9/2019 Protection Coordination Analysis

    59/60

    :: Conclusion ::

    2.The tedious analysis process of protection coordination study

    can even further simplified in SKM software. Engineer can use SKMDapper for short circuit analysis then followed by SKM Captor forprotection coordination analysis. Therefore protection coordinationstudies completely achieved with the help of SKM software.

    59

  • 8/9/2019 Protection Coordination Analysis

    60/60

    :: Conclusion ::

    3.Based on SKM simulation, it was concluded that redundant

    relay can be introduced in the existing power system to maximizereliability of the system. It was also proven in SKM Captor thatredundant relay successfully achieve desired protectioncoordination.

    60