Pre-Demolition Hazardous Materials SurveyReport
Contra Costa College DistrictHealth and Science Building2600 Mission Bell DriveSan Pablo, California
Project No: R1167C66
July 25, 2017
Prepared for:
Contra Costa Community College District500 Court StreetMartinez, CA 94553
Prepared by:
RGA Environmental, Inc.1466 66th StreetEmeryville, CA 94608
Report prepared by: Remington CaldwellSenior Industrial Hygienists, CAC 97-2180
Report reviewed by: Kenneth PilgrimDepartment Manager, CAC 03-3503
TABLE OF CONTENTS
1. EXECUTIVE SUMMARY ..................................................................................................................................... 1
2. SCOPE OF WORK .............................................................................................................................................. 2
3. METHODS AND SAMPLING STRATEGY .............................................................................................................. 2
4. ASBESTOS RESULTS .......................................................................................................................................... 4
5. LEAD RESULTS .................................................................................................................................................. 6
6. PCB RESULTS .................................................................................................................................................... 7
7. CONCLUSIONS AND RECOMMENDATIONS ....................................................................................................... 7
8. REGULATORY REQUIREMENTS ......................................................................................................................... 8
9. LIMITATIONS .................................................................................................................................................. 11
APPENDICES
1. Laboratory Results and Chain of Custody – Asbestos
2. Laboratory Results and Chain of Custody – Lead
3. Laboratory Results and Chain of Custody – PCBs
4. Sample Location Figures
5. Inspector Certifications
Page 1
Pre-Demolition Hazardous Materials SurveyReportContra Costa Community CollegeHealth and Science Building2600 Mission Bell DriveSan Pablo, California
1. Executive Summary
The following is a report of the pre-demolition hazardous materials survey conducted byRemington Caldwell, Certified Asbestos Consultant (CAC) and California Department of PublicHealth (CDPH) Inspector/Assessor and John Alexander, Certified Asbestos Consultant (CAC) andCalifornia Department of Public Health (CDPH) Inspector/Assessor with RGA Environmental, ATerracon Company (RGA). The survey was performed on April 3, 18 and May 9, 2017 at theHealth and Science building located at 2600 Mission Bell Drive, San Pablo, California.
The survey scope included the interior, exterior, and all roof levels of the Health and Sciencebuilding and the attached corridor connecting to the vacant Liberal Arts building.
A total of thirty-four (34) suspected asbestos containing materials (ACMs) were identified andsampled throughout the interior, exterior, and roof of the captioned structure and attachedcorridor connector. Seven (7) of the materials were confirmed to be positive for asbestoscontent upon laboratory analysis. Due to the current occupancy, six (6) suspect materials wereassumed to be asbestos containing.
Three (3) painted surfaces and one (1) window sealant were sampled for potential leadcontent. Three (3) of the painted surfaces were found to contain lead content above thelaboratory detection limit. The window sealant sample was found to contain lead above thelaboratory detection limit. One (1) of the paint samples were found to contain lead inconcentrations exceeding 5,000 parts per million (ppm), the threshold for designation of lead-based paint. Due to the occupancy, four (4) suspect ceramic tiles were observed and assumedto be lead containing.
Three (3) suspect exterior sealants were sampled for potential polychlorinated biphenyl (PCB)content. PCBs were reported in two (2) of the samples.
One (1) roof mounted mechanical unit was observed on the main roof level of building. The unitwas marked as containing R-22 refrigerant, a hydrochlorofluorocarbon (HCFC) basedrefrigerant. One (1) chilled water cooler was identified in the first floor hallway.
Pre-Demolition Hazardous Materials Survey ReportHealth and Science Building2600 Mission Bell DriveSan Pablo, California
Page 2
Mercury containing fluorescent light tubes and compact fluorescent lamp (CFL) bulbs werepresent throughout the interior and exterior of the building. Four (4) high intensity discharge(HID) fixtures were observed on the exterior of the building.
Representative lighting ballasts inspected in the building were labeled as containing “No PCBs”.All ballasts not specifically labeled as “No PCBs” are assumed to contain polychlorinatedbiphenyls (PCBs).
Seven (7) exit signs with backup batteries were confirmed present on the ground and first floor,however, no tritium exits signs were observed. One (1) emergency egress lighting unit withbackup batteries was observed within the structure.
2. Scope of Work
The scope of the survey was as follows:
· Inspect the subject property for the presence of suspect ACMs, lead-containing paint andmaterials, mercury-containing products, PCB lighting ballasts and sealants,chlorofluorocarbon (CFC) or hydrochlorofluorocarbon (HCFC) containing equipment, tritiumexit signs, and universal wastes.
· Collect samples of suspect ACMs following a National Emissions Standards for Hazardous AirPollutants (NESHAPS) protocol for sample collection for a demolition survey.
· Asbestos bulk samples will be analyzed using polarized light microscopy (PLM) inaccordance with the EPA’s July 1993 method for the determination of asbestos in bulkbuilding materials - EPA 600/R-93/116.
· Collect bulk paint chip samples of primary painted surfaces and other materials suspectedto be lead containing. Bulk samples will be analyzed at an accredited laboratory by FlameAtomic Absorption (AA) for Total Lead reported in parts per million (ppm).
· Collect bulk samples of suspect PCB containing sealants on exterior of buildings if present.PCB samples will be analyzed by analytical method SW8082.
· Submit written report including analytical results, regulatory requirements, and conclusions.
3. Methods and Sampling Strategy
Visual Inspection
Accessible building materials on the interior and exterior of the structure were visuallyinspected using the methods presented in the federal Asbestos Hazard Emergency ResponseAct (AHERA) regulations (40 CFR, Part 763) as a guideline. AHERA was originally only applicableto schools, however State and Federal Occupational Safety and Health Administration (OSHA)and Asbestos School Hazard Abatement Reauthorization Act (ASHARA) have adopted theAHERA sampling methodology for all buildings subject to demolition or renovation.
Pre-Demolition Hazardous Materials Survey ReportHealth and Science Building2600 Mission Bell DriveSan Pablo, California
Page 3
Visual Inspection for Mercury Containing Materials
Approximately two hundred and eighty (280) fluorescent light tubes (mercury containing) wereidentified in the building. Approximately Ten (10) CFLs and (4) HID bulbs were noted on theinterior and exterior of the building. All of the light tubes, HID, and CFL bulbs should beremoved without breakage prior to removal of fixtures and managed as a universal waste.
Visual Inspection for PCB-containing Equipment and Materials
Approximately one hundred and sixty-five (165) fluorescent light ballasts were identified on theinterior of the structure. Ballasts observed were labeled as “No PCBs”. All ballasts should beinspected prior to disposal to verify the presence/absence of PCBs. Ballasts should be assumedto be PCB-containing unless specified by the manufacturer’s label as containing “No PCBs”.
Visual Inspection for Tritium-containing Exit Signs
Seven (7) exit signs with backup batteries were identified on the ground and first floor levels.Exit sign were lit with either incandescent or LED bulbs. No tritium-containing exits signs wereobserved within the building.
Visual Inspection for CFC Containing Equipment
One roof-top mechanical system was observed on the main roof level. The refrigerant type wasconfirmed as R-22 on the identification labels on the exterior of the unit. The R-22, an HCFCrefrigerant, should be captured from the unit prior to disposal or disconnecting close-looppressurized lines. A chilled water cooler was observed in the first floor hallway. The refrigeranttype could not be determined. No testing was performed.
Bulk Sampling of Asbestos
Bulk samples were collected of homogeneous suspect ACMs from the on the subject building. Ahomogeneous material is defined as a surfacing material, thermal system insulation, ormiscellaneous material that is uniform in color, size, texture and age of construction. Examplesof homogeneous materials include:
· Resilient flooring of identical color and pattern;· Troweled on surfacing materials located in contiguous areas;· Acoustical ceiling material produced by the same manufacturer and installed during the
same time period.
The building was visually inspected for the presence of suspect materials. As materials wereidentified, bulk samples were obtained with the aid of a coring device or other hand tool andplaced into individual sampling bags. Each sample was given a discreet identification numberand recorded on field notes as well as chain-of-custody forms. Refer to accompanying tablesand appendices for details on material sample locations and results.
Pre-Demolition Hazardous Materials Survey ReportHealth and Science Building2600 Mission Bell DriveSan Pablo, California
Page 4
Bulk Sample Analysis - Asbestos
Bulk samples were analyzed by EMLab P&K (EML) in Henderson, Nevada and Arvado, Colorado.EML is accredited under the National Institute of Standards and Technology's NationalVoluntary Laboratory Accreditation Program (NVLAP).
When None Detected (ND) appears in this report, it should be interpreted as meaning noasbestos was observed in the sample material above the reliable limit of detection for the PLMmethod.
Note: Under EPA assessment criteria, if a single sample of a homogeneous material testspositive for asbestos, all areas of that homogeneous material are considered to be asbestoscontaining.
Bulk Sampling of Lead Paint and Suspect Bulk Materials
Paint chip and bulk samples were collected using a hand scraper or chisel and were placed intoindividual plastic sampling containers. Each sample was provided a discreet sample number,which was recorded on a chain-of-custody form. The samples were transported underchain-of-custody procedures to QuanTEM Laboratories (QuanTEM) in Oklahoma City,Oklahoma. Please refer to Table III for details on sample locations and sample results. Allsamples were analyzed for lead content in accordance to EPA Method 7000B.
4. Asbestos Results
During the survey, a total of thirty-four (34) suspected asbestos containing materials (ACMs)were identified. Seven (7) materials were confirmed positive for asbestos content uponlaboratory analysis. Six (6) suspect asbestos-containing material were assumed to containasbestos. The confirmed and assumed asbestos containing materials are listed in Table I below.
TABLE IASBESTOS-CONTAINING MATERIALS
HM# - MaterialDescription Material Location Waste
Category Asbestos Type EstimatedQuantity
01 – Drywall and JointCompound – Smooth Finish Ground Floor and 1st Floor RACM Drywall: ND
Compounds: <1%-2% CH 18,000 sf
02 – Cove Base Mastic 1st Floor, Throughout Cat. II Cove base: NDGlue: 2% CH
600 lf or200 sf
03 – Joint Compound underWallpaper
1st Floor-Auditorium/Lecture HallWalls
RACMCompound:
<1% CH, Assumed: >1%CH
See HM 01
07 – Drywall and JointCompound
1st Floor-Janitor Room andRestrooms RACM Drywall: ND
Joint<1%-2% CH 3000 sf
18 – Vinyl Floor Tile andBlack Mastic
Ground Floor – NurseStation Cat. II 12” White VFT: ND
Black Mastic: 10% CH 200 sf
20 – Base Cove Mastic Ground Floor – ThroughoutBuilding Cat. II Cove Base: ND
Brown Mastic: 2% CH400 lf or
150 sf
Pre-Demolition Hazardous Materials Survey ReportHealth and Science Building2600 Mission Bell DriveSan Pablo, California
Page 5
HM# - MaterialDescription Material Location Waste
Category Asbestos Type EstimatedQuantity
25 – 2” Blue Ceramic Tile-Grout and Mortar
1st Floor – Men’s RestroomFloor Cat. II Assumed 200 sf
26 – 2” Brown Ceramic Tile –Grout and Mortar
1st Floor – Women’sRestroom Floor Cat. II Assumed 200 sf
27 – 3”x4” Tan Wainscot Tile– Grout and Mortar
1st Floor – Women’sRestroom Cat. II Assumed 400 sf
28 – 3”x4” Yellow WainscotTile – Grout and Mortar 1st Floor – Men’s Restroom Cat. II Assumed 10 sf
29 – Exterior Stucco 1st Floor – Exterior NA 0.1 – 0.3% CH 8,000 sf
Mechanical Flange Gaskets Above ceilings Cat. I Assumed 20 gaskets
9” Vinyl Floor Tile, Grey andMastic, Black
Ground Floor –CorridorConnecting to Liberal ArtsBuilding
Cat. II VFT: AssumedBlack Mastic: Assumed 450 sf
NA = Not Applicable, ND = None Detected, CH = Chrysotile, CR = Crocidolite, RACM = Regulated asbestos containing material (friable), Cat. I =Non-friable (note ACM must be reclassified as a RACM if rendered friable during removal), Cat. II = Category II Non-friable (note ACM must bereclassified as a RACM if rendered friable during removal), sf = square feet, lf = linear feet
Twenty-one (21) suspect materials were sampled, but were not reported to contain asbestos.The non-asbestos containing materials are listed in Table II below.
TABLE IINON-ASBESTOS CONTAINING MATERIALS
HM# - Material Description Material Location(s)
4 – Drywall Texture 1st Floor
5 – Carpet Glue, Blue and Residual Tan 1st Floor, Lecture Hall
8 – 4” Fiberglass TSI with Aluminum Covering 1st Floor, Janitors Closet
9 – 12” White Vinyl Floor Tile with Yellow Glue 1st Floor, 1st Floor, Throughout
10 – 12” White Vinyl Floor Tile w/ Black Mastic 1st Floor, Nurse Service Room
11 – Carpet Glue, Yellow 1st Floor, Nurse Lab
12 – Duct Insulation White Tape on Metal Duct
13 – 2’x4’ White Ceiling Tile with Small Holes and PinHoles 1st Floor, Classroom and Storage Area.
14 – Residual Black Mastic under Wood Subfloor 1st Floor, Classroom, Storage
15 – White Sink Insulation 1st Floor, Nursing Office
16 – 2’x2’ White Ceiling Tile 1st Floor, Throughout Floor
Pre-Demolition Hazardous Materials Survey ReportHealth and Science Building2600 Mission Bell DriveSan Pablo, California
Page 6
HM# - Material Description Material Location(s)17 – 12” White Vinyl Floor Tile w/Brown Smudge andYellow Glue Ground Floor, Hallway
19 – 12” White Vinyl Floor Tile w/Blue Smudge andYellow Glue Ground Floor, Room HS3
21 – Tar and Gravel w/ Felt Paper Main Roof, Main Roof Field
22 – Rolled Shingle (Flashing) Main Roof, Flashing
23 – Parapet Wall, Rolled Shingle Main Roof, Parapet Wall
24 – Patch, Grey and Black Main Roof, Roof Patch
83 – Brick Mortar Throughout Exterior
84 – White Window Sealant Throughout Exterior Window Frames
85 – Black Felt Liberal Arts Building-This samples will not be in theHealth Science Report
87 – White Elastomeric Coating Roof Sealant on Corridor Connector for HealthScience/Liberal Arts Buildings
5. Lead Results
Three (3) painted surfaces and one (1) window sealant sample were sampled for potential leadcontent. All of the painted surfaces were found to contain lead content above the laboratorydetection limit. One of the paint samples was found to contain a lead in concentrationexceeding 5,000 parts per million (ppm), the threshold for designation of lead-based paint. Four(4) suspect lead-containing ceramic floor and wall tiles were assumed to contain lead.
The laboratory results for lead testing are summarized in Table III below.
TABLE IIILEAD IN PAINT SAMPLE RESULTS
SampleNumber Material Description and Location Results mg/kg
(ppm)
Pb – 1 Beige Paint on Wallpaper in Lecture Hall 7,970
Pb – 2 White Paint on Drywall, Throughout Interior of Building 2,120
Pb – 12 Off-White Sealant between Metal Window Frame and Brick 50.2
Pb – 13 Brown Paint on Metal Louver 1,370
- 2” Blue Ceramic Tile-Grout and Mortar, Men’s Restroom Assumed
Pre-Demolition Hazardous Materials Survey ReportHealth and Science Building2600 Mission Bell DriveSan Pablo, California
Page 7
SampleNumber Material Description and Location Results mg/kg
(ppm)
- 2” Brown Ceramic Tile – Grout and Mortar, Women’s Restroom Assumed
- 3” x 4” Tan Wainscot Tile – Grout and Mortar, Women’s Restroom Assumed
- 3” x 4” Yellow Wainscot Tile – Grout and Mortar, Men’s Restroom Assumed
mg/kg= Milligram per kilogram, ppm = parts per million
6. PCB Results
Three (3) bulk samples of exterior sealants was collected from the building to determine thepotential presence of PCBs. Two of the samples was reported to contain PCBs. All of thematerials were reported less than 50 ppm PCB, the threshold for a contaminated PCBcontaining material. The laboratory results for the PCB bulk sampling are summarized in TableIV below.
TABLE IVPCB SAMPLE RESULTS
Sample Number Material Description & Location Results (ppm)
PCB-01 Door Frame Sealant, White – 1st floor Entry ND<0.50
PCB-3 Window Sealant – West Wall of Courtyard 1.9
PCB-4 Door Sealant - South Wall of Connector 1.1
Mg/kg= Milligram per kilogram, ppm = parts per million, ND< = None Detected above analytical limit
7. Conclusions and Recommendations
Based upon the survey results, RGA concludes the following:
· Asbestos was detected in various materials including floor tile mastics, cove basemastics, drywall finishing compounds, and exterior stucco. The grout/mastics associatedwith the ceramic tiles in the restrooms, mechanical pipe valve flange gaskets, and 9”grey vinyl floor tile and associated mastics are assumed to contain asbestos.
· If additional suspect materials that have not been characterized as ACM or non-ACM inthis report are discovered during demolition, these materials should be assumed to
Pre-Demolition Hazardous Materials Survey ReportHealth and Science Building2600 Mission Bell DriveSan Pablo, California
Page 8
contain asbestos and be treated accordingly until proven otherwise by appropriatesampling and laboratory analysis.
· Lead was detected above the laboratory detection limit in the painted surfaces tested.One (1) of the painted surfaces was found to contain lead in concentrations exceeding5,000 parts per million the threshold for lead based paint. Four (4) ceramic tile sampleswere assumed to be lead containing.
· Mercury-containing fluorescent-light tubes, HID bulbs, and CFL bulbs and wereidentified throughout the survey area. Mercury-containing tubes and bulbs should beremoved from the fixtures or equipment without breakage and packaged for mercuryreclamation as a universal waste through an appropriate vendor prior to removal of anyfixtures.
· Suspect PCB-containing ballasts associated with the fluorescent lights were observedthroughout the structures. Each ballast label should be inspected for the phrase “NoPCBs” prior to disposal. Ballasts not labeled as such should be assumed to contain PCBs.PCB ballasts should be removed from fixtures and disposed of as PCB-containingmaterials prior to disposal of the fixtures.
· One roof-top HVAC system was confirmed to contain R-22 refrigerant. One (1) chilledwater-fountain was observed in the 1st floor corridor. The refrigerant type for the water-fountain could not be confirmed.
8. Regulatory Requirements
AsbestosImpacting materials containing greater than 0.1% asbestos either through repair,maintenance, or demolition activities triggers numerous regulations enforced by suchagencies as OSHA (worker protection) and EPA (environmental exposure, transportationand disposal).
Listed below are the regulations that apply if the materials are removed:
· Any individual who contracts to provide health and safety services relating to ACMsmust be certified by Cal-OSHA as either a Certified Asbestos Consultant or a SiteSurveillance Technician. The activities they are certified to provide include: conductingasbestos surveys; writing work plans or specifications for abatement; monitoring thework of abatement contractors; collecting air samples; and determining if the work areais safe for re-occupancy by non-asbestos workers. Regulation: Cal-OSHA 8 CCR 1529(q)(1).
· If more than 100 square feet of materials that contain greater than 0.1% asbestos willbe abated, the materials must be abated by a Cal-OSHA registered asbestos abatement
Pre-Demolition Hazardous Materials Survey ReportHealth and Science Building2600 Mission Bell DriveSan Pablo, California
Page 9
contractor. Regulation: Cal-OSHA 8 CCR 1529 (R).
· ACMs that are classified by OSHA as other/miscellaneous materials are present.Removal of these materials is considered a Class II activity according to Cal-OSHAregulations. Work practices and engineering controls for Class II work are specified inCal-OSHA 8 CCR 1529 (g) (7-8).
· Removal of friable ACMs greater than 100 square feet or 100 linear feet requiresnotification of the Bay Area Air Quality Management District ten (10) working days inadvance of intended removal.
· Friable ACMs greater than 1% asbestos must be manifested, transported, and disposedof as hazardous waste in accordance with the Department of Toxic and SubstancesControl (DTSC), a division of Cal-EPA. DTSC regulates disposal of asbestos waste. DTSCissues U.S. EPA hazardous waste generator identification numbers.
Lead
Impacting lead materials or lead-containing paint either through repair, maintenance,renovation or demolition activities triggers numerous regulations enforced by suchagencies as OSHA (worker protection), EPA (environmental exposure, transportation anddisposal), and Department of Public Health (DPH).
Listed below are the lead regulations that apply:
· There are presently no federal, state or local regulations limiting the concentration oflead in public sector buildings, however several regulations established for the privatesector as well as for government subsidized housing are used industry wide asguidelines for assessing exposure to lead. The Consumer Product Safety Commission(CPSC) has set a maximum limit of 90 ppm in paint used for residential purposes. TheDepartment of Housing and Urban Development (HUD) requires abatement of leadhazards involving paint in concentrations exceeding 5,000 ppm.
· Proper waste stream categorization is required for the disposal of all lead containingmaterials and painted construction debris with total lead content that exceeds 50 ppm.The debris should be classified as hazardous waste if lead waste concentrations exceedeither the total lead concentration or soluble lead concentration regulatory limits. Totallead concentration is determined by Total Threshold Limit Concentration (TTLC). Solubleor leachable lead is determined by the Soluble Threshold Limit Concentration (STLC,California required test) and/or Toxicity Characteristic Leaching Procedure (TCLP)(Federal EPA required test). Regulatory limits characterize a lead waste as a hazardouswaste if lead concentrations exceed 1,000 ppm by TTLC or 5 milligrams per liter by STLCor TCLP.
Pre-Demolition Hazardous Materials Survey ReportHealth and Science Building2600 Mission Bell DriveSan Pablo, California
Page 10
· Federal OSHA as well as California OSHA regulates all worker exposure duringconstruction activities that impact lead-containing paint. California OSHA enforces theLead in Construction Standard in Title 8 CCR 1532.1. The scope covers construction workwhere employees may be exposed to lead during such activities as demolition, removal,surface preparation for re-painting, renovation, clean-up and routine maintenance. TheOSHA specified method of compliance includes respiratory protection, protectiveclothing and equipment, housekeeping, hygiene facilities, medical surveillance, andtraining, among other requirements.
PCBsPCBs are regulated by the EPA under 40 CFR 761. The production of PCBs has been bannedsince 1979 and may be present in electrical capacitors, sealants, hydraulic oils, andtransformers commonly found in buildings. Materials with greater than 50 ppm PCB contentare considered PCB contaminated waste while materials with greater than 500 ppm PCB areconsidered PCB containing.
PCB containing equipment and/or contaminated materials must be removed and disposedproperly prior to demolition of a building. PCB containing lighting ballasts may be present insome lighting fixtures and must be verified by labeling. All PCB containing materials must beremoved and disposed prior to building demolition.
Universal Waste and Other Potential Hazardous MaterialsUniversal waste are common wastes with hazardous properties that must be managed andhave landfill disposal restrictions. Example of universal waste include electronic devices,batteries, and mercury containing equipment or lighting. Handling, transportation, anddisposal is simplified under the universal waste regulation in the California Code ofRegulations Title 22, Division 4.5 Chapter 11.
All materials in the buildings meeting the definition of the universal waste must beremoved prior to demolition and handled, transported and disposed through anappropriate vendor.
RefrigerantsThe use, management, and release of ozone depleting substances used as refrigerants areregulated under the Clean Air Act (CAA) of 1990. Section 608 of the CAA forbids the ventingof regulated refrigerants such as CFC, HCFC, blended refrigerants. All regulated refrigerantsassociated with the buildings and equipment must be recovered prior to severingpressurized systems or disposal of equipment.
Pre-Demolition Hazardous Materials Survey ReportHealth and Science Building2600 Mission Bell DriveSan Pablo, California
Page 11
9. Limitations
RGA warrants that the findings contained herein have been prepared in general accordancewith accepted professional practices as applied by similar professionals in the community at thetime of its preparation. Changes in the state of the art or in applicable regulations cannot beanticipated and have not been addressed in this report.
Although every effort was made to access building materials throughout the building, in theevent that additional materials not listed in this report are uncovered during demolition, thesematerials should be assumed hazardous and may contain asbestos until suitably provenotherwise.
The field and laboratory results reported herein are considered sufficient in detail and scope todetermine the presence of ACMs, lead containing materials, PCB sealants, mercury lightingequipment, and PCBs ballasts identified in this report. Also, note that this is a survey report andnot an abatement specification. This document is not appropriate for competitive bidding orfor use as an asbestos or lead abatement specification.
Appendix 1
Laboratory Results and Chain of Custody - Asbestos
Approved by:
Approved SignatoryDr. Kamashwaran Ramanathan
Report for:
Mr. Kenneth PilgrimRGA Environmental, Inc.1466 66th StreetEmeryville, CA 94608
Regarding: Project: R1167C66; CCCD-LA&H.S. PreDemo-2600 Mission Bell, S. Pablo, CA.EML ID: 1706603
All samples were received in acceptable condition unless noted in the Report Comments portion in the body of the report. The results relate only to the items tested. The results include an inherent uncertainty of measurement associated with estimating percentages by polarized light microscopy. Measurement uncertainty data for sample results with >1% asbestos concentration can be provided when requested.
EMLab P&K ("the Company") shall have no liability to the client or the client's customer with respect to decisions or recommendations made, actions taken or courses of conduct implemented by either the client or the client's customer as a result of or based upon the Test Results. In no event shall the Company be liable to the client with respect to the Test Results except for the Company's own willful misconduct or gross negligence nor shall the Company be liable for incidental or consequential damages or lost profits or revenues to the fullest extent such liability may be disclaimed by law, even if the Company has been advised of the possibility of such damages, lost profits or lost revenues. In no event shall the Company's liability with respect to the Test Results exceed the amount paid to the Company by the client therefor.
Dates of Analysis:Asbestos PLM: 04-10-2017
Service SOPs: Asbestos PLM (EPA Methods 600/R-93/116 & 600/M4-82-020, SOP EM-AS-S-1267)
EMLab ID: 1706603, Page 1 of 22EMLab P&K, LLC
EMLab P&K6100 Mountain Vista St, Ste #160, Henderson, NV 89014
(866) 888-6653 Fax (623) 780-7695 www.emlab.comClient: RGA Environmental, Inc.C/O: Mr. Kenneth PilgrimRe: R1167C66; CCCD-LA&H.S. PreDemo-2600 Mission Bell, S. Pablo, CA.
Date of Sampling: 04-03-2017Date of Receipt: 04-06-2017Date of Report: 04-10-2017
ASBESTOS PLM REPORT: EPA-600/M4-82-020 & EPA METHOD 600/R-93-116Total Samples Submitted: 77Total Samples Analyzed: 77
Total Samples with Layer Asbestos Content > 1%: 12
Location: 1A, Drywall/joint compound-rough-over wallpaper-1st-Nurse lab-SW corner-perimeter wall Lab ID-Version‡: 7956157-1
Sample Layers Asbestos ContentWhite Drywall with Brown Paper ND
Joint Compound < 1% ChrysotileCream Tape ND
White Texture with Paint < 1% ChrysotileComposite Asbestos Fibrous Content: < 1% Asbestos
Composite Non-Asbestos Content: 15% CelluloseSample Composite Homogeneity: Poor
Comments: Composite asbestos content provided is only for Drywall/Joint compound. Composite content provided does not follow the guidelines set forth by NVLAP. This analysis was performed by following the NESHAP guidelines.
Location: 1B, Drywall/joint compound-rough-over wallpaper-1st-storage/Equip room for Nurse lab Lab ID-Version‡: 7956158-1
Sample Layers Asbestos ContentWhite Drywall with Brown Paper ND
Joint Compound < 1% ChrysotileCream Tape ND
White Texture with Paint NDComposite Asbestos Fibrous Content: < 1% Asbestos
Composite Non-Asbestos Content: 15% CelluloseSample Composite Homogeneity: Poor
Comments: Composite asbestos content provided is only for Drywall/Joint compound. Composite content provided does not follow the guidelines set forth by NVLAP. This analysis was performed by following the NESHAP guidelines.
EMLab ID: 1706603, Page 2 of 22EMLab P&K, LLC
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. EMLab P&K reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is reflected by the value of "x".
EMLab P&K6100 Mountain Vista St, Ste #160, Henderson, NV 89014
(866) 888-6653 Fax (623) 780-7695 www.emlab.comClient: RGA Environmental, Inc.C/O: Mr. Kenneth PilgrimRe: R1167C66; CCCD-LA&H.S. PreDemo-2600 Mission Bell, S. Pablo, CA.
Date of Sampling: 04-03-2017Date of Receipt: 04-06-2017Date of Report: 04-10-2017
ASBESTOS PLM REPORT: EPA-600/M4-82-020 & EPA METHOD 600/R-93-116Location: 1C, Drywall/joint compound-rough-over wallpaper-ground-H53-smooth Lab ID-Version‡: 7956159-1
Sample Layers Asbestos ContentWhite Drywall with Brown Paper ND
Joint Compound 2% ChrysotileCream Tape ND
White Texture with Paint 2% ChrysotileComposite Asbestos Fibrous Content: < 1% Asbestos
Composite Non-Asbestos Content: 15% CelluloseSample Composite Homogeneity: Poor
Comments: Composite asbestos content provided is only for Drywall/Joint compound. Composite content provided does not follow the guidelines set forth by NVLAP. This analysis was performed by following the NESHAP guidelines.
Location: 2A, 4" black covebase-white and brown glue-1st-lecture hall-east wall Lab ID-Version‡: 7956160-1
Sample Layers Asbestos ContentBlack Baseboard ND
Brown Mastic 2% ChrysotileSample Composite Homogeneity: Moderate
Location: 2B, 4" black covebase-white and brown glue-foyer-west wall Lab ID-Version‡: 7956161-1
Sample Layers Asbestos ContentBlack Baseboard ND
Brown Mastic 2% ChrysotileSample Composite Homogeneity: Moderate
EMLab ID: 1706603, Page 3 of 22EMLab P&K, LLC
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. EMLab P&K reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is reflected by the value of "x".
EMLab P&K6100 Mountain Vista St, Ste #160, Henderson, NV 89014
(866) 888-6653 Fax (623) 780-7695 www.emlab.comClient: RGA Environmental, Inc.C/O: Mr. Kenneth PilgrimRe: R1167C66; CCCD-LA&H.S. PreDemo-2600 Mission Bell, S. Pablo, CA.
Date of Sampling: 04-03-2017Date of Receipt: 04-06-2017Date of Report: 04-10-2017
ASBESTOS PLM REPORT: EPA-600/M4-82-020 & EPA METHOD 600/R-93-116Location: 2C, 4" black covebase-white and brown glue-Nurse station Lab ID-Version‡: 7956162-1
Sample Layers Asbestos ContentBlack Baseboard ND
Brown Mastic 2% ChrysotileSample Composite Homogeneity: Moderate
Location: 3A, Wallpaper glue-white-1st Lecture hall-N.W. Lab ID-Version‡: 7956163-1
Sample Layers Asbestos ContentTan Wallpaper with Texture < 1% Chrysotile
Sample Composite Homogeneity: Moderate
Location: 3B, Wallpaper glue-white-1st Lecture hall-N.E. Lab ID-Version‡: 7956164-1
Sample Layers Asbestos ContentTan Wallpaper with Texture < 1% Chrysotile
Sample Composite Homogeneity: Moderate
Location: 3C, Wallpaper glue-white-1st Lecture hall-S.E. Lab ID-Version‡: 7956165-1
Sample Layers Asbestos ContentTan Wallpaper with Texture < 1% Chrysotile
Sample Composite Homogeneity: Moderate
EMLab ID: 1706603, Page 4 of 22EMLab P&K, LLC
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. EMLab P&K reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is reflected by the value of "x".
EMLab P&K6100 Mountain Vista St, Ste #160, Henderson, NV 89014
(866) 888-6653 Fax (623) 780-7695 www.emlab.comClient: RGA Environmental, Inc.C/O: Mr. Kenneth PilgrimRe: R1167C66; CCCD-LA&H.S. PreDemo-2600 Mission Bell, S. Pablo, CA.
Date of Sampling: 04-03-2017Date of Receipt: 04-06-2017Date of Report: 04-10-2017
ASBESTOS PLM REPORT: EPA-600/M4-82-020 & EPA METHOD 600/R-93-116Location: 4A, Drywall texture-1st corridor Lab ID-Version‡: 7956166-1
Sample Layers Asbestos ContentWhite Texture with Paint ND
Sample Composite Homogeneity: Moderate
Location: 4B, Drywall texture-1st-audio visual lab Lab ID-Version‡: 7956167-1
Sample Layers Asbestos ContentWhite Texture with Paint ND
Sample Composite Homogeneity: Moderate
Location: 4C, Drywall texture-1st-Nurse lab SE corner perimeter Lab ID-Version‡: 7956168-1
Sample Layers Asbestos ContentWhite Texture with Paint ND
Sample Composite Homogeneity: Moderate
Location: 4D, Drywall texture-1st-storage/Equip room Lab ID-Version‡: 7956169-1
Sample Layers Asbestos ContentWhite Texture with Paint ND
Sample Composite Homogeneity: Moderate
EMLab ID: 1706603, Page 5 of 22EMLab P&K, LLC
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. EMLab P&K reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is reflected by the value of "x".
EMLab P&K6100 Mountain Vista St, Ste #160, Henderson, NV 89014
(866) 888-6653 Fax (623) 780-7695 www.emlab.comClient: RGA Environmental, Inc.C/O: Mr. Kenneth PilgrimRe: R1167C66; CCCD-LA&H.S. PreDemo-2600 Mission Bell, S. Pablo, CA.
Date of Sampling: 04-03-2017Date of Receipt: 04-06-2017Date of Report: 04-10-2017
ASBESTOS PLM REPORT: EPA-600/M4-82-020 & EPA METHOD 600/R-93-116Location: 4E, Drywall texture-1st-hallway to exam room Lab ID-Version‡: 7956170-1
Sample Layers Asbestos ContentWhite Texture with Paint ND
Sample Composite Homogeneity: Moderate
Location: 4F, Drywall texture-1st-entry Lab ID-Version‡: 7956171-1
Sample Layers Asbestos ContentWhite Texture with Paint ND
Sample Composite Homogeneity: Moderate
Location: 4G, Drywall texture-1st-storage/Equip. room Lab ID-Version‡: 7956172-1
Sample Layers Asbestos ContentWhite Texture with Paint ND
Sample Composite Homogeneity: Moderate
Location: 5A, Carpet glue-blue with tan residue-1st-lecture hall-front-at exit door north east Lab ID-Version‡: 7956173-1
Sample Layers Asbestos ContentYellow Mastic ND
Sample Composite Homogeneity: Good
EMLab ID: 1706603, Page 6 of 22EMLab P&K, LLC
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. EMLab P&K reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is reflected by the value of "x".
EMLab P&K6100 Mountain Vista St, Ste #160, Henderson, NV 89014
(866) 888-6653 Fax (623) 780-7695 www.emlab.comClient: RGA Environmental, Inc.C/O: Mr. Kenneth PilgrimRe: R1167C66; CCCD-LA&H.S. PreDemo-2600 Mission Bell, S. Pablo, CA.
Date of Sampling: 04-03-2017Date of Receipt: 04-06-2017Date of Report: 04-10-2017
ASBESTOS PLM REPORT: EPA-600/M4-82-020 & EPA METHOD 600/R-93-116Location: 5B, Carpet glue-blue with tan residue-1st-lecture hall-back-at exit door north west Lab ID-Version‡: 7956174-1
Sample Layers Asbestos ContentYellow Mastic ND
Sample Composite Homogeneity: Good
Location: 5C, Carpet glue-blue with tan residue-1st-lecture hall-front-at exit door south west Lab ID-Version‡: 7956175-1
Sample Layers Asbestos ContentYellow Mastic ND
Sample Composite Homogeneity: Good
Location: 1D, Drywall/joint compound-smooth-under wallpaper-1st-lecture hall Lab ID-Version‡: 7956176-1
Sample Layers Asbestos ContentWhite Drywall with Brown Paper ND
Joint Compound NDCream Tape ND
White Texture with Paint < 1% ChrysotileComposite Non-Asbestos Content: 15% CelluloseSample Composite Homogeneity: Poor
Location: 1E, Drywall/joint compound-smooth-under wallpaper-ground-hallway to L.A.Lab ID-Version‡: 7956177-1
Sample Layers Asbestos ContentWhite Drywall with Brown Paper ND
Joint Compound NDCream Tape ND
White Texture with Paint NDComposite Non-Asbestos Content: 15% CelluloseSample Composite Homogeneity: Poor
EMLab ID: 1706603, Page 7 of 22EMLab P&K, LLC
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. EMLab P&K reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is reflected by the value of "x".
EMLab P&K6100 Mountain Vista St, Ste #160, Henderson, NV 89014
(866) 888-6653 Fax (623) 780-7695 www.emlab.comClient: RGA Environmental, Inc.C/O: Mr. Kenneth PilgrimRe: R1167C66; CCCD-LA&H.S. PreDemo-2600 Mission Bell, S. Pablo, CA.
Date of Sampling: 04-03-2017Date of Receipt: 04-06-2017Date of Report: 04-10-2017
ASBESTOS PLM REPORT: EPA-600/M4-82-020 & EPA METHOD 600/R-93-116Location: 1F, Drywall/joint compound-smooth-under wallpaper-hallway/main corridor to RR and lecture Lab ID-Version‡: 7956178-1
Sample Layers Asbestos ContentWhite Drywall with Brown Paper ND
Joint Compound NDCream Tape ND
White Texture with Paint NDComposite Non-Asbestos Content: 15% CelluloseSample Composite Homogeneity: Poor
Location: 7A, Drywall-grey-with joint compound-cmooth-janitor closet walls-N.W. wallsLab ID-Version‡: 7956179-1
Sample Layers Asbestos ContentWhite Drywall with Brown Paper ND
Joint Compound < 1% ChrysotileCream Tape ND
Joint Compound < 1% ChrysotileCream Tape ND
White Texture with Paint NDComposite Asbestos Fibrous Content: < 1% Asbestos
Composite Non-Asbestos Content: 15% CelluloseSample Composite Homogeneity: Poor
Comments: Composite asbestos content provided is only for Drywall/Joint compound. Composite content provided does not follow the guidelines set forth by NVLAP. This analysis was performed by following the NESHAP guidelines.
Location: 7B, Drywall-grey-with joint compound-cmooth-janitor closet walls-S.E. wallsLab ID-Version‡: 7956180-1
Sample Layers Asbestos ContentWhite Drywall with Brown Paper ND
White Texture with Paint 2% ChrysotileComposite Non-Asbestos Content: 10% CelluloseSample Composite Homogeneity: Poor
EMLab ID: 1706603, Page 8 of 22EMLab P&K, LLC
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. EMLab P&K reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is reflected by the value of "x".
EMLab P&K6100 Mountain Vista St, Ste #160, Henderson, NV 89014
(866) 888-6653 Fax (623) 780-7695 www.emlab.comClient: RGA Environmental, Inc.C/O: Mr. Kenneth PilgrimRe: R1167C66; CCCD-LA&H.S. PreDemo-2600 Mission Bell, S. Pablo, CA.
Date of Sampling: 04-03-2017Date of Receipt: 04-06-2017Date of Report: 04-10-2017
ASBESTOS PLM REPORT: EPA-600/M4-82-020 & EPA METHOD 600/R-93-116Location: 7C, Drywall-grey-with joint compound-cmooth-janitor closet walls-west walls
Lab ID-Version‡: 7956181-1
Sample Layers Asbestos ContentWhite Drywall with Brown Paper ND
Joint Compound NDCream Tape ND
White Texture with Paint 2% ChrysotileComposite Non-Asbestos Content: 15% CelluloseSample Composite Homogeneity: Poor
EMLab ID: 1706603, Page 9 of 22EMLab P&K, LLC
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. EMLab P&K reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is reflected by the value of "x".
EMLab P&K6100 Mountain Vista St, Ste #160, Henderson, NV 89014
(866) 888-6653 Fax (623) 780-7695 www.emlab.comClient: RGA Environmental, Inc.C/O: Mr. Kenneth PilgrimRe: R1167C66; CCCD-LA&H.S. PreDemo-2600 Mission Bell, S. Pablo, CA.
Date of Sampling: 04-03-2017Date of Receipt: 04-06-2017Date of Report: 04-10-2017
ASBESTOS PLM REPORT: EPA-600/M4-82-020 & EPA METHOD 600/R-93-116Location: 8A, 4" fiberglass and SF with aluminium paper wrap-1st-janitors closet Lab ID-Version‡: 7956182-1
Sample Layers Asbestos ContentCream Wrap ND
Yellow Insulation NDComposite Non-Asbestos Content: 80% Glass FibersSample Composite Homogeneity: Moderate
Location: 8B, 4" fiberglass and SF with aluminium paper wrap-1st-janitors closet Lab ID-Version‡: 7956183-1
Sample Layers Asbestos ContentCream Wrap ND
Yellow Insulation NDComposite Non-Asbestos Content: 80% Glass FibersSample Composite Homogeneity: Moderate
Location: 8C, 4" fiberglass and SF with aluminium paper wrap-1st-janitors closet Lab ID-Version‡: 7956184-1
Sample Layers Asbestos ContentCream Wrap ND
Yellow Insulation NDComposite Non-Asbestos Content: 80% Glass FibersSample Composite Homogeneity: Moderate
Location: 9A, 12" white vinyl floor tile and yellow glue-1st-hall Lab ID-Version‡: 7956185-1
Sample Layers Asbestos ContentGray Floor Tile NDYellow Mastic ND
Sample Composite Homogeneity: Moderate
EMLab ID: 1706603, Page 10 of 22EMLab P&K, LLC
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. EMLab P&K reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is reflected by the value of "x".
EMLab P&K6100 Mountain Vista St, Ste #160, Henderson, NV 89014
(866) 888-6653 Fax (623) 780-7695 www.emlab.comClient: RGA Environmental, Inc.C/O: Mr. Kenneth PilgrimRe: R1167C66; CCCD-LA&H.S. PreDemo-2600 Mission Bell, S. Pablo, CA.
Date of Sampling: 04-03-2017Date of Receipt: 04-06-2017Date of Report: 04-10-2017
ASBESTOS PLM REPORT: EPA-600/M4-82-020 & EPA METHOD 600/R-93-116Location: 9B, 12" white vinyl floor tile and yellow glue-1st-corridor-storage closet Lab ID-Version‡: 7956186-1
Sample Layers Asbestos ContentGray Floor Tile NDYellow Mastic ND
Sample Composite Homogeneity: Moderate
Location: 9C, 12" white vinyl floor tile and yellow glue-1st-Nurse station Lab ID-Version‡: 7956187-1
Sample Layers Asbestos ContentGray Floor Tile NDYellow Mastic ND
Sample Composite Homogeneity: Moderate
Location: 10A, 12" white VFT and black mastic-1st-lab service Lab ID-Version‡: 7956188-1
Sample Layers Asbestos ContentGray Floor Tile NDBlack Mastic ND
Sample Composite Homogeneity: Moderate
Location: 10B, 12" white VFT and black mastic-1st-lab service Lab ID-Version‡: 7956189-1
Sample Layers Asbestos ContentGray Floor Tile NDBlack Mastic ND
Sample Composite Homogeneity: Moderate
EMLab ID: 1706603, Page 11 of 22EMLab P&K, LLC
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. EMLab P&K reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is reflected by the value of "x".
EMLab P&K6100 Mountain Vista St, Ste #160, Henderson, NV 89014
(866) 888-6653 Fax (623) 780-7695 www.emlab.comClient: RGA Environmental, Inc.C/O: Mr. Kenneth PilgrimRe: R1167C66; CCCD-LA&H.S. PreDemo-2600 Mission Bell, S. Pablo, CA.
Date of Sampling: 04-03-2017Date of Receipt: 04-06-2017Date of Report: 04-10-2017
ASBESTOS PLM REPORT: EPA-600/M4-82-020 & EPA METHOD 600/R-93-116Location: 10C, 12" white VFT and black mastic-1st-audio visual room Lab ID-Version‡: 7956190-1
Sample Layers Asbestos ContentGray Floor Tile NDBlack Mastic ND
Sample Composite Homogeneity: Moderate
Location: 11A, Carpet glue-yellow-1st-Nurse lab Lab ID-Version‡: 7956191-1
Sample Layers Asbestos ContentYellow Carpet Glue ND
Sample Composite Homogeneity: Good
Location: 11B, Carpet glue-yellow-1st-Nurse lab Lab ID-Version‡: 7956192-1
Sample Layers Asbestos ContentYellow Carpet Glue ND
Sample Composite Homogeneity: Good
Location: 11C, Carpet glue-yellow-1st-Nurse lab Lab ID-Version‡: 7956193-1
Sample Layers Asbestos ContentYellow Carpet Glue ND
Sample Composite Homogeneity: Good
EMLab ID: 1706603, Page 12 of 22EMLab P&K, LLC
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. EMLab P&K reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is reflected by the value of "x".
EMLab P&K6100 Mountain Vista St, Ste #160, Henderson, NV 89014
(866) 888-6653 Fax (623) 780-7695 www.emlab.comClient: RGA Environmental, Inc.C/O: Mr. Kenneth PilgrimRe: R1167C66; CCCD-LA&H.S. PreDemo-2600 Mission Bell, S. Pablo, CA.
Date of Sampling: 04-03-2017Date of Receipt: 04-06-2017Date of Report: 04-10-2017
ASBESTOS PLM REPORT: EPA-600/M4-82-020 & EPA METHOD 600/R-93-116Location: 12A, Duct insulation-white tape-on metal-1st-audio visual lab Lab ID-Version‡: 7956194-1
Sample Layers Asbestos ContentYellow Insulation with Paint ND
Composite Non-Asbestos Content: 80% Glass FibersSample Composite Homogeneity: Good
Location: 12B, Duct insulation-white tape-on metal-1st-audio visual lab Lab ID-Version‡: 7956195-1
Sample Layers Asbestos ContentYellow Insulation with Paint ND
Composite Non-Asbestos Content: 80% Glass FibersSample Composite Homogeneity: Good
Location: 12C, Duct insulation-white tape-on metal-1st-lab servicing Lab ID-Version‡: 7956196-1
Sample Layers Asbestos ContentGray Wrap ND
Sample Composite Homogeneity: Good
Location: 13A, 2x4 ceiling tile-white with small hole and pinholds-1st-classroom-staorage-1 room Lab ID-Version‡: 7956197-1
Sample Layers Asbestos ContentGray Ceiling Tile with White Surface ND
Composite Non-Asbestos Content: 90% CelluloseSample Composite Homogeneity: Moderate
EMLab ID: 1706603, Page 13 of 22EMLab P&K, LLC
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. EMLab P&K reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is reflected by the value of "x".
EMLab P&K6100 Mountain Vista St, Ste #160, Henderson, NV 89014
(866) 888-6653 Fax (623) 780-7695 www.emlab.comClient: RGA Environmental, Inc.C/O: Mr. Kenneth PilgrimRe: R1167C66; CCCD-LA&H.S. PreDemo-2600 Mission Bell, S. Pablo, CA.
Date of Sampling: 04-03-2017Date of Receipt: 04-06-2017Date of Report: 04-10-2017
ASBESTOS PLM REPORT: EPA-600/M4-82-020 & EPA METHOD 600/R-93-116Location: 13B, 2x4 ceiling tile-white with small hole and pinholds-1st-classroom-staorage-1 room Lab ID-Version‡: 7956198-1
Sample Layers Asbestos ContentGray Ceiling Tile with White Surface ND
Composite Non-Asbestos Content: 90% CelluloseSample Composite Homogeneity: Moderate
Location: 13C, 2x4 ceiling tile-white with small hole and pinholds-1st-classroom-staorage-1 room Lab ID-Version‡: 7956199-1
Sample Layers Asbestos ContentGray Ceiling Tile with White Surface ND
Composite Non-Asbestos Content: 90% CelluloseSample Composite Homogeneity: Moderate
Location: 14A, Residual black material under plywood subfloor-1st-classroom-storage Lab ID-Version‡: 7956200-1
Sample Layers Asbestos ContentBlack Non-Fibrous Material ND
Sample Composite Homogeneity: Good
Location: 14B, Residual black material under plywood subfloor-1st-classroom-storage Lab ID-Version‡: 7956201-1
Sample Layers Asbestos ContentBlack Non-Fibrous Material ND
Yellow Insulation NDBrown Semi-Fibrous Material ND
Composite Non-Asbestos Content: 35% Cellulose20% Glass Fibers
Sample Composite Homogeneity: Moderate
EMLab ID: 1706603, Page 14 of 22EMLab P&K, LLC
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. EMLab P&K reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is reflected by the value of "x".
EMLab P&K6100 Mountain Vista St, Ste #160, Henderson, NV 89014
(866) 888-6653 Fax (623) 780-7695 www.emlab.comClient: RGA Environmental, Inc.C/O: Mr. Kenneth PilgrimRe: R1167C66; CCCD-LA&H.S. PreDemo-2600 Mission Bell, S. Pablo, CA.
Date of Sampling: 04-03-2017Date of Receipt: 04-06-2017Date of Report: 04-10-2017
ASBESTOS PLM REPORT: EPA-600/M4-82-020 & EPA METHOD 600/R-93-116Location: 15A, White sink insulation-1st-nursing office Lab ID-Version‡: 7956202-1
Sample Layers Asbestos ContentWhite Sink Undercoating ND
Sample Composite Homogeneity: Moderate
Location: 15B, White sink insulation-1st-nursing office Lab ID-Version‡: 7956203-1
Sample Layers Asbestos ContentWhite Sink Undercoating ND
Sample Composite Homogeneity: Moderate
Location: 15C, White sink insulation-1st-nursing office Lab ID-Version‡: 7956204-1
Sample Layers Asbestos ContentWhite Sink Undercoating ND
Sample Composite Homogeneity: Moderate
Location: 16A, 2"x2" white ceiling tile-1st-lab services Lab ID-Version‡: 7956205-1
Sample Layers Asbestos ContentYellow Ceiling Tile with White Surface ND
Composite Non-Asbestos Content: 80% Glass FibersSample Composite Homogeneity: Moderate
EMLab ID: 1706603, Page 15 of 22EMLab P&K, LLC
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. EMLab P&K reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is reflected by the value of "x".
EMLab P&K6100 Mountain Vista St, Ste #160, Henderson, NV 89014
(866) 888-6653 Fax (623) 780-7695 www.emlab.comClient: RGA Environmental, Inc.C/O: Mr. Kenneth PilgrimRe: R1167C66; CCCD-LA&H.S. PreDemo-2600 Mission Bell, S. Pablo, CA.
Date of Sampling: 04-03-2017Date of Receipt: 04-06-2017Date of Report: 04-10-2017
ASBESTOS PLM REPORT: EPA-600/M4-82-020 & EPA METHOD 600/R-93-116Location: 16B, 2"x2" white ceiling tile-1st-nursing office Lab ID-Version‡: 7956206-1
Sample Layers Asbestos ContentYellow Ceiling Tile with White Surface ND
Composite Non-Asbestos Content: 80% Glass FibersSample Composite Homogeneity: Moderate
Location: 16C, 2"x2" white ceiling tile-1st-room 105-exam room Lab ID-Version‡: 7956207-1
Sample Layers Asbestos ContentYellow Ceiling Tile with White Surface ND
Composite Non-Asbestos Content: 80% Glass FibersSample Composite Homogeneity: Moderate
Location: 17A, 12" white VFT with brown smudge and yellow-ground-HSF and hallwayLab ID-Version‡: 7956208-1
Sample Layers Asbestos ContentGray Floor Tile NDYellow Mastic ND
Sample Composite Homogeneity: Moderate
Location: 17B, 12" white VFT with brown smudge and yellow-ground-HSF and hallwayLab ID-Version‡: 7956209-1
Sample Layers Asbestos ContentGray Floor Tile NDYellow Mastic ND
Sample Composite Homogeneity: Moderate
EMLab ID: 1706603, Page 16 of 22EMLab P&K, LLC
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. EMLab P&K reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is reflected by the value of "x".
EMLab P&K6100 Mountain Vista St, Ste #160, Henderson, NV 89014
(866) 888-6653 Fax (623) 780-7695 www.emlab.comClient: RGA Environmental, Inc.C/O: Mr. Kenneth PilgrimRe: R1167C66; CCCD-LA&H.S. PreDemo-2600 Mission Bell, S. Pablo, CA.
Date of Sampling: 04-03-2017Date of Receipt: 04-06-2017Date of Report: 04-10-2017
ASBESTOS PLM REPORT: EPA-600/M4-82-020 & EPA METHOD 600/R-93-116Location: 17C, 12" white VFT with brown smudge and yellow-ground-HSF and hallway
Lab ID-Version‡: 7956210-1
Sample Layers Asbestos ContentGray Floor Tile NDYellow Mastic ND
Sample Composite Homogeneity: Moderate
Location: 18A, 12" tan VFT with dark brown smudge-ground-lab service Lab ID-Version‡: 7956211-1
Sample Layers Asbestos ContentTan Floor Tile NDBlack Mastic 10% Chrysotile
Sample Composite Homogeneity: Moderate
Location: 18B, 12" tan VFT with dark brown smudge-ground-lab service Lab ID-Version‡: 7956212-1
Sample Layers Asbestos ContentTan Floor Tile NDBlack Mastic 10% Chrysotile
Sample Composite Homogeneity: Moderate
Location: 18C, 12" tan VFT with dark brown smudge-ground-lab service Lab ID-Version‡: 7956213-1
Sample Layers Asbestos ContentTan Floor Tile NDBlack Mastic 10% Chrysotile
Sample Composite Homogeneity: Moderate
EMLab ID: 1706603, Page 17 of 22EMLab P&K, LLC
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. EMLab P&K reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is reflected by the value of "x".
EMLab P&K6100 Mountain Vista St, Ste #160, Henderson, NV 89014
(866) 888-6653 Fax (623) 780-7695 www.emlab.comClient: RGA Environmental, Inc.C/O: Mr. Kenneth PilgrimRe: R1167C66; CCCD-LA&H.S. PreDemo-2600 Mission Bell, S. Pablo, CA.
Date of Sampling: 04-03-2017Date of Receipt: 04-06-2017Date of Report: 04-10-2017
ASBESTOS PLM REPORT: EPA-600/M4-82-020 & EPA METHOD 600/R-93-116Location: 19A, 12" white VFT with blue smudge-ground-HSB Lab ID-Version‡: 7956214-1
Sample Layers Asbestos ContentWhite Floor Tile NDYellow Mastic ND
Sample Composite Homogeneity: Moderate
Location: 19B, 12" white VFT with blue smudge-ground-HSB Lab ID-Version‡: 7956215-1
Sample Layers Asbestos ContentWhite Floor Tile NDYellow Mastic ND
Sample Composite Homogeneity: Moderate
Location: 19C, 12" white VFT with blue smudge-ground-HSB Lab ID-Version‡: 7956216-1
Sample Layers Asbestos ContentWhite Floor Tile NDYellow Mastic ND
Sample Composite Homogeneity: Moderate
Location: 20A, 4" black covebase with white glue and brown glue-ground floor-HS1 Lab ID-Version‡: 7956217-1
Sample Layers Asbestos ContentBlack Baseboard ND
Brown Mastic 2% ChrysotileSample Composite Homogeneity: Moderate
EMLab ID: 1706603, Page 18 of 22EMLab P&K, LLC
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. EMLab P&K reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is reflected by the value of "x".
EMLab P&K6100 Mountain Vista St, Ste #160, Henderson, NV 89014
(866) 888-6653 Fax (623) 780-7695 www.emlab.comClient: RGA Environmental, Inc.C/O: Mr. Kenneth PilgrimRe: R1167C66; CCCD-LA&H.S. PreDemo-2600 Mission Bell, S. Pablo, CA.
Date of Sampling: 04-03-2017Date of Receipt: 04-06-2017Date of Report: 04-10-2017
ASBESTOS PLM REPORT: EPA-600/M4-82-020 & EPA METHOD 600/R-93-116Location: 20B, 4" black covebase with white glue and brown glue-ground floor-HS2-store room Lab ID-Version‡: 7956218-1
Sample Layers Asbestos ContentBlack Baseboard ND
Brown Mastic 2% ChrysotileSample Composite Homogeneity: Moderate
Location: 20C, 4" black covebase with white glue and brown glue-ground floor-hallway-near LA Lab ID-Version‡: 7956219-1
Sample Layers Asbestos ContentBlack Baseboard ND
Brown Mastic 2% ChrysotileSample Composite Homogeneity: Moderate
Location: 21A, Tar and gravel with felt with paper-main roof-north Lab ID-Version‡: 7956220-1
Sample Layers Asbestos ContentBlack Roofing Felt with Paper ND
Composite Non-Asbestos Content: 45% CelluloseSample Composite Homogeneity: Moderate
Location: 21B, Tar and gravel with felt with paper-main roof-center Lab ID-Version‡: 7956221-1
Sample Layers Asbestos ContentBlack Roofing Felt with Paper ND
Composite Non-Asbestos Content: 45% CelluloseSample Composite Homogeneity: Moderate
EMLab ID: 1706603, Page 19 of 22EMLab P&K, LLC
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. EMLab P&K reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is reflected by the value of "x".
EMLab P&K6100 Mountain Vista St, Ste #160, Henderson, NV 89014
(866) 888-6653 Fax (623) 780-7695 www.emlab.comClient: RGA Environmental, Inc.C/O: Mr. Kenneth PilgrimRe: R1167C66; CCCD-LA&H.S. PreDemo-2600 Mission Bell, S. Pablo, CA.
Date of Sampling: 04-03-2017Date of Receipt: 04-06-2017Date of Report: 04-10-2017
ASBESTOS PLM REPORT: EPA-600/M4-82-020 & EPA METHOD 600/R-93-116Location: 21C, Tar and gravel with felt with paper-main roof-south Lab ID-Version‡: 7956222-1
Sample Layers Asbestos ContentBlack Roofing Felt with Paper ND
Composite Non-Asbestos Content: 45% CelluloseSample Composite Homogeneity: Moderate
Location: 21D, Tar and gravel with felt with paper-main roof-medium-east-roof Lab ID-Version‡: 7956223-1
Sample Layers Asbestos ContentBlack Roofing Felt with Paper ND
Composite Non-Asbestos Content: 45% CelluloseSample Composite Homogeneity: Moderate
Location: 21E, Tar and gravel with felt with paper-small-south roof Lab ID-Version‡: 7956224-1
Sample Layers Asbestos ContentBlack Roofing Felt with Paper ND
Composite Non-Asbestos Content: 45% CelluloseSample Composite Homogeneity: Moderate
Location: 22A, Flashing-rolled shingle-and curb-main roof-large-north area-flashing Lab ID-Version‡: 7956225-1
Sample Layers Asbestos ContentBlack Roofing Shingle with Gray Pebbles ND
Composite Non-Asbestos Content: 30% Glass FibersSample Composite Homogeneity: Moderate
EMLab ID: 1706603, Page 20 of 22EMLab P&K, LLC
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. EMLab P&K reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is reflected by the value of "x".
EMLab P&K6100 Mountain Vista St, Ste #160, Henderson, NV 89014
(866) 888-6653 Fax (623) 780-7695 www.emlab.comClient: RGA Environmental, Inc.C/O: Mr. Kenneth PilgrimRe: R1167C66; CCCD-LA&H.S. PreDemo-2600 Mission Bell, S. Pablo, CA.
Date of Sampling: 04-03-2017Date of Receipt: 04-06-2017Date of Report: 04-10-2017
ASBESTOS PLM REPORT: EPA-600/M4-82-020 & EPA METHOD 600/R-93-116Location: 22B, Flashing-rolled shingle-and curb-main roof-large-center area-curb Lab ID-Version‡: 7956226-1
Sample Layers Asbestos ContentBlack Roofing Shingle with Gray Pebbles ND
Composite Non-Asbestos Content: 30% Glass FibersSample Composite Homogeneity: Moderate
Location: 22C, Flashing-rolled shingle-and curb-main roof-large-south area-flashing Lab ID-Version‡: 7956227-1
Sample Layers Asbestos ContentBlack Roofing Shingle with Gray Pebbles ND
Composite Non-Asbestos Content: 30% Glass FibersSample Composite Homogeneity: Moderate
Location: 23A, Parapet wall-rolled shingle-main roof-north area Lab ID-Version‡: 7956228-1
Sample Layers Asbestos ContentBlack Roofing Shingle with Gray Pebbles ND
Composite Non-Asbestos Content: 30% Glass FibersSample Composite Homogeneity: Moderate
Location: 23B, Parapet wall-rolled shingle-main roof-center area Lab ID-Version‡: 7956229-1
Sample Layers Asbestos ContentBlack Roofing Shingle with Gray Pebbles ND
Composite Non-Asbestos Content: 30% Glass FibersSample Composite Homogeneity: Moderate
EMLab ID: 1706603, Page 21 of 22EMLab P&K, LLC
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. EMLab P&K reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is reflected by the value of "x".
EMLab P&K6100 Mountain Vista St, Ste #160, Henderson, NV 89014
(866) 888-6653 Fax (623) 780-7695 www.emlab.comClient: RGA Environmental, Inc.C/O: Mr. Kenneth PilgrimRe: R1167C66; CCCD-LA&H.S. PreDemo-2600 Mission Bell, S. Pablo, CA.
Date of Sampling: 04-03-2017Date of Receipt: 04-06-2017Date of Report: 04-10-2017
ASBESTOS PLM REPORT: EPA-600/M4-82-020 & EPA METHOD 600/R-93-116Location: 23C, Parapet wall-rolled shingle-main roof-south area Lab ID-Version‡: 7956230-1
Sample Layers Asbestos ContentBlack Roofing Shingle with Gray Pebbles ND
Composite Non-Asbestos Content: 30% Glass FibersSample Composite Homogeneity: Moderate
Location: 24A, Gray and black patch-main roof-patch on HVAC curb Lab ID-Version‡: 7956231-1
Sample Layers Asbestos ContentBlack Roofing Material ND
Sample Composite Homogeneity: Good
Location: 24B, Gray and black patch-main roof-patch on flashing-south area Lab ID-Version‡: 7956232-1
Sample Layers Asbestos ContentBlack Roofing Material ND
Sample Composite Homogeneity: Good
Location: 24C, Gray and black patch-main roof-patch on pipe penetration Lab ID-Version‡: 7956233-1
Sample Layers Asbestos ContentBlack Roofing Material ND
Sample Composite Homogeneity: Good
EMLab ID: 1706603, Page 22 of 22EMLab P&K, LLC
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. EMLab P&K reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is reflected by the value of "x".
Approved by:
Approved SignatoryNoah Lazarte
Report for:
Mr. Kenneth PilgrimRGA Environmental, Inc.1466 66th StreetEmeryville, CA 94608
Regarding: Project: R1167C66; CCCCD LA & HS Demo, 2600 Mission Bell, San Pablo, CAEML ID: 1717674
All samples were received in acceptable condition unless noted in the Report Comments portion in the body of the report. The results relate only to the items tested. The results include an inherent uncertainty of measurement associated with estimating percentages by polarized light microscopy. Measurement uncertainty data for sample results with >1% asbestos concentration can be provided when requested.
EMLab P&K ("the Company") shall have no liability to the client or the client's customer with respect to decisions or recommendations made, actions taken or courses of conduct implemented by either the client or the client's customer as a result of or based upon the Test Results. In no event shall the Company be liable to the client with respect to the Test Results except for the Company's own willful misconduct or gross negligence nor shall the Company be liable for incidental or consequential damages or lost profits or revenues to the fullest extent such liability may be disclaimed by law, even if the Company has been advised of the possibility of such damages, lost profits or lost revenues. In no event shall the Company's liability with respect to the Test Results exceed the amount paid to the Company by the client therefor.
Dates of Analysis:Asbestos PLM: 05-01-2017
Service SOPs: Asbestos PLM (EPA Methods 600/R-93/116 & 600/M4-82-020, SOP EM-AS-S-1267)
EMLab ID: 1717674, Page 1 of 5EMLab P&K, LLC
EMLab P&K4955 Yarrow Street , Arvada, CO 80002
(800) 651-4802 Fax (623) 780-7695 www.emlab.comClient: RGA Environmental, Inc.C/O: Mr. Kenneth PilgrimRe: R1167C66; CCCCD LA & HS Demo, 2600 Mission Bell, San Pablo, CA
Date of Sampling: 04-18-2017Date of Receipt: 04-27-2017Date of Report: 05-01-2017
ASBESTOS PLM REPORT: EPA-600/M4-82-020 & EPA METHOD 600/R-93-116Total Samples Submitted: 14Total Samples Analyzed: 14
Total Samples with Layer Asbestos Content > 1%: 0
Location: 29A, Exterior stucco, HS, exterior, West, at door Lab ID-Version‡: 8012912-1
Sample Layers Asbestos ContentGray Stucco < 1% Chrysotile
Sample Composite Homogeneity: Good
Location: 29B, Exterior stucco, HS, exterior, North, West wing Lab ID-Version‡: 8012913-1
Sample Layers Asbestos ContentGray Stucco < 1% Chrysotile
Sample Composite Homogeneity: Good
Location: 29C, Exterior stucco, HS, exterior, North, East wing, courtyard Lab ID-Version‡: 8012914-1
Sample Layers Asbestos ContentGray Stucco < 1% Chrysotile
Sample Composite Homogeneity: Good
Location: 29D, Exterior stucco, HS, exterior, North, East wing, North Lab ID-Version‡: 8012915-1
Sample Layers Asbestos ContentGray Stucco < 1% Chrysotile
Sample Composite Homogeneity: Good
EMLab ID: 1717674, Page 2 of 5EMLab P&K, LLC
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. EMLab P&K reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is reflected by the value of "x".
EMLab P&K4955 Yarrow Street , Arvada, CO 80002
(800) 651-4802 Fax (623) 780-7695 www.emlab.comClient: RGA Environmental, Inc.C/O: Mr. Kenneth PilgrimRe: R1167C66; CCCCD LA & HS Demo, 2600 Mission Bell, San Pablo, CA
Date of Sampling: 04-18-2017Date of Receipt: 04-27-2017Date of Report: 05-01-2017
ASBESTOS PLM REPORT: EPA-600/M4-82-020 & EPA METHOD 600/R-93-116Location: 29E, Exterior stucco, HS, exterior, North, East side of East wing Lab ID-Version‡: 8012916-1
Sample Layers Asbestos ContentGray Stucco < 1% Chrysotile
Sample Composite Homogeneity: Good
Location: 29F, Exterior stucco, HS, exterior, East elevation Lab ID-Version‡: 8012917-1
Sample Layers Asbestos ContentGray Stucco ND
Sample Composite Homogeneity: Good
Location: 29G, Exterior stucco, HS, exterior, ground floor, West elevation Lab ID-Version‡: 8012918-1
Sample Layers Asbestos ContentGray Cementitious Material < 1% Chrysotile
Light Gray Stucco NDSample Composite Homogeneity: Moderate
Location: 83A, Brick mortar, HS, South side, ground floor, SW corner Lab ID-Version‡: 8012919-1
Sample Layers Asbestos ContentGray Mortar ND
Sample Composite Homogeneity: Good
EMLab ID: 1717674, Page 3 of 5EMLab P&K, LLC
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. EMLab P&K reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is reflected by the value of "x".
EMLab P&K4955 Yarrow Street , Arvada, CO 80002
(800) 651-4802 Fax (623) 780-7695 www.emlab.comClient: RGA Environmental, Inc.C/O: Mr. Kenneth PilgrimRe: R1167C66; CCCCD LA & HS Demo, 2600 Mission Bell, San Pablo, CA
Date of Sampling: 04-18-2017Date of Receipt: 04-27-2017Date of Report: 05-01-2017
ASBESTOS PLM REPORT: EPA-600/M4-82-020 & EPA METHOD 600/R-93-116Location: 83B, Brick mortar, HS, South side, ground floor, SE corner Lab ID-Version‡: 8012920-1
Sample Layers Asbestos ContentRed Brick ND
Gray Mortar NDSample Composite Homogeneity: Moderate
Location: 83C, Brick mortar, HS, South side, ground floor, East elevation Lab ID-Version‡: 8012921-1
Sample Layers Asbestos ContentRed Brick ND
Gray Mortar NDLight Gray Mortar ND
Sample Composite Homogeneity: Poor
Location: 84A, Window frame sealant, off-white, HS, West side, 1st, at door frame and brick Lab ID-Version‡: 8012922-1
Sample Layers Asbestos ContentOff-White Sealant ND
Sample Composite Homogeneity: Good
Location: 84B, Window frame sealant, off-white, HS, courtyard, West side, window frame/wall Lab ID-Version‡: 8012923-1
Sample Layers Asbestos ContentOff-White Sealant ND
Sample Composite Homogeneity: Good
EMLab ID: 1717674, Page 4 of 5EMLab P&K, LLC
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. EMLab P&K reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is reflected by the value of "x".
EMLab P&K4955 Yarrow Street , Arvada, CO 80002
(800) 651-4802 Fax (623) 780-7695 www.emlab.comClient: RGA Environmental, Inc.C/O: Mr. Kenneth PilgrimRe: R1167C66; CCCCD LA & HS Demo, 2600 Mission Bell, San Pablo, CA
Date of Sampling: 04-18-2017Date of Receipt: 04-27-2017Date of Report: 05-01-2017
ASBESTOS PLM REPORT: EPA-600/M4-82-020 & EPA METHOD 600/R-93-116Location: 84C, Window frame sealant, off-white, HS, courtyard, East side, window frame/wall Lab ID-Version‡: 8012924-1
Sample Layers Asbestos ContentOff-White Sealant ND
Sample Composite Homogeneity: Good
Location: 85A, Felt paper, behind brick, HS, ground floor, East elevation, at door frameLab ID-Version‡: 8012925-1
Sample Layers Asbestos ContentTan Paper NDBlack Tar NDComposite Non-Asbestos Content: 85% CelluloseSample Composite Homogeneity: Moderate
EMLab ID: 1717674, Page 5 of 5EMLab P&K, LLC
The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government. EMLab P&K reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.
Inhomogeneous samples are separated into homogeneous subsamples and analyzed individually. ND means no fibers were detected. When detected, the minimum detection and reporting limit is less than 1% unless point counting is performed. Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is reflected by the value of "x".
Approved by:
Approved SignatoryNoah Lazarte
Report for:
Mr. Kenneth PilgrimRGA Environmental, Inc.1466 66th StreetEmeryville, CA 94608
Regarding: Project: R1167C66; CCCCD LA & HS Demo, 2600 Mission Bell, San Pablo, CAEML ID: 1717674
All samples were received in acceptable condition unless noted in the Report Comments portion in the body of the report. Due to the nature of the analyses performed, field blank correction of results is not applied. The results relate only to the items tested.
EMLab P&K ("the Company") shall have no liability to the client or the client's customer with respect to decisions or recommendations made, actions taken or courses of conduct implemented by either the client or the client's customer as a result of or based upon the Test Results. In no event shall the Company be liable to the client with respect to the Test Results except for the Company's own willful misconduct or gross negligence nor shall the Company be liable for incidental or consequential damages or lost profits or revenues to the fullest extent such liability may be disclaimed by law, even if the Company has been advised of the possibility of such damages, lost profits or lost revenues. In no event shall the Company's liability with respect to the Test Results exceed the amount paid to the Company by the client therefor.
Dates of Analysis:Asbestos-EPA 1000 point count: 05-10-2017 and 05-11-2017
Service SOPs: Asbestos-EPA 1000 point count (EPA Methods 600/R-93/116 & 600/M4-82-020, SOP EM-AS-S-1262)
EMLab ID: 1717674, Page 1 of 3EMLab P&K, LLC
EMLab P&K4955 Yarrow Street , Arvada, CO 80002
(800) 651-4802 Fax (623) 780-7695 www.emlab.comClient: RGA Environmental, Inc.C/O: Mr. Kenneth PilgrimRe: R1167C66; CCCCD LA & HS Demo, 2600 Mission Bell, San Pablo, CA
Date of Sampling: 04-18-2017Date of Receipt: 04-27-2017Date of Report: 05-11-2017
ASBESTOS POINT COUNT REPORT: EPA METHOD 600/R-93-116
Location: 29AExterior stucco, HS, exterior, West, at door
Total Points Counted: 1000
Lab ID-Version‡: 8039870-1
Sample Layers Asbestos Type Asbestos PointsCounted
AsbestosConcentration (%)
Gray Stucco Chrysotile 2 0.2Layer Totals: 2 0.2
Comments:
Location: 29BExterior stucco, HS, exterior, North, West wing
Total Points Counted: 1000
Lab ID-Version‡: 8039871-1
Sample Layers Asbestos Type Asbestos PointsCounted
AsbestosConcentration (%)
Gray Stucco Chrysotile 1 0.1Layer Totals: 1 0.1
Comments:
Location: 29CExterior stucco, HS, exterior, North, East wing, courtyard
Total Points Counted: 1000
Lab ID-Version‡: 8039872-1
Sample Layers Asbestos Type Asbestos PointsCounted
AsbestosConcentration (%)
Gray Stucco Chrysotile 3 0.3Layer Totals: 3 0.3
Comments:
EMLab ID: 1717674, Page 2 of 3EMLab P&K, LLC
The analytical sensitivity is 1 asbestos point. The limit of detection is 1 asbestos point divided by the total number of asbestos points counted and multiplied by 100.
The results relate only to the items tested. Interpretation is left to the company and/or persons who conducted the field work. The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government.
All samples were received in acceptable condition unless otherwise noted. EMLab P&K reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.
‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is reflected by the value of "x".
EMLab P&K4955 Yarrow Street , Arvada, CO 80002
(800) 651-4802 Fax (623) 780-7695 www.emlab.comClient: RGA Environmental, Inc.C/O: Mr. Kenneth PilgrimRe: R1167C66; CCCCD LA & HS Demo, 2600 Mission Bell, San Pablo, CA
Date of Sampling: 04-18-2017Date of Receipt: 04-27-2017Date of Report: 05-11-2017
ASBESTOS POINT COUNT REPORT: EPA METHOD 600/R-93-116
Location: 29DExterior stucco, HS, exterior, North, East wing, North
Total Points Counted: 1000
Lab ID-Version‡: 8039873-1
Sample Layers Asbestos Type Asbestos PointsCounted
AsbestosConcentration (%)
Gray Stucco Chrysotile 1 0.1Layer Totals: 1 0.1
Comments:
Location: 29EExterior stucco, HS, exterior, North, East side of East wing
Total Points Counted: 1000
Lab ID-Version‡: 8039874-1
Sample Layers Asbestos Type Asbestos PointsCounted
AsbestosConcentration (%)
Gray Stucco Chrysotile 1 0.1Layer Totals: 1 0.1
Comments:
Location: 29GExterior stucco, HS, exterior, ground floor, West elevation
Total Points Counted: 1000
Lab ID-Version‡: 8039875-1
Sample Layers Asbestos Type Asbestos PointsCounted
AsbestosConcentration (%)
Gray Cementitious Material Chrysotile 3 0.3Layer Totals: 3 0.3
Comments:
EMLab ID: 1717674, Page 3 of 3EMLab P&K, LLC
The analytical sensitivity is 1 asbestos point. The limit of detection is 1 asbestos point divided by the total number of asbestos points counted and multiplied by 100.
The results relate only to the items tested. Interpretation is left to the company and/or persons who conducted the field work. The test report shall not be reproduced except in full, without written approval of the laboratory. The report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST, or any agency of the federal government.
All samples were received in acceptable condition unless otherwise noted. EMLab P&K reserves the right to dispose of all samples after a period of thirty (30) days, according to all state and federal guidelines, unless otherwise specified.Floor tile samples may contain large amounts of interference material and it is recommended that the sample be analyzed by gravimetric point count analysis to lower the detection limit and to aid in asbestos identification.
‡ A "Version" indicated by -"x" after the Lab ID# with a value greater than 1 indicates a sample with amended data. The revision number is reflected by the value of "x".
Appendix 2
Laboratory Results and Chain of Custody - Lead
Acct. No.:
Project: CCCD-LA&H.S. Predemo-2600 Mission Bell,
Location:
Project No.:
QuanTEM Set ID: 278479
Date Received: 04/06/17
Received By: Travis Miller
Date Sampled:
Time Sampled:
Date of Report: 04/07/17
C018
CA
R1167C66
Matrix Parameter Results Units MethodClient ID
QuanTEM
ID
Reporting
Limits
Date/Time
Analyzed
Environmental Chemistry Analysis Report
Client: RGA Environmental
K. Pilgrim
1466 66th Street
Emeryville, CA 94608
Analyst: CR
AIHA ID: 101352
Lead 0.797 0.00494 % 04/06/17 15:46 P EPA 7000B (1)PaintPb-1001
Lead 0.212 0.005 % 04/06/17 15:04 P EPA 7000B (1)PaintPb-2002
Authorized Signature:_______________________________________________
Cherry Rossen, Technical Manager
Page 1 of 1
Note: Sample results have not been corrected for blank values.
This report applies only to the standards or procedures indicated and to the specific samples tested. It is not indicative of the qualities of apparently
identical or similar products or procedures, nor does it represent an ongoing assurance program unless so noted. These reports are for the exclusive use of
the client and are not to be reproduced without specific written permission. QuanTEM is not responsible for user-supplied data used in calculations.
Unless otherwise noted, upon receipt the condition of the sample was acceptable for analysis.
Wipe materials must meet ASTM E1792 criteria. Method detection limits and resultant reporting limits may not be valid for non-ASTM E1792 wipe
material.
EPA Method 7000B (1) = EPA 600/R-93/200 Preparation Modified. EPA 7000B Analysis Modified
EPA Method 7082 (2) = EPA 600/R-93/200 Preparation Modified. EPA 7082 Analysis Modified
Supplemental Report
QAQC Results
QA ID: 15143 Date: 4/6/2017
Test: Lead
Notes:
Matrix: Paint Approved By: Cherry Rossen
Date Approved: 4/6/2017
Blank Data:
Duplicate Data:
Recovery Data:
Standards Data:
Lab Number: 278479
Type of Blank Blank Value
0FCB
0ICB
0Matrix Blank 1
0Matrix Blank 2
0Matrix Blank 3
0Matrix Blank 4
Sample Number Result Duplicate % RPD
1.9811.831 7.9278426-034
Sample Number Result Spike Level Result +
Spike
Dup. Result +
Spike
% Spike RPD% Recovery % Dup.
Recovery
1.992 2.1100.000 2.102105.9 105.5 0.4LCS-P1
1.988 2.0890.000 2.046105.1 102.9 2.0LCS-P2
1.985 2.0650.000 2.046104.0 103.0 0.9LCS-P3
1.993 2.0890.000 2.100104.8 105.4 0.5LCS-P4
2.000 2.0770.086 99.6278471-001
2.000 2.1630.171 99.6278426-013
2.000 3.8051.831 98.7278426-034
Standard Low Limit Obtained High Limit
4.5 5.55CCV
4.5 5.54.9FCV
0.9 1.11ICV
0.08 0.120.12RLVS
Page 1 of 2
Authorized Signature:_______________________________________________
Cherry Rossen, Technical Manager
Supplemental Report
QAQC Results
QA ID: 15144 Date: 4/6/2017
Test: Lead
Notes:
Matrix: Paint Approved By: Cherry Rossen
Date Approved: 4/6/2017
Blank Data:
Duplicate Data:
Recovery Data:
Standards Data:
Lab Number: 278479
Type of Blank Blank Value
0FCB
0ICB
Sample Number Result Duplicate % RPD
20.76520.779 0.1278426-002
Standard Low Limit Obtained High Limit
4.5 5.54.9CCV
4.5 5.54.9FCV
0.9 1.11ICV
Page 2 of 2
Authorized Signature:_______________________________________________
Cherry Rossen, Technical Manager
Acct. No.:
Project: CCCCD-LA&HS Pre Demo, 2600 Mission Be
Location:
Project No.:
QuanTEM Set ID: 279332
Date Received: 04/27/17
Received By: Peyton Awbrey
Date Sampled:
Time Sampled:
Date of Report: 04/28/17
C018
San Pablo, CA
R1167C66
Matrix Parameter Results Units MethodClient ID
QuanTEM
ID
Reporting
Limits
Date/Time
Analyzed
Environmental Chemistry Analysis Report
Client: RGA Environmental
K. Pilgrim
1466 66th Street
Emeryville, CA 94608
Analyst: CR
AIHA ID: 101352
Lead <49.4 49.4 ppm 04/28/17 11:16 P EPA 7000B (1)PaintPb-8001
Lead 180 48.8 ppm 04/28/17 11:16 P EPA 7000B (1)PaintPb-9002
Lead 674 49.3 ppm 04/28/17 11:16 P EPA 7000B (1)PaintPb-10003
Lead 2,890 49.3 ppm 04/28/17 11:16 P EPA 7000B (1)PaintPb-11004
Lead 50.2 49.7 ppm 04/28/17 11:16 P EPA 7000B (1)PaintPb-12005
Lead 1,370 49.3 ppm 04/28/17 11:16 P EPA 7000B (1)PaintPb-13006
Authorized Signature:_______________________________________________
Cherry Rossen, Technical Manager
Page 1 of 1
Note: Sample results have not been corrected for blank values.
This report applies only to the standards or procedures indicated and to the specific samples tested. It is not indicative of the qualities of apparently
identical or similar products or procedures, nor does it represent an ongoing assurance program unless so noted. These reports are for the exclusive use of
the client and are not to be reproduced without specific written permission. QuanTEM is not responsible for user-supplied data used in calculations.
Unless otherwise noted, upon receipt the condition of the sample was acceptable for analysis.
Wipe materials must meet ASTM E1792 criteria. Method detection limits and resultant reporting limits may not be valid for non-ASTM E1792 wipe
material.
EPA Method 7000B (1) = EPA 600/R-93/200 Preparation Modified. EPA 7000B Analysis Modified
EPA Method 7082 (2) = EPA 600/R-93/200 Preparation Modified. EPA 7082 Analysis Modified
Supplemental Report
QAQC Results
QA ID: 15213 Date: 4/28/2017
Test: Lead
Notes:
Matrix: Paint Approved By: Cherry Rossen
Date Approved: 4/28/2017
Blank Data:
Duplicate Data:
Recovery Data:
Standards Data:
Lab Number: 279332
Type of Blank Blank Value
0FCB
0ICB
0Matrix Blank 1
0Matrix Blank 2
Sample Number Result Duplicate % RPD
0.4360.405 7.4279191-001
Sample Number Result Spike Level Result +
Spike
Dup. Result +
Spike
% Spike RPD% Recovery % Dup.
Recovery
2.042 2.0860.000 2.151102.2 105.3 3.0LCS-P1
1.942 2.3830.000 2.092122.7 107.7 13.0LCS-P2
2.000 1.9820.024 97.9279331-001
2.000 2.3640.405 98.0279191-001
Standard Low Limit Obtained High Limit
4.5 5.54.7CCV
4.5 5.51ICV
4.5 5.54.6FCV
0.08 0.120.11RLVS
Page 1 of 1
Authorized Signature:_______________________________________________
Cherry Rossen, Technical Manager
Appendix 3
Laboratory Results and Chain of Custody - PCB
WorkOrder:
Report Created for: Terracon
1466 66th Street
Emeryville, CA 94608
Project Contact: Kenneth Pilgrim
Project Name: R1167C66; CCCCD LA+HS Pre-Demo
Project P.O.:
Project Received: 04/20/2017
Analytical Report reviewed & approved for release on 05/01/2017 by:
Angela Rydelius,
Laboratory Manager
1704938
The report shall not be reproduced except in full, without the written
approval of the laboratory. The analytical results relate only to the
items tested. Results reported conform to the most current NELAP
standards, where applicable, unless otherwise stated in the case
narrative.
Analytical Report
1534 Willow Pass Rd. Pittsburg, CA 94565 ♦ TEL: (877) 252-9262 ♦ FAX: (925) 252-9269 ♦ www.mccampbell.com
CA ELAP 1644 ♦ NELAP 4033ORELAP
McCampbell Analytical, Inc."When Quality Counts"
Page 1 of 9
Glossary of Terms & Qualifier Definitions
Client: Terracon
Project: R1167C66; CCCCD LA+HS Pre-Demo
WorkOrder: 1704938
McCampbell Analytical, Inc.1534 Willow Pass Road, Pittsburg, CA 94565-1701
Toll Free Telephone: (877) 252-9262 / Fax: (925) 252-9269
http://www.mccampbell.com / E-mail: [email protected]"When Quality Counts"
Glossary Abbreviation
%D Serial Dilution Percent Difference
95% Interval 95% Confident Interval
DF Dilution Factor
DI WET (DISTLC) Waste Extraction Test using DI water
DISS Dissolved (direct analysis of 0.45 µm filtered and acidified water sample)
DLT Dilution Test (Serial Dilution)
DUP Duplicate
EDL Estimated Detection Limit
IGN1 Sample is non metalic
ITEF International Toxicity Equivalence Factor
LCS Laboratory Control Sample
MB Method Blank
MB % Rec % Recovery of Surrogate in Method Blank, if applicable
MDL Method Detection Limit
ML Minimum Level of Quantitation
MS Matrix Spike
MSD Matrix Spike Duplicate
N/A Not Applicable
ND Not detected at or above the indicated MDL or RL
NR Data Not Reported due to matrix interference or insufficient sample amount.
PDS Post Digestion Spike
PDSD Post Digestion Spike Duplicate
PF Prep Factor
RD Relative Difference
RL Reporting Limit (The RL is the lowest calibration standard in a multipoint calibration.)
RPD Relative Percent Deviation
RRT Relative Retention Time
SPK Val Spike Value
SPKRef Val Spike Reference Value
SPLP Synthetic Precipitation Leachate Procedure
ST Sorbent Tube
TCLP Toxicity Characteristic Leachate Procedure
TEQ Toxicity Equivalents
WET (STLC) Waste Extraction Test (Soluble Threshold Limit Concentration)
Page 2 of 9
Glossary of Terms & Qualifier Definitions
Client: Terracon
Project: R1167C66; CCCCD LA+HS Pre-Demo
WorkOrder: 1704938
McCampbell Analytical, Inc.1534 Willow Pass Road, Pittsburg, CA 94565-1701
Toll Free Telephone: (877) 252-9262 / Fax: (925) 252-9269
http://www.mccampbell.com / E-mail: [email protected]"When Quality Counts"
Analytical Qualifiers
P agreement between quantitative confirmation results exceed method recommended limits
a4 reporting limits raised due to the sample's matrix prohibiting a full volume extraction.
h4 sulfuric acid permanganate (EPA 3665) cleanup
Page 3 of 9
Analytical Report
McCampbell Analytical, Inc.1534 Willow Pass Road, Pittsburg, CA 94565-1701
Toll Free Telephone: (877) 252-9262 / Fax: (925) 252-9269
http://www.mccampbell.com / E-mail: [email protected]"When Quality Counts"
Client: Terracon
Project: R1167C66; CCCCD LA+HS Pre-Demo
Date Received: 4/20/17 14:50
Date Prepared: 4/20/17
WorkOrder: 1704938
Extraction Method: SW3550B
Analytical Method: SW8082
Unit: mg/kg
Polychlorinated Biphenyls (PCBs) Aroclors
PCB-01 1704938-001A Solid 04/18/2017 GC23 137565
Analytes Result DF Date AnalyzedRL
Client ID Lab ID Matrix Date Collected Instrument Batch ID
Aroclor1016 ND 0.50 1 04/21/2017 17:49
Aroclor1221 ND 0.50 1 04/21/2017 17:49
Aroclor1232 ND 0.50 1 04/21/2017 17:49
Aroclor1242 ND 0.50 1 04/21/2017 17:49
Aroclor1248 ND 0.50 1 04/21/2017 17:49
Aroclor1254 ND 0.50 1 04/21/2017 17:49
Aroclor1260 ND 0.50 1 04/21/2017 17:49
PCBs, total ND 0.50 1 04/21/2017 17:49
Surrogates REC (%) Limits
Analytical Comments: a4,h4Analyst(s): SS
Decachlorobiphenyl 94 70-130 04/21/2017 17:49
Angela Rydelius, Lab ManagerNELAP 4033ORELAP
Page 4 of 9
Quality Control Report
McCampbell Analytical, Inc.1534 Willow Pass Road, Pittsburg, CA 94565-1701
Toll Free Telephone: (877) 252-9262 / Fax: (925) 252-9269
http://www.mccampbell.com / E-mail: [email protected]"When Quality Counts"
Client: Terracon
Project: R1167C66; CCCCD LA+HS Pre-Demo
Date Analyzed: 4/21/17
Date Prepared: 4/19/17
WorkOrder: 1704938
BatchID: 137565
Analytical Method: SW8082
Unit: mg/kg
Sample ID: MB/LCS/LCSD-137565
Instrument: GC23
Matrix: Soil
Extraction Method: SW3550B
QC Summary Report for SW8082
Analyte MB
Result
RL SPK
Val
MB SS
%REC
MB SS
Limits
Aroclor1016 ND 0.050 - - -
Aroclor1221 ND 0.050 - - -
Aroclor1232 ND 0.050 - - -
Aroclor1242 ND 0.050 - - -
Aroclor1248 ND 0.050 - - -
Aroclor1254 ND 0.050 - - -
Aroclor1260 ND 0.050 - - -
PCBs, total ND 0.050 - - -
Surrogate Recovery
Decachlorobiphenyl 0.05086 0.050 102 70-130
Analyte LCS
Result
LCSD
Result
SPK
Val
LCS
%REC
LCSD
%REC
LCS/LCSD
Limits
RPD RPD
Limit
Aroclor1016 0.140 0.138 0.15 93 92 70-130 1.21 20
Aroclor1260 0.154 0.164 0.15 103 109 70-130 6.23 20
Surrogate Recovery
Decachlorobiphenyl 0.0515 0.0464 0.050 103 93 70-130 10.4 20
QA/QC OfficerNELAP 4033ORELAP
Page 5 of 9
McCampbell Analytical, Inc.1534 Willow Pass Rd
Pittsburg, CA 94565-1701
(925) 252-9262
CHAIN-OF-CUSTODY RECORD Page
Lab ID Matrix Collection Date Hold
Requested Tests (See legend below)
Report to:
Kenneth Pilgrim
1466 66th Street
Emeryville, CA 94608
(510) 547-7771 FAX: (510) 547-1983
PO:
04/20/2017
Client ID
ProjectNo: R1167C66; CCCCD LA+HS Pre-Demo
WorkOrder: 1704938
1 of 1
Date Logged:
Date Received: 04/20/2017
1 2 3 4 5 6 7 8 9 10 11 12
Terracon
Bill to:
Anita G. Ilsley
Terracon
1466 66th Street
Emeryville, CA 94608
Requested TAT: 5 days;
ClientCode: RGAE
Email: [email protected]
EDF EQuIS Email HardCopy ThirdParty
Excel J-flagWriteOn
cc/3rd Party:
WaterTrax
A1704938-001 Solid 4/18/2017 00:00PCB-01
Prepared by: Jena Alfaro
NOTE: Soil samples are discarded 60 days after results are reported unless other arrangements are made (Water samples are 30 days). Hazardous samples will be returned to client or disposed of at client expense.
Comments:
8082_PCB_Solid1 2 3 4
5 6 7 8
9 10
Test Legend:
11 12
Page 6 of 9
Lab ID Client ID Collection Date
& Time
Date Logged:
TATMatrix Test Name Containers
/Composites
WORK ORDER SUMMARY
Work Order: 1704938
Comments:
Client Name: TERRACON Project: R1167C66; CCCCD LA+HS Pre-Demo
QC Level: LEVEL 2
HoldDe-
chlorinated
SubOutBottle & Preservative
4/20/2017
Sediment
Content
EDF Fax Email HardCopy ThirdPartyExcel J-flagWriteOn
Kenneth PilgrimClient Contact:
[email protected]'s Email:
WaterTrax
McCampbell Analytical, Inc.1534 Willow Pass Road, Pittsburg, CA 94565-1701
Toll Free Telephone: (877) 252-9262 / Fax: (925) 252-9269
http://www.mccampbell.com / E-mail: [email protected]"When Quality Counts"
1704938-001A PCB-01 4/18/2017 5 daysSolid SW8082 (PCBs Only) 1 Plastic Baggie, Small
1 of 1Page
- STLC and TCLP extractions require 2 days to complete; therefore, all TATs begin after the extraction is completed (i.e., One-day TAT yields results
in 3 days from sample submission).
NOTES:
- MAI assumes that all material present in the provided sampling container is considered part of the sample - MAI does not exclude any material from
the sample prior to sample preparation unless requested in writing by the client.
Page 7 of 9
Page 8 of 9
Sample Receipt Checklist
McCampbell Analytical, Inc.1534 Willow Pass Road, Pittsburg, CA 94565-1701
Toll Free Telephone: (877) 252-9262 / Fax: (925) 252-9269
http://www.mccampbell.com / E-mail: [email protected]"When Quality Counts"
Client Name: Terracon
WorkOrder №: 1704938
Date Logged: 4/20/2017
Logged by: Jena AlfaroMatrix: Solid
Carrier: Client Drop-In
Shipping container/cooler in good condition? Yes No
Custody seals intact on shipping container/cooler? Yes No NA
Samples Received on Ice? Yes No
Chain of custody present? Yes No
Chain of custody signed when relinquished and received? Yes No
Chain of custody agrees with sample labels? Yes No
Samples in proper containers/bottles? Yes No
Sample containers intact? Yes No
Sufficient sample volume for indicated test? Yes No
NAAll samples received within holding time? Yes No
NASample/Temp Blank temperature
Yes No NAWater - VOA vials have zero headspace / no bubbles?
pH acceptable upon receipt (Metal: <2; 522: <4; 218.7: >8)? Yes No NA
Temp:
Chain of Custody (COC) Information
Yes NoSample IDs noted by Client on COC?
Yes NoDate and Time of collection noted by Client on COC?
Yes NoSampler's name noted on COC?
Sample Receipt Information
Sample Preservation and Hold Time (HT) Information
Sample labels checked for correct preservation? Yes No
Project Name: R1167C66; CCCCD LA+HS Pre-Demo
Comments:
Total Chlorine tested and acceptable upon receipt for EPA 522? Yes No NA
UCMR3 Samples:
Free Chlorine tested and acceptable upon receipt for EPA 218.7, 300.1, 537, 539?
Yes No NA
Date and Time Received 4/20/2017 14:50
Received by: Jena Alfaro
Page 9 of 9
WorkOrder:
Report Created for: Terracon
1466 66th Street
Emeryville, CA 94608
Project Contact: Kenneth Pilgrim
Project Name: R1167C66; Health Science Bldg
Project P.O.:
Project Received: 05/11/2017
Analytical Report reviewed & approved for release on 05/31/2017 by:
Angela Rydelius,
Laboratory Manager
1705534
The report shall not be reproduced except in full, without the written
approval of the laboratory. The analytical results relate only to the
items tested. Results reported conform to the most current NELAP
standards, where applicable, unless otherwise stated in the case
narrative.
Analytical Report
1534 Willow Pass Rd. Pittsburg, CA 94565 ♦ TEL: (877) 252-9262 ♦ FAX: (925) 252-9269 ♦ www.mccampbell.com
CA ELAP 1644 ♦ NELAP 4033ORELAP
McCampbell Analytical, Inc."When Quality Counts"
Page 1 of 9
Glossary of Terms & Qualifier Definitions
Client: Terracon
Project: R1167C66; Health Science Bldg
WorkOrder: 1705534
McCampbell Analytical, Inc.1534 Willow Pass Road, Pittsburg, CA 94565-1701
Toll Free Telephone: (877) 252-9262 / Fax: (925) 252-9269
http://www.mccampbell.com / E-mail: [email protected]"When Quality Counts"
Glossary Abbreviation
%D Serial Dilution Percent Difference
95% Interval 95% Confident Interval
DF Dilution Factor
DI WET (DISTLC) Waste Extraction Test using DI water
DISS Dissolved (direct analysis of 0.45 µm filtered and acidified water sample)
DLT Dilution Test (Serial Dilution)
DUP Duplicate
EDL Estimated Detection Limit
ERS External reference sample. Second source calibration verification.
ITEF International Toxicity Equivalence Factor
LCS Laboratory Control Sample
MB Method Blank
MB % Rec % Recovery of Surrogate in Method Blank, if applicable
MDL Method Detection Limit
ML Minimum Level of Quantitation
MS Matrix Spike
MSD Matrix Spike Duplicate
N/A Not Applicable
ND Not detected at or above the indicated MDL or RL
NR Data Not Reported due to matrix interference or insufficient sample amount.
PDS Post Digestion Spike
PDSD Post Digestion Spike Duplicate
PF Prep Factor
RD Relative Difference
RL Reporting Limit (The RL is the lowest calibration standard in a multipoint calibration.)
RPD Relative Percent Deviation
RRT Relative Retention Time
SPK Val Spike Value
SPKRef Val Spike Reference Value
SPLP Synthetic Precipitation Leachate Procedure
ST Sorbent Tube
TCLP Toxicity Characteristic Leachate Procedure
TEQ Toxicity Equivalents
WET (STLC) Waste Extraction Test (Soluble Threshold Limit Concentration)
Page 2 of 9
Glossary of Terms & Qualifier Definitions
Client: Terracon
Project: R1167C66; Health Science Bldg
WorkOrder: 1705534
McCampbell Analytical, Inc.1534 Willow Pass Road, Pittsburg, CA 94565-1701
Toll Free Telephone: (877) 252-9262 / Fax: (925) 252-9269
http://www.mccampbell.com / E-mail: [email protected]"When Quality Counts"
Analytical Qualifiers
a4 reporting limits raised due to the sample's matrix prohibiting a full volume extraction.
h4 sulfuric acid permanganate (EPA 3665) cleanup
Page 3 of 9
Analytical Report
McCampbell Analytical, Inc.1534 Willow Pass Road, Pittsburg, CA 94565-1701
Toll Free Telephone: (877) 252-9262 / Fax: (925) 252-9269
http://www.mccampbell.com / E-mail: [email protected]"When Quality Counts"
Client: Terracon
Project: R1167C66; Health Science Bldg
Date Received: 5/11/17 16:30
Date Prepared: 5/11/17
WorkOrder: 1705534
Extraction Method: SW3550B/3630C
Analytical Method: SW8082
Unit: mg/kg
Polychlorinated Biphenyls (PCBs) Aroclors w/ Column Style Clean-up
PCB-3 1705534-001A Solid 05/09/2017 GC23 139363
Analytes Result DF Date AnalyzedRL
Client ID Lab ID Matrix Date Collected Instrument Batch ID
Aroclor1016 ND 0.50 10 05/30/2017 11:12
Aroclor1221 ND 0.50 10 05/30/2017 11:12
Aroclor1232 ND 0.50 10 05/30/2017 11:12
Aroclor1242 ND 0.50 10 05/30/2017 11:12
Aroclor1248 ND 0.50 10 05/30/2017 11:12
Aroclor1254 1.9 0.50 10 05/30/2017 11:12
Aroclor1260 ND 0.50 10 05/30/2017 11:12
PCBs, total 1.9 0.50 10 05/30/2017 11:12
Surrogates REC (%) Limits
Analyst(s): SS
Decachlorobiphenyl 108 70-130 05/30/2017 11:12
PCB-4 1705534-002A Solid 05/09/2017 GC22 139363
Analytes Result DF Date AnalyzedRL
Client ID Lab ID Matrix Date Collected Instrument Batch ID
Aroclor1016 ND 0.25 5 05/31/2017 13:45
Aroclor1221 ND 0.25 5 05/31/2017 13:45
Aroclor1232 ND 0.25 5 05/31/2017 13:45
Aroclor1242 ND 0.25 5 05/31/2017 13:45
Aroclor1248 ND 0.25 5 05/31/2017 13:45
Aroclor1254 1.1 0.25 5 05/31/2017 13:45
Aroclor1260 ND 0.25 5 05/31/2017 13:45
PCBs, total 1.1 0.25 5 05/31/2017 13:45
Surrogates REC (%) Limits
Analytical Comments: h4,a4Analyst(s): CK
Decachlorobiphenyl 86 70-130 05/31/2017 13:45
Angela Rydelius, Lab ManagerNELAP 4033ORELAP
Page 4 of 9
Quality Control Report
McCampbell Analytical, Inc.1534 Willow Pass Road, Pittsburg, CA 94565-1701
Toll Free Telephone: (877) 252-9262 / Fax: (925) 252-9269
http://www.mccampbell.com / E-mail: [email protected]"When Quality Counts"
Client: Terracon
Project: R1167C66; Health Science Bldg
Date Analyzed: 6/1/17
Date Prepared: 5/11/17
WorkOrder: 1705534
BatchID: 139363
Analytical Method: SW8082
Unit: mg/kg
Sample ID: MB/LCS/LCSD-139363
Instrument: GC23
Matrix: Soil
Extraction Method: SW3550B/3630C
QC Summary Report for SW8082 w/ Column Clean-up
Analyte MB
Result
RL SPK
Val
MB SS
%REC
MB SS
Limits
Aroclor1016 ND 0.050 - - -
Aroclor1221 ND 0.050 - - -
Aroclor1232 ND 0.050 - - -
Aroclor1242 ND 0.050 - - -
Aroclor1248 ND 0.050 - - -
Aroclor1254 ND 0.050 - - -
Aroclor1260 ND 0.050 - - -
Aroclor1262 ND 0.050 - - -
Aroclor1268 ND 0.050 - - -
PCBs, total ND 0.050 - - -
Surrogate Recovery
Decachlorobiphenyl 0.05851 0.050 117 70-130
Analyte LCS
Result
LCSD
Result
SPK
Val
LCS
%REC
LCSD
%REC
LCS/LCSD
Limits
RPD RPD
Limit
Aroclor1016 0.145 0.143 0.15 97 96 70-130 1.15 20
Aroclor1260 0.130 0.176 0.15 86 118 70-130 1.22 20
Surrogate Recovery
Decachlorobiphenyl 0.0584 0.0598 0.050 117 120 70-130 2.37 20
QA/QC OfficerNELAP 4033ORELAP
Page 5 of 9
McCampbell Analytical, Inc.1534 Willow Pass Rd
Pittsburg, CA 94565-1701
(925) 252-9262
CHAIN-OF-CUSTODY RECORD Page
Lab ID Matrix Collection Date Hold
Requested Tests (See legend below)
Report to:
Kenneth Pilgrim
1466 66th Street
Emeryville, CA 94608
(510) 547-7771 FAX: (510) 547-1983
PO:
05/11/2017
Client ID
ProjectNo: R1167C66; Health Science Bldg
WorkOrder: 1705534
1 of 1
Date Logged:
Date Received: 05/11/2017
1 2 3 4 5 6 7 8 9 10 11 12
Terracon
Bill to:
Anita G. Ilsley
Terracon
1466 66th Street
Emeryville, CA 94608
Requested TAT: 5 days;
ClientCode: RGAE
Email: [email protected]
EDF EQuIS Email HardCopy ThirdParty
Excel J-flagWriteOn
cc/3rd Party:
WaterTrax
A1705534-001 Solid 5/9/2017 00:00PCB-3
A1705534-002 Solid 5/9/2017 00:00PCB-4
Prepared by: Jena Alfaro
NOTE: Soil samples are discarded 60 days after results are reported unless other arrangements are made (Water samples are 30 days). Hazardous samples will be returned to client or disposed of at client expense.
Comments:
8082_PCB_Solid1 2 3 4
5 6 7 8
9 10
Test Legend:
11 12
Page 6 of 9
Lab ID Client ID Collection Date
& Time
Date Logged:
TATMatrix Test Name Containers
/Composites
WORK ORDER SUMMARY
Work Order: 1705534
Comments:
Client Name: TERRACON Project: R1167C66; Health Science Bldg
QC Level: LEVEL 2
HoldDe-
chlorinated
SubOutBottle & Preservative
5/11/2017
Sediment
Content
EDF Fax Email HardCopy ThirdPartyExcel J-flagWriteOn
Kenneth PilgrimClient Contact:
[email protected]'s Email:
WaterTrax
McCampbell Analytical, Inc.1534 Willow Pass Road, Pittsburg, CA 94565-1701
Toll Free Telephone: (877) 252-9262 / Fax: (925) 252-9269
http://www.mccampbell.com / E-mail: [email protected]"When Quality Counts"
1705534-001A PCB-3 5/9/2017 5 daysSolid SW8082 (PCBs Only) 1 Plastic Baggie, Small
1705534-002A PCB-4 5/9/2017 5 daysSolid SW8082 (PCBs Only) 1 Plastic Baggie, Small
1 of 1Page
- STLC and TCLP extractions require 2 days to complete; therefore, all TATs begin after the extraction is completed (i.e., One-day TAT yields results
in 3 days from sample submission).
NOTES:
- MAI assumes that all material present in the provided sampling container is considered part of the sample - MAI does not exclude any material from
the sample prior to sample preparation unless requested in writing by the client.
Page 7 of 9
Page 8 of 9
Sample Receipt Checklist
McCampbell Analytical, Inc.1534 Willow Pass Road, Pittsburg, CA 94565-1701
Toll Free Telephone: (877) 252-9262 / Fax: (925) 252-9269
http://www.mccampbell.com / E-mail: [email protected]"When Quality Counts"
Client Name: Terracon
WorkOrder №: 1705534
Date Logged: 5/11/2017
Logged by: Jena AlfaroMatrix: Solid
Carrier: Bernie Cummins (MAI Courier)
Shipping container/cooler in good condition? Yes No
Custody seals intact on shipping container/cooler? Yes No NA
Samples Received on Ice? Yes No
Chain of custody present? Yes No
Chain of custody signed when relinquished and received? Yes No
Chain of custody agrees with sample labels? Yes No
Samples in proper containers/bottles? Yes No
Sample containers intact? Yes No
Sufficient sample volume for indicated test? Yes No
NAAll samples received within holding time? Yes No
NASample/Temp Blank temperature
Yes No NAWater - VOA vials have zero headspace / no bubbles?
pH acceptable upon receipt (Metal: <2; 522: <4; 218.7: >8)? Yes No NA
Temp:
Chain of Custody (COC) Information
Yes NoSample IDs noted by Client on COC?
Yes NoDate and Time of collection noted by Client on COC?
Yes NoSampler's name noted on COC?
Sample Receipt Information
Sample Preservation and Hold Time (HT) Information
Sample labels checked for correct preservation? Yes No
Project Name: R1167C66; Health Science Bldg
Comments:
Total Chlorine tested and acceptable upon receipt for EPA 522? Yes No NA
UCMR3 Samples:
Free Chlorine tested and acceptable upon receipt for EPA 218.7, 300.1, 537, 539?
Yes No NA
Date and Time Received 5/11/2017 16:30
Received by: Jena Alfaro
Page 9 of 9
Appendix 4
Sample Location Figures
Sheet Number
Sheet Name
Project Number
Date Drafted By
Checked By
June 14, 2017 RC
KP
Roof
Figure 1Not to Scale
N
R1167C66
Note: Sample location figures are for informational purposes and are approximate innature. No scale is associated with any of the provided documents.
Contra Costa CollegeHealth & Science Building2600 Mission Bell Drive
San Pablo, California
21A
21B
21C24B
21D
21E
24C22C
22B
22A
23C
23A
23B
24A
87C
87B
87A
Sheet Number
Sheet Name
Project Number
Date Drafted By
Checked By
June 14, 2017 RC
KP
2nd Floor
Figure 2Not to Scale
N
R1167C66
Note: Sample location figures are for informational purposes and are approximate innature. No scale is associated with any of the provided documents.
Contra Costa CollegeHealth & Science Building2600 Mission Bell Drive
San Pablo, California
Sheet Number
Sheet Name
Project Number
Date Drafted By
Checked By
June 14, 2017 RC
KP
Ground Floor
Figure 3Not to Scale
N
R1167C66
Note: Sample location figures are for informational purposes and are approximate innature. No scale is associated with any of the provided documents.
Contra Costa CollegeHealth & Science Building2600 Mission Bell Drive
San Pablo, California
Appendix 5
Inspectors Certifications