25
Jeff Schramuk NACE CP Specialist #7695 4/24/2015 www.cpsolutionsinc.net 1 1 Practical Solutions to External Corrosion Problems on Buried Water Mains Jeff Schramuk NACE CP Specialist #7695 630-235-1559 www.cpsolutionsinc.net Illinois Section AWWA Annual WDC: 4/28/2015 2 1. Corrosion Problems Facing Water Utilities 2. Asset Management 3. Understanding Corrosion Terminology 4. Pipe Materials and Coatings 5. Basic Cathodic Protection 6. CP for Existing WMs using an Anode Retrofit Program 7. Solving Corrosion Problems at WM Breaks 8. Cathodic Protection Performance Verification Topics to be Covered

Practical Solutions to External Corrosion Problems …...Jeff Schramuk NACE CP Specialist #7695 4/24/2015 1 1 Practical Solutions to External Corrosion Problems on Buried Water Mains

  • Upload
    others

  • View
    4

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Practical Solutions to External Corrosion Problems …...Jeff Schramuk NACE CP Specialist #7695 4/24/2015 1 1 Practical Solutions to External Corrosion Problems on Buried Water Mains

Jeff Schramuk NACE CP Specialist #7695

4/24/2015

www.cpsolutionsinc.net 1

1

Practical Solutions to External Corrosion Problems

on Buried Water Mains

Jeff SchramukNACE CP Specialist #7695

630-235-1559www.cpsolutionsinc.net

Illinois Section AWWA Annual WDC: 4/28/2015

2

1. Corrosion Problems Facing Water Utilities

2. Asset Management

3. Understanding Corrosion Terminology

4. Pipe Materials and Coatings

5. Basic Cathodic Protection

6. CP for Existing WMs using an Anode Retrofit Program

7. Solving Corrosion Problems at WM Breaks

8. Cathodic Protection Performance Verification

Topics to be Covered

Page 2: Practical Solutions to External Corrosion Problems …...Jeff Schramuk NACE CP Specialist #7695 4/24/2015 1 1 Practical Solutions to External Corrosion Problems on Buried Water Mains

Jeff Schramuk NACE CP Specialist #7695

4/24/2015

www.cpsolutionsinc.net 2

3

Module 1 Corrosion Problems

Facing Water Utilities

4

What’s the Rest of the (Unexcavated) Pipe Look Like?

Page 3: Practical Solutions to External Corrosion Problems …...Jeff Schramuk NACE CP Specialist #7695 4/24/2015 1 1 Practical Solutions to External Corrosion Problems on Buried Water Mains

Jeff Schramuk NACE CP Specialist #7695

4/24/2015

www.cpsolutionsinc.net 3

5

What Are the Consequences of Pipeline Failures?

Water Main BreaksEnergy Pipeline “Incidents”

6

Module 2 Asset Management

Page 4: Practical Solutions to External Corrosion Problems …...Jeff Schramuk NACE CP Specialist #7695 4/24/2015 1 1 Practical Solutions to External Corrosion Problems on Buried Water Mains

Jeff Schramuk NACE CP Specialist #7695

4/24/2015

www.cpsolutionsinc.net 4

7

“A water utility’s asset management plan is an optimization process that

attempts to meet the competing objectives of cost minimization and

reliability maximization.”

Source: Rubin, S.J., A Call for Reliability Standards, Journal AWWA, (Jan-2011)

Asset Management: A Real-World Definition

8

Risk = (Likelihood of Failure) x (Consequence of Failure)

Evaluating Failure Risk: Probability vs. Consequences

Page 5: Practical Solutions to External Corrosion Problems …...Jeff Schramuk NACE CP Specialist #7695 4/24/2015 1 1 Practical Solutions to External Corrosion Problems on Buried Water Mains

Jeff Schramuk NACE CP Specialist #7695

4/24/2015

www.cpsolutionsinc.net 5

9

Module 3 Understanding

Corrosion Terminology

10

Anode – A metal electrode in contact with the electrolyte which corrodes.

Cathode - A metal electrode in contact with the electrolyte which is protected against corrosion.

Electrolyte – A solution or conducting medium such as soil, water or concrete which contains oxygen and dissolved chemicals.

Metal Path – An external circuit that connects the anode and the cathode.

Four Components of a Basic Corrosion Cell

Page 6: Practical Solutions to External Corrosion Problems …...Jeff Schramuk NACE CP Specialist #7695 4/24/2015 1 1 Practical Solutions to External Corrosion Problems on Buried Water Mains

Jeff Schramuk NACE CP Specialist #7695

4/24/2015

www.cpsolutionsinc.net 6

11

Anodic Area

(Metal Loss)

DC Current

Cathodic

Area

(Protected)

Anodes & Cathodes on a Buried Metallic Pipe

12

Module 4 Pipe Materials and Coatings

Page 7: Practical Solutions to External Corrosion Problems …...Jeff Schramuk NACE CP Specialist #7695 4/24/2015 1 1 Practical Solutions to External Corrosion Problems on Buried Water Mains

Jeff Schramuk NACE CP Specialist #7695

4/24/2015

www.cpsolutionsinc.net 7

13

Eliminating the Corrosion Cell

Ste

el a

t -6

00

mV

Cop

pe

r a

t -2

00

mV

14

Mortar Integrity on Reinforced Concrete Pipe

Photo courtesy of CP Solutions, Inc. – Bartlett, IL …but is there latent damage?

New installation looks good…

Page 8: Practical Solutions to External Corrosion Problems …...Jeff Schramuk NACE CP Specialist #7695 4/24/2015 1 1 Practical Solutions to External Corrosion Problems on Buried Water Mains

Jeff Schramuk NACE CP Specialist #7695

4/24/2015

www.cpsolutionsinc.net 8

15

Prestressed Concrete Cylinder Pipe – Corrosion Failures

Photo Credits: CP Solutions, Inc.

16

Large Diameter Coated Steel Pipe – Installation Photos

Photo Credits: CP Solutions, Inc.

Page 9: Practical Solutions to External Corrosion Problems …...Jeff Schramuk NACE CP Specialist #7695 4/24/2015 1 1 Practical Solutions to External Corrosion Problems on Buried Water Mains

Jeff Schramuk NACE CP Specialist #7695

4/24/2015

www.cpsolutionsinc.net 9

17

Coating Integrity on Coated Steel Pipe

Photo courtesy of CP Solutions, Inc. – Bartlett, IL

…but is there latent damage?New installation looks good…

18

Poly-Wrap Integrity on Ductile Iron Pipe

Photo courtesy of CP Solutions, Inc. – Bartlett, IL…but is there latent damage?

New installation looks good…

Page 10: Practical Solutions to External Corrosion Problems …...Jeff Schramuk NACE CP Specialist #7695 4/24/2015 1 1 Practical Solutions to External Corrosion Problems on Buried Water Mains

Jeff Schramuk NACE CP Specialist #7695

4/24/2015

www.cpsolutionsinc.net 10

Rip and tears in the poly wrapping

leave the pipe exposed

Oxygen and water can travel

beneath the poly wrapping

Loose Polyethylene

Wrapping

Ductile Iron Pipe

Soil Contaminants

19

Have you ever tried to track down a joint leak within a poly-wrapped water line?

Loose Poly Wrapping – An Effective Corrosion Barrier?

20

Epoxy Coated Valves & Fittings – Before Burial

Photo Credits: CP Solutions, Inc.

Page 11: Practical Solutions to External Corrosion Problems …...Jeff Schramuk NACE CP Specialist #7695 4/24/2015 1 1 Practical Solutions to External Corrosion Problems on Buried Water Mains

Jeff Schramuk NACE CP Specialist #7695

4/24/2015

www.cpsolutionsinc.net 11

21

Epoxy Coated Valve – After Burial

Photo Credit: CP Solutions, Inc.

22

Module 5 Basic Cathodic Protection

Page 12: Practical Solutions to External Corrosion Problems …...Jeff Schramuk NACE CP Specialist #7695 4/24/2015 1 1 Practical Solutions to External Corrosion Problems on Buried Water Mains

Jeff Schramuk NACE CP Specialist #7695

4/24/2015

www.cpsolutionsinc.net 12

23

Basic Corrosion: Corrosion occurs where DC current

discharges from the metal to the electrolyte.

CP Objective: To allow your structure to receive DC current

(be cathodic) from an expendable anode placed in the soil.

How Cathodic Protection Works

Material Potential*Pure Magnesium -1.75

Magnesium Alloy -1.60

Zinc -1.10

Aluminum Alloy -1.00

Mild Steel (New) -0.70

Mild Steel (Old) -0.50

Cast / Ductile Iron -0.50

Stainless Steel -0.50 to + 0.10

Copper, Brass, Bronze -0.20

Gold 0.20

Carbon, Graphite, Coke 0.40*Measured in Volts versus a Cu-CuSO4 Reference Electrode

24

Le

ss

Active

M

ore

Practical Galvanic Series

Page 13: Practical Solutions to External Corrosion Problems …...Jeff Schramuk NACE CP Specialist #7695 4/24/2015 1 1 Practical Solutions to External Corrosion Problems on Buried Water Mains

Jeff Schramuk NACE CP Specialist #7695

4/24/2015

www.cpsolutionsinc.net 13

25

Ca

tho

de

Ca

tho

de

An

od

e

1. Anode

2. Cathode

3. Electrolyte

4. Metal Path

Galvanic Corrosion Mitigated w/Cathodic Protection

26

Typical Horizontal Sacrificial Anode Installation

Sacrificial Anode

Coating Defect

Connection to Pipe

Grade

Page 14: Practical Solutions to External Corrosion Problems …...Jeff Schramuk NACE CP Specialist #7695 4/24/2015 1 1 Practical Solutions to External Corrosion Problems on Buried Water Mains

Jeff Schramuk NACE CP Specialist #7695

4/24/2015

www.cpsolutionsinc.net 14

27

Module 6 Cathodic Protection

for Existing Water Mains

using an

Anode Retrofit Program

28

Anode Retrofit Program (ARP) - A method to

install sacrificial anodes to buried water mains.

Since 2003 – Louisville (KY) Water Company

Since 2004 – Des Moines (IA) Water Works

Since 1980’s – Many Ontario (Canada) Water Utilities

More Recently – Several California Water Utilities

Anode Retrofit Programs – An Overview

Page 15: Practical Solutions to External Corrosion Problems …...Jeff Schramuk NACE CP Specialist #7695 4/24/2015 1 1 Practical Solutions to External Corrosion Problems on Buried Water Mains

Jeff Schramuk NACE CP Specialist #7695

4/24/2015

www.cpsolutionsinc.net 15

Anode Retrofit Program - Purpose

Reduce the Number of Broken Water Mains

Extend Service Life of Water Mains

Reduce Operating Costs of Water Mains

Photos courtesy of CP Solutions, Inc. – Bartlett, IL

30

DMWW’s Long-Term Main Break Data (1994-2011)

After 2007 there are approx. 30 annual breaks per 100 miles pipe (excluding rural water system)

0

50

100

150

200

250

300

350

400

Nu

mb

er

of

Bre

aks

Year

Total Main Breaks - Trends

Page 16: Practical Solutions to External Corrosion Problems …...Jeff Schramuk NACE CP Specialist #7695 4/24/2015 1 1 Practical Solutions to External Corrosion Problems on Buried Water Mains

Jeff Schramuk NACE CP Specialist #7695

4/24/2015

www.cpsolutionsinc.net 16

31

$2,500

$3,500

$4,500

$5,500

$6,500

$7,500

2000 2002 2004 2006 2008 2010 2012 2014 2016

Rep

air

Co

st/

Ma

in B

rea

k

Year

Repair costs have doubled since

2000

DMWW’s Main Break Repair Costs (2000-2013…)

32

Typical Anode Retrofit Installation Method

Page 17: Practical Solutions to External Corrosion Problems …...Jeff Schramuk NACE CP Specialist #7695 4/24/2015 1 1 Practical Solutions to External Corrosion Problems on Buried Water Mains

Jeff Schramuk NACE CP Specialist #7695

4/24/2015

www.cpsolutionsinc.net 17

Keyhole to Pipe & Wire Connection

Exothermic Welding Tool Down the Hole

Testing the Wire Connection

Photos courtesy of CP Solutions, Inc. – Bartlett, IL

34

Alternative (Non-Keyhole) Installation Methods

Page 18: Practical Solutions to External Corrosion Problems …...Jeff Schramuk NACE CP Specialist #7695 4/24/2015 1 1 Practical Solutions to External Corrosion Problems on Buried Water Mains

Jeff Schramuk NACE CP Specialist #7695

4/24/2015

www.cpsolutionsinc.net 18

35

Does the data show that retrofitting CP

anodes on water mains actually

reduces the main break rates?

Main Break Reduction Evaluation of the DMMW’s ARP

36

DMWW Main Break Comparison – ARP vs. No-ARP

0.0

20.0

40.0

60.0

80.0

100.0

120.0

140.0

Cu

mu

lati

ve S

um

Mai

n B

reak

s

Year

No-ARP(1985-ARPYear)

With ARP(ARP Year-2012)

*Source: “Implementing and Managing a Large Water Utility’s Underground Corrosion Program,” Journal AWWA, Vol. 104, No. 7, July 2012

Break reduction

after ARP

Extrapolated prior

break data w/o ARP

Page 19: Practical Solutions to External Corrosion Problems …...Jeff Schramuk NACE CP Specialist #7695 4/24/2015 1 1 Practical Solutions to External Corrosion Problems on Buried Water Mains

Jeff Schramuk NACE CP Specialist #7695

4/24/2015

www.cpsolutionsinc.net 19

37

Economic Evaluation of the DMMW’s ARP

But does the economic data show that retrofitting CP

anodes on water mains is actually

cost-effective?

38

DMWW Anode Retrofit Program: 2004-2011 Summary

ARP installed on ~82,000 feet of 6” - 16” cast iron mains

ARP costs are $9 to $15/ft. pipe

ARP cost ~10-15% of break repairs/pipe replacement

ARP resulted in average reduction of 85% in main breaks

ARP adds a ~25-year service life extension to water mains

Page 20: Practical Solutions to External Corrosion Problems …...Jeff Schramuk NACE CP Specialist #7695 4/24/2015 1 1 Practical Solutions to External Corrosion Problems on Buried Water Mains

Jeff Schramuk NACE CP Specialist #7695

4/24/2015

www.cpsolutionsinc.net 20

39

Module 7 Solving Corrosion Problems

at Water Main Breaks

40

What’s Your Biggest Cost to Repair a Main Break?

Page 21: Practical Solutions to External Corrosion Problems …...Jeff Schramuk NACE CP Specialist #7695 4/24/2015 1 1 Practical Solutions to External Corrosion Problems on Buried Water Mains

Jeff Schramuk NACE CP Specialist #7695

4/24/2015

www.cpsolutionsinc.net 21

41

Do I really want to re-excavate this hole for

another water main break?

“Hot-Spotting”: CP Anodes at Water Main Breaks

Install a sacrificial CP anode while the water main repair excavation is already open!

42

Document all leak and main break repairs as

recommended by AwwaRF

Install a sacrificial anode every time the main is

exposed for repairs or tapping.

Install the anodes where earlier leak problems

have occurred

Source: Research Applications, Proven Utility Benefits, Paper #8, AwwaRF, August 1995.

AWWARF Shows that CP Reduces Main Breaks

Page 22: Practical Solutions to External Corrosion Problems …...Jeff Schramuk NACE CP Specialist #7695 4/24/2015 1 1 Practical Solutions to External Corrosion Problems on Buried Water Mains

Jeff Schramuk NACE CP Specialist #7695

4/24/2015

www.cpsolutionsinc.net 22

43

Cost of repairing a water main break

versus

installing a sacrificial anode during a pipe repair...

Average Cost of a Main Break

$3,500 to $5,000

Cost of a CP Anode and a Connection Device

Less than $150!

Cathodic Protection Is Proactively Inexpensive

44

Use a Secure Connection to Attach Sacrificial Anodes

sacrificial

anode

Connection

device

Page 23: Practical Solutions to External Corrosion Problems …...Jeff Schramuk NACE CP Specialist #7695 4/24/2015 1 1 Practical Solutions to External Corrosion Problems on Buried Water Mains

Jeff Schramuk NACE CP Specialist #7695

4/24/2015

www.cpsolutionsinc.net 23

45

Safe Work Practice in Wet Trench Conditions

Safe to install in standing water

46

Module 8 Cathodic Protection

Performance Verification

Page 24: Practical Solutions to External Corrosion Problems …...Jeff Schramuk NACE CP Specialist #7695 4/24/2015 1 1 Practical Solutions to External Corrosion Problems on Buried Water Mains

Jeff Schramuk NACE CP Specialist #7695

4/24/2015

www.cpsolutionsinc.net 24

47

.900 V

+

Reference Electrode Placed into Soil

Directly Above Pipe -

Electrical Contact to

Pipe

Area of Pipe “Measured”

Structure-to-Soil Potential w/Portable Reference Electrode

VM (-) connected to second pipe

test wire

VM (+) connected toPortable Reference Electrode

Voltmeter set on DC VoltsBlue = Pipe Wire (1 of 2)

Red = Anode Wire

CP Performance Validation – S/S Potential Data

Page 25: Practical Solutions to External Corrosion Problems …...Jeff Schramuk NACE CP Specialist #7695 4/24/2015 1 1 Practical Solutions to External Corrosion Problems on Buried Water Mains

Jeff Schramuk NACE CP Specialist #7695

4/24/2015

www.cpsolutionsinc.net 25

49

Increased water main service life

Increased level of reliable water service to customers

Increased health and security of the municipal water supply

Summary: The Real Benefits of Corrosion Mitigation

Cathodic protection saves $5 to $10 for every $1

spent resulting in…

Water Main Life Extension of least 25 years at acost that is much less than…

Direct costs of pipe repairs and/or water main replacement.

Indirect costs resulting from water loss/service disruptions.

50

Jeff SchramukNACE CP Specialist #7695

630-235-1559www.cpsolutionsinc.net

Do You Have Any Questions?

All material in this presentation is, unless otherwise stated, the property of CP Solutions, Inc (CPSI). Copyright and other intellectual property laws protect these

materials. Reproduction or retransmission of the materials, in whole or in part, in any manner, without the prior written consent of CPSI, is a violation of copyright law.

Illinois Section AWWA Annual WDC: 4/28/2015