67
CNPP Service Éditions [email protected] CEA 4001-2013 – Sprinklers Systems – Inquiry on amendments 2016 (February) 1/67 This document brings together all the amendments or modifications to be made to the CEA 4001-2013 proposed by the expert group EG4. Thank you for reviewing each of them by using the table at the end of this document. All comments and suggestions will be studied by GEI4 and adjustments will be done where appropriate. PROPOSAL n° 1 – Modification of Chapter 1 Chapter 1: Checking of the definition of “distribution pipe” and “distribution pipe spur” Replace “distribution pipe spur” by “distribution pipe” in figure F.1.3a, FHe, FHf and FHj and in annex D.3.3. Delete the definition of distribution pipe spur and modify definitions of distribution pipe as follow: distribution pipe A pipe feeding either a range pipe. directly or a single sprinkler on a non-terminal range pipe more than 0.3m long. distribution pipe spur A distribution pipe from a main distribution pipe, to a terminal branched pipe array.

PROPOSAL n° 1 – Modification of Chapter 1 - vds-global.comvds-global.com/fileadmin/compliance/cea4001/CEA4001_INQUIRY_ON... · sprinkler system and shall comply with the relevant

Embed Size (px)

Citation preview

CNPP Service Éditions [email protected]

CEA 4001-2013 – Sprinklers Systems – Inquiry on amendments 2016 (February) 1/67

This document brings together all the amendments or modifications to be made to the CEA 4001-2013 proposed by the expert group EG4. Thank you for reviewing each of them by using the table at the end of this document. All comments and suggestions will be studied by GEI4 and adjustments will be done where appropriate.

PROPOSAL n° 1 – Modification of Chapter 1

Chapter 1: Checking of the definition of “distribution pipe” and “distribution pipe spur”

Replace “distribution pipe spur” by “distribution pipe” in figure F.1.3a, FHe, FHf and FHj and in annex D.3.3. Delete the definition of distribution pipe spur and modify definitions of distribution pipe as follow:

distribution pipe A pipe feeding either a range pipe. directly or a single sprinkler on a non-terminal range pipe more than 0.3m long.

distribution pipe spur A distribution pipe from a main distribution pipe, to a terminal branched pipe array.

CEA 4001-2013 – Sprinklers Systems – Inquiry on amendments 2016 (February) 2/67

PROPOSAL n° 2 – Modification of Chapter 8

Chapter 8: the Name of the water supply is not consistent within the chapter; choice of water supply and type of water supply Modify title of chapter 8 and title of §8.6 as follow:

8 CHOICE OF WATER SUPPLY TYPE OF WATER SUPPLY

8.6 Type of water supply Choice of water supply

(The content will be modify accordingly)

CEA 4001-2013 – Sprinklers Systems – Inquiry on amendments 2016 (February) 3/67

PROPOSAL n° 3 – Modification of Chapter 9

Modify 9.6.2.2 and 9.6.2.3 as follow: this important modification is aimed at reducing the diameter of suction pipe that appears to be unnecessary oversized.

9.6.2.2 Positive head

The diameter of the suction pipe shall be no less than 65 mm. Furthermore, the diameter shall be

such that a velocity of 4 1.8 m/s is not exceeded when the pump is operating at flow defined in

table T9.6.2.1a. This velocity may be increased to 2.5 m/s, if the pressure in the suction pipe is not

more than 0.4 bar below ambient pressure, when considering water supply at low water level.

Where more than one pump is provided the suction pipes may only be inter-connected if they are

fitted with stop valves to allow each pump to continue operating when the other is removed for

maintenance. The connections shall be dimensioned as appropriate for the flow rate required.

9.6.2.3 Suction lift conditions

The diameter of the suction pipe shall be no less than 80 mm. Furthermore, the diameter shall be

such that a velocity of 2.5 1.5 m/s is not exceeded when the pump is operating at flow defined in

table T9.6.2.1a equal to 1.4 × Q100. This velocity may be increased to 2.5 m/s, if the pressure in the

suction pipe is not more than 0.4 bar below ambient pressure, when considering water supply at

low water level.

Where there is more than one pumpset installed, the suction pipes shall not be interconnected.

The height from the low water level (see 8.3.5) to the centre line of the pump shall not exceed 3.2 m.

The suction pipe shall be positioned in the tank or reservoir in accordance with figure F 8.3.5a and

table T 8.3.5a or figure F 8.4.1b and tableT8.4.1a, as appropriate. A foot valve shall be fitted at the

lowest point on the suction pipe. Each pump shall have automatic priming arrangements in

accordance with 9.6.2.4.

Modify 9.1 as follow:

9.1 General

The H(Q) characteristic curve for the sprinkler pumps should be stable and flat. No instability may

amount to more than 5% of the maximum deliver head.

Pumps shall be driven either by electric motors or diesel engines capable of providing at least the

power required to comply with the following:

a)

For pumps with non-overloading power characteristic curves: the maximum power required at the

peak of the power curve plus a 5% safety margin for electrical driven pump or 20% for diesel engines;

b)

For pumps with rising power characteristic curves: the maximum power for any conditions of pump

load, from zero flow to a flow corresponding to Qmax a pump NPSH required equal to 16 m or maximum

suction static head plus 11 m whichever is greater plus a 5% safety margin for electrical driven pump

or 20% for diesel engines;

CEA 4001-2013 – Sprinklers Systems – Inquiry on amendments 2016 (February) 4/67

The coupling between the driver and the pump of horizontal pumpsets shall be of a type which

ensures that either can be removed independently and in such a way that pump internals can be

inspected or replaced without affecting suction or discharge piping. End suction pumps shall be of

the “back pull-out” type.

Pipework shall be supported independently of the pump.

PROPOSAL n° 4 – Modification of Chapter 10

Chapter 10.4.4: the requirements within this chapter needed to be updated in order to redefine

the different type of PRE-ACTION system.

The table below is not part of the proposal but is a support to understand the proposal.

Preaction type

Short description name Area of operation

Size of the system

Maximum Water delivery time at remote test valve

Type A1 If failure of detection , works as dry

Single interlock with fail safe mode

No increase of area of operation

Max 500 Max 60 seconds for HH and 90 sec for OH and LH

Type A2 No detection, no water even if sprinkler activates

Single interlock No increase of area of operation

Max 500 Max 60 seconds for HH and 90 sec for OH and LH

Type B Either activation of detection or activation of spk will activate alarm valve

Primed Single interlock

No increase of area of operation

Max 500 Max 60 seconds for HH and 90 sec for OH and LH

Type C Both activation of detection and activation of spk are required to activate alarm valve. Either one alone will not activate the valve

Double interlock Increase the area of operation by 25%

Max 500 Max 60 seconds for HH and 90 sec for OH and LH

Modify chapter 10.4 as follow: 10.4 Pre-action installations 10.4.1 General Pre-action installations are divided into two 4 types: It is required that the pre-action valve is equipped with a device that allows manual activation independently from any detection system. 10.4.1.1 Pre-action installation Type A1: Single interlock with fail safe mode

In the event of a fire detection fault, the pre-action installation shall operate as a dry pipe installation. This is a dry pipe system filled with air or inert gas in which the control valve set is activated by an automatic fire detection system but not by the operation of the sprinklers. In the event of a fire detection system goes into fault mode, the pre-action installation shall operate as a dry pipe installation. The air/inert gas pressure in the installation shall be monitored at all times. Consideration shall be given to fit a manually operated valve in an appropriate position to enable the pre-action valve to be activated in an emergency.

CEA 4001-2013 – Sprinklers Systems – Inquiry on amendments 2016 (February) 5/67

NOTE : type A1 pre-action installations should only be installed in areas where considerable damage could occur if there were an accidental discharge of water. 10.4.1.2 Pre-action installation Type A2: Single interlock This is a system filled with air or inert gas in which the control valve set is activated by an automatic fire detection system but not by the operation of the sprinkler. In the event of a fire detection system fault or failure, the pre-action installation may not operate automatically. The air/inert gas pressure in the installation shall be monitored at all times. 10.4.1.32 Pre-action installation Type B : Primed Single interlock This is an otherwise normal dry pipe system in which the control valve set is opened either by an automatic fire detection system or by the operation of the sprinklers. Independently of the response of the detectors, a pressure drop in the pipework causes the opening of the alarm valve. NOTE : type B pre-action installations may be installed wherever a dry pipe system is called for and the spread of fire is expected to be rapid, e.g. in high-rack storage. They may also be used instead of ordinary dry pipe systems with or without an accelerator or exhauster. 10.4.1.4 Pre-action installation Type C : Double interlock This is an otherwise normal dry pipe system in which the control valve set is opened by both activation of detection and the operation of the sprinkler. Either one alone will not activate automatically the valve. NOTE : type C pre-action installations should be installed in areas where considerable damage could occur if there were an accidental flooding of pipework. Typical application is in-rack protection in cold warehouses (deep freezer). 10.4.2 Sprinkler orientation In Type A installations All sprinklers in a pre-action installation shall be fitted in the upright position, except where dry pendent or horizontal sidewall sprinklers are used. or, only in a frost proof building, in the up-right or pendent position. In Type B installations, sprinklers shall be installed in the upright position. Note: Pendent position may be used in a building where there is no risk of frost, if accepted by authority. In such a case consideration shall be given to limit the size of the system. 10.4.3 Automatic detection system The detection system shall be installed in all rooms and compartments protected by the pre-action sprinkler system and shall comply with the relevant parts of EN54 CEA 4040 or equivalent and the components shall comply with relevant part of EN 54.. 10.4.4 Size of installations The number of sprinklers to be controlled by a pre-action type A alarm valve shall not exceed 500. 10.4.5 water delivery time The maximum water delivery time as measured at the remote test valve shall be limited to 60 seconds for HH and 90 sec for OH and LH. Note : For type A1, A2 and B, this is aimed to ensure that the system will effectively react similar as a wet system. For type C, this is aimed to ensure that the water delivery time corresponds to the requirement of a dry system.

CEA 4001-2013 – Sprinklers Systems – Inquiry on amendments 2016 (February) 6/67

Storage methods Maximum permitted storage height (m) (See note 1)

Minimum design density

Area of operation (wet or pre- action system

type A1, A2 or B (See note 2)

category I category II category III category IV mm/min m²

ST1 free standing or block

stacking

5,3 6,5 7,6

4,1 5,0 5,9 6,7 7,5

2,9 3,5 4,1 4,7 5,2

1,6 2,0 2,3 2,7 3,0

7,5 10,0 12,5 15,0 17,5

260

5,7 6,3 6,7 7,2

3,3 3,6 3,8 4,1 4,4

20,0 22,5 25,0 27,5 30,0

300 ST2

post pallets in single rows and ST4

Palletised racks (See note 3)

4,7 5,7 6,8

3,4 4,2 5,0 5,6 6,0

2,2 2,6 3,2 3,7 4,1

1,6 2,0 2,3 2,7 3,0

7,5 10,0 12,5 15,0 17,5

260

4,4 4,7 5,3 5,7 6,0

3,3 3,6 3,8 4,1 4,4

20,0 22,5 25,0 27,5 30,0

300

ST3 post or box pallets in multiple rows and

ST5/ST6 solid or slatted shelves

4,7 5,7

3,4 4,2 5,0

2,2 2,6 3,2

1,6 2,0 2,3 2,7 3,0

7,5 10,0 12,5 15,0 17,5

260

NOTE 1: the vertical distance from the floor to the sprinkler deflectors, minus 1m or the highest value shown in the table, whichever is the lower. NOTE 2: dry, and alternate systems should be avoided on High Hazard storages especially with the more combustible products (the higher categories) and the higher storages. Should it nonetheless be Where a pre-action type C, a dry or alternate system is installed, the area of operation shall be increased by 25 %. Note 3: for double row rack storage (ST4) exceeding 3,2m in height, longitudinal flue space no less than 0,15m shall be permanently maintaine from floor to top of storage.

Modify table T6.1a as follow: Table T 6.1a: Design density and area of operation for LH, OH and HHP

Hazard class Design density (minimum) mm/min

Area of operation m²

Wet or pre-action type A1, A2 or B Dry, pre-action type C or alternate

LH 2,25 84 not allowed - use OH1

OH1 5,0 72 90

OH2 5,0 144 180

OH3 5,0 216 270

OH4 5,0 360 not allowed - use HHP1

HHP1 7,5 260 325

HHP2 10,0 260 325

HHP3 12,5 260 325

HHP4 Special consideration apply

Modify table T6.2.2a as follow: Table T 6.2.2a: Design criteria for HHS with roof or ceiling protection only

CEA 4001-2013 – Sprinklers Systems – Inquiry on amendments 2016 (February) 7/67

Modify table T6.2.3.2a as follow. Table T 6.2.3.2a: Design criteria for roof sprinklers with in-rack protection

Storage methods Maximum permitted storage height above highest level of

intermediate sprinklers (1)

M

Minimum design density

mm/min

Area of operation

(wet or pre- action system

(2)

m² category I category II category III category IV

ST4 palletized rack 3,5 3,5 2,2 2,6 3,2 3,5

1,6 2,0 2,3 2,7

7,5 10,0 12,5 15,0

260

ST5 and ST6 solid or slatted shelves

4,7 5,7

3,4 4,2 5,0

2,2 2,6 3,2

1,6 2,0 2,3 2,7

3,0

7,5 10,0 12,5 15,0

17,5

260

NOTE 1: the vertical distance from the highest level of in-rack sprinklers to the roof or ceiling sprinklers, minus1m. NOTE 2: dry, and alternate systems should be avoided on High Hazard storages especially with the more combustible products (the higher categories) and the higher storages. Should it nonetheless be Where a dry, pre-action type C or alternate system is installed, the area of operation shall be increased by 25 %.

Modify: Table T8.3.2.1a and Table T8.3.4a as follow Table T 8.3.2.1a: Minimum water volume for precalculated LH and OH systems

Group Height h of the highest sprinkler above the lowest

sprinkler (See note 1)

Minimum water volume m3

LH - Wet or pre-action type A1, A2 or B h ≤ 15 15< h ≤ 30 30 < h ≤ 45

9 10 11

OH1 - Wet or pre-action type A1, A2 or B h ≤ 15 15 < h ≤ 30 30 < h ≤ 45

55 70 80

OH1 - Dry, alternate or pre-action type C OH2 - Wet or pre-action type A1, A2 or B

h ≤ 15 15 < h ≤ 30 30 < h ≤ 45

105 125 140

OH2 - Dry, alternate or pre-action type C OH3 - Wet or pre-action type A1, A2 or B

h ≤ 15 15 < h ≤ 30 30 < h 45

135 160 185

OH3 - Dry, alternate or pre-action type C OH4 - Wet or pre-action type A1, A2 or B

h ≤ 15 15 < h ≤ 30 30 < h ≤ 45

160 185 200

OH4 - Dry, alternate or pre-action type C Use HH protection

NOTE 1: Excluding sprinklers in the sprinkler valve room.

CEA 4001-2013 – Sprinklers Systems – Inquiry on amendments 2016 (February) 8/67

Table T 8.3.4a: Minimum capacity of reduced capacity tanks

Hazard Class Minimum capacity m3

LH - Wet or pre-action type A1, A2 or B 5

OH1 - Wet or pre-action type A1, A2 or B 10

OH1 – Dry, alternate or pre-action type C OH2 - Wet or pre-action type A1, A2 or B

20

OH2 - Dry, alternate or pre-action type C OH3 - Wet or pre-action type A1, A2 or B

30

OH3 - Dry, alternate or pre-action type C OH4 - Wet or pre-action type A1, A2 or B

50

HHP and HHS 70, but in no case less than 10% of the full capacity

Modify Table T 9.7.2a as follow

Table T 9.7.2a: Minimum pump characteristics for LH and OH (pre-calculated systems)

Hazard class Sprinkler height h

above the control valve

set(s) m

Nominal data Characteristic

Pressure bar

Flow l/min

Pressure bar

Flow l/min

Pressure bar

Flow l/min

LH wet or pre- action type A1, A2 or B

h ≤ 15 15 < h ≤ 30 30 < h ≤ 45

1.5 1.8 2.3

300 340 375

3.7 5.2 6.7

225 225 225

- - -

- - -

OH1 wet or pre-action type A1, A2 or B

h ≤ 15 15 < h ≤ 30 30 < h ≤ 45

1.2 1.9 2.7

900 1 150 1 360

2.2 3.7 5.2

540 540 540

2.5 4.0 5.5

375 375 375

OH1 dry, alternate or pre-action type C OH2 wet or pre-action type A1, A2 or B

h ≤ 15 15 < h ≤ 30 30 < h ≤ 45

1.4 2.0 2.6

1 750 2 050 2 350

2.5 4.0 5.5

1 000 1 000 1 000

2.9 4.4 5.9

725 725 725

OH2 dry, alternate or pre-action type C OH3 wet or pre-action type A1, A2 or B

h ≤ 15 15 < h ≤ 30 30 < h ≤ 45

1.4 2.0 2.5

2 250 2 700 3 100

2.9 4.4 5.9

1 350 1 350 1 350

3.2 4.7 6.2

1 100 1 100 1 100

CEA 4001-2013 – Sprinklers Systems – Inquiry on amendments 2016 (February) 9/67

OH3 dry, alternate or pre-action type C OH4 wet or pre-action type A1, A2 or B

h ≤ 15 15 < h ≤ 30 30 < h ≤ 45

1.9 2.4 3.0

2 650 3 050 3 350

3.0 4.5 6.0

2 100 2 100 2 100

3.5 5.0 6.5

1 800 1 800 1 800

NOTE 1: The pressures shown are as measured at the control valve set(s) NOTE 2: In the case of buildings which exceed the heights shown, it shall be proved that the pump characteristics are adequate for supplying the flows and pressures specified in 6.3.1.

Modify Table T 10.1.1a as follow Table T 10.1.1a: Maximum number of sprinklers per installation - wet pipe and pre-action installations

Hazard class Maximum number of sprinklers

LH 500

OH, including any LH sprinkler 1 000, except as allowed in Annexes D and F

HH, including any OH and LH sprinklers 1 000

Modify Table K6.1a as follow

Table T K.6.1a: Non-woven synthetic fabric: design criteria with roof or ceiling protection only

Storage methods

Maximum storage height

(see note 1)

Minimum design density mm/min

Area of operation (wet or pre-action system (see note 2))

m2

ST1 Free standing or block stacking

1.6 2.0 2.3 2.7

10.0 12.5 15.0 17.5

260

3.0 3.3 3.6 3.8 4.1

20.0 22.5 25.0 27.5 30.0

300

NOTE 1: the vertical distance from the floor to the sprinkler deflectors, minus 1 m, or the highest value shown in the table, whichever is the lower. NOTE 2: dry, alternate or pre-action type C installations should be avoided.

Modify Definition as follow

Installation, pre-action

One of types of dry Installation in which the alarm valve can or must be opened by an independent fire

detection system in the protected area. (see §10.4.1)

CEA 4001-2013 – Sprinklers Systems – Inquiry on amendments 2016 (February) 10/67

Modify annex I as follow

j) pre-action alarm valve assemblies Type A1;

k) pre-action alarm valve assemblies Type A2;

l) pre-action alarm valve assemblies Type B.

m) pre-action alarm valve assemblies Type C.

PROPOSAL n° 5 – Modification of Chapter 11

Modify 11.5 as follow

11.5 Intermediate sprinklers in High Hazard occupancies

11.5.1 General

Sprinklers protecting row racks shall be positioned in the longitudinal flue spaces, preferably in the

intersection with the transverse flue (see Figures F 11.5.1a and F 11.5.1b).

Whenever any rack or structural steelwork is likely to interfere significantly with the water discharge

from the sprinklers, additional sprinklers shall be provided and taken into account in the flow

calculation.

It shall be ensured that water from sprinklers operating at intermediate levels can penetrate the

goods stored. The distance between goods stored in racking and placed back to back shall be at least

0.15 m, and if necessary pallet stops should be fitted. There shall be a clearance of at least 0.15 m

from the sprinkler deflectors to the top of the storage.

The position of the deflector should preferably be installed minimum 0.02 m below the horizontal

beam. For other arrangement attention shall be given to the water distribution.

In rack sprinklers shall be arranged horizontally so that there is no more than one pallet between

each end of the rack and the nearest sprinkler.

NOTE: this chapter is based on the use of standardised European pallets (1.2 m × 0.8 m) with typical

height of 1 m to 1.7 m.

If the size varies importantly from this, authorities can be consulted for alternative arrangement of

in-rack sprinklers.

11.5.2 Maximum vertical distance between sprinklers at intermediate levels

The vertical distance from the floor to the lowest intermediate level and between levels shall not

exceed 3.50 m or two tiers, whichever is the lesser, as shown in Figures F 11.5.1a and F 11.5.1b. An

intermediate level shall be installed above the top level of storage except where all the roof or ceiling

sprinklers are situated at less than 4 m above the top of the storage.

In no case shall the highest level of intermediate sprinklers be installed lower than one tier level

below the top of the storage.

11.5.3 Horizontal position of sprinklers at intermediate levels

In the case of Category I or II goods, sprinklers shall where possible be installed in the longitudinal

flue at the intersection with every second transverse flue, with the sprinklers staggered with respect

to the next highest row (see Figure F 11.5a). The horizontal distance between sprinklers shall not

CEA 4001-2013 – Sprinklers Systems – Inquiry on amendments 2016 (February) 11/67

exceed 3.75 m and the product of the horizontal distance and the vertical distance between

sprinklers shall not exceed 9.8 m².

In the case of Category III or IV goods, sprinklers shall be installed in the longitudinal flue at the

intersection with each transverse flue (see Figure F 11.5.1b). The horizontal distance between

sprinklers shall not exceed 1.9 m and the product of the horizontal distance and the vertical distance

between sprinklers shall not exceed 4.9 m².

11.5.4 Numbers of rows of sprinklers at each level

The number of sprinkler rows per level shall be determined by the total width. When racking is

placed back to back the total width shall be calculated by adding together the width of each rack and

the distance between them.

1 row of sprinklers per level shall be installed for every 3.2 m of rack width. They shall be installed in

the flue spaces wherever possible.

11.5.5 HHS intermediate sprinklers in non-shelved racks

When required (see 6.2.2 and table T 5.3.2a), intermediate sprinkler (in rack) sprinklers shall be

provided for palletised rack storage and multiple row rack storage according to the following:

11.5.5.1 Single row rack

a)

Single row racks not more than 1.6 m wide shall be protected by single rows of sprinklers fitted on the

side of the rack not used for access or in the middle of rack at the tier levels. Sprinklers shall be fitted

at every 2nd transverse flue space for Cat. I and II and at every transverse flue space for Cat. III and

Cat.IV. Where sprinkler are installed outside of the rack, the allowable horizontal distance from the

sprinklers to the edge of the stored goods shall not exceed 150mm.

The distance between the sprinkler and the opposite side of the rack shall not exceed 1.6m.

If the distance from wall to rack edge or goods, whichever is smaller, exceeds 600mm, in-rack

sprinklers shall be installed in the middle of the rack.

See figure F11.5.5.1a

The maximum vertical distance between sprinklers shall be as stated in clause 11.5.2.

b)

Single row racks more than 1.6 m wide and not more than 3.2 m wide shall be protected by a single

CEA 4001-2013 – Sprinklers Systems – Inquiry on amendments 2016 (February) 12/67

row of sprinklers fitted in the middle of the rack tier levels. Sprinklers shall be fitted at every 2nd

transverse flue space for Cat. I and II and at every transverse flue space for Cat. III and Cat. IV. The maximum vertical distance between sprinklers shall be as stated in clause 11.5.2.

c)

For single row racks of more than 3.2 m width, authority shall be consulted.

11.5.5.2 Double row rack

a)

Double row racks no more than 3.2 m wide shall be protected by sprinklers centrally in the longitudinal

flue space at the tier levels shown in Figures F 11.5.1a and F 11.5.1b; The maximum vertical distance between sprinklers shall be as stated in clause 11.5.2.

The maximum horizontal distance between sprinklers shall be as stated in clause 11.5.3.

b)

Double row racks more than 3.2 m wide, but not more than 6.4 m wide shall be protected by two rows

of sprinklers installed centred over the respective load. The sprinklers at a particular level in each line

shall be located in the same set of transverse flue spaces. The sprinklers in the transverse flue spaces

shall be arranged so that the maximum vertical distance between two sprinklers is 7 m for cat I and II

and 3.5 m for cat III and IV. The vertical distance from the floor to the lowest intermediate level and between levels shall not

exceed 3.50 m or two tiers, whichever is the lesser.

Additionally, at a maximum vertical distance of 7 m (between intermediate levels), the longitudinal

flue shall be protected by sprinklers every 2nd transverse flue space for category I and II and every

transverse flue space for category III and IV. It shall be ensured that the maximum distance between

the top longitudinal flue in rack protection and the top of storage is 3.5 m or less according to table T

6.2.3.2a.

The maximum horizontal distance between sprinklers shall be as stated in clause 11.5.3.

See figure F 11.5.5.2a

NOTE : the layout for cat I and II is not shown

c)

For double row racks of more than 6.4 m width, authority shall be consulted.

d)

For double row racks next to a wall (less than 700 mm from the wall) authority shall be consulted.

Consideration should be given to the installation of supplementary sprinklers especially if the wall is

made of combustible material.

11.5.5.3 Multiple row racks with flue space in only one direction

In this type of rack the only possible flue space is in the loading direction, because pallets are, by

design, butted to the others. This concept applies even if the goods are smaller than the pallet size.

See figure F 11.5.5.3a and b

CEA 4001-2013 – Sprinklers Systems – Inquiry on amendments 2016 (February) 13/67

The figure F 11.5.5.3a fixes the maximum distances between in rack sprinklers. Multiple-row rack

HHS1-2 with flue space in only one direction.

The figure F 11.5.5.3b fixes the maximum distances between in rack sprinklers. Multiple-row rack

HHS3-4 with flue space in only one direction.

For category I and II goods the horizontal distance between sprinklers shall not exceed 3.75 m and

the product of the horizontal distance and the vertical distance between sprinklers shall not exceed

9.8 m².

For category III and IV goods the horizontal distance between sprinklers shall not exceed 1.9 m and

the product of the horizontal distance and the vertical distance between sprinklers shall not exceed

4.9 m².

Hydraulic calculation shall be carried out according to § 6.2.3.3

For multiple row racks next to a wall (less than 700 mm from the wall) authority shall be consulted.

Consideration should be given to the installation of supplementary sprinklers especially if the wall is

made of combustible material.

11.5.5.4 Multiple row racks with longitudinal and transverse flue spaces

In this type of configuration, the rack structure and the organisation of the storage are made so that

longitudinal and transverse flue spaces exist.

In this case the flue spaces shall be at least 150 mm wide.

The figures F 11.5.5.4a and F 11.5.5.4b fix the maximum distances between in rack sprinklers.

a) Multiple row racks HHS 1 – 2

Sprinklers shall be arranged so that, within a vertical distance of maximum 7m, there is at least an in-

rack sprinkler at each intersection between longitudinal and transverse flue space.

Where the height of storage allows only one level of in-rack protection, authority should be

consulted for the sprinkler positioning.

b)

Multiple row racks HHS 3 Sprinklers shall be arranged so that, within a vertical distance of maximum 7m, there is at least an in-

rack sprinkler at each intersection between longitudinal and transverse flue space.

c)

Multiple row racks HHS 4 Multiple row rack configuration with longitudinal and transverse flue spaces in HHS 4 shall be

submitted to authority.

d)

For multiple row racks next to a wall (less than 700 mm from the wall) authority shall be consulted.

Consideration should be given to the installation of supplementary sprinklers especially if the wall is made of

combustible material.

ST4 movable rack storage configuration shall be submitted to authority but can be interpolated from

this chapter 11.5.5.

CEA 4001-2013 – Sprinklers Systems – Inquiry on amendments 2016 (February) 14/67

11.5.6 HHS intermediate sprinklers below solid or slatted shelves in racks (ST5 and ST6)

Intermediate sprinklers shall provided above each shelf (including the top shelf if the roof or ceiling

sprinklers are more than 4 m above the goods or water access to the goods is restricted), and located

as shown in Table T 11.5.6a and Figure F 11.5.6a. The vertical distance between rows shall not

exceed 3.5 m.

Single rows of sprinklers shall be central above shelves. Double rows shall be positioned so that each

row is the same distance from the nearest shelf edge.

The distance from the end of the shelf parallel to the range pipe lines to the nearest sprinkler shall be

half the sprinkler spacing along the range lines or 1.6 m, whichever is the smaller.

PROPOSAL n° 6 – Modification of Chapter 13.6

Modify 13.6 as follow:

13.6 Flushing connections

Each end of a distribution pipe feeding a zone or installation shall be fitted with a valve not less than 50mm nominal diameter or distribution pipe diameter whichever is smaller. The valve outlet shall be fitted with a metallic plug or cap. Flushing connections, with or without permanently installed valves, shall be fitted on the spur ends of the installation distribution pipes. They shall - be at least DN50 and

In case of distribution pipes bigger than DN50 flushing connection shall be connected eccentrically at the bottom of the distribution pipe or directly to the bottom of the distribution pipe. and be at least 200mm long Flushing connections shall be fitted with a suitable plug or cap. NOTE 1: it may be desirable in certain cases to fit flushing connections on ranges, e.g. in the form of a blank tee. NOTE 2: in addition to their use for flushing of the pipework, flushing connections may be used to check that water is available and for carrying out pressure and flow tests. NOTE 3: pipework which is completely full of water may be damaged by the increase in pressure due to temperature rises. If complete venting of air in an installation is likely to occur, e.g. in the case of a gridded layout with flushing connections at the extremities, consideration should be given to the fitting of pressure relief valves or expansion vessels.

PROPOSAL n° 7 – Modification of Chapter 15

15 Pipework

15.1 Underground piping

Pipes shall be installed in accordance with the manufacturer’s instructions and shall be protected

against corrosion.

NOTE: the following types of pipe are recommended: cast iron, ductile iron, spun cement, High

density PE and PP, reinforced glass fibre.

CEA 4001-2013 – Sprinklers Systems – Inquiry on amendments 2016 (February) 15/67

Adequate precautions shall be taken to prevent damage to piping, for example by passing vehicles.

15.2 Above ground piping

15.2.1 General

Piping downstream of control valves shall be steel or copper or another material in accordance with

appropriate specifications valid in the place of use of the system.

If accepted by the authorities, other systems for piping and connections than listed in this standard

can be used if they have been approved for their specific application in the place of use of the

system. Test standard has also to be approved by the authorities.

NOTE 1: if required by authorities, internally galvanised steel, can be used for dry, alternate or pre-

action installations.

Pipes shall be installed in such a way that they are easily accessible for repairs and alterations. Unless

complying with 15.2.9 they shall not be embedded in concrete floors or ceilings.

15.2.2 Steel pipes

15.2.2.1 Quality of pipe

All steel pipes shall be in accordance either with EN 10216 (seamless pipes), EN 10217 (welded pipes)

or EN 10255.

Acceptable series are given in table T 15.2.2.2a.

15.2.2.2 Minimum wall thickness

The minimum acceptable wall thickness of steel pipe shall be in accordance with Table T 15.2.2.2a.

Table T 15.2.2.2a minimum wall thickness for steel pipes

Nominal diameter

External Ø

Roll grooved or welded Threaded pipes and cut grooved

EN 10 216-1 EN 10 255 (L2/L Serie)

EN 10 217–1

EN 10 255 (M Serie)

EN 10 216 –1

EN 10 217 –1

DN 20 3/4 26,9 2,6 N/A 2,6 N/A 3,2 3,2

DN 25 1" 33,7 2,6 2,6 2,6 3,2 3,2 3,2

DN 32 1"1/4 42,4 2,6 2,6 2,6 3,2 3,2 3,2

DN 40 1"1/2 48,3 2,6 2,9 2,6 3,2 3,2 3,2

DN 50 2" 60,3 2,6 2,9 2,6 3,6 3,6 3,6

DN 65 2"1/2 76,1 2,6 3,2 2,6 3,6 3,6 3,6

DN 80 3" 88,9 2,9 3,2 3,2 4 4 4

DN 100 4" 114,3 3,2 3,6 3,6 4,5 4,5 4,5

DN 125 5" 139,7 3,6 4,5 4 5 5 5

DN 150 6" 168,3* 4 4,5 4,5 5 5 5

DN 200 8" 219,1 4,5 - 4,5 - 6,3 6,3

DN 250 10" 273 5 - 5 - 6,3 6,3

DN 300 12" 323,9 5,6 - 5,6 - 7,1 7,1

DN 350 14" 355,6 5,6 - 5,6 - 8 8

DN 400 16" 406,4 6,3 - 6,3 - 8,8 8,8

DN 450 18" 457 6,3 - 6,3 - 10 10

DN 500 20" 508 6,3 - 6,3 - 11 11

N/A: Not applicable * 165,1 for EN 10255

CEA 4001-2013 – Sprinklers Systems – Inquiry on amendments 2016 (February) 16/67

Considering possible evolution of pipe standards, the minimum wall thickness shall be either the one

given in this table or the one given in the standard, whichever is greater.

When mechanical pipe joints are used, minimum wall thickness shall also be in accordance with the

joint approval recommendations. When product approval requires a greater thickness, the largest

value shall be applied.

15.2.2.3 Stainless steel pipes

Stainless steel pipes shall comply with EN ISO 1127 and have the minimum thickness given in table

T15.2.2.3a.

Table T15.2.2.3a specifies the minimum wall thickness for roll grooved or welded stainless steel

pipes. For machined or cut grooved pipe refer to Table T15.2.2.2a

When mechanical pipe joints are used, minimum wall thickness shall also be in accordance with the

joint approval recommendations. When product approval requires a greater thickness, the largest

value shall be applied.

Table T15.2.2.3a minimum wall thickness for roll grooved or welded stainless steel pipes

Nominal diameter (mm) for stainless steel

Minimum thickness

25 2,0 mm

32

40

50

65 2,9 mm

80

90

100

125 3,2 mm

150

200

250 4,0 mm

15.2.3 Copper pipe

15.2.3.1 General

Copper pipes shall be used in wet pipe systems only, installed in flow direction downstream of the

alarm valve. Pipes up to DN 50 shall be in accordance with EN 1057. Pipes larger than DN 50 and up

to DN 100 shall be in accordance with EN 12449.

15.2.3.2 Pipe wall thickness

Table T15.2.3.2a gives the minimum wall thickness of copper pipe.

CEA 4001-2013 – Sprinklers Systems – Inquiry on amendments 2016 (February) 17/67

Table T 15.2.3.2a: Minimum wall thickness for copper pipes

DN ≤ 40 50 ≤ 80 100

Minimum wall thickness (mm)

1,5 2,0 2,5

When mechanical pipe joints are used, minimum wall thickness shall also be in accordance with the

joint approval recommendations. When product approval requires a greater thickness, the largest

value shall be applied.

15.2.4 Welding

15.2.4.1 Steel pipe

Welders shall be approved in accordance with EN 287-1.

Pipe and fittings less than DN 65 shall be welded in the installer workshop / factory, except for

limited adjustments, providing that the workshop quality control procedures are applied on site.

In no case shall welding, flame cutting, soldering or any other hot work be carried out on already

installed pipework.

Welded sockets shall comply with EN 10241. The boring for welded sockets shall be at least equal to

the thread external diameter and not more than 2mm smaller than the socket external diameter. The

boring shall be deburred inside. The procedure of welding sockets onto pipes ≤ DN 50 shall be

approved by the authorities.

An accredited laboratory accepted by the authorities shall check the following welding procedures

and welding test pieces:

Socket weld procedure: Welding of sockets onto pipes smaller than DN 65 mm;

Pipe weld procedure: Welding of pipes smaller than DN 65mm including welding of pipes smaller

than DN 65mm onto larger dimensioned pipes.

The company performing welding shall have a quality management system accepted by the

authorities such as ISO 9001.

The quality management system shall include the following main requirements:

• The welded joint shall be made according to EN 25817, quality class D “Arc-welded joints in steel –

guidance on quality levels for imperfections”;

• No debris shall be left inside the pipes after the welding operation;

• The welding shall fully penetrate the pipe wall. The welding shall not intrude into the pipe more

than:

a) 1 mm average;

b) 1,5 mm maximum.

• The bending strength of the welded pipe joint shall be at least 80% of the pipe bending strength;

• If robot welding machines are used, the welding operation shall be fully automatic.

CEA 4001-2013 – Sprinklers Systems – Inquiry on amendments 2016 (February) 18/67

15.2.4.2 Copper pipes

Copper pipes shall be hard soldered using capillary solder fittings in accordance with EN 1254. The

fittings shall bear the manufacturer’s code.

For soldered connections of copper with copper, hard solders CP 105 or CP 203 shall be used in

accordance with EN 1044. The use of flux is not necessary.

For soldered connections of copper-zinc alloys (brass) or copper-tin alloys (red brass) among

themselves or with copper, hard solders AG 304 or AG 306 shall be used in accordance with EN

1044, using flux FH10 in accordance with EN 1045.

The junction from steel to copper shall be a flange connection with the steel pipe being provided

with a steel flange PN 16 in accordance with EN 1092-1 and the copper pipe being provided with a

solder flange in accordance with EN 1092 made of red brass. Stainless steel screws shall be used.

Hard solder connections shall be performed by specially trained experts only. The respective

qualification certificate which shall not be any older than two years and acquired at an institution

approved by the authorities shall be submitted to the authorities.

15.2.5 Mechanical pipe joints

Mechanical pipe couplings shall be approved.

Pipe joints with flanges according to relevant EN 1092 standard or equivalent, capillary solder fittings

in accordance with EN 1254, malleable cast iron fittings in accordance with EN 10242 (including

sealing material) are accepted without approval.

15.2.6 Flexible hoses that connect more than one single sprinkler

This chapter deals with flexible hoses / expansion joints that connect more than one single sprinkler.

15.2.6.1 General

If relative movement is likely to occur between different sections of pipework within the sprinkler

system, e.g. owing to expansion joints or in the case of free-standing storage racking, a flexible

section or joint shall be fitted at the point of connection to the distribution main. It shall meet the

following requirements.

a) it shall be capable of withstanding a test pressure of four times the maximum working

pressure or 40 bar, whichever is the greater, and shall not include parts which, when subject to fire,

might impair either the integrity or the performance of the sprinkler system;

b) Flexible hoses shall contain a continuous pressure-retaining stainless steel or non-ferrous

metal inner tube;

c) Flexible hoses shall not be fitted in the fully extended position.

d) Flexible hoses and joints shall not be used to take up misalignment between a distribution

main and the feed pipes to intermediate sprinklers.

CEA 4001-2013 – Sprinklers Systems – Inquiry on amendments 2016 (February) 19/67

The expansion joints and hoses shall be fitted where they are protected from external mechanical

impact.

15.2.6.2 Connections for mobile equipment

The pipework for mobile equipment, such as mobile racks or machines, can be connected via pipe

expansion joints or reinforced rubber hoses with stainless steel braiding approved by the authorities

to withstand a minimum pressure rating of 16 bar. The hoses shall be approved for the particular

installation situation (e.g. pressure load, operating temperature, distance and location of connection

points, frequency of movements, direction of movements, stroke lengths of movements, flow

conditions) and the number of guaranteed load changes shall be indicated.

15.2.7 Flexible hose for connecting one single sprinkler through false ceiling

The flexible hoses (metal) may be used only in static installations (e.g. for installation adjustment).

The flexible hoses are permitted to be used in LH, OH and HHP activities.

The flexible hoses are permitted to be used in hydraulically calculated wet system only.

Flexible hose shall be installed according to listing and product approval and particular attention shall

be paid to the following points:

The flexible hose assembly (hose, nipple and specific support) shall be approved and

accepted by the authority

The hose diameter shall not be less than DN 20 for LH and OH, and no less than DN 25

for HHP

The length including nipple shall not exceed 2m

The nipple (end of flexible hose where sprinkler head is connected) shall be fixed to false

ceiling structure with its specific support

Minimum bending radius should be 75 mm or the minimum value given by the product

approval, whichever is greater

Maximum allowed number of bends should be 3 or the maximum value given by the

product approval, whichever is less.

The hoses must be installed torsion-free.

Hydraulic calculation shall take into account the specific pressure loss given by the

product approval.

o Note: friction loss in flexible hose can be up to 10 times higher than in a rigid

pipe.

15.2.8 Press fitting pipe systems

Such pipe systems may be installed in sprinkler systems, provided that the system is approved for the

specific application. Application is limited to the protection of LH, OH1, OH2 or OH3 as well as

exhibition halls, cinemas, theatres and concert halls.

CEA 4001-2013 – Sprinklers Systems – Inquiry on amendments 2016 (February) 20/67

Mounting and installation shall be in accordance with product approval, Sprinkler installer shall be

specifically trained by product manufacturer.

Minimum wall thickness shall be part of the approval. A press fitting pipe system comprises at least

the following components:

- pipes;

- pipe fittings;

- transition pieces to other pipe qualities (materials) or valves;

- joining technique including the required materials, joining means, tools and assessment

principles for the quality of the pipe connection;

- specific pipe hangers, where required.

Components of different pipe systems shall not be combined.

The following shall be met as a matter of principle:

a) application in sprinkler wet pipe downstream of the alarm valve

b) the hanger distances specified in 15.3.2 for copper pipes apply to all systems unless approval

is more restrictive;

c) additives in the extinguishing water shall only be used if permitted by the product approval.

15.2.9 Concrete casting of sprinkler pipework

Pipe systems may be installed in concrete ceilings, provided that the system has an approval for this

type of application and installation. Mounting and installation shall be in accordance with product

approval. Sprinkler installer shall be specifically trained by product manufacturer.

The relevant requirements in chapter 15 shall be followed. The bridging of expansion joints shall be

avoided. Where this is not possible, the bridging shall be in accordance with the respective approval.

It is recommended to agree the procedure with the architect or structural engineer in the planning

phase.

The concrete installation dates shall be announced to the authorities beforehand. The authorities

reserve the right to do an on-site inspection or witness the pressure tests.

15.2.10 CPVC pipe systems

Such pipe systems may be installed in sprinkler systems, provided that the system is approved for the

specific application. Mounting and installation shall be in accordance with product approval.

Sprinkler installer shall be specifically trained by product manufacturer.

A CPVC pipe system comprises at least the following components:

- pipes;

- pipe fittings;

- transition pieces to other pipe qualities (materials) or valves;

CEA 4001-2013 – Sprinklers Systems – Inquiry on amendments 2016 (February) 21/67

- joining technique including the required materials, joining means, tools and assessment

principles for the quality of the pipe connection;

- specific pipe hangers, where required.

Components of different pipe systems shall not be combined.

Application is limited to the protection of LH and OH1 or OH2.

The following shall be met as a matter of principle:

a) installation is permitted only in wet systems.

b) unless specifically listed for that purpose, CPVC pipe shall not be exposed to UV light (e.g.

sunlight, UV lamp, etc).

c) CPVC pipe shall not be installed exposed unless specifically approved, and the area is

protected with quick response sprinklers.

d) when CPVC pipe runs in concealed spaces, these concealed spaces shall be protected by

sprinklers unless there is no fire load at all and the ceiling height is below 0,8m.

e) maximum ambient temperature shall be limited to 50ºC.Distance between two supports

shall not exceed value given in table T15.2.10a

f) additives in the extinguishing water are not permitted (e.g. anti-freeze solution, foaming

agent, other additives);

g) for hydraulic calculation using Hazen-Williams formula, C factor equal to 140 shall be used

h) test pressure with air is not permitted. Only hydrostatic test with water is permitted.

Table T15.2.10a maximum distance between 2 supports for CPVC pipes

Nominal diameter

20mm 25mm 32mm 40mm 50mm 65mm 80mm

Maximum distance in m

1,7 1,8 2 2,1 2,4 2,7 3

15.2.11 Plastic and composite pipe

Such pipe systems may be installed in sprinkler systems, provided that the system is approved for the

specific application. Mounting and installation shall be in accordance with product approval.

Sprinkler installer shall be specifically trained by product manufacturer.

A plastic or composite pipe system comprises at least the following components:

- pipes;

- pipe fittings;

- transition pieces to other pipe qualities (materials) or valves;

- joining technique including the required materials, joining means, tools and assessment

principles for the quality of the pipe connection;

CEA 4001-2013 – Sprinklers Systems – Inquiry on amendments 2016 (February) 22/67

- specific pipe hangers, where required.

Components of different pipe systems shall not be combined.

Application is limited to risks listed by authorities.

15.2.12 Protection against fire and mechanical damage

Piping shall be installed in such a way that the pipes are not exposed to mechanical damage. Where

pipes are installed above gangways with low headroom, or at intermediate levels, or in other similar

situations, precautions shall be taken against mechanical damage.

Where it is unavoidable for water supply or distribution pipework to pass through unsprinklered

areas, the pipework shall be either:

A) Enclosed by a 60 minutes fire barrier made of uncombustible material unless required

differently by the authorities or

B) Protected by sprinklers with a maximum spacing of 3m. Operation of these sprinklers has to

be monitored, e.g flow switch.

15.2.13 Painting

Non-galvanised ferrous pipework shall be painted for anticorrosive purposes. Authorities may accept

unpainted pipework if environmental conditions allows it.

Galvanised piping shall be painted wherever the coating has been damaged, e.g. by threading.

NOTE: extra protection may be needed for unusually corrosive conditions.

15.2.14 Drainage

Means shall be provided to enable all the pipework to be drained. Where this cannot be

done through the drain valve at the control valve set, extra valves shall be fitted in accordance with

13.4.

In the case of dry, alternate and pre-action installations range pipes shall have a slope

towards the distribution pipe of at least 0,4 % and distribution pipes shall have a slope

towards the appropriate drain valve of at least 0,2%.

Note: to better limit the risk of counter slope, and consequently to avoid water trapped into the pipe

work, wherever it is possible, the range pipe should have a slope toward the distribution pipe of at

least 1,2% and distribution pipes should have a slope toward the appropriate drain valve of at least

0,4%.

Range pipes shall only be connected to the side or top of distribution pipes.

CEA 4001-2013 – Sprinklers Systems – Inquiry on amendments 2016 (February) 23/67

15.3 Pipe supports

15.3.1 General

Pipe supports shall be fixed directly to the building or, if necessary, to machines, storage

racks or other structures. They shall not be used to support any other installation. They shall be of

the adjustable type in order to secure an even load bearing capability. Supports shall completely

surround the pipe and shall not be welded to the pipe or fittings.

The part of the structure to which the supports are secured shall be capable of supporting the

pipework (see Table T 15.2a). Pipes greater than DN50 should not be supported from corrugated

steel sheet or aerate concrete slabs.

Distribution pipes and risers shall have a suitable number of fixed points to take account of axial

forces.

Axial forces can occur for example due to:

shear force and weight force in the case of risers or drop pipes

inflow of water into a dry pipework

pipe deflexions

No part of any support shall be made of combustible material.

Nails shall not be used.

Supports for copper pipes shall be provided with a suitable lining with sufficient electrical

resistance, in order to prevent contact corrosion.

15.3.2 Spacing and location

Unless specified elsewhere, supports shall generally be spaced no more than 4m apart on steel pipe

and 2m apart on copper pipe. For pipes of over DN 50 these distances may be increased by 50%

provided that one of the following conditions is met:

- 2 independent supports are fitted to the structure;

- a support is used which is capable of bearing a load 50% greater than that called for in Table T

15.3.2a.

When pipe couplings are used:

- there shall be at least one support within 1m of each joint;

- there shall be at least one support on each pipe section.

The horizontal distance from the last support to the end of branch line shall not exceed:

- 0,9m for DN 25 diameter piping;

- 1,2m for piping greater than DN 25 diameter.

The horizontal distance from any upright sprinkler to a support shall not be less than 0,15m.

CEA 4001-2013 – Sprinklers Systems – Inquiry on amendments 2016 (February) 24/67

Vertical pipes shall have additional supports in the following cases:

- pipes more than 2m long;

- pipes more than 1m long feeding single sprinklers.

The following pipes do not need to be separately supported unless they are at a low level or

otherwise vulnerable to mechanical impact:

- horizontal pipes less than 0,45m long, feeding individual sprinklers;

- drop or rise pipes less than 0,6m long feeding individual sprinklers.

Extension sleeves for threaded rods of hangers shall be secured, e.g. by a counter nut. The same

applies to threaded rods for fastening corrugated steel sheet hangers.

Pipe supports for corrugated steel sheets, aerate or pumice concrete slabs shall be agreed by the

authorities.

Plugs in aerate or pumice concrete slabs shall have a distance of not less than 150 mm from the edge

of the slab.

Sleeves and recesses in beams or equivalent load bearing construction can be considered as

acceptable pipe supports, subject to :

if the bearing area in pipe sleeves has a length of 10 cm minimum, it may be regarded

as “two independent supports” (see beginning of chapter 15.3.2).

an additional support shall be installed to prevent any lateral displacement at least

every 25 m.

where sprinkler branch pipes pass through sleeves, the free pipe end shall be supported

as well. The nominal diameter of sleeves for branch pipes shall not exceed DN 80.

Where sprinkler pipe hangers are fastened to wooden beams, the minimum values specified in Table

T 15.3.2a shall be complied with.

Table T 15.3.2a: Pipe supports on wooden beams

Nominal diameter Bolt diameter mm

Wood screw diameter Mm

DN 50 6 2 x 6

> DN 50 DN 100 8 2 x 8

> DN 100 DN 150 10 2 x 10

>DN 150 DN 200 12 2 x 12

In the case of double hangers the number of wood screws or bolts shall be increased in accordance

with Figure F 15.3.2a subject to the type of hanger.

CEA 4001-2013 – Sprinklers Systems – Inquiry on amendments 2016 (February) 25/67

Figure F 15.3.2a: Pipe supports on wooden beams

Single

hangers

Spacing

4 m

2 wood screws

1 bolt

Double

hangers

Spacing

6 m

4 wood screws

2 bolts

1 through bolt

Bolts shall have washers on both sides. The minimum thickness of the wooden beams shall be 0,1 m.

The bolts shall be located at a distance from the lower beam edge that is at least 3 times their

diameter.

Wood screws shall be screwed in up to a depth of at least 8 times their diameter and only be fixed

into the side of wooden beams. The distance between screws and lower beam edge shall be at least

5 times their diameter.

Beam clamps for pipes up to DN 65 shall be fastened to beams only if their contact areas do not

deviate from the horizontal by more than 10°. The clamps shall only be loaded by vertical traction.

The clamp screws shall be mounted to the sloping area of the beam. Any other types of beam clamps

shall be approved by the authorities.

Sound absorbing inlays for pipe hangers shall be used only if required. The type of sound absorbing

inlay shall be agreed with the authorities in each individual case.

15.3.3 Design

Pipe supports shall either be approved or designed in accordance with the requirements of Tables T

15.2.3a and T 15.2.3b.

Table T 15.2.3a: Design parameters for pipe supports made of steel

Nominal pipe diameter (d) mm

Minimum load capacity at 20°C1) N

Minimum cross section2) mm²

d 50

50 < d 100

2.000 3.500

30 (M8) 50 (M10)

CEA 4001-2013 – Sprinklers Systems – Inquiry on amendments 2016 (February) 26/67

100 < d 150

150 < d 200

200 < d 250

250 < d 300

5.000 8.500 10.000 12.500

70 (M12) 125 (M16) 150 (M18) 180 (M20)

1) When the material is heated to 200°C the load bearing capacity shall not

deteriorate more than 25%. 2) Values in brackets are valid for threaded components.

Table T 15.2.3b: Minimum dimension of flat steel rods and clips

Nominal pipe diameter (d) mm

Flat steel rods Pipe clips

galvanised mm Black steel mm

galvanised mm Black steel mm

d≤50 50<d≤200

2,5 2,5

3,0 3,0

25x1,5 25x2,5

25x3,0 25x3,0

15.3.4 Anchorage in concrete ceilings

Anchors shall be approved by the building control authorities as follows:

for individual fastening in cracked concrete (European Technical Approval in accordance with

European Technical Approval Guideline 001/Part 1-4 Opt. 1-6), or

for multiple fastening of non-bearing constructions (European Technical Approval in accordance with

European Technical Approval Guideline 001/Part 6).

Note: Comparable national approvals such as any still valid general building control approvals for

anchors for lightweight ceiling lining and false ceilings are equivalent to approvals in accordance with

ETAG 001/Part6.

The anchors shall be dimensioned in accordance with the building control approval. The relevant

load is the 1,4-fold of the effective load.

Anchors shall fulfil the requirements of the following table as regards tensile strength (steel failure,

NRk,s) and thread (if applicable).

Table T 15.3.4a: Minimum tensile strength and minimum thread

Use for ceiling anchorage of pipes of nominal width D by means of one anchor per anchorage spot

Minimum thread of anchor

Characteristic tensile strength (steel failure) NRk,s [N]

D ≤ DN 50 M 8 ≥ 6.000

DN 50 < D ≤ DN 100 M10 ≥ 10.500

DN 100 < D ≤ DN 150 M12 ≥ 15.000

DN 150 < D ≤ DN 200 M16 ≥ 25.500

DN 200 < D ≤ DN 250 M20 ≥ 30.000

DN 250 < D ≤ DN 300 M20 ≥ 37.500

CEA 4001-2013 – Sprinklers Systems – Inquiry on amendments 2016 (February) 27/67

When anchors approved for multiple anchorage of non-bearing constructions are used, it shall be

ensured even in the event of theoretical failure of one anchor the pipework remains functional.

Note: This may be achieved e.g. at pipe deflexions or end anchorage of projecting pipes by using one

anchor approved for multiple anchorage of non-bearing constructions for every two independent

anchorage spots (pipe hangers) or by reducing the hanger distances at these spots. The distance of

the penultimate hanger from the pipe end shall not exceed 3 m, and 2,5 m for pipes DN 25. The

fastening of pipe deflexions shall be designed such that after an assumed failure of a hanger at a

deflexion a hanger distance of 6 m is not exceeded. Redundancies are not required, provided that at

the relevant spots an anchor approved for individual anchorage in cracked concrete is used.

15.4 Pipework in concealed spaces

Where sprinkler protection is required in concealed spaces such as false ceilings and floors, the

pipework shall be designed as follows:

15.4.1 False ceilings above LH or OH occupancies

Sprinklers above the ceiling may be fed from the same range pipes as the sprinklers below the

ceiling.

15.4.2 All other cases

The sprinklers in the concealed space shall be fed from separate range pipes. In the case of pre-

calculated systems, distribution pipes feeding sprinklers both inside and outside the concealed space

shall be no less than 65mm diameter.

PROPOSAL n° 8 – Modification of Chapter 18

Modify 18.3 as follow

18.3 User’s test and control programme of inspection and checking

18.3.1 General

The installer shall provide the user with a test and control inspection and checking programme for

the system. The programme shall include instruction on the action to be taken in respect of faults,

operation of the system, with particular mention of the procedure for emergency manual starting of

pumps, and details of the weekly routine of 18.3.2.

PROPOSAL n° 9 – Modification of D3 and F7

Suppress D3.3 and modify the annex D3.3 to D3.7 as follow (because suppression of D.3.3 impacts numbering.

D.3.3 Flushing Valves

Each zone shall be fitted with a valve not less than 20mm nominal diameter, either on the end of the distribution pipe hydraulically most remote from the water supply, or on the end of each

CEA 4001-2013 – Sprinklers Systems – Inquiry on amendments 2016 (February) 28/67

distribution pipe spur, as appropriate. The valve outlet shall be fitted with a brass plug cap.

D.3.3 Monitoring Zoned sprinkler installations shall be provided with tamper proof devices to monitor the status of: a) each stop valve (i.e. either fully open or not fully open), including subsidiary stop valves, capable of interrupting the flow of water to sprinklers; b) water flow into each zone immediately downstream of each zone subsidiary stop valve, to indicate the operation of each zone, by means of a water flow alarm switch capable of detecting a flow equal to or greater than that from any single sprinkler; c) water flow through each installation control valve set. D.3.45 Zone test and drainage facilities Permanent test and drainage facilities shall be provided immediately downstream of the water flow alarm switch on each zone. The test facility shall simulate operation of any single sprinkler head. Adequate provision shall be made for the disposal of waste water. D.3.56 Installation control valve set The main control valve set of a zoned sprinkler installation shall have two stop valves, one on each side of a single alarm valve with a bypass connection of the same nominal bore around all three valves, fitted with a normally closed stop valve (see Figure F D.3.56a). Each of the three stop valves shall be fitted with tamper proof devices to monitor their status (i.e. fully open or not fully open).

Figure F D 3.56a- Control valve bypass arrangement for zoned multi-storey building installations

D.3.67 Installation monitoring and alarms The monitoring devices required by D.3.34 and D.3.56 shall be electrically connected to a control and indicating panel, located on the premises, where the following indications and warnings shall be given: a) by means of green visual indicators that each monitored stop valve is in its correct operational position;

CEA 4001-2013 – Sprinklers Systems – Inquiry on amendments 2016 (February) 29/67

b) by means of audible devices and amber visual indicators that one or more control valve sets are not fully open; c) by means of audible devices and amber visual indicators that one or more zone subsidiary stop valves are not fully open; d) by means of audible devices and amber visual indicators that the static pressure in any trunk main supplying the system has fallen to a value 0,5bar or more below the normal static pressure; d) by means of audible devices and red visual indicators that water is flowing into the installation; e) by means of audible devices and red visual indicators that water is flowing into one or more zones.

Facilities shall be provided at the indicator panel for silencing the audible alarms but the visual indicators shall continue to operate until the installation is restored to the normal standby condition. Any change in the panel alarm or fault indication after the audible alarm has been silenced shall cause it to resume sounding until it is again silenced or the panel reset to the normal standby condition.

Modify F7 as follow (consequence of suppression of D3.3):

F.7 Additional precautions for maintenance

Only one zone of a multi-zone installation shall be shut down at a time. An installation or zone shall be shut down for the minimum time necessary for maintenance. The partial or complete shut-down of a sprinkler installation shall be avoided wherever possible. Only the smallest part of the installation necessary shall be isolated. When a zone (or zones) is charged or recharged with water after draining, the flushing valve(s) (see 13.6 D.3.3) shall be used to check that water is available in the zone (or zones). Individual alarm valves in a duplicate control valve set, where required, shall be separately serviced, provided the water supply to the installation is maintained. The following procedure shall be followed before servicing duplicate control valve sets: - the stop valves to the duplicate alarm valve shall be checked and if necessary opened. One of the stop valves to the alarm valve to be serviced shall be closed and an alarm test (see 18.3.2.3) carried out immediately on the other alarm valve; - if water is not available, the stop valve shall be opened immediately, and the fault rectified before proceeding.

CEA 4001-2013 – Sprinklers Systems – Inquiry on amendments 2016 (February) 30/67

PROPOSAL n° 10 – Modification of Annex K

Modify K7 as follow:

K.7 Special requirements for protection of storage utilising Polypropylene (PP) and

Polyethylene (PE) storage containers

K.7.1 Storage methods ST4 – Palletised rack

Polypropylene and Polyethylene storage containers having a single wall, through which water can

permeate (1) shall be classified as high hazard category III (HHS3).

All other configurations shall be classified as high hazard category IV (HHS4).

“Sprinklers shall have the sensitivity rating “Special” or “Quick” (see note 1 table T 12.5.1a).

NOTE 1: containers shall be assumed to be water permeable if the head of water collected in the

container does not exceed 10 mm for a water discharge into the container, equivalent to 20 mm/min.

(Storage containers with 5 mm diameter drainage holes uniformly distributed at not less than 50

holes/m2 of container plan area, may satisfy the above water permeability requirements).

Consideration shall be given to the influence of the stored goods and any packaging materials on

water permeability.

The maximum horizontal distance of the sprinklers in intermediate levels for category HHS 4 shall not

exceed 1.5 m and 2.5 m for category HHS 3. Sprinkler shall have the sensitivity rating “special” at the

ceiling and “special” or “quick” in intermediate level. The maximum storage height for racks without

intermediate sprinklers shall not exceed 2.1 m for HHS 3 and 1.2 m for HHS 4.

K.7.2 Storage methods ST1 - free or block standing - ST2 and ST3 - post pallet storage

The maximum storage height shall not exceed 3 m.

Only non-combustible pallets with closed surface like steel pallets shall be used. The storage height

on each pallet shall not exceed 1 m. The top storage containers on the pallet shall be closed with a

lid.

Sprinklers shall have the sensitivity rating “Special” or “Quick”.

Film-forming foam shall be added to the water of the sprinkler system.

NOTE: if other sprinkler protection concepts are demonstrated by appropriate fire tests as adequate

protection the above requirements can be adapted.

CEA 4001-2013 – Sprinklers Systems – Inquiry on amendments 2016 (February) 31/67

PROPOSAL n° 11 – Modification of Annex L

Annex L

(normative)

ESFR sprinkler protection

L.10 Introduction

ESFR sprinklers are ceiling sprinklers which have the capability of suppressing fires within storage

risks. There is little room for error in the design and installation of ESFR sprinkler systems; the design

principles and the operating characteristics are significantly different from standard sprinkler

protection. ESFR sprinklers may be unable to cope with adverse design features and non-

compliances, which may be common practice when installing standard sprinkler protection. Design

and installation deviations from this standard may not just result in a reduced effectiveness, but

rather in a total system failure. It is therefore essential that all the requirements of this annex are

complied with, without exception, when applying ESFR protection.

L.11 Scope

This annex specifies requirements and recommendations for the design and installation of ESFR

sprinkler systems in buildings. It covers occupancies, storage arrangements, installation design,

building requirements and the management of protected buildings which is essential to ensure

satisfactory performance of ESFR sprinkler systems.

Only storage configurations and stored goods described in L7 are covered by this annex.

Unless specified differently in this annex L, all the requirements of the CEA 4001 are applicable when

designing and installing ESFR sprinklers.

L.12 Specific definitions

Sprinkler, ESFR (Early Suppression Fast Response) Pattern

A thermosensitive device designed to react at a predetermined temperature by automatically

releasing a stream of water and distributing it in a specified pattern and density over a designated

area to provide early suppression of a fire when installed on the appropriate sprinkler piping with a

suitable water supply.

ESFR sprinklers shall be quick (thermal) response and have one of the following temperature ratings:

Bulbs:

68°C

93°C

Fusible element:

68 to 74°C

93 to 104°C

The higher temperature ratings shall only be used where needed because of high ambient

temperature conditions.

The nominal K factor of ESFR sprinklers shall be between 200 and 360.

CEA 4001-2013 – Sprinklers Systems – Inquiry on amendments 2016 (February) 32/67

In addition to the design criteria specified in tables below, it shall be ensured that the type of ESFR

sprinkler (pendent or upright) used is installed according to its approval conditions (storage height,

max ceiling height, classification of goods…).

Note: higher K factor ESFR are in development. Their use shall be submitted to authority.

Ceiling height

The ceiling height shall be taken as the maximum vertical distance measured from the floor to the

underside of the ceiling. In the case of corrugated metal ceilings with a depth up to 75 mm, the

measurement can be made to the lowest point on the corrugation. In the case of corrugated metal

ceilings with a depth of more than 75 mm, the measurement shall be made to the average level

between the highest and the lowest point of the corrugation.

Maximum storage height

The vertical distance from the floor to the sprinkler deflector minus 1 m or the value shown in tables,

whichever is the lower

Cartoned

A method of storage consisting of cardboard (corrugated), wood or paperboard containers fully

enclosing (no open top) the goods.

exposed

Commodities that contains some plastic (>5%) and that are not in carton packaging (uncatoned) or

covering that absorb water or otherwise appreciably retard the burning hazard of the commodity.

L.13 Classification of goods

For the design of ESFR sprinkler systems the standard classification system within CEA 4001 have

been replaced by four different categories of plastics:

Cartoned unexpanded

Exposed unexpanded

Cartoned expanded

Exposed expanded

For goods containing no plastics at all, or very small amounts of plastics (i.e. Category I and II), the

design criteria for Cartoned unexpanded plastics shall be used.

If the protected commodity contains more than 15 % by weight, or more than 25 % by volume, of a

commodity requiring higher design demands, this higher category shall be used.

Minor numbers of single pallet loads of a higher design category may be allowed within the

protected area without changing the design criteria, providing none of the higher category pallet

loads are placed adjacent to each other However, if more than 15 pallet loads of a higher category

are stored within 9 000 m2, the design shall be based on this higher category.

L.13.4 Laced tyre storage

Tyre storage, often on pallets, where the tyres are stored in layers angled from the horizontal such

that alternating layers dovetail together, in a compact combination, see Figure L.1.4.1a

CEA 4001-2013 – Sprinklers Systems – Inquiry on amendments 2016 (February) 33/67

Figure F 4.1a—Laced tyre storage

L.13.5 Paper categories

The paper is categorized based on its weight per m².

Heavyweight: 100 g/m2

Mediumweight: 50 < 100 g/m2

Lightweight: < 50 g/m2.Tissue paper, toilet paper, towelling and other similar absorbent paper

products, shall be protected as lightweight paper, regardless of weight.

L.14 General

ESFR sprinkler protection shall only be used in buildings where the property, storage systems and

contents are controlled by appropriate management systems. The management system

documentation shall include procedures for at least the following:

a) risk assessment controls for incoming goods;

b) routine checking and inspection procedures;

c) sprinkler system maintenance contract with a qualified company

d) maintenance of an outline specification for the building and fire protection with a record of any

changes which may influence the performance of the sprinkler system;

e) regular review of methods of storage;

f) regular review of hazard;

g) regular review of compliance with ESFR installation requirements;

h) dealing with non-compliances.

NOTE The critical review of the hazard and storage methods specified in (a), (b), (d), (e), (f) and (g)

above should, at least, be in accordance chapter 18.

Regular review of hazard should include checking that aisles and flues in storages comply with

respective requirements.

The written procedures should encompass actions to be taken if major non-compliances occur and

should include informing authorities such as fire authorities and leading insurers.

L.15 Occupancies and fire hazards

ESFR sprinklers may be used to protect storages in accordance with Tables T.L.7.4b to T.L.7.4p. Table

T.L.7.4a provides a reference guide to Tables T.L.7.4b to T.L.7.4p.

ESFR sprinklers shall not be used to protect areas where one of the following is present:

CEA 4001-2013 – Sprinklers Systems – Inquiry on amendments 2016 (February) 34/67

a) Commodities and storage configurations which have not been approved by the authorities for

protection with ESFR sprinklers, e.g. flammable and combustible liquids;

b) Open top containers which may retain water;

c) Automatic heat and smoke venting;

Note 1: ESFR sprinkler protection may be used in conjunction with manually operated smoke

ventilation systems, suitable only for heat and smoke ventilation purposes, operated by the fire

brigade.

Note 2: If accepted by the authority, smoke vents can be automatically activated by individual

thermal sensitive element, providing they are rated no less than 140°C.

d) Solid shelving larger than 2 m2 per shelf.

L.16 ST4 (Racked), ST5 (shelved), ST2 and ST3 (post pallet) storage

L.16.4 Longitudinal and transverse flues

Storages shall have longitudinal and transverse flues, which are:

a) continuous for the full height of each block of storage;

b) vertically aligned;

c) free of stored goods and of any kind of obstruction

d) regularly spaced and having dimensions as follows:

Maintain all transverse flue spaces at a minimum net width of 0,075m throughout the

vertical height of the rack ; and

Maintain longitudinal flue spaces at a minimum net width of 0,15m throughout the vertical

height of the rack.

e) longitudinal flues shall be spaced at distances of not more than 3.0 m

f) Transverse flues shall be spaced at distances of not more than 3.0 m

g) The area between flue spaces shall not exceed 2m².

Note : e.g. a pallet of 2,5m in length cannot exceed 0,8m in width and shall be surrounded by flue

spaces as defined in d).

L.16.5 Shelving

Single and double row shelved racks have to be considered as solid shelves which cannot be

protected with ESFR sprinklers, except if they comply with one of the following:

a) slatted shelves shall have shelf open areas, uniformly interspaced, of at least 50 % of the shelf

plan area. The distance between openings shall not exceed 0,15 m; or

b) grated or mesh type shelves shall have uniform openings of at least 50 % of the shelf plan area.

The horizontal distance between openings shall not exceed 0,15 m; or

CEA 4001-2013 – Sprinklers Systems – Inquiry on amendments 2016 (February) 35/67

c) shelves having openings of less than 50% of the plan area shall not exceed 2.0 m² total plan area

and shall be bounded on all four edges by flue spaces of not less than 0.15 m width;

In all the above mentioned cases, the load shall not obstruct the transverse flue space. The distance

between 2 adjacent transverse flue spaces shall not exceed 3m.

When conditions above are met, the rack can be considered as open rack and may be protected by

an ESFR system.

When ST5 is mentioned in annex L, it shall be limited to 3,2m storage height and to a maximum

length of 12m with no less than 3,2m separation to adjacent storage, unless the requirements of L7.2

is fulfilled.

L.16.6 In-rack sprinklers for ESFR systems

In some cases additional In-Rack Sprinklers are required. This means that ceiling only protection is

not able to cool and/or control fire spread. In these cases one line of In- Rack Sprinklers shall be

provided close to 1/2 the storage height of the rack. The In-Rack Sprinklers shall be positioned at

each intersection of the transversal and longitudinal flue. Sprinklers need to be positioned within

150 mm of the centerline of the flue. All flues need to be protected.

Where required, one level of K115 or K160 quick response sprinklers shall be used.

In-rack sprinkler hydraulic design criteria shall be the most hydraulically remote eight sprinklers at

227l/min each.

Ceiling sprinkler demand shall be included in the hydraulic calcultion for the in-rack sprinkler

protection.

The most unfavourable demand shall be the most unfavourable combination between ceiling

demand and in-rack demand, that is not necessarily the most unfavourable ceiling demand neither

the most unfavourable in-rack demand.

L.16.7 Design requirements

Minimum operating pressure for the ESFR sprinklers included in the design area, see L.10.6.4, shall

be taken from the appropriate tables T.L.7.4b to T.L.7.4p. For guidance on the appropriate table, see

Table T.L.7.4a

Table T 7.4a — Guide to ESFR sprinkler use

Storage method

ST1 ST2/ST3 ST4 ST5

Commodity Table reference

Plastics

Unexpanded cartoned T. L.7.4b T .L.7.4c T .L.7.4c T .L.7.4b Unexpanded exposed T .L.7.4d T .L.7.4e T .L.7.4e T .L.7.4d Expanded cartoned T .L.7.4F T .L.7.4g T .L.7.4g T .L.7.4F Expanded exposed T .L.7.4h T .L.7.4i T .L.7.4i T .L.7.4h

Rubber tyres T. L.7.4n T .L.7.4n

CEA 4001-2013 – Sprinklers Systems – Inquiry on amendments 2016 (February) 36/67

Paper rolls stored on end: Light weight T .L.7.4j - - - Medium weight T .L.7.4k Heavy weight T .L.7.4l - - - Heavy weight plastic coated T .L.7.4m - - -

Commodities stored below Mezzanines T .L.7.4o T .L.7.4p T .L.7.4p -

Table T 7.4b —Unexpanded plastic in cartons, ST1 or ST5 storage

Storage applications: ST1 Free standing or block storage ST5 Solid or slatted shelves 1m or less wide (see L7.2)

Commodities: Cartoned unexpanded Plastics

Maximum storage height

Maximum ceiling height M

9,1 10,7 12,2 13,7 M

Sprinkler minimum operating pressure Bar

ESFR pendent or upright sprinkler nominal k-factor 200

7,6 3,5 5,2 NA NA

9,1 NA 5,2 NA NA

ESFR pendent sprinkler nominal k-factor 240

7,6 2,4 3,6 3,6 NA

9,1 NA 3,6 3,6 NA

10,7 NA NA 3,6 NA

ESFR upright sprinkler nominal k-factor 240

7,6 2,4 3,6 NA NA

9,1 NA 3,6 NA NA

ESFR pendent sprinkler nominal k-factor 320

7,6 1,7 2,4 2,8 2,8

9,1 NA 2,4 2,8 2,8

10,7 NA NA 2,8 2,8

12,2 NA NA NA 2,8

ESFR pendent sprinkler nominal k-factor 360

7,6 1,0 1,4 1,7 2,8

9,1 NA 1,4 1,7 2,8

10,7 NA NA 1,7 2,8

12,2 NA NA NA 2,8

NA Not applicable

CEA 4001-2013 – Sprinklers Systems – Inquiry on amendments 2016 (February) 37/67

Table T 7.4c — Unexpanded plastic in cartons, ST2, ST3 or ST4 storage

Storage applications: ST2/ST3 Post pallets ST4 Palletized racking

Commodities: Plastics: cartoned unexpanded

Maximum storage height

Maximum ceiling height M

9,1 10,7 12,2 13,7 m

Sprinkler minimum operating pressure Bar

ESFR pendent sprinkler nominal k-factor 200

7,6 3,5 5,2 6,2 + 1 level of in-rack

6,2 + 1 level of in-rack

9,1 NA 5,2 6,2 + 1 level of in-rack

6,2 + 1 level of in-rack

10,7 NA NA 6,2 + 1 level of in-rack

6,2 + 1 level of in-rack

12,2 NA NA NA 6,2 + 1 level of in-rack

ESFR upright sprinkler nominal k-factor 200

7,6 3,5 5,2 NA NA

9,1 NA 5,2 NA NA

ESFR pendent sprinkler nominal k-factor 240

7,6 2,4 3,6 3,6 4,3+ 1 level of in-rack

9,1 NA 3,6 3,6 4,3 + 1 level of in-rack

10,7 NA NA 3,6 4,3 + 1 level of in-rack

12,2 NA NA NA 4,3 + 1 level of in-rack

ESFR upright sprinkler nominal k-factor 240

7,6 2,4 3,6 NA NA

9,1 NA 3,6 NA NA

ESFR pendent sprinkler nominal k-factor 320

7,6 1,7 2,4 2,8 2,8

9,1 NA 2,4 2,8 2,8

10,7 NA NA 2,8 2,8

12,2 NA NA NA 2,8

ESFR pendent sprinkler nominal k-factor 360

7,6 1,0 1,4 1,7 2,8

9,1 NA 1,4 1,7 2,8

10,7 NA NA 1,7 2,8

12,2 NA NA NA 2,8

NA - Not applicable

CEA 4001-2013 – Sprinklers Systems – Inquiry on amendments 2016 (February) 38/67

Table T 7.4d — Exposed unexpanded plastic, ST1 or ST5 storage

Storage applications: ST1 Free standing or block storage ST5 Solid or slatted shelves 1m or less wide (see L7.2)

Commodities: Plastics :exposed unexpanded

Maximum storage height

Maximum ceiling height M

9,1 10,7 12,2 13,7 m

Sprinkler minimum operating pressure Bar

ESFR pendent sprinkler nominal k-factor 200

7,6 3,5 5,2 NA NA

9,1 NA 5,2 NA NA

ESFR pendent sprinkler nominal k-factor 240

7,6 2,4 3,6 3,6 NA

9,1 NA 3,6 3,6 NA

10,7 NA NA 3,6 NA

ESFR pendent sprinkler nominal k-factor 320

7,6 2,4 3,5 3,5 NA

9,1 NA 3,5 3,5 NA

10,7 NA NA 3,5 NA

ESFR pendent sprinkler nominal k-factor 360

7,6 2,4 3,5 3,5 NA

9,1 NA 3,5 3,5 NA

10,7 NA NA 3,5 NA

NA - Not applicable

CEA 4001-2013 – Sprinklers Systems – Inquiry on amendments 2016 (February) 39/67

Table T 7.4e — Exposed unexpanded plastic, ST2, ST3 or ST4 storage

Storage applications: ST2/ST3 Post pallets ST4 Palletized racking

Commodities: Plastics :exposed unexpanded

Maximum storage height

Maximum ceiling height M

9,1 10,7 12,2 13,7 m

Sprinkler minimum operating pressure Bar

ESFR pendent sprinkler nominal k-factor 200

7,6 3,5 5,2 5,2 6,2 + 1 level of in-rack

9,1 NA 5,2 5,2 6,2 + 1 level of in-rack

10,7 NA NA 5,2 6,2 + 1 level of in-rack

12,2 NA NA NA 6,2 + 1 level of in-rack

ESFR pendent sprinkler nominal k-factor 240

7,6 2,4 3,6 4,1 4,3 + 1 level of in-rack

9,1 NA 3,6 4,1 4,3 + 1 level of in-rack

10,7 NA NA 4,1 4,3 + 1 level of in-rack

12,2 NA NA NA 4,3 + 1 level of in-rack

ESFR pendent sprinkler nominal k-factor 320

7,6 2,4 3,5 4,1 4,3+ 1 level of in-rack

9,1 NA 3,5 4,1 4,3+ 1 level of in-rack

10,7 NA NA 4,1 4,3+ 1 level of in-rack

12,2 NA NA NA 4,3+ 1 level of in-rack

ESFR pendent sprinkler nominal k-factor 360

7,6 2,4 3,5 4,1 4,3+ 1 level of in-rack

9,1 NA 3,5 4,1 4,3+ 1 level of in-rack

10,7 NA NA 4,1 4,3+ 1 level of in-rack

12,2 NA NA NA 4,3 + 1 level of in-rack

NA - Not applicable

CEA 4001-2013 – Sprinklers Systems – Inquiry on amendments 2016 (February) 40/67

Table T 7.4f — Expanded plastic in cartons, ST1 or ST5 storage

Storage applications: ST1 Free standing or block storage ST5 Solid or slatted shelves 1m or less wide (see L7.2)

Commodities: Plastics: cartoned expanded

Maximum storage height

Maximum ceiling height

M

9,1 10,7 12,2 13,7 m

Sprinkler minimum operating pressure

Bar

ESFR pendent or upright sprinkler nominal k-factor 200

7,6 3,5 NA NA NA

ESFR pendent or upright sprinkler nominal k-factor 240

7,6 2,4 NA NA NA

ESFR pendent sprinkler nominal k-factor 320

7,6 2,4 NA NA NA

ESFR pendent sprinkler nominal k-factor 360

7,6 2,4 NA NA NA

NA - Not applicable

CEA 4001-2013 – Sprinklers Systems – Inquiry on amendments 2016 (February) 41/67

Table T 1.4g — Expanded plastic in cartons, ST2, ST3 or ST4 storage

Storage applications: ST2/ST3 Post pallets ST4 Palletized racking

Commodities: Plastics: cartoned expanded

Maximum storage height

Maximum ceiling height

M

9,1 10,7 12,2 13,7 m

Sprinkler minimum operating pressure

Bar

ESFR pendent or upright sprinkler nominal k-factor 200

7,6 3,5 NA NA NA

ESFR pendent or upright sprinkler nominal k-factor 240

7,6 2,4 NA NA NA

ESFR pendent sprinkler nominal k-factor 320

7,6 2,4 NA NA NA

ESFR pendent sprinkler nominal k-factor 360

7,6 2,4 NA NA NA

NA - Not applicable

CEA 4001-2013 – Sprinklers Systems – Inquiry on amendments 2016 (February) 42/67

Table T 7.4h — Exposed expanded plastic, ST1 or ST5 storage

Storage applications:

ST1 Free standing or block storage ST5 Solid or slatted shelves 1m or less wide (see L7.2)

Commodities: Plastics: exposed expanded

Maximum storage height

Maximum ceiling height

M

7,6 9,1 10,7 12,2 m

Sprinkler minimum operating pressure

Bar

ESFR pendent sprinkler nominal k-factor 200

6,1 3,5 6,9 NA NA

7,6 NA 6,9 NA NA

ESFR upright sprinkler nominal k-factor 200

6,1 3,5 NA NA NA

ESFR pendent sprinkler nominal k-factor 240

6,1 2,4 6,9 NA NA

7,6 NA 6,9 NA NA

ESFR upright sprinkler nominal k-factor 240

6,1 2,4 NA NA NA

ESFR pendent sprinkler nominal k-factor 320

6,1 1,7 4,8 NA NA

7,6 NA 4,8 NA NA

ESFR pendent sprinkler nominal k-factor 360

6,1 1,4 4,8 NA NA

7,6 NA 4,8 NA NA

NA - Not applicable

CEA 4001-2013 – Sprinklers Systems – Inquiry on amendments 2016 (February) 43/67

Table T 7.4i — Exposed expanded plastic, ST2, ST3 or ST4 storage

Storage applications: ST2/ST3 Post pallets ST4 Palletized racking

Commodities: Plastics: exposed expanded

Maximum storage height

Maximum ceiling height

M

7,6 9,1 10,7 12,2 m

Sprinkler minimum operating pressure

Bar

ESFR pendent sprinkler nominal k-factor 200

6,1 5,2 6,9 NA NA

7,6 NA 6,9 NA NA

ESFR pendent sprinkler nominal k-factor 240

6,1 3,6 4,8 NA NA

7,6 NA 4,8 NA NA

ESFR pendent sprinkler nominal k-factor 320

6,1 3,6 4,8 NA NA

7,6 NA 4,8 NA NA

ESFR pendent sprinkler nominal k-factor 360

6,1 3,6 4,8 NA NA

7,6 NA 4,8 NA NA

NA - Not applicable

CEA 4001-2013 – Sprinklers Systems – Inquiry on amendments 2016 (February) 44/67

Table T 7.4j — Rolls of light weight paper on end, ST1 storage

Storage applications: ST1 Free standing or block storage Suitable for paper rolls with or without steel bands or steel wires to prevent the paper from unrolling. Not suitable for protecting paper roll storages where the roll stacks are separated in both directions by 100 mm or more.

Commodities: Paper rolls stored on end

Maximum storage height

Maximum ceiling height

M

9,1 12,2 m

Sprinkler minimum operating pressure

Bar

ESFR pendent sprinkler nominal k-factor 200

7,6 5,21 5,22

NOTE 1 : The number of ESFR sprinklers assumed to be operating shall be 16 NOTE 2 : The number of ESFR sprinklers assumed to be operating shall be 25 (control mode)

Table T 7.4k — Medium weight paper rolls on end, ST1 storage

Storage applications: ST1 Free standing or block storage Suitable for paper rolls with or without steel bands or steel wires to prevent the paper from unrolling. Not suitable for protecting paper roll storages where the roll stacks are separated in both directions by 100 mm or more.

Commodities: Paper rolls stored on end – Medium weight paper

Maximum storage height

Maximum ceiling height

M

9,1 10,7 12,2 m

Sprinkler minimum operating pressure

Bar

ESFR pendent sprinkler nominal k-factor 200

6,1 6,1 6,1 6,1

ESFR pendent sprinkler nominal k-factor 240

6,1 3,4 5,2 5,2

ESFR pendent sprinkler nominal k-factor 320

6,1 1,7 5,2 5,2

ESFR pendent sprinkler nominal k-factor 360

6,1 1,4 2,1 2,7

NA Not applicable

CEA 4001-2013 – Sprinklers Systems – Inquiry on amendments 2016 (February) 45/67

Table T 7.4l — Heavy weight paper rolls stored on end, ST1 storage

Storage applications: ST1 Free standing or block storage Where the paper roll stacks are separated in both directions by 100 mm or more the paper rolls shall have steel bands or steel wires to prevent the paper from unrolling, otherwise protection suitable for paper rolls with or without steel bands or steel wires.

Commodities: Paper rolls stored on end – heavy weight paper

Maximum storage height

Maximum ceiling height

m

9,1 10,7 12,2 13,7 m

Sprinkler minimum operating pressure Bar

ESFR pendent sprinkler nominal k-factor 200

7,6 3,4 5,2 5,2 NA

9,1 NA 5,2 5,2 NA

ESFR pendent sprinkler nominal k-factor 240

7,6 2,4 3,6 3,6 NA

9,1 NA 3,6 3,6 NA

ESFR pendent sprinkler nominal k-factor 320

7,6 1,7 2,8 2,8 3,4

9,1 NA 2,8 2,8 3,4

ESFR pendent sprinkler nominal k-factor 360

7,6 1 1,7 1,7 3,4

9,1 NA 1,7 1,7 3,4

NA - Not applicable

CEA 4001-2013 – Sprinklers Systems – Inquiry on amendments 2016 (February) 46/67

Table T 7.4m — Plastic coated heavy weight paper, ST1 storage

Storage applications: ST1 Free standing or block storage Where the paper roll stacks are separated in both directions by 100 mm or more the paper rolls shall have steel bands or steel wires to prevent the paper from unrolling, otherwise protection suitable for paper rolls with or without steel bands or steel wires.

Commodities: Paper rolls stored on end – plastic coated heavy weight paper

Maximum storage height

Maximum ceiling height

M

9,1 10,7 12,2 m

Sprinkler minimum operating pressure

Bar

ESFR pendent sprinkler nominal k-factor 200

7,6 3,4 5,2 5,2

ESFR pendent sprinkler nominal k-factor 240

7,6 2,4 3,6 3,6

CEA 4001-2013 – Sprinklers Systems – Inquiry on amendments 2016 (February) 47/67

Table T 7.4n — Rubber tyres, ST3 or ST4 storage

Storage applications: ST3 open portable racks in multiple rows ST4 Palletized racking

Open bottomed storage systems only.

Commodities: Rubber tyres

Maximum storage height

Maximum ceiling height

m

9,1 10,7 12,2 m

Sprinkler minimum operating pressure

Bar

ESFR pendent sprinkler nominal k-factor 200

7,6 3,51 5,2² NA

ESFR pendent sprinkler nominal k-factor 240

7,6 2,41 3,6² 3,6²

ESFR pendent sprinkler nominal k-factor 320

7,6 1,71 2,4² 3,6²

ESFR pendent sprinkler nominal k-factor 360

7,6 1,01 1,7² or 2,8 2,8

9,1 NA 5,2 5,2

Note 1: Tyres shall be stored on side or on tread, but not laced Note 2: Tyres shall be stored only on side.

CEA 4001-2013 – Sprinklers Systems – Inquiry on amendments 2016 (February) 48/67

Table T L.7.4o — Various commodities beneath mezzanines up to 4.5m, ST1 storage

Storage applications: Mezzanines with: ST1 Free standing or block stacking,

Commodities: Plastics: cartoned unexpanded Plastics :exposed unexpanded Plastics: cartoned expanded Plastics: exposed expanded Paper rolls stored on end – Medium weight paper

Suitable for paper rolls with or without steel bands or steel wires to prevent the paper from unrolling. Not suitable for protecting paper roll storages where the roll stacks are separated in both directions by 100 mm or more.

Maximum storage height Maximum mezzanine height

m

4,5 M

Sprinkler minimum operating pressure

Bar

ESFR pendent or upright sprinkler nominal k-factor 200

Mezzanine height -1m clearance 3,5

ESFR pendent or upright sprinkler nominal k-factor 240

Mezzanine height -1m clearance 2,4

Table T 7.4p — Various commodities beneath mezzanines up to 4.5m , ST3 and ST4 storage

Storage applications: Mezzanines with: ST3 Post pallets in multiple rows ST4 Palletized racking

Commodities: Plastics: cartoned unexpanded Plastics :exposed unexpanded Plastics: cartoned expanded Plastics: exposed expanded

Maximum storage height Maximum ceiling height

m

≤ 4,5 m

Sprinkler minimum operating pressure

Bar

ESFR pendent sprinkler nominal k-factor 200

Mezzanine height -1m clearance 3,5

ESFR pendent sprinkler nominal k-factor 240

Mezzanine height -1m clearance 2,4

CEA 4001-2013 – Sprinklers Systems – Inquiry on amendments 2016 (February) 49/67

L.17 Building requirements

L.17.4 Roof or ceiling slope

The roof or ceiling slope shall not exceed 17% (170 mm/m).

L.17.5 Measures required to correct excessive roof or ceiling slope.

Where roof or ceiling slopes exceed 17%, the roof or ceiling shall be under-drawn with a suspended

ceiling. The suspended ceiling shall be of non-combustible construction, having an acceptable slope.

ESFR sprinklers shall be deployed below the suspended ceiling. Standard sprinkler protection shall be

installed within this concealed space if required by 5.4.

NOTE Ceiling slope influences the movement of hot gases across the ceiling and therefore influences

the operation of sprinkler heads during a fire. Excessive ceiling slope may result in the operation

sprinklers remote from the fire whilst delaying the operation of sprinklers in close proximity to the

fire.

L.17.6 Ceiling strength

Ceilings and any sub-ceilings shall be firmly secure and shall be capable of withstanding a vertical

upward thrust of 50 N/m2.

NOTE Ceiling materials considered suitable are 10 mm gypsum board, corrugated and sheet steel

and mineral tiles.

L.17.7 Sky lights

Sky lights shall be flush to the ceiling or underdrawn at the ceiling level. Sky lights shall be capable of

withstanding a temperature of 300°C for a period of at least 5 min.

Additional sprinklers need to be installed in skylights with a volume greater than 1 m3, measured

above the normal ceiling level, when the distance from the normal or suspended ceiling level to the

top of the deflector exceeds the maximum allowable distance between the ESFR sprinkler and

ceiling, see Table T L.8.9a. Any additional sprinkler shall also be of the ESFR type.

L.17.8 Powered ventilation

Coordinate the location of sprinklers and the design of powered heating, ventilation and air

conditioning for buildings protected by suppression mode sprinklers so that the air velocity at

sprinklers does not exceed 1.5 m/sec.

If it is not possible to meet this requirement, at least one of the following measures shall in this case

be adopted to mitigate the effects of air movement on ESFR sprinklers in the event of fire:

a) where powered ventilation is employed, the buildings shall be protected by a fire alarm

installation approved by the authorities. The powered ventilation shall be stopped and any

dampers closed automatically in response to the fire detection system alarm of fire; or

b) the horizontal distance between stored goods and the perimeter of the extraction ventilator

openings shall be not less than L (in m) given by the equation:

L = 1/2S + d

where

CEA 4001-2013 – Sprinklers Systems – Inquiry on amendments 2016 (February) 50/67

S is the sprinkler spacing (in m);

d is the ventilator duct diameter (in m).

or

c) install a horizontal sub-ceiling below the extraction ventilator openings. ESFR sprinklers shall be

located below the sub-ceiling in accordance with the normal spacing requirements, (see Figure F

L.2). The sub-ceiling shall have a minimum diameter or cross-sectional dimension W given by

either of the equations below.

If the ventilation airflow rate is known:

W = Q / 283 h

If the ventilation airflow rate is unknown:

W = 2,6 A* / h

where

Q is the ventilator air flow rate (in m3/min);

A* is the ventilator opening area (in m2)

h is the vertical distance between ceiling and top of the subceiling (in m).

Ceiling sprinklers shall be a horizontal distance of at least 0,7 times the sprinkler spacing from the

perimeter of the sub-ceiling.

NOTES

Note 1 Powered ventilators and fire dampers should preferably be stopped before the first sprinkler

operates. Fire detection systems should be either:

aspirating smoke detectors installed in all ventilation ducts extracting from the ESFR

protected risk; or

a fire detection system of detection performance equivalent to an aspirating smoke

detection system.

Note 2 If the air flow rate through the ventilator is not known then the duct velocity should be

measured using a suitable device such as Pitot tube and micromanometer. The air flow rate Q (in

m3/min) through a circular section duct may be calculated using the equation:

Q = 49 / 60 x A x V

where

A is the cross-sectional area of a circular duct (in m2)

v is the maximum velocity through the duct (in m/min)

CEA 4001-2013 – Sprinklers Systems – Inquiry on amendments 2016 (February) 51/67

Figure 1 — Sprinklered sub-ceiling below a ventilator

Powered ventilation

Key 1. Sub-ceiling dimension – W (in m)

2. Sub-ceiling sprinkler

3. Roof or ceiling sprinkler

4. Sub-ceiling

5. Ventilator

6. Ventilator diameter – D (in m)

7. Ceiling

8. Vertical distance between sub-ceiling and ventilator – h (in m)

Ventilator air flow rate – Q(in m3/min)

L.17.9 Walkways and conveyors

Walkways and conveyors, not exceeding 3,0 m width, shall be protected underneath by a centrally

located single row of ESFR sprinklers or spray pattern sprinklers. The sprinklers shall be spaced not

more than 3,0 m apart. Walkways and conveyors exceeding 3,0 m width shall be treated as

mezzanines.

L.17.10 Sprinkler protection beneath mezzanines

Where the height of the mezzanines above the floor exceeds 4,5 m, the underside of the mezzanines

shall be protected by ESFR sprinklers according to table T L7.4b to T L7.4n. Where the height of the

mezzanines above the floor is 4,5 m or less ESFR according to table T L7.4o or T L7.4p, or appropriate

spray pattern sprinkler protection may be employed.

Where mezzanines have openings into the protected building, the storage beneath the mezzanine

shall not be closer to the open face than:

a) the outside line of sprinklers beneath the mezzanine, if there is no vertical smoke curtain of at

least 600 mm depth; or

b) within the bounds of a 600 mm deep smoke curtain.

NOTE Where spray pattern sprinkler protection is used below low mezzanines, it should fully comply

with the appropriate CEA 4001 clauses.

CEA 4001-2013 – Sprinklers Systems – Inquiry on amendments 2016 (February) 52/67

L.18 ESFR sprinkler installation design.

L.18.1 Installation type

Sprinkler installations shall be of the wet-pipe type.

L.18.2 ESFR sprinkler location relative to obstructions at or near the ceiling or roof

Pendent ESFR sprinklers shall be located at the appropriate horizontal distance from obstructions at

the ceiling or roof such as beams, ducts, joists, distribution pipes, range pipes or light fittings as given

in Table T L.8.9a

NOTE ESFR sprinklers should be located no closer than 0,1 m horizontally from the bottom near

side edge of joists, trusses or similar obstructions. In some instances it may be advantageous to vary

ESFR sprinkler spacings across the ceiling to avoid obstructions to the sprinkler water distribution.

Table T L18.2a — ESFR sprinkler location relative to ceiling obstructions such as beams or joists

Distance a 1 Distance b 1

Horizontal distance from sprinkler axis to side of obstruction Maximum height of ESFR sprinkler deflector above (+) bottom of obstruction

Greater than mm Less than mm mm

100 300 0

300 500 40

500 600 75

600 800 140

800 900 200

900 1100 250

1100 1200 300

1200 1400 380

1400 1500 460

1500 1700 560

1700 1800 660

1800 1850 790

Note 1: See Figure F L18.2b

Figure F L18.2b Position of deflector when located above bottom of beam or other obstruction

located at the ceiling.

CEA 4001-2013 – Sprinklers Systems – Inquiry on amendments 2016 (February) 53/67

Key:

a - Object is located entirely within checkerboard area: this does not represent any obstruction to the

sprinkler.

b - Object is located entirely within discharge area of the sprinkler: this does not represent an

obstruction to the umbrella discharge pattern of the sprinkler. However, it should be verified if the

object represents an obstruction to the sprinkler’s inner core discharge.

c - Umbrella discharge pattern obstructions are all objects (usually situated at or near ceiling level)

which cross the border from the checkerboard area into the inner core area of the sprinkler thus

disrupting the umbrella pattern.

If the above recommended distances cannot be ensured, install two rows of sprinklers on both side

of the object. The maximum distance between the object and the sprinkler shall not exceed half (1/2)

of the maximum recommended distance between sprinklers for the specific ceiling height.

Figure FL18.2d — Position of deflector when located above bottom of beam or other obstruction

located at the ceiling and the recommended distances can not be ensured.

Note: Exceptions

i.) The object located at or near ceiling level is at least 70% open

ii.) The object located at or near ceiling level is no wider than 75 mm and is separated from

other objects by a minimum of 300 mm.

Upright ESFR sprinklers shall be located at the appropriate horizontal distance from obstructions at

the ceiling or roof such as beams, ducts, joists, distribution pipes, range pipes or light fittings. See

individual listings for each sprinkler type.

ESFR sprinklers shall be permitted for use in buildings with all types of ceiling construction. Where

the depth of solid structural members (beams, stem etc) exceed 300 mm, ESFR sprinklers shall be

installed in each bay formed by the solid structural members. Minimum sprinkler spacing and area of

coverage shall comply with the requirements of Table T L.18.2a

CEA 4001-2013 – Sprinklers Systems – Inquiry on amendments 2016 (February) 54/67

L.18.10 ESFR Obstructions entirely below Sprinkler Deflector

Figure F L.18.10a. Position of objects when located entirely below ESFR sprinklers

Key:

a - The maximum width of the object permitted in this area is 20 mm

b - The maximum width of the object permitted in this area is 32 mm

c - The maximum width of the object permitted in this area is 50 mm

d - Objects having a width between 50 and 300 mm (inclusive) shall be located at least 300 mm

horizontally from the sprinkler deflector. A minimum of 450 mm vertical distance shall be kept

between the underside of the object and the top of storage.

e - Objects having a with between 300 and 600 mm (not inclusive) should be located at least 600 mm

horizontally from the sprinkler deflector. A minimum of 900 mm vertical distance shall be kept

between the underside of the object and the top of storage.

f - Objects having a width between 600 and 1200 mm (inclusive) shall be fitted with one row of

sprinklers centered under them, having the same branch line size, same orientation, same

temperature rating and same K-Factor like the ceiling level sprinklers.

g - Objects having a width between 1200 and 3000 mm (inclusive) shall be fitted with two rows of

sprinklers under them, having the same branch line size, same orientation, same temperature rating

and same K-Factor like the ceiling level sprinklers.

*Note : Upright Storage sprinklers can tolerate individual objects up to 100 mm wide located directly

below them at any vertical distance.

All the above mentioned recommendations should be verified together with each other. The position

of the objects shall be verified for the whole space between the sprinkler deflector and the top of

storage.

CEA 4001-2013 – Sprinklers Systems – Inquiry on amendments 2016 (February) 55/67

L.18.11 Open Structures like Bar Joists or Open Trusses.

ESFR sprinklers shall be installed a minimum of 0,3 m horizontally from the bottom of a bar joist or

open truss.

L.19 Pipe sizing

ESFR sprinkler installations shall be fully hydraulically calculated.

L.19.1 Minimum pipe sizes

The nominal bore of distribution pipes and range pipes shall not be less than 25 mm.

L.19.2 Minimum ESFR sprinkler flow pressure

The calculated discharge pressure of any ESFR sprinkler, when all the design sprinklers at ceiling level

plus any additional sprinklers under obstructions are operating, shall not be less than as given in

Tables T L.7.4b to T L.7.4p

L.19.3 The number of sprinklers assumed to be operating

The number of roof or ceiling ESFR sprinklers assumed to be operating shall be twelve (12).

In case of ESFR sprinklers below solid mezzanines with a height of 4,5 m or less, the number of these

ESFR sprinklers assumed to be operating shall be six (6), without the need to add them to the

demand of the roof sprinkler.

In case of open mezzanines, the authorities shall be consulted.

Any additional ESFR sprinklers below obstructions do not need to be added to the ceiling demand in

the hydraulic calculation.

Where additional spray sprinklers are installed below obstructions near the floor level , e.g. to

protect the area below conveyors, sprinklers with a k-factor of minimum 115 shall be provided and

up to 8 sprinklers shall be added to demand of the ceiling in the hydraulic calculation at a rate of 115

l/min per spray sprinkler

Where the tables above specify “1 level of in-racks”, spray sprinklers with a k-factor of minimum 115

shall be provided and 8 in-rack sprinklers shall be added to demand of the ceiling in the hydraulic

calculation at a rate of 230 l/min per spray sprinkler.

L.19.4 Shape of design sprinkler area

To determine the water supply capacity and for pipe sizing purposes , the shape of the design

sprinkler area shall be taken as four adjacent sprinklers operating on each of three adjacent range

pipes, plus any additional sprinklers as specified. Where ESFR sprinklers are used to protect storage

areas beneath mezzanines and where the design number of sprinklers is reduced to six ESFR

sprinklers, then three sprinklers shall be assumed to operate on each of two ranges.

NOTE Where range pipes have fewer than the designated number of ESFR sprinklers per range, all

the sprinklers should be assumed to be operating, and the number of ranges involved should be

increased to compensate.

CEA 4001-2013 – Sprinklers Systems – Inquiry on amendments 2016 (February) 56/67

L.19.5 Sprinklers beneath obstructions etc

For pipe sizing purpose, any additional ESFR sprinklers beneath obstructions within the design area,

shall be assumed to be operating, at not less than the specified ESFR sprinkler flow pressure as

defined in Tables T L.7.4b to T L.7.4p

NOTE See also L.11 for additional In-Rack sprinkler requirements.

L.20 Sprinkler spacing and location

L.20.1 ESFR sprinkler area of coverage

The area of coverage and spacing of ESFR sprinklers shall comply with Table T L.20.

Table 10.1a — ESFR sprinkler spacing

Ceiling height Distance between sprinklers Area of coverage per sprinkler

Minimum Maximum Minimum Maximum

m m m m2 m2

≤ 9,1 2,4 3,7 6,0 9,3

> 9,1 ≤ 13,7 2,4 3,1 6,0 9,3

L.20.2 Obstructions

Elimination of obstructions is critical to the success of suppression mode sprinklers. There can be

cases where a slight extension in sprinkler spacing and coverage in isolated areas can eliminate

obstructions. If increasing spacing between two adjacent heads on ranges or between two adjacent

ranges can eliminate obstructions, then the max spacing may be extended as follows, limited to a

maximum of two adjacent sprinklers on ranges or two adjacent ranges.

a) In buildings up to 9,1 m high, the maximum spacing of 3,7 m and area of coverage may be

increased to 10.7 m2 for those sprinklers that need to be moved in order to be at least 300 mm

from joists.

b) In buildings over 9,1 and up to 12.2 m high, the maximum spacing of 3,1 m may be increased to

3.4 m, with a maximum area of coverage of 10,2 m2, for those sprinklers that need to be moved

in order to be at least 300 mm from bar joists.

L 10.3 Sprinkler positioning relative to roof and ceilings

Sprinklers shall be located beneath the ceiling in accordance with Table T L.21

Table T L2 — Sprinkler distance from the underside of the ceiling

Sprinkler nominal K factor l.min-1.bar-1/2

Vertical distance from the underside of the ceiling to the sprinkler deflector

Not less than mm

Not more than mm

200, 240 and 280 –pendent ESFR

150 360

200 and 240 –upright ESFR

75 150

320 and 360 ESFR 150 460

CEA 4001-2013 – Sprinklers Systems – Inquiry on amendments 2016 (February) 57/67

L.10.4 Sprinkler orientation relative to the floor or pipework

ESFR sprinklers shall be installed with the deflector parallel to the ceiling or roof.

L 10.5 Clear space below sprinklers

Throughout the protected area the clear space below ESFR sprinklers (including any mezzanines)

shall be at least 1,0 m.

L 10.6 Positioning of ESFR sprinklers relative to draught or smoke curtains

Where draught or smoke curtains are required by the fire authorities within ESFR sprinkler arrays,

the sprinklers on either side of the draught or smoke curtain should be of equal distance (± 200 mm),

from the smoke curtain.

NOTE The distance of sprinklers from the draught or smoke curtain may vary along the length of the

draught or smoke curtain if there are changes in sprinkler spacing.

L 10.7 ESFR sprinkler protection adjacent to areas protected by standard sprinklers

Where ESFR sprinkler protection is adjacent to areas protected by standard sprinklers the following

measures shall be complied with:

a) Where ESFR and the adjacent non-ESFR sprinklers are at the same ceiling height or where ESFR

sprinklers are installed at a greater ceiling height than non-ESFR sprinklers, smoke curtains shall

be installed at the ceiling separating ESFR and non-ESFR sprinklers. The smoke curtains shall be

at least 600 mm deep and shall be located at the mi- point between the ESFR and non-ESFR

sprinklers. The smoke curtain shall be made of non-combustible material.

b) An aisle 1,2 m wide, free of all stored goods, shall be maintained between ESFR protected areas

and those protected by non-ESFR sprinklers. The centre of the aisle shall coincide with the

midpoint between the ESFR and non-ESFR sprinklers.

L 11 WATER SUPPLIES

L 11.1 Water supply selection

For each ESFR system there shall be:

a) At least two full capacity suction pumps, one of which shall be diesel driven. Each pump when

operating alone shall provide not less than Q100. for the design number of sprinklers, at sprinkler

head operating pressures of not less than that specified above plus any flow needed for pump

cooling. The pumps shall have compatible pressure flow characteristics so that when operating

in parallel neither pump shall be overloaded at any point within the specified range of output

flows; or

b) three half capacity suction pumps, two of which shall be diesel driven. Each pump shall have

compatible flow characteristics so that when operating in parallel it is not overloaded at any

CEA 4001-2013 – Sprinklers Systems – Inquiry on amendments 2016 (February) 58/67

point within the specified range of output flows. A flow of Q100 for the design number of

sprinklers, at sprinkler head operating pressure of not less than that specified above, plus any

flow needed for pump cooling, shall be provided by any combination of two pumps operating in

parallel.

NOTE Where the water supply is providing protection to storages containing high value goods or

their loss would be critical or where there are multiple buildings or storage additional pumping

capacity should be considered.

L 11.2 Duration

The water source for ESFR sprinklers shall have a system design capacity of not less than 60 minutes

of duration based on Q100.

PROPOSAL n° 12 – Introduction of a new annex: ANNEX Q - Control Mode

Specific Application Sprinklers (CMSA)

ANNEX Q

Control Mode Specific Application Sprinklers: CMSA

Q.1 Introduction

Control Mode Specific Application Sprinklers have K-factors equal to or greater than K160. These

sprinklers can be applied for special storage risk or for high hazard risks.

These sprinklers which operate in Control Mode for Specific Applications, known as CMSA –

Sprinklers, might also be known as large drop sprinklers. The term CMSA-Sprinkler or CMSA

Protection will be used within this Annex.

CMSA Sprinklers are mainly used to control fires within storage risks. It can be anticipated that with

proper design the ceiling will experience a 3 minute average temperature of less than 300 ° C, to

ensure that unprotected steel structures will not collapse. There is little room for error in the design

and installation of these sprinkler systems; the design principles and the operating characteristics are

significantly different from standard sprinkler protection. CMSA sprinklers might be unable to cope

with adverse design features and non-compliances, which might be common practice when installing

standard sprinkler protection. It is therefore essential that all the requirements of this annex are

complied with, without exception, when applying CMSA-Protection.

Protection of storage configurations other than those mentioned in this annex need to be proven by

full scale fire tests.

All of CEA 4001 applies, except those portions dealing with water demands and water supplies and

other subjects or modifications specifically addressed by this Annex.

This annex specifies requirements and recommendations for the design and installation of CMSA

sprinkler systems in buildings. The protection of aerosols, flammable and combustible liquids, laced

storage of rubber tyres and storage of candles are not included in this annex.

CEA 4001-2013 – Sprinklers Systems – Inquiry on amendments 2016 (February) 59/67

Definitions (to be transferred in definition chapter (chater 2)

Sprinkler, Control Mode Specific Application (CMSA sprinkler)

A sprinkler with a minimum K-Factor of 160, pendent or upright that is capable of providing large

water quantities to penetrate the fire plume with high momentum.

Q.2 General

Q.2.1 Sprinkler type and temperature rating

Both pendent and upright standard response CMSA sprinklers might be used.

Where ambient temperature allows (see 14.4), for wet systems sprinklers with a temperature rating

of 68 °C to 74 °C shall be used.

In dry systems sprinklers with a temperature rating of 141 °C shall be used.

Q.2.2 Water demand

Design CMSA sprinkler systems to provide the number of sprinklers at the minimum specified

pressure for the specific occupancy.

The location of the sprinklers to be supplied simultaneously shall be determined as defined in G.3.3.1

and G.3.3.2.

Q.2.3 Sprinkler location

Q.2.3.1 Sprinkler spacing

Limit the area of CMSA sprinklers to a minimum of 7,5 m² and a maximum of 9 m². Limit the distance

between range pipes and between sprinklers on range pipes to no more than 3,7 m nor less

than 2,4 m. For open joist construction, limit the maximum distance to 3,0 m.

Q.2.3.2 Range pipe sizes

The nominal diameter of range pipe (including riser nipples) shall not be less than 32 mm.

Where upright CMSA sprinklers are used, the nominal diameter of range pipe shall not be greater

than 50 mm, except starter pieces, which might be a nominal diameter of 65 mm.

Range pipes with a nominal diameter of 65 mm and above are acceptable when riser nipples are

provided to elevate the sprinkler deflectors above the centerline of the pipe according to

Table T.Q.1a

Table T.Q.2.3.2a — Minimum distance from upright CMSA sprinkler deflector to range pipe

Range pipe nominal diameter Minimum distance mm mm

65 330

80 380

100 460

CEA 4001-2013 – Sprinklers Systems – Inquiry on amendments 2016 (February) 60/67

Q.2.3.3 Minimum clear space below sprinklers

Maintain at least 1 m between ceiling sprinkler deflectors and the top of storage.

Q.2.3.4 Excessive clearance

As the design tables (T.Q.3 a to f) gives both maximum ceiling height and maximum storage height,

the clearance concern is already included in the design criteria.

Q.2.3.5 Distance of sprinklers below ceiling

Position sprinklers in accordance with Table T.Q.2.3.5a.

NOTE The preferred distance below ceiling is 180 mm

Table T.Q.2.3.5a. — Minimum and maximum distances of deflectors below ceiling for various

construction types

Construction type Minimum distance Maximum distance mm mm

Smooth ceiling (ceiling free from significant irregularities)

150 200

Joist, beam and girder, Concrete T 150 300

Ceiling with bays of a maximum of 25 m² in size (panel construction)

150 360

Q.2.3.6 Location of sprinklers in beam and girder, concrete T and panel construction

Under beam and girder construction, Concrete T and under panel construction, the branch lines

might run across the beams, but locate the sprinklers in the bays and not under the beams. Limit the

maximum distance above the bottom of beams to the values specified in Table T.Q.2.3.6a. At the

same time the maximum distance to ceiling based on Table T.Q.2.3.6a shall be applied. A panel

construction exists when beams or joists create bays smaller than 25 m².

Q.2.3.7 Obstructions to sprinkler distribution

Effective protection requires direct and prompt attack upon the burning fuel by the sprinkler

discharge. Sprinklers shall be located to ensure that building elements do not create obstructions to

the sprinkler distribution.

Q.2.3.8 Obstructions located at the ceiling

Where sprinkler deflectors are located above the bottom of beams, girders, ducts, fluorescent

lighting fixtures, or other obstructions located at the ceiling, position the sprinklers so the maximum

distance from the bottom of the obstruction to the deflectors does not exceed the value specified in

Table T.Q.2.3.6a. Use Figure T.Q.2.3.2a in conjunction with Table T.Q.2.3.6a in positioning sprinkler

deflectors.

CEA 4001-2013 – Sprinklers Systems – Inquiry on amendments 2016 (February) 61/67

Figure F.Q.2.3.6a — Position of deflector when located above bottom of beam or other obstruction

located at the ceiling

Table T.Q.2.3.6a — Position of deflector when located above bottom of beam, joist or other

obstruction

Distance (a) Maximum distance from underside of beam/joist (b)

Less than 0,3 m 0 mm

0,3 m to less than 0,5 m 40 mm

0,5 m to less than 0,6 m 80 mm

0,6 m to less than 0,8 m 140 mm

0,8 m to less than 0,9 m 200 mm

0,9 m to less than 1,1m 250 mm

1,1 m to less than 1,2 m 300 mm

1,2 m to less than 1,4 m 380 mm

1,4 m to less than 1,5 m 460 mm

1,5 m to less than 1,7 m 560 mm

1,7 m to less than 1,8 m 660 mm

1,8 m 780 mm

Q.2.3.9 Obstructions located below the sprinklers

Position sprinklers with respect to fluorescent lighting fixtures, ducts, and other obstructions located

entirely below the sprinklers so the minimum horizontal distance from the near side of the

obstruction to the centre of the sprinkler is not less than the value specified in Table T.Q.2.3.9a, as

illustrated in Figure F.Q.2.3.9a. If obstruction is combustible and sprinklers are positioned so that the

combustible obstruction is not protected, provide additional protection. For this purpose lesser K-

Factor sprinklers with same temperature rating are permitted.

a

b

KeyD Deflector b Distance from underside of beam/joista Distance from beam/joist

D

a

b

KeyD Deflector b Distance from underside of beam/joista Distance from beam/joist

D

CEA 4001-2013 – Sprinklers Systems – Inquiry on amendments 2016 (February) 62/67

Figure F.Q.2.3.9a — Position of sprinkler in relation to obstructions located entirely below the

sprinklers

Key: D Deflector a Distance to Side of Obstruction b Distance Deflector Above Bottom of Obstruction

Table F.Q.2.3.9a — Position of sprinklers in relation to obstructions located entirely below the

sprinklers

Distance deflector above bottom of obstruction

Minimum distance to side of obstruction

Less than 150 mm 0,5 m

150 mm to less than 300 mm 0,9 m

300 mm to less than 460 mm 1,2 m

460 mm to less than 610 mm 1,5 m

610 mm to less than 760 mm 1,7 m

760 mm to less than 910 mm 1,8 m

When the bottom of the obstruction is located 1 m or more below the sprinkler deflectors, position

sprinklers so that the obstruction is centred between adjacent sprinklers, as shown in

Figure F.Q.2.3.9b.

For obstruction less than 600 mm width, the extension to either side of the midpoint between

sprinklers might not exceed 300 mm. Maintain at least an 460 mm clearance between the top of

storage and the bottom of the obstruction. If the extension to either side of the midpoint between

sprinklers exceed 300 mm, install one or more lines of sprinklers below obstructions.

For obstruction 600 mm width and above, install one or more lines of sprinklers below obstructions.

CEA 4001-2013 – Sprinklers Systems – Inquiry on amendments 2016 (February) 63/67

Figure F.Q.2.3.9b — Position of sprinklers in relation to obstructions located 1000 mm or more below

deflectors

Q.2.3.10 Obstructions parallel to and directly below range pipe

In the special case of an obstruction running parallel to and directly below a range pipe, locate the

sprinkler at least 1 m above the top of the obstruction, as illustrated in Figure F.Q.2.3.10a. Limit the

obstruction to a width less than 300 mm and a maximum extension of 150 mm to either side of the

centreline of the range pipe.

Figure F.Q.2.3.10a — Position of sprinklers in relation to obstructions running parallel to and directly

below range pipes

Q.3 Design

The design of CMSA sprinkler systems is based on the K-Factor and nominal temperatures. Smoke

vents shall be on manual operation only. No interpolation between storage height and design criteria

is permitted as clearance is already considered in the design.

Design criteria shall be in accordance with Tables T.Q.3 a to f.

CEA 4001-2013 – Sprinklers Systems – Inquiry on amendments 2016 (February) 64/67

Table T.Q.3a — Protection of indoor storage ST1 of Idle Wood Pallets

Nominal K-Factor

Maximum storage height

Maximum ceiling height

Type of system

Number of design sprinklers by minimum pressure in bar

Duration Tempe-rature

1.5 bar

1.7 bar

2,1 bar

3.5 bar

m m min

160 6,1 10,7 Wet 15 90 68 °C

Dry 25 120 141 °C

240 6,1 10,7 Wet 15 90 68 °C

Dry 25 120 141°C

280 6,1 10,7 Wet 15 90 68 °C

280 6,1 12,2 Wet 15 90 141 °C

Table T.Q.3b — Protection of idle plastic pallets (ST1)

Nominal K-Factor

Maximum storage height

Maximum ceiling height

Type of system

Number of design sprinklers by minimum pressure in bar

Duration Tempe-rature

1.5 bar 3.5 bar m m min

160 3,0 7,6 Wet 25 120 68 °C

240 3,0 7,6 Wet 25 120 68 °C

Table T.Q.3c — Design criteria for free standing storage (ST 1) of HHS1, HHS2 and HHS3 excluding

plastics

Commodity Max Storage height

Max ceiling

K-factor

Type Number of Sprinklers

Pressure Duration

Tempe-rature

m m bar min

HHS1/ HHS2

7,6 9,1

280 Wet 15

1,1

90 68 °C 9,1 10,7 1,7

10,7 12,2 2,1

HHS1/ HHS2

9,1 15,2

160 Wet 15 1,7 90 68 °C

Dry 25 1,7 120 141 °C

240 Wet 15 1,0 90 68 °C

Dry 25 1,0 120 141 °C

HHS3*

160 Wet 20 3,5 120 68 °C

Dry 25 3,5 120 141 °C

240 Wet 20 1,5 120 68 °C

Dry 25 1,5 120 141 °C

* less than 5 % expanded and unexpanded plastic (PE,PS,PP) per storage unit.

CEA 4001-2013 – Sprinklers Systems – Inquiry on amendments 2016 (February) 65/67

Table T.Q.3d — Design criteria for free standing storage (ST 1) of HHS 3 and HHS 4.

Commodity Max Storage height

Max ceiling height

K-factor Type Number of Sprinklers

Pressure in bar

Duration Tempe-rature

m m min

HHS 3

6,1 12,2

160 Wet 15 3,5 90 68 °C

Dry 25 3,5 120 141 °C

240 Wet 15 1,5 90 68 °C

Dry 25 3,5 120 141 °C

HHS3

7,6 9,1

160 Wet 20 3,5 120 68 °C

Dry 30 3,5 120 141 °C

240 Wet 15 1,5 90 68 °C

Dry 25 1,5 120 141 °C

HHS3 excluding expanded plastic

6,1 9,1

280 Wet 15

1,1

90 68 °C

6,1 10,7 1,7

6,1 12,2 2,1

7,6 9,1 1,1

7,6 10,7 1,7

7,6 12,2 2,1

9,1 10,7 1,7

10,7 12,2 2,1

HHS4 Excluding rubber tyres

6,1 9,1 160 Wet 25 3,5 120 68 °C

240 Wet 25 1,5 120 68 °C

HHS4 Excluding rubber tyres

4,6 10,7 160 Wet 25 3,5 120 68 °C

240 Wet 25 1,5 120 68 °C

Table T.Q.3e — Design criteria for single, double, and multiple-row racks for palletized rack storage (ST4) of HHS1, HHS2 and HHS 3 commodities excluding plastics

Commodity Max Storage height

Max. ceiling height

K-factor Type Number of Sprinklers

Pressure Duration Tempe-rature

m m bar min

HHS1

6,1 12,2

160 Wet 15 1,7 90 68 °C

Dry 25 1,7 120 141 °C

240 Wet 15 1,0 90 68 °C

Dry 25 1,0 120 141 °C

7,6 13,7

160 Wet 20 2,8 120 68 °C

Dry 30 2,8 120 141 °C

240 Wet 20 1,4 120 68 °C

Dry 30 1,4 120 141 °C

10,7 12,2

160 Wet 36a 3,8 120 68 °C

Dry 36a 3,8 120 141 °C

240 Wet 36a 1,5 120 68 °C

Dry 36a 1,5 120 141 °C

HHS2 6,1 12,2 160

Wet 15 1,7 90 68 °C

Dry 25 1,7 120 141 °C

240 Wet 15 1,0 90 68 °C

CEA 4001-2013 – Sprinklers Systems – Inquiry on amendments 2016 (February) 66/67

Dry 25 1,0 120 141 °C

7,6 12,2

160 Wet 20 3,5 120 68 °C

Dry 25 3,5 120 141 °C

240 Wet 20 1,5 120 68 °C

Dry 25 1,5 120 141 °C

HHS2

7,6 9,1

280 Wet 15

1,1

90 68 °C 9,1 10,7 1,7

10,7 12,2 2,1

HHS3*

6,0 7,6

160 Wet 15 3,5 90 68 °C

Dry 25 3,5 120 141 °C

240 Wet 15 1,5 90 68 °C

Dry 25 1,5 120 141 °C

7,6 9,0 240 Wet 25 1,5 120 68 °C

Dry 40 1,5 120 141 °C a This design is based on the 6 most remote sprinklers on the most remote range pipes * less than 5% expanded and unexpanded plastic (PE,PS,PP) per storage unit.

Table T.Q.3f — Design criteria for single-, double-, and multiple-row racks for palletized rack (ST4) for HHS 3 and HHS 4

Commodity Max Storage height

Max ceiling height

K-factor Type Number of Sprinklers

Pressure Duration Tempe-rature

m m bar m

HHS3 6,1 7,6

160 Wet 15 3,5 90 68 °C

Dry 25 3,5 120 141 °C

240 Wet 15 1,5 90 68 °C

Dry 25 1,5 120 141 °C

HHS3 except exposed plastic

6,1 9,1

280 Wet 15

1,1

90 68 °C

6,1 10,7 1,7

6,1 12,2 2,1

7,6 9,1 1,1

7,6 10,7 1,7

7,6 12,2 2,1

9,1 10,7 1,7

10,7 12,2 2,1

HHS4 3,0 7,6

160 Wet 25 3,5 120 68 °C

Dry 40 3,5 120 141 °C

240 Wet 25 1,5 120 68 °C

Dry 40 1,5 120 141 °C

CEA 4001-2013 – Sprinklers Systems – Inquiry on amendments 2016 (February) 67/67

CNPP Service Éditions [email protected]

CEA 4001-2013 – Sprinklers Systems – Inquiry on amendments 2016 (February)

All comments and suggestions will be studied by GEI4 and adjustments will be done where appropriate.

Name: Company:

Proposal Comments and suggestions

PROPOSAL n° 1 – Modification of Chapter 1

PROPOSAL n° 2 – Modification of Chapter 8

PROPOSAL n° 3 – Modification of Chapter 9

PROPOSAL n° 4 – Modification of Chapter 10

PROPOSAL n° 5 – Modification of Chapter 11

PROPOSAL n° 6 – Modification of Chapter 13.6

PROPOSAL n° 7 – Modification of Chapter 15

PROPOSAL n° 8 – Modification of Chapter 18

PROPOSAL n° 9 – Modification of D3 and F7

PROPOSAL n° 10 – Modification of Annex K

PROPOSAL n° 11 – Modification of Annex L

PROPOSAL n° 12 – Introduction of a new

annex: ANNEX Q - Control Mode Specific

Application Sprinklers (CMSA)