PRODUCT MANAGEMENT, REV. FEBRUARY 2018
PVS-100/120-TL The largest 1000Vdc string inverter in the solar industry
Andrea Genovesi, Gianluca Marri, Marco Trova, Arttu Rantala
March 5, 2018 Slide 2
Introduction
Value Proposition
Datasheet, available models & ordering codes
Efficiency, P-Q Capability, Temperature & Voltage Deratings
Improve Safety, Availability and Fault Segregation Capabilities of your PV System
Installation Guidelines
Advanced Communication Capabilities
«Web User Interface» & «ABB Installer» for Solar Inverters
Agenda
ABB – PVS-100/ PVS-120
March 5, 2018 Slide 3
Introduction
Value Proposition
Datasheet, available models & ordering codes
Efficiency, P-Q Capability, Temperature & Voltage Deratings
Improve Safety, Availability and Fault Segregation Capabilities of your PV System
Installation Guidelines
Advanced Communication Capabilities
«Web User Interface» & «ABB Installer» for Solar Inverters
Agenda
ABB – PVS-100/ PVS-120
March 5, 2018 Slide 4
New cost effective high power platform
ABB – PVS-100/ PVS-120
– Reduced CAPEX—high power density
– Reduced OPEX—fast installation and easy configuration, thanks to ABB AbilityTM Platform offering
• Smart communication capabilities, Wi-FI- fast configuration with any laptop/tablet/smart phone
• Integrated data logging and direct connection to ABB cloud
– High reliability—via extensive testing and advanced cooling methods
Application?
– For large commercial/ industrial rooftops and for ground mounted PV installations
Why?
Two box construction
ABB – PVS-100/ PVS-120
March 5, 2018 Slide 5
• High power density almost 1000W/kg
• Two box structure (Inverter box ~70 kg, wiring box ~55kg)
• Benefits:
• Two person can manage the mounting of boxes
• Cost saving on logistics
• Wiring box/ inverter box can be stocked separately
• Future local variants of wiring box possible
869 mm
1086 mm419 mm
Dimensions
Power module
Wiring Box
Complete portfolio
ABB – PVS-100/ PVS-120
March 5, 2018 Slide 6
30kW 100kW 1MW 5MW 20MW+
Complete portfolio benefits:
- With higher power inverters further cost effectiveness and savings in balance of system cost
- Use smaller inverter to fill in the corners of the plant
March 5, 2018 Slide 7
Introduction
Value Proposition
Datasheet, available models & ordering codes
Efficency, P-Q Capability, Temperature & Voltage Deratings
Improve Safety, Availability and Fault Segregation Capabilities of your PV System
Installation Guidelines
Advanced Communication Capabilities
«Web User Interface» & «ABB Installer» for Solar Inverters
Agenda
ABB – PVS-100/ PVS-120
VALUE PROPOSITION – Six in One
ABB – PVS-100/ PVS-120
March 5, 2018 Slide 8
• Power dense
• Installer friendly
• Versatile
• All-in-One, combiner-free design
• ABB Ability
• O&M friendly
Six in ONE
“O&M f riendly edit abile”
SIX in ONE
VALUE PROPOSITION – Six in One
ABB – PVS-100/ PVS-120
March 5, 2018 Slide 9
The larger capacity on the market for a 1000Vdc string inverter!
Less inverters are required to complete the optimal power block
Reduced logistic and installation costs
POWER DENSE
“O&M f riendly edit abile”
SIX in ONE
From 3 Boxes to
a single Box
AC
DENSE
ABB – PVS-100/ PVS-120
March 5, 2018 Slide 10
2,4 MW Power Block Lay-out
COMMON DATA
Installed DC Power [kWp] 2976
PV module Type
Poly
72cells
310Wp
Panels in series 20
Total number of strings 480
• N° 20 x PVS-120: 24 strings for each inverter
or
• N° 40 x 60kVA Inverter: 12 strings for each inverter (ref. TRIO-60.0-TM)
DENSE
ABB – PVS-100/ PVS-120
March 5, 2018 Slide 11
2,4 MW Power Block Lay-out
60kW Inverter solution PVS-120 inverter solution
MV station
60kW Inverter
PVS-120
• N° 40 inverter / 120MPPT• N° 20 AC recombiner box
• N° 20 inverter / 120MPPTAC Box
AC
AC AC
AC AC
AC AC
AC AC
AC AC
AC AC
AC AC
AC AC
AC
AC AC
AC
DENSE
ABB – PVS-100/ PVS-120
March 5, 2018 Slide 12
2,4 MW Power Block Lay-out
60kW Inverter solution PVS-120 inverter solution
MV station
60kW Inverter
PVS-120
• N° 40 inverter / 120MPPT • N° 20 AC recombiner box
• N° 20 inverter / 120MPPTAC Box
AC
AC AC
AC AC
AC AC
AC AC
AC AC
AC AC
AC AC
AC AC
AC
AC AC
AC
Saving:
• 50% less inverters
• Reducing cost for logistics and installation up to 50%
Saving:
• Avoid cost for AC recombiner box (up to 0,35 €cent/W saving)
• Avoid cost for logistics and installation
VALUE PROPOSITION – Six in One
ABB – PVS-100/ PVS-120
March 5, 2018 Slide 13
The easier to install for a product of its category!.
Same as installing a DC string combiner box. The PV module’s mounting structure can be used to install the inverters
Saving time and cost on logistics and site preparation (no heavy trucks and no concrete foundations required)
Operational costs reduced by quicker installation via Installation wizard, installer app and wireless access with any laptop and mobile device
INSTALLER FRIENDLY
“O&M f riendly edit abile”
SIX in ONE
INSTALLER FRIENDLY
ABB – PVS-100/ PVS-120
March 5, 2018 Slide 14March 5, 2018 Slide 14
Mounting Bracket: 3 pieces simple to assemble
INSTALLER FRIENDLY
ABB – PVS-100/ PVS-120
March 5, 2018 Slide 15March 5, 2018 Slide 15
Two Boxes (Wiring Box and Inverter Box): Easy to install on the bracket
Click
Toggle Clamps on both sides
ABB – PVS-100/ PVS-120
March 5, 2018 Slide 16
Fast installation, service friendly
– Fast opening of cover with key
– PV quick connectors for fast installations
– Wi-Fi for WebUI access
– Benefits
• Reduced time for cabling, fuse/ SPD check (AC, Comm wiring)
• Configuration via Wi-Fi without the need to open covers reduces risk of water leak inside the inverter
• Reduced time to repair (i.e. consumables fuses, SPD)
• Repair on site concept—fast and cost effective repair at site or close to the site
Installer and maintenance friendly mechanical design
Key
VALUE PROPOSITION – Six in One
ABB – PVS-100/ PVS-120
March 5, 2018 Slide 17
Multi-mppt (6) wide input voltage range platform
Larger capacity comes without compromising the inherent flexibility and versatility which is typical of smaller string inverters
Design-friendly inverter, can be easily adapted for any application in commercial rooftop and free fieldground mount installations
VERSATILE
Fixed Tilt Mounting
20°
Single-Axis Tracking
60°
East-West Mounting
“O&M f riendly edit abile”
SIX in ONE
VERSATILE
March 5, 2018 Slide 18
Free Field Ground Mount Installation
L
H
H
L
1
2
3
4
5
6
1
2
3
4
5
6
L
H
M
L
H
M
INVERTERDC/DC
INVERTERDC/DC3 X LANDSCAPE
2 X PORTRAIT
PVS-100/120
PVS-100/120
ABB – PVS-100/ PVS-120
VERSATILE
March 5, 2018 Slide 19
Commercial Rooftop Installation
1
2
3
4
5
6
INVERTERDC/DC
WE
E
W
PVS-100/120
24 strings (12 east, 12 west) / 4 each MPPT
20 modules in series, 350Wp
PDC = 168kWp
DC/AC Ratio = 140%
ABB – PVS-100/ PVS-120
VALUE PROPOSITION – Six in One
ABB – PVS-100/ PVS-120
March 5, 2018 Slide 20
Saving capex and opex costs!
Integrated string combiner box with DC disconnect and the AC wiring compartment
Wide space for wiring and ability to receive large Aluminum cable cross section
Saving the cost of separate DC combiner box and AC 1st
level combiners plus the associated installation costs!
Two combiner models available:
All-In-One / Combiner-Free Design
“O&M f riendly edit abile”
SIX in ONE
WB-SX2-PVS-100/120-TLWB-SX-PVS-100/120-TL
BASE solution
Save costs
FULL optional
solution
All-In-One / Combiner-Free Design
March 5, 2018 Slide 21
LV/MVTrafoAC
Typical design with two 60kWp string inverters: What we can do with the NEW PVS-100/120 ?
ABB – PVS-100/ PVS-120
All-In-One / Combiner-Free Design
March 5, 2018 Slide 22
PVS-100/120-TL-POWERMODULE-400
WB-SX2-PVS-100/120-TL
Up to 4x185mmq / 3x185mmq +PE
Up to 24 strings(2x6mmq)
LV/MVTrafo
Typical design with two 60kWp string inverters: What we can do with the NEW PVS-100/120 ?
Integrated string combiner box with DC disconnect and the AC wiring compartment
Saving the cost of separate DC combiner box and AC 1st
level combiners plus the associated installation costs!
ABB – PVS-100/ PVS-120
All-In-One / Combiner-Free Design
March 5, 2018 Slide 23
AC
What do we mean with
a real “ALL-IN-ONE” combiner?DC Side connections & protections
AC
AC Side connections & protections
Control & Monitoring
ABB – PVS-100/ PVS-120
VALUE PROPOSITION – Six in One
ABB – PVS-100/ PVS-120
March 5, 2018 Slide 24
ABB Ability
“O&M f riendly edit abile”
SIX in ONE
Improved user experience in large scale installations (Installer App for plant commissioning, installation wizard,…)
Self-consistent: advanced logging and control capabilities embedded into the inverter, thus improving reliability.
Reduced time on site: Life time free remote cloud services (FW upgrade, asset management, ….)
Proven technology: for better protecting customer’ s investment (TCP/IP, Modbus Sunspec certified , IEC 61850 information model,…)
Future-proof: meet current and future regulatory norms(like Rule 21- Step 2, EC61850, …)
ABB Ability
ABB – PVS-100/ PVS-120
March 5, 2018 Slide 25
Internet
Plant Portfolio
Manager
Plant ViewerPlant Viewer
for Mobile
Aurora Vision
TC
P /
IP
Monitoring
FW Upgrade
RS485
VSN800 Weather Station
Meter @ POI
Eth
ern
et
(Mo
db
us
TC
P S
un
sp
ec
Wi-Fi Wi-Fi
Ethernet(Modbus TCP Sunspec)
Installer App
Ethernet
Accounts/ Assets
management
Router / Gateway
Utility
Closed LoopControl
Operations & Maintenance
Protecting Customer Investment
Off-the-Shelf TCP/IP components
Standard technology: no need to educate people
IP protocol is the only one really suitable for IoT
Modbus TCP Sunspec for zero cost integration with third party devices
Compliant with modern regulatory norms (like Rule 21 – Step 2, IEC61850,….)
Multiple data streams and services can run at the same time - Remote monitoring - Plant control (incl. dynamic feed-in) - Remote FW update - Remote parameter’s setting
ABB Ability
ABB – PVS-100/ PVS-120
March 5, 2018 Slide 26
Internet
Plant Portfolio
Manager
Plant ViewerPlant Viewer
for Mobile
Aurora Vision CLOUD
Switch
Installer App for Plant
Commissioning
WLAN enabled device for accessingto integrated Web Server
Switch
Minimizing Customer Costs
Accessories directly connected to the inverter: (VSN800 Weather Station, meter, …)
Multi inverter commissioning via Installer App
Integrated Web Server and Wi-Fi channel: parameter’s setting via any WLAN-enabled device
Free of charge access to ABB cloud remote services including: - Remote access to inverter data - Remote FW update - Remote monitoring / Troubleshooting - User and asset management - Reporting and alarming through mobile app and
web portal
Eth
ern
et
Fib
er
RS485
VALUE PROPOSITION – Six in One
ABB – PVS-100/ PVS-120
March 5, 2018 Slide 27
Easy and Basic Maintenance during system operating life
Advanced cooling concept combined with a 2 box design help in preserving the lifetime and minimizing the O&M costs
− Heavy-duty cooling fans, easily removable during scheduled maintenance cycles
− Power module can be easily replaced without removing the wiring box.
O&M friendly
“O&M f riendly edit abile”
SIX in ONE
O&M friendly
March 5, 2018 Slide 28
Routine maintenance only includes inspection, cleaning and checks that can be performed without any advanced technical skills
External inspections
Wiring box inspections (PV connectors, AC tightening cable check)
ABB – PVS-100/ PVS-120
O&M friendly
March 5, 2018 Slide 29
Smart access to all wiring box protection devices
SPD type II
SPD type II
Fuses Boards
O&M friendly
ABB – PVS-100/ PVS-120
O&M friendly
ABB – PVS-100/ PVS-120
March 5, 2018 Slide 30
Advanced cooling concept
2 independent and separated forced air circuits
• External circuit for power converter:- Cold air from the sides of the unit- Hot air exhaust from the rear
• Internal air recirculation circuit: - cooling of electromechanical components
(inductors, contactors, capacitors, …)- Internal air temperature equalization
N°2 monitored and replaceable internal fans recirculating air inside wiring box & power converter
N°2 monitored and replaceable IP54 fans on both sides
O&M friendly
ABB – PVS-100/ PVS-120
March 5, 2018 Slide 31
Advanced cooling concept
2 independent external air circuits:
• Booster on the left side
• Inverter on the right side
Benefits:
• Increased lifetime as temperature of components is kept under control
• Enables vertical and horizontal mounting
• Fans speed modulation, to reduce self consumption and preserve fan lifespan
• Wiring box temperature controlled (minimize thermal stress on fuse and contactor)
O&M friendly
March 5, 2018 Slide 32
Power module can be easily replaced without removing the wiring box.
ABB – PVS-100/ PVS-120
March 5, 2018 Slide 33
Introduction
Value Proposition
Datasheet, available models & ordering codes
Efficency, P-Q Capability, Temperature & Voltage Deratings
Improve Safety, Availability and Fault Segregation Capabilities of your PV System
Installation Guidelines
Advanced Communication Capabilities
«Web User Interface» & «ABB Installer» for Solar Inverters
Agenda
ABB – PVS-100/ PVS-120
Data-sheet
ABB – PVS-100/ PVS-120
March 5, 2018 Slide 34
Inverter parameters
• 6 Independent MPP / 24 strings
• One string/MPPT supports 30 A fusing to allow 5th string per MPP channel
• PVS-100 (100kW, 400Vac, 3ph 50/60Hz):
• VMPPT = 480 – 850 Vdc
• PVS-120 (120kW, 480Vac, 3ph 50/60Hz):
• VMPPT = 570 – 850 Vdc
User Interface
• Standard LEDs
• Integrated Web User Interface for managing inverter
• IOS and Android installation app for multiple inverter commissioning
• Standard level access to Aurora Vision remote monitoring service
Communication
• 2 x Ethernet;
• Wi-Fi Channel
• 1 x RS485;
• Modbus RTU/TCP (Sunspec compliant);
• Integrated datalogger and direct connection to Aurora Vision remote portal
Construction, weight, volume
• IP66
• Forced Air cooling
• Two box construction
• Mounting vertically/horizontally
• High Power density ~1000W/kg
IP
Efficiency (PVS-120)
• Max. Efficency: 98,9%
• EU Efficency: 98,6%
• CEC Efficency: 98,6%
In/Out protections
• Type 2 Surge arrester (both DC and AC)
• Insulation monitoring control per IEC 62109-2
ABB – PVS-100/ PVS-120
March 5, 2018 Slide 35
Components
1. Power module
2. Wiring box
3. Mounting bracket
It is necessary to order 3 components above.
As optionally
4. AC multicore plate for 1+PE cables(as default single core plate for 4+PE cables)
PVS-100/PVS-120 components
“Unipack” codes with package of above components to reduce custom duties are
available as well
1
4
2
3
1
2
3
4
ABB – PVS-100/ PVS-120
March 5, 2018 Slide 36
Available options—All integrated
SX version—Cost cut SX2 version—Full version
1. PVS-120-TL-POWER MODULE or PVS-100-TL-POWER MODULE
2. WB-SX-PVS-100-TL or WB-SX-PVS-120-TL
3. MOUNTING BRACKET; PVS-100/120
1. PVS-120-TL-POWER MODULE or PVS-100-TL-POWER MODULE
2. WB-SX2-PVS-100-TL or WB-SX2-PVS-120-TL
3. MOUNTING BRACKET; PVS-100/120
DC input AC output
Wiring boxDC—quick connectors
Input monitoring
Fuses (15A as standard)
DC disconnect switch
DC SPD Type II
AC disconnectswitch
AC SPD Type II
WB-SX-PVS-100-TL / WB-SX-PVS-120-TL
24 chPer
MPPT (6ch)Positive pole only
–
WB-SX2-PVS-100-TL / WB-SX2-PVS-120-TL
24 chPer individual string (24ch)
Both poles
1
2
3
1
2
3
ABB – PVS-100/ PVS-120
March 5, 2018 * At least one PVS installation and lifting kit required per plantSlide 37
Available PN
PN Model designation Class
3P809900000A PVS-100-TL-POWER MODULE PVS
3P209900000A PVS-120-TL-POWER MODULE PVS
3P47000WB06A WB-SX2-PVS-100-TL/24 INPUTS PVS
3P47000WB07A WB-SX-PVS-100-TL/24 INPUTS PVS
3P47000WB08A WB-SX2-PVS-120-TL/24 INPUTS PVS
3P47000WB09A WB-SX-PVS-120-TL/24 INPUTS PVS
3P510000000A MOUNTING BRACKET Accessory
3P51000J000A AC OUTPUT PANEL M63 FOR WIRING BOX Accessory
3P899901000A PVS-100-TL;SX2;FULL Unipack
3P899902000A PVS-100-TL;SX;FULL Unipack
3P909901000A PVS-120-TL;SX2;FULL Unipack
3P909902000A PVS-120-TL;SX;FULL Unipack
3P51000A000A PVS INSTALLATION AND LIFTING KIT* Accessory
March 5, 2018
1 Single core plate as default 4xM40 + M252 Multi core plate as accessory M63+ M25Slide 38
Cabling—easy access
ABB – PVS-100/ PVS-120
– 48 PV quick connectors enables fast and secure connection
– 2 DC switches
DC connection
– Single core1 & multicore2 AC cable panels 185mm2 with M10 lug
– Supports long distances (Direct from field to LV switchboard at MVC)
– Cu or Al both supported
– 4W or 3W, no neutral required to operate inverter, savings in cable costs
AC connection
Comm
– 2 x Ethernet (RJ45) + 1 RS-485
DC
AC
COMM
SX2 wiring box details– DC Side, electrical drawings
ABB – PVS-100/ PVS-120
March 5, 2018 Slide 39
DC Switch 1DC Switch 2MPPT 1-2-3 (12 PV Quick connectors)MPPT 4-5-6 (12 PV Quick connectors)
SX2 wiring box details
ABB – PVS-100/ PVS-120
March 5, 2018 Slide 40
Fuses Boards
SPD Type 2 (DC Side)
Power Supply Board
Optional Pre-Charge Boardor PID Board
SX2 wiring box details – DC Side, electrical drawings
ABB – PVS-100/ PVS-120
March 5, 2018 Slide 41
Positive fuse board Negative fuse board DC SPD type 2
SX2 wiring box details – AC Side, electrical drawings
ABB – PVS-100/ PVS-120
March 5, 2018 Slide 42
AC Connections terminals (M10 lug)
AC Switch
AC Contactor
(DSP controller)
AC Box cover
AC SPD type 2Monitoring & Control Board
2 x Ethernet (RJ45)
1 x RS485
Remote OFF
SX2 wiring box details – AC Side, connections
ABB – PVS-100/ PVS-120
March 5, 2018 Slide 43
• Supports long distances (Direct from field to LV switchboard at MVC)
• Cu or Al both supported
• 4W or 3W, no neutral required to operate inverter, savings in cable costs
• Multi core (M63 + 1xM25 Cable lugs) or Single core (4xM40 + 1xM25 Cable lugs) AC cable panels: 185mm2 with M10 lug.
PE Connection
Control & Monitoring connectionsclamping range: min. ÷ max. cable diameter(*)
M63 25mm 55mm
M40 15mm 28mm
M25 10mm 17mm
M63 M40
(*) Preliminary data
March 5, 2018 Slide 44
Introduction
Value Proposition
Datasheet, available models & ordering codes
Efficency, P-Q Capability, Temperature & Voltage Deratings
Improve Safety, Availability and Fault Segregation Capabilities of your PV System
Installation Guidelines
Advanced Communication Capabilities
«Web User Interface» & «ABB Installer» for Solar Inverters
Agenda
ABB – PVS-100/ PVS-120
Vin ηMAX
ηEuro
ηCEC
570 98,46 98,22 98,21
720 98,87 98,64 98,58
800 98,67 98,46 98,46
10 20 30 40 50 60 70 80 90 100
P/Pn [%]
Efficiency PVS-120
94
95
96
97
98
99
570Vdc
720Vdc
800Vdc
94
95
94.5
95.5
96.5
96
97
98
97.5
99
98.5
η[%
]
PVS-120: Efficiency vs Input Voltage
DC Input Voltage
η[%
]
98.00
98.20
98.40
98.60
98.80
99.00
550 600 650 700 750 800 850
Eta_Max
Eta_CEC
Eta_Euro
ABB – PVS-100/ PVS-120
March 5, 2018 Slide 45
System design optimization:
Max efficiency available in the middle of the input operating voltage range
String length can be optimized, while fully exploiting the best inverter performance under typical operating conditions
Performance optimization:
System PR is kept unchanged or furtherincreased as compared to single stageinverters;
Weighted efficiency >98.2% in the input range 570 - 800 Vdc!
Best Performance in the Typical DC Operating Range
ABB – PVS-100/ PVS-120
March 5, 2018 Slide 46
Inverter architecture that maximize system PRTcell @ 5°C
22 panels in series / 60cells / 1000W/m2
Tcell @ 75°C
Higher PR
• Similar performance of single stage inverters in the same DC operating range thanks to the bypass function
• No clipping losses at high temperatures, when Vmpp falls below the minimum operating limit of single stage inverters!
DC Power [kW]
DC Voltage [V]
144
120
96
72
48
24
0 100 200 300 400 500 600 700 800 900 1000
DC Power [kW]
0 100 200
Single stage
Double stage
Single stage inverter:
power loss due to
narrow input range
DC Voltage [V]
800 900 1000300 400 500 700600
144
120
96
72
48
24
Input Voltage [V]
ȠT ≈ ȠINVȠT = ȠDC/DC x ȠINV
Bypass modeDouble stage mode
DC/DC Inverter DC/DC Inverter
710V 725V
ABB – PVS-100/ PVS-120
March 5, 2018 Slide 47
Output Power derating vs Input Voltage
Secured Energy Yield
1) MPPT range not depending on AC voltage:
MPPT voltage window not affected by AC Voltage fluctuation.
String design can be optimized to match peak inverter efficiency without affecting energy harvest at low irradiance and/or high temperature
2) Smooth high DC voltage derating
DC power is reduced linearly from 100% at 850Vdc to zero at 1000Vdc
No risk of shut-down or MPP locking at near-zero power under cold conditions
Conditions / Ratings PVS-100 PVS-120
Rated AC Voltage [Vacr] 400 V 480 V
Full Power MPPT range 480 … 850 V 570 … 850 V
Maximum MPPT current 6 x 36 A
Maximum AC current 145 A
Output Power vs Input Voltage
200 400 600 800 1000
480 570 850360
20
40
60
80
100
120
78
P [kW]
Vin [V]
PVS-120
PVS-100
PVS-100/ 120
(*) Preliminary data
ABB – PVS-100/ PVS-120
March 5, 2018 Slide 48
Output Power derating vs Ambient Temperature
Secured Energy Yield:
Inverter suitable for application in harsh environmental conditions.
Performance unaffected by mounting position, either vertical or horizontal
Conditions / Ratings PVS-100 PVS-120
Rated AC Voltage [Vacr] 400 V 480 V
Full Power MPPT range 480 … 850 V 570 … 850 V
Maximum AC current 145 A
(*) Preliminary data
Output Power vs Ambient Temperature
20 30 40 50 6020
40
60
80
100
120
P [kW]
Tamb [°C]
PVS-120
PVS-100
March 5, 2018 Slide 49
Introduction
Value Proposition
Datasheet, available models & ordering codes
Efficency, P-Q Capability, Temperature & Voltage Deratings
Improve Safety, Availability and Fault Segregation Capabilities of your PV System
Installation Guidelines
Advanced Communication Capabilities
«Web User Interface» & «ABB Installer» for Solar Inverters
Agenda
ABB – PVS-100/ PVS-120
Improve Safety, Availability and Fault Segregation Capabilities of your PV system
ABB – PVS-100/ PVS-120
March 5, 2018 Slide 50
IEC 62109-2 requirements for Non-isolated inverter connected to Ungrounded Array:
1 - Riso (Isolation resistance):Preventive measure (before grid connection) of the insulation resistance to the earth of the PV generator. • Grid connection is only possible if Riso > 33 KOhm.
2 - GFI (ground fault interface):Real-time monitoring of earth leakage current (AC + DC component) equivalent to an advanced RCD. Two protections are needed:
a. Disconnect within 0,3s if the continuous residual current exceeds maximum 10 mA per kVA of rated continuous output power
b. Disconnect from the mains within the time specified if a sudden increase in the RMS residual current is detected exceeding the values listed in the table.
Continuous residual current max. Value
PVS-100 1A
PVS-120 1,2A
Residual current sudden change
Max. Time to inverter disconnection from the mains
30mA 0,3s
60mA 0,15s
150mA 0,04s
March 5, 2018 Slide 51
Introduction
Value Proposition
Datasheet, available models & ordering codes
Efficency, P-Q Capability, Temperature & Voltage Deratings
Improve Safety, Availability and Fault Segregation Capabilities of your PV System
Installation Guidelines
Advanced Communication Capabilities
«Web User Interface» & «ABB Installer» for Solar Inverters
Agenda
ABB – PVS-100/ PVS-120
Distribution Systems
ABB – PVS-100/ PVS-120
March 5, 2018 Slide 52
TN-S: MV/LV transformer with star configuration; N and PE are separate conductors conductor
\
L1
L2
L3
N NPE
L1
L2
L3
PE
MV/LV transformer
Both 3 or 4 Wiring connection are permitted.Inverter automatically recognize the system.
ABB – PVS-100/ PVS-120
March 5, 2018 Slide 53
\
L1
L2
L3
PEN
L1
L2
L3
PEN
MV/LV transformer
TN-C: MV/LV transformer with star configuration; N and PE are the same conductor
Distribution Systems
TN-C-S: is also permitted
TT: MV/LV transformer star configuration; PE (building connection point). Not compatible with this size of inverters (use of high sensitive RCD)
IT: MV/LV transformer, no earthingnot permitted AC system! (corner ground is not supported either)
Both 3 or 4 Wiring connection are permitted.Inverter automatically recognize the system.
Horizontal and vertical mounting
ABB – PVS-100/ PVS-120
March 5, 2018 Slide 54
• Same bracket can be used in vertical and horizontal positions
• Wiring box is installed at first and then power module
• Power module can be easily replaced without removing the wiring box
Mounting bracket
Minimum & recommended clearances – wall mounting
ABB – PVS-100/ PVS-120
March 5, 2018 Slide 55
(*): Increase according to minimum cable’s bending radius
PRELIMINARY
Minimum & recommended clearances – wall mounting
ABB – PVS-100/ PVS-120
March 5, 2018 Slide 56
(*): Increase according to minimum cable’s bending radius
PRELIMINARY
ABB – PVS-100/ PVS-120
March 5, 2018 Slide 57
(*): Recommended clearance to prevent flooding and cable damage during grass trimming. This maybe reduced (> 15cm) if grass trimming and flooding do not represent a risk;Increase according to minimum cable’s bending radius, if needed
Minimum & recommended clearances – free field mounting
PRELIMINARY
ABB – PVS-100/ PVS-120
March 5, 2018 Slide 58
Minimum & recommended clearances: horizontal and back to back mounting
(*): Clearance may be reduced if an air deflector or decoupling plate is installed
Horizontal mounting Back to Back mounting
PRELIMINARY
ABB – PVS-100/ PVS-120
March 5, 2018 PRELIMINARYSlide 59
Maximum tilt angles
A minimum of 5° is recommended for water drainage
March 5, 2018 Slide 60
Introduction
Value Proposition
Datasheet, available models & ordering codes
Efficency, P-Q Capability, Temperature & Voltage Deratings
Improve Safety, Availability and Fault Segregation Capabilities of your PV System
Installation Guidelines
Advanced Communication Capabilities
«Web User Interface» & «ABB Installer» for Solar Inverters
Agenda
ABB – PVS-100/ PVS-120
Overview – New Communication Features!
ABB – PVS-100/ PVS-120
March 5, 2018 Slide 61
• Wireless and Ethernet field network - Fast, low cost, industry standard IP communications.
• Ethernet daisy chain support - Reduces installation time enabling advanced closed loop control applications.
• Inverter Installer App – Simplifies the inverter installation process and reduces installation time/costs.
• Integrated Web User Interface – with installation wizard and advanced parameter settings and diagnostic
100/120kVA 1000VDC string inverter
ABB – PVS-100/ PVS-120
March 5, 2018 Slide 62
Communication Interfaces
Integrated Wi-Fi (IEEE 802.11 b/g/n @ 2.4 GHz)• 2 radio channels integrated• Touch-free inverter commissioning • Wirelessly accessing to the inverter WUI• Station mode setting for transferring data to cloud
2 x Ethernet ports • 10/100 Mbit/s (RJ45 plug )• Configured for daisy chain layout connection
(Linear or ring shape topology)• Suitable also for radial layout connection • Remote monitoring and FW update without the
need of installing any additional device
1 x RS485 port• Master and slave setting• Recommended for direct connection of accessories
(i.e. meteo station, etc…)
Communication interfaces
Ethernet field bus (Daisy Chain, ring shaped or radial layout)
ABB – PVS-100/ PVS-120
March 5, 2018 Slide 63
Standard Ethernet cable:• Cross-section: min. 2 x 2 x 0.22 mm2
or min. 2 x 2 x AWG 24• Cable type: 100BaseTx, CAT5 with shielding
S-UTP, F-UTP or higher• UV-resistant if used outdoor• Plug type: RJ45
Three different topologies:1. Daisy chain over Ethernet cable
(max 100m inverter to inverter distance)2. Ring shaped layout for improving service
continuity also in case of inverter failure3. Radial layout
(max 100m inverter to switch distance)
< 1
00
m
Ethernet switch
Internet
Plant Portfolio
Manager
Plant ViewerPlant Viewer
for Mobile
Aurora Vision
1
2
3
Communication over Ethernet
March 5, 2018 Slide 64
Introduction
Value Proposition
Datasheet, available models & ordering codes
Efficency, P-Q Capability, Temperature & Voltage Deratings
Improve Safety, Availability and Fault Segregation Capabilities of your PV System
Installation Guidelines
Advanced Communication Capabilities
«Web User Interface» & «ABB Installer» for Solar Inverters
Agenda
ABB – PVS-100/ PVS-120
Commissioning and inverter setting
ABB – PVS-100/ PVS-120
March 5, 2018 Slide 65
− Automatic setting up of the communication after the turning on of all the inverters connected by Ethernet cable (with or without DHCP server)
− Installer App for commissioning the entire plant (up to 50 inverters over the same LAN)
− Single inverter settings via Wi-Fi / AME by any WLAN enabled device
− Network info also available within every single inverter’s Web User Interface
− Accessing to a single inverter’s Web User Interface is also possible from the Ethernet switch(multicast DNS service needed on the switch)
Ethernet switch
Internet
Plant Portfolio
Manager
Plant ViewerPlant Viewer
for Mobile
Aurora VisionCommissioning over Ethernet
‘Installer App’ to reduce plant installation costs
March 5, 2018 Slide 66
Touch-free Inverter Commissioning
Via Wi-Fi Access Point connection
App compatible with any Android and IOS smartphone and mobile device
Multiple Inverter Installation
Commissioning of the entire plant/cluster (up to 50 inverters over the same LAN)
Optionally scan and track shipped inverters
Smart app manages passcodes to minimize password issues
Fast setup of single or multiple inverters: grid standard, input mode…
that’s it you’re on line!
Simple and Quick Plant Installation Solution
ABB – PVS-100/ PVS-120
Try it!
Web User Interface – easy configuration and maintenance operation
March 5, 2018 Slide 67
WUI – Easy Analysis and Configuration
ABB – PVS-100/ PVS-120
Commissioning Wizard and FW Upgrade
Simple 4-step guided commissioning process
Local/Remote FW upgrade
Supporting advanced diagnostic
Dashboard – one-page Inverter information
Status summary with all internal key operatingparameters
Detailed analysis for critical operatingparameters (i.e. deratings…)
Event log with reporting and filtering
Supporting advanced inverter setting
DC input and AC protection parameters
Grid Support and Control Functions
ABB three phase string inverter—PVS-100/ PVS-120
More information will follow, stay tunedMarch 5, 2018 Slide 73
Safety & general certificates availability
– CE & RCM mark
– RED Directive
– IEC62116, IEC61727(anti-islanding)
– IEC60068-2-1/2/14/30/78 (Environmental)
– IEC/EN61683 (Efficiency)
As of Feb-18
Grid codes availability
– CEI0-16, CEI0-21 (Italy)
– Turkey HV / Turkey LV
– Jordan_IRR-DCC-MV
– AS4777.2 (Australia)
– VDE-AR-N 4105
– VFR_2014 (France) + UTE C15-712-1
– UK59-3
– Coming soon! BDEW, EN50438, Thailand PEA/MEA, South Korea-60Hz Brazil-60Hz, Dubai