Upload
vitinrj
View
5
Download
0
Embed Size (px)
DESCRIPTION
Proactive Network Monitoring PQ
Citation preview
7/21/2019 Proactive Network Monitoring PQ 4p
http://slidepdf.com/reader/full/proactive-network-monitoring-pq-4p 1/9
Marko Pikkarainen29.3.2012
Power quality and proactive network monitoring
Marko PikkarainenTampere University of Technology
The Department of Electrical Energy Engineering
SET-1520 New Applications in Electrical Energy Engineering27.3.2012
Marko Pikkarainen29.3.2012
Content of the presentation
• 1. Power quality in general (EMC)
• Consequences of poor Power Quality
• Economical impacts
• Standard (EN 50160)
Power quality quantities
• 2. Some recent changes in the field of power quality
• Flicker
• 3. Proactive power quality monitoring
Power quality in general
• Power Quality: The characteristics of the electricity at a given point on
in electrical system, evaluated against a set of reference technical
parameters (IEC 61000-4-30)
• Electromagnetic compatibility (EMC): The ability of an electrical
equipment or system to function satisfactorily in its electromagneticenvironment without introducing intolerable electromagnetic
disturbances to anything in that environment
3
Marko Pikkarainen29.3.2012
Consequences of poor PQ
•Poor power quality can have different effects. The range reaches from
disturbing effect on human beings (flicker) up to consequences on
operation of equipment.
•There are long term and momentary effects. Harmonics and unbalance
cause increased losses in the utilities equipment and reduce life time ofcomponents.
•Momentary effects are a sudden malfunction or damage of a device.
They commonly appear with the quality parameters such as: voltageinterruption, voltage dips and transient overvoltage.
•The most commonly reported symptoms of power quality phenomena
are light flickering, circuit breakers t ripping and computers locking up orrestarting. Also some damages are reported due to voltage quality
problems
4
Marko Pikkarainen29.3.2012
7/21/2019 Proactive Network Monitoring PQ 4p
http://slidepdf.com/reader/full/proactive-network-monitoring-pq-4p 2/9
Economical impacts of power quality
The importance of power quality problems can be reviewed by its
economic impacts.
•In the USA economical losses due to interruptions are estimated to be
between 104-164*109
dollar annually.•Other power quality problems are estimated to have 15-24*109 dollareconomic loss impact annually.
• Gross domestic product of USA was 14 526*109 dollar (2010)
5
Marko Pikkarainen29.3.2012
Regulation and standardisation
There are several regulations, standards and laws that regulate the
distribution utilities actions and design and use of elect rical equipments
• national laws and regulations
• directives and standards
• general guidelines by field of business
EMC standard
• IEC 61000 series
6
Marko Pikkarainen29.3.2012
61000- 1- x Gener al
61000-2-x Environment •Description of the environment•Classification of the environment
•Compatibility levels
61000-3-x Limits •Emission limits
•Immunity limits
61000-4-x Testing and measurement
techniques
•Measurement techniques
•Testing techniques
61000-5-x Installation and mitigation
guidelines
•Installation guidelines
•Mitigation methods and devices
61000-6-x Gener ic s tandards
61000-9-x Miscellaneous All the rest
EN 50160
• Standard EN 50160 defines, describes and specifies the main
characteristics of the voltage at a network user's supply terminals in
public low, medium and high voltage AC electricity distribution networks
under normal operating conditions. (EN50160)
Some problems :
• Covers only normal operation and even for that case only during 95% of time
obligatory
• For some power quality parameters only indicative values are given
• EN 50160 is not EMC standard, compliance with EN 50160 standard doesn‘tguarantee undisturbed operation of all devices
• Describes maximum values or variations of the voltage characteristics under
normal operating conditions which can be expected by the customer at any
place of the network
7
Marko Pikkarainen29.3.2012
Voltage fluctuations and flicker
• Flicker (PST, PLT) is the subjective impression of luminance variations of lightning as a result of voltage
fluctuations.
• Flicker is more a physiological than a physical value.
• The flicker effect depends on: the amplitude of the relative voltage fluctuation and the repetition rate of the
appearance of the voltage fluctuation. With the same frequency of the voltage fluctuation the flicker effect isdirectly proportionally to the amplitude of the voltage variation.
• Flicker causes normally no damage of devices or an interference of their function.
• PST and PLT occurs without dimension (pu).
• The borderline was established laboratory tests with individuals. (for incandescent lamps)
8
Marko Pikkarainen29.3.2012
t
u(t)
regular sinusoidal
voltagefluctuation
U
U
regular rectangular
voltagefluctuation
arbitraryrectangular
voltagefluctuation
U2
U
0.1
1
10
0.1
0.001
1
0.01
10
0.1
100
1
1000
10
10000 changes/min
100 Hz flickerfrequency
P =1st
[%]U
U
7/21/2019 Proactive Network Monitoring PQ 4p
http://slidepdf.com/reader/full/proactive-network-monitoring-pq-4p 3/9
Voltage fluctuations and flicker
Very common reason for customer complaints (it is easy to observe)
Origins for flicker:
• starting currents of induction motors, fluctuating torque of load (stone crusher), weldingmachines, electro heat devices with thermostat, Electric arc furnaces
Remedial measures:
• Increase short circuit capacity of the network
• Starting current limitation
• Smoothing of load torque
• Avoidance of sharp load changes
• Automatic welding machines, 3-phase instead of 1-phase welding machine
• For EAFs: use of DC EAF, power-factor correction, use of dynamic compensation units
Limits in EN 50160
Under normal operating conditions, in any period of one week the long term flicker severity
caused by voltage fluctuation should be Plt 1 for 95 % of the time.
9
Marko Pikkarainen29.3.2012
Voltage fluctuations and flicker
Under normal operating conditions excluding the periods with interruptions, supply
voltage variations should not exceed ± 10 % of the nominal voltage Un.
In cases of electricity supplies in networks not interconnected with transmission
systems or for special remote network users, voltage variations should not exceed+10 % / - 15 % of Un. Network users should be informed of the conditions.
Under normal operating conditions:
• during each period of one week 95 % of the 10 min mean r.m.s. values of the
supply voltage shall be within the range of Un ± 10 %; and
• all 10 min mean r.m.s. values of the supply voltage shall be within the range of
Un + 10 % / - 15 %.
10
Marko Pikkarainen29.3.2012
Voltage unbalance
In EN 50160 voltage unbalance is defined as a ratio of the negat ive
sequence voltage and positive sequence voltage
Consequences of unbalance:
• Increase of the losses in the grid components• Increase losses and vibration moments in electrical machines
• Could increase non-characteristical harmonic currents of rectifier andinverter
Sources for unbalance:
• Non three phase loads (most of the loads in LV level / customer end)
• Railways
• Electric Arc Furnaces
11
Marko Pikkarainen29.3.2012
1
2
U
U k
u
1
2
I
I I u
Voltage unbalance
Remedial measures
•Increase short circuit capacity of the network (network strengthening)
•Distributesingle phase loads evenly between phases, use three phase loads
•Disconnection via converter sets of a three-phase motor and a single-phase
alternator •Use inverters to change three phase system to single or two phase system
•Balancing using Steinmetz principle
Lim its in EN 50160
•during each period of one week, 95 % of the 10 min mean r.m.s. values of the
negative phase sequence component (fundamental) of the supply voltage shall be
within the range 0 % to 2 % of the positive phase sequence component
(fundamental). In some areas with partly single phase or two phase connected
network users' installations, unbalances up to about 3 % at three-phase supplyterminals occur.
12
Marko Pikkarainen29.3.2012
7/21/2019 Proactive Network Monitoring PQ 4p
http://slidepdf.com/reader/full/proactive-network-monitoring-pq-4p 4/9
Harmonics
When the waveform of voltage or current is not pure sine wave those can be
modelled using Fourier transform method (in real life it rarely is)
• Fundamental: Signal component that occurs with the line frequency
• Harmonics: Signal components which frequencies are multiple integer of the fundamental
• Interharmonics: Signal components which frequencies are not mult iple integer of the
fundamental (no limits in EN 50160)
• Subharmonics: Signal components which frequencies are below the mains frequency (nolimits in EN 50160)
• The classical harmonics-theory deals with frequencies from 0 Hz to about 2500 Hz (50 thharmonic, Bashir tell youmore about higher frequencies)
Consequences of harmonics:
• increase thermal and mechanical stress of the components and devices, increases grid
losses, might produce inf luence for r ipple-control devices, might produce f licker byinterharmonics.
13
Marko Pikkarainen29.3.2012
Harmonics
Sources for harmonics:
• Power electronics
• Transformers, iron core inductor (in normal mode
effect negligible)
• Electric arc furnaces
Remedial measures:
• Power factor correction (passive, active)
• Central filter systems (also distributed)
• Changing of the mains circuits switching state, in
order to avoid resonances
• Increase short circuit capacity
Lim its in EN 50160
• during each period of one week, 95 % of the 10 min
mean r.m.s. values of each individual harmonic
voltage shall be less than or equal to the value given
in table
14
Marko Pikkarainen29.3.2012
Odd harmonics Even harmonics
N ot mu l ti pl es o f 3 Mu lt ipl es o f 3
Orderh
Relative
amplitude uh
O rd e r h R e l at ive
amplitude uh
Order h Relat ive
amplitude uh
5 6,00 % 3 5,00 % 2 2,00 %
7 5,00 % 9 1,50 % 4 1,00 %
11 3,50 % 15 0,50 % 6..24 0,50 %
13 3,00 % 21 0,50 %
17 2,00 %
19 1,50 %
23 1,50 %
25 1,50 %
NOTE: Novalu esaregivenfor harmonicsof orderhigherthan25,astheya re
usuallysmall,but largelyunpredictabledueto resonanceeffects.
Frequency
The mains frequency is global quantity in interconnected networks. The
change in frequency is result of change between power production and
consumption. In interconnected networks with controlled reserves, the
frequency shows only low fluctuation.
• Frequency rise (more production than consumption)
• Frequency falls (more consumption than production)
Consequencesof abnormal frequency:
• clocks that run synchronously to the line frequency may face some problems
• Produce mechanical stresses in turbines
• Affects to uncontrolled synchronous- and asynchronous drives
15
Marko Pikkarainen29.3.2012
Frequency
Remedial measures
• Use of reserve power plants
• Load shedding
Lim its in EN 50160
Interconnected 49,5 Hz - 50,5 Hz during 99,5% of a year
networks 47 Hz - 52 Hz dur ing 100 % of the t ime
Islanded 49 Hz - 51 Hz during 95% of a week
networks 42,5 Hz –57,5 Hz dur ing 100 % of the time
16
Marko Pikkarainen29.3.2012
7/21/2019 Proactive Network Monitoring PQ 4p
http://slidepdf.com/reader/full/proactive-network-monitoring-pq-4p 5/9
Voltage dips and swells short voltage
interuptions
Temporary reduction of the r.m.s. voltage at a point in the electrical
supply system when the voltage falls below 90 % of the reference
voltage
• voltage dip duration (from 10 ms up to including 1 min)
• voltage dip residual voltage (minimum voltage)
• swells are same as dips but voltage rises above 110 % of the reference
voltage
Consequences of voltage dips
• Problems with programmable logic controllers
• Problems with electronic devices (restarts of computers)
• Problems with asynchronous motors (halt, antiphase)
Produces costs: shut down costs, standstill costs, restart costs, additional costs
17
Marko Pikkarainen29.3.2012
Voltage dips and swells
Sources for voltage dips• Faul ts
• Motor starting• Transformer switching
• Swells switching operations and
load disconnectionsRemedial measures• Use of dynamic voltage restorer
• Change of networks switching state
• Improve grid reliability
• Increase short circuit capacity of the network
Lim its in EN 50160• The vast majority of voltage dips has a duration less than 1 s and a
residual voltage above 40 %. However, voltage dips with a smallerresidual voltage and longer duration can occur infrequently. In some
areas, voltage dips with a residual voltage between 90 % and 85 % of
Uc can occur very frequently as a result of the switching of loads in
network users‘ installations
18
Marko Pikkarainen29.3.2012
~ ~= =
~
as yr i sor switch
P
Q
grid load
rectifier
energystorage
inverter
Interruptions
Definition
• condition in which the voltage at the supply terminals is lower than 5 % of thereference voltage (EN 50160)
• prearranged, when network users are informed in advance; or
• accidental, caused by permanent or transient faults, mostly related to
external events, equipment failures or interference. An accidental
interruption is classified as:
• a long interruption (longer than 3 min);
• a short interruption (up to and including 3 min)
Consequences of interruptions
• Produces costs: shut down costs, standstill costs, restart costs, additional costs
Sources for interruptions
• Normally, interruptions are caused by the operation of switches or protective
devices. (faults)
• Maintenance of components
19
Marko Pikkarainen29.3.2012
Interruptions
Remedial measures
• Decrease fault occurrence (overhead lines -> underground cables)
• Install remote controlled components to grid (switch, isolator)
• Build backup connection or backup power generation units for sensitive
customers
Limits in EN 50160
• Under normal operating conditions, the annual frequency of voltage
interruptions longer than three minutes varies substantially between areas. Thisis due to, among other things, differences in system layout (e.g. cable systems
versus overhead line systems), environmental and climatic conditions.
• The duration of most of the short interruptions may be less than some seconds.
Indicative values, intended to provide readers with information on the range ofmagnitude which can be expected, can be found in IEC/TR 61000-2-8
20
Marko Pikkarainen29.3.2012
7/21/2019 Proactive Network Monitoring PQ 4p
http://slidepdf.com/reader/full/proactive-network-monitoring-pq-4p 6/9
High frequency signals / Mains signalling
voltages
Signal superimposed on the supply voltage for the purpose of
transmission of information in the public supply network and to network
users' premises. Three types of signals in the public supply network canbe classified:
• ripple control signals: superimposed sinusoidal voltage signals in the frequency
range 110 Hz to 3 000 Hz;
• power-line-carrier signals: superimposed sinusoidal voltage signals in the
frequency range 3 kHz to 148,5 kHz (for PLC purposes, in some networks also
frequencies above 148,5 kHz are used.);
• mains marking signals: superimposed short time alterations (transients) at
selected points of the voltage waveform
Consequences of signalling voltages
• EMC problems might occur: the operation of touch dimmer lamps might be
disturbed by PLC (power line communication)
21
Marko Pikkarainen29.3.2012
Transient over voltages
Short duration overvoltage usually with a durat ion of a few milliseconds
or less
Consequences of transient over voltages
• Breakage of devices and components
Sources for transient over voltages
• lightning, switching or operation of fuses
Remedial measures
• surge protective devices (For withstanding transient overvoltages in thevast majority of cases, LV Installations and end users’ appliances are
designed according to EN 60664-1.)
22
Marko Pikkarainen29.3.2012
Some changes in field of power quality
23
Marko Pikkarainen 29.3.2012
Flicker sensitivity of compact florescent
lamps
• Flicker is the subjective impression of luminance variations of lightning
as a result of voltage fluctuations. Flicker is more a physiological than a
physical value. The tests to produce the borderline of flicker were
established in laboratory with individuals. This borderline is valid for
incandescent lamps.
• The result of the European Commission Regulation number 244/2009
is that incandescent bulbs will be gradually phased out from the market
• Compact fluorescent lamps have different flicker response because the
working principle is different
• Flickermeter is able to detect voltage changes with appearing
frequency from 0.05 Hz to 35 Hz.
24
Marko Pikkarainen29.3.2012
7/21/2019 Proactive Network Monitoring PQ 4p
http://slidepdf.com/reader/full/proactive-network-monitoring-pq-4p 7/9
Flicker sensitivity of compact florescent
lamps
25
Marko Pikkarainen29.3.2012
Flicker sensitivity of compact florescent
lamps
26
Marko Pikkarainen29.3.2012
Flicker measurement in future
• Same measurement method but new limit
• Valid for traditional voltage changes
• Interharmonics are not affecting to result
• New measurement method with modified lamp characteristic
and old limit (1 pu)• Interharmonics could be taken into consideration
• Replace flicker with rapid voltage changes
27
Marko Pikkarainen29.3.2012
u(t)
variable gainT = 1 min demodulation
P
Pst
lt
weightingfilter lampe -eye
H(s)
squaring andsmoothing
statisticalevaluation
8.8 Hz 0.53 Hz0 .0 5H z 3 5 Hz
UU (t)
UU (t) weighted
% % %²
momentaryflickerlevell P
f
Proactive power quality monitoring
28
Marko Pikkarainen 29.3.2012
7/21/2019 Proactive Network Monitoring PQ 4p
http://slidepdf.com/reader/full/proactive-network-monitoring-pq-4p 8/9
Traditional power quality monitoring
• Power quality measurements are based on centralized measurements
from MV level
• Outages, frequency problems and voltage levels in MV level have been
spotted from centralized measurements
• From LV side power quality is usually monitored with case specific
measurements
• customer complaints and clarification requests
• There has not been available comprehensive and continuous power
quality information over entire distr ibution network
• The novel AMR technology and distribution substation automation hasincreased the power quality awareness
• Of some power quality quantities:
• Interruptions, voltage levels, harmonics...
29
Marko Pikkarainen29.3.2012
Power quality monitoring in the future
•Power quality monitoring will need information from voltage from each
customer connection point
• AMI is obvious system to produce the needed data
•In addition of voltage measurement a proper current measurement could
provide critical information to power quality monitoring application
•AMI could short the clarification t ime of power quality disturbances and
make it more efficient
•If the clarification time decreases also it could speed up decisions and acts of
how to decrease the effect of disturbance
•Savings
•Also customer satisfaction level could increase
30
Marko Pikkarainen29.3.2012
Proactive power quality monitoring
Goal:
• To detect power quality and reliability problems automatically
• To detect the most probable reason for power quality problems
automatically
• To predict the behaviour of different power quality quantities in thefuture
• Short term prediction (operations)
• Long term prediction (planning)
• To improve power quality, to operate network optimally
Methods:
• efficient utilization of static and dynamic information
• optimization of network monitoring processes and information
management
31
Marko Pikkarainen29.3.2012
New model of proactive network monitoring32
Marko Pikkarainen29.3.2012
Network
Information
Customer
Information
Measurements(AMR, conditionmonitoring,
PQ, weather,relay data, etc.)
Future
scenarios
Standards,
recommendations
•Analysis
•Detection ofpotentialproblems
•Priorisation
Immediate
actions
Proactive
actions
Operation
Maintenance
Planning
7/21/2019 Proactive Network Monitoring PQ 4p
http://slidepdf.com/reader/full/proactive-network-monitoring-pq-4p 9/9
Example of proactive network monitoring,
Flicker
33
Marko Pikkarainen29.3.2012
Network
Information
Customer
Information
Future
scenariosMeasurements(AMR, condition
monitoring,
PQ, weather,relay data, etc.)
Standards,
recommendations
•Analysis•Simulation•Detection ofpotential
problems•Priorisation
Planning
REFERENCES
H. Renner, M. Sakulin, Power quality, T extbook to lectur e “Power quality and supply reliabil ity“
H. Renner, “Power quality and supply reliability“ , Lecture notes
M. Pikkarainen, B. A. Siddiqui, P. Pakonen, P. Verho, S. Vehviläinen, 2011, “ Vision of Power Quality Monitoring andManagement in Future Distri bution Network s”, Conference paper, CIRED 2011.
M. Pikkarainen, P. Nevalainen, P. Pakonen, P. Verho, 2010, "Practical Case Study: Measurement of Power QualityProblems Caused by Common New Loads “, Conferenc e paper, NORDAC
“T he Cost of Power Disturbances to Industrial & Digital Economy Companies” , 2001, Consortium f or ElectricInfrastructure to Support a Digital Society.
European Commission Regulation, 2009, implementing Directiv e 2005/32/EC of the European Parliament and of the Council
with regard to ecodesign requirements for non-dir ectional household lamps, No 244/2009.
RongCai, 2009, “Flicker Interaction Studies and Flickermeter Improvement”, Dissertation, Eindhoven University of
Technology, Netherland
EN 50160, 2007, “Voltage characteristics of electricit y supplied by public distributio n networks” , Standard
L. P. Frater, N. R. Watson, “Lig ht Flicker Sensitiv ity of High Efficienc y Compact Fluorescent Lamps”, Power EngineeringConference, 2007. AUPEC 2007. Australasian Univ ersities
34
Marko Pikkarainen29.3.2012
Thank you for your attention
35
Marko Pikkarainen 29.3.2012