PROTECT 3.M

15 – 120kVA

Page 2: PROTECT 3.M 15 – 120kVA. PROTECT 3.M the new generation of uninterruptible power supplies (UPS) with 3-phase Mains input and 3-phase Mains output

PROTECT 3.M

the new generation ofuninterruptible power supplies (UPS) with3-phase Mains input and 3-phase Mains output

Page 3: PROTECT 3.M 15 – 120kVA. PROTECT 3.M the new generation of uninterruptible power supplies (UPS) with 3-phase Mains input and 3-phase Mains output

PROTECT 3.M General data

PROTECT 3.M will be offered in two cubicle variances.

Variance 1:Cubicle dimensions: (W x H x D) 600mm x 1600mm x 1000mmMaximum 6 modules each 15kVA = 90kVA per cubicleVariance 2:Cubicle dimensions: (W x H x D) 600mm x 2000mm x 1000mmMaximum 8 modules each 15kVA = 120kVA per cubicle

15kVA per Modul (hot-swappable)Degree of redundancy selectable via DisplayEach Modul is independent , Controllcard/Display are just for Communication and Indication.Integrated Distribution with up to 36 breakers as an optionLCD DisplayCommunication via RS232, RS485, SNMP & AS400

Page 4: PROTECT 3.M 15 – 120kVA. PROTECT 3.M the new generation of uninterruptible power supplies (UPS) with 3-phase Mains input and 3-phase Mains output

PROTECT 3.M General data

1.6 m cubicleMB at the bottom

2.0 m cubicleMB at the top

Page 5: PROTECT 3.M 15 – 120kVA. PROTECT 3.M the new generation of uninterruptible power supplies (UPS) with 3-phase Mains input and 3-phase Mains output

PROTECT 3.M

High MTBF ability

Each UPS module in the Protect 3.M is the full function UPS. There is no additional controlling module to the parallel application and load sharing. Regarding to the serious calculation on the system MTBF, if you have two more UPS modules for parallel redundancy, the system ability is above 99.999% and the MTBF will be close to 15 Million Hours.

MTTR

Once the system has one more UPS module for parallel redundancy, the system will still keepworking if one of the UPS modules fails. If the failed modules exceed the parallel redundancy modules, the module replacement procedure only need 5 minutes for system recover.

Page 6: PROTECT 3.M 15 – 120kVA. PROTECT 3.M the new generation of uninterruptible power supplies (UPS) with 3-phase Mains input and 3-phase Mains output

PROTECT 3.M Battery

Battery

+/- 240Volt DC (20 bloc for each string)Integrated batteriecharger in each Module (2700W / 4.5A)

Battery Management in two stepsStep 1) up to 90% battery capacity constant currentStep 2) above 90% capacity constant voltage

Page 7: PROTECT 3.M 15 – 120kVA. PROTECT 3.M the new generation of uninterruptible power supplies (UPS) with 3-phase Mains input and 3-phase Mains output

PROTECT 3.M Technical data part I

Classification VFI SS 111 acc. to IEC 62040-3 Protect 3.M 1.6m rack Protect 3.M 2.0m rack

Type power 90 kVA 120kVA

  72 kW 96 kW

max. modules per rack 6 8

UPS-input

Input voltage 400 / 230Vac (3/N/PE~)

Input voltage range without battery mode 277 - 520Vac(3ph~)

Frequency 50 Hz / 60Hz

Current consumption (max.)  120A with 6 modules  160A with 8 modules

Power factor > 0.99 at 100% Load

THD(i) <=5%

UPS-output

Rated output voltage 400V ± 2%

Frequency in battery mode 50 Hz ± 0.5%

Output current22 A / per module 132A with 6 modules

22 A / per module 176A with 8 modules

Transfer time at mains outage 0 ms ( zero transfer )

Voltage waveform Sinusoidal

Overload response (online mode) 130% for 10min / 150% for 1min

Crest factor 3

Page 8: PROTECT 3.M 15 – 120kVA. PROTECT 3.M the new generation of uninterruptible power supplies (UPS) with 3-phase Mains input and 3-phase Mains output

PROTECT 3.M Technical data part II

Battery

Nominal voltage

240VDC (40pcs for each set in series connection.One battery neutral wire from the central)

Autonomy time Free to choose runtime extension with scalable external battery.Available configurations with 24,38 or 65 Ah)

Overload / deep discharge protection Yes

Communication  

Interfaces RS232 / RS485 for status and measurement values, Communication slot ( for pot.-free contacts or SNMP adapter)

Shutdown software (on CD) Included for all typical operating systems (e.g. MS-Windows,Novell Netware,Mac OS,Linux,Unix derivates, etc.)

Failure indicators (acoustic/optical) LCD with digital information of input and output parameters (voltage,frequency,power etc.) battery parameter incl. failure diagnosis by password protect level, LED for status and main failures.

Page 9: PROTECT 3.M 15 – 120kVA. PROTECT 3.M the new generation of uninterruptible power supplies (UPS) with 3-phase Mains input and 3-phase Mains output

PROTECT 3.M Technical data part III

General data

Efficiency total > 90%

Audible noise (1m distance) <62 dB

Operating temperature range 0º - 40 ºC

Humidity 20% - 90%

Installation height up to 1000m, at nominal load

Equipment colour RAL 7035

Size approx.W x H x D (mm) 600 x 1600 x 1000  600 x 2000 x 1000

Weight appr. (kg)

250kg rack +35kg per module

300kg rack + 35kg per module

Certification CE

Page 10: PROTECT 3.M 15 – 120kVA. PROTECT 3.M the new generation of uninterruptible power supplies (UPS) with 3-phase Mains input and 3-phase Mains output

PROTECT 3.M · Applications

Single - and multi-user systems

( Workstations, FileServer, Application Server, ... )

Network protection (client / server architecture)

e.g. intranet / internet application

EDP - equipment (CAD - systems, ...)

Communication equipment (IT - sector)

Component protection of telecommunication

Cash systems (trade)

Other user-critical applicationen

(process systems (stored-program contoller, ... ))

Page 11: PROTECT 3.M 15 – 120kVA. PROTECT 3.M the new generation of uninterruptible power supplies (UPS) with 3-phase Mains input and 3-phase Mains output

PROTECT 3.M · conceptual highlights

Modularity with UPS plug-in modules

in VFI (double-conversion) technology

n + x technology

free choice of redundancy level

scalable design for flexible

power- / autonomy time requirements

central simplified management

more efficient service

independent UPS - modules

(without any central control logic)

Page 12: PROTECT 3.M 15 – 120kVA. PROTECT 3.M the new generation of uninterruptible power supplies (UPS) with 3-phase Mains input and 3-phase Mains output

PROTECT 1.M · UPS classes

Publication by ZV

EI: U

PS

Guide

........... by additional lightning arrestors

Voltage Phenomenon Time e. g. IEC UPS solution 62040-3

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

Outage - blackouts

Sags / brownouts

Dynamic overvoltage

Undervoltage

Overvoltage

Lightning

Transients (Surge)

Frequency variations

Voltage distortion (Burst)

Voltage harmonics

> 10 ms

continuous

continuous

sporadic

< 4 ms

sporadic

periodic

continuous

VFD

Voltage +FrequencyDependent

VIVoltage

Independent

VFI

Voltage +Frequency

Independent

Classification 3

Offline

Classification 2

LineInteractive

Classification 1

(true) Online

real Double-Conversion

Page 13: PROTECT 3.M 15 – 120kVA. PROTECT 3.M the new generation of uninterruptible power supplies (UPS) with 3-phase Mains input and 3-phase Mains output

Protect 3.M System architecture

Integrated Distribution with up to 36 breakers as an option

Communication module incl. communication port

LCD-Display

UPS-modules each 15kVA

Page 14: PROTECT 3.M 15 – 120kVA. PROTECT 3.M the new generation of uninterruptible power supplies (UPS) with 3-phase Mains input and 3-phase Mains output

PROTECT 3.M · UPS module design

Inverter

Battery system

Rectifier

Load

Mains

Electronicstatic bypass

~

~

Battery charger

~

PFC

Filter

Mains

filter

DSP / CanBus

control logic unit

RS232

SNMP

DC/DC Booster

High power reserves as a result of a max. 24 kVAtotal output

High safety reserves asa result of n+x technology

Independent UPS modules (no central control) slide-in types; suitable for rackmount

Diagram of an UPS PROTECT module :

Page 15: PROTECT 3.M 15 – 120kVA. PROTECT 3.M the new generation of uninterruptible power supplies (UPS) with 3-phase Mains input and 3-phase Mains output

PROTECT 3.M · n + x technology · redundancy level

n + x technology

advantage

n + x technology

advantage

Quantity of UPS modules 1 2 3 4 5 6 7 8

Load modul modules modules modules modules modules modules modules

15 kVA

noredundancy n + 1

(15 kVA)n + 2

(30 kVA)n + 3

(45 kVA)n + 4

(60 kVA)n + 5

(75 kVA)n + 6

(90 kVA)n + 7 (105 kVA)

30 kVA  no

redundancyn + 1

(15 kVA)n + 2

(30 kVA)n + 3

(45 kVA)n + 4

(60 kVA)n + 5

(75 kVA)n + 6

(90 kVA)

45 kVA    no

redundancyn + 1

(15 kVA)n + 2

(30 kVA)n + 3

(45 kVA)n + 4

(60 kVA)n + 5

(75 kVA)

60 kVA - - -    no

redundancyn + 1

(15 kVA)n + 2

(30 kVA)n + 3

(45 kVA)n + 4

(60 kVA)

75 kVA   - - -    no

redundancyn + 1

(15 kVA)n + 2

(30 kVA)n + 3

(45 kVA)

90 kVA     - - -    no

redundancyn + 1

(15 kVA)n + 2

(30 kVA)

105 kVA       - - - - - - - - -no

redundancyn + 1

(15 kVA)

120 kVA             - - -no

redundancy

Higher reliability

Easy to increase overall capacity

Modules hot - swapable (without any interruption)

Page 16: PROTECT 3.M 15 – 120kVA. PROTECT 3.M the new generation of uninterruptible power supplies (UPS) with 3-phase Mains input and 3-phase Mains output

Protect 3.M Usage >> Delivery

Cubicle packing

Module packing

Page 17: PROTECT 3.M 15 – 120kVA. PROTECT 3.M the new generation of uninterruptible power supplies (UPS) with 3-phase Mains input and 3-phase Mains output

Protect 3.M - Mains connection

Mains Battery Load

Page 18: PROTECT 3.M 15 – 120kVA. PROTECT 3.M the new generation of uninterruptible power supplies (UPS) with 3-phase Mains input and 3-phase Mains output

PROTECT 3.M – LCD display

Appear „green light“

Appear „yellow light“

Appear „yellow light“

Appear „red light“and warning alarm

Page 19: PROTECT 3.M 15 – 120kVA. PROTECT 3.M the new generation of uninterruptible power supplies (UPS) with 3-phase Mains input and 3-phase Mains output

PROTECT 3.M Communication interface

“Dual monitoring“ interfacefrom left to the right:

- RS485- RS485- RS232- RS485

- Expansible

AS/400 card with potential-free contacts

SNMP / SNMP PRO card (with connector for additional temperature measurements)

Page 20: PROTECT 3.M 15 – 120kVA. PROTECT 3.M the new generation of uninterruptible power supplies (UPS) with 3-phase Mains input and 3-phase Mains output

PROTECT 3.M SNMP-Adapter

SNMP Slot-Adapter for UPS Features:

Agent for RFC1628 MIB UPS standard MIB

Embedded Web-Server Monitoring via Web

Configuration via Web

Embedded Event Manager Start of different Jobs

Net Broadcast

E-Mail

Monitoring of environmental conditions Temperature, Humidity, GenSet, Fire, Air

condition, Smoke shutter...

Support Software products Network Management Software „NMS“

NMS special for Power Supply Systems

Shutdown Software “CompuWatch”

Direct multi-server shutdown of different OS with communication modules

SNMP Adapter Pro: 6000001271SNMP Adapter: 6000004036

Page 21: PROTECT 3.M 15 – 120kVA. PROTECT 3.M the new generation of uninterruptible power supplies (UPS) with 3-phase Mains input and 3-phase Mains output

PROTECT 3.M AS/400 slotcard

Pin 1: UPS FaultBattery below cutoff voltage

Pin 2: Summary Alarm:UPS failure, Utility power failure, Battery low

Pin 3 and 4: Short from Pin 3 to 4 generates an UPS shutdown,e.g. by installing an external switch for EPO.

Pin 5: Common ground for relays (pins 1, 2, 6, 7, 8 und 9)Pin 6: Bypass active; mains operationPin 7: Battery low

Battery voltage is below the predetermined levelPin 8: UPS on; normal operation

(relay closed during normal operation)Pin 9: Utility Failure; battery operation

Attention ! Contact load rating: AC / DC 24 V / 0,5 A

Pin-assignment

Description

1 UPS Failure

2 Summary alarm (signal of pins 1, 7and 9)

3 Emergency shutdown, e.g. connection of an external switch for EPO (closer)

4

5 Common ground for pins 1, 2, 6, 7, 8 und 9

6 Bypass active

7 Battery low

8 UPS on

9 Utility Failure

Page 22: PROTECT 3.M 15 – 120kVA. PROTECT 3.M the new generation of uninterruptible power supplies (UPS) with 3-phase Mains input and 3-phase Mains output

UPS system: PROTECT 3.M

Graphical front-end of CompuWatch Normal operation

Page 23: PROTECT 3.M 15 – 120kVA. PROTECT 3.M the new generation of uninterruptible power supplies (UPS) with 3-phase Mains input and 3-phase Mains output

PROTECT 3.M