Protectionand control

Sepam rangeSepam 2000Sepam 1000+

Sepam 100

Page 2: Protection and control Sepam range Sepam 2000 …ms.schneider-electric.be/OP_MAIN/Sepam/AC0401UK.pdfCommunication Sepam 2000 offers the option of a high performing communication module

2 Sepam range

Sepam concept

Electromagnetic compatibility testing is performedin an anechoic chamber.

Kirchhoff protection testing laboratory.

Mastery of digital techniquesAs a result of the success of the first Sepam unit, Merlin Gerin developeda new range: Sepam 1000+ and Sepam 2000.This range is more comprehensive,more effective and fully appropriate for the control of electrical substations in publicand industrial distribution systems. All protection and control devices must:c supply optimal service under the best security and availability conditions,c ensure dependable operation in the highly disturbed electrical substationenvironment.

To achieve these objectives, the development of this new range calledfor substantial implementation of expertise and enhanced investigationsin the following main areas:c electrical phenomena, transient operation,c signal processing,c protection algorithms,c electromagnetic compatibility (EMC),c dependability, reliability,c communication networks.

During the design phase, dependability studies (FMECA (1)) were carried outto determine the hardware and software architectures, considerably improvingavailability and operating security.

All the studies were performed in accordance with a stringent quality plan.A large number of qualification tests were performed, in a dedicated protectiontesting laboratory (Kirchhoff laboratory).The protection functions are tested in the laboratory by simulating the phenomena(EMTP (2)) as they appear in electrical networks.

Major advantagesThe use of digital techniques provides protection and control devices with majoradvantages:

AvailabilityThe use of extensive self-testing and self-diagnosis procedures allows wide-rangemonitoring of the device.The user is continuously informed of Sepam’s operating condition.He can therefore take immediate and efficient action in the event of a failure.The risk of running an installation with faulty protection is substantially lowered.Periodic testing is no longer essential.

Global cost reductionThe integration in a Sepam of all the functions needed for the protection andcontrol of a system offers substantial advantages such as more rational operation,optimized performance and better service for a reduced overall cost.Reduction in the cost of:c design: by the choice of units that are ready to use, without requiring detailedengineering work,c installation: by the integration of auxiliary relays, measuring instrumentsand annunciation devices,c commissioning: by simple installation and testing,c operation: by remote control and improved access to more complete information,c maintenance: by the reduction of preventive maintenance.

DependabilityExtensive dependability and reliability calculations have been carried outon Sepam. They show that the failure rate, and therefore the risk of misoperation,is minimized with an integrated Sepam type solution.

SimplicitySepam requires only simple parameter setting (calibration of the currentand voltage transformers, and general information on the network).

FlexibilityThe flexibility of Sepam 2000’s built-in PLC makes it suitable for all possiblecontrol logic schemes.

(1) FMECA: Failure Modes, Effects and Criticality Analysis.(2) EMTP: Electromagnetic Transient Program.

Page 3: Protection and control Sepam range Sepam 2000 …ms.schneider-electric.be/OP_MAIN/Sepam/AC0401UK.pdfCommunication Sepam 2000 offers the option of a high performing communication module

3Sepam range

A complete rangeAll applicationsThe Sepam range is a set of protection and control units which have the capacityto fullfil all types of applications:c substations,c busbars,c transformers,c motors,c capacitors,c generators,c measure and control.Each Sepam is an optimized solution in terms of functions, performance and price.

All functionsEach Sepam includes all the protection, metering, control, monitoringand annunciation functions required for its assigned application.The functions have very wide setting ranges, all types of curves, and can thereforefit into any protection system.The choice of functions offered in each Sepam is the result of the engineering,experience and expertise of Merlin Gerin specialists who are confronted daily withthe challenge of developing electrical equipment projects.In addition, the so-called “logic discrimination” function makes it possible tofurther lower the tripping time when a fault occurs, whatever the time discriminationintervals and the type of curve (definite time or IDMT).This principle makes it possible to incorporate economical busbar protection,or to set a shorter protection time delay upstream than downstream,and still maintain tripping discrimination.It means that Sepam can meet the protection and control needs of low voltagenetworks and high voltage networks up to 220 kV as efficiently as required.

Industrial rangeThe design of all the types of Sepam for each application is basedon two hardware units: Sepam 1000+ series and Sepam 2000 series.The hardware manufacturing process is ISO9001 certified and includes a burn-incycle. Sepam’s robustness and its outstanding electromagnetic compatibility(EMC) allow it to be used in highly disturbed environments without requiring anyparticular precautions.

Sepam in a climatic burn-in chamber.

A complete range:Sepam 100, Sepam 1000+ and Sepam 2000.

Page 4: Protection and control Sepam range Sepam 2000 …ms.schneider-electric.be/OP_MAIN/Sepam/AC0401UK.pdfCommunication Sepam 2000 offers the option of a high performing communication module

4 Sepam range

Sepam 2000

Standard Sepam 2000 is delivered with its connectors.

PresentationSepam 2000 is focused on performance.It can be used for the most demanding applications.

Sepam 2000 has a large control and monitoring capacity, provided by its built-inPLC and interface for communication with a centralized control system.The built-in PLC considerably cuts down on the use of auxiliary relays and theassociated wiring.

Each Sepam 2000 is supplied with its standard control and annunciation program,which allows it to be used without any additional engineering work or programming.The available data as well as Sepam 2000’s remote control capacity enable it to beintegrated in an energy management system. Sepam 2000 reports to the controlroom, so the user is immediately informed of any situation. Having this informationat his disposal, he can take the appropriate measures without leaving the controlroom.

Each Sepam 2000 is designed to meet all the application needs and includesall the necessary functions, ready for use.Simply choose the appropriate Sepam 2000 from the selection tables showingthe functions available for each application (1) :c substations,c busbars,c transformers,c motors,c capacitors,c generators.

Example :An incomer in a substation with multiple supply sources, in a high impedanceearthed system, should be equipped with:c definite time or IDMT phase overcurrent and earth fault protection,c directional overcurrent and, sometimes, directional earth fault protectionfor discrimination between parallel incomers.c an undervoltage relay to control supply source changeover.c all the measurements and accumulated energy readings needed to operatethe substation. For this application, the S03 type Sepam 2000 could be chosen,including the standard control and monitoring functions, such as trip circuitsupervision and logic discrimination.

(1) for public distribution application, please consult us.

Standard (S36) Sepam 2000and compact (S26) Sepam 2000.

Page 5: Protection and control Sepam range Sepam 2000 …ms.schneider-electric.be/OP_MAIN/Sepam/AC0401UK.pdfCommunication Sepam 2000 offers the option of a high performing communication module

5Sepam range

Simple setting with the TSM 2001 pocket terminal.

DescriptionSepam 2000 replaces measuring instruments suchas ammeters, voltmeters, wattmeters,energy meters, etc.It displays alarm and operating messages related tothe protection functions and control logic systems,thereby eliminating the many indicating lamps foundon previous installations.The front face includes:c a lighted alphanumerical display, legible from adistance of several meters,c keys to select the measurement to be displayedand to acknowledge messages. As a security feature,these keys do not give access to the protectionsettings,c 3 lights:v “trip” (tripping by the protective relay),v “circuit breaker open”,v “circuit breaker closed”,c a green light indicating the presenceof “auxiliary power supply”,c a red light signalling malfunctions and relay fail-safeposition (watchdog),c a door for access to:v to the serial connection inlet,v the cartridge slot.The cartridge contains the different programs requiredfor Sepam 2000 operation.

Installation and connectionSepam 2000 is delivered with its connectors.The connectors are individually disconnectablescrew-on terminals.All types of Sepam can be installed by makinga simple rectangular cut-out in the mounting support.Some types of Sepam 2000 also come in a compactversion (S26).

Control logic and annunciationEach type of Sepam 2000 is equiped with a built-in PLC with at least 10 logicinputs and 6 logic outputs (which can be extended to 26 inputs and 14 outputs).This flexibility is provided for standard network management automation functionssuch as logic discrimination, reclosing, load shedding, etc.Customized process control programs may also be developed on Sepam(see “for customized applications” document).

OperationSepam 2000 is simple to consult and set thanks to the serial link on the front of thedevice.The settings may be made on the front panel (serial link):- one by one, using the TSM2001 pocket terminal, or the SFT2801 PC softwareprogram,- all at once using the SFT2821 PC software program (downloading),The TSM 2001 pocket terminal is equiped with a keyboard, a 4-line display(20-character per line) and a menu system.It is easy to read measurements, enter settings, modify operating conditionsand review maintenance information such as “fault current”, “number of c.b.operations”, etc.Access to the protection function settings is protected by a password.Sepam 2000 stores the parameters and the settings in its non volatile memory.In the event of an auxiliary power supply failure, they are saved and retrievedas soon as the power is restored.

Disturbance recordingSepam 2000 has a high performing disturbance recording function. It is used torecord analog signals (current/voltage) and logic states during a time interval whichincludes the disturbance. Sepam 2000 also has a graphical wave form recoverysoftware package for the analysis and use of the data (SFT 2826).

CommunicationSepam 2000 offers the option of a high performing communication module.(Jbus/Modbus or other) * for connection to a remote control and monitoring device.This option provides:c measurement of electrical variablesc annunciation,c switchgear controlc reading and modification of settingsc network diagnosis by :v event loggingv graphical wave form display.

(*) please consult us.

Page 6: Protection and control Sepam range Sepam 2000 …ms.schneider-electric.be/OP_MAIN/Sepam/AC0401UK.pdfCommunication Sepam 2000 offers the option of a high performing communication module

6 Sepam range

Sepam 2000substations and busbars

functions ANSI Sepam typescode substations busbars

S01 S02 S03 S04 S05 S06 S07 S08 S09 B01 B02 B03 B04 B07 B12protectionsphase overcurrent 50/51 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4earth fault (sensitive E/F) 50N/51N(G) 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4undervoltage 27 1 1 1 1 1 1 2 2 2/2* 2positive sequence undervoltage 27D 2 2remanent undervoltage 27R 1 1 1 1 1 1 1 1/1* 1overvoltage 59 2 2 2 2 2 2 2 2 2/2* 2neutral voltage displacement 59N 1 1 1 1 1 1directional overcurrent 67 1 1 1 1directional earth fault 67N 1 1 1 1 1 1reverse real power 32P 1 1 1underfrequency 81L 2 2 2 2 2 4overfrequency 81H 2 2 2 2 2 2rate of change of frequency 81R 2 2synchronism check 25 1meteringphase currents (I1, I2, I3) c c c c c c c c c c c c c c cpeak demand phase currents (I1, I2, I3) c c c c c c c c c c c c c c cvoltages (U21, U32, U13, V1, V2, V3) c c c c c c c c c c c c/c** creal / reactive power (P, Q) c c c c c c c c c c c c cpeak demand real / reactive power c c c c c c c c c c c c cpower factor c c c c c c c c c c c c cfrequency c c c c c c c c c c c c caccumulated real / reactive energy (±Wh, ±VArh) c c c c c c c c c c c c ctripping currents (I1, I2, I3, Io) c c c c c c c c c c c c c c ctrue rms current c c c c c c c c c c c c c c cdisturbance recording c c c c c c c c c c c c c c cphase rotation c cresidual current c c c c c c c c c c c c c c cresidual voltage c c c c c c c c c c c c ccumulative breaking current c c c c c c c c c c c c c c cand number of breakscontrol and monitoringopen / close c c c c c c c c c c c c c c clockout relay 86 c c c c c c c c c c c c c c cinhibit closing 69 c c c c c c c c c c c c c c cannunciation 30 c c c c c c c c c c c c c c crecloser 79 c c c c clogic discrimination 68 c c c c c c c c c c c c c c ctrip circuit supervision 74 c c c c c c c c c c c c c c cdetection of plugged 74 c c c c c c c c c c c c c c cconnectors (DPC)operation counter c c c c c c c c c c c c c c cphase fault trip counter c c c c c c c c c c c c c c cearth fault trip counter c c c c cdisturbance recording triggering c c c c c c c c c c c c c c cSepam modelsstandard S36 YR XR XR XR XR XR XR XR XR XR XR XR XR TR XR

compact S26 LX LT LT LT LT LT LT LT LT LT LT LT LT

number of standard ESTOR boards 1 2 2 1 1 2 2 2 2 2 2 1 2 3 3

The figures in the columns represent the number of similar protection devices.For example, for phase overcurrent protection, “4” means: 4 separate overcurrent protection devices.* available function with 2 sets of sensors.** phase-to-neutral voltage measurement only available on second set of sensors with a single VT.

Selection table

Page 7: Protection and control Sepam range Sepam 2000 …ms.schneider-electric.be/OP_MAIN/Sepam/AC0401UK.pdfCommunication Sepam 2000 offers the option of a high performing communication module

7Sepam range

functions ANSI Sepam types (2)

code T01 T02 T03 T04 T05 T06 T07 T09 T10 T11 T12 T13 T14 T15 T16 T17 T18 T19protectionsthermal overload 49 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1phase overcurrent 50/51 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4earth fault (sensitive E/F) 50N/ 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4

51N(G)neutral voltage displacement 59N 1 1 1 1 1 1 1 1 1 1 1directional overcurrent 67 1 1 1 1 1directional earth fault 67N 1 1 1 1 1 1 1 1tank earth leakage (3) 50/51 1 1 1 1 1 1 1neutral 50N/ 2 2 2 2 2 2 2

51Nundervoltage 27 1 1 1 1remanent undervoltage 27R 1 1 1 1overvoltage 59 2 2 2 2restricted earth fault (3) 64REF 1 1 1 1 1 1 1meteringphase currents (I1, I2, I3) c c c/c* c c c/c* c/c* c c c c/c* c/c* c c/c* c c c/c* cpeak demand phase currents (I1, I2, I3) c c c c c c c c c c c c c c c c c cvoltages (U21, U32, U13, V1, V2, V3) c c c c c c c c c c c c c c creal / reactive power (P, Q) c c c c c c c c c c c c c c cpeak demand real / reactive power c c c c c c c c c c c c c c cpower factor c c c c c c c c c c c c c c cfrequency c c c c c c c c c c c c c c cthermal capacity used c c c c c c c c c c c c c c c c c caccumulated real / reactive c c c c c c c c c c c c c c c(±Wh, ±VArh)tripping currents c c c c c c c c c c c c c c c c c c(I1, I2, I3, Io)true rms current c c c c c c c c c c c c c c c c c cdisturbance recording c c c c c c c c c c c c c c c c c cresidual current c c c/c* c c c/c* c/c* c c c c/c* c/c* c c/c* c c c/c* cresidual voltage c c c c c c c c c c c c c c ccumulative breaking current c c c c c c c c c c c c c c c c c cand number of breakscontrol and monitoringopen / close c c c c c c c c c c c c c c c c c clockout relay 86 c c c c c c c c c c c c c c c c c cinhibit closing 69 c c c c c c c c c c c c c c c c c cannunciation 30 c c c c c c c c c c c c c c c c c cBuchholz thermal relay c c c c c c c c c c cdetection of gas, pressureand temperature levels (DGPT/PTC)inter-tripping (1) c c c c c c c c c c clogic discrimination 68 c c c c c c c c c c c c c c c c c ctrip circuit supervision 74 c c c c c c c c c c c c c c c c c cdetection of plugged 74 c c c c c c c c c c c c c c c c c cconnectors (DPC)operation counter c c c c c c c c c c c c c c c c c cphase fault trip counter c c c c c c c c c c c c c c c c c cdisturbance recording triggering c c c c c c c c c c c c c c c c c cSepam modelsstandard S36 YR XR KR YR XR LR LR XR XR XR LR LR XR LR XR XR LR XRcompact S26 LX LT LX LT LT LT LT LT LT LT LTSepam equipped with 6 RTDs type T21 T22 T23 T24 T25 T26 T27 T29 T30 T31 T32 T33 T34 T35 T36 T37 T38 T39standard S36 ZR SR KZ ZR SR LS LS SR SR SR LS LS SR LS SR SR LS SRcompact S26 LS LSnumber of standard ESTOR boards 2 2 2 1 1 2 1 2 2 1 1 1 2 2 1 2 2 2

Selection table

The figures in the columns represent the number of similar protection devices.For example, for phase overcurrent protection, “4” means: 4 separate overcurrent protection devices.(1) inter-tripping: this is related to neutral voltage displacement, tank earth leakage, neutral protection functions and Buchholz tripping, gas detector tripping,pressure detector functions.(2) For differential protection 87T, please see Sepam 2000 D22.(3) the tank earth leakage and restricted earth fault protections are exclusive. The choice is made parameter setting. See other connection schemes for restrictedearth fault.* available function with 2 sets of sensors.

Sepam 2000transformer

Page 8: Protection and control Sepam range Sepam 2000 …ms.schneider-electric.be/OP_MAIN/Sepam/AC0401UK.pdfCommunication Sepam 2000 offers the option of a high performing communication module

8 Sepam range

Sepam 2000motor

functions ANSI Sepam types (1)

code M02 M03 M04 M05 M06 M07 M08 M09 M11 M14 M15 M16M20 M21 M22 M23

protectionsthermal overload 49 1 1 1 1 1 1 1 1 1 1 1 1phase overcurrent 50/51 2 2 2 2 2 2 2 2 2 2 2 2earth fault (sensitive E/F) 50N/51N(G) 2 2 2 2 2 2 2 2 2 2 2 2negative sequence / unbalance 46 1 1 1 1 1 1 1 1 1 1 1 1locked rotor/excessive starting time 48/51LR 1 1 1 1 1 1 1 1 1 1 1 1phase undercurrent 37 1 1 1 1 1 1 1 1 1 1 1 1starts per hour 66 1 1 1 1 1 1 1 1 1 1 1 1positive sequence undervoltage 27D 2 2 2 2 2 2 2 2 2 2direction of rotation 47 1 1 1 1 1 1 1 1 1 1directional earth fault 67N 1 1 1 1reverse real power 32P 1 1 1reactive overpower 32Q/40 1 1 1temperature set points 38/49T 6 6 6 6 6 6 6

12 12 12 12motor differential 87M 1 1 1 1meteringphase currents (I1, I2, I3) c c c c c c c c c c c cpeak demand phase currents (I1, I2, I3) c c c c c c c c c c c cvoltages (U21, U32, U13, V1, V2, V3) c c c c c c c c c creal / reactive power (P, Q) c c c c c c c c c cpeak demand real / reactive power c c c c c c c c c cpower factor c c c c c c c c c cfrequency c c c c c c c c c caccumulated real / reactive energy (±Wh, ±VArh) c c c c c c c c c ctripping currents (I1, I2, I3, Io) c c c c c c c c c c c ctrue rms current c c c c c c c c c c c cdisturbance recording c c c c c c c c c c c cthermal capacity used c c c c c c c c c c c cstart inhibit time delay / c c c c c c c c c c c cnumber of starts before inhibitiontemperature c c c c c c cphase rotation c c c c c c c c c cunbalance ratio / unbalance current c c c c c c c c c c c cstarting time and current c c c c c c c c c c c cresidual current c c c c c c c c c c c cresidual voltage c c c ccumulative breaking current c c c c c c c c c c c cand number of breaksdifferential current c c c cand through currentcontrol and monitoringopen / close c c c c c c c c c c c clockout relay 86 c c c c c c c c c c c cinhibit closing 69 c c c c c c c c c c c cannunciation 30 c c c c c c c c c c c cload shedding c c c c c c c c c c c crestart c c c c c c c c c clogic discrimination 68 c c c c c c c c c c c ctrip circuit supervision 74 c c c c c c c c c c c cdetection of plugged 74 c c c c c c c c c c c cconnectors (DPC)operation counter c c c c c c c c c c c crunning hours counter c c c c c c c c c c c cphase fault trip counter c c c c c c c c c c c cdisturbance recording triggering c c c c c c c c c c c cSepam modelsstandard S36 YR XR XR ZR LR LS LS SR SR LS XR SR

SS SS SS SScompact S26 LX LT LT LS(2) LTnumber of standard ESTOR boards 1 1 1 1 1 1 1 1 1 1 1 1

Selection table

The figures in the columns represent the number of similar protection devices.For example, for phase overcurrent protection, “2” means: 2 separate overcurrent protection devices.(1) for motor transformer block please consult us.(2) except for M20.

Page 9: Protection and control Sepam range Sepam 2000 …ms.schneider-electric.be/OP_MAIN/Sepam/AC0401UK.pdfCommunication Sepam 2000 offers the option of a high performing communication module

9Sepam range

Sepam 2000generators

Selection tablefunctions ANSI Sepam types generator -

transformer unitcode G01 G02 G03 G04 G05 G06 G07 G08 G17 G18 G00 G15 G16

G12 G13protectionsthermal overload 49 1 1 1 1 1 1 1 1 1 1 1 1phase overcurrent 50/51 4 4 4 4 4 4 4 4 4 4 4 4/2 * 4/2 *voltage restrained overcurrent 50V/51V 1 1 1 1 1 1 1 1 1 1 1 1negative sequence / unbalance 46 1 1 1 1 1 1 1 1 1 1 1 1earth fault (sensitive E/F) 50N/51N(G) 2 2neutral 50G/51G 4 4 4 4 4 4 4 4 2 2 4 4 4undervoltage 27 2 2 2 2 2 2 2 *** 2 *** 2 2 2overvoltage 59 2 2 2 2 2 2 2 2 2 2 2neutral voltage displacement 59N/64 1 1 1 1 1 1 1 1 1 1 1 1 1directional earth fault 67 1 1 1directional overcurrent 67N 1 1 1reverse real power 32P 1 1 1 1 1 1 1 1 1 1 1 1 1reactive overpower 32Q/40 1 1 1 1 1 1 1 1 1 1 1 1 1underfrequency 81L 1 1 1 1 1 1 1 1 1 1 1overfrequency 81H 1 1 1 1 1 1 1 1 1 1 1temperature (6 /12 RTDs) 38/49T 6/12 6 6/12 6 6 6restricted earth fault 64REF 1 1 1 1 1generator differential (1) 87G 1 1synchronism check 25 1 1meteringphase currents (I1, I2, I3) c c c c c c c c c/c* c/c* c c/c* c/c*peak demand phase currents (I1, I2, I3) c c c c c c c c c c c c cvoltage (U21, U32, U13, V1, V2, V3) c c c/c** c/c** c c c c c c c c creal / reactive power c c c c c c c c c c c c cpeak demand real / reactive power c c c c c c c c c c c c cpower factor c c c c c c c c c c c c cfrequency c c c c c c c c c c c c cthermal capacity used c c c c c c c c c c c caccumulated real / reactive energy (±Wh, ±VArh) c c c c c c c c c c c c ctripping currents (I1, I2, I3, Io) c c c c c c c c c c c c ctrue rms current (l rms) c c c c c c c c c c c c ctemperature c c c c c cdisturbance recording c c c c c c c c c c c c cresidual current c c c c c c c c c c c c/c* c/c*residual voltage c c c c c c c c c c c c ccumulative breaking current c c c c c c c c c c c c cand number of breaksdifferential and through currents c ccontrol and monitoringopen / close c c c c c c c c c c c clockout relay 86 c c c c c c c c c c c c cinhibit closing 69 c c c c c c c c c c cannunciation 30 c c c c c c c c c c c c clogic discrimination 68 c c c c c c c c c c c c ctrip circuit supervision 74 c c c c c c c c c c cBuchholz, thermal relay, DGPT, PTC c c cgroupe stop c c c c c c c c c c c cfield loss c c c c c c c c c c c cdetection of plugged connectors (DPC) c c c c c c c c c c c c coperation counter c c c c c c c c c c c crunning hours counter c c c c c c c c c c c cphase fault trip counter c c c c c c c c c c c c cdisturbance recording triggering c c c c c c c c c c c c cVT monitoring c cSepam modelsstandard S36 XR SR/ TR TS XR SR/ XR SR LR LS LR LS

SS SScompact S26 LT LTnumber of standard ESTOR boards 2 2 2 2 2 2 2 2 2 2 2 2 2The figures in the columns represent the number of units of the functions.Example: for phase overcurrent protection , ‘4’ signifies: 4 separate phase overcurrent protection units.(1) for differential protection, a Sepam 100 LD may also be used.(*) function available with 2 sets of sensors.(**) phase to neutral voltage measurement available with second set of sensors only with a single VT.(***) U21 and U32 only.

Page 10: Protection and control Sepam range Sepam 2000 …ms.schneider-electric.be/OP_MAIN/Sepam/AC0401UK.pdfCommunication Sepam 2000 offers the option of a high performing communication module

10 Sepam range

Sepam 2000capacitors

functions ANSI Sepam typescode C01 C02 C03 C04 C06 C08

protectionthermal overload 49 1 1 1 1 1

phase overcurrent 50/51 2 2 2 2 2 2

earth fault (sensitive E/F) 50N/51N(G) 2 2 2 2 2 2

neutral to neutral unbalance:single-bank capacitor 50N/51N 2 2

three-bank capacitor 50/51 3*2 3*2

undervoltage 27 1 1

overvoltage 59 2 2

meteringphase currents (I1, I2, I3) c c c c c/c* c/c*

peak demand phase currents (I1, I2, I3) c c c c c cvoltages (U12, U23, U13, V1, V2, V3) c c c creal / reactive power (P, Q) c c c cpeak demand real / reactive power c cpower factor c c c cfrequency c c c cthermal capacity used c c c c caccumulated real / reactive energy (±Wh, ±VARh) c c c ctripping currents (I1, I2, I3, I0) c c c c c ctrue rms current c c c c c cdisturbance recording c c c c c cresidual current c c/c* c c/c* c cresidual voltage c c c ccumulative breaking current c c c c c cand number of breaks

control and monitoringopen / close c c c c c clockout relay 86 c c c c c cinhibit closing 69 c c c c c cannunciation 30 c c c c c cdelay capacitor re-energizing c c c c c clogic discrimination 68 c c c c c ctrip circuit supervision 74 c c c c c cdetection of plugged connectors (DPC) 74 c c c c c coperation counter c c c c c cphase fault trip counter c c c c c cexternal protection tripping c c c c c cVT monitoring c cunbalance c c c cbank control cdisturbance recording triggering c c c c c cSepam modelsstandard S36 YR KR XR LR LR LR

compact S26 LX LT

number of standard ESTOR boards 1 1 1 1 1 3

Selection table

The figures in the columns represent the number of similar protection devices.For example, for phase overcurrent protection, “2” means: 2 separate overcurrent protection devices.* available function with 2 sets of sensors.

Page 11: Protection and control Sepam range Sepam 2000 …ms.schneider-electric.be/OP_MAIN/Sepam/AC0401UK.pdfCommunication Sepam 2000 offers the option of a high performing communication module

11Sepam range

functions Sepam typesR01 R02 R03 R04 R06 R07 R08 R09

metering (1)

phase current (I1, I2, I3) c c c c cpeak demand current (I1, I2, I3) ccccc ccccc ccccc ccccc cccccvoltage (U21, U32, U13, V1, V2, V3) ccccc ccccc ccccc ccccc cccccreal / reactive power (P, Q) ccccc ccccc ccccc ccccc cccccpeak demand real / reactive power ccccc ccccc ccccc ccccc cccccpower factor ccccc ccccc ccccc ccccc cccccfrequency ccccc ccccc ccccc ccccc cccccreal and reactive energy ccccc ccccc ccccc ccccc ccccc(± Wh, ± VARh)

memorization of ccccc ccccc ccccc ccccctripping currents (Io, I1, I2, I3)

temperature (6 RTDs) ccccc ccccctemperature (12 RTDs) ccccctrue rms current ccccc ccccc ccccc cccccresidual current ccccc ccccc ccccc cccccresidual voltage ccccc ccccc ccccc ccccclow level analog input (2)

number of channels 8 8

control and monitoringresetting to zero of I phase, W, VAr and ccccc ccccc ccccc ccccc"I TRIP" peak demand currents

outputs 10 14 14 10 38 38 38 38

inputs 18 26 26 18 48 48 48 48

maximum capacity (3) 18 26 26 18 112 112 112 112

temperature 6 RTDs (2 settings) ccccc ccccc 12 RTDs (2 settings) cccccdetection of plugged connectors ccccc ccccc ccccc ccccc ccccc ccccc ccccc cccccwatchdog ccccc ccccc ccccc ccccc ccccc ccccc ccccc cccccSepam modelsS36 XR XR SR SS

S26 LT

S46 RR XR NR ZR

number of standard ESTOR or ETOR/STOR boards2 3 3 2 3 3 3 3

Selection table

(1) direct connection to CT and VT.(2) connection to converters with format: 0-20, 4-20, 0-10, ±10 mA. Choice may be parameterized on front panel (serial link).(3) by adding ETOR boards with 16 logical inputs.

Sepam 2000metering and control

Page 12: Protection and control Sepam range Sepam 2000 …ms.schneider-electric.be/OP_MAIN/Sepam/AC0401UK.pdfCommunication Sepam 2000 offers the option of a high performing communication module

12 Sepam range

Sepam 2000transformer differential protection

Sepam 2000 D22 transformer differential protection is designed for:c double-winding transformers (1),c transformer and motor units,c transformer and generator units.

Sepam 2000 D22 provides fast protection against faults which occurin the protected zone:c phase-to-phase faults,c phase-to-earth faults,c faults between winding turns.

Sepam 2000 D22 includes:c percentage differential function,c restricted earth fault protection,c high set point function for violent faults,c 2 processing functions, thermostat and Buchholz, for the transformer,neutral coil or on-load tap changer.

Sepam 2000 D22 does not require an adaptation or resetting transformer.

(1) please consult us for 3-winding version.

protections ANSI code D22

transformer differential 87T 1biased characteristichigh set

restricted earth fault 64REF 1biased characteristic

metering

I1 and I1’ currents and phase shift cI2 and I2’ currents and phase shiftI3 and I3’ currents and phase shift

residual current Io’ cdifferential currents Id1, Id2, Id3 cthrough currents It1, It2, It3 ctripping currents: cdifferential: trip Id1, trip Id2, trip Id3through: trip It1, trip It2, trip It3

control and monitoring

latching/acknowledgment 86 cannunciation 30 cdetection of plugged connectors 74 cBuchholz and thermostat cauxiliary 1, auxiliary 2 cfault trip counter cSepam 2000 model

S36 CR

Sepam 2000 D22.

Page 13: Protection and control Sepam range Sepam 2000 …ms.schneider-electric.be/OP_MAIN/Sepam/AC0401UK.pdfCommunication Sepam 2000 offers the option of a high performing communication module

13Sepam range

Example of a personalized message.

Example of a customized scheme developed using Logipam (1).

Sepam 2000customization

In addition to the protection and metering functions, Sepam 2000 also includescontrol logic and annunciation.This standard control logic may be adapted to most usuals schemes by a simpleparametring at commissioning stage.This enables optimized cabling and more dependable operation.(Diagrams are specified to take into account the most frequent needs).

In order to offer greater flexibility to adapt to your installations, functions can bemodified and new control and annunciation functions can be added byprogramming in an electrican’s language (Logipam (1)).Programming can be done on site.

Built-in PLCc up to 26 logic inputs and 14 output relays(by 8-input / 4-output modules),c 24, 48, 127, 220 Vdc power supply,c 512 internal relays,c 24 event counters,c 60 timers,c 64 personalized 11-character messages that can be programmed regardingevents,c 128 bistable relays,c 64 internal relays that can be set via the pocket terminal.c 96 internal relays that can be set by via communication.

Remote monitoring and control via communicationc setting of protection functions and control logic time delays (remote setting),c measurement readout (remote metering),c logic input and output relay readout (remote indication),c remote control of 96 internal relays (remote control),c self-testing results readout (remote diagnosis).

The Logipam software package has a simulation function for functional testingof the control logic scheme before programming of the Sepam cartridge.

(1) LogipamTM: scheme programming software package for Sepam 2000 (please consult us).

Page 14: Protection and control Sepam range Sepam 2000 …ms.schneider-electric.be/OP_MAIN/Sepam/AC0401UK.pdfCommunication Sepam 2000 offers the option of a high performing communication module

14 Sepam range

Sepam 1000+

Sepam 1000+ is a simple, reliable range of protection and metering units designedfor the operation of machines and the electrical distribution networks of industrialinstallations and utility substations for all levels of voltage.

This protection unit is suited to each application requirement, providing anoptimum cost/function ratio.

The Sepam 1000+ range includes different types of units for different applications:c Sepam 1000+ S20: substation (incomers and feeders) protection,c Sepam 1000+ T20: transformer protection,c Sepam 1000+ M20: motor protection,c Sepam 1000+ B21: voltage metering and protection functions for busbars,c Sepam 1000+ B22: loss of mains protection.

Main functionsProtectionsc Overcurrent and earth fault protection with adjustable time reset and withswitching from one setting group to the other controlled by a logic order.c Earth fault protection insensitivity to transformer closing.c Detection of phase unbalance.c RMS thermal protection which takes into account external operating temperatureand ventilation operating rates.c Rate of change of frequency protection (ROCOF), for a fast and reliabledisconnection.

Communication

Fully compatible with the Modbus standard, Sepam 1000+ enables remoteoperation of equipment:c reading of all available information (measures, alarms, settings,...)c remote control of the breaking device.

Diagnosis3 types of diagnostic information are available for better operation:c network diagnosis: tripping current, unbalance ratio, disturbance recording…,c switchgear diagnosis: cumulative breaking current, operating time,c diagnosis of the protection unit and additional modules: self-testing results,watchdog,… .

Control logic and monitoringThe unit includes programmed logic blocks to avoid the use of additional externalauxiliary relays, indication lights and corresponding wiring.

User Machine Interface2 levels of User-Machnie Interface (UMI) are available to suit every operating need:c standard UMI:low-cost solution for installations that do no require local operation (run from aremote control and monitoring system).c fixed or remote advanced UMI:optimum response for local operation, this easy-to-read UMI includes:v a “graphic” LCD display for the display of measures,parameter/ protection settings and alarm and operating messages.v a 9-key keypad giving access to device parameters and protection settings.(Modification protected by password.)

Expert UMI softwareThe SFT 2841 software gives access to all Sepam 1000+ functions, with all theuser friendless and comfort offered by a Windows type environment.

Sepam 1000+ with standard UMI and with fixed advanced UMI

Example of SFT 2841 screen on PC (Expert UMI).

Sepam 1000+, a modular solution

Page 15: Protection and control Sepam range Sepam 2000 …ms.schneider-electric.be/OP_MAIN/Sepam/AC0401UK.pdfCommunication Sepam 2000 offers the option of a high performing communication module

15Sepam range

functions type of Sepamsubstation transformer motor busbar

protection ANSI code S20 T20 M20 B21(5) B22phase overcurrent (1) 50/51 4 4 4earth fault (or neutral) (1) 50N/51N 4 4 4unbalance / negative sequence 46 1 1 1thermal overload 49 RMS 2 2phase undercurrent 37 1excessive starting time, locked rotor 48/51LR 1starts per hour 66 1positive sequence undervoltage 27D/47 2 2remanent undervoltage 27R 1 1phase-to-phase undervoltage 27 2 2phase-to-neutral undervoltage 27S 1 1phase-to-phase overvoltage 59 2 2neutral voltage displacement 59N 2 2overfrequency 81H 1 1underfrequency 81L 2 2rate of change of frequency 81R 1recloser (4 cycles) 79 vthermostat / Buchholz vtemperature monitoring (2) 38/49T v vmeteringphase current I1, I2, I3 RMS c c cresidual current Io c c caverage current I1, I2, I3 c c cpeak demand phase current IM1, IM2, IM3 c c cline voltage U21, U32, U13 c cphase voltage V1, V2, V3 c cresidual voltage Vo c cpositive sequence voltage Vd / rotation direction c cfrequency c ctemperature measurement (2) v vnetwork diagnosistripping current I1, I2, I3, Io c c cunbalance ratio / negative sequence current c c crunning hours counter c cthermal capacity used c cremaining operating time before c coverload trippingwaiting time after overload tripping c cstarting current and time cstart inhibit time delay, cnumber of starts before inhibitiondisturbance recording c c c c cswitchgear diagnosiscumulative breaking square current c c ctrip circuit supervision v v v v vnumber of operations v v voperating time v v vcharging time v v vself-diagnosiswatchdog c c c c coutput relay test (3) v v v v vcontrol and monitoringcircuit breaker / contactor control (4) v v v v vlogic discrimination v v v4 addressable logic outputs c c c c cadditional modulesMET 148 – 8 temperature sensor inputs v vMSA 141 – 1 low level analog output v v v v vMES 108 (4 I/4 O) or MES 114 (10 I/4 O) v v v v vACE 949-2 (2 wires) or ACE 959 (4 wires) – RS485 interface v v v v vc standard, v according to parameter setting and MES 108 or MES 114 input/output module options.(1) 4 relays with the possibility of logic discrimination or switching from one 2-relay group of settings to another 2-relay group.(2) with MET 148 sensor option, 2 set points per sensor.(3) with advanced UMI option only.(4) for shunt trip unit or undervoltage release coil according to parameter setting.(5) performs the B20 type functions.

Selection table

Sepam 1000+

Page 16: Protection and control Sepam range Sepam 2000 …ms.schneider-electric.be/OP_MAIN/Sepam/AC0401UK.pdfCommunication Sepam 2000 offers the option of a high performing communication module

16 Sepam range

I

O

local

remote

I

O

local

remote

Example:Sepam 100 MI X03Circuit breaker and isolatingswitch annunciationand control.

Example:Sepam 100 MI X02Outgoing or incoming feedercircuit breaker annunciationand control.

PresentationSepam 100 is a series of modules which fit the Sepam range.These modules can be installed on their own or combined with Sepam 1000+

or Sepam 2000.

Sepam 100 includes:

c on front panel: orders, settings and informations,c on rear panel: connectors.

The Sepam 100 series includes several types:c Sepam 100 LA provides DT phase and residual current protection withoutrequiring an auxiliary power supply. Combined with Sepam 1000+ or 2000,this module provides “reflex” protection, operating in redundancy, in the eventof a failure in the main protection chain (auxiliary power suply, tripping, etc).

c Sepam 100 RT processes the information received from the transformerthermostat and Buchholz contacts. It provides annunciation, tripping and circuitbreaker lockout (this information is stored in the event of an auxiliary powerfailure), trip circuit supervision...,c Sepam 100 LD provides high impedance differential protection,c Sepam 100 MI modules are used for control and annunciation of the protectionof circuit breaker and isolating switches.(a large number of mimic diagram schemes are available).

Sepam 100

Most frequently used complementary modules:Sepam100 LA, Sepam100 RT.

Page 17: Protection and control Sepam range Sepam 2000 …ms.schneider-electric.be/OP_MAIN/Sepam/AC0401UK.pdfCommunication Sepam 2000 offers the option of a high performing communication module

17Sepam range

Sensors

Installation of CSH core balance CTs.

Standard current sensorsSepam is adapted for all types of phase and residual current sensors:standard 1A or 5A with rated currents from 10A to 6.25 kA.

CSH core balance CTsThe CSH 120 and CSH 200 core balance CTs, designed by Merlin Gerin,provide more sensitive protection by direct metering of earth fault current.

The only difference between the two core balance CTs is their diameter.Both can be connected directly to Sepam analog input for residual currentmetering.

CSH core balance CTs inner diameter

CSH 120 120 mm

CSH 200 200 mm

Characteristics

ACE 990 core balance CT interfaceSepam can be adapted to earth fault core balance CTs with a transformation ratiobetween 1/50 and 1/1500.Earth fault current is measured by the ACE 990 interface.

ACE 990 core balance CT interface.

Page 18: Protection and control Sepam range Sepam 2000 …ms.schneider-electric.be/OP_MAIN/Sepam/AC0401UK.pdfCommunication Sepam 2000 offers the option of a high performing communication module

18 Sepam range

Dimensions and weights

201

20

222

mounting latches (x2)

e = 3 mm max

300

Side view (S26 - S36 - S46)

Characteristics

Sepam 2000

Sepam A (mm)

S46 429

S36 338

S26 250

Cut-out

202

A

Compact Sepam 2000 (S26)

weight: approx. 7 kg

222

264

Standard Sepam 2000 (S36)

weight: approx. 9 kg

222

352

440

222

Standard Sepam 2000 (S46)

weight: approx. 11 kg

Page 19: Protection and control Sepam range Sepam 2000 …ms.schneider-electric.be/OP_MAIN/Sepam/AC0401UK.pdfCommunication Sepam 2000 offers the option of a high performing communication module

19Sepam range

Electrical characteristics

analog inputscurrent transformer 1 A CT < 0.001 VA10 A to 6250 A ratings 5 A CT < 0.025 VA

voltage transformer 100 to 120 V > 100 kΩ220 V to 250 kV ratings(1)

auxiliary power supplyDC voltage 24/30 Vdc(2) 48/127 Vdc 220/250 Vdc

typical consumption 18 W 19.5 W 21 W

logic inputsvoltage 24/30 Vdc(2) 48/127 Vdc 220/250 Vdc

consumption 4 mA 4 mA 3 mA

logic outputs (relays)voltage 24/30 Vdc 48 Vdc 125 Vdc 220/250 Vdc

rated current 8 A 8 A 8 A 8 A

400 ms overload 15 A 15 A 15 A 15 A

making capacity 15 A 15 A 15 A 15 A

breaking capacity : DC with resistive load 8 A 4 A 0,8 A 0,3 ADC at L/R = 20 ms 6 A 2 A 0.4 A 0.15 ADC at L/R = 40 ms 4 A 1 A 0.2 A 0.1 AAC with resistive load 8 A 8 A 8 A 8 AAC with p.f. = 0.3 5 A 5 A 5 A 5 A

Environmental characteristicselectric insulationdielectric withstand IEC 60255-5 2 kV - 1 mn (1)

1.2/50 µs impulse wave withstand IEC 60255-5 5 kV (2)

climatic withstandoperation IEC 60068-2- 1 and 2 - 5 °C to + 55 °C

IEC 60068-2-14 - 5 °C to + 55 °Cstorage IEC 60068-2 - 25 °C to + 70 °Cdamp heat IEC 60068-2 -3 93% RH at 40 °C

56 days (storage)10 days (operation)

corrosion influence IEC 60654-4 class I

mechanical robustnessdegree of protection IEC 60529 IP 51 front face

vibrations IEC 60255-21-1 class I

shocks / jolts IEC 60255-21-2 class I

earthquakes IEC 60255-21-3 class I

fire resistance IEC 60695-2-1 glow wire

electromagnetic compatibilityradiated fields IEC 60255-22-3 class x 30 V/m

IEC 61000-4-3 class III 10 V/m

electrostatic discharge IEC 60255-22-2 class IIIIEC 61000-4-2 class III

damped 1 MHz wave IEC 60255-22-1 class III

5 ns electrical fast transients/burst IEC 60255-22-4 class IVIEC 61000-4-4 class IV

1.2/50µs - 8/20µs surge immunity IEC 61000-4-5 class III 2 kV differential mode (42 Ω)1 kV common mode (42 Ω)

conducted disturbance emission EN 55022/CISPR22 class B with auxiliary power supply (3)

radiated field emission EN 55022/CISPR22 class B (4)

“ ” marking on our product guarantees their conformity to European directives.(1) except for communication 1.4 kVdc and auxiliary power supply 2.8 kVdc(2) except for communication 3 kV common mode, 1 kV differential mode(3) EN 50081-1 generic standard(4) EN 50081-2 generic standard

Sepam 2000

(1) up to 500 kV with S46(2) not available with S46

Page 20: Protection and control Sepam range Sepam 2000 …ms.schneider-electric.be/OP_MAIN/Sepam/AC0401UK.pdfCommunication Sepam 2000 offers the option of a high performing communication module

20 Sepam range

Characteristics (cont’d)

Weight = approx. 1.2 kg without option.Weight = approx. 1.7 kg with option.

98

222

31

mounting latch

198

Flush mounting on front panel shown with advancedUMI and optional MES 114 module.

Top view Side view

160176

Sepam 1000+

cutout

Mounting sheet thickness < 3 mm.

202

162

Electrical characteristics

analog inputs

current transformer (1) 1 A CT < 0.001 VA1 A to 6250 A ratings 5 A CT < 0.025 VA

voltage transformer 100 to 120 V > 100 kΩ220 V to 250 kV ratings

input for RTDs (2) (MET 148 module)

type of RTD Pt 100 Ni 100 / 120

isolation from earth no no

logic inputs (MES 108 or MES 114 module)

voltage (2) 24 to 250 Vdc -20/+10% (from 19.2 to 275 Vdc)

consumption 3 mA typical

control logic outputs (O1, O2, O11 contacts) (2)

voltage DC 24 / 48 Vdc 127 Vdc 220 Vdc

AC (47.5 to 63 Hz) 100 to 240 Vac

continuous rating 8 A 8 A 8 A 8 A

breaking resistive load 8 / 4 A 0.7 A 0.3 Acapacity L/R load < 20 ms 6 / 2 A 0.5 A 0.2 A

L/R load < 40 ms 4 / 1 A 0.2 A 0.1 A

resistive load 8 A

load p.f. > 0.3 5 A

monitoring logic outputs (O3, O4, O12, O13, O14 contacts) (2)

voltage DC 24 / 48 Vdc 127 Vdc 220 Vdc

AC (47.5 to 63 Hz) 100 to 240 Vac

continuous rating 2 A 2 A 2 A

breaking L/R load < 20 ms 2 / 1 A 0.5 A 0.15 Acapacity load p.f. > 0.3 1 A

power supply (2)

range deactivated cons. (3) max. cons. (3) inrush current

24 Vdc -20% +50 % (19.2 to 36 Vdc) 3 to 6 W 7 to 11 W < 10 A for 10 ms

48 / 250 Vdc -20% +10 % 2 to 4.5 W 6 to 8 W < 10 A for 10 ms

110 / 240 Vac -20% +10 % (47.5 to 63 Hz) 3 to 9 VA 9 to 15 VA < 15 A forfirst half-period

analog output (MSA 141 module)

current 4 - 20 mA, 0 - 20 mA, 0 - 10 mA

load impedance < 600 Ω (wiring included) (2)

accuracy 0.5%(1) wiring: maximum core section ≤ 6 mm2 (≥ AWG 10) and ring lug terminal ø 4 mm.(2) wiring: 1 wire maximum core section 0.2 to 2.5 mm2 (≥ AWG 24-12) or 2 wires maximum core section 0.2 to 1mm2 (≥ AWG 24-16).(3) according to configuration.

Page 21: Protection and control Sepam range Sepam 2000 …ms.schneider-electric.be/OP_MAIN/Sepam/AC0401UK.pdfCommunication Sepam 2000 offers the option of a high performing communication module

21Sepam range

Environmental characteristics

isolation

dielectric withstand at power frequency IEC 60255-5 2 kVrms – 1 mn (1)

1.2/50 µs impulse wave IEC 60255-5 5 kV (2)

electromagnetic compatibility

fast transient bursts IEC 60255-22-4 class IVIEC 61000-4-4 class IV

1 MHZ damped oscillating wave IEC 60255-22-1 class III

immunity to radiated fields IEC 60255-22-3 class X 30 V/mIEC 61000-4-3 class III 10 V/m

immunity to conducted RF disturbances IEC 61000-4-6 class III 10 V

electrostatic discharge IEC 60255-22-2 class III 6 kV / 8 kV (contact / air)IEC 61000-4-2 class III

conducted disturbance emission EN 55022 / CISPR 22 class B on power supply (3)

disturbing field emission EN 55022 / CISPR 22 class A (4)

mechanical robustness

degree of protection IEC 60529 IP 52 on front panel and othersides closed

IP 20 on rear panel

vibrations IEC 60255-21-1 class II

shocks / jolts IEC 60255-21-2 class II

earthquakes IEC 60255-21-3 class II

fire resistance IEC 60695-2-1 glow wire 630°Cclimatic withstand

operation IEC 60068-1 and 2 -25°C to +70°Cstorage IEC 60068-1 and 2 -25°C to +70°Cdamp heat IEC 60068-2-3 93% RH at 40°C,

56 days (storage)10 days (operation)

(1) except for communication 1 kVrms.(2) except for communication 3 kV common mode, 1 kV differential mode.(3) generic EN 50081-1 standard.(4) generic EN 50081-2 standard.

Sepam 1000+

Page 22: Protection and control Sepam range Sepam 2000 …ms.schneider-electric.be/OP_MAIN/Sepam/AC0401UK.pdfCommunication Sepam 2000 offers the option of a high performing communication module

22 Sepam range

201

20

222

mounting latch

88 84 max

e = 3 mm max

A

Electrical characteristics Sepam 100 RT

logic inputs

24/30 Vdc 48/127 Vdc 220/250 Vdc

power consumption 10 mA 5 mA 4 mA

typical filtering time 5 ms

logic outputs (relays)

breaking capacity (1) 24/30 Vdc 48 Vdc 127 Vdc 220/250 Vdc

contact O1 7 A 4 A 0,7 A 0.3 A

contacts O2 to O5 3.4 A 2 A 0.3 A 0.15 A

making capacity 8 A

permissible steady state current 8 A

number of operations under full load 10 000

response time typical 15 ms(inputs to outputs) max. 25 ms

power supply

range typical consumption maxi consumption inrush current

24/30 Vdc ± 20% 2.5 W 6,5 W < 10 A during 10 ms

48/127 Vdc ± 20% 3.5 W 7.5 W < 10 A during 10 ms

220/250 Vdc - 20%, + 10% 4 W 9 W < 10 A during 10 ms

222

88

Weight : 2.5 kg

Sepam 100

Characteristics (cont’d)

Sepam A (mm)

100 LD 175

100 RT 175

100 MI 55

86 max

202

Cutout

Electrical characteristics Sepam 100 MI

logic inputs

voltage 24/30 V 48/127 V

max. consumption per input 35 mA 34 mA

logic outputs (relays)

voltage 24/30 V 48/127 V

permissible rated current 8 A

breaking DC resistive load 4 A 0.3 Acapacity AC resistive load 8 A 8 A

number of on-load operations 10 000 10 000

power supply

auxiliary power source 24 to 30 V –20% +10%DC or AC current (50 ou 60 Hz) 48 to 127 V–20% +10%

consumption 24 to 30 V: 7.7 VA max. (at 33 V)48 V: 4 VA110 V: 18 VA

Page 23: Protection and control Sepam range Sepam 2000 …ms.schneider-electric.be/OP_MAIN/Sepam/AC0401UK.pdfCommunication Sepam 2000 offers the option of a high performing communication module

23Sepam range

Environmental characteristics

climatic

operation IEC 60068-2 -10 °C to +70 °C (1)

storage IEC 60068-2 -25 °C to +70 °Cdamp heat IEC 60068-2 93 % to +40 °Ccorrosion influence IEC 60654-4 class I

mechanical

degree of protection IEC 60529 IP 51 (2) on front

vibrations IEC 60255-21-1 class I

shocks / jolts IEC 60255-21-2 class I

earthquakes IEC 60255-21-3 class I

fire IEC 60695-2-1 glow wire

isolement électrique

power frequency IEC 60255-5 2 kV - 1 mn

1.2/50 µs impulse wave resistance IEC 60255-5 5 kV

electromagnetic

radiation IEC 60255-22-3 class x 30 V/m

electrostatic discharge IEC 60255-22-2 class III

one-way transients IEC 61000-4-5

1MHz damped oscillating wave IEC 60255-22-1 class III

5 ns fast transients IEC 60255-22-4 class IV

“ ” marking on our product guarantees their conformity to European directives.(1) -5° to +55°C for Sepam 100LD and Sepam 100LA.(2) IP41 for Sepam 100LD.

Electrical characteristics Sepam 100 LD

analog inputs (with plate)

constant current 10 In

3 sec. current 500 In

logic input (remote reset)

voltage 24/250 Vdc 127/240 Vac

maximum power consumption 3.5 W 3.7 VA

logic outputs

constant current 8 A

voltage 24/30 Vdc 48 Vdc 127 Vdc/Vac 220 Vdc/Vac

breaking capacity resistive dc load 7 A 4 A 0.7 A 0.3 A(contact 01) resistive ac load 8 A 8 A

breaking capacity resistive dc load 3.4 A 2 A 0.3 A 0.15 A(contacts 02 à 05) resistive ac load 4 A 4 A

power supply

range consumption when inactive max. consumption inrush current

24/30 Vdc ±20 % 2.5 W 6 W < 10 A for 10 ms

48/125 Vdc ±20 % 3 W 6 W < 10 A for 10 ms

220/250 Vdc -20 %, +10 % 4 W 8 W < 10 A for 10 ms

100/127 Vac -20 % +10 % 6 VA 10 VA < 15 A for 10 ms

220/240 Vac -20 % +10 % 12 VA 16 VA < 15 A for 10 ms

operating frequency 47.5 to 63 Hz

Sepam 100

Page 24: Protection and control Sepam range Sepam 2000 …ms.schneider-electric.be/OP_MAIN/Sepam/AC0401UK.pdfCommunication Sepam 2000 offers the option of a high performing communication module

24 Sepam range

Training your technicians.

Example of a network coordination study.

Tailor-made serviceDeveloping an electrical installation and designing a control-monitoringarchitecture depend not only on making an efficient analysis of the requirementsbut also on finding a technical and economic compromise which is the fruitof experience.

Merlin Gerin has an organization of skilled staff to help you make choicesand confirm solutions. This team has acquired irreplaceable experience by beingconfronted with a wide variety of situations.

They are at your disposal for:

c preliminary network studies and coordination studies,c studies of the architecture of your control monitoring system,c Sepam customization to suit your application,c testing and start-up,,c future installation upgrading and maintenance,c training of your technicians.

These people, who are close by, benefit from training and ongoing support bya group of experts as well as outstanding investigation resources (1) which make itpossible for them to deal with all types of situations and provide the right answerfor your needs.

RetrofitSepam’s customization feature makes it especially competitive for retrofitoperations or for up grading to include a supervision system. Sepam can beintegrated within an existing installation thanks to its flexibility. Adaptation to anytype of sensors programmability, allowing any kind of control scheme.Our service teams are at your disposal to design with your technicianthe necessary adaptation to make your equipment more efficient.

Services

(1) Kirchhoff protection testing laboratory. MORGAT and EMTP network simulation softwareCalculation software (short-circuit current, dynamic stability, etc).

AC0401/7ENART.62386 08/2000

This document has beenprinted on ecological paper.

Schneider ElectricIndustries SA

Postal addressF-38050 Grenoble cedex 9Tel: 33 (0)4 76 57 60 60Telex: merge 320842 Fhttp://www.schneider-electric.com

As standards, specifications and designs change fromtime to time, please ask for confirmation of the informationgiven in this publication.

Publishing: Schneider Electric Industries SADesign, production: IdraPrinting:Rcs Nanterre B 954 503 439