Protection 11

  • Upload
    indra

  • View
    221

  • Download
    0

Embed Size (px)

Citation preview

  • 8/10/2019 Protection 11

    1/43

    Generator & transformer

    Protection

    Hui Ren

    Electrical Engineering Department

    North China Electric Power University

    Source: Power System Protection, Edited by the Electricity Training Association

  • 8/10/2019 Protection 11

    2/43

    2014/11/4 HUI REN @ NCEPU100-2

    Differential protection

    overcurrent protectionEarth fault protection

    Overload protection

    Loss of field protection

    Reverse power protection

    Phaseto phase faults

    interturn faults

    earth faults

    earth faults

    Loss of excitation

    overloading

    Reverse power

    Stator

    faults

    rotor

    faults

    overvoltage

    Abnormal

    conditionOvervoltage protection

    Interturn fault protection

    Generator faults, Abnormal

    Condition and Protection

  • 8/10/2019 Protection 11

    3/43

    2014/11/4 HUI REN @ NCEPU

    100-3

    Overall differential protection for phase-to-

    phase faults

    Overcurrent protection as backup

    protection and protection for earth fault.

  • 8/10/2019 Protection 11

    4/43

    2014/11/4 HUI REN @ NCEPU

    100-4

    (a) Basic differential

    overcurrentrelay

    (b) percentage

    differential relay

    Differential Relay

  • 8/10/2019 Protection 11

    5/43

    2014/11/4 HUI REN @ NCEPU

    100-5

    Percentage-differential relaying for a wye-connected

    generator.

    Differential Relay

  • 8/10/2019 Protection 11

    6/43

    2014/11/4 HUI REN @ NCEPU

    100-6

    Percentage-differential relaying for a delta-connectedgenerator.

    Differential Relay

  • 8/10/2019 Protection 11

    7/43

    2014/11/4 HUI REN @ NCEPU

    100-7

    Percentage-differential relay for

    a generator and transformer unit

  • 8/10/2019 Protection 11

    8/43

    2014/11/4 HUI REN @ NCEPU

    100-8

    Inter-turn fault protection

    Inter-turn fault can not be detected by the Differentialprotection

    Remaining clear of earth, no differential current except fora large current circulating the shorted turns.

    Fault evolving and cleared by other protection If the faults occur in the stator slots, they quickly develop

    into faults to earth, then cleared by the stator earth faultprotection.

    risk If occur at the winding ends, may cause extensive damage

    to the generator before the fault evolves to one detectableby other protection.

  • 8/10/2019 Protection 11

    9/43

  • 8/10/2019 Protection 11

    10/43

    2014/11/4 HUI REN @ NCEPU

    100-10

    High-resistance groundingAdvantages of High-resistance grounding

    reduced thermal and mechanical stress inapparatus carrying ground fault current;

    reduced shock, burn, and flash hazards topersonnel in the vicinity of a ground fault,

    ability to control transient overvoltages due toarcing faults.

    For these reasons, most generators usehigh-resistance grounding.

    Stator Ground Protection

  • 8/10/2019 Protection 11

    11/43

    2014/11/4 HUI REN @ NCEPU

    100-11

    drawbacks of High resistance grounding it complicates the detection of ground

    faults on the stator winding, particularlywhen the fault is close to the neutral.

    Due to the small fault current, thegenerator differential relay is insensitive toa ground fault.

    The differential relay has troubledistinguishing the small fault current fromthe third harmonic current that also flows inthe neutral.

    Stator Ground Protection

  • 8/10/2019 Protection 11

    12/43

    2014/11/4 HUI REN @ NCEPU

    100-12

    Two methods of detecting a short circuit to ground

    Overvoltagerelay

    Stator Ground Protection

  • 8/10/2019 Protection 11

    13/43

    2014/11/4 HUI REN @ NCEPU

    100-13

    100% of Stator ground protection

    Stator Ground Protection

  • 8/10/2019 Protection 11

    14/43

    2014/11/4 HUI REN @ NCEPU

    100-14

    Rotor earth-fault protection

    Utilizing a high resistance connected

    across the rotor circuit, the centre point of

    which is connected to earth through the

    coil of a sensitive relay.

  • 8/10/2019 Protection 11

    15/43

    2014/11/4 HUI REN @ NCEPU

    100-15

    If the prime mover does not produce sufficient torque todrive the generator, the generator may operate as a motordriving the prime mover. Since this is a potentiallydangerous condition for steam turbines, gas turbines,engines, and some hydro turbines, protection is needed.

    The simplest way to provide this protection is with adirectional relay that senses the real (or average) powerflow P, but is insensitive to the reactive flow Q. If the relaydetects P into the generator from the electrical system, thenthe prime mover may have insufficient input power and therelay should trip. The relay may be set to alarm and/or tripafter a time delay of a few seconds.

    Reverse Power Relay

  • 8/10/2019 Protection 11

    16/43

    2014/11/4 HUI REN @ NCEPU

    100-16

    Faults external to the generator are usually cleared quicklyby circuit protection, but failure of remote protection tooperate, or its associated circuit breaker to trip, wouldleave the faulted circuit connected to the genrator.

    Phase to ground and phase to phase short circuits

    unbalanced loads, and unsymmetrical (non-transposed)transmission lines are produce varying degrees of negativesequence current in the generatorso cause the rotoroverheating. Therefore, the negative sequence protection isone of the primary protection.

    the negative sequence relay is a backup protection, since itprimarily protects the generator from faults external to theunit. Because of this, the relay must be coordinated withother relays in the system. Typical relay application is atime-overcurrent relay with a negative-sequence currentmeasuring network

    Negative phase-sequence relay

  • 8/10/2019 Protection 11

    17/43

    2014/11/4 HUI REN @ NCEPU

    100-17

    diagram of a negative phase sequence overcurrent relay

    Negative Sequence Relay

    Negative phasesequence current

    measuring network

  • 8/10/2019 Protection 11

    18/43

    2014/11/4 HUI REN @ NCEPU

    100-18

    Loss of excitation (field failure)

    protection

    Loss of excitation results in a generator losingsynchronism and running above synchronous speed.Operating as an induction generator, it would produceits main flux from wattless stator current drawn fromthe power system to which it was still connected.Excitation under these conditions requirescomponents of reactive current which may wellexceed the rating of the generator and so overload the

    stator winding.

  • 8/10/2019 Protection 11

    19/43

    2014/11/4 HUI REN @ NCEPU

    100-19

    Loss of field (loss of excitation) relays arerecommended for generators. If the generator

    loses its excitation, then it will draw its excitation

    from the electrical system by drawing reactive

    power as what an induction machine would,meaning the generator is supplying real power but

    absorbing reactive power.

    Excitation under these conditions requires

    components of reactive current which may well

    exceed the rating of the generator and so overload

    the stator winding.

    Loss of Field Protection

  • 8/10/2019 Protection 11

    20/43

    2014/11/4 HUI REN @ NCEPU

    100-20

    Loss of Field Protection

    Although loss of field can be damaging to the

    generator, it is also a system problem that causes low

    voltage and resulting in low reactive-power support

    of other nearby generators. In some cases, systeminstability could occur because one machine lost its

    field at a time when the remaining generators were

    heavily loaded with reactive power.

  • 8/10/2019 Protection 11

    21/43

    2014/11/4 HUI REN @ NCEPU

    100-21

    Introduction

    Differential protection

    Percentage differential protection Magnetizing inrush current

    Overcurrent relays

    Pressure relays

    Conclusion

    Transformer Protection Topic

  • 8/10/2019 Protection 11

    22/43

    2014/11/4 HUI REN @ NCEPU

    100-22

    Fault, abnormal condition and protection

    Differential protection

    Overcurrent protection

    Overload protection

    Overfluxing protection

    Overheating protection

    Phase to phase faults

    interturn faults

    Phase to earth faults

    Core fault

    overfluxing

    overheating

    tank fault

    Introduction

  • 8/10/2019 Protection 11

    23/43

    2014/11/4 HUI REN @ NCEPU

    100-23

    Differential protection

    Similar to that of generators, but

    The differential protection system comparesh.v. and l.v. current, which are in a known

    relationship under healthy conditions, ratherthan the same current entering and leavingthe protected apparatus, as for generatorprotection.

    So, it is capable of detecting interturn shortcircuits, since these change the effectiveoverall transformation ratio of the powertransformer.

  • 8/10/2019 Protection 11

    24/43

    2014/11/4 HUI REN @ NCEPU

    100-24

    c.t. connection requirements

    Giving a through fault balance

    No zero-sequence currents;

    Phase shift due to the through transformer of

    positive and negative-sequence currents mustbe compensated;

    Effect of tap changing equipment upon the

    overall transformer ratio.

  • 8/10/2019 Protection 11

    25/43

    2014/11/4 HUI REN @ NCEPU

    100-25

    Two basic requirements that the differential-relay connectionsmust satisfy are:

    (1) the differential relay must not operate for load or

    external faults;

    (2) the relay must operate for severe enough internal faults.

    Differential ProtectionDifferential Protection

  • 8/10/2019 Protection 11

    26/43

    2014/11/4 HUI REN @ NCEPU

    100-26

    Unbalanced currentunbalances between CTs during external faultsarising from an accumulation of unbalances forthe following reasons:

    (1) tap-changing in the power transformer;

    (2) mismatch between CT currents and relay tapratings;

    (3) the difference between the errors of the CTs oneither side of the power transformer;

    (4) the inrush current;

    Differential Protection

  • 8/10/2019 Protection 11

    27/43

    2014/11/4 HUI REN @ NCEPU

    100-27

    the CTs on any

    wye winding of a

    power transformer

    should beconnected in delta,

    and the CTs on

    any delta winding

    should be

    connected in wye.

    Differential Protection

  • 8/10/2019 Protection 11

    28/43

    2014/11/4 HUI REN @ NCEPU

    100-28

    Connections of Two-winding transformer with differentialrelays.

    Percentage (biased) Differential

    Protection

  • 8/10/2019 Protection 11

    29/43

    2014/11/4 HUI REN @ NCEPU

    100-29

    Percentage Differential

    Protection

  • 8/10/2019 Protection 11

    30/43

    2014/11/4 HUI REN @ NCEPU

    100-30

    Problems related to differential relaying of power

    transformersdisturbance measurement Side effects 1 Side effects 2 Side effects 3

    inrush Accurate estimationof the 2ndand the 5thharmonics takes

    around one cycle.

    Due to the magneticof the core, the 2nd

    and the 5thharmonic

    may be jeopardizing

    relay security

    The harmonicsmayblock a relay during

    severe internal faults

    due to saturation of CT

    The means ofrestraining the

    relay from

    tripping during

    external

    faults,inrush and

    overexcitation

    may Limit the

    relay speed ofoperation

    overfluxing The 5thharmonic maybe present in internal

    fault currents due to

    saturation of CT

    External fault The measuredcurrents display

    enormous rate of

    change and are often

    significantly distorted

    The CTs saturation

    during external fault

    may produce an

    extra differential

    signal

    All the means of

    preventing false tripping

    during external faults

    reduce to the

    dependability of the

    relay

    Internal fault The internal currentmay be as low an

    few percent of the

    rated value

    The security demandsunder inrush,

    overexcitation and

    external faults may limit

    relay dependability

  • 8/10/2019 Protection 11

    31/43

    2014/11/4 HUI REN @ NCEPU

    100-31

    the magnetizing inrush may be also caused by

    (a) Initial magnetizing due to switching a

    transformer in.

    (b) occurrence of an external fault, voltagerecovery after clearing an external fault.

    (c) when a phase-to-ground fault evolves into a

    phase-to-phase-to-ground fault

    (d) out-of-phase synchronizing of a connected

    generator.

    Magnetizing Inrush Current

  • 8/10/2019 Protection 11

    32/43

    2014/11/4 HUI REN @ NCEPU

    100-32

    When a transformer is switched-off, the

    magnetizing voltage is taken away, the

    magnetizing current goes to zero while

    the flux follows the hysteresis loop of the

    core. This results in certain residual flux

    left in the core. When, afterwards, the

    transformer is re-energized by analternating sinusoidal voltage, the flux

    becomes also sinusoidal but biased by the

    remaining flux. The residual flux may be

    as high as 80-90% of the rated flux, and

    therefore, it may shift the flux-currenttrajectories far above the knee-point of

    the characteristic resulting in both large

    peak values and heavy distortions of the

    magnetizing current .

    Inrush due to switching-in

  • 8/10/2019 Protection 11

    33/43

    2014/11/4 HUI REN @ NCEPU

    100-33

    Characteristics of the inrush current

    Include a large dc component.Include amounts of higher harmonics , mainly the second harmonic.

    Typical Inrush Current

  • 8/10/2019 Protection 11

    34/43

    2014/11/4 HUI REN @ NCEPU

    100-34

    0

    10

    20

    30

    40

    50

    60

    70

    2nd

    3rd

    4th

    5th

    6th

    7th

    Harmonic components of the

    inrush current

  • 8/10/2019 Protection 11

    35/43

    2014/11/4 HUI REN @ NCEPU

    100-35

    This is a classical way to restrain the relay from tripping during

    magnetizing inrush conditions. As analyzed before, themagnetizing inrush current consists of certain amounts of higherharmonics, but the second harmonic always dominates. Generally,low levels of harmonics indicate internal fault and enabletripping, while high levels indicate inrush and restrain the relay.

    For digital relays this may be written as:

    Where, Id2is the amplitude of the second Harmonic in the

    differential current;

    Id1is the amplitude of the power frequency component in

    the differential current;

    Kis the restraint ratio of the second harmonic, and the

    setting is about 0.15-0.2(15-20%).

    Second Harmonic Restraint

  • 8/10/2019 Protection 11

    36/43

    2014/11/4 HUI REN @ NCEPU

    100-36

    The shape, magnitude and duration of the inrushcurrent depend on several factors:

    Size of a transformer

    Impedance of the system from which a transformer

    is energized

    Magnetic properties of the core material

    Remanence in the core

    The moment when a transformer is switched in

    How a transformer is switched in

    Inrush Current

  • 8/10/2019 Protection 11

    37/43

    2014/11/4 HUI REN @ NCEPU

    100-37

    Sample inrush currents in a three-phase wye-delta connected

    transformers

  • 8/10/2019 Protection 11

    38/43

    2014/11/4 HUI REN @ NCEPU

    100-38

    Inrush currents measured in separate phases of athree-phase transformer may differ considerably

    because of the following:

    The angle of the energizing voltages are

    different in different phases.

    When the delta-connected winding is switched-

    in, magnetizing voltages are line voltages.

    Depending on the core type and other conditions,only some of the core legs may get saturated.

    Inrush in Three Phase

    Transformer

  • 8/10/2019 Protection 11

    39/43

    2014/11/4 HUI REN @ NCEPU

    100-39

    Due to the large and slowly decaying dc component, the inrushcurrent is likely to saturate the CTs even if the magnitude of the

    current is comparatively small. When being saturated, a CT

    introduces certain distortions to its secondary current. Due to

    CTs saturation during inrush conditions, the amount of thesecond harmonic may drop considerably.

    Saturation of current

    transformers during inrush

  • 8/10/2019 Protection 11

    40/43

    2014/11/4 HUI REN @ NCEPU

    100-40

    Overcurrent protection

    High current settingmust not operate

    under emergency loading conditions

    Slow operationtime setting may have to

    be high in order to grade with other

    overcurrent relays on the system

    On large transformersas backup

    protection for terminal faults, or unclearedl.v. system faults.

  • 8/10/2019 Protection 11

    41/43

    2014/11/4 HUI REN @ NCEPU

    100-41

    Various types of mechanical relays such as suddenpressure relays and gas-accumulation relays havebeen used for transformer protection.

    On the occurrence of an internal transformer fault,

    the pressure inside the tank suddenly rises. Thesudden pressure relay senses this, but it isinsensitive to pressure changes that normallyoccur in a transformer during operation. In many

    cases, the pressure relay will operate on aninternal fault that does not produce enough currentto trip the differential relays to avoid catastrophicfailures.

    Pressure Relay

  • 8/10/2019 Protection 11

    42/43

    2014/11/4 HUI REN @ NCEPU

    100-42

    Percentage differential protectionApplication: above 6300KVA

    Magnetizing inrush current

    The cause of magnetizing inrush currentThe characteristics of magnetizing inrush

    current

    The measures of distinguish inrush current

    Overcurrent protection

    Application: external phase-fault protection

    Conclusion

  • 8/10/2019 Protection 11

    43/43

    2014/11/4 HUI REN @ NCEPU

    No matter what the initial conditions are, when excitation is lost, the equivalent

    generator impedance traces a path from the first quadrant into a region of the

    fourth quadrant that is entered only when excitation is severely reduced or lost.By encompassing this region within the relay characteristic, the relay will

    operate when the generator first starts to slip poles and will trip the field breaker

    and disconnect the generator from the system before either the generator or the

    system can be damaged.

    the most common type of lose-of-

    excitation relay is a directional-distance relay measuring the AC

    current and voltage at the main

    generator terminals. Figure shows

    several loss-of-excitation

    characteristics and the operating

    characteristic of one type of loss-of

    excitation relay on an R-X diagram.

    Loss of Field Protection