Upload
others
View
1
Download
0
Embed Size (px)
Citation preview
1
0118 918 6470 · www.caice.co.uk · [email protected] · Follow @caiceUK
Product and Technical Data Brochure
Acoustic Louvre
2
0118 918 6470 · www.caice.co.uk · [email protected] · Follow @caiceUK
Caice Acoustic Louvres
For more than 20 years Caice have been
combining our acoustic expertise with
precision UK based manufacturing to deliver
high performing product solutions for our
clients.
The Acoustic Louvre product with single bank and
chevron variants is an integral part of our
environmental noise control portfolio; designed to
meet the most stringent noise criteria requirements.
All Acoustic Louvre products are selected to meet a
client’s specific needs and are suitable for a range of
applications including: fresh air intakes for ventilation
systems, mechanical equipment screens and noise
barriers.
Rest assured that high performance doesn’t mean a
compromise on aesthetics. Our Continuous Line
product design means that concealed joins and
corners provide a seamless look to a screen or
enclosure. Combining this with a range of material,
paint and treatment options, the finished product can
be as individual as a specific project requires. Recent installations at Premier Inn, Tenby
and Project Dragonfly, Kent
3
0118 918 6470 · www.caice.co.uk · [email protected] · Follow @caiceUK
Features & Benefits
Technical Sales Team
Providing specification, acoustic design and pricing
Design Team
Producing product design and product templates
CAD Team
Producing fully 3D Inventor drawings
Project Managers
Interfacing with clients and delivering projects on time and to a budget.
Above Acoustic Louvre Screen designed,
manufactured and installed by Caice at Bank
of America’s offices in Central London.
4
0118 918 6470 · www.caice.co.uk · [email protected] · Follow @caiceUK
Caice Acoustic enclosure with integral door.
Premier Inn, Tenby
5
0118 918 6470 · www.caice.co.uk · [email protected] · Follow @caiceUK
Single Bank Acoustic Louvre, Standard Performance Profile, 150mm Deep
Performance
Technical Data For SS150 Acoustic Louvre
Typical
weight 29kg/
m2
Aerodynamic coefficient at 1200 high is 18.38k
Acoustic Louvres should not be selected in the shaded area above.
Acoustic Data dB in each Octave Band Centre Frequency (Hz)
63 125 250 500 1k 2k 4k 8k
Sound reduction index 4 4 6 8 11 11 11 10
Weighted sound reduction index (Rw) 11
Static insertion loss 3 4 6 10 12 13 13 14
Regenerated sound power level at 1m/s face velocity 48 41 34 35 30 22 13 12
Regenerated sound power level at 2m/s face velocity 66 58 51 51 50 47 41 28
0 1 2 3
Face Velocity (m/s)
0
20
40
60
100
80
Pre
ssure
Loss (P
a)
1.5 2.5 0.5
600 High 1200 High
Free Area and Height Range
Height
(mm)
Airway
Free Area
(%)
Airways
(71mm)
Face
Free
Area
(%)
425-624 17-11 1 42-29
625-824 23-17 2 45-34
825-1024 26-21 3 46-37
1025-1224 28-23 4 47-39
1225-1424 29-25 5 47-41
1425-1624 30-26 6 48-42
1625-1824 30-27 7 48-43
1825-2024 31-28 8 48-43
2025-2224 31-29 9 48-44
2225-2424 32-29 49-45 10
1800 High
6
0118 918 6470 · www.caice.co.uk · [email protected] · Follow @caiceUK
Single Bank Acoustic Louvre, Higher Performance Profile, 150mm Deep
Performance
Technical Data For SH150 Acoustic Louvre
Typical
weight 35kg/
m2
Aerodynamic coefficient at 1200 high is 18.38k
Acoustic Louvres should not be selected in the shaded area above.
Acoustic Data dB in each Octave Band Centre Frequency (Hz)
63 125 250 500 1k 2k 4k 8k
Sound reduction index 5 5 7 9 13 13 13 12
Weighted sound reduction index (Rw) 13
Static insertion loss 4 5 7 12 16 16 16 18
Regenerated sound power level at 1m/s face velocity 53 47 38 36 33 29 18 12
Regenerated sound power level at 2m/s face velocity 70 65 58 53 51 51 45 35
0 1 2 3
Face Velocity (m/s)
0
20
40
60
100
80
Pre
ssure
Loss (P
a)
0.5 1.5 2.5
600 High 1200 High 1800 High
Free Area and Height Range
Height
(mm)
Airway
Free Area
(%)
Airways
(43mm)
Face
Free
Area
(%)
505-664 17-13 2 24-18
665-824 19-15 3 27-22
825-984 21-17 4 29-24
985-1144 22-19 5 30-26
1145-1304 22-20 6 31-28
1305-1464 23-20 7 32-29
1465-1624 23-21 8 33-30
1625-1784 23-21 9 33-30
1785-1944 24-22 10 34-31
1945-2104 24-22 34-31 11
2105-2264 24-22 34-32 12
2265-2424 24-23 34-32 13
7
0118 918 6470 · www.caice.co.uk · [email protected] · Follow @caiceUK
Technical Data For SS300 Acoustic Louvre Single Bank Acoustic Louvre, Standard Performance Profile, 300mm Deep
Typical
weight
43kg/m2
Performance
Acoustic Data dB in each Octave Band Centre Frequency (Hz)
63 125 250 500 1k 2k 4k 8k
Sound reduction index 6 6 9 13 21 20 16 13
Weighted sound reduction index (Rw) 17
Static insertion loss 5 6 9 14 20 20 20 20
Regenerated sound power level at 1m/s face velocity 48 41 34 30 25 20 13 12
Regenerated sound power level at 2m/s face velocity 66 58 51 47 45 43 39 28
0 1 2 3
Face Velocity (m/s)
0
20
40
60
100
80
Pre
ssure
Loss (P
a)
0.5 2.5 1.5
600 High 1200 High 1800 High
Free Area and Height Range
Height
(mm)
Airway
Free Area
(%)
Face
Free
Area
(%)
Airways
(71mm)
625-824 23-17 32-24 2
825-1024 26-21 36-29 3
1025-1224 28-23 39-33 4
1225-1424 29-25 41-35 5
1425-1624 30-26 42-37 6
1625-1824 30-27 43-38 7
1825-2024 31-28 44-40 8
2025-2224 31-29 44-40 9
2225-2424 32-29 45-41 10
2425-2624 32-30 45-42 11
Acoustic Louvres should not be selected in the shaded area above.
Aerodynamic coefficient at 1200 high is 18.38k
8
0118 918 6470 · www.caice.co.uk · [email protected] · Follow @caiceUK
Aerodynamic coefficient at 1200 high is 18.38k
Single Bank Acoustic Louvre, Higher Performance Profile, 300mm Deep
Performance
Technical Data For SH300 Acoustic Louvre
Typical
weight
53kg/m2
Acoustic Louvres should not be selected in the shaded area above.
Acoustic Data dB in each Octave Band Centre Frequency (Hz)
63 125 250 500 1k 2k 4k 8k
Sound reduction index 7 7 10 17 29 30 27 21
Weighted sound reduction index (Rw) 21
Static insertion loss 6 7 10 18 31 28 26 25
Regenerated sound power level at 1m/s face velocity 50 44 39 34 30 26 17 12
Regenerated sound power level at 2m/s face velocity 70 60 55 52 49 49 43 35
0 1 2 3
Face Velocity (m/s)
0
20
40
60
100
80
Pre
ssure
Loss (P
a)
0.5 1.5 2.5
600 High 1200 High 1800 High
Free Area and Height Range
Height
(mm)
Airway
Free Area
(%)
Airways
(43mm)
Face
Free
Area
(%)
665-824 13-10 2 18-15
825-984 15-13 3 22-18
985-1144 17-15 4 24-21
1145-1304 19-16 5 26-23
1305-1464 20-17 6 28-25
1465-1624 20-18 7 29-26
1625-1784 21-19 8 30-27
1785-1944 21-20 9 30-28
1945-2104 22-20 10 31-29
2105-2264 22-21 31-29 11
2265-2424 22-21 32-30 12
2425-2584 23-21 32-30 13
9
0118 918 6470 · www.caice.co.uk · [email protected] · Follow @caiceUK
Chevron Acoustic Louvre, Standard Performance Profile, 300mm Deep
Performance
Technical Data For CS300 Acoustic Louvre
Typical
weight 57kg/
m2
Aerodynamic coefficient at 1200 high is 18.38k
Acoustic Louvres should not be selected in the shaded area above.
Acoustic Data dB in each Octave Band Centre Frequency (Hz)
63 125 250 500 1k 2k 4k 8k
Sound reduction index 5 6 8 12 19 19 18 17
Weighted sound reduction index (Rw) 16
Static insertion loss 4 5 8 12 20 20 20 21
Regenerated sound power level at 1m/s face velocity 53 46 43 40 41 36 24 12
Regenerated sound power level at 2m/s face velocity 74 66 60 57 57 56 50 40
0 1 2 3
Face Velocity (m/s)
0
20
40
60
100
80
Pre
ssure
Loss (P
a)
0.5 1.5 2.5
600 High 1200 High 1800 High
Free Area and Height Range
Height
(mm)
Airway
Free Area
(%)
Airways
(71mm)
Face
Free
Area
(%)
425-624 17-11 1 42-29
625-824 23-17 2 45-34
825-1024 26-21 3 46-37
1025-1224 28-23 4 47-39
1225-1424 29-25 5 47-41
1425-1624 30-26 6 48-42
1625-1824 30-27 7 48-43
1825-2024 31-28 8 48-43
2025-2224 31-29 9 48-44
2225-2424 32-29 49-45 10
10
0118 918 6470 · www.caice.co.uk · [email protected] · Follow @caiceUK
Chevron Acoustic Louvre, Standard Performance Profile, 600mm Deep
Performance
Technical Data For CS600 Acoustic Louvre
Typical
weight
85kg/m2
Aerodynamic coefficient at 1200 high is 18.38k
Acoustic Louvres should not be selected in the shaded area above.
Acoustic Data dB in each Octave Band Centre Frequency (Hz)
63 125 250 500 1k 2k 4k 8k
Sound reduction index 7 8 13 23 37 33 29 29
Weighted sound reduction index (Rw) 25
Static insertion loss 6 8 13 23 38 32 32 32
Regenerated sound power level at 1m/s face velocity 54 46 37 32 28 24 15 12
Regenerated sound power level at 2m/s face velocity 71 66 57 50 47 46 41 30
0 1 2 3
Face Velocity (m/s)
0
20
40
60
100
80
Pre
ssure
Loss (P
a)
0.5 1.5 2.5
600 High 1200 High 1800 High
Free Area and Height Range
Height
(mm)
Airway
Free Area
(%)
Face
Free
Area
(%)
Airways
(71mm)
625-824 23-17 32-24 2
825-1024 26-21 36-29 3
1025-1224 28-23 39-33 4
1225-1424 29-25 41-35 5
1425-1624 30-26 42-37 6
1625-1824 30-27 43-38 7
1825-2024 31-28 44-40 8
2025-2224 31-29 44-40 9
2225-2424 32-29 45-41 10
2425-2624 32-30 45-42 11
11
0118 918 6470 · www.caice.co.uk · [email protected] · Follow @caiceUK
Acoustic Louvre Technical Data
Construction Code Description
Product
AL Acoustic Louvre
Format
M Modular
R Rectangular Single Piece Unit
I Internal Corner On Its Own
E External Plain Corner On Its Own
C Chamfered Mitre External Corner On Its Own
S Single Door On Its Own
D Double Door On Its Own
P Penthouse With Roof
T Triangular
O Circular
F Faceted
R Curved Radius
N Non Standard Shape
Suffix N Blades In Normal Orientation
Suffix U Blades In Upside Down Orientation
SS150 Single Bank Standard Profile 150 Deep
SH150 Single Bank High Performance Profile (Reduced Airway) 150 Deep
SS300 Single Bank Standard Profile 300 Deep
SH300 Single Bank High Performance Profile (Reduced Airway) 300 Deep
CS300 Chevron Standard Profile 300 Deep
CS600 Chevron Standard Profile 600 Deep
Type
U Unfinished Base Material
P Polyester Powder All Visible Surfaces
N Non-Standard Polyester Powder Paint All Visible Surfaces
A Anodised (only on aluminium)
S Syntha Pulvin (only on aluminium)
Finish
G Galvanised Steel
A Aluminium
Material
N No Mesh
B Bird Mesh
I Insect Mesh
S Single Skin Blanking
D Double-Skin Acoustic Blanking
T Celotex Thermal Blanking
Mesh
Options
Integral Doors (where n= number off)
Sn Integral Single Leaf Door
Dn Integral Double Leaf Door
Flashing
I Internal Picture Frame
E External Picture Frame
C Extended Drip Cill
Notching (where n= number off)
Rn Rear Notch
Fn Face Notch
Penetration (where n= number off)
Pn Rectangular Penetration
Removable (where n= number off)
Wn Removable Sections For Withdrawal
Fixings
B Brackets For Fixing To Structure **
Other
X Other Options
** Assembly fixings are always supplied by us as standard.
AL / M N / SS 300 / G U / I / W 2
Telephone
0118 918 6470
Facsimile
0118 918 6480
www.caice.co.uk
Caice Acoustic Air Movement Ltd.
Riverside House
3 Winnersh Fields
Gazelle Close
Winnersh
Wokingham
RG41 5QS
Registered office and
head office
Company Registration Number
2790667
VAT Registration Number
GB614683632