    High Voltage Insulation Diagnostics

    Presented by: Bostjan Flis

    [email protected]

    WELCOME!

  • 7/27/2019 Prezentare izolatie Metrel

    2/15

    Content overview

    Application areas of HV insulation testing

    What influences insulation resistance

    Symptoms of bad insulation

    Testing methods Insulation testing with DC test voltage - insulation characteristics

    Insulation testing with DC test voltage - test parameters

    Limit values

    Connection schemes

    Test data evaluation i.e. statistics keeping

    General requirements for HV insulation testers Metrel HV insulation testers

    Metrel's solution providing, services and development

  • 7/27/2019 Prezentare izolatie Metrel

    3/15

    Application areas of HV insulation testing

    Insulation resistance testing is part ofpredictive maintenance of:

    - Rotary machines (generators, motors)

    - Transformers (industry, utilities, power distribution)

    - Cables

    - Measuring transducers

    - Distribution boards

    Benefits:

    - Lower TCO (total cost of ownership)

    - increased electrical safety

    - prevention against fire hazard

  • 7/27/2019 Prezentare izolatie Metrel

    4/15

    What influences insulation resistance

    - Thermal exposure

    - Overload

    - Moisture

    - Electrical shocks

    - Mechanical shocks (vibrations, bad transportation)

    - Dirt (oil, dust, conductive materials)

    - General ageing of insulation

    Symptoms of bad insulation

    - Insulation breakdowns in a form of electrical short-circuits

    - Fire

    - Long-term downgrading values of insulation resistance

    - Insulation resistance values under by standards determined values

  • 7/27/2019 Prezentare izolatie Metrel

    5/15

    Insulation testing methods

    - AC insulation testing (50/60Hz, 1 minute)

    - Insulation surge breakdown testing

    - Insulation testing with switching voltage

    - Insulation testing with DC voltage

    - Dielectric losses (tg)

    - Partial discharges

    - U I characteristics

  • 7/27/2019 Prezentare izolatie Metrel

    6/15

    Insulation testing with DC test voltage - insulation characteristics

    Riso Cpi

    Rpi

    Cis

    Riss

    Riss

    Itot

    +

    Guar

    U

    ICisoIRCpiIRiso

    IRiss U Test voltage

    Riss1 and Riss2 Insulation surface resistance

    Riso Insulation resistance

    Ciso Capacitance of an insulation system

    Rpi Polarisation resistance

    Cpi Polarisations capacitance

    Itot Total insulation current

    IRiss Insulation surface leakage current

    IRiso Resisitve part of the insulation current

    IRCpi Polarisation current

    ICiso Capacitive part of the insulation current

    uA

    0

    10

    20

    30

    40

    t [s]0 200 400 600 800

    IRiso

    Itot

    IRiss

    IRCpi

    ICiso

  • 7/27/2019 Prezentare izolatie Metrel

    7/15

    Insulation parameters

    Polarisation Index (PI)

    PI = R tot (10 Min) / R tot (1Min)

    Dielectric absoption ratio (DAR)

    DAR = R tot (1 Min) / R tot (30 Sek)

    Dielectric discharge (DD)

    DD = I DIS (1 min) / (U * C ISO )

    I DIS.a discharge current measured 1 minute after disconnecting the insulation system from the test voltage

    C ISO. capacitance of the insulation system

    U test voltage Discharge of

    Ciss

    Ito t

    [s]10 20 30 40 50 6000

    Badinsulation

    Goodinsulation

    Discharging of Cpi

  • 7/27/2019 Prezentare izolatie Metrel

    8/15

    Limit values for insulation testing

    with DC voltage

    Insulation resistance

    Limit value

    General applications > 1M per 1kV der Nennspannung des Prflings

    Rotary machines according toIEEE 43-2000

    a./ 1 M + 1 M/1kVb./ 5 M for motors under 600Vc./ 100 M for motors above 600V

    Switching- and control devices according to IEC 60439-1 > 1k for 1V of the UN of the test object

    Splitting transformers and safety low voltage transformers accordingto IEC 61558 a./ Basis insulation > 2Mb./ Additional insulation > 5M

    c./ Reinforced insulation > 7M

    Polarisation index (PI)

    PI Wert

    Evaluation

    1 to 1.5 BAD (valid for older types of insulation materials)

    2 to 4 SUFFICIENT (valid for older types of insulation materials)> 4 VERY GOOD (also for the modern type of insulation materials)

    Dielektric absorption ratio (DAR)

    DAR value

    Evaluation

    < 1 BAD

    1 DAR 1.25 SUFFICIENT

    > 1.4 VERY GOOD

    kVM ni UR

    Thumb rule(motors and generators):

  • 7/27/2019 Prezentare izolatie Metrel

    9/15

    Connection schemes

    Precondition!

    - Measuring object has to be disconnected from power supply network (voltage free)

    - Surface of the insulation system has to be dry and clean

    VNNN

    G

    VNNN

    G

    VNNN

    G

    Power transformer

    HV vs LV

    HV vs G

    LV vs GDevice A Device B

    Device N

    Power supply

    PE - ground

    Port A Port A Port A

    Port BPort B

    PE PE

    Port C1

    Port C2Port C2

    Port C1Port C

    Multiple devices

  • 7/27/2019 Prezentare izolatie Metrel

    10/15

    Test data evaluation i.e. statistics keeping

    Statistics

    - Always assure the same measuring conditions

    (connection, temperature, test voltage, diagnostics parameters)

    - Regular test intervals (6 months or one year)

    - Results keeping for the entire life period of the equipment

    - Observation of downgrading trends

    Temperature coefficient

    (all values are to be calculated on 75C)

    rK

    RR1

    //i10/75i10

    0304,028,2

    10r

    K

  • 7/27/2019 Prezentare izolatie Metrel

    11/15

    General requirements for HV insulation testers

    Test functions:

    - Insulation resistance

    - Step voltage test

    - Capacitance

    - PI, DD, DAR

    - Current in A and mA range

    - Voltage AC/DC

    Accessories:

    - Shielded test leads

    - High quality test terminals (HV, antistatic, high surface resistance)

    - PC Software for downloading of test results and creating test reports

    Other features:

    - Guard terminal to eliminate surface insulation currents

    - Automatic discharging of the test object after measurement

    - Built-in timer

    - On-Line graph R = f(t)

    - EM immunity for usage in HV environments

    - EM Filters for improved accuracy

    - Good charging system (accus or mains or both)

  • 7/27/2019 Prezentare izolatie Metrel

    12/15

    Metrel HV insulation testers

    Integrated features:

    Test voltage up to 10kV DC

    Resistance measuring range up to 10T

    Automated calculation of PI, DAR and DD for profound insulation diagnostics

    On-Line R=f(t) display

    Test voltage setting in 25V steps

    Shielded 12kV test leads to reduce influence of external EM fields

    CAT IV/600V over-voltage category for utilities and industrial applications

    New TeraLink PRO Windows PC Software for TeraOhm 5kV PlusHandbook Modern insulation testing on CD

  • 7/27/2019 Prezentare izolatie Metrel

    13/15

    Metrel's solution providing, services and development

    Product training in Metrel training centre

    On-Line technical support

    Application training and publications

    Repair & Calibration training

    Calibration equipment

    Repair & Calibration services

    Advanced technical solutions for all products segments

    (Hardware, Firmware, PC Software)

    Customised solutions (Instruments, Software, Accessories)

  • 7/27/2019 Prezentare izolatie Metrel

    14/15

    WHY NOT

    METREL?

  • 7/27/2019 Prezentare izolatie Metrel

    15/15

    THANK YOU!