Pri Sec Distribution System

Embed Size (px)

Citation preview

  • 8/2/2019 Pri Sec Distribution System

    1/22

    After reading this Module , you should be able to:

    Provide classification of distribution systems

    Discuss design considerations

    Provide an analysis of AC and DC distribution systems

  • 8/2/2019 Pri Sec Distribution System

    2/22

    The part of the electrical-supply system existing between

    the distribution substations and the distributiontransformers is called the primary system.

    It is made of circuits, known as primary feeders or

    primary distribution feeders. The most commonly used

    nominal primary voltage is 11 kV.

  • 8/2/2019 Pri Sec Distribution System

    3/22

    The secondary distribution system receives power from the

    secondary side of distribution transformers at low voltage

    and supplies power to various connected loads via service

    lines.The secondary distribution System is the final sub-system of

    the power system.

    The secondary distribution systems are generally of the

    radial type except for some specific service areas such as

    hospitals, business centers and military installations, which

    require highly reliable service, and therefore, may be of a

    grid or mesh type.

  • 8/2/2019 Pri Sec Distribution System

    4/22

    Figure : Radial secondary distribution system configuration

  • 8/2/2019 Pri Sec Distribution System

    5/22

    Good voltage regulation is the most important factor in a

    distribution system for delivering good service to the

    consumer. For this purpose, careful consideration is

    required for the design of feeders and distributor networks.

    Feeders are the conductors that connect substations to

    consumer ports and have large current carrying capacity.

    The current loading of a feeder is uniform along the whole

    of its length since no tappings are taken from it. The design

    of a feeder is based mainly on the current that is to be

    carried.

  • 8/2/2019 Pri Sec Distribution System

    6/22

    Distributors are the conductors, which run along a street

    or an area to supply power to consumers.

    These can be easily recognized by the number of

    tappings, which are taken from them for the supply to

    various consumer terminals.

    The current loading of a distributor is not uniform and itvaries along the length while its design is largely

    influenced by the voltage drop along it.

  • 8/2/2019 Pri Sec Distribution System

    7/22

    Service Main and Sub Main The service mains are the

    conductors forming connecting links between distributors

    and metering points of the consumer's terminal. Figure

    14.1 shows the layout of a distribution system. The term

    sub main refers to the several connections given to

    consumers from one service main.

  • 8/2/2019 Pri Sec Distribution System

    8/22

  • 8/2/2019 Pri Sec Distribution System

    9/22

    It has been established that 70% of the total losses occur

    in the primary and secondary distribution system while

    transmission and sub-transmission lines account for only

    30% of the total losses.

    Distribution losses amount to 15.5% of the generation

    capacity and the target level is to bring it down to 7.5%.

    Therefore the primary and secondary distribution systems

    must be planned with care to ensure losses within

    acceptability limits

  • 8/2/2019 Pri Sec Distribution System

    10/22

    Inadequate Size of Conductor :

    The rural load is usually scattered and fed byradial feeders.

    Feeder Length In practice, 11 kV and 415 V lines in rural

    areas are hurriedly extended radially over long distances to

    feed loads scattered over large areas. This results in high

    line resistance, low voltage, and high current, and

    therefore, leads to high I 2R losses in the line.

  • 8/2/2019 Pri Sec Distribution System

    11/22

    Location of Distribution Transformers Often the distribution

    transformers are not located centrally in relation to the

    intended customer. Consequently, the farthest customers

    obtain an extremely low voltage even though a reasonablygood voltage level is maintained at the secondary

    transformer.

    This again leads to higher line losses.

    Therefore, in order to reduce the voltage drop in the line

    transmitting power to consumers located farthest from the

    line, the DT should be located at the load center to keep the

    voltage drop within permissible limits.

  • 8/2/2019 Pri Sec Distribution System

    12/22

    Low Voltage Whenever the voltage applied to an induction

    motor deviates from rated voltage, its performance is

    adversely affected. A reduced voltage, in case of an induction

    motor, results in higher currents drawn for the same output

    leading to higher losses. This can be overcome by adjusting

    the tap changer at power transformer and at distributiontransformer, if available.

  • 8/2/2019 Pri Sec Distribution System

    13/22

    Use of Over-rated Distribution Transformers

    Studies on 11 kV feeders have revealed that often the

    rating of distribution transformers (DTs) is much higher

    than the maximum kVA demand on the LT feeder. An

    overrated transformer produces an unnecessarily high iron

    loss.From the above, it is clear that the rating should be

    judiciously selected to keep the losses within the permissible

    limits.

  • 8/2/2019 Pri Sec Distribution System

    14/22

    Low PowerFactor In most of the LT distribution

    systems, it is found that the power factor varies from as

    worse as 0.65 to 0.75. A low power factor contributes

    towards high distribution losses.

    For a given load, if the power factor is low, the current

    drawn is high, consequently the losses proportional to a

    square of the current, will be more.

    Thus, line losses owing to the poor power factor can be

    reduced by improving the power factor by using shunt

    capacitors for the purpose.

  • 8/2/2019 Pri Sec Distribution System

    15/22

    The following methods are adopted for the reduction of

    distribution-system losses:

    1. HV distribution system

    2. Feeder reconfiguration

    3. Grading of conductor

    4. Construction of new substation5. . Reactive-power compensation

  • 8/2/2019 Pri Sec Distribution System

    16/22

    1 . HV Distribution System

    The low-voltage distribution system contributes a majority of the

    total distribution losses because of poor voltage regulation .

    The present situation is that LV lines are extended, irrespective of

    voltage drops, up to the full capacity of the DT and sometimes

    over and above the transformer capacity. Hence, no purpose will

    be served by prescribing low kVA-km loading limits for LV lines.

    The only practice and feasible solution is to eliminate or

    minimize LV lines by switching over to single- phase high voltage

    distribution. By adopting HV distribution, the losses in the LV

    distribution can be minimized.

  • 8/2/2019 Pri Sec Distribution System

    17/22

    2 . Feeder Reconfiguration

    It is defined as the process of altering the topological

    structure of distribution feeders by changing the

    open/closed status of the sectionalising and tie switches.

    Feeder reconfiguration allows the transfer of loads from

    heavy loaded feeders to moderately heavy loaded feeders.

    Such transfers are effective in improving the voltage

    profile along the feeders and effecting reduction in the

    overall system power losses.

  • 8/2/2019 Pri Sec Distribution System

    18/22

    3. Grading of Conductor

    In normal practice, the conductor used for radial distribution

    feeders is of uniform cross-sectional area. However, the load

    magnitude at the substation is high and it reduces as we

    proceed to the tail-end of the feeder. This indicates that the

    use of a higher-sized conductor, which is capable of supplying

    load from the source point, is not necessary at the tail-end

    point. Similarly, the use of different conductor cross-sectionsfor intermediate sections will lead to a minimum capital

    investment cost and line loss.

  • 8/2/2019 Pri Sec Distribution System

    19/22

    4. Construction of New Substation

    If a new substation is to be constructed and connected

    to an existing network, several possible solutions are to

    be studied. These solutions may include various

    connection schemes of the substation and several

    feasible locations .

    The optimum site for a substation is defined as that

    location which will result in minimum cost for construction

    and minimum losses. Therefore, by constructing a new

    substation at load centres, the line osses will be reduced

    due to an improvement in the voltage profile and a

    reduction in the length of the lines.

    5 R i P C i

  • 8/2/2019 Pri Sec Distribution System

    20/22

    5. Reactive Power Compensation

    Voltage-reactive power control function has a pivotal role

    to play in the distribution automation.

    The problem of reactive power compensation can be

    attempted by providing static capacitors.

    The method presently used to compensate the reactive

    power component is to increase the reactive power by

    increasing the terminal voltage of the generator (or), by

    increasing the field current of the synchronous machine in

    condenser mode at the generating stations. This procedure isnot effective because the power-system losses will be further

    increased due to the increase of reactive power in the

    transmission system.

  • 8/2/2019 Pri Sec Distribution System

    21/22

    An alternative method for compensating the reactive power isthe use ofcapacitors in distribution systems at customer

    points. Shunt capacitors supply the amount of reactive power

    to the system at the point where they are connected.

    There are two methods of capacitor compensation viz.

    1. Series compensation (capacitors are placed in series with line)

    2. Shunt compensation (capacitors are placed in parallel with

    load)

  • 8/2/2019 Pri Sec Distribution System

    22/22

    The fundamental function of capacitors, whether they are

    series or shunt in a power system is to generate reactive

    power to improve power factor and voltage, thereby

    enhancing the system capacity and reducing losses.

    In series capacitors, the reactive power is proportional to

    the square of the load current, whereas in shunt capacitors

    it is proportional to the square of the voltage.