Upload
shefian-md-dom
View
232
Download
2
Embed Size (px)
Citation preview
8/9/2019 Protection Coordination Analysis
1/60
1
Power System Protection Coordinationwith Redundant Relay Application
in Switchgear and MCCPresenter
Shefian Bin Md Dom (HGE120021)
SupervisorDr. Ab Halim Bin Abu Bakar
8/9/2019 Protection Coordination Analysis
2/60
:: Presentation Outlines::
Introduction
Problem Statement
Research Objectives
Result & Discussion
Conclusion
2
8/9/2019 Protection Coordination Analysis
3/60
:: Introduction ::
The operation of the protection system should be fast and shouldisolate only the faulty section in the shortestpossible time to achieveminimumdisturbance to the system.
Failure of a protective relay can result in devastating equipment
damage and prolonged downtime as fault travel further deep intopowersystem structure fromthe actual faultlocation.
This can be prevented by having optimum protectioncoordinationbetweenprotectionequipment.
3
8/9/2019 Protection Coordination Analysis
4/60
:: Introduction ::4
8/9/2019 Protection Coordination Analysis
5/60
:: Introduction ::5 Old-TimerTools !
8/9/2019 Protection Coordination Analysis
6/60
:: Introduction ::6 Old-TimerTools !
8/9/2019 Protection Coordination Analysis
7/60
:: Introduction ::7 Old-TimerTools !
8/9/2019 Protection Coordination Analysis
8/60
:: Introduction ::8 Old-TimerTools !
8/9/2019 Protection Coordination Analysis
9/60
:: Introduction ::9 TodayTools !
8/9/2019 Protection Coordination Analysis
10/60
::Problem Statement ::
Generally, optimum protection coordination study will ensurenearest protection devices to response against fault in shortestpossible time withinacceptable grading margin.
Protection coordination study require complicated analysis and
long duration of time will involved as short-circuit analysis andprotectiongrading mustbe complete together.
In the even of faulty on main protection relay, there must be aredundant relay with proper protection coordination to ensurecomplete isolation of fault from travel further into power systemnetwork.
10
8/9/2019 Protection Coordination Analysis
11/60
:: Research Objectives::11
1. To describe methodology required to achieve protectioncoordinationinpowersystem network.
2. To perform full analysisusing SKMsoftware inorderto achieveprotectioncoordinationbetween protectiondevices.
3.To evaluate the suitability of introducing redundant relay in
the existing power system network from the aspect of properprotectioncoordination.
8/9/2019 Protection Coordination Analysis
12/60
:: Methodology ::
1 • Study Protection Coordination Concept
2• Familiarization of Power System Analysis Software
3• Technical Data Collection
4• Perform Protection Coordination Analysis
5• Review with Industrial Expert & Professional
6• Produce Protection Coordination Report
12
8/9/2019 Protection Coordination Analysis
13/60
:: Result& Discussion ::
Network Modelling
Coordination Basis
Fault Level Analysis
Device Plug Setting
Protection Coordination
13
8/9/2019 Protection Coordination Analysis
14/60
The network modelling is replication of actual network
parameters from few different projects.Lynas Phase 2 (LampsUp), Onshore Malaysia.
PKN PTA, Wloclawek, Onshore Poland.
Petrofac FPSO Berantai & Wellhead, OffshoreMalaysia
Petronas Platform Bekok C, Offshore Malaysia
The analysis approach consist of real parameters fromlisted projects dedicate for conceptual study purposeand no commercial value.
Divide into Upstream (Switchgears) and Downstream(MCC)
14 Network Modelling
8/9/2019 Protection Coordination Analysis
15/60
15 Network Modelling
8/9/2019 Protection Coordination Analysis
16/60
bbb16 Network Modelling (Upstream 33/11kV)
8/9/2019 Protection Coordination Analysis
17/60
17 Network Modelling (Upstream 33kV)
8/9/2019 Protection Coordination Analysis
18/60
18 Network Modelling (Upstream 11kV)
8/9/2019 Protection Coordination Analysis
19/60
19 Network Modelling (Downstream 0.4kV)
8/9/2019 Protection Coordination Analysis
20/60
20 Network Modelling (Downstream 0.4kV)
8/9/2019 Protection Coordination Analysis
21/60
21 Network Modelling (Downstream 0.4kV)
8/9/2019 Protection Coordination Analysis
22/60
22 Network Modelling (Downstream 0.4kV)
8/9/2019 Protection Coordination Analysis
23/60
23 Network Modelling (Downstream 0.4kV)
8/9/2019 Protection Coordination Analysis
24/60
24 Network Modelling (Downstream 0.4kV)
8/9/2019 Protection Coordination Analysis
25/60
Coordination basis is set of information to show initial criteria and
assumption of respective power network under discussion.
Sample of Coordination Basis:
“The coordination margin between relays in series will be minimum
0.30s”
25 Coordination Basis
8/9/2019 Protection Coordination Analysis
26/60
26 Coordination Basis
CoordinationBasis
General
CoordinationMargin
Plug Setting Discrimination
MCCModules
Load Type StartingMethod
Protections
Transformer
Apparent(VA) Loaded Discrimination
8/9/2019 Protection Coordination Analysis
27/60
27
Fault LevelAnalysis
ANSI IEC
IEC60909 IEC61363
Comprehensive
Fault Level Analysis (Comprehensive)
8/9/2019 Protection Coordination Analysis
28/60
28 Fault Level Analysis (Comprehensive)
Sources ofFault Current
Utility
Generator
SynchronousMotor
InductionMotor
8/9/2019 Protection Coordination Analysis
29/60
The maximum fault levels will be used in coordination asdiscrimination margin point.
The definition of maximum fault levels condition includes full loadcapac ity, bus tie momentary close during synchronization betweenall busesunder Auto Transfer Switch (ATS) and generatoroperated.
29 Fault Level Analysis (Comprehensive)
Switchboard
Maximum Fault DesignFault
Three-Phase RMS
Fault (kA)
Three-Phase RMS
Fault (kA)
2LV8551A 62.121 80kA
2LV8551B 58.729 80kA
4MV8552 10.327 25kA
4MV8501 9.743 25kA
8/9/2019 Protection Coordination Analysis
30/60
30
SKM
Device Plug Setting (ANSI 51 OC IDMT)
8/9/2019 Protection Coordination Analysis
31/60
31 Device Plug Setting (ANSI 51 OC IDMT)
SKM
8/9/2019 Protection Coordination Analysis
32/60
32 Device Plug Setting (ANSI 50 OC DT)
SKM
8/9/2019 Protection Coordination Analysis
33/60
Protection Coordination (LV/MCC)33
MNSiSStarter
8/9/2019 Protection Coordination Analysis
34/60
Protection Coordination (LV/MCC)34
Protection: ANSI 49 Thermal Overload
This function is used to protect equipment suchmotors and transformers against overloads basedon measurement of the c urrent consumed.
MNSiSStarter
8/9/2019 Protection Coordination Analysis
35/60
Protection Coordination (LV/MCC)35
The cold curve defines the
protection tripping time based onzero heat rise.
MNSiSStarter
8/9/2019 Protection Coordination Analysis
36/60
Protection Coordination (LV/MCC)36
8/9/2019 Protection Coordination Analysis
37/60
Protection Coordination (LV/MCC)37
The hot curve defines the
protection tripping time based on100 % nominal heat rise.
MNSiSStarter
8/9/2019 Protection Coordination Analysis
38/60
Protection Coordination (LV/MCC)38
8/9/2019 Protection Coordination Analysis
39/60
Protection Coordination (LV/MCC)39
MNSiSStarter
8/9/2019 Protection Coordination Analysis
40/60
Protection Coordination (LV/MCC)40
MNSiSStarter
8/9/2019 Protection Coordination Analysis
41/60
8/9/2019 Protection Coordination Analysis
42/60
8/9/2019 Protection Coordination Analysis
43/60
8/9/2019 Protection Coordination Analysis
44/60
Protection Coordination (LV/MCC)44
MNSiSFeeder
8/9/2019 Protection Coordination Analysis
45/60
Protection Coordination (LV/MCC)45
Protection: ANSI 50/51 Phase Overcurrent The phase overcurrent protection function is
three-pole. It picks up if one, two or three of thephase currents reach the operation set point.
REF542+ R-2LV8551A
8/9/2019 Protection Coordination Analysis
46/60
Protection Coordination (LV/MCC)46
REF542+ R-2LV8551A
8/9/2019 Protection Coordination Analysis
47/60
Protection Coordination (LV/MCC)47
8/9/2019 Protection Coordination Analysis
48/60
REF542+ R-2LV8551A REF542+ 4TR8560
Protection Coordination (LV/MV)48
Protection Grading withFull Discrimination Technique
8/9/2019 Protection Coordination Analysis
49/60
49
0.4kV LV SWGR
6.6kV MV SWGR
WellheadPlatform FPSO Berantai Vessel
FPSO VesselA floating production, storage and offloading (FPSO)unit is a floating vessel used by the offshore oil and
gas industry for the production, processingof hydrocarbonsand for storage of oil
Protection Grading withFull Discrimination Technique
Protection Coordination (LV/MV)
REF542+ R-2LV8551A
0.4kV LV SWGR
8/9/2019 Protection Coordination Analysis
50/60
50
Protection Grading withNo Discrimination Technique
REF542+ 4TR8560REF542+ R-2LV8551A
Protection Coordination (LV/MV)
8/9/2019 Protection Coordination Analysis
51/60
51
Protection Grading withNo Discrimination Technique
Substation 1
Substation 2
Substation 3
Substation 4
Protection Coordination (LV/MV)
8/9/2019 Protection Coordination Analysis
52/60
52
Full Discrimination No Discrimination
1) Suitable for implementation whereMV and LV substation location veryfar from each other.
1) Suitable for implementation whereMV or LV substation exist in thesame building or area.
2) Total time margin will be longer 2) Total time margin will be shorter
3) Fault isolation on either transformerprimary or secondary with respectto fault location.
3) Fault isolation on both transformerprimary and secondary regardlessfault location.
Protection Coordination (LV/MV)
8/9/2019 Protection Coordination Analysis
53/60
Self-supplied (No external power required)
Use microprocessor with Rogowsky Coil Sensor Simulation secondary injection using 5V USB EKIP CB Remote Open / Close using Modbus RTU Robust Design and Compact in size
53
Redundant Relay of ABB SACE PR123/P
Protection Coordination (LV/MV)
8/9/2019 Protection Coordination Analysis
54/60
8/9/2019 Protection Coordination Analysis
55/60
55
Protection Grading withMix Discrimination Technique
Protection Coordination (LV/MV)
8/9/2019 Protection Coordination Analysis
56/60
56
Protection Grading withMix Discrimination Technique
Protection Coordination (LV/MV)
8/9/2019 Protection Coordination Analysis
57/60
57 Protection Coordination (LV/MV)
8/9/2019 Protection Coordination Analysis
58/60
8/9/2019 Protection Coordination Analysis
59/60
:: Conclusion ::
2.The tedious analysis process of protection coordination study
can even further simplified in SKM software. Engineer can use SKMDapper for short circuit analysis then followed by SKM Captor forprotection coordination analysis. Therefore protection coordinationstudies completely achieved with the help of SKM software.
59
8/9/2019 Protection Coordination Analysis
60/60
:: Conclusion ::
3.Based on SKM simulation, it was concluded that redundant
relay can be introduced in the existing power system to maximizereliability of the system. It was also proven in SKM Captor thatredundant relay successfully achieve desired protectioncoordination.
60