RIA452 Process display with digital output, monitoring and pump control functions RIA452 Input with two-wire loop power supply and intrinsic safety option Pump control function Digital output with integration Specs at a glance: • Display: 7-digit/14 segment multicolored • Approval: ATEX II (1) GD [EEx ia] IIC optional • Standard Dimensions: 96 × 96 mm (3.78" × 3.78") • Relays: 4 or 8 (optional) • Function: Linearization, pump control function, integration • Output: Optional 1 × analog output Application The RIA452 process display interprets and displays process signals with high resolution and accuracy. It can also be used to automate control tasks via limit values or analogue and digital outputs. Function Up to eight presettable relays monitor the measured value for any infringement (undershooting/ overstepping) of the preset limit values. Further operation modes for the relays are sensor or device errors, batch and pump control functions (e.g. alternating pump control). The scalable analog output offers wide options to transfer the input signal: zoom function, linearization, offset, inverting and signal conversion (conversion in-/output). The optional impuls output offers the possibility to create integrated process values. Simple setting up using a serial interface and PC programme or manually using the configurating dial on the front of the unit. Application example EX EX Complete product information: www.e-direct.endress.com/ria452 € 366.– 11–35 pcs. Endress+Hauser GmbH Lehnergasse 4 1230 Wien Austria Phone 01 880 56 0 Fax 01 880 56 335 E-Mail [email protected]

Process display with digital output, monitoring and pump ... · L to DIN 43710, GOST Digital input 4 ×, max. 10 Hz Accuracy 0.1 % of the measurement range end value Output Transmitter

  • Upload
    others

  • View
    1

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Process display with digital output, monitoring and pump ... · L to DIN 43710, GOST Digital input 4 ×, max. 10 Hz Accuracy 0.1 % of the measurement range end value Output Transmitter

RIA452

Process display with digital output, monitoring and pump control functions

RIA452

• Input with two-wire loop power supply and intrinsic safety option

• Pump control function• Digital output with integration

Specs at a glance:

• Display: 7-digit/14 segment multicolored

• Approval: ATEX II (1) GD [EEx ia] IIC optional

• Standard Dimensions: 96 × 96 mm (3.78" × 3.78")

• Relays: 4 or 8 (optional)

• Function: Linearization, pump control function, integration

• Output: Optional 1 × analog output

Application The RIA452 process display interprets and displays process signals with high resolution and accuracy. It can also be used to automate control tasks via limit values or analogue and digital outputs.

Function Up to eight presettable relays monitor the measured value for any infringement (undershooting/overstepping) of the preset limit values. Further operation modes for the relays are sensor or device errors, batch and pump control functions (e.g. alternating pump control). The scalable analog output offers wide options to transfer the input signal: zoom function, linearization, offset, inverting and signal conversion (conversion in-/output). The optional impuls output offers the possibility to create integrated process values. Simple setting up using a serial interface and PC programme or manually using the configurating dial on the front of the unit.

Application example

EX EX

Complete product information:www.e-direct.endress.com/ria452

€ 366.–11–35 pcs.

Endress+Hauser GmbHLehnergasse 41230 WienAustria

Phone 01 880 56 0Fax 01 880 56 335E-Mail [email protected]

Page 2: Process display with digital output, monitoring and pump ... · L to DIN 43710, GOST Digital input 4 ×, max. 10 Hz Accuracy 0.1 % of the measurement range end value Output Transmitter

RIA452

Technical data

InputAnalog input 1 × 0/4 to 20 mA (impedance 5 Ω)Universal input 0/4 to 20 mA, 0 to 5 mA, ±40 mV, ±150 mV,

±600 mV, ±2,5 V, 0 to 10 V, 0 to 5 V, ±10 V, 30 to 3000 Ω resistance thermometer Pt100/500/1000, Cu50/100, Pt50 thermocouple types J, K, T, N, B, S, R to IEC 584; D, C to ASTM E998; L to DIN 43710, GOST

Digital input 4 ×, max. 10 HzAccuracy 0.1 % of the measurement range end value

OutputTransmitter supply 24 V DC, 250 mA, on option intrinsically safe

1 × 24 V DC, 22 mA in additionAnalog output 1 × 0/4 to 20 mA, 0 to 10 V DCOutput impedance Max. ≤600 ΩDigital output 1 × open collector passive 12.5 kHz 4 ×

relays (changeover contact), 250 V AC/ 30 V DC, 3-A; expandable to 8 relays (option)

Linearity ≤0.1 % of the measurement range end value

Operating conditionsAmbient temperature –20 to +60 °C (–4 to 140 °F)Storage temperature –30 to +70 °C (–22 to 158 °F)Climatic class To IEC 60 654-1 class B2 bedewing is

forbiddenEMC Interference immunity to IEC 61326

(industrial environment) and NAMUR NE 21;interference emissions to IEC 61326 Class A

Ingress protection Front IP 65, Terminals IP 20

Power supplySupply voltage 90 to 250 V AC, 50/60 Hz

20 to 36 V DC/ 20 to 28 V AC, 50/60 Hz

Mechanical constructionElectrical connection Plug on screw terminals, size 1.5 m² solid,

1.0 mm² multi with ferruleMaterials used Housing front: ABS plastic, electro-plated

Housing casing: PC10GF plastic

User interfaceDisplay 7 digit 14-segment LC-display in white

(10 mm / 0.39"); engineering unit with 9 × 77 Dot Matrix display; 42-parts bargraph in yellow with over- and under range in red;limit value markings in yellow; status display

Range of display –99999 to +99999Operation via Jog-Shuttle or using RS232 and PC

software ReadWin® 2000

FunctionsFeatures Linearization with 32 points, elapsed hour

indicator, alternating pump control, tendency analysis, batch-function, integration, min/max value storage

ApprovalsEx approval ATEX II (1) GD [EEx ia] IIC

Dimensions in mm (inches)

RIA452

96 (3.78)

m₃/min

96 (3

.78)

130.5 (5.14)143.4 (5.71)

16.3 (0.64)

Installation according to instruction manual.

Page 3: Process display with digital output, monitoring and pump ... · L to DIN 43710, GOST Digital input 4 ×, max. 10 Hz Accuracy 0.1 % of the measurement range end value Output Transmitter

RIA452

Electrical connection

54

55

56

44

45

46

51

52

53

41

42

43

L/L+

N/L

-

NC

CDI RS232

Relay 4

Relay 3

Relay 2

Relay 1

Relay 8

Relay 7

Relay 6

Relay 5

Relay 1-8 250 V AC/30 V DC

Analog output0 to 20 mA, 0 to 10 V DC

Digital output, passive open collector max. 24 V, 200 mA

90 to 250 V AC50/60 Hz

Clam

ps 1

2 an

d 82

are

link

ed in

tern

ally

Loop

pow

ersu

pply

Max

. 22

mA

Inpu

t0

to 2

0 m

A

Inpu

t0

to 2

0 m

A

20 to 36 V DC

20 to 36 V AC50/60 Hz

+-

+-

+-

+-

+

+

-

- 1234

-+ + -

Loop power supply24 V, <= 250 mA

154

155

156

144

145

146

151

152

153

141

142

143

81821112

91 92 31 32 33 34 96

97

197

297

397

Current input

Digi

tal i

nput

s to

DIN

192

40

Current input

Universal input

0 to 20 mA

Voltage input

Voltage input

+/–1 V

+/– 30 V

Thermocouples

RTD:4-wire

3-wire

191715131112

Page 4: Process display with digital output, monitoring and pump ... · L to DIN 43710, GOST Digital input 4 ×, max. 10 Hz Accuracy 0.1 % of the measurement range end value Output Transmitter

RIA452

More products to complete your measuring point …

Price table

Power supply

Code Voltage1 90 to 250 V AC2 20 to 36 V DC / 20 to 28 V AC

Process indicator RIA452 Order no. Price/pcs. in €Approval Measuring Signal Output 1 to 3 4 to 10 11 to 35Non-hazardous area

0/4 to 20mA 4 limit values RIA452-A 11A11A 416.– 387.– 366.–4 limit values, analog RIA452-A 12A11A 452.– 420.– 398.–8 limit values, pulse and integration RIA452-A 13A11A 539.– 502.– 475.–8 limit values, analog, pulse and integration RIA452-A 14A11A 575.– 535.– 506.–4 limit values, pulse and integration RIA452-A 15A11A 496.– 461.– 436.–

Universal U,I,R,RTD,TC

4 limit values RIA452-A 21A11A 474.– 441.– 417.–4 limit values, analog RIA452-A 22A11A 510.– 474.– 449.–8 limit values, pulse and integration RIA452-A 23A11A 597.– 556.– 526.–8 limit values, analog, pulse and integration RIA452-A 24A11A 633.– 589.– 557.–4 limit values, pulse and integration RIA452-A 25A11A 554.– 515.– 487.–

ATEX II(1)GD(EEx ia)IIC

0/4 to 20mA 4 limit values RIA452-B 11A11A 457.– 425.– 402.–4 limit values, analog RIA452-B 12A11A 493.– 458.– 434.–8 limit values, pulse and integration RIA452-B 13A11A 580.– 540.– 511.–8 limit values, analog, pulse and integration RIA452-B 14A11A 616.– 573.– 542.–4 limit values, pulse and integration RIA452-B 15A11A 537.– 499.– 472.–

Accessories Order no. Price/pcs. in €Configuration kit, USB TXU10-AA 101.72Field housing RIA452 (200 × 160 × 228 mm) 51009957 148.80Prices are applicable for Austria until 30/06/2020, in Euro per unit, net excluding value added tax (VAT), cost of packing and dispatch. Endress+Hauser retains the right to change or modify pricing at any time. The terms of sales and delivery of Endress+Hauser are applicable. Current prices and delivery times can be verified prior to ordering on www.e-direct.endress.com.

Complete product information:www.e-direct.endress.com/ria452