VAPOUR ABSORPTION MACHINES Presented by - Cooling Division – C&H SBU - Thermax

Presentation on Thermax Chiller unit

Embed Size (px)

DESCRIPTION

Submitted by Anurag Kesharwani , Balco

Citation preview

Page 1: Presentation on Thermax Chiller unit

VAPOUR ABSORPTION MACHINES

Presented by - Cool ing Divis ion – C&H SBU - Thermax

Page 2: Presentation on Thermax Chiller unit

Welcome to the home of Energy & Environment

We have tried to answer the following questions, so that, it would help you understand the product in a much easier way

• Who are you and what do you do?• What is Cooling and what are the conventional methods of cooling?• How does an Electrical Chiller work?• When should one go for an Absorption Chiller and how did a VAM evolve in

Thermax?• Why should one go for an Absorption Chiller?• What are the governing principles of a VAM?• How does an Absorption Machine work?• Can you explain the whole scheme?• What makes Thermax VAMs more unique and reliable?• What do we offer and where we can/have offered?• What do those Abbreviations mean?• I have more queries, how can I get them cleared?• How can we reach you?• Who has certified us?

Page 3: Presentation on Thermax Chiller unit

Who are you and what do you do?

Vision – To be a globally respected high performance organization offering sustainable solution in energy and environment

Boilers & Heaters

Absorption Cooling

Water & Waste

Solutions

Air Pollution Control

Chemicals

Cogeneration

Page 4: Presentation on Thermax Chiller unit

What is Cooling and what are the conventional methods of cooling?

Cooling – Transfer of heat from source to sink by performing an external work; even a body @ -272*C has one more degree of heat energy to be removed to achieve absolute zero (i.e.), 0*K (or) -273*C

1 TR = 3024KCal = 3.52KW = amount of energy absorbed by 1ton of ice, when it melts to water, at 0*C

CONVENTIONAL METHODS OF COOLING:Natural Refrigeration

E.g., Clay water pot, SweatingMechanical Refrigeration

Gas Refrigerators Vapour Refrigerators

Vapour Compression Vapour Absorption

Page 5: Presentation on Thermax Chiller unit

How does an Electrical Chiller work?

Parts & Process involved: Evaporator - Refrigerant Vapourization Compressor - Refrigerant (Vapour Phase)

Compression Condenser - Refrigerant ---> Vapour to

Liquid Expansion Valve - Pressure Reducer / Throttling

Valve – To help refrigerant achieve the required

Temperature

Page 6: Presentation on Thermax Chiller unit

Working CycleVapour Compression Machine

Reefer Cycle.swf

Page 7: Presentation on Thermax Chiller unit

When should one go for an Absorption Chiller and how did a VAM evolve in

Thermax?

We would go for an Absorption Chiller: When excess heat source is available, for e.g., availability of excess

steam in a boiler When Heat is ineffectively dissipated into the atmosphere, for e.g.,

exhaust from a D.G, steam from a turbine outlet When the operational expenditure of VAM is very much lesser than the

VCM, for e.g., when the industry is facing issues with power supply from the grid (high cost/frequent power cuts)

When the production cost of steam is almost negligible, for e.g., In sugar plants, they have a co-gen power plant by using the baggasse (a by-product of the process)

Evolution of VAM technology in Thermax: 1984-87 – Marketing tie-up with Sanyo, Japan 1988-94 – Technology collaboration with Sanyo, Japan 1991-96 - Direct Fired – Technology tie-up – Kawasaki Till Date – Installed over 3000 Machines in over 50 Countries

92% +Market Share

in India

Page 8: Presentation on Thermax Chiller unit

Why should one go for an Absorption Chiller?

We should go for an Absorption Chiller, because: It is a simple Heat Exchanger operating at different pressures,

hence, we can assure that it has an unmatched Reliability It has a very less operating and maintenance cost, along with

an automatic and step-less modulation system It does not have any moving parts, hence, no noise, no

vibration and no dynamic load (Roof-top positioning is possible) Waste heat is utilized usefully and in-turn, avoids the need for

switching to a HT connection and also avoids a DG running especially for the chilling purpose (the load on EB power and DG is reduced to a huge extent)

It operates on an environment friendly refrigerant (i.e.), CFC free, ozone friendly machine

It is fully automated, hence, we require minimal amount of human intervention

Page 9: Presentation on Thermax Chiller unit

What are the governing principles of a VAM?

Working Materials – Thermax VAM Refrigerant – DM Water Salt – Lithium Bromide (LiBr) Inhibitor – Lithium Molybdate (Moly) Performance Booster – Octyl Alcohol

Boiling Point of Water is directly proportional to the Vapour Pressure of the system @atm. Pressure (760mm of Hg) – Water boils @100*C In VAM, we maintain a shell pressure of 6mm of Hg, which

facilitates the water to boil @3.7*CHygroscopic nature of Salt

As we need to separate salt and water, it has to have a higher Vapour pressure difference, hence, we use LiBr as the salt solution

The operating concentration of LiBr lies between 57-64% in Water

Page 10: Presentation on Thermax Chiller unit

How does an Absorption Machine work?

Parts & Process involved: Evaporator – Refrigerant

Vapourization Absorber – Refrigerant (Vapour)

– Absorption by Absorbent

Generator – Regeneration of Refrigerant & Absorbent

Condenser – Liquefaction of Refrigerant

Totally we have 2 Shells: Lower Shell – Evaporator and

Absorber Upper Shell – Generator and

Condenser

Page 11: Presentation on Thermax Chiller unit
Page 12: Presentation on Thermax Chiller unit
Page 13: Presentation on Thermax Chiller unit

Condenser(Top Left Chamber) - Condensation of Refrigerant - Heat transfer to Cooling Water

Page 14: Presentation on Thermax Chiller unit

Can you explain the whole scheme?

Page 15: Presentation on Thermax Chiller unit
Page 16: Presentation on Thermax Chiller unit

What makes Thermax VAMs more unique and reliable?

Step-less Modulation - for a cooling load of 10 to 100%, the heat input can be modulated without any drop in Efficiency

Crystallization free m/c - pro-active, anti-crystallization mechanism is provided instead of a Reactive Auto de-crystallization mechanism using Online Concentration Control setup

Split Evaporator Design - twin-evaporator is provided to improve the COP of the machine by 5% and capacity by 10%

SS 430 Ti Generator Tubes - straight; plain; Titanium stabilized; Ferritic; Stainless Steel tubes in the HTG, to avoid the failure of generator tubes due to the presence of high temperature and concentration

Canned Motor Pumps - the impeller and the motor are packaged in a single shell, bolted construction

Distributor Tray - gravity feed mechanism is paired up with the distributor tray (nozzle is avoided) for the spray system

Page 17: Presentation on Thermax Chiller unit

Advanced Series Flow:In a double effect machine, we split the flow of the dil. LiBr into two different paths. One line would flow through LTHE, HTHE and then flows to the HTG, whereas, the other line flows through the DHE and HR and mixes into the first line before reaching the HTG, in order to have a maximum utilization of the heat input. The LTHE gets heated by the incoming Abs. spray line, the HTHE gets heated by the Intermediate solution coming out of the HTG, the DHE gets heated by the Vapour coming out of the LTG and the HR gets heated by the steam coming out of the HTG. Thus, we can say that, Thermax VAMs have minimum amount of heat loss

What makes Thermax VAMs more unique and reliable?

Variable Flow Drive: VFD modulates the frequency input to the Abs. Pump, based on the Generator level, which subsequently avoids

1) frequent ON/OFF of Abs. Pump – reduction in heat exchanger life

2) excess heat input during part load conditions

Page 18: Presentation on Thermax Chiller unit

What do we offer and where we can/have offered?

We offer, Steam Fired VAM – 50 to 3500TR Exhaust Fired VAM – 50 to 3500TR Direct Fired VAM – 50 to 3000TR Hot Water Fired VAM – 50 to 1150TR

We had offered to, Breweries & Distilleries Chemical Industry Commercial Centers Dairy & Confectionary Educational Institutions Engineering & Electronic Industry Hotels & Hospitality

Medical Centers Paper Plants Pharmaceuticals Power Plants Refineries & Petro-chemicals Steel Plants Super Markets & Malls

Combination of two or three heat sources are possible:COGENIE or TRIGENIE

Page 19: Presentation on Thermax Chiller unit

What do those Abbreviations mean?

Abs.COP*CDGHT

HTGHTHE

Kg/scmLTGLiBrLTHEm/cSS

SCVTR

VAMVCM

AbsorbentCo-efficient Of Performance

degree CelsiusDiesel Generator

High TransmissionHigh Temperature Generator

High Temperature Heat Exchanger

kilogram/square centimeterLow Temperature Generator

Lithium BromideLow Temperature Heat

Exchangermachine

Stainless SteelSteam Control Valve

Tonnage of RefrigerationVapour Absorption Machine

Vapour Compression Machine

Page 20: Presentation on Thermax Chiller unit

I have more queries, how can I get them cleared?

Thank you for your patient viewing & hearingWe hope that we have answered the questions

which may rise, when you think of an absorption machine. If you have any of the feasible scenarios for an absorption machine, we are always on your search-list. We would be very much delighted to work in one- breath with you for a greener, energy efficient future

For anymore queries, please feel free to contact the respective regional sales engineer or visit www.thermaxindia.com and post your query

The contact details are given below

Page 21: Presentation on Thermax Chiller unit
Page 22: Presentation on Thermax Chiller unit