Sr. no. Document Clause no /Sr.No of BOQ
Description Query Query raised by AEMLRemark Inclusion in Corrigendum
A1 NIT NIT Qualifying criteria ‐ Clarification The registered bidders who have not
supplieed cables for last 4‐5 years, a fresh visit to their plant shall be conducted by AEML while evaluating them.
Yes
2 NIT ‐ Spec for control cables ‐ Clarification Attached as Annexure Yes3 Tech Spec
SP‐CES‐EL‐LT‐CBL‐R012.1.5A Binder tape Binder tape or rubberised cotton
tapeClarification Rubberised cotton tape as per AEML spec. Yes
4 Tech SpecSP‐CES‐EL‐LT‐CBL‐R01
3.0.0 Type test on one cable drum of eachtype/rating, from the first lot, shall beconducted at Govt.‐approved /Internationally accredited labs.
Shall the sample be tested from 3rd party NABL accredited Lab?
Clarification Only CPRI/ERDA testing acceptable Yes
5 Tech SpecSP‐CES‐EL‐LT‐CBL‐R01
3.0.0 b Drum marking ‐ Clarification Progressive (sequential) length ofcable at every meter, starting from zero for everydrum.Drum no to be printed along with sequential marking.
Yes
B1 SCC Payment Terms LC payment terms Revised Payment Terms as 100% payment
with in 60 days(Credit) from the date of receipt & acceptance of material at store.(45 Days‐Credit for MSME Vendors).
YES
2 Open Tender NIT EMD value Reduction in EMD value Revised EMD value is Rs.12 Lakhs Yes
Commercial Points
Pre‐Bid Meeting ‐LT cables(NIT NO AEML/MDB/2019‐20/11)Technical QueryParticipants:
1. KEI‐ Mr. N L Parab2. Ravin ‐ Mr. Prakash Lakhkar3. KEC ‐ Kaushik Waghela4. Polycab ‐ Mr. Sachin Gupta & Mr. Mushtaq Shaikh5. RR Kabel ‐ Mr. Smit Shah6. Laser cables ‐ Mr.Aniruddha banerjee & Mr.Suresh Kedia7. Zenium Cables ‐ Mr.Sachin Dhorlekar8. AEML‐ Ashweni Jain, Damodar Sahasrabudhe, Tanu Srivastava, Deep Muntode, Devendra Mahajan
MOM:
1. AEML explained the scope of supply, Technical Specification requirements to Bidders. 2. During pre‐bid meeting, Bidders raised queries, response of which is attached herewith.3. In case Bidders wish to send additional Technical queries, they can send mails to CES Dept. with a copy to CPG.
Technical Points
Specification No. SP-CES-EL-LT-CBL-R01 Rev No. R01
Prepared By Checked By Reviewed By Approved By Date
05/04/2019
TS AKJ DRS SPS PVC
Technical Specification on LT cables
Index
1. Revision Record…………………………………………………………………..................................3
2. General Specification………………………………………………..........................................4
3. Annexure A : Scope, Documentation and Delivery Schedule……………................................16
4. Annexure B : Guaranteed Technical Particulars (GTP)……………………....................................18
5. Annexure C : Service Conditions…………………………………………………................................................23
Revision Record
Item/ clause
no: Nature of Change
Approved by
Rev.
No. Revision
record Revision record added. DSP/AM R1
6.0.0 Drum lengths revised size-wise DSP/AM R1
2.1.6 Batch No./ Lot no. added for embossing DSP/AM R1
Annexure – B -GTP. 9.0.0
Eccentricity of insulation - added DSP/AM R1
2.1.4 Ovality over the core added. DSP/AM R1
2.1.6 Anti-Tracking & Anti-rodent properties for outer sheath - added
DSP/AM R1
5.0.0 Cross-sectional drawings – details stated. DSP/AM R1
2.1.5 Armour coverage percentage calculation - added DSP/AM R1
Annexure – A - Scope / Documentation / Delivery - added.
DSP/AM R1
Annexure – B - Combined GTP prepared for Multi-core and single core cables.
DSP/AM R1
Annexure – C Service Conditions - added.
DSP/AM R1
GENERAL SPECIFICATION
1.0.0 Codes & Standards :
The cables shall be designed, manufactured and tested in accordance with the following Indian & IEC standards.
National Standards
IS- 7098
Part-1 Cross-Linked Polyethylene Insulated PVC sheathed
cables (For working voltage upto & including 1100 V)
IS 1554 Part-1 PVC insulated Cables
IS- 6474 : 1984 Polyethylene insulation & sheath of electric cables.
IS- 5831 : 1984 PVC insulation & sheath of electric cables.
IS- 10810 : 1984 Methods of test for cables.
IS- 8130 : 1984 Conductors for insulated electric cables and flexible cords.
IS- 3975 : 1999 Mild steel wires, formed wires and tapes for armouring of cables.
IS 613 Copper Rods and Bars for Electrical Purposes - Specification
International Standards
IEC 228 Conductors of insulated cables. Guide to the
dimensional limits of circular conductors.
IEC 331 Fire resisting characteristics of electric cables. IEC 332 - 3 Tests on electric cables under fire conditions. Part 3:
Tests on bunched wires or cables.
IEC 502 Extruded solid dielectric insulated power cables for rated voltages from 1kV to 30 kV.
IEC 754 - 1 Test on gases evolved during combustion of materials from cables. Part 1: Determination of the amount of halogen acid gas evolved during combustion of polymeric material taken from cables.
IEC 811 Pts 1 through 5
Common test methods for insulating and sheathing materials of electric cables.
IEC 885 Pts 1 through 3
Electric test methods for electric cables.
IEC 304 Standard colours for insulation for low frequency cables and wires.
IEC 227 01-1 through 6 PVC insulated cables of rated voltages up to and including 450/750 V.
IEC 1034 Pts 1 & 2 Measurement of smoke density of electric cables burning under defined conditions.
IEC 28 International Standard of Resistance for Copper IEC 60840 Tests on extruded power cables
International Standards
IEC 60228 Conductors of insulated cables. Guide to the dimensional
limits of
circular conductors. IEC 60331 Fire resisting characteristics of electric cables.
IEC 60502 - 2 Extruded solid dielectric insulated power cables for rated voltages
from 1kV to 30 kV. IEC 60811 Pts 1 through 5
Common test methods for insulating and sheathing materials of
electric cables. IEC 60885 Pts 1 through 3
Electric test methods for electric cables.
IEC 60304 Standard colours for insulation for low frequency cables and wires.
IEC 60227 01 - 1 through 6
PVC insulated cables of rated voltages up to and including 450/750
V. IEC 1034 Pts 1 & 2
Measurement of smoke density of electric cables burning under
defined conditions. IEC 60028 International Standard of Resistance for Copper
IEC 60840 Tests on extruded power cables
ASTM-D-2843
® Smoke Density Rating as per ASTM
ASTM-D-2863
® a)
b)
Oxygen Index Test
Temperature Index IEC 60754 - 1 Test on gases evolved during combustion of materials
from cables. Part 1: Determination of the amount of
halogen acid gas evolved during combustion of
polymeric material taken from cables.
(HCL gas emission test - by weight) IEC 60332 – 1 Tests on electric cables under fire conditions :
Test for vertical flame propagation for a single insulated wire or cable.
IEEE - 383 Flame Retardancy Test - Ladder Test
SS-424-14-75
® Swedish Chimney Test
BICC Handbook Chapter 6 on Cable in fire
2.0.0 Cable Construction Features
This Specification generally covers following types / sizes of
L. T. Cables used in network in Mumbai Discom area (mostly
under-ground) or any Project site (mostly over-ground) :
Note : (Ref. : Table stating Cable sizes given below.)
a) Cable Designation :
As per IS, cable designation shall comprise of
following codes / options, as applicable for this
Specification :
(N.A. - Not applicable in this Specification)
- (with Copper conductor)
A Aluminium conductor
--------------------------------------------------------
2X XLPE insulation
--------------------------------------------------------
W Steel round Wire armour
W W Double steel round Wire armour (N.A.)
Wa Non-magnetic round Wire armour
(mostly, aluminium,
hard-drawn H4 grade) F
Steel formed wire
(strip) armour
FF Double steel formed wire (strip) armour (N.A.)
Fa Non-magnetic formed wire (strip) armour (N.A.)
- (un-armoured or without armour)
--------------------------------------------------------
Y PVC outer sheath
b) Standard cable sizes
are marked as **
(appearing in this
colour).
c) Cable sizes for Transmission
Project are marked as ***
(appearing in this colour).
d) Single-core Cables (1c x 500 and 1c x 630 sq. mm) with
FRLS properties are included in the List of Cables below
in this colour. Also, relevant text from following
Specification for these 1-core Cables, is also incorporated
in this Specification :
Sr. No.
Description Cable Code (a)
Multi-core Cables 1 1.1 kV, 2c x 25 sq. mm. Al A2XFY 2 1.1 kV, 4c x 25 sq. mm. Al (b) A2XFY
3 1.1 kV, 4c x 50 sq. mm. Al (b) A2XFY
4 1.1 kV, 3.5c x 150 sq. mm. Al (b) A2XFY
5 1.1 kV, 3.5c x 300 sq. mm. Al (b) A2XWY Or A2XFY
Single-core Cables 6 1.1 kV, 1c x 500 sq. mm. Al (unarmoured) (
d)
A2X-Y
7 1.1 kV, 1c x 500 sq. mm. Al (armoured) A2X-WaY
8 1.1 kV, 1c x 630 sq. mm. Al (unarmoured) (d)
A2X Y A2X Y
The L. T. Cables shall be suitable for laying under-ground
(buried, with chances of flooding by water) or for laying on
racks, in ducts, trenches, conduits, and so on. Purchaser to
state specific usage / requirement (refer Annexure-D). ®
Description of each item mentioned in the Specification (the
text, BOQ, GTP or Site Specific Requirement) shall be
followed, along with IS : 7098 – Part 1.
2.1.1 Conductor Aluminium conductor Electrolytic Grade Stranded Aluminium Conductor
Grade : H2 / H4 (hard-drawn) as per IS: 8130 / 84
Shape of Cables i) Stranded Compacted Circular :
-- for mult-core cables, sizes upto
10 sq. mm.
-- for single core cables.
ii) Stranded Compacted Sector-shaped : for
multi-core cables, sizes from 16 sq. mm. and
above.
2.1.2 Insulation a) Extruded XLPE (Cross-Linked Poly-Ethylene)
Insulation
b) Entire XLPE Insulation shall be coloured
(pigmented), as per phases / neutral, as given below
:
(ref. IS : 7089 Part-1)
i) For 3.5-core and 4 -core cables :
Colour : red, yellow, blue, black
ii) For single-core cables : Colour : natural (non-pigmented)
2.1.3 Core Identification a) As per Cl.10 of IS 7098 Part-1.
b) Also refer Cl. 2.1.2 (Insulation) and the GTP.
2.1.3A Core Binding Tape Core binding tape shall be with 50 % overlap.
2.1.3B Filler Fillers, where applicable, shall be of non-hygroscopic
material, compatible with the temperature ratings of the
cable and shall have no deleterious effect on any
component of the cable
2.1.3C Binding Tape over Laid-up cores
Thickness of this tape shall not be construed as part of the thickness of Inner Sheath.
2.1.4 Inner Sheath (common
covering) a) Extruded Inner Sheath of PVC type ST-2 (IS 5831), for
multi-core Cables.
b) Colour - Black
c) Shape over the inner sheath shall be circular. Ovality
check shall be carried out, as applicable.
d) If Cable is 1-core, then there shall be no inner
sheath. However, then in place of inner sheath, there
shall be a protective barrier, of type depending on
whether the 1-core Cable is with armour or un-
armoured, as per manufacturer’s
standard.
2.1.5 Armour a) i) Armour shall be as per cable codes as indicated in the table in the beginning
ii) However, as per IS, if the diameter below armour is
upto & including 13 mm, the armour shall be
:Galvanised Steel Round Wire, as applicable.
b) Single core cables of standard sizes of 500 sq. mm.
and 630 sq. mm., are normally used between Distribution
Transformers and L.T. Panels in a sub- station. Hence,
these single-core sizes shall be without armour (un-
armoured).
[ Note : Armouring, if required for 1-core Cables, it
shall be of Aluminium round wire H4 grade. ]
Area of Coverage of armouring shall be 90 % minimum. (Armour coverage percentage calculation shall be submitted.)
2.1.5A Binder Tape Rubberised Cotton Tape (desirable)
2.1.6 Outer Sheath a) Extruded outer sheath of PVC (Poly-Vinyl Chloride)
compound, conforming to the requirement of ST-2
type compound (ref. IS : 5831), with anti-termite
and anti-rodent properties.
b) Shape of the completed cable over the outer
sheath shall be circular
c) Ovality check shall be carried out.
d) Colour :
Yellow - For Multi-core cables
e) Black - For Single-core 500 / 630 sq. mm.)
f) The Outer Sheath shall be embossed with :
1. The voltage designation (1100 V)
2. Type of construction / cable code
(example : A2XFY)
3. Manufacturer’s Name or and Trade mark 4. Number of Cores and nominal cross-sectional
area of conductor
5. The drum progressive length of cable at
every metre, starting from zero for every drum.
Colour filled in in the progressive marking shall be with
proper contrast as follows :
i) Black colour shall be used for marking in case
of cables with Yellow colour for the outer
sheath.
ii) White colour shall be used for marking in case
of cables with Black colour for the outer
sheath.
6. Name of buyer/purchaser,
7. Month & Year of manufacturing
8. IS reference, i.e. IS : 7098
9. Lot no. / Batch no
10. Purchase Order Number & date
11. Word ‘FRLSH’, in case the cable is FRLSH type.
2.1.7 Sealing of Cable end Both ends of the cable shall be sealed with PVC Cap.
After fixing, the PVC cap shall be filled with P.
U. (Poly-Urethane) Compound through a cut provided in
the cap. Further, a Heat Shrinkable cap (H. S. cap) shall
be shrunk over the PVC cap to fully prevent any water
seepage through the cable end
(even though dipped in water).
3.0.0 Manufacturing Process for XLPE Insulation
a) Sioplas b) Dry cure / Gas cure
Testing & Inspection Tests shall be carried out in accordance with IEC /
ASTM / IS standards. a) Type Test
1) Cables must be of type tested quality. TTRs
(Type Test Report) shall be submitted for the
type, size & rating of cable offered along with
bid.
2) If the manufacturer’s lab is accredited by govt. /
authorised body, then it shall beacceptable for
type testing
3) Type test on one cable drum of each rating and
type, from first lot, shall be conducted at Govt.
approved / Internationally accredited labs.
4) Refer Annexure-C for Special Tests to be
carried out on Outer Sheath of FRLS Cables,
where applicable.
b) Routine Tests
1. Measurement of Electrical Resistance
(Conductor Resistance Test)
2. High Voltage Test,
with power frequency AC voltage, at room
temperature.
3. Measurement of Insulation Resistance (I.R.) c) Inspection
1. The Buyer reserves the right to witness all tests
specified on completed cables.
2. The Buyer reserves the right to inspect cables at the
Sellers works at any time prior to dispatch, to prove
compliance with the specifications.
3. In-process and final inspection call intimation shall be given in advance to purchaser
i) Acceptance test : ii) Shall be conducted as per Cl.15.2 of IS 7098 Part-1
for each lot of cable. iii) Ovality check over the cores and over the
completed Cables, as applicable. iv) Refer Annexure-C for Special Tests to be carried out
on Outer Sheath of FRLS Cables, where applicable.
v) Test certificates : Three sets of complete test certificates (routine & acceptance tests) need to be submitted along with the delivery of cables.
Drawing, Data & Manuals Refer Annexure – A also To be submitted along with
bid The seller has to submit as follows :
a) Cross-section drawing of cable :
Cross-Sectional Drawing shall show every feature of
construction, including the thickness / diameter over
every layer. This drawing shall also indicate the
embossing of text to appear over the outer sheath,
giving type/size, etc. of the cable, drum no./lot no.,
sequential marking over every meter (marking to
start from zero for every drum), font sizes to be used,
additional text, if any, etc. Also, Drum details,
markings to be made on both sides of the drum, and
so on.
®
b) Completely filled GTP
c) Type Test Report (TTR) Complete Cable Catalogue and Manual along with the bid.
After award of contract Within 15 days, the seller has to submit four sets of
above-mentioned drawings for buyer’s approval Final As Built 6 sets hardcopy + One Soft copy of all documents
including type test certificates Cable Drums Drum Length & tolerance :
For 2c x 25 sq. mm. cable drum :
1000 mm +/- 5 % For all other sizes : 500 mm +/- 5 %
Overall cable length for the
order +/- 2 % tolerance for the entire order.
Short length of cables a) Minimum acceptable short length shall be more
than 100 metres.
(Should it be “not less than 250 m”)
Manufacturer shall be required to take prior approvalfrom AEML (Engineering & Procurement) for any short length supply
b) Manufacturer shall not be allowed to put two cable pieces of different short lengths in same cable drum.
Packing, Shipping, Handling
& Storage
a) Packing i) Both the ends of the cables shall be properly sealed
to prevent any deterioration of the cable, due to
ingress of water, etc.
ii) Cable starting end shall project, outside the
completely wound cable, by sufficient length
enabling verify cable details, including the starting-
end length marking. ®
iii) Similarly,both ends of the cable shall be saddled
/ secured to the drum properly to prevent any
damage to the ends any time. ®
iv) Before putting on wooden planks, protective
covers (thick plastic sheets, etc.) shall be secured
over the wound cable, to avoid any abrasion by
wooden planks, over the outer sheath of the cable.
®
v) After providing the protective covers, the cable
drums shall be finally closed by wooden planks
(with saddles), without leaving any gaps between
the planks; i.e. 100 % covering
shall be ensured. ® b) Drum Identification
markings Direct markings (i.e. text painting through stencils, etc,)
shall be done on the drums, instead of attaching labels,
which may be misplaced/lost over a period of time. ®
1. Drum identification number
2. Cable voltage grade
3. Cable code (e.g. A2XFY, etc.)
4. Number of cores and cross sectional area
5. Cable quantity, i.e. cable length (Metre)
6. Purchase order number & date
7. SAP item code 8. Total weight of cable and drum (kg)
9. Manufacturer's Name
10. Buyer’s name
11. Month & Year of Manufacturing
12. Direction of rotation of drum
13. Cable length final end-markings
(i. e., initial reading and end reading seen on the cable shall be marked on the drum.)
c) Shipping information The seller shall give complete shipping information concerning the weight, size of each package
d) Transit damage The seller shall be held responsible for all transit damage due to improper packing.
e) Type of Drum and Drum handling
Steel / wooden drums, as per relevant IS / IEC.
i) Wooden drums shall be with M.S. spindle plate with
nut-bolts.
ii) Spindle Plate hole diameter : ®
for 25 / 50 sq.mm. cable drums : 80 mm dia. for
150 / 300 sq.mm. cable drums : 110 mm dia.
-- to suit spindle rod, while handling as per expected weight of the cable drums.
8.0.0 Quality Assurance 8.0.1 Vendor quality plan To be submitted for purchaser approval
8.0.2 Inspection points To be mutually identified & agreed in quality plan
9.0.0 Progress reporting 9.0.1 Outline Document To be submitted for purchaser approval for outline of
production, inspection, testing, inspection, packing, dispatch, documentation programme
9.0.2 Detailed Progress report To be submitted to Purchaser once a month
containing
i) Progress on material procurement
ii) Progress on fabrication (As
applicable)
iii) Progress on assembly (As applicable)
iv) Progress on internal stage inspection
v) Reason for any delay in total programme
vi) Details of test failures if any in manufacturing stages
vii) Progress on final box Constraints / Forward iv) path
10.0.0 Deviation a) Deviations from this specification are only
acceptable where the Seller has listed in his
quotation the requirements he cannot, or does not,
wish to comply with and the Buyer has accepted, in
writing, the deviations before the order is placed.
b) In the absence of a list of deviations, it will be
assumed by the Buyer that the Seller complies
fully with this specification.
Annexure - A
Scope, Documentation and Delivery Schedule
1. Scope
A. Scope Design, manufacture, testing at
manufacturer’s works before dispatch,
packing, delivery, unloading, stacking at
stores/site of L. T. Power
cables as per Bill of Quantity (BOQ). B. Delivery Schedule To be filled up on a case-to-case basis.
2. Document Submission
Submission of drawings, calculations, catalogues, manuals,
test reports shall be as follows :
(Legend : GTP - Guaranteed Technical Particulars,
TTR - Type Test Report, RTR - Routine Test Report)
Along with offer For Approval
(after award
of
contract)
Final documents
(after approval)
GTP 3 copies 4 copies + 1 soft copy
6 copies +
1 soft copy in CD Drawings 3 copies
(Typical drawings)
4 copies + 1 soft copy
6 copies +
1 soft copy in CD Calculations 3 copies
(Typical)
4 copies + 1 soft copy
6 copies +
1 soft copy in CD Catalogues &
Manual
1 copy 6 copies +
1 soft copy in CD Test Report 2 copies of TTR
and
sample RTR **
6 copies +
1 soft copy in CD
1. Delivery Schedule
a) Delivery period Start Date : from date of LOI
b) Delivery period End Date : as agreed with supplier
c) Material dispatch Clearance : after inspection by purchaser
Annexure – B
GUARANTEED TECHNICAL PARTICULARS (GTP)
(For Multi-core and Single-core Power Cables)
Note : 1) Each data shall be given for every type / size of
cable. Seller may give separate GTP for every
type / size of cable, if necessary.
2) GTP shall be read in line with purchaser’s Site Specific Requirement.
Sr. No.
Description Unit Buyer’s requirement Seller’s Data
1.0 Purchase Req. No. 2.0 Guarantee Period (Min.) 60 Months (from date
of commissioning) / 66 Months (from date of receipt at purchaser’s store) whichever is earlier
3.0 Applicable IS Standard followed by vendor
IS 7098 Part-1
4.0 Make 5.0 Type (1.1 kV)
Multi-core Cables
1.1 kV, 2c x 25 sq. mm.
Al A 2X F Y
1.1 kV,
4c x 25 sq. mm.
Al A 2X F Y
1.1 kV,
4c x 50
sq. mm.
Al A 2X F Y
1.1 kV, 3.5c x 150 sq. mm.
Al A 2X F Y
1.1 kV, 3.5c x 300 sq. mm
Al A or A
2X 2X
W Y
F Y
Single-core Cables
1.1 kV, 1c x 500 sq. mm.
(unarmoured) (d)
Al A 2X - Y
1.1 kV, 1c x 500 sq. mm.
(armoured) (d)
Al A 2X Wa Y
1.1 kV, 1c x 630 sq. mm.
Al A 2X - Y
(unarmoured) (d)
6.0 Voltage Grade kV 1.1 7.0 Cable Condition Conductor temperature
/ Insulation required
Cables used for Power needs : Expected Maximum Conductor temperature during :
i) Normal Continuous Operation
deg. C 90°C
ii) Short time Circuit Condition
deg. C 250°C
iii) Due to (i) and (ii) above XLPE Insulation adopted.
8.0 Conductor Grade : H2
as per IS: 8130 / 84
a. Material and Grade b. Size sq. mm. As shown
under 5.0 above
c. Wires in each conductor Nos. As per Manufacturer standard /
as per IS 8130
d. Conductor Shape Multi-core
/ Single- core
As per Cl. 2.1.1
e. Dia. of wires in each conductor before compaction
mm As per Manufacturer Standard
f. Diameter over conductor mm g. Maximum Conductor
resistance at 20 C
ohm / km
As per Table 2 of IS 8130
h. Longitudinal Water Barrier Protection ® (if required by purchaser)
Is it provided and shown in the cross-sectional drawing
? (Yes / No)
9.0 Insulation Extruded
XLPE
a. Insulation Material b. Make and grade of
Insulation compound
c. Nominal thickness As per Table 3 of IS 7098
Part-1
d. Minimum thickness mm
e. Eccentricity ® % As per Standards
f. Diameter over Insulation (Approx.)
mm
g. Ovality check over the core, As applicable. ®
%
10.0 Layers over the Insulation a Water Swellable tape
(if required by purchaser) ®
Project Site Specific Requirements
b. Cable core identification (By means of coloured insulation) ®
a) As per Cl. 10 of IS 7098 Part-1
b) For 3.5c / 4c cables : R,Y,B,BLACK
c) For 1-core cables : Natural
c. Diameter over laid up core (Approx.)
mm
11.0 Fillers
(Material and type) As per Cl. …….
a) For multi-core Cables Applicable (Specify no. & size of fillers at center & core interstices
for each type of cable.)
b) For single-core Cables Not applicable 11.0 Inner Sheath a. Material and type Extruded PVC type ST-
2
b. Minimum thickness As per Table 5 of IS 7098 Part-1
a) For multi-core Cables State thickness for each type of cable.
b) For single-core Cables Not applicable c. Colour Black d. Diameter over inner sheath
(apprx.) mm
12.0 Armour a) As per Table 6
of IS 7098 Part-1
b) As per manufacturer’s Standard
a. a) Multi-core cable No. G. I. Strip / G. I. Wire,
as applicable as per IS.
b) Single-core cable No. Not required b. Armour - GI strips
a) Width of strip b) Thickness of strip c) Number of strips
mm i) 4 x 0.8 ii) As per Manufacturer
Standard
c. Armour – wires (where applicable)
a) Diameter of wire b) Number of wires
As per IS 7098 Part-1
d. Approx. Equivalent Area sq. mm. e.
Area covered by Armour % Min. 90 % Calculation sheet shall
be attached. ®
f. Fault current carrying capacity of armour ® ---- Required ? -------
… kA for … sec.
Calculation sheet shall be attached.
G Dia. over Armour (apprx.) mm 13.0 Outer Sheath As per Table 8 of
IS 7098 Part-1
a. Material and type Extruded PVC (ST-2), with anti-termite and anti-
rodent properties b. FR-LSH Properties (as per
Site Specific Requirements) ®
If required by Purchaser -- Provided ?
– yes / no
c. Make & Grade of compound used
d. Thickness (minimum) As per IS 7098 Part-1 e. Colour For multi-core :
Yellow For single-core : Black
®
f. Embossing As per Cl. 2.1.6 (d) Provided - Yes / No
14.0 Overall diameter of Cable
(apprx.) mm
15.0 Standard drum length with
tolerance 500 +/- 5 %
(In case of 2c x 25 sq.mm., 1000 +/- 5 %)
16.0 Cable Drum ® a. Type of drum Steel / Wooden
(Specify the relevant IS
followed for drum design)
b. Drum markings - as per Specification
Provided ? - Yes / No
c. Markings on both faces - as required by purchser
Provided ? - Yes / No
d. Drums with M. S. spindle plates with nut-bolt arrangement
Provided ? - Yes / No
(Refer sizes in the Spec.)
17.0 - A
Cross-Sectional Drawing (ref. Cl. 5.0.0) ®
Is drawing submitted, showing every feature of constructions ?
(Yes / No)
- B Sealing End-Cap
(required at both the ends) PVC cap + P.U. Compound + H.S. cap
Is manufacturer’s drawing submitted ?
(Yes / No)
18.0 A
MS Spindle Plate & nut-bolt arrangement for drum
Provided -- Yes / No
19.0 Weights a) Net weight of cable (
apprx.) kg / km
b) Weight of empty drum Kg c) Weight of cable with
drum kg
20.0 Continuous current rating
for standard I. S. condition laid Direct
a. In ground 30 C Amp b. In duct 30 C Amp c. In air 40 C Amp 21.0 Short circuit current
carrying capacity of conductor
kA for 1 sec.
22.0 Electrical Parameters at
Maximum Operating temperature:
a. AC Resistance ohm / km
b. Reactance at 50 c/s ohm / km
c. Impedance ohm / km
d. Capacitance micro- farad / km
23.0 Recommended minimum
bending radius mm ……. x Overall Dia.
of Cable
24.0 Derating factor for following
Ambient Temperatures : Ground / Air
a. At 30 C b. At 35 C c. At 40 C
d. At 45 C e. At 50 C 25.0 Group factor for following
numbers of cables laid : Touching Trefoil
a. 3 Nos. b. 4 Nos. c. 5 Nos. d. 6 Nos. 26.0 Recommended pressure for
laying cable using power winch ® ------ Is it required ? ---------
N / sq. mm.
30 N / sq. mm. (to be checked)
27.0 Process of Cross linking of
Polyethylene Sio-plas cure / Dry cure
/ Gas cure
28.0 Type test ®
(TTR - Type Test Report) Applicable TTR no. and
date, pertaining to the type and size of cable being
offered here.
29.0 Quality Assurance Plan
(QAP) ®
Submitted ? - Yes / No
30.0 List of Sub-Vendors Is this list attached ? (Yes / No)
Annexure - C
Service Conditions
(Atmospheric / Soil conditions at Site)
A. Mumbai
a) Average grade
Atmospheric condition
Heavily polluted, salt-laden, dusty, humid
with possibility of condensation b) Average grade
Soil condition
Water-logged
c) Maximum altitude above sea
level
1000 M
d) Ambient air temperature Highest 45 deg C, average 35 deg C
e) Minimum ambient air
temperature
20 deg C
f) Relative Humidity 100 % Max
g) Thermal Resistivity of Soil 120 deg. C cm/W
h) Seismic Zone 3
i) Rainfall 3000 mm concentrated in four months
Scanned by CamScanner