Professional Report 1 / V5.7.12.15251 / 13.12.2011 / 13:57:48 Vela Solaris AG, their distribution partners or SPF do not accept any liability for the correctness of the specifications and th Proyecto 8bd: Agua caliente. 200 litros y 2 T8 S Location of the system Budaörs Longitude: 18.967° Latitude: 47.45° Elevation: 142 m This report has been created by: Gustavo Martín Sicardo P.I. La Isla C/Río Viejo 39 41703 Dos Hermanas (Sevilla) Map section System overview (annual values) Total fuel and/or electrical energy consumption of thesystem [Etot] 2,128.2 kWh Total energy consumption [Quse] 2,056 kWh System performance (Quse / Etot) 0.97 Comfort demand Energy demand covered

Professional Report 1/ V5.7.12.15251 / 13.12.2011 / 13:57:48 Vela Solaris AG, their distribution partners or SPF do not accept any liability for the correctness

Embed Size (px)

Citation preview

Page 1: Professional Report 1/ V5.7.12.15251 / 13.12.2011 / 13:57:48 Vela Solaris AG, their distribution partners or SPF do not accept any liability for the correctness

Professional Report 

1 / V5.7.12.15251 / 13.12.2011 / 13:57:48

Vela Solaris AG, their distribution partners or SPF do not accept any liability for the correctness of the specifications and the results.

Proyecto 8bd: Agua caliente. 200 litros y 2 T8 S

Location of the system

 

Budaörs

Longitude: 18.967°

Latitude: 47.45°

Elevation: 142 m

This report has been created by:

 

Gustavo Martín Sicardo

P.I. La Isla

C/Río Viejo 39 41703 Dos Hermanas (Sevilla)

 

Map section

System overview (annual values)

Total fuel and/or electrical energy consumption of the system [Etot]

2,128.2 kWh

Total energy consumption [Quse] 2,056 kWh

System performance (Quse / Etot) 0.97

Comfort demand Energy demand covered

Page 2: Professional Report 1/ V5.7.12.15251 / 13.12.2011 / 13:57:48 Vela Solaris AG, their distribution partners or SPF do not accept any liability for the correctness

Professional Report 

2 / V5.7.12.15251 / 13.12.2011 / 13:57:48

Vela Solaris AG, their distribution partners or SPF do not accept any liability for the correctness of the specifications and the results.

Overview solar thermal energy (annual values)

Collector area 4.1 m²

Solar fraction total 63.3%

Total annual field yield 1,910.6 kWh

Collector field yield relating to gross area 461.5 kWh/m²/Year

Collector field yield relating to aperture area 505.5 kWh/m²/Year

Max. fuel savings 202.2 m³(Gas): [Natural gas H]

Max. energy savings 2,122.9 kWh

Max. reduction in CO2 emissions 491.6 kg

Solar fraction: fraction of solar energy to system [SFn]

Horizon line

Meteorological data-Overview

Average outdoor temperature 10.9 °C

Global irradiation, annual sum 1,206.9 kWh/m²

Diffuse irradiation, annual sum 595 kWh/m²

Page 3: Professional Report 1/ V5.7.12.15251 / 13.12.2011 / 13:57:48 Vela Solaris AG, their distribution partners or SPF do not accept any liability for the correctness

Professional Report 

3 / V5.7.12.15251 / 13.12.2011 / 13:57:48

Vela Solaris AG, their distribution partners or SPF do not accept any liability for the correctness of the specifications and the results.

Collector Termicol T8S

Data Source  

Number of collectors   2

Number of arrays   1

Total area m² 4.14

Total aperture area m² 3.78

Total absorber area m² 3.84

Tilt angle (hor.=0°, vert.=90°) ° 40

Orientation (E=+90°, S=0°, W=-90°) ° 0

Collector field yield [Qsol] kWh 1,910.6

Irradiation onto collector area [Esol] kWh 5,229.3

Collector efficiency [Qsol / Esol] % 36.5

Direct irradiation after IAM kWh 2,753.7

Diffuse irradiation after IAM kWh 2,188.1

Hot water demand Constant

Volume withdrawal/daily consumption l/d 150

Temperature setting °C 45

Energy demand [Qdem] kWh 2,172.1

Pump Solar loop pump Wilo-Star-ST 25/6

Circuit pressure drop bar 0.012

Flow rate l/h 151.2

Fuel and electrical energy consumption [Epar] kWh 58

Storage tank 3 200l potable water universal tank

Volume l 200

Height m 1.2

Material   Stainless steel

Insulation   Rigid PU foam

Thickness of insulation mm 80

Heat loss kWh 246.7

Connection losses kWh 137.7

Loop

Solar loop

Fluid mixture   Propilenglicol

Fluid concentration % 33.3

Fluid domains volume l 18.1

Pressure on top of the circuit bar 4

Component overview (annual values)

Page 4: Professional Report 1/ V5.7.12.15251 / 13.12.2011 / 13:57:48 Vela Solaris AG, their distribution partners or SPF do not accept any liability for the correctness

Professional Report 

4 / V5.7.12.15251 / 13.12.2011 / 13:57:48

Vela Solaris AG, their distribution partners or SPF do not accept any liability for the correctness of the specifications and the results.

Solar thermal energy to the system [Qsol] kWh

Heat generator energy to the system (solar thermal energy not included) [Qaux] kWh

Solar fraction: fraction of solar energy to system [SFn] %

Page 5: Professional Report 1/ V5.7.12.15251 / 13.12.2011 / 13:57:48 Vela Solaris AG, their distribution partners or SPF do not accept any liability for the correctness

Professional Report 

5 / V5.7.12.15251 / 13.12.2011 / 13:57:48

Vela Solaris AG, their distribution partners or SPF do not accept any liability for the correctness of the specifications and the results.

Total fuel and/or electrical energy consumption of the system [Etot] kWh

Year Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec

Solar thermal energy to the system [Qsol]

kWh 1911 69 97 152 199 223 223 235 220 190 173 80 49

Heat generator energy to the system (solar thermal energy not included) [Qaux]

kWh 1108 178 138 117 71 51 32 28 33 51 73 149 186

Heat generator fuel and electrical energy consumption [Eaux]

kWh 2070 302 244 215 145 114 76 66 79 105 148 262 314

Solar fraction: fraction of solar energy to system [SFn]

% 63.3 28 41.3 56.6 73.6 81.3 87.3 89.4 87 78.9 70.2 35 21

Total fuel and/or electrical energy consumption of the system [Etot]

kWh 2128 304 247 220 151 120 82 73 85 111 154 265 316

Irradiation onto collector area [Esol]

kWh 5229 205 269 431 523 603 604 659 619 524 423 219 153

Electrical energy consumption of pumps [Epar]

kWh 58 2 3 4 6 6 7 7 6 5 5 3 2

Heat loss to indoor room (including heat generator losses) [Qint]

kWh 1755 172 152 157 141 138 121 123 129 131 147 167 177

Heat loss to surroundings (without collector losses) [Qext]

kWh 227 10 14 19 24 24 24 25 23 22 21 11 8

Total energy consumption [Quse]

kWh 2056 192 178 196 184 180 162 158 153 148 160 165 182

Page 6: Professional Report 1/ V5.7.12.15251 / 13.12.2011 / 13:57:48 Vela Solaris AG, their distribution partners or SPF do not accept any liability for the correctness

Professional Report 

6 / V5.7.12.15251 / 13.12.2011 / 13:57:48

Vela Solaris AG, their distribution partners or SPF do not accept any liability for the correctness of the specifications and the results.

CollectorDaily maximum temperature [ °C]

Energy flow diagram