GEOTECHNICAL INVESTIGATION
TERMS Concrete & Materials
Testing Laboratory Inc.#19 L. Intalan St., Bagong Ilog, Pasig City.
Tel # 6559785 / 470-5412
FINAL REPORT
ON
" PROPOSED PAMPANGA RIVER
SLOPE PROTECTION WORKS AT SAN
ESTEBAN CUT - OFF CHANNEL
PALIMPI ( PHASE 1 ) "
Masantol Pampanga
DPWH REGION 3
DPWH-BRS Accredited Laboratory
Cordon Isabela
Page
I. INTRODUCTION 1
II. FIELD INVESTIGATION 2
III. LABORATORY TESTING 2-4
IV. RESULTS OF FIELD AND LABORATORY TESTING 5
V. 5-7
A. Shallow Strip Foundation 5
B. Lateral Earth Pressure 5-6
C. Slope Stability 7
D. Mat Foundation with Underlying Soil Improvement 7
LIMITATIONS 8
Appendices
Final Boring Log
Laboratory Test Results
Drilling Photos
Bussiness Permit and License
Geotechnical Engineer's P. T. R.
FINAL REPORT
GEOTECHNICAL INVESTIGATION
" PROPOSED PAMPANGA RIVER SLOPE PROTECTION WORKS AT SAN ESTEBAN CUT - OFF CHANNEL
PALIMPI ( PHASE 1 ) "
Masantol Pampanga
TABLE OF CONTENTS
EVALUATION / RECOMMENDATIONS FOR LATERAL EARTH PRESSURE
ANALYSIS, SLOPE STABILITY and FOUNDATION DESIGN
Appendix D
Section
Appendix E
ATTACHMENTS
Appendix A
Appendix B
Appendix C
Page 1 of 8
EVALUATION OF GEOTECHNICAL CONDITIONS for the
PROPOSED PAMPANGA RIVER SLOPE PROTECTION WORKS AT SAN
ESTEBAN CUT - OFF CHANNEL PALIMPI ( PHASE 1 )
Masantol Pampanga
INTRODUCTION
This assessment of the geotechnical conditions in the above-mentioned project site is based on the findings gathered from the field and laboratory works conducted by Terms Concrete Testing. It is understood that the subsurface exploration program is to be intended for a revetment project. Included in this report are recommendations on design parameters for lateral earth pressure coefficients for slope stability analysis and design. One borehole at 34.50m depth were drilled for the soil exploration program. During drilling of soil-type material, Standard Penetration Test (SPT) and soil sampling were undertaken at regular interval of 1.5m. Upon encountering rock-type formation, the coring procedure would then be employed to penetrate through the hard strata and extract samples. The retrieved soil and/or rock samples were taken to the soil laboratory for various laboratory tests.
Page 2 of 8
II. FIELD INVESTIGATION
The field investigation consisted of drilling boreholes with Standard Penetration Test for the boreholes. The boreholes were advanced by wash boring to the specified boring depths. The SPTs, conducted at every 1.5 meter interval, consisted of driving a standard split spoon sampler of 5.08 cm (2 inches O.D.) diameter in three successive segments of 15 cm (6 inches) using a freely falling drop hammer of 63.6 kg (140 lbs) weight from a height of 76.2 cm (30 inches). The number of blows required to penetrate the three 15-cm layers are recorded. The blow counts of the last two layers are added to give the N-value of a particular 45cm stretch, a measure of density or consistency of the soil. SPT procedures are conducted in accordance to ASTM D-1586. Soil samples were retrieved using the spoon sampler. When very hard material including gravel and rock formation are encountered, coring procedure is employed. For rock-type samples, Rock-Quality Designation (RQD) was applied in describing their properties. RQD is a measure of the degree of jointing or fracture in a rock mass that is measured as a percentage of the drill core in lengths of 10 cm or more. High-quality rock has an RQD of more than 75% while low quality of has less than 50%. All the recovered soil samples and cored samples were brought to the soil laboratory for further testings.
III. LABORATORY TESTING Retrieved soil or cored samples from every 1.5m depth were subjected to the following laboratory tests in conformance with the procedures given in the current ASTM standards as described below: Grain Size Analysis as per ASTM D422 Sieve analyses were performed to determine the gradational characteristics of the soil in order to come up with soil classification information
Page 3 of 8
Determination of Moisture Content as per ASTM D2216 The method determines the water (moisture) content of soil by weight. Moisture content of soil is the ratio of the mass of pore water in a given soil mass to the mass of the solid material particles, given in percentage. Atterberg Limit Test as per ASTM D4318 (for plastic material) Atterberg Limits test of fine grained (i.e., clayey or silty) material were performed to come up with soil classification data and to determine moisture content at which the behavior of soil changes. Liquid Limit of Soils The liquid limit of soil is the water content (percentage in weight) of the oven-dried soil after reaching the condition between the liquid and plastic states. Plastic Limit of Soils The plastic limit of soil is the water content (percentage in weight) of the oven-dried soil after reaching the condition between the plastic and semi-solid states. Plasticity Index of Soils The plasticity index is defined as the difference between the liquid and plastic limits of the soil. Soil Classification Tests as per ASTM D2487 The soil samples were classified based on the Unified Soils Classification System (ASTM 2487) which is a universal format in identifying and classifying soil materials. Based on laboratory determination of particle size characteristics, liquid limit and plasticity index, the standard classifies mineral and organo-mineral soils for engineering purposes. Unconfined Compression Test ASTM D2938 Unconfined Compression Test (UCT) is a method in determining the mechanical properties of rocks and fine-grained soils. It gives a measure of the undrained strength and the stress-strain characteristics of the rock or soil. It is customary to include the unconfined compression test in the laboratory test program of geotechnical investigation specially when dealing with rocks. It should be noted that no UCTs were performed for rock samples which did not pass the requirement as test specimen, e.g. not intact sample to fulfill the specified dimensioning. Further, rock properties are identified through the following measures:
Page 4 of 8
Total core recovery (TCR)
TCR is the borehole core recovery percentage, defined as the quotient:
lsum of pieces = Sum of length of core pieces ltotal core run= Total length of core run
Rock Quality Designation (RQD) RQD is an approximate measure of the degree of jointing or fracture in a rock mass, measured as a percentage of the drill core in lengths of 100 mm or more. High-quality rock has an RQD of more than 75% while low quality of less than 50%. Whereas rock quality designation could have several definitions, a popular definition was developed in 1964 by D. U. Deere wherein it is the borehole core recovery percentage incorporating only pieces of solid core that are longer than 100 mm in length measured along the centerline of the core. As such, pieces of core that are not competent (hard and sound) should not be counted inspite of being 100 mm in length.
RQD is defined as the quotient:
lsum of pieces = Sum of length of core sticks longer than 100 mm measured along
the center line of the core ltotal core run= Total length of core run
From the RQD index the rock mass can be classified as follows:
RQD Rock mass quality
<25% very poor
25-50% Poor
50-75% Fair
75-90% Good
90-100% Excellent
Page 5 of 8
IV. RESULTS OF FIELD AND LABORATORY TESTING
The results of the borehole are generally represented below; BH 1 GWT: -9.0m
Depth,m USCS
Classification
Remarks (Relative Condition /
Consistency)
0.0 – 24.0/25.0 CH Very Soft-Stiff
25.0-34.0 SM Loose-Very Dense
V. EVALUATION / RECOMMENDATIONS FOR LATERAL EARTH PRESSURE ANALYSIS, SLOPE STABILITY and FOUNDATION DESIGN
A. Shallow Strip Foundation Using an isolated footing scheme with a minimum recommended embedment depth of 3.0m, the following values could be employed:
The above values are governed by either the limiting settlement magnitude of 25mm or shear capacity failure depending on the depth. Further, the recommended values are applicable to footing width of not more than 2.5m. B. Lateral Earth Pressure The ff. geotechnical parameters are recommended for lateral earth pressure analysis:
Embedment Depth Allowable Bearing Capacity for
Strip Foundation
3.0m 25 kPa
3.5m 35 kPa
4.0m 55 kPa
Page 6 of 8
SANDY Materials
Characteristic Very Loose Loose Medium
Dense Dense to
Very Dense
Φ (degree) 27.5 30.0 32.5 35.0-37.5
Y/ γ’ (Kn/m3) 17/9 18/10 19/11 19/11
Cu (Undrained)
(kPa)
0 0 0
0
C (kPa) 0 0 0 0
Poisson’s Ratio
(Saturated)
0.35-0.4 0.3-0.4 0.3
0.3
Poisson’s Ratio
(Unsaturated)
0.35-0.40 0.3-0.4 0.3-0.4
0.30
Ka 0.37 0.33 0.30 0.24-0.27
Kp 2.74 3.0 3.22 3.68-4.11
Es (MN/m2) 3-5 7-12 12-20 20-70
CLAYEY Materials
Characteristic Very Soft Soft Firm Medium
Stiff to Stiff Very Stiff to Very Hard
Φ (degree) 12.5 17.5 18 20.0 25-30
Y/ γ’ (Kn/m3) 16/6 17/7 18/8 18/8 19/9 to 22/12
Cu (Undrained)
(kPa)
4-8
10-25
20-40 25-50
50-200
C (kPa) 1-2 4-10 10-15 15-20 25
Poisson’s Ratio
(Saturated)
0.1-0.2
0.1-0.3
0.-0.3 0.1-0.3
0.1-0.3
Poisson’s Ratio
(Unsaturated)
0.5
0.4-0.5
0.40-0.5 0.40-0.5
0.40-0.5
Ka 0.64 0.54 0.52 0.41-0.49 0.41-0.33
Kp 1.55 1.86 1.90 2.04 2.46-3.0
Es (MN/m2) 1-2 2-5 3-5 5-20 20-70
Page 7 of 8
C. Slope Stability Possible slope stability solutions can be any of the ff methods:
Mechanically Stabilized Earth (MSE)
Soil Nailing
Rock Anchor
Sheet Pile with tie back anchors
Retaining Wall
Revetment Wall The adequate engineering measure for slope stabilization depends on the terrain, slope angle, location of critical slip circle, etc. Use of Slope Stability Charts for preliminary analysis of locating the slip circle is recommended. An example of a well-known Slope Stability Chart can be found on the Appendix of Soil Strength and Slope Stability (2005) by Duncan & Wright. However, for a detailed analysis, use of Finite Element software is recommended. Finite Element software can analyze multiple locations of critical slip surfaces in the slope and take into consideration factors such as seepage, rapid drawdown etc. A good drainage system is also recommended to control the flow of water away from the structure / slope. As excess pore water pressure may develop in the slope and more often than not, can cause slope failure. D. Mat Foundation with Underlying Soil Improvement If the above recommendation does not suffice or is impractical, mat foundation with underlying soil improvement can be employed. The following soil improvement systems can be applied:
1) Jet-grouted Columns 2) Soil-Cement Columns 3) Stone Columns 4) (Micropiles)
Specialist contractors can propose detailed design based on the actual slab footprint and loading.
Page 8 of 8
LIMITATIONS The foregoing assessment and recommendations are based on the prevailing exploration and laboratory results. Should there be significant differences in the soil stratification encountered during the construction stage, the undersigned should be informed immediately so that necessary supplemental recommendations can be made.
MIGUEL DIMADURA, M CivEng Consulting Geotechnical/Sub-Structural Engineer PRC CE Reg. 59571
GEOLOGIC SETTING
A. Lithology
The study area is part of the delta of the Pampanga River which is located in the northern bounds of
the Manila Bay. The Pampanga River delta forms a shallow coastal area that is adjacent to the
Central Luzon Valley Basin. Underlying the delta are thick layers of sedimentary deposits of mud,
clay, sand and silt that originate from the Central Luzon Valley, southern slopes of the Caraballo
Mountains and the western slopes of Sierra Madre. Beneath the Quaternary deposits in the delta is
the Guadalupe Formation. The Guadalupe Formation is divided into two members – Alat
Conglomerate and Diliman Tuff. The Alat Conglomerate is the lower member which is characterized
by a sequence of conglomerate, sandstone and mudstones with approximately 200m thickness.
Diliman Tuff is the upper member and characterized by bedded deposits of fine vitric tuff, welded
pyroclastic breccias and tuffaceous sandstones. Approximate thickness of the Diliman Tuff is around
1300-2000 meters.
B. Tectonic Structures
Active faults closest to the area of interest are the West Valley Fault and East Zambales Fault. West
Valley Fault is part of the Valley Fault System which is a 135 km long dextral (right lateral strike-slip)
tectonic feature, trending north-south originating from the Angat area in Bulacan and terminating in
Tagaytay Ridge. Offset-based magnitude estimates for the West Valley fault is approximately M7.3 -
7.7 (Rimando, 2006). The trace of the West Valley Fault is located approximately 42 km southeast
from the study area .
The East Zambales Fault is a strike-slip fault present at the eastern footslopes of the Zambales Range
with 110 km length and 26 km in width (Japan International Cooperation Agency, 2004). Magnitude
estimates indicate that movement along the East Zambales Fault can generate an earthquake with
7.4 magnitude. The trace of the East Zambales Fault is located approximately 38 km north-northwest
of the study area. Figure 1 shows the location of the study area with respect to the active faults
present.
EARTHQUAKE HAZARDS
A. Ground Shaking
Ground shaking is the most immediate effect caused by earthquakes which can be accompanied by
surface rupture and displacements. The Philippine Institute of Volcanology and Seismology
(PHIVOLCS) used a deterministic model to determine the extent of ground shaking that can occur
during an earthquake event. The deterministic model was based on the work of Fukushima (1990)
which measures the horizontal peak ground acceleration at a geographical point based on its
distance from the fault rupture and wave magnitude of the earthquake event. Based on the model,
an earthquake event with 7.2 magnitude and propagated along the West Valley Fault would
generate a peak ground of acceleration of 0.20 – 0.30 g in the study area (Figure 2). An earthquake
event with magnitude 7.4 and propagated along the East Zambales Fault can generate a horizontal
peak ground acceleration of 0.15 – 0.25 g in the study area (Figure 3).
B. Liquefaction
Liquefaction is the transformation of water-saturated, unconsolidated granular material to a more
fluid like mass due to intense ground shaking. During liquefaction, sediments are compacted, losing
their strength and assuming a more liquid behavior resulting to structures built on top of liquefied
sediments to sink or tilt. The risk of liquefaction is more pronounced in areas underlain by
Quaternary Alluvium. The study area is exposed to high susceptibilities of liquefaction due to the
unconsolidated layers of sediments that underlie it.
Figure 1. Location map of the study area with respect to the East Zambales Fault and the West Valley Fault
Figure 2. Distribution of horizontal peak ground acceleration values caused by a Magnitude 7.2 earthquake event generated along the West Valley Fault. Map modified from PHIVOLCS (n.d)
Study Area
East Zambales Fault
West Valley Fault
Study Area
References:
Fukushima, Y., Tanaka T., 1990, A New Attenuation Relation for Peak Horizontal Acceleration of Strong
Earthquake Ground Motion in Japan, Bull. Seism. Soc. Am., Vol. 80, No. 4, 757-783.
Japan International Cooperation Agency. (2004). Metro Manila Earthquake Impact Reduction Study.
Retrieved from
http://ndrrmc.gov.ph/attachments/article/1472/Earthquake_Impact_Reduction_Study_Volu
me2.PDF
Peña, R., & Aurelio, M. (2005). Geology and Mineral Resources of the Philippines. Quezon City: Department of Environment and Natural Resources.
Philippine Institute of Volcanology and Seismology (Cartographer). (n.d). Rapid Earthquake Damage Assessment System (REDAS) [map].
Rimando, R. (2006). Neotectonics of Marikina Valley Fault System and Tectonic Framework of
Structures in Northern and Central Luzon, Philippines. Tectonophysics, 17-38.
Study Area
Figure 3. Distribution of horizontal peak ground acceleration values caused by a Magnitude 7.4 earthquake event generated along the East Zambales Fault. Map modified from PHIVOLCS (n.d)
BOREHOLE LOCATION PLANDRAWN NOT TO SCALE
CONTROL NUMBER
DRILLED BY
DATE STARTED
DATE FINISHED
WEATHER
ENCODED BY
0.00
#4 100.00 LL= 65.80
#10 100.00 PL= 31.14
#40 94.93 PI= 34.66
1.50 1.50 SPT NO REC SS-1 - #200 86.29
#4 100.00 LL= 65.90
#10 100.00 PL= 31.73
#40 93.00 PI= 34.17
3.00 3.00 SPT NO REC SS-2 - #200 82.02
#4 100.00 LL= 64.20
#10 100.00 PL= 31.00
#40 94.82 PI= 33.20
4.50 4.50 SPT 0.35 SS-3 - 5 5 4 9 #200 86.06
#4 100.00 LL= 63.70
#10 100.00 PL= 31.35
#40 94.35 PI= 32.35
6.00 6.00 SPT 0.35 SS-4 - 5 4 3 7 #200 85.09
#4 100.00 LL= 62.80
#10 100.00 PL= 30.77
#40 95.45 PI= 32.03
7.50 7.50 SPT NO REC SS-5 - #200 87.03
#4 100.00 LL= 64.70
#10 100.00 PL= 31.42
#40 94.92 PI= 33.28
9.00 9.00 SPT NO REC SS-6 - #200 86.02
#4 100.00 LL= 69.20
#10 100.00 PL= 32.46
#40 94.38 PI= 36.74
10.50 10.50 SPT NO REC SS-7 - #200 84.37
#4 100.00 LL= 66.20
#10 100.00 PL= 31.68
#40 95.97 PI= 34.52
12.00 12.00 SPT NO REC SS-8 - #200 89.09
#4 100.00 LL= 67.30
#10 100.00 PL= 32.04
#40 94.31 PI= 35.26
13.50 13.50 SPT NO REC SS-9 - #200 85.24
#4 100.00 LL= 66.30
#10 100.00 PL= 32.09
#40 94.25 PI= 34.21
15.00 15.00 SPT NO REC SS-10 - #200 85.00
#4 100.00 LL= 67.40
#10 100.00 PL= 32.04
#40 94.35 PI= 35.36
16.50 16.50 SPT NO REC SS-11 - #200 85.09
#4 100.00 LL= 69.50
#10 100.00 PL= 32.04
#40 92.67 PI= 37.46
18.00 18.00 SPT NO REC SS-12 - #200 82.46
#4 100.00 LL= 68.60
#10 100.00 PL= 32.00
#40 93.46 PI= 36.60
19.50 19.50 SPT NO REC SS-13 - #200 85.00
#4 100.00 LL= 63.70
#10 100.00 PL= 31.13
#40 93.75 PI= 32.57
21.00 21.00 SPT NO REC SS-14 - #200 83.40- -
COHESIVE SOILS COHENSIONLESS SOILS
N - VALUES CONSISTENCY N - VALUES CONSISTENCY
CH-Silty CLAY MH-Clayey SILT 0 - 2 VERY SOFT 0 - 4 VERY LOOSE
ML-Sandy SILT SW-Well Graded SAND 3 - 4 SOFT 5 - 10 LOOSE
SM-Silty SAND 5 - 8 FIRM 11 - 30 MEDIUM DENSE
SP-Poorly Graded SAND 9 - 15 STIFF 31 -50 DENSE
SP-SM-Poorly Graded SAND with silt 16 - 30 VERY STIFF >50 VERY DENSE
SW-SM-Well Graded SAND with silt > 30 HARD
GRADING
% PASSING
SUNNY DAY
CH
CH
CH
ATTERBERG
CH
CH
CH
CLASSIFICATION
UNIFIED
PROPOSED PAMPANGA RIVER SLOPE PROTECTION WORKS AT SAN ESTEBAN CUT -
OFF CHANNEL PALIMPI ( PHASE 1 )
PROJECT LOCATION Masantol Pampanga
Peter John Pasculado
15-Sep-19
13-Sep-19
I.Espaldon
CLIENT
PROJECT NAME
DPWH REGION 3
9.00m
34.50m
FINAL BORING LOG
CH
CH
CH
CH
Firm, brownish gray silty
CLAY of high plasticity.
Very soft, brownish gray
silty CLAY of high plasticity.
Very soft, brownish gray
silty CLAY of high plasticity.
Very soft, brownish gray
silty CLAY of high plasticity.
Very soft, brownish gray
silty CLAY of high plasticity.
Very soft, brownish gray
silty CLAY of high plasticity.
Very soft, brownish gray
silty CLAY of high plasticity.
Very soft, brownish gray
silty CLAY of high plasticity.
Very soft, brownish gray
silty CLAY of high plasticity.
CH
CH
Very soft, brownish gray
silty CLAY of high plasticity.
LEGENDS, SYMBOLS, AND
RANGE OF VALUES
STANDARD
PENETRATION
TEST
20.55
CORINGUNDISTURBED
SAMPLING
Very soft, brownish gray
silty CLAY of high plasticity.
CH
CH
HAMMER WEIGHT
HAMMER WEIGHT
17.55
14.55WASH
BORING
16.05
WASH
BORING
13.05
WASH
BORING
8.55
WASH
BORING
10.05
11.55
WASH
BORING
WASH
BORING
HAMMER WEIGHT
HAMMER WEIGHT
Stiff, brownish gray silty
CLAY of high plasticity.
Very soft, brownish gray
silty CLAY of high plasticity.
HAMMER WEIGHT
REC.
(m)
Very soft, brownish gray
silty CLAY of high plasticity.
HAMMER WEIGHT
1.05WASH
BORING
SAMPLE
N0.DEPTH SOIL DESCRIPTION
SPT BLOWS
PER 15 CM
SAMPLING
DEPTH
TYPE OF
SAMPLING
N.
VALUE
BOREHOLE NO. BH-1
FINAL DEPTH
RQD
(%)
N - VALUE (GRAPHICAL)
GROUND WATER LEVEL
WASH
BORING
2.55WASH
BORING
7.05WASH
BORING
5.55WASH
BORING
4.05
WASH
BORING
19.05
WASH
BORING
WASH
BORING
HAMMER WEIGHT
HAMMER WEIGHT
HAMMER WEIGHT
HAMMER WEIGHT
HAMMER WEIGHT
HAMMER WEIGHT
0 20 40 60 80 100
Encoded By:
I.Espaldon Jr. Laboratory Technician/Encoder
Certified By:
M. CUNAHAP Laboratory Head
BH-1
CONTROL NUMBER
DRILLED BY
DATE STARTED
DATE FINISHED
WEATHER
ENCODED BY
#4 100.00 LL= 64.40
#10 100.00 PL= 30.69
#40 95.69 PI= 33.71
22.50 22.50 SPT NO REC SS-15 - #200 87.07
#4 100.00 LL= 62.80
#10 100.00 PL= 30.82
#40 93.51 PI= 31.98
24.00 24.00 SPT NO REC SS-16 - #200 84.13
#4 100.00 LL= -
#10 96.78 PL= NP
#40 83.24 PI= -
25.50 25.50 SPT 0.35 SS-17 - 2 3 4 7 #200 23.49
#4 100.00 LL= -
#10 97.40 PL= NP
#40 85.56 PI= -
27.00 27.00 SPT 0.35 SS-18 - 4 3 4 7 #200 31.36
#4 100.00 LL= -
#10 97.14 PL= NP
#40 84.68 PI= -
28.50 28.50 SPT 0.35 SS-19 - 7 5 6 11 #200 27.19
#4 100.00 LL= -
#10 96.35 PL= NP
#40 81.97 PI= -
30.00 30.00 SPT 0.35 SS-20 - 11 11 13 24 #200 22.71
#4 100.00 LL= -
#10 96.61 PL= NP
#40 82.75 PI= -
31.50 31.50 SPT 0.35 SS-21 - #200 24.54
#4 100.00 LL= -
#10 96.68 PL= NP
#40 81.91 PI= -
33.00 33.00 SPT 0.35 SS-22 - #200 19.86
#4 100.00 LL= -
#10 96.84 PL= NP
#40 84.58 PI= -
34.50 34.50 SPT 0.35 SS-23 - #200 28.06
COHESIVE SOILS COHENSIONLESS SOILS
N - VALUES CONSISTENCY N - VALUES CONSISTENCY
CH-Silty CLAY MH-Clayey SILT 0 - 2 VERY SOFT 0 - 4 VERY LOOSE
ML-Sandy SILT SW-Well Graded SAND 3 - 4 SOFT 5 - 10 LOOSE
SM-Silty SAND 5 - 8 FIRM 11 - 30 MEDIUM DENSE
SP-Poorly Graded SAND 9 - 15 STIFF 31 -50 DENSE
SP-SM-Poorly Graded SAND with silt 16 - 30 VERY STIFF >50 VERY DENSE
SW-SM-Well Graded SAND with silt > 30 HARD
SMMedium dense, gray silty
SAND fine grained non
plastic.
Medium dense, gray silty
SAND fine grained non
plastic.SM
28.05WASH
BORING
Very dense, gray silty SAND
fine grained non plastic.
29.55WASH
BORING
CH
GRADING
LEGENDS, SYMBOLS, AND
RANGE OF VALUESSTANDARD
PENETRATION
TEST
UNDISTURBED
SAMPLING
Loose, gray silty SAND fine
grained non plastic.
Very dense, gray silty SAND
fine grained non plastic.
SM
Very soft, brownish gray
silty CLAY of high plasticity.
Loose, gray silty SAND fine
grained non plastic.
SAMPLE
N0.
RQD
(%)
CORING
SM
CH
CLASSIFICATION
UNIFIEDATTERBERG
I.Espaldon
Peter John Pasculado
% PASSING
TYPE OF
SAMPLING
REC.
(m)
22.05WASH
BORING
BOREHOLE NO. 13-Sep-19
SUNNY DAY9.00m
26.55WASH
BORING
15-Sep-19
PROJECT NAMEPROPOSED PAMPANGA RIVER SLOPE PROTECTION WORKS AT SAN ESTEBAN CUT -
OFF CHANNEL PALIMPI ( PHASE 1 )
DPWH REGION 3
WASH
BORING
FINAL DEPTH
PROJECT LOCATION
34.50m
Masantol Pampanga
25.05
WASH
BORING
SAMPLING
DEPTHSOIL DESCRIPTION
N.
VALUE
SPT BLOWS
PER 15 CM
Very soft, brownish gray
silty CLAY of high plasticity.
CLIENT
N - VALUE (GRAPHICAL)
DEPTH
GROUND WATER LEVEL
23.55
31.05WASH
BORING
FINAL BORING LOG
SM
SM
34.05WASH
BORING
Very dense, gray silty SAND
fine grained non plastic.SM
50/15
32.55WASH
BORING
50/15
50/15
HAMMER WEIGHT
HAMMER WEIGHT
BH-1
0 20 40 60 80 100
Encoded By:
I.Espaldon Jr. Laboratory Technician/Encoder
Certified By:
M. CUNAHAP
Laboratory Head
BH-1
9-5-19/9-13-19
DATE DRILLED
TCT 10/10/2019
OFFICE DATE RECEIVE
TCT 10-11-19/10-14-19
OFFICE DATE TEST
Original Wt., gms: 202.4
Oven Dry Wt., gms: 145.9
Wash O.D. Wt., gms: 20.2
INCH / NO. MM.
WT.
PASSING
gms
% PASSING% RETAINED
1-1/2" 37.5 0.0 145.90 100.00 0.00
1" 25 0.0 145.90 100.00 0.00
3/4" 19 0.0 145.90 100.00 0.00
1/2" 12.5 0.0 145.90 100.00 0.00
3/8" 9.5 0.0 145.90 100.00 0.00
#4 4.75 0.0 145.90 100.00 0.00
#10 2 0.0 145.90 100.00 0.00
#40 0.425 7.4 138.50 94.93 5.07
#200 0.075 12.6 125.90 86.29 13.71
0.2
125.7
145.9
CU=
CC=
1 2 3 1 2
Container + Wet Soil, g.49.9 50.4 53.0 50.6 50.1
Container + Dry Soil, g.38.8 39.8 42.1 44.2 43.9
Moisture Loss, g. 11.1 10.6 10.9 6.4 6.2
Container I.D. CG5 ID2 ZK9 MV4 QS3
Container, g. 23.6 23.8 24.0 23.7 23.9
Dry Soil, g. 15.2 16.0 18.1 20.5 20.0
Moisture content, 73.3 66.7 60.0 31.2 31.1
Number of Blows18 24 32 Average 31.1
Liquid Limit: 65.8
Plastic Limit: 31.1
Plasticity Index: 34.7
Remarks:
Soil Description:
Group Symbols:
38.73%
LIQUID LIMIT PLASTIC LIMIT
Spec's. Item No. :
Nat. Moisture Content, % :
Fineness Modulus :
SIEVE SIZE
WEIGHT
RETAINED
gms
CUMULATIVE
PAN
This report is the result of test performed on the sample taken from site.
Clayey SILT
MH
WASH LOSS
DETERM. NO.
TEST REPORT FOR LIQUID LIMIT & PLASTIC LIMIT
ASTM D 4318 - 05
TOTAL
Sampled at:
Tested by:
Sampled by: PJ. Pasculado / Driller
J. Llona & B. Aquino & W. Palisoc / Lab. Tech.
TEST REPORT FOR SIEVE ANALYSIS
ASTM D - 422
Jobsite
Soil (BH-1 : SS-1)
PROPOSED PAMPANGA RIVER SLOPE PROTECTION WORKS AT SAN ESTEBAN CUT - OFF CHANNEL PALIMPI
( PHASE 1 )Name of Project:
Kind of Sample:
0.00
10.00
20.00
30.00
40.00
50.00
60.00
70.00
80.00
90.00
100.00
0.0010.010.11101001000
US STANDARD SIEVE SIZE
48
51
54
57
60
63
66
69
72
75
78
81
10 100
Mo
istu
re C
on
ten
t (%
)
No. of Blows
Certified By:
M. CUNAHAP ' Soil Laboratory Head
Tested By:
I. ESPALDON JR. Laboratory Technician
9-5-19/9-13-19
DATE DRILLED
TCT 10/10/2019
OFFICE DATE RECEIVE
TCT 10-11-19/10-14-19
OFFICE DATE TEST
Original Wt., gms: 184.5
Oven Dry Wt., gms: 132.9
Wash O.D. Wt., gms: 24.2
INCH / NO. MM.
WT.
PASSING
gms
% PASSING% RETAINED
1-1/2" 37.5 0.0 132.90 100.00 0.00
1" 25 0.0 132.90 100.00 0.00
3/4" 19 0.0 132.90 100.00 0.00
1/2" 12.5 0.0 132.90 100.00 0.00
3/8" 9.5 0.0 132.90 100.00 0.00
#4 4.75 0.0 132.90 100.00 0.00
#10 2 0.0 132.90 100.00 0.00
#40 0.425 9.3 123.60 93.00 7.00
#200 0.075 14.6 109.00 82.02 17.98
0.3
108.7
132.9
CU=
CC=
1 2 3 1 2
Container + Wet Soil, g.51.2 50.8 51.7 52.5 53.0
Container + Dry Soil, g.39.3 40.2 41.4 45.6 45.9
Moisture Loss, g. 11.9 10.7 10.3 6.9 7.1
Container I.D. CR2 OX9 GM1 NJ6 DW4
Container, g. 23.8 24.0 23.9 23.7 23.6
Dry Soil, g. 15.5 16.2 17.5 21.9 22.3
Moisture content, 76.3 65.9 58.6 31.7 31.7
Number of Blows16 25 34 Average 31.7
Liquid Limit: 65.9
Plastic Limit: 31.7
Plasticity Index: 34.2
Remarks:
TEST REPORT FOR SIEVE ANALYSIS
ASTM D - 422
Jobsite
Soil (BH-1 : SS-2)
PROPOSED PAMPANGA RIVER SLOPE PROTECTION WORKS AT SAN ESTEBAN CUT - OFF CHANNEL PALIMPI
( PHASE 1 )Name of Project:
Tested by:
Sampled by: PJ. Pasculado / Driller
J. Llona & B. Aquino & W. Palisoc / Lab. Tech.
Group Symbols:
CUMULATIVE
Kind of Sample:
Sampled at:
PAN
DETERM. NO.
Soil Description:
WASH LOSS
SIEVE SIZE
WEIGHT
RETAINED
gms
TOTAL
This report is the result of test performed on the sample taken from site.
Clayey SILT
MH
38.83%
LIQUID LIMIT PLASTIC LIMIT
Spec's. Item No. :
Nat. Moisture Content, % :
Fineness Modulus :
TEST REPORT FOR LIQUID LIMIT & PLASTIC LIMIT
ASTM D 4318 - 05
0.00
10.00
20.00
30.00
40.00
50.00
60.00
70.00
80.00
90.00
100.00
0.0010.010.11101001000
US STANDARD SIEVE SIZE
48
51
54
57
60
63
66
69
72
75
78
81
84
10 100
Mo
istu
re C
on
ten
t (%
)
No. of Blows
Certified By:
M. CUNAHAP ' Soil Laboratory Head
Tested By:
I. ESPALDON JR. Laboratory Technician
9-5-19/9-13-19
DATE DRILLED
TCT 10/10/2019
OFFICE DATE RECEIVE
TCT 10-11-19/10-14-19
OFFICE DATE TEST
Original Wt., gms: 206.1
Oven Dry Wt., gms: 144.9
Wash O.D. Wt., gms: 20.5
INCH / NO. MM.
WT.
PASSING
gms
% PASSING% RETAINED
1-1/2" 37.5 0.0 144.90 100.00 0.00
1" 25 0.0 144.90 100.00 0.00
3/4" 19 0.0 144.90 100.00 0.00
1/2" 12.5 0.0 144.90 100.00 0.00
3/8" 9.5 0.0 144.90 100.00 0.00
#4 4.75 0.0 144.90 100.00 0.00
#10 2 0.0 144.90 100.00 0.00
#40 0.425 7.5 137.40 94.82 5.18
#200 0.075 12.7 124.70 86.06 13.94
0.3
124.4
144.9
CU=
CC=
1 2 3 1 2
Container + Wet Soil, g.50.6 51.3 51.8 52.4 52.9
Container + Dry Soil, g.39.4 40.3 41.3 45.7 46.0
Moisture Loss, g. 11.2 11.0 10.5 6.8 6.9
Container I.D. DU9 CO1 ES5 BK8 MT4
Container, g. 24.0 23.7 23.6 23.9 23.8
Dry Soil, g. 15.4 16.6 17.7 21.8 22.2
Moisture content, 72.7 66.2 59.5 31.0 31.0
Number of Blows17 23 31 Average 31.0
Liquid Limit: 64.2
Plastic Limit: 31.0
Plasticity Index: 33.2
Remarks:
42.24%
PAN
DETERM. NO.
TEST REPORT FOR LIQUID LIMIT & PLASTIC LIMIT
ASTM D 4318 - 05
TOTAL
LIQUID LIMIT PLASTIC LIMIT
This report is the result of test performed on the sample taken from site.
Clayey SILT
MH
WASH LOSS
Soil Description:
Group Symbols:
J. Llona & B. Aquino & W. Palisoc / Lab. Tech.
CUMULATIVE
Spec's. Item No. :
Nat. Moisture Content, % :
Fineness Modulus :
SIEVE SIZE
WEIGHT
RETAINED
gms
PROPOSED PAMPANGA RIVER SLOPE PROTECTION WORKS AT SAN ESTEBAN CUT - OFF CHANNEL PALIMPI
( PHASE 1 )Name of Project:
Tested by:
Sampled by: PJ. Pasculado / Driller
Kind of Sample:
Sampled at: Jobsite
Soil (BH-1 : SS-3)
TEST REPORT FOR SIEVE ANALYSIS
ASTM D - 422
0.00
10.00
20.00
30.00
40.00
50.00
60.00
70.00
80.00
90.00
100.00
0.0010.010.11101001000
US STANDARD SIEVE SIZE
47
50
53
56
59
62
65
68
71
74
77
80
10 100
Mo
istu
re C
on
ten
t (%
)
No. of Blows
Certified By:
M. CUNAHAP ' Soil Laboratory Head
Tested By:
I. ESPALDON JR. Laboratory Technician
9-5-19/9-13-19
DATE DRILLED
TCT 10/10/2019
OFFICE DATE RECEIVE
TCT 10-11-19/10-14-19
OFFICE DATE TEST
Original Wt., gms: 197.5
Oven Dry Wt., gms: 146.9
Wash O.D. Wt., gms: 22.2
INCH / NO. MM.
WT.
PASSING
gms
% PASSING% RETAINED
1-1/2" 37.5 0.0 146.90 100.00 0.00
1" 25 0.0 146.90 100.00 0.00
3/4" 19 0.0 146.90 100.00 0.00
1/2" 12.5 0.0 146.90 100.00 0.00
3/8" 9.5 0.0 146.90 100.00 0.00
#4 4.75 0.0 146.90 100.00 0.00
#10 2 0.0 146.90 100.00 0.00
#40 0.425 8.3 138.60 94.35 5.65
#200 0.075 13.6 125.00 85.09 14.91
0.3
124.7
146.9
CU=
CC=
1 2 3 1 2
Container + Wet Soil, g.50.1 49.8 50.6 51.8 51.3
Container + Dry Soil, g.39.0 39.6 40.8 45.1 44.7
Moisture Loss, g. 11.1 10.2 9.9 6.7 6.6
Container I.D. VW4 XL9 CM6 RF2 ZL8
Container, g. 24.0 23.8 23.7 23.9 23.6
Dry Soil, g. 15.0 15.8 17.1 21.2 21.1
Moisture content, 73.7 64.3 57.8 31.4 31.3
Number of Blows16 24 32 Average 31.3
Liquid Limit: 63.7
Plastic Limit: 31.3
Plasticity Index: 32.4
Remarks:
TEST REPORT FOR SIEVE ANALYSIS
ASTM D - 422
Jobsite
Soil (BH-1 : SS-4)
PROPOSED PAMPANGA RIVER SLOPE PROTECTION WORKS AT SAN ESTEBAN CUT - OFF CHANNEL PALIMPI
( PHASE 1 )Name of Project:
Tested by:
Sampled by: PJ. Pasculado / Driller
J. Llona & B. Aquino & W. Palisoc / Lab. Tech.
Group Symbols:
CUMULATIVE
Kind of Sample:
Sampled at:
PAN
DETERM. NO.
Soil Description:
WASH LOSS
SIEVE SIZE
WEIGHT
RETAINED
gms
TOTAL
This report is the result of test performed on the sample taken from site.
Clayey SILT
MH
34.45%
LIQUID LIMIT PLASTIC LIMIT
Spec's. Item No. :
Nat. Moisture Content, % :
Fineness Modulus :
TEST REPORT FOR LIQUID LIMIT & PLASTIC LIMIT
ASTM D 4318 - 05
0.00
10.00
20.00
30.00
40.00
50.00
60.00
70.00
80.00
90.00
100.00
0.0010.010.11101001000
US STANDARD SIEVE SIZE
46
49
52
55
58
61
64
67
70
73
76
79
10 100
Mo
istu
re C
on
ten
t (%
)
No. of Blows
Certified By:
M. CUNAHAP ' Soil Laboratory Head
Tested By:
I. ESPALDON JR. Laboratory Technician
9-5-19/9-13-19
DATE DRILLED
TCT 10/10/2019
OFFICE DATE RECEIVE
TCT 10-11-19/10-14-19
OFFICE DATE TEST
Original Wt., gms: 184.7
Oven Dry Wt., gms: 134.2
Wash O.D. Wt., gms: 17.5
INCH / NO. MM.
WT.
PASSING
gms
% PASSING% RETAINED
1-1/2" 37.5 0.0 134.20 100.00 0.00
1" 25 0.0 134.20 100.00 0.00
3/4" 19 0.0 134.20 100.00 0.00
1/2" 12.5 0.0 134.20 100.00 0.00
3/8" 9.5 0.0 134.20 100.00 0.00
#4 4.75 0.0 134.20 100.00 0.00
#10 2 0.0 134.20 100.00 0.00
#40 0.425 6.1 128.10 95.45 4.55
#200 0.075 11.3 116.80 87.03 12.97
0.1
116.7
134.2
CU=
CC=
1 2 3 1 2
Container + Wet Soil, g.50.9 51.2 51.7 53.0 52.5
Container + Dry Soil, g.39.7 40.6 41.7 46.2 45.7
Moisture Loss, g. 11.2 10.6 10.0 6.8 6.8
Container I.D. DR4 XO1 VM9 PS6 EQ3
Container, g. 23.6 23.8 23.9 24.0 23.7
Dry Soil, g. 16.1 16.8 17.8 22.2 22.0
Moisture content, 70.0 62.7 56.3 30.6 30.9
Number of Blows18 25 33 Average 30.8
Liquid Limit: 62.8
Plastic Limit: 30.8
Plasticity Index: 32.0
Remarks:
37.63%
PAN
DETERM. NO.
TEST REPORT FOR LIQUID LIMIT & PLASTIC LIMIT
ASTM D 4318 - 05
TOTAL
LIQUID LIMIT PLASTIC LIMIT
This report is the result of test performed on the sample taken from site.
Clayey SILT
MH
WASH LOSS
Soil Description:
Group Symbols:
J. Llona & B. Aquino & W. Palisoc / Lab. Tech.
CUMULATIVE
Spec's. Item No. :
Nat. Moisture Content, % :
Fineness Modulus :
SIEVE SIZE
WEIGHT
RETAINED
gms
PROPOSED PAMPANGA RIVER SLOPE PROTECTION WORKS AT SAN ESTEBAN CUT - OFF CHANNEL PALIMPI
( PHASE 1 )Name of Project:
Tested by:
Sampled by: PJ. Pasculado / Driller
Kind of Sample:
Sampled at: Jobsite
Soil (BH-1 : SS-5)
TEST REPORT FOR SIEVE ANALYSIS
ASTM D - 422
0.00
10.00
20.00
30.00
40.00
50.00
60.00
70.00
80.00
90.00
100.00
0.0010.010.11101001000
US STANDARD SIEVE SIZE
45
48
51
54
57
60
63
66
69
72
75
78
10 100
Mo
istu
re C
on
ten
t (%
)
No. of Blows
Certified By:
M. CUNAHAP ' Soil Laboratory Head
Tested By:
I. ESPALDON JR. Laboratory Technician
9-5-19/9-13-19
DATE DRILLED
TCT 10/10/2019
OFFICE DATE RECEIVE
TCT 10-11-19/10-14-19
OFFICE DATE TEST
Original Wt., gms: 204.1
Oven Dry Wt., gms: 141.6
Wash O.D. Wt., gms: 20.0
INCH / NO. MM.
WT.
PASSING
gms
% PASSING% RETAINED
1-1/2" 37.5 0.0 141.60 100.00 0.00
1" 25 0.0 141.60 100.00 0.00
3/4" 19 0.0 141.60 100.00 0.00
1/2" 12.5 0.0 141.60 100.00 0.00
3/8" 9.5 0.0 141.60 100.00 0.00
#4 4.75 0.0 141.60 100.00 0.00
#10 2 0.0 141.60 100.00 0.00
#40 0.425 7.2 134.40 94.92 5.08
#200 0.075 12.6 121.80 86.02 13.98
0.2
121.6
141.6
CU=
CC=
1 2 3 1 2
Container + Wet Soil, g.51.8 53.0 51.3 49.9 50.4
Container + Dry Soil, g.39.9 41.4 41.1 43.7 44.1
Moisture Loss, g. 11.9 11.6 10.2 6.2 6.4
Container I.D. DM1 VP6 EJ4 ZK9 OW3
Container, g. 23.6 23.7 23.9 24.0 23.8
Dry Soil, g. 16.3 17.7 17.2 19.7 20.3
Moisture content, 73.2 65.4 58.9 31.5 31.4
Number of Blows17 24 32 Average 31.4
Liquid Limit: 64.7
Plastic Limit: 31.4
Plasticity Index: 33.3
Remarks:
Group Symbols:
TEST REPORT FOR SIEVE ANALYSIS
ASTM D - 422
Jobsite
Soil (BH-1 : SS-6)
PROPOSED PAMPANGA RIVER SLOPE PROTECTION WORKS AT SAN ESTEBAN CUT - OFF CHANNEL PALIMPI
( PHASE 1 )Name of Project:
Kind of Sample:
Sampled at:
Tested by:
Sampled by: PJ. Pasculado / Driller
J. Llona & B. Aquino & W. Palisoc / Lab. Tech.
This report is the result of test performed on the sample taken from site.
Clayey SILT
MH
WASH LOSS
DETERM. NO.
TEST REPORT FOR LIQUID LIMIT & PLASTIC LIMIT
ASTM D 4318 - 05
TOTAL
Soil Description:
Spec's. Item No. :
Nat. Moisture Content, % :
Fineness Modulus :
SIEVE SIZE
WEIGHT
RETAINED
gms
CUMULATIVE
PAN
LIQUID LIMIT PLASTIC LIMIT
44.14%
0.00
10.00
20.00
30.00
40.00
50.00
60.00
70.00
80.00
90.00
100.00
0.0010.010.11101001000
US STANDARD SIEVE SIZE
47
50
53
56
59
62
65
68
71
74
77
80
10 100
Mo
istu
re C
on
ten
t (%
)
No. of Blows
Certified By:
M. CUNAHAP ' Soil Laboratory Head
Tested By:
I. ESPALDON JR. Laboratory Technician
9-5-19/9-13-19
DATE DRILLED
TCT 10/10/2019
OFFICE DATE RECEIVE
TCT 10-11-19/10-14-19
OFFICE DATE TEST
Original Wt., gms: 200.7
Oven Dry Wt., gms: 145.9
Wash O.D. Wt., gms: 23.1
INCH / NO. MM.
WT.
PASSING
gms
% PASSING% RETAINED
1-1/2" 37.5 0.0 145.90 100.00 0.00
1" 25 0.0 145.90 100.00 0.00
3/4" 19 0.0 145.90 100.00 0.00
1/2" 12.5 0.0 145.90 100.00 0.00
3/8" 9.5 0.0 145.90 100.00 0.00
#4 4.75 0.0 145.90 100.00 0.00
#10 2 0.0 145.90 100.00 0.00
#40 0.425 8.2 137.70 94.38 5.62
#200 0.075 14.6 123.10 84.37 15.63
0.3
122.8
145.9
CU=
CC=
1 2 3 1 2
Container + Wet Soil, g.49.9 50.6 50.1 51.8 51.3
Container + Dry Soil, g.38.3 39.7 40.0 44.9 44.6
Moisture Loss, g. 11.6 10.9 10.1 6.9 6.7
Container I.D. DU7 VJ2 XL9 TM1 GN4
Container, g. 23.6 24.0 23.8 23.7 23.9
Dry Soil, g. 14.7 15.7 16.2 21.2 20.7
Moisture content, 79.3 69.1 62.1 32.5 32.4
Number of Blows16 25 34 Average 32.5
Liquid Limit: 69.2
Plastic Limit: 32.5
Plasticity Index: 36.7
Remarks:
Soil Description:
Group Symbols:
37.56%
LIQUID LIMIT PLASTIC LIMIT
Spec's. Item No. :
Nat. Moisture Content, % :
Fineness Modulus :
SIEVE SIZE
WEIGHT
RETAINED
gms
CUMULATIVE
PAN
This report is the result of test performed on the sample taken from site.
Clayey SILT
MH
WASH LOSS
DETERM. NO.
TEST REPORT FOR LIQUID LIMIT & PLASTIC LIMIT
ASTM D 4318 - 05
TOTAL
Sampled at:
Tested by:
Sampled by: PJ. Pasculado / Driller
J. Llona & B. Aquino & W. Palisoc / Lab. Tech.
TEST REPORT FOR SIEVE ANALYSIS
ASTM D - 422
Jobsite
Soil (BH-1 : SS-7)
PROPOSED PAMPANGA RIVER SLOPE PROTECTION WORKS AT SAN ESTEBAN CUT - OFF CHANNEL PALIMPI
( PHASE 1 )Name of Project:
Kind of Sample:
0.00
10.00
20.00
30.00
40.00
50.00
60.00
70.00
80.00
90.00
100.00
0.0010.010.11101001000
US STANDARD SIEVE SIZE
52
55
58
61
64
67
70
73
76
79
82
85
10 100
Mo
istu
re C
on
ten
t (%
)
No. of Blows
Certified By:
M. CUNAHAP ' Soil Laboratory Head
Tested By:
I. ESPALDON JR. Laboratory Technician
9-5-19/9-13-19
DATE DRILLED
TCT 10/10/2019
OFFICE DATE RECEIVE
TCT 10-11-19/10-14-19
OFFICE DATE TEST
Original Wt., gms: 199.4
Oven Dry Wt., gms: 151.3
Wash O.D. Wt., gms: 16.7
INCH / NO. MM.
WT.
PASSING
gms
% PASSING% RETAINED
1-1/2" 37.5 0.0 151.30 100.00 0.00
1" 25 0.0 151.30 100.00 0.00
3/4" 19 0.0 151.30 100.00 0.00
1/2" 12.5 0.0 151.30 100.00 0.00
3/8" 9.5 0.0 151.30 100.00 0.00
#4 4.75 0.0 151.30 100.00 0.00
#10 2 0.0 151.30 100.00 0.00
#40 0.425 6.1 145.20 95.97 4.03
#200 0.075 10.4 134.80 89.09 10.91
0.2
134.6
151.3
CU=
CC=
1 2 3 1 2
Container + Wet Soil, g.51.3 50.9 51.8 52.7 52.2
Container + Dry Soil, g.39.4 40.0 41.1 45.7 45.4
Moisture Loss, g. 11.9 10.9 10.7 7.0 6.8
Container I.D. SD5 VO8 DH1 IW4 KA6
Container, g. 23.8 24.0 23.7 23.6 23.9
Dry Soil, g. 15.6 16.0 17.4 22.1 21.5
Moisture content, 76.3 67.9 61.2 31.7 31.7
Number of Blows16 23 31 Average 31.7
Liquid Limit: 66.2
Plastic Limit: 31.7
Plasticity Index: 34.5
Remarks:
TEST REPORT FOR SIEVE ANALYSIS
ASTM D - 422
Jobsite
Soil (BH-1 : SS-8)
PROPOSED PAMPANGA RIVER SLOPE PROTECTION WORKS AT SAN ESTEBAN CUT - OFF CHANNEL PALIMPI
( PHASE 1 )Name of Project:
Tested by:
Sampled by: PJ. Pasculado / Driller
J. Llona & B. Aquino & W. Palisoc / Lab. Tech.
Group Symbols:
CUMULATIVE
Kind of Sample:
Sampled at:
PAN
DETERM. NO.
Soil Description:
WASH LOSS
SIEVE SIZE
WEIGHT
RETAINED
gms
TOTAL
This report is the result of test performed on the sample taken from site.
Clayey SILT
MH
31.79%
LIQUID LIMIT PLASTIC LIMIT
Spec's. Item No. :
Nat. Moisture Content, % :
Fineness Modulus :
TEST REPORT FOR LIQUID LIMIT & PLASTIC LIMIT
ASTM D 4318 - 05
0.00
10.00
20.00
30.00
40.00
50.00
60.00
70.00
80.00
90.00
100.00
0.0010.010.11101001000
US STANDARD SIEVE SIZE
49
52
55
58
61
64
67
70
73
76
79
82
10 100
Mo
istu
re C
on
ten
t (%
)
No. of Blows
Certified By:
M. CUNAHAP ' Soil Laboratory Head
Tested By:
I. ESPALDON JR. Laboratory Technician
9-5-19/9-13-19
DATE DRILLED
TCT 10/10/2019
OFFICE DATE RECEIVE
TCT 10-11-19/10-14-19
OFFICE DATE TEST
Original Wt., gms: 185.6
Oven Dry Wt., gms: 138.9
Wash O.D. Wt., gms: 20.8
INCH / NO. MM.
WT.
PASSING
gms
% PASSING% RETAINED
1-1/2" 37.5 0.0 138.90 100.00 0.00
1" 25 0.0 138.90 100.00 0.00
3/4" 19 0.0 138.90 100.00 0.00
1/2" 12.5 0.0 138.90 100.00 0.00
3/8" 9.5 0.0 138.90 100.00 0.00
#4 4.75 0.0 138.90 100.00 0.00
#10 2 0.0 138.90 100.00 0.00
#40 0.425 7.9 131.00 94.31 5.69
#200 0.075 12.6 118.40 85.24 14.76
0.3
118.1
138.9
CU=
CC=
1 2 3 1 2
Container + Wet Soil, g.51.3 50.6 51.8 52.5 53.0
Container + Dry Soil, g.39.7 39.8 41.2 45.5 46.0
Moisture Loss, g. 11.7 10.8 10.6 7.0 7.1
Container I.D. RC5 QX1 YL9 MV4 EN2
Container, g. 24.0 23.6 23.8 23.7 23.9
Dry Soil, g. 15.7 16.2 17.4 21.8 22.1
Moisture content, 74.4 67.1 60.7 32.1 32.0
Number of Blows18 25 33 Average 32.0
Liquid Limit: 67.3
Plastic Limit: 32.0
Plasticity Index: 35.3
Remarks:
Soil Description:
Group Symbols:
33.62%
LIQUID LIMIT PLASTIC LIMIT
Spec's. Item No. :
Nat. Moisture Content, % :
Fineness Modulus :
SIEVE SIZE
WEIGHT
RETAINED
gms
CUMULATIVE
PAN
This report is the result of test performed on the sample taken from site.
Sandy SILT
ML
WASH LOSS
DETERM. NO.
TEST REPORT FOR LIQUID LIMIT & PLASTIC LIMIT
ASTM D 4318 - 05
TOTAL
Sampled at:
Tested by:
Sampled by: PJ. Pasculado / Driller
J. Llona & B. Aquino & W. Palisoc / Lab. Tech.
TEST REPORT FOR SIEVE ANALYSIS
Jobsite
Soil (BH-1 : SS-9)
PROPOSED PAMPANGA RIVER SLOPE PROTECTION WORKS AT SAN ESTEBAN CUT - OFF CHANNEL PALIMPI
( PHASE 1 )Name of Project:
Kind of Sample:
0.00
10.00
20.00
30.00
40.00
50.00
60.00
70.00
80.00
90.00
100.00
0.0010.010.11101001000
US STANDARD SIEVE SIZE
50
53
56
59
62
65
68
71
74
77
80
83
10 100
Mo
istu
re C
on
ten
t (%
)
No. of Blows
Certified By:
M. CUNAHAP ' Soil Laboratory Head
Tested By:
I. ESPALDON JR. Laboratory Technician
9-5-19/9-13-19
DATE DRILLED
TCT 10/10/2019
OFFICE DATE RECEIVE
TCT 10-11-19/10-14-19
OFFICE DATE TEST
Original Wt., gms: 184.7
Oven Dry Wt., gms: 125.3
Wash O.D. Wt., gms: 19.1
INCH / NO. MM.
WT.
PASSING
gms
% PASSING% RETAINED
1-1/2" 37.5 0.0 125.30 100.00 0.00
1" 25 0.0 125.30 100.00 0.00
3/4" 19 0.0 125.30 100.00 0.00
1/2" 12.5 0.0 125.30 100.00 0.00
3/8" 9.5 0.0 125.30 100.00 0.00
#4 4.75 0.0 125.30 100.00 0.00
#10 2 0.0 125.30 100.00 0.00
#40 0.425 7.2 118.10 94.25 5.75
#200 0.075 11.6 106.50 85.00 15.00
0.3
106.2
125.3
CU=
CC=
1 2 3 1 2
Container + Wet Soil, g.51.2 49.9 51.7 52.8 52.3
Container + Dry Soil, g.39.5 39.5 41.3 45.7 45.4
Moisture Loss, g. 11.7 10.4 10.4 7.1 6.9
Container I.D. CR4 XQ8 MT6 EL1 SY5
Container, g. 24.0 23.8 23.6 23.7 23.9
Dry Soil, g. 15.5 15.7 17.7 22.0 21.5
Moisture content, 75.0 66.2 59.0 32.1 32.1
Number of Blows17 25 34 Average 32.1
Liquid Limit: 66.3
Plastic Limit: 32.1
Plasticity Index: 34.2
Remarks:
TEST REPORT FOR SIEVE ANALYSIS
ASTM D - 422
Jobsite
Soil (BH-1 : SS-10)
PROPOSED PAMPANGA RIVER SLOPE PROTECTION WORKS AT SAN ESTEBAN CUT - OFF CHANNEL PALIMPI
( PHASE 1 )Name of Project:
Tested by:
Sampled by: PJ. Pasculado / Driller
J. Llona & B. Aquino & W. Palisoc / Lab. Tech.
Group Symbols:
CUMULATIVE
Kind of Sample:
Sampled at:
PAN
DETERM. NO.
Soil Description:
WASH LOSS
SIEVE SIZE
WEIGHT
RETAINED
gms
TOTAL
This report is the result of test performed on the sample taken from site.
Sandy SILT
ML
47.41%
LIQUID LIMIT PLASTIC LIMIT
Spec's. Item No. :
Nat. Moisture Content, % :
Fineness Modulus :
TEST REPORT FOR LIQUID LIMIT & PLASTIC LIMIT
ASTM D 4318 - 05
0.00
10.00
20.00
30.00
40.00
50.00
60.00
70.00
80.00
90.00
100.00
0.0010.010.11101001000
US STANDARD SIEVE SIZE
49
52
55
58
61
64
67
70
73
76
79
82
10 100
Mo
istu
re C
on
ten
t (%
)
No. of Blows
Certified By:
M. CUNAHAP ' Soil Laboratory Head
Tested By:
I. ESPALDON JR. Laboratory Technician
9-5-19/9-13-19
DATE DRILLED
TCT 10/10/2019
OFFICE DATE RECEIVE
TCT 10-11-19/10-14-19
OFFICE DATE TEST
Original Wt., gms: 197.2
Oven Dry Wt., gms: 146.9
Wash O.D. Wt., gms: 22.0
INCH / NO. MM.
WT.
PASSING
gms
% PASSING% RETAINED
1-1/2" 37.5 0.0 146.90 100.00 0.00
1" 25 0.0 146.90 100.00 0.00
3/4" 19 0.0 146.90 100.00 0.00
1/2" 12.5 0.0 146.90 100.00 0.00
3/8" 9.5 0.0 146.90 100.00 0.00
#4 4.75 0.0 146.90 100.00 0.00
#10 2 0.0 146.90 100.00 0.00
#40 0.425 8.3 138.60 94.35 5.65
#200 0.075 13.6 125.00 85.09 14.91
0.1
124.9
146.9
CU=
CC=
1 2 3 1 2
Container + Wet Soil, g.50.2 53.0 50.7 51.4 51.9
Container + Dry Soil, g.38.9 41.2 40.5 44.7 45.1
Moisture Loss, g. 11.3 11.9 10.2 6.8 6.8
Container I.D. DQ5 VO9 MK1 RL6 EH2
Container, g. 24.0 23.8 23.9 23.6 23.7
Dry Soil, g. 14.9 17.4 16.6 21.1 21.4
Moisture content, 76.2 68.3 61.7 32.1 32.0
Number of Blows17 24 32 Average 32.0
Liquid Limit: 67.4
Plastic Limit: 32.0
Plasticity Index: 35.4
Remarks:
Fineness Modulus :
ASTM D 4318 - 05
TOTAL
LIQUID LIMIT PLASTIC LIMIT
Soil Description:
This report is the result of test performed on the sample taken from site.
Sandy SILT
MLGroup Symbols:
PAN
DETERM. NO.
TEST REPORT FOR LIQUID LIMIT & PLASTIC LIMIT
WASH LOSS
PJ. Pasculado / Driller
SIEVE SIZE
WEIGHT
RETAINED
gms
CUMULATIVE
34.24%
Spec's. Item No. :
Nat. Moisture Content, % :
Soil (BH-1 : SS-11)
PROPOSED PAMPANGA RIVER SLOPE PROTECTION WORKS AT SAN ESTEBAN CUT - OFF CHANNEL PALIMPI
( PHASE 1 )
Sampled at:
Tested by:
Sampled by:
Name of Project:
Kind of Sample:
J. Llona & B. Aquino & W. Palisoc / Lab. Tech.
TEST REPORT FOR SIEVE ANALYSIS
ASTM D - 422
Jobsite
0.00
10.00
20.00
30.00
40.00
50.00
60.00
70.00
80.00
90.00
100.00
0.0010.010.11101001000
US STANDARD SIEVE SIZE
50
53
56
59
62
65
68
71
74
77
80
83
10 100
Mo
istu
re C
on
ten
t (%
)
No. of Blows
Certified By:
M. CUNAHAP ' Soil Laboratory Head
Tested By:
I. ESPALDON JR. Laboratory Technician
9-5-19/9-13-19
DATE DRILLED
TCT 10/10/2019
OFFICE DATE RECEIVE
TCT 10-11-19/10-14-19
OFFICE DATE TEST
Original Wt., gms: 181.5
Oven Dry Wt., gms: 132.3
Wash O.D. Wt., gms: 23.3
INCH / NO. MM.
WT.
PASSING
gms
% PASSING% RETAINED
1-1/2" 37.5 0.0 132.30 100.00 0.00
1" 25 0.0 132.30 100.00 0.00
3/4" 19 0.0 132.30 100.00 0.00
1/2" 12.5 0.0 132.30 100.00 0.00
3/8" 9.5 0.0 132.30 100.00 0.00
#4 4.75 0.0 132.30 100.00 0.00
#10 2 0.0 132.30 100.00 0.00
#40 0.425 9.7 122.60 92.67 7.33
#200 0.075 13.5 109.10 82.46 17.54
0.1
109.0
132.3
CU=
CC=
1 2 3 1 2
Container + Wet Soil, g.51.7 50.8 51.2 49.9 50.4
Container + Dry Soil, g.39.7 39.6 40.5 43.5 43.9
Moisture Loss, g. 12.0 11.2 10.7 6.4 6.5
Container I.D. RW3 CX8 NK6 LM1 DH4
Container, g. 24.0 23.8 23.9 23.7 23.6
Dry Soil, g. 15.7 15.8 16.6 19.8 20.3
Moisture content, 76.9 71.3 64.5 32.1 32.0
Number of Blows18 23 31 Average 32.0
Liquid Limit: 69.5
Plastic Limit: 32.0
Plasticity Index: 37.5
Remarks:
Group Symbols:
TEST REPORT FOR SIEVE ANALYSIS
ASTM D - 422
Jobsite
Soil (BH-1 : SS-12)
PROPOSED PAMPANGA RIVER SLOPE PROTECTION WORKS AT SAN ESTEBAN CUT - OFF CHANNEL PALIMPI
( PHASE 1 )Name of Project:
Kind of Sample:
Sampled at:
Tested by:
Sampled by: PJ. Pasculado / Driller
J. Llona & B. Aquino & W. Palisoc / Lab. Tech.
This report is the result of test performed on the sample taken from site.
Clayey SILT
MH
WASH LOSS
DETERM. NO.
TEST REPORT FOR LIQUID LIMIT & PLASTIC LIMIT
ASTM D 4318 - 05
TOTAL
Soil Description:
Spec's. Item No. :
Nat. Moisture Content, % :
Fineness Modulus :
SIEVE SIZE
WEIGHT
RETAINED
gms
CUMULATIVE
PAN
LIQUID LIMIT PLASTIC LIMIT
37.19%
0.00
10.00
20.00
30.00
40.00
50.00
60.00
70.00
80.00
90.00
100.00
0.0010.010.11101001000
US STANDARD SIEVE SIZE
52
55
58
61
64
67
70
73
76
79
82
85
10 100
Mo
istu
re C
on
ten
t (%
)
No. of Blows
Certified By:
M. CUNAHAP ' Soil Laboratory Head
Tested By:
I. ESPALDON JR. Laboratory Technician
9-5-19/9-13-19
DATE DRILLED
TCT 10/10/2019
OFFICE DATE RECEIVE
TCT 10-11-19/10-14-19
OFFICE DATE TEST
Original Wt., gms: 200.8
Oven Dry Wt., gms: 145.3
Wash O.D. Wt., gms: 22.0
INCH / NO. MM.
WT.
PASSING
gms
% PASSING% RETAINED
1-1/2" 37.5 0.0 145.30 100.00 0.00
1" 25 0.0 145.30 100.00 0.00
3/4" 19 0.0 145.30 100.00 0.00
1/2" 12.5 0.0 145.30 100.00 0.00
3/8" 9.5 0.0 145.30 100.00 0.00
#4 4.75 0.0 145.30 100.00 0.00
#10 2 0.0 145.30 100.00 0.00
#40 0.425 9.5 135.80 93.46 6.54
#200 0.075 12.3 123.50 85.00 15.00
0.2
123.3
145.3
CU=
CC=
1 2 3 1 2
Container + Wet Soil, g.51.2 53.0 51.7 50.4 50.9
Container + Dry Soil, g.39.2 41.2 41.0 44.0 44.3
Moisture Loss, g. 12.0 11.8 10.7 6.4 6.6
Container I.D. VQ5 CO8 EM2 NZ6 LF4
Container, g. 23.6 23.9 23.7 24.0 23.8
Dry Soil, g. 15.6 17.3 17.3 20.0 20.5
Moisture content, 77.2 68.5 62.1 32.0 32.0
Number of Blows17 25 33 Average 32.0
Liquid Limit: 68.6
Plastic Limit: 32.0
Plasticity Index: 36.6
Remarks:
Fineness Modulus :
ASTM D 4318 - 05
TOTAL
LIQUID LIMIT PLASTIC LIMIT
Soil Description:
This report is the result of test performed on the sample taken from site.
Clayey SILT
MHGroup Symbols:
PAN
DETERM. NO.
TEST REPORT FOR LIQUID LIMIT & PLASTIC LIMIT
WASH LOSS
PJ. Pasculado / Driller
SIEVE SIZE
WEIGHT
RETAINED
gms
CUMULATIVE
38.20%
Spec's. Item No. :
Nat. Moisture Content, % :
Soil (BH-1 : SS-13)
PROPOSED PAMPANGA RIVER SLOPE PROTECTION WORKS AT SAN ESTEBAN CUT - OFF CHANNEL PALIMPI
( PHASE 1 )
Sampled at:
Tested by:
Sampled by:
Name of Project:
Kind of Sample:
J. Llona & B. Aquino & W. Palisoc / Lab. Tech.
TEST REPORT FOR SIEVE ANALYSIS
ASTM D - 422
Jobsite
0.00
10.00
20.00
30.00
40.00
50.00
60.00
70.00
80.00
90.00
100.00
0.0010.010.11101001000
US STANDARD SIEVE SIZE
51
54
57
60
63
66
69
72
75
78
81
84
10 100
Mo
istu
re C
on
ten
t (%
)
No. of Blows
Certified By:
M. CUNAHAP ' Soil Laboratory Head
Tested By:
I. ESPALDON JR. Laboratory Technician
9-5-19/9-13-19
DATE DRILLED
TCT 10/10/2019
OFFICE DATE RECEIVE
TCT 10-11-19/10-14-19
OFFICE DATE TEST
Original Wt., gms: 181.7
Oven Dry Wt., gms: 131.3
Wash O.D. Wt., gms: 22.0
INCH / NO. MM.
WT.
PASSING
gms
% PASSING% RETAINED
1-1/2" 37.5 0.0 131.30 100.00 0.00
1" 25 0.0 131.30 100.00 0.00
3/4" 19 0.0 131.30 100.00 0.00
1/2" 12.5 0.0 131.30 100.00 0.00
3/8" 9.5 0.0 131.30 100.00 0.00
#4 4.75 0.0 131.30 100.00 0.00
#10 2 0.0 131.30 100.00 0.00
#40 0.425 8.2 123.10 93.75 6.25
#200 0.075 13.6 109.50 83.40 16.60
0.2
109.3
131.3
CU=
CC=
1 2 3 1 2
Container + Wet Soil, g.53.0 50.3 49.8 51.7 51.2
Container + Dry Soil, g.40.5 39.8 40.4 45.1 44.7
Moisture Loss, g. 12.5 10.5 9.4 6.7 6.6
Container I.D. QC3 SO2 JL7 OV5 EM1
Container, g. 23.5 24.0 23.9 23.7 23.6
Dry Soil, g. 17.0 15.8 16.5 21.4 21.1
Moisture content, 73.7 66.6 56.7 31.1 31.1
Number of Blows16 22 34 Average 31.1
Liquid Limit: 63.7
Plastic Limit: 31.1
Plasticity Index: 32.6
Remarks:
TEST REPORT FOR SIEVE ANALYSIS
ASTM D - 422
Jobsite
Soil (BH-1 : SS-14)
PROPOSED PAMPANGA RIVER SLOPE PROTECTION WORKS AT SAN ESTEBAN CUT - OFF CHANNEL PALIMPI
( PHASE 1 )Name of Project:
Tested by:
Sampled by: PJ. Pasculado / Driller
J. Llona & B. Aquino & W. Palisoc / Lab. Tech.
Group Symbols:
CUMULATIVE
Kind of Sample:
Sampled at:
PAN
DETERM. NO.
Soil Description:
WASH LOSS
SIEVE SIZE
WEIGHT
RETAINED
gms
TOTAL
This report is the result of test performed on the sample taken from site.
Clayey SILT
MH
38.39%
LIQUID LIMIT PLASTIC LIMIT
Spec's. Item No. :
Nat. Moisture Content, % :
Fineness Modulus :
TEST REPORT FOR LIQUID LIMIT & PLASTIC LIMIT
ASTM D 4318 - 05
0.00
10.00
20.00
30.00
40.00
50.00
60.00
70.00
80.00
90.00
100.00
0.0010.010.11101001000
US STANDARD SIEVE SIZE
46
49
52
55
58
61
64
67
70
73
76
79
10 100
Mo
istu
re C
on
ten
t (%
)
No. of Blows
Certified By:
M. CUNAHAP ' Soil Laboratory Head
Tested By:
I. ESPALDON JR. Laboratory Technician
9-5-19/9-13-19
DATE DRILLED
TCT 10/10/2019
OFFICE DATE RECEIVE
TCT 10-11-19/10-14-19
OFFICE DATE TEST
Original Wt., gms: 195.7
Oven Dry Wt., gms: 146.2
Wash O.D. Wt., gms: 19.0
INCH / NO. MM.
WT.
PASSING
gms
% PASSING% RETAINED
1-1/2" 37.5 0.0 146.20 100.00 0.00
1" 25 0.0 146.20 100.00 0.00
3/4" 19 0.0 146.20 100.00 0.00
1/2" 12.5 0.0 146.20 100.00 0.00
3/8" 9.5 0.0 146.20 100.00 0.00
#4 4.75 0.0 146.20 100.00 0.00
#10 2 0.0 146.20 100.00 0.00
#40 0.425 6.3 139.90 95.69 4.31
#200 0.075 12.6 127.30 87.07 12.93
0.1
127.2
146.2
CU=
CC=
1 2 3 1 2
Container + Wet Soil, g.51.2 50.6 51.7 52.5 53.0
Container + Dry Soil, g.39.7 39.9 41.3 45.7 46.1
Moisture Loss, g. 11.5 10.7 10.4 6.8 6.9
Container I.D. LM6 VD1 OS9 KR5 CJ2
Container, g. 24.0 23.6 23.9 23.7 23.8
Dry Soil, g. 15.7 16.3 17.4 22.0 22.3
Moisture content, 73.1 65.3 59.4 30.7 30.7
Number of Blows17 24 31 Average 30.7
Liquid Limit: 64.4
Plastic Limit: 30.7
Plasticity Index: 33.7
Remarks:
Soil Description:
Group Symbols:
33.86%
LIQUID LIMIT PLASTIC LIMIT
Spec's. Item No. :
Nat. Moisture Content, % :
Fineness Modulus :
SIEVE SIZE
WEIGHT
RETAINED
gms
CUMULATIVE
PAN
This report is the result of test performed on the sample taken from site.
Clayey SILT
MH
WASH LOSS
DETERM. NO.
TEST REPORT FOR LIQUID LIMIT & PLASTIC LIMIT
ASTM D 4318 - 05
TOTAL
Sampled at:
Tested by:
Sampled by: PJ. Pasculado / Driller
J. Llona & B. Aquino & W. Palisoc / Lab. Tech.
TEST REPORT FOR SIEVE ANALYSIS
ASTM D - 422
Jobsite
Soil (BH-1 : SS-15)
PROPOSED PAMPANGA RIVER SLOPE PROTECTION WORKS AT SAN ESTEBAN CUT - OFF CHANNEL PALIMPI
( PHASE 1 )Name of Project:
Kind of Sample:
0.00
10.00
20.00
30.00
40.00
50.00
60.00
70.00
80.00
90.00
100.00
0.0010.010.11101001000
US STANDARD SIEVE SIZE
47
50
53
56
59
62
65
68
71
74
77
80
10 100
Mo
istu
re C
on
ten
t (%
)
No. of Blows
Certified By:
M. CUNAHAP ' Soil Laboratory Head
Tested By:
I. ESPALDON JR. Laboratory Technician
9-5-19/9-13-19
DATE DRILLED
TCT 10/10/2019
OFFICE DATE RECEIVE
TCT 10-11-19/10-14-19
OFFICE DATE TEST
Original Wt., gms: 203.2
Oven Dry Wt., gms: 144.9
Wash O.D. Wt., gms: 23.3
INCH / NO. MM.
WT.
PASSING
gms
% PASSING% RETAINED
1-1/2" 37.5 0.0 144.90 100.00 0.00
1" 25 0.0 144.90 100.00 0.00
3/4" 19 0.0 144.90 100.00 0.00
1/2" 12.5 0.0 144.90 100.00 0.00
3/8" 9.5 0.0 144.90 100.00 0.00
#4 4.75 0.0 144.90 100.00 0.00
#10 2 0.0 144.90 100.00 0.00
#40 0.425 9.4 135.50 93.51 6.49
#200 0.075 13.6 121.90 84.13 15.87
0.3
121.6
144.9
CU=
CC=
1 2 3 1 2
Container + Wet Soil, g.51.2 49.9 51.7 50.8 50.3
Container + Dry Soil, g.39.6 39.9 41.6 44.4 44.1
Moisture Loss, g. 11.6 10.0 10.1 6.4 6.2
Container I.D. QP8 VJ1 WX5 FL2 AB3
Container, g. 23.7 23.9 24.0 23.6 23.8
Dry Soil, g. 15.9 16.0 17.6 20.8 20.3
Moisture content, 72.7 62.7 57.2 30.8 30.8
Number of Blows16 25 32 Average 30.8
Liquid Limit: 62.8
Plastic Limit: 30.8
Plasticity Index: 32.0
Remarks:
TEST REPORT FOR SIEVE ANALYSIS
ASTM D - 422
Jobsite
Soil (BH-1 : SS-16)
PROPOSED PAMPANGA RIVER SLOPE PROTECTION WORKS AT SAN ESTEBAN CUT - OFF CHANNEL PALIMPI
( PHASE 1 )Name of Project:
Tested by:
Sampled by: PJ. Pasculado / Driller
J. Llona & B. Aquino & W. Palisoc / Lab. Tech.
Group Symbols:
CUMULATIVE
Kind of Sample:
Sampled at:
PAN
DETERM. NO.
Soil Description:
WASH LOSS
SIEVE SIZE
WEIGHT
RETAINED
gms
TOTAL
This report is the result of test performed on the sample taken from site.
Clayey SILT
MH
40.23%
LIQUID LIMIT PLASTIC LIMIT
Spec's. Item No. :
Nat. Moisture Content, % :
Fineness Modulus :
TEST REPORT FOR LIQUID LIMIT & PLASTIC LIMIT
ASTM D 4318 - 05
0.00
10.00
20.00
30.00
40.00
50.00
60.00
70.00
80.00
90.00
100.00
0.0010.010.11101001000
US STANDARD SIEVE SIZE
46
49
52
55
58
61
64
67
70
73
76
79
10 100
Mo
istu
re C
on
ten
t (%
)
No. of Blows
Certified By:
M. CUNAHAP ' Soil Laboratory Head
Tested By:
I. ESPALDON JR. Laboratory Technician
9-5-19/9-13-19
DATE DRILLED
TCT 10/10/2019
OFFICE DATE RECEIVE
TCT 10-11-19/10-14-19
OFFICE DATE TEST
Original Wt., gms: 285.5
Oven Dry Wt., gms: 245.2
Wash O.D. Wt., gms: 187.9
INCH / NO. MM.
WT.
PASSING
gms
% PASSING% RETAINED
1-1/2" 37.5 0.0 245.20 100.00 0.00
1" 25 0.0 245.20 100.00 0.00
3/4" 19 0.0 245.20 100.00 0.00
1/2" 12.5 0.0 245.20 100.00 0.00
3/8" 9.5 0.0 245.20 100.00 0.00
#4 4.75 0.0 245.20 100.00 0.00
#10 2 7.9 237.30 96.78 3.22
#40 0.425 33.2 204.10 83.24 16.76
#200 0.075 146.5 57.60 23.49 76.51
0.3
57.3
245.2
CU=
CC=
1 2 3 1 2
Container + Wet Soil, g. - - - - -
Container + Dry Soil, g. - - - - -
Moisture Loss, g. - - - - -
Container I.D. - - - - -
Container, g. - - - - -
Dry Soil, g. - - - - -
Moisture content, - - - - -
Number of Blows- - - Average -
Liquid Limit: -
Plastic Limit: NP Soil Description:
Plasticity Index: - Group Symbols:
Remarks:
ASTM D 4318 - 05
TOTAL
LIQUID LIMIT PLASTIC LIMIT
WASH LOSS
16.44%
Spec's. Item No. :
Nat. Moisture Content, % :
Fineness Modulus :
SIEVE SIZE
WEIGHT
RETAINED
gms
CUMULATIVE
This report is the result of test performed on the sample taken from site.
Silty SAND
SM
PAN
DETERM. NO.
TEST REPORT FOR LIQUID LIMIT & PLASTIC LIMIT
Sampled at:
Tested by:
Sampled by:
J. Llona & B. Aquino & W. Palisoc / Lab. Tech.
TEST REPORT FOR SIEVE ANALYSIS
ASTM D - 422
Jobsite
Soil (BH-1 : SS-17)
PROPOSED PAMPANGA RIVER SLOPE PROTECTION WORKS AT SAN ESTEBAN CUT - OFF CHANNEL PALIMPI
( PHASE 1 )Name of Project:
Kind of Sample:
PJ. Pasculado / Driller
0.00
10.00
20.00
30.00
40.00
50.00
60.00
70.00
80.00
90.00
100.00
0.0010.010.11101001000
US STANDARD SIEVE SIZE
44
47
50
53
56
59
62
65
68
71
10 100
Mo
istu
re C
on
ten
t (%
)
No. of Blows
Certified By:
M. CUNAHAP ' Soil Laboratory Head
Tested By:
I. ESPALDON JR. Laboratory Technician
9-5-19/9-13-19
DATE DRILLED
TCT 10/10/2019
OFFICE DATE RECEIVE
TCT 10-11-19/10-14-19
OFFICE DATE TEST
Original Wt., gms: 313.9
Oven Dry Wt., gms: 265.3
Wash O.D. Wt., gms: 182.4
INCH / NO. MM.
WT.
PASSING
gms
% PASSING% RETAINED
1-1/2" 37.5 0.0 265.30 100.00 0.00
1" 25 0.0 265.30 100.00 0.00
3/4" 19 0.0 265.30 100.00 0.00
1/2" 12.5 0.0 265.30 100.00 0.00
3/8" 9.5 0.0 265.30 100.00 0.00
#4 4.75 0.0 265.30 100.00 0.00
#10 2 6.9 258.40 97.40 2.60
#40 0.425 31.4 227.00 85.56 14.44
#200 0.075 143.8 83.20 31.36 68.64
0.3
82.9
265.3
CU=
CC=
1 2 3 1 2
Container + Wet Soil, g. - - - - -
Container + Dry Soil, g. - - - - -
Moisture Loss, g. - - - - -
Container I.D. - - - - -
Container, g. - - - - -
Dry Soil, g. - - - - -
Moisture content, - - - - -
Number of Blows- - - Average -
Liquid Limit: -
Plastic Limit: NP Soil Description:
Plasticity Index: - Group Symbols:
Remarks:
TEST REPORT FOR SIEVE ANALYSIS
ASTM D - 422
Jobsite
Soil (BH-1 : SS-18)
PROPOSED PAMPANGA RIVER SLOPE PROTECTION WORKS AT SAN ESTEBAN CUT - OFF CHANNEL PALIMPI
( PHASE 1 )Name of Project:
Kind of Sample:
Sampled at:
Tested by:
Sampled by: PJ. Pasculado / Driller
J. Llona & B. Aquino & W. Palisoc / Lab. Tech.
CUMULATIVE
PAN
DETERM. NO.
TEST REPORT FOR LIQUID LIMIT & PLASTIC LIMIT
WASH LOSS
ASTM D 4318 - 05
TOTAL
LIQUID LIMIT PLASTIC LIMIT
This report is the result of test performed on the sample taken from site.
Silty SAND
SM
Spec's. Item No. :
Nat. Moisture Content, % : 18.32%
Fineness Modulus :
SIEVE SIZE
WEIGHT
RETAINED
gms
0.00
10.00
20.00
30.00
40.00
50.00
60.00
70.00
80.00
90.00
100.00
0.0010.010.11101001000
US STANDARD SIEVE SIZE
40
43
46
49
52
55
58
61
64
67
70
10 100
Mo
istu
re C
on
ten
t (%
)
No. of Blows
Certified By:
M. CUNAHAP ' Soil Laboratory Head
Tested By:
I. ESPALDON JR. Laboratory Technician
9-5-19/9-13-19
DATE DRILLED
TCT 10/10/2019
OFFICE DATE RECEIVE
TCT 10-11-19/10-14-19
OFFICE DATE TEST
Original Wt., gms: 295.3
Oven Dry Wt., gms: 251.9
Wash O.D. Wt., gms: 183.7
INCH / NO. MM.
WT.
PASSING
gms
% PASSING% RETAINED
1-1/2" 37.5 0.0 251.90 100.00 0.00
1" 25 0.0 251.90 100.00 0.00
3/4" 19 0.0 251.90 100.00 0.00
1/2" 12.5 0.0 251.90 100.00 0.00
3/8" 9.5 0.0 251.90 100.00 0.00
#4 4.75 0.0 251.90 100.00 0.00
#10 2 7.2 244.70 97.14 2.86
#40 0.425 31.4 213.30 84.68 15.32
#200 0.075 144.8 68.50 27.19 72.81
0.3
68.2
251.9
CU=
CC=
1 2 3 1 2
Container + Wet Soil, g. - - - - -
Container + Dry Soil, g. - - - - -
Moisture Loss, g. - - - - -
Container I.D. - - - - -
Container, g. - - - - -
Dry Soil, g. - - - - -
Moisture content, - - - - -
Number of Blows- - - Average -
Liquid Limit: -
Plastic Limit: NP Soil Description:
Plasticity Index: - Group Symbols:
Remarks:
Fineness Modulus :
ASTM D 4318 - 05
TOTAL
WEIGHT
RETAINED
gms
CUMULATIVE
LIQUID LIMIT PLASTIC LIMIT
Spec's. Item No. :
Nat. Moisture Content, % : 17.23%
WASH LOSS
SIEVE SIZE
This report is the result of test performed on the sample taken from site.
Silty SAND
SM
PAN
DETERM. NO.
TEST REPORT FOR LIQUID LIMIT & PLASTIC LIMIT
Sampled at:
Tested by:
Sampled by: PJ. Pasculado / Driller
TEST REPORT FOR SIEVE ANALYSIS
ASTM D - 422
Jobsite
Soil (BH-1 : SS-19)
PROPOSED PAMPANGA RIVER SLOPE PROTECTION WORKS AT SAN ESTEBAN CUT - OFF CHANNEL PALIMPI
( PHASE 1 )Name of Project:
Kind of Sample:
J. Llona & B. Aquino & W. Palisoc / Lab. Tech.
0.00
10.00
20.00
30.00
40.00
50.00
60.00
70.00
80.00
90.00
100.00
0.0010.010.11101001000
US STANDARD SIEVE SIZE
42
45
48
51
54
57
60
63
66
69
10 100
Mo
istu
re C
on
ten
t (%
)
No. of Blows
Certified By:
M. CUNAHAP ' Soil Laboratory Head
Tested By:
I. ESPALDON JR. Laboratory Technician
9-5-19/9-13-19
DATE DRILLED
TCT 10/10/2019
OFFICE DATE RECEIVE
TCT 10-11-19/10-14-19
OFFICE DATE TEST
Original Wt., gms: 288.6
Oven Dry Wt., gms: 252.3
Wash O.D. Wt., gms: 195.4
INCH / NO. MM.
WT.
PASSING
gms
% PASSING% RETAINED
1-1/2" 37.5 0.0 252.30 100.00 0.00
1" 25 0.0 252.30 100.00 0.00
3/4" 19 0.0 252.30 100.00 0.00
1/2" 12.5 0.0 252.30 100.00 0.00
3/8" 9.5 0.0 252.30 100.00 0.00
#4 4.75 0.0 252.30 100.00 0.00
#10 2 9.2 243.10 96.35 3.65
#40 0.425 36.3 206.80 81.97 18.03
#200 0.075 149.5 57.30 22.71 77.29
0.4
56.9
252.3
CU=
CC=
1 2 3 1 2
Container + Wet Soil, g. - - - - -
Container + Dry Soil, g. - - - - -
Moisture Loss, g. - - - - -
Container I.D. - - - - -
Container, g. - - - - -
Dry Soil, g. - - - - -
Moisture content, - - - - -
Number of Blows- - - Average -
Liquid Limit: -
Plastic Limit: NP Soil Description:
Plasticity Index: - Group Symbols:
Remarks:
TEST REPORT FOR SIEVE ANALYSIS
ASTM D - 422
Jobsite
Soil (BH-1 : SS-20)
PROPOSED PAMPANGA RIVER SLOPE PROTECTION WORKS AT SAN ESTEBAN CUT - OFF CHANNEL PALIMPI
( PHASE 1 )Name of Project:
Kind of Sample:
Sampled at:
Tested by:
Sampled by: PJ. Pasculado / Driller
J. Llona & B. Aquino & W. Palisoc / Lab. Tech.
CUMULATIVE
PAN
DETERM. NO.
TEST REPORT FOR LIQUID LIMIT & PLASTIC LIMIT
WASH LOSS
ASTM D 4318 - 05
TOTAL
LIQUID LIMIT PLASTIC LIMIT
This report is the result of test performed on the sample taken from site.
Silty SAND
SM
Spec's. Item No. :
Nat. Moisture Content, % : 14.39%
Fineness Modulus :
SIEVE SIZE
WEIGHT
RETAINED
gms
0.00
10.00
20.00
30.00
40.00
50.00
60.00
70.00
80.00
90.00
100.00
0.0010.010.11101001000
US STANDARD SIEVE SIZE
44
47
50
53
56
59
62
65
68
71
74
10 100
Mo
istu
re C
on
ten
t (%
)
No. of Blows
Certified By:
M. CUNAHAP ' Soil Laboratory Head
Tested By:
I. ESPALDON JR. Laboratory Technician
9-5-19/9-13-19
DATE DRILLED
TCT 10/10/2019
OFFICE DATE RECEIVE
TCT 10-11-19/10-14-19
OFFICE DATE TEST
Original Wt., gms: 293.7
Oven Dry Wt., gms: 253.9
Wash O.D. Wt., gms: 191.8
INCH / NO. MM.
WT.
PASSING
gms
% PASSING% RETAINED
1-1/2" 37.5 0.0 253.90 100.00 0.00
1" 25 0.0 253.90 100.00 0.00
3/4" 19 0.0 253.90 100.00 0.00
1/2" 12.5 0.0 253.90 100.00 0.00
3/8" 9.5 0.0 253.90 100.00 0.00
#4 4.75 0.0 253.90 100.00 0.00
#10 2 8.6 245.30 96.61 3.39
#40 0.425 35.2 210.10 82.75 17.25
#200 0.075 147.8 62.30 24.54 75.46
0.2
62.1
253.9
CU=
CC=
1 2 3 1 2
Container + Wet Soil, g. - - - - -
Container + Dry Soil, g. - - - - -
Moisture Loss, g. - - - - -
Container I.D. - - - - -
Container, g. - - - - -
Dry Soil, g. - - - - -
Moisture content, - - - - -
Number of Blows- - - Average -
Liquid Limit: -
Plastic Limit: NP Soil Description:
Plasticity Index: - Group Symbols:
Remarks:
Fineness Modulus :
ASTM D 4318 - 05
TOTAL
WEIGHT
RETAINED
gms
CUMULATIVE
LIQUID LIMIT PLASTIC LIMIT
Spec's. Item No. :
Nat. Moisture Content, % : 15.68%
WASH LOSS
SIEVE SIZE
This report is the result of test performed on the sample taken from site.
Silty SAND
SM
PAN
DETERM. NO.
TEST REPORT FOR LIQUID LIMIT & PLASTIC LIMIT
Sampled at:
Tested by:
Sampled by: PJ. Pasculado / Driller
TEST REPORT FOR SIEVE ANALYSIS
ASTM D - 422
Jobsite
Soil (BH-1 : SS-21)
PROPOSED PAMPANGA RIVER SLOPE PROTECTION WORKS AT SAN ESTEBAN CUT - OFF CHANNEL PALIMPI
( PHASE 1 )Name of Project:
Kind of Sample:
J. Llona & B. Aquino & W. Palisoc / Lab. Tech.
0.00
10.00
20.00
30.00
40.00
50.00
60.00
70.00
80.00
90.00
100.00
0.0010.010.11101001000
US STANDARD SIEVE SIZE
44
47
50
53
56
59
62
65
68
71
74
10 100
Mo
istu
re C
on
ten
t (%
)
No. of Blows
Certified By:
M. CUNAHAP ' Soil Laboratory Head
Tested By:
I. ESPALDON JR. Laboratory Technician
9-5-19/9-13-19
DATE DRILLED
TCT 10/10/2019
OFFICE DATE RECEIVE
TCT 10-11-19/10-14-19
OFFICE DATE TEST
Original Wt., gms: 283.9
Oven Dry Wt., gms: 238.2
Wash O.D. Wt., gms: 191.2
INCH / NO. MM.
WT.
PASSING
gms
% PASSING% RETAINED
1-1/2" 37.5 0.0 238.20 100.00 0.00
1" 25 0.0 238.20 100.00 0.00
3/4" 19 0.0 238.20 100.00 0.00
1/2" 12.5 0.0 238.20 100.00 0.00
3/8" 9.5 0.0 238.20 100.00 0.00
#4 4.75 0.0 238.20 100.00 0.00
#10 2 7.9 230.30 96.68 3.32
#40 0.425 35.2 195.10 81.91 18.09
#200 0.075 147.8 47.30 19.86 80.14
0.3
47.0
238.2
CU=
CC=
1 2 3 1 2
Container + Wet Soil, g. - - - - -
Container + Dry Soil, g. - - - - -
Moisture Loss, g. - - - - -
Container I.D. - - - - -
Container, g. - - - - -
Dry Soil, g. - - - - -
Moisture content, - - - - -
Number of Blows- - - Average -
Liquid Limit: -
Plastic Limit: NP Soil Description:
Plasticity Index: - Group Symbols:
Remarks:
TEST REPORT FOR SIEVE ANALYSIS
ASTM D - 422
Jobsite
Soil (BH-1 : SS-22)
PROPOSED PAMPANGA RIVER SLOPE PROTECTION WORKS AT SAN ESTEBAN CUT - OFF CHANNEL PALIMPI
( PHASE 1 )Name of Project:
Kind of Sample:
Sampled at:
Tested by:
Sampled by: PJ. Pasculado / Driller
J. Llona & B. Aquino & W. Palisoc / Lab. Tech.
CUMULATIVE
PAN
DETERM. NO.
TEST REPORT FOR LIQUID LIMIT & PLASTIC LIMIT
WASH LOSS
ASTM D 4318 - 05
TOTAL
LIQUID LIMIT PLASTIC LIMIT
This report is the result of test performed on the sample taken from site.
Silty SAND
SM
Spec's. Item No. :
Nat. Moisture Content, % : 19.19%
Fineness Modulus :
SIEVE SIZE
WEIGHT
RETAINED
gms
0.00
10.00
20.00
30.00
40.00
50.00
60.00
70.00
80.00
90.00
100.00
0.0010.010.11101001000
US STANDARD SIEVE SIZE
44
47
50
53
56
59
62
65
68
71
74
10 100
Mo
istu
re C
on
ten
t (%
)
No. of Blows
Certified By:
M. CUNAHAP ' Soil Laboratory Head
Tested By:
I. ESPALDON JR. Laboratory Technician
9-5-19/9-13-19
DATE DRILLED
TCT 10/10/2019
OFFICE DATE RECEIVE
TCT 10-11-19/10-14-19
OFFICE DATE TEST
Original Wt., gms: 303.6
Oven Dry Wt., gms: 256.2
Wash O.D. Wt., gms: 184.6
INCH / NO. MM.
WT.
PASSING
gms
% PASSING% RETAINED
1-1/2" 37.5 0.0 256.20 100.00 0.00
1" 25 0.0 256.20 100.00 0.00
3/4" 19 0.0 256.20 100.00 0.00
1/2" 12.5 0.0 256.20 100.00 0.00
3/8" 9.5 0.0 256.20 100.00 0.00
#4 4.75 0.0 256.20 100.00 0.00
#10 2 8.1 248.10 96.84 3.16
#40 0.425 31.4 216.70 84.58 15.42
#200 0.075 144.8 71.90 28.06 71.94
0.3
71.6
256.2
CU=
CC=
1 2 3 1 2
Container + Wet Soil, g. - - - - -
Container + Dry Soil, g. - - - - -
Moisture Loss, g. - - - - -
Container I.D. - - - - -
Container, g. - - - - -
Dry Soil, g. - - - - -
Moisture content, - - - - -
Number of Blows- - - Average -
Liquid Limit: -
Plastic Limit: NP Soil Description:
Plasticity Index: - Group Symbols:
Remarks:
Fineness Modulus :
ASTM D 4318 - 05
TOTAL
WEIGHT
RETAINED
gms
CUMULATIVE
LIQUID LIMIT PLASTIC LIMIT
Spec's. Item No. :
Nat. Moisture Content, % : 18.50%
WASH LOSS
SIEVE SIZE
This report is the result of test performed on the sample taken from site.
Silty SAND
SM
PAN
DETERM. NO.
TEST REPORT FOR LIQUID LIMIT & PLASTIC LIMIT
Sampled at:
Tested by:
Sampled by: PJ. Pasculado / Driller
TEST REPORT FOR SIEVE ANALYSIS
ASTM D - 422
Jobsite
Soil (BH-1 : SS-23)
PROPOSED PAMPANGA RIVER SLOPE PROTECTION WORKS AT SAN ESTEBAN CUT - OFF CHANNEL PALIMPI
( PHASE 1 )Name of Project:
Kind of Sample:
J. Llona & B. Aquino & W. Palisoc / Lab. Tech.
0.00
10.00
20.00
30.00
40.00
50.00
60.00
70.00
80.00
90.00
100.00
0.0010.010.11101001000
US STANDARD SIEVE SIZE
44
47
50
53
56
59
62
65
68
71
74
10 100
Mo
istu
re C
on
ten
t (%
)
No. of Blows
Certified By:
M. CUNAHAP ' Soil Laboratory Head
Tested By:
I. ESPALDON JR. Laboratory Technician
PROJECT:
Location:
Client
PROPOSED PAMPANGA RIVER SLOPE
PROTECTION WORKS AT SAN ESTEBAN
CUT - OFF CHANNEL PALIMPI ( PHASE 1 )
Masantol Pampanga
DPWH REGION 3
TERMS Concrete Testing #19 L. Intalan St. Bagong Ilog, Pasig City