2.0 ARTIFICIAL LIGHTING
2.1 Zone: Café & Gallery According to MS1525, the illuminance required for the cafeteria is 200lux.There are different types of lighting fixture used for respective purposes. The lighting level id divided accordingly to the targeted lighting level for each type of light bulb.
Total Floor Area (m²) 140m²Standard Illuminance Required (lux) 200Assumption of Reflection White Plaster Ceiling & Glass Curtain Wall
0.7,0.5Room Index (K) RI= L x W
(L+W ) x H
RI= 16.8 x14.9(16.8+14.9 ) x 1.6 RI=4.93
Utilization Factor UF= 83100 UF=0.83
Maintenance Factor 0.8
Lumen Method Calculation
1300 lm (Incandescent, yellow) 1760lm (Compact fluorescent, yellow)Brand: Philips Standard Extra Low Brand: Philips Linear Compact
Voltage A60 Fluorescent Lamp 4-pin base
N = E x A F x UF x MF
N = 100 x 140 1300 x 0.83 x 0.8
N= 16
N = E x A F x UF x MF
N = 100 x 140 1760 x 0.83 x 0.8
N= 12
Conclusion:Calculation shown 16 units of pendant light consist of Philips Standard Extra Low Voltage A60 (1300Lm) are required to light up 100 lux of cafeteria and 12 units of wall scone consists of Philips Linear Compact Fluorescent Lamp 4-pin base (1769Lm) are required to light up another 100 lux of gallery in the cafeteria to achieve 200 lux standard for dining area.
2.2 Workshop According to MS1525, the illuminance required for the workshop is 300lux.There
are different types of lighting fixture used for respective purposes. The lighting level id divided accordingly to the targeted lighting level for each type of light bulb.
Total Floor Area (m²) 51.6m²Standard Illuminance Required (lux) 300Assumption of Reflection White Plaster Ceiling & Brick Wall
0.7,0.3Room Index (K) RI= L x W
(L+W ) x H
RI= 16.8 x3.31(16.8+3.31 ) x1.6 RI=1.73
Utilization Factor UF= 71100 UF=0.71
Maintenance Factor 0.8
Lumen Method Calculation
3100 lm (Cool daylight) 800lm (Warm white)
Brand: Master TL5 High Efficiency Fluorescent Lamp
Brand: Philips LED Bulb 10-60W E27 6500K
N = E x A F x UF x MF
N = 250 x 51.6 3100 x 0.71 x 0.8
N= 7
N = E x A F x UF x MF
N = 50 x 51.6 800 x 0.71 x 0.8
N= 6
Conclusion:Calculation shown 7 units of task ambient light consist of Master TL5 High Efficiency Fluorescent Lamp (3100Lm) are required to light up 250 lux of workshop and 6 units of Philips LED Bulb 10-60W E27 6500K (800 Lm) are required to light up another 50 lux of workshop achieve 300 lux standard for workshop.
2.3 Zone: Art & Craft Market According to MS1525, the illuminance required for the cafeteria is 200lux.There are different types of lighting fixture used for respective purposes. The lighting level id divided accordingly to the targeted lighting level for each type of light bulb.
Total Floor Area (m²) 244m²Standard Illuminance Required (lux) 500Assumption of Reflection White Plaster Ceiling & Concrete
0.7 , 0.5Room Index (K) RI= L x W
(L+W ) x H
RI= 20.8 x17.3(20.8+17.3 ) x 2 RI=4.7
Utilization FactorUF= 82
100 UF=0.82
Maintenance Factor 0.8
Lumen Method Calculation
3100 lm (Cool daylight) 4200 lm (Cool daylight)Brand: Master TL5 High Efficiency Fluorescent Lamp
Brand: led single pin tube 8ft led tube 40w 85-265v F8AS led tube t8 2400mm
N = E x A F x UF x MF
N = 150 x 244 3100 x 0.82 x 0.8
N= 18
N = E x A F x UF x MF
N = 350 x 244 4200 x 0.82 x 0.8
N= 31
Conclusion:Calculation shown 18 units of task ambient light consist of Master TL5 High Efficiency Fluorescent Lamp (3100Lm) are required to light up 150 lux of art & craft market and 31 units of task ambient light consists of led single pin tube 8ft led tube 40w 85-265v F8AS led tube t8 2400mm (4200Lm) are required to light up another 350 lux of art & craft market to achieve 500 lux standard for supermarket
3.0 REVEBERATION TIME
3.1 Zone: Workshop
The table shows some typical reverberation time
Surface Area(m²) Absorption (1000Hz)
SA
Brick wall (unglazed) 1.0 0.04 0.044mm glass wall 0.3 0.03 0.009Glass window x4 4.5x4=18 0.04 0.72Concrete floor with timber finishes 51.6 0.06 3.096Plasterboard ceiling 51.6 0.05 2.6Seats (leather) x12 0.61 x 12=7.32 0.88 6.4416Timber table x3 1.6 x 3=4.8 0.10 0.48Doors (solid wood panels) 2.7 0.04 0.108People (adults) x24 24 0.46 11.04
Total Absorption 25
RT= 0.16v Total SA
RT= 0.16(206.4) 25
RT= 1.3s
Conclusion:The reverberation time for the workshop is 1.3s . It is a good and recommended range of sound level. The sound is within the space and does not take much time to reflect. Comfortable environment is produced for the user in the area as there are fewer echoes produced.
4.0 EXTERNAL NOISE SOUND PRESSURE LEVEL (SPL)
Total intensities = (1.995 x 10-4) + (1 x 10-4) = 2.995 x 10-4
Combined SPL = 10 log l1
1x 10-12
2.995 x 10-4
= 10 log 1x 10-12
= 10 x8.476
= 84.76dB
Conclusion:Total sound pressure received by Jalan Tun HS Lee is 77db from the traffic noise and the trading activities noise opposite it.
Opposite trading activities noise : 80dBL= 10 log l1
1x 10-12
80= 10 log l1
1x 10-12
Antilog8.0= 1 1x 10-12
l1= (1 x 108) x (1x 10-12) = 1 x 10-4
Traffic noise in Jalan Tun Hs.Lee : 83dBL= 10 log l1
1x 10-12
83= 10 log l1
1x 10-12
Antilog8.3= 1 1x 10-12
l1= (1.995 x 108) x (1x 10-12) = 1.995 x 10-4
5.0 Sound Reduction Index 5.1 Zone: Workshop
The table shows the sound pressure levels of common sound sources
From the table above, the average sound pressure produced by the workshop is around 85dB. The west side of the café , consists of the curtain windows (45dB) with the area of 18m² and the east side consists of the brick wall (48dB) with the area of 17m².
Transmission Loss for curtain windows Transmission Loss for brick wallSRI= 10 log 10 1 T
45= 10 log 10 1 T1T = 10 4.5
T= 1
3.16 X 104
T= 3.16 x 10-5
SRI= 10 log 10 1 T
48= 10 log 10 1 T1T = 10 4.8
T= 1
6.31 X 10-5
T= 1.58 x 10-5
Toverall= (18 x 3.16 x 10-5) + (17 x 1.58 x 10-5) 18 + 17
= 2.36 x 10-5
SRI = 10 log 10 1
2.36 x 10-5
=46Db
Total noise entering the workshop= 85dB – 46Db = 39dB