PRE-ENGINEEREDSOLUTIONS
LCP Fused Coordination Panel • LPS Series POWR-Switch
Pre-Engineered Solutions
© 2016 Littelfuse POWR-GARD® Productslittelfuse.com
Features/Benefits• Meets NEC® requirements• Class CC and J fuse holders have built-in
open-circuit indication• Fast-acting UL Listed fuses protect against short circuits • Feed through/sub feed lugs and 84-circuit
configuration available• Ground and neutral bars• Copper bus standard
Advanced Design Options• MLO, Main Circuit Breaker, or Main Fused Pullout device• Fused Class T branch circuit pullout• Spare fuse cabinet accessory (holds six spare fuses)• TVSS overvoltage protection • Any NEMA enclosure required• High amperage sub-fed branch breakers (J60A) • Unique Specifier Tool (see pg. 146) to easily identify panel
configurations from tens of thousands of options
SpecificationsVoltage Ratings 120/208, 120/240, 277/480 VacMain Bus Rating 100 A - 400 A StandardConductor Terminals 6 AWG - 300 kcmilUL Listed UL 67 Panel boards and UL 50 Enclosures
Web ResourcesFor more information, visit: littelfuse.com/lcp
DescriptionThe Littelfuse® Coordination Panel provides a simple, time-saving solution for circuits that require selective coordination. This UL Listed product saves time and money, and increases safety by minimizing system downtime.
Applications• Elevators • Hospitals• Hotel and Entertainment Industry• Amusement Parks and Stadiums
Code RequirementsSystems required by the NEC® to be selectively coordinated include:
• Health Care Essential Electrical Systems (NEC 517.30)• Elevators (NEC 620.62)• Emergency Systems (NEC 700.28)• Legally Required Standby Systems (NEC 701.27)• Critical Operations Power Systems (NEC 708.54)
† Fuses quoted separately to meet panel specifications. Coordination for breakers >60 A depends on upstream and downstream devices. More specialized configurations are also available. Contact factory for more information. Note: The Littelfuse LPS and LCP products are custom designed products that fall outside standard specifications.
Customizable Options (select one from each column)NUMBER
OF CIRCUITS
VOLTAGE MAIN DEVICESNEUTRAL RATING
PANEL MOUNTING
PANEL DOOR
FUSE HOLDERS
BRANCH CIRCUIT PROTECTION DEVICES
(1-3 POLE)†
PANEL FEED
OPTIONAL LUGSSTANDARDENCLOSURE
RATING
2 - 42
120/208 V 3P, 4 W
120/240 V 1P, 3 W
277/480 V 3P, 4 W
125, 225, 400 or 600 A MLO
Up to 600 A MCB or Main Fuse
Pullout
100%
200%
Surface
Flush
Standard
Door-in-door
30 A Class CC
60 A Class J
10 A- 60 A fused circuit breaker
60 A-200 A
fused pullouts
Sub-fed circuit breakers >60 A
(not fused)
Top
Bottom
None
Sub-Fed (MLO panels)
Feed-Through
NEMA 1
NEMA 3R
NEMA 4X
LCP FUSED COORDINATION PANELSelective Coordination Panel
Pre-Engineered Solutions
littelfuse.com © 2016 Littelfuse POWR-GARD® Products
LCP FUSED COORDINATION PANEL Selective Coordination Panel
Inner Line
GND Bus
Neutral Detail
Neutral Detail
(6 AWG - 300 kcmil) Cu/AlIncoming Main Lugs
Cutler HammerGHB (480 V) or BAB (208 V)Circuit Breakers(or Pullouts)
LPSC001ID POWR-SafeDead front Class CC 600 VACFuseholder for use with LittelfuseCCMR, KLKR or KLDR Class CC fuses or POWR-Safe LPSJ holders for use the Class J fuses. (Fuses not included)
LPSC001ID POWR-SafeDead front Class CC 600 VACFuseholder for use with LittelfuseCCMR, KLKR or KLDR Class CC fuses or POWR-Safe LPSJ holders for use the Class J fuses. (Fuses not included)
Front TrimType 1 (NEMA) Enclosure
Front View with Front RemovedHinged Door with Catch and Lock
Dimensions in mm [inches]
Dimensions in mm [inches]
GND Bus
Inner Line
(6 AWG - 300 kcmil) Cu/AlIncoming Main Lugs
Cutler HammerGHB (480 V) or BAB (208 V)Circuit Breakers(or Pullouts)
Front TrimType 1 (NEMA) EnclosureFront View with Front Removed Hinged Door with
Catch and Lock
[6.00]152.4
[6.00]152.4
[28.00]711.2
[28.00]711.2
[36.00]914.4
[24.00]609.6
[16.50]419.1
[28.00]711.2
[42.00]1066.8
[30.00]762
[16.50]419.1
[9.69]246.06
[8.94]227.01
[28.00]711.2
[9.69]246.06
[8.94]227.01
Dimensions mm (inches)Standard Coordination Panel Board (up to 30 circuits)
Standard Coordination Panel Board (31-42 circuits)
Inner Line
GND Bus
Neutral Detail
Neutral Detail
(6 AWG - 300 kcmil) Cu/AlIncoming Main Lugs
Cutler HammerGHB (480 V) or BAB (208 V)Circuit Breakers(or Pullouts)
LPSC001ID POWR-SafeDead front Class CC 600 VACFuseholder for use with LittelfuseCCMR, KLKR or KLDR Class CC fuses or POWR-Safe LPSJ holders for use the Class J fuses. (Fuses not included)
LPSC001ID POWR-SafeDead front Class CC 600 VACFuseholder for use with LittelfuseCCMR, KLKR or KLDR Class CC fuses or POWR-Safe LPSJ holders for use the Class J fuses. (Fuses not included)
Front TrimType 1 (NEMA) Enclosure
Front View with Front RemovedHinged Door with Catch and Lock
Dimensions in mm [inches]
Dimensions in mm [inches]
GND Bus
Inner Line
(6 AWG - 300 kcmil) Cu/AlIncoming Main Lugs
Cutler HammerGHB (480 V) or BAB (208 V)Circuit Breakers(or Pullouts)
Front TrimType 1 (NEMA) EnclosureFront View with Front Removed Hinged Door with
Catch and Lock
[6.00]152.4
[6.00]152.4
[28.00]711.2
[28.00]711.2
[36.00]914.4
[24.00]609.6
[16.50]419.1
[28.00]711.2
[42.00]1066.8
[30.00]762
[16.50]419.1
[9.69]246.06
[8.94]227.01
[28.00]711.2
[9.69]246.06
[8.94]227.01
Note: The Littelfuse LPS and LCP products are custom designed products that fall outside standard specifications.
Dimensions may change depending on panel components. More specialized configurations are also available. Contact factory for more information.
Pre-Engineered Solutions
© 2016 Littelfuse POWR-GARD® Productslittelfuse.com
Fax to Your Local Littelfuse Rep Agency or Call 1-800-TEC-FUSE
Job Name: LF Quote #
Panel ID:
Distributor:
LF Rep Agency:
FUSE HOLDER BKR CKT# PH. CKT# BKR FUSE HOLDER
30A CC Holder 20/1 1 A 2 **20/3** 30A CC HolderInput Values Step 3 30A CC Holder 20/1 3 B 4 **//** 30A CC Holder
42 # of Panel Circuits 30A CC Holder 20/1 5 C 6 **///3** 30A CC Holder30A CC Holder 20/1 7 A 8 **20/3** 30A CC Holder
Step 2 277/480V 3 Phase, 4 Wire Voltage, Phase, Wire 30A CC Holder 20/1 9 B 10 **//** 30A CC Holder60A J Holder **60/3** 11 C 12 **///3** 30A CC Holder
Flush Mount Mounting 60A J Holder **//** 13 A 14 **20/3** 30A CC Holder60A J Holder **///3** 15 B 16 **//** 30A CC Holder
200A Main Breaker Main Circuit Breaker 30A CC Holder 20/1 17 C 18 **///3** 30A CC Holder30A CC Holder 20/1 19 A 20 20/1 30A CC Holder
200% Neutral Rating 30A CC Holder 20/1 21 B 22 20/1 30A CC Holder30A CC Holder 20/1 23 C 24 20/1 30A CC Holder
Bottom Feed Panel Feed 30A CC Holder 20/1 25 A 26 20/1 30A CC Holder30A CC Holder 20/1 27 B 28 20/1 30A CC Holder
Feed-Through Lugs Panel Options 30A CC Holder 20/1 29 C 30 20/1 30A CC Holder30A CC Holder 20/1 31 A 32 20/1 30A CC Holder
Type 3R Enclosure Rating 30A CC Holder 20/1 33 B 34 20/1 30A CC Holder30A CC Holder 20/1 35 C 36 20/1 30A CC Holder
Door-in-Door Panel Door 30A CC Holder 20/1 37 A 38 20/1 30A CC Holder30A CC Holder 20/1 39 B 40 **60/2** 60A J Holder
30A CC Holder 20/1 41 C 42 **//2** 60A J Holder
***Consult Factory when specifying 2 Pole and 3 Pole Circuit Breakers ***
Bill of Materials
Quantity
Base Part Number:
LCP 42 C 1Options From above:
Mounting: 1Main Circuit Breaker: 1
Neutral Rating: 1Panel Feed: 1
Panel Options: 1Enclosure Rating: 1
Panel Door: 1
Select Poles Breaker Select Amperage1 Breaker 313 Breaker 32 Breaker 1
Breaker 0Breaker 0
Step 4 Breaker 0Breaker 0Breaker 0
30 Amp Class CC Holder 4060 Amp Class J Holder 2
800-TEC FUSE
Fuseholder Quantities Calculate Automatically
Flush Mount200A Main Breaker
200%Bottom Feed
Feed-Through LugsType 3R
Door-in-Door
Please configure individual feeder circuits by selecting fuse holder and breaker placement and size in Drop down menus.
Littelfuse Reps
Enter Breaker Quantities From Above Panel Schedule
2020
www.littelfuse.com
60
Step 1
LCP42C-Sample
H1EM1
Littelfuse Distributor
Part Numbers
Littelfuse Coordination Panel Circuit Schedule
LCP Fused Coordination Panel Specifier
Simplify Communication and Minimize ErrorsA Microsoft Excel® spreadsheet designed to help engineers and contractors clearly convey which technical components they would like incorporated into the Littelfuse Coordination Panel.
• Easily specify technical components of your panels /system
• Quickly and accurately captures desired electrical protection devices
• Effectively manage each job with up-to-date information
• Ensures all pertinent information is captured to prevent unnecessary delays
Panel circuit schedule identifies
specific branch circuit protection
devices each panel needs
Identify specific panel options
Automatically tabulates your Bill of Material to keep an accurate count
Automatically generates base part number
Easy identification for project tracking
Get Started Today!1. Download The Specifier from
Littelfuse.com/lcp or request it from your Littelfuse sales representative
2. Fill it out to identify what you need (See sample below)
3. Send it back to Littelfuse and get a quick quote
4. Automatically generate your custom Bill of Material and base part number
LCP FUSED COORDINATION PANEL Selective Coordination Panel
Pre-Engineered Solutions
littelfuse.com © 2016 Littelfuse POWR-GARD® Products
LPS SERIES POWR-SWITCHShunt Trip Disconnect Switch
Description The Littelfuse® POWR-Switch provides a simple and economical solution for applications that require selective coordination and shunt trip capabilities.
Utilizes Class J time-delay fuses that are easily coordinated with other system overcurrent devices. The shunt trip capability allows the POWR-Switch to meet the ANSI/ASME standard that requires power to be automatically disconnected before water is turned on by the fire safety system.
Applications• Elevator circuits • Data processing rooms• Building emergency systems
Web ResourcesDownload technical information: littelfuse.com/lps
Specifications (POWR-Switch)
Supply Voltage Rating* 208 V, 240 V, 480 VAmpere Range 30 A, 60 A, 100 A, 200 A, 400 AInterrupting Rating 200 kAEnclosures NEMA 1 (standard) NEMA 3R, NEMA 4, NEMA 12 (optional)Approvals UL Listed (File: E219511)*Contact factory for 600 V options.
Specifications (Shunt Trip)
Voltage Rating 120 V, 60 Hz Max Inrush 4 AMax On time 1.5 cyclesMomentary Inrush 140 VA
Features/Benefits• Pre-engineered single unit, which makes
procurement easier than systems with multiple components
• Reduces labor costs up to 66% and total installation costs by over 30%
• Pre-installed UL listed Class J fuse holder – unique Class J size eliminates the need for any rejection type fuse clips
• Optional features offer flexibility for a variety of applications
• Control power terminal block
• UL Listed package
• Cu and AI wire rated
• Pre-wired control circuits lower installation time
• Lockable operating handle meets all code and safety requirements (Accepts up to 3 locks)
• Every unit is fully tested before delivery
Options• Control power transformer with fuses and blocks
• Fire safety interface relay
• Key to test switch
• Pilot light ”On”
• Isolated neutral lug
• Mechanical interlock auxiliary contact for hydraulic elevators with automatic recall (5 amp 120 Vac rated)
• Fire alarm voltage monitoring relay
• Option to bypass alarm when performing maintenance (-AZ option)
• XPress-Ship™ service offers 48 Hours direct shipment service on select fully loaded LPS POWR-Switches
Pre-Engineered Solutions
© 2016 Littelfuse POWR-GARD® Productslittelfuse.com
LPS SERIES POWR-SWITCHShunt Trip Disconnect Switch
LITTELFUSE SWITCH
CATALOG NUMBER
CONTROL POWER
TRANSFORMER STD. 100VA WITH PRI & SEC FUSE
(120 V SEC.)
FIRE SAFETY INTERFACE RELAY (3 PDT, 10 A, 120 V)
KEY TO TEST SWITCH
PILOT LIGHT “ON”
ISOLATED NEUTRAL
LUG
MECHANICAL INTERLOCK AUX.
CONTACT FOR HYDRAULIC
ELEVATORS W/ AUTOMATIC RECALL
(5 A ,120 VAC)
FIRE ALARM SHUNT TRIP
VOLTAGE MONITORING
RELAY
OPTIONAL ENCLOSURES —
AZ OPTION (BYPASS
FIRE ALARM DURINGMAINT. TEST)
REQUIRED REQUIRED REQUIRED OPTIONAL OPTIONAL OPTIONAL REQUIRED OPTIONAL OPTIONAL OPTIONAL
BASE
CA
TALO
G #
RATI
NG
RATI
NG
OPTI
ON
CODE
RATI
NG
OPTI
ON
CODE
RATI
NG
OPTI
ON
CODE
RATI
NG
OPTI
ON
CODE
RATI
NG
OPTI
ON
CODE
RATI
NG
OPTI
ON
CODE
RATI
NG
OPTI
ON
CODE
RATI
NG
OPTI
ON
CODE
OPTI
ON
CODE
LPS3* 30 A 208 V T20 24 VDC Coil R2 120 V K Red R 30–60 A N6 1 NO & 1 NC A 1-Pole F1 NEMA 3R U – AZ
LPS6* 60 A 240 V T24 120 VAC Coil R1 Green G 100 A N1 2 NO & 2 NC B 3-Pole F3 NEMA 4 Y –
LPS1* 100 A 480 V T48 White W 200 A N2 NEMA 12 Z –
LPS2* 200 A 400 A N4 –
LPS4* 400 A –
*Part Numbers: Any voltage can be paired with any amperage. Options can be any combination but the ratings must match the option code. Not all options are required. Contact factory for 600 V control power transformer option.
Note: When ordering - desired options must be listed in the order shown above. Typical options include Control Power Transformer, Fire Safety Interface Relay, Mechanical Interlock Auxiliary Contact and Fire Alarm Voltage Monitoring Relay.
Example Catalog Number from Desired Options
Dimensions of EnclosureCATALOG SERIES AMPERE RATING NEMA 1 DIMENSIONS NEMA 3R DIMENSIONS NEMA 4, 12 DIMENSIONS LUG SIZE
LPS3 30 24”H x 20”W x 9”D 24”H x 20”W x 8”D 24”H x 20”W x 10”D #14 - #8 AL or CU
LPS6 60 24”H x 20”W x 9”D 24”H x 20”W x 8”D 24”H x 20”W x 10”D #14 - #2 AL or CU
LPS1 100 24”H x 20”W x 9”D 24”H x 20”W x 8”D 24”H x 20”W x 10”D #8 - 1/0 AL or CU
LPS2 200 30”H x 20”W x 9”D 30”H x 24”W x 8”D 30”H x 20”W x 10”D #6 - 250kcmil AL or CU
LPS4 400 48”H x 36”W x 11”D Contact Factory Contact Factory 3/0 AL or CU
Note: Over-size enclosures used to accommodate control power transformer, interface relay and terminal blocks.
Ordering InformationComplete catalog numbers consist of switch catalog numbers and the desired options. See example below.
XPress-Ship™ AMPERE RATING
VOLTAGE RATING CATALOG NUMBER XPress-Ship™
ORDERING NUMBER60 A 480 V LPS6T48R1KGN6BF3-AZ XPS6T48R1KGN6F3-AZ*
US Only 100 A 480 V LPS1T48R1KGN1BF3-AZ XPS1T48R1KGN1F3-AZ*
Littelfuse XPress-Ship™ service offers 48 Hours** direct-shipment service on select fully-loaded LPS POWR-Switch to meet your urgent system requirements on time.
XPress-Ship™ switches include three JTD_ID Series fuses rated at the device’s maximum ampacity.
100 A 480 V LPS1T48R1KGN1BF3 XPS1T48R1KGN1BF3
200 A 208 V LPS2T20R1KGN2BF3-AZ XPS2T20R1KGN2F3-AZ*
200 A 480 V LPS2T48R1KGN2BF3 XPS2T48R1KGN2BF3
*AZ option includes B & F3 options.
**XPress-Ship™ 48 hour service requires ordering from XPress-Ship Ordering Numbers shown above and is subject to a maximum of any combination of three switches per customer order. XPress-Ship service offers 48 hour shipment from the factory through standard ground transportation. For expedited delivery, contact your local Littelfuse Representative.
LPS1 T20 R1 K G N1 B F3 U – AZ = Littelfuse Catalog Number LPS1T20R1KGN1BF3U-AZ
Pre-Engineered Solutions
littelfuse.com © 2016 Littelfuse POWR-GARD® Products
Shunt-Trip OperationThe disconnecting means is a shunt-trip operated switch. The control power source for the shunt-trip operator is a 120 Vac supply originating in the Littelfuse POWR-Switch LPS Series disconnect. Current to the shunt-trip device is switched by an isolation relay, which is in turn controlled by the FACP.
The control signal may be either 24 Vdc from the FACP (option R2) or a “dry” contact closure in the FACP (option R1). In the case of a “dry” contact closure, the sensing voltage is 120 VAC originating in the Littelfuse POWR-Switch LPS Series disconnect.
CAUTION: When using the “dry” contact closure, option 1, DO NOT supply 120 Vac from the FACP as equipment damage or personnel injury may occur.
A key test option (option K) is available to test the shunt-trip circuit.
Supervisory IndicationAdditionally, an optional separate relay can be specified to monitor the 120 Vac control power source in the Littelfuse POWR-Switch LPS Series disconnect. This relay (option FR) is used to provide supervisory indication of “Control Power Available” as required by NFPA 72 Section 6.15.4.4.
Other OptionsOptional features include contact closure for control of auxiliary power, i.e. battery lowering/door opening system (options A and B). Support for state of Arizona, Oregon and Texas requirements to prevent “nuisance” fire alarms by over-riding the “Control Power not Available” signal when the Littelfuse POWR-Switch LPS Series disconnect is manually (intentionally) turned off, and distinctive signaling for ON-OFF-TRIPPED conditions (option AZ).
All Littelfuse POWR-Switch LPS Series disconnect switches are UL-Listed and designed for safe access by qualified personnel. When maintenance or shutdown service is required, no energized parts are exposed inside the enclosure when the disconnect switch is manually turned to the OFF position. For proper maintenance safety precautions, always turn off incoming power to the Littelfuse POWR-Switch LPS Series switch when possible. When servicing any live electrical equipment, always wear appropriate personal protective equipment.
Fuse TablePOWR-SWITCH VOLTAGE/ PRIMARY FUSES (2) SECONDARY FUSE (1)
TRANSFORMER TYPE FUSE TYPE FUSE RATING FUSE TYPE FUSE RATING208/120 KLDR001 1 FLM1.12 1-1/8240/120 KLDR500 1/2 FLM1.12 1-1/8480/120 KLDR400 4/10 FLM1.12 1-1/8600/120 KLDR250 1/4 FLM1.12 1-1/8
Power Wiring Torque SpecificationsCHARACTERISTICS LPS3 LPS6 LPS1 LPS2 LPS4
Amps 30 60 100 200 400AWG 10 6 3 3/0 (2) 3/0
Molded Case Switch (MCS) Mfr. ABB ABB ABB ABB ABBMCS Catalog No. TS3H150DBBS4 TS3H150DBBS4 TS3H150DBBS4 TS3H225DQQS4 T5H400DWS4
MCS Lug Type K4TB K4TB K4TB K4TD KT5400-3MCS Lug Torque (in-lbs) 50 in-lb* 50 in-lb* 50 in-lb* 200 in-lb* 275 in-lb*
Fuse Block Mfr. LITTELFUSE LITTELFUSE LITTELFUSE LITTELFUSE LITTELFUSEFuse Block Catalog No. LFJ60030-3 LFJ60060-3 LFJ60100-3 LFJ60200-3 LFJ60400-3Fuse Lug Torque (in-lbs) 25 in-lb† 45 in-lb† 120 in-lb† 275 in-lb† 275 in-lb†
Neutral Lug Mfr. LITTELFUSE LITTELFUSE LITTELFUSE LITTELFUSE LITTELFUSENeutral Lug Catalog No. LS21211 LS21211 LS21211 LS31231 LS455712
Neutral Lug Torque (in-lbs) 35 in-lb† 45-120 in-lb† 120 in-lb† 275 in-lb† 500 in-lb†
Ground Lug Mfr. PANDUIT PANDUIT PANDUIT PANDUIT PANDUITGround Lug Catalog No. LAMA 1/0-14-Q LAMA 1/0-14-Q LAMA 1/0-14-Q LAMA 250-56-Q LAMA 350-38-Q
Ground Lug Torque 25 in-lb‡ 45 in-lb‡ 120 in-lb‡ 275 in-lb‡ 275 in-lb‡
Note: Torque specs apply only to wire compression screws. Other requirements may exist for attachment of lugs and accessories to these devices. See manufacturer data.
*ABB.com † Littelfuse Device nameplate data. ‡ Panduit, “Torque Chart for Aluminum Mechanical Connectors”.
LPS SERIES POWR-SWITCHShunt Trip Disconnect Switch
Noida
Kaunas
Norwich
Muzquiz
Bellingham
Matamoros
Boston
Bremen
Trollhättan
SaskatoonWinnipeg
Piedras Negras
Seoul Yokohama
SuzhouWuxi Shanghai
TaipeiDongguanShenzhen
Hong Kong
Lipa City
Singapore
São Paulo
Lake MillsRapid CityChicago
Champaign
Swindon
Local Resources for a GLOBAL Market
Littelfuse World Headquarters8755 West Higgins Road, Suite 500Chicago, IL 60631USATel: +1-800-832-3873Fax: +1-847-787-5190E-mail: [email protected]
Littelfuse SymCom222 Disk DriveRapid City, SD 57701USATel: + 1-800-843-8848Fax: + 1-605-348-5685E-mail: [email protected]
Littelfuse Startco3714 Kinnear PlaceSaskatoon, SK S7P 0A6CanadaTel: +1-306-373-5505Fax: +1-306-374-2245E-mail: [email protected]
Littelfuse products are certified to many standards around the world. To check certifications on specific product please refer to the product datasheet on Littelfuse.com.
© 2016 Littelfuse, Inc. Rev: 1-B-052316
To view all Littelfuse product catalogs, visit our website at Littelfuse.com/Catalogs. Go to Littelfuse.com/TechnicalResouces
Specifications, descriptions and illustrative material in this literature are as accurate as known at the time of publication, but are subject to changes without notice. Visit Littelfuse.com for the most up-to-date technical information.
Protection Relays & Controls Catalog (PF130) The comprehensive line of electronic and microprocessor-based protection relays safeguard equipment and personnel to prevent expensive damage, downtime or injury due to electrical faults.
Visit Technical Resources at Littelfuse.com Technical information is only a click away. The Littelfuse Technical Resources contains datasheets, product manauals, whitepapers, application guides, demos, on-line design tools, and more.
Fuses and Fuse Holders Catalog (PF101N) Littelfuse offers a complete circuit protection portfolio of industrial power fuses, including time-saving indication products for an instant visual blown-fuse identification.