1 TECH BRIEF | Practical Applications for Cat 8 Leviton.com/ns Practical Applications for CAT 8 Category 8 cabling solutions have arrived with the ability to support new 25/40GBASE-T networks. It’s impressive that the same tried-and-true twisted pair cabling and RJ-45 interface that delivered 10 megabits per second 15 years ago still play an important role in next generation networks. But what are the practical applications for Cat 8? Where will it be deployed? First of all, these cabling systems make sense for applications requiring speeds greater than 10 Gb/s. This goes beyond the capabilities of Cat 6A, which has the performance specifications and flexibility to handle 10 Gb/s or slower speeds. Also, for now, Cat 8 cabling systems will be limited to the access layer in data centre networks. Due to its distance limitations of 30 metres or less in a two-connector channel — per IEEE, ISO, and TIA standards — Cat 8 cabling really isn’t applicable for enterprise or premise networks. However, for data centre managers, Cat 8 offers some huge benefits. When planning for networks greater than 10 Gb/s in the access layer, the decision of which cable type to use largely depends on the network topology you prefer: Top-of-Rack (ToR), End-of-Row (EoR), or Middle-of- Row (MoR). Cat 8 will be able to support all of these topologies. For data centre managers, Cat 8 offers some huge benefits. ToR EoR MoR

Practical Applications for CAT 8 - Leviton Network Solutions Europe · But what are the practical applications for Cat 8? Where will it be deployed? First of all, these cabling systems

  • Upload
    others

  • View
    1

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Practical Applications for CAT 8 - Leviton Network Solutions Europe · But what are the practical applications for Cat 8? Where will it be deployed? First of all, these cabling systems

1TECH BRIEF | Practical Applications for Cat 8 Leviton.com/ns

PracticalApplications

for CAT 8

Category 8 cabling solutions have arrived with the ability to support new 25/40GBASE-T networks. It’s impressive that the same tried-and-true twisted pair cabling and RJ-45 interface that delivered 10 megabits per second 15 years ago still play an important role in next generation networks.

But what are the practical applications for Cat 8? Where will it be deployed? First of all, these cabling systems make sense for applications requiring speeds greater than 10 Gb/s. This goes beyond the capabilities of Cat 6A, which has the performance specifications and flexibility to handle 10 Gb/s or slower speeds.

Also, for now, Cat 8 cabling systems will be limited to the access layer in data centre networks. Due to its distance limitations of 30 metres or less in a two-connector channel — per IEEE, ISO, and TIA standards — Cat 8 cabling really isn’t applicable for enterprise or premise networks. However, for data centre managers, Cat 8 offers some huge benefits. When planning for networks greater than 10 Gb/s in the access layer, the decision of which cable type to use largely depends on the network topology you prefer: Top-of-Rack (ToR), End-of-Row (EoR), or Middle-of-Row (MoR). Cat 8 will be able to support all of these topologies.

For data centre managers, Cat 8 offers some huge benefits.

ToR

EoR

MoR

Page 2: Practical Applications for CAT 8 - Leviton Network Solutions Europe · But what are the practical applications for Cat 8? Where will it be deployed? First of all, these cabling systems

TECH BRIEF | Practical Applications for Cat 8 Leviton.com/ns2

UID 1 2

1 2 3 4 5 6 7 8HP

DIMMS

PCIRISERCAGE

FANS

POWERSUPPLY

POWERSUPPLY

PROCPROC

DIMMS

MIRROR

OVERTEMP

INTERLOCK

PPM

ProLiantDL385 G2

UID 1 2

1 2 3 4 5 6 7 8HP

DIMMS

PCIRISERCAGE

FANS

POWERSUPPLY

POWERSUPPLY

PROCPROC

DIMMS

MIRROR

OVERTEMP

INTERLOCK

PPM

ProLiantDL385 G2

UID 1 2

1 2 3 4 5 6 7 8HP

DIMMS

PCIRISERCAGE

FANS

POWERSUPPLY

POWERSUPPLY

PROCPROC

DIMMS

MIRROR

OVERTEMP

INTERLOCK

PPM

ProLiantDL385 G2

UID 1 2

1 2 3 4 5 6 7 8HP

DIMMS

PCIRISERCAGE

FANS

POWERSUPPLY

POWERSUPPLY

PROCPROC

DIMMS

MIRROR

OVERTEMP

INTERLOCK

PPM

ProLiantDL385 G2

UID 1 2

1 2 3 4 5 6 7 8HP

DIMMS

PCIRISERCAGE

FANS

POWERSUPPLY

POWERSUPPLY

PROCPROC

DIMMS

MIRROR

OVERTEMP

INTERLOCK

PPM

ProLiantDL385 G2

UID 1 2

1 2 3 4 5 6 7 8HP

DIMMS

PCIRISERCAGE

FANS

POWERSUPPLY

POWERSUPPLY

PROCPROC

DIMMS

MIRROR

OVERTEMP

INTERLOCK

PPM

ProLiantDL385 G2

UID 1 2

1 2 3 4 5 6 7 8HP

DIMMS

PCIRISERCAGE

FANS

POWERSUPPLY

POWERSUPPLY

PROCPROC

DIMMS

MIRROR

OVERTEMP

INTERLOCK

PPM

ProLiantDL385 G2

UID 1 2

1 2 3 4 5 6 7 8HP

DIMMS

PCIRISERCAGE

FANS

POWERSUPPLY

POWERSUPPLY

PROCPROC

DIMMS

MIRROR

OVERTEMP

INTERLOCK

PPM

ProLiantDL385 G2

UID 1 2

1 2 3 4 5 6 7 8HP

DIMMS

PCIRISERCAGE

FANS

POWERSUPPLY

POWERSUPPLY

PROCPROC

DIMMS

MIRROR

OVERTEMP

INTERLOCK

PPM

ProLiantDL385 G2

UID 1 2

1 2 3 4 5 6 7 8HP

DIMMS

PCIRISERCAGE

FANS

POWERSUPPLY

POWERSUPPLY

PROCPROC

DIMMS

MIRROR

OVERTEMP

INTERLOCK

PPM

ProLiantDL385 G2

UID 1 2

1 2 3 4 5 6 7 8HP

DIMMS

PCIRISERCAGE

FANS

POWERSUPPLY

POWERSUPPLY

PROCPROC

DIMMS

MIRROR

OVERTEMP

INTERLOCK

PPM

ProLiantDL385 G2

UID 1 2

1 2 3 4 5 6 7 8HP

DIMMS

PCIRISERCAGE

FANS

POWERSUPPLY

POWERSUPPLY

PROCPROC

DIMMS

MIRROR

OVERTEMP

INTERLOCK

PPM

ProLiantDL385 G2

2423222120191817161514137 8 9 10 11 121 2 3 4 5 6

25 26 27 28 29 30 32 33 34 35 3631 424140393837 484746454443

CISCO NEXUS 2248TP 1GE FABRIC EXTENDER

STAT

1 2 3 441 42 43 44 45 46 47 4839 4037 3829 30 31 32 33 34 35 3627 2825 2617 18 19 20 21 22 23 2415 1613 145 6 7 8 9 10 11 123 41 2ID

UID 1 2

1 2 3 4 5 6 7 8HP

DIMMS

PCIRISERCAGE

FANS

POWERSUPPLY

POWERSUPPLY

PROCPROC

DIMMS

MIRROR

OVERTEMP

INTERLOCK

PPM

ProLiantDL385 G2

UID 1 2

1 2 3 4 5 6 7 8HP

DIMMS

PCIRISERCAGE

FANS

POWERSUPPLY

POWERSUPPLY

PROCPROC

DIMMS

MIRROR

OVERTEMP

INTERLOCK

PPM

ProLiantDL385 G2

UID 1 2

1 2 3 4 5 6 7 8HP

DIMMS

PCIRISERCAGE

FANS

POWERSUPPLY

POWERSUPPLY

PROCPROC

DIMMS

MIRROR

OVERTEMP

INTERLOCK

PPM

ProLiantDL385 G2

UID 1 2

1 2 3 4 5 6 7 8HP

DIMMS

PCIRISERCAGE

FANS

POWERSUPPLY

POWERSUPPLY

PROCPROC

DIMMS

MIRROR

OVERTEMP

INTERLOCK

PPM

ProLiantDL385 G2

UID 1 2

1 2 3 4 5 6 7 8HP

DIMMS

PCIRISERCAGE

FANS

POWERSUPPLY

POWERSUPPLY

PROCPROC

DIMMS

MIRROR

OVERTEMP

INTERLOCK

PPM

ProLiantDL385 G2

UID 1 2

1 2 3 4 5 6 7 8HP

DIMMS

PCIRISERCAGE

FANS

POWERSUPPLY

POWERSUPPLY

PROCPROC

DIMMS

MIRROR

OVERTEMP

INTERLOCK

PPM

ProLiantDL385 G2

UID 1 2

1 2 3 4 5 6 7 8HP

DIMMS

PCIRISERCAGE

FANS

POWERSUPPLY

POWERSUPPLY

PROCPROC

DIMMS

MIRROR

OVERTEMP

INTERLOCK

PPM

ProLiantDL385 G2

UID 1 2

1 2 3 4 5 6 7 8HP

DIMMS

PCIRISERCAGE

FANS

POWERSUPPLY

POWERSUPPLY

PROCPROC

DIMMS

MIRROR

OVERTEMP

INTERLOCK

PPM

ProLiantDL385 G2

UID 1 2

1 2 3 4 5 6 7 8HP

DIMMS

PCIRISERCAGE

FANS

POWERSUPPLY

POWERSUPPLY

PROCPROC

DIMMS

MIRROR

OVERTEMP

INTERLOCK

PPM

ProLiantDL385 G2

UID 1 2

1 2 3 4 5 6 7 8HP

DIMMS

PCIRISERCAGE

FANS

POWERSUPPLY

POWERSUPPLY

PROCPROC

DIMMS

MIRROR

OVERTEMP

INTERLOCK

PPM

ProLiantDL385 G2

UID 1 2

1 2 3 4 5 6 7 8HP

DIMMS

PCIRISERCAGE

FANS

POWERSUPPLY

POWERSUPPLY

PROCPROC

DIMMS

MIRROR

OVERTEMP

INTERLOCK

PPM

ProLiantDL385 G2

UID 1 2

1 2 3 4 5 6 7 8HP

DIMMS

PCIRISERCAGE

FANS

POWERSUPPLY

POWERSUPPLY

PROCPROC

DIMMS

MIRROR

OVERTEMP

INTERLOCK

PPM

ProLiantDL385 G2

2423222120191817161514137 8 9 10 11 121 2 3 4 5 6

25 26 27 28 29 30 32 33 34 35 3631 424140393837 484746454443

CISCO NEXUS 2248TP 1GE FABRIC EXTENDER

STAT

1 2 3 441 42 43 44 45 46 47 4839 4037 3829 30 31 32 33 34 35 3627 2825 2617 18 19 20 21 22 23 2415 1613 145 6 7 8 9 10 11 123 41 2ID

UID 1 2

1 2 3 4 5 6 7 8HP

DIMMS

PCIRISERCAGE

FANS

POWERSUPPLY

POWERSUPPLY

PROCPROC

DIMMS

MIRROR

OVERTEMP

INTERLOCK

PPM

ProLiantDL385 G2

UID 1 2

1 2 3 4 5 6 7 8HP

DIMMS

PCIRISERCAGE

FANS

POWERSUPPLY

POWERSUPPLY

PROCPROC

DIMMS

MIRROR

OVERTEMP

INTERLOCK

PPM

ProLiantDL385 G2

UID 1 2

1 2 3 4 5 6 7 8HP

DIMMS

PCIRISERCAGE

FANS

POWERSUPPLY

POWERSUPPLY

PROCPROC

DIMMS

MIRROR

OVERTEMP

INTERLOCK

PPM

ProLiantDL385 G2

UID 1 2

1 2 3 4 5 6 7 8HP

DIMMS

PCIRISERCAGE

FANS

POWERSUPPLY

POWERSUPPLY

PROCPROC

DIMMS

MIRROR

OVERTEMP

INTERLOCK

PPM

ProLiantDL385 G2

UID 1 2

1 2 3 4 5 6 7 8HP

DIMMS

PCIRISERCAGE

FANS

POWERSUPPLY

POWERSUPPLY

PROCPROC

DIMMS

MIRROR

OVERTEMP

INTERLOCK

PPM

ProLiantDL385 G2

UID 1 2

1 2 3 4 5 6 7 8HP

DIMMS

PCIRISERCAGE

FANS

POWERSUPPLY

POWERSUPPLY

PROCPROC

DIMMS

MIRROR

OVERTEMP

INTERLOCK

PPM

ProLiantDL385 G2

UID 1 2

1 2 3 4 5 6 7 8HP

DIMMS

PCIRISERCAGE

FANS

POWERSUPPLY

POWERSUPPLY

PROCPROC

DIMMS

MIRROR

OVERTEMP

INTERLOCK

PPM

ProLiantDL385 G2

UID 1 2

1 2 3 4 5 6 7 8HP

DIMMS

PCIRISERCAGE

FANS

POWERSUPPLY

POWERSUPPLY

PROCPROC

DIMMS

MIRROR

OVERTEMP

INTERLOCK

PPM

ProLiantDL385 G2

UID 1 2

1 2 3 4 5 6 7 8HP

DIMMS

PCIRISERCAGE

FANS

POWERSUPPLY

POWERSUPPLY

PROCPROC

DIMMS

MIRROR

OVERTEMP

INTERLOCK

PPM

ProLiantDL385 G2

UID 1 2

1 2 3 4 5 6 7 8HP

DIMMS

PCIRISERCAGE

FANS

POWERSUPPLY

POWERSUPPLY

PROCPROC

DIMMS

MIRROR

OVERTEMP

INTERLOCK

PPM

ProLiantDL385 G2

UID 1 2

1 2 3 4 5 6 7 8HP

DIMMS

PCIRISERCAGE

FANS

POWERSUPPLY

POWERSUPPLY

PROCPROC

DIMMS

MIRROR

OVERTEMP

INTERLOCK

PPM

ProLiantDL385 G2

UID 1 2

1 2 3 4 5 6 7 8HP

DIMMS

PCIRISERCAGE

FANS

POWERSUPPLY

POWERSUPPLY

PROCPROC

DIMMS

MIRROR

OVERTEMP

INTERLOCK

PPM

ProLiantDL385 G2

2423222120191817161514137 8 9 10 11 121 2 3 4 5 6

25 26 27 28 29 30 32 33 34 35 3631 424140393837 484746454443

CISCO NEXUS 2248TP 1GE FABRIC EXTENDER

STAT

1 2 3 441 42 43 44 45 46 47 4839 4037 3829 30 31 32 33 34 35 3627 2825 2617 18 19 20 21 22 23 2415 1613 145 6 7 8 9 10 11 123 41 2ID

Cat 8 CopperPatch Cords

Fibre Links

ToR

MoR

EoR

Topology

Cabling for Top-of-Rack

If you prefer a ToR topology, you now have a choice between twinax Direct Attach Copper (DAC) assemblies or Cat 8 for copper infrastructure. The ToR model uses a simplified cabling scheme — short intra-rack cable runs with a small number of uplinks to the aggregate switches.

Quad small form-factor pluggable (QSFP+) DAC passive assemblies were standardised in 2010 through IEEE 802.3ba. They are low-power solutions and have a similar form-factor to SFP+ 10 Gb/s (and future 25 Gb/s) assemblies. However, they have a limited distance of up to seven metres. With such limited reach, they are a better fit for ToR topologies instead of longer distances used in other topologies.

Also, unlike some twinax solutions, Cat 8 cabling leverages the benefits of autonegotiation. Autonegotiation allows for two Ethernet devices to connect to each other and select a common transmission speed that both devices support. Autonegotiation requirements are laid out in IEEE 802.3 BASE-T standards. For example, 25 Gb/s ToR switches can communicate with 10Gb/s servers, whether over Cat 8 or Cat 6A connectivity. In addition, the different category ratings use the same RJ-45 connector form factor, whereas twinax requires different assembly modules depending on the data rate.

This also allows for network migration to 25/40GBASE-T to be done in phases, allowing for more flexibility in terms of timing, disruption, and cost. With staggered active gear upgrades, BASE-T solutions can allow for mixed server speeds in each rack or cabinet supporting any combination of 1, 2.5, 5, or 10, 25, or 40 Gb/s servers, creating better port utilisation of the switches.

Page 3: Practical Applications for CAT 8 - Leviton Network Solutions Europe · But what are the practical applications for Cat 8? Where will it be deployed? First of all, these cabling systems

TECH BRIEF | Practical Applications for Cat 8 Leviton.com/ns3

1 2 3 4 5 6

25 26 27 28 29 30

7 8 9 10 11 12

31 32 33 34 35 36

13 14 15 16 17 18

37 38 39 40 41 42

19 20 21 22 23 24

43 44 45 46 47 48

UID 1 2

1 2 3 4 5 6 7 8HP

DIMMS

PCIRISERCAGE

FANS

POWERSUPPLY

POWERSUPPLY

PROCPROC

DIMMS

MIRROR

OVERTEMP

INTERLOCK

PPM

ProLiantDL385 G2

UID 1 2

1 2 3 4 5 6 7 8HP

DIMMS

PCIRISERCAGE

FANS

POWERSUPPLY

POWERSUPPLY

PROCPROC

DIMMS

MIRROR

OVERTEMP

INTERLOCK

PPM

ProLiantDL385 G2

UID 1 2

1 2 3 4 5 6 7 8HP

DIMMS

PCIRISERCAGE

FANS

POWERSUPPLY

POWERSUPPLY

PROCPROC

DIMMS

MIRROR

OVERTEMP

INTERLOCK

PPM

ProLiantDL385 G2

UID 1 2

1 2 3 4 5 6 7 8HP

DIMMS

PCIRISERCAGE

FANS

POWERSUPPLY

POWERSUPPLY

PROCPROC

DIMMS

MIRROR

OVERTEMP

INTERLOCK

PPM

ProLiantDL385 G2

UID 1 2

1 2 3 4 5 6 7 8HP

DIMMS

PCIRISERCAGE

FANS

POWERSUPPLY

POWERSUPPLY

PROCPROC

DIMMS

MIRROR

OVERTEMP

INTERLOCK

PPM

ProLiantDL385 G2

UID 1 2

1 2 3 4 5 6 7 8HP

DIMMS

PCIRISERCAGE

FANS

POWERSUPPLY

POWERSUPPLY

PROCPROC

DIMMS

MIRROR

OVERTEMP

INTERLOCK

PPM

ProLiantDL385 G2

UID 1 2

1 2 3 4 5 6 7 8HP

DIMMS

PCIRISERCAGE

FANS

POWERSUPPLY

POWERSUPPLY

PROCPROC

DIMMS

MIRROR

OVERTEMP

INTERLOCK

PPM

ProLiantDL385 G2

UID 1 2

1 2 3 4 5 6 7 8HP

DIMMS

PCIRISERCAGE

FANS

POWERSUPPLY

POWERSUPPLY

PROCPROC

DIMMS

MIRROR

OVERTEMP

INTERLOCK

PPM

ProLiantDL385 G2

UID 1 2

1 2 3 4 5 6 7 8HP

DIMMS

PCIRISERCAGE

FANS

POWERSUPPLY

POWERSUPPLY

PROCPROC

DIMMS

MIRROR

OVERTEMP

INTERLOCK

PPM

ProLiantDL385 G2

UID 1 2

1 2 3 4 5 6 7 8HP

DIMMS

PCIRISERCAGE

FANS

POWERSUPPLY

POWERSUPPLY

PROCPROC

DIMMS

MIRROR

OVERTEMP

INTERLOCK

PPM

ProLiantDL385 G2

UID 1 2

1 2 3 4 5 6 7 8HP

DIMMS

PCIRISERCAGE

FANS

POWERSUPPLY

POWERSUPPLY

PROCPROC

DIMMS

MIRROR

OVERTEMP

INTERLOCK

PPM

ProLiantDL385 G2

UID 1 2

1 2 3 4 5 6 7 8HP

DIMMS

PCIRISERCAGE

FANS

POWERSUPPLY

POWERSUPPLY

PROCPROC

DIMMS

MIRROR

OVERTEMP

INTERLOCK

PPM

ProLiantDL385 G2

1 2 3 4 5 6

25 26 27 28 29 30

7 8 9 10 11 12

31 32 33 34 35 36

13 14 15 16 17 18

37 38 39 40 41 42

19 20 21 22 23 24

43 44 45 46 47 48

UID 1 2

1 2 3 4 5 6 7 8HP

DIMMS

PCIRISERCAGE

FANS

POWERSUPPLY

POWERSUPPLY

PROCPROC

DIMMS

MIRROR

OVERTEMP

INTERLOCK

PPM

ProLiantDL385 G2

UID 1 2

1 2 3 4 5 6 7 8HP

DIMMS

PCIRISERCAGE

FANS

POWERSUPPLY

POWERSUPPLY

PROCPROC

DIMMS

MIRROR

OVERTEMP

INTERLOCK

PPM

ProLiantDL385 G2

UID 1 2

1 2 3 4 5 6 7 8HP

DIMMS

PCIRISERCAGE

FANS

POWERSUPPLY

POWERSUPPLY

PROCPROC

DIMMS

MIRROR

OVERTEMP

INTERLOCK

PPM

ProLiantDL385 G2

UID 1 2

1 2 3 4 5 6 7 8HP

DIMMS

PCIRISERCAGE

FANS

POWERSUPPLY

POWERSUPPLY

PROCPROC

DIMMS

MIRROR

OVERTEMP

INTERLOCK

PPM

ProLiantDL385 G2

UID 1 2

1 2 3 4 5 6 7 8HP

DIMMS

PCIRISERCAGE

FANS

POWERSUPPLY

POWERSUPPLY

PROCPROC

DIMMS

MIRROR

OVERTEMP

INTERLOCK

PPM

ProLiantDL385 G2

UID 1 2

1 2 3 4 5 6 7 8HP

DIMMS

PCIRISERCAGE

FANS

POWERSUPPLY

POWERSUPPLY

PROCPROC

DIMMS

MIRROR

OVERTEMP

INTERLOCK

PPM

ProLiantDL385 G2

UID 1 2

1 2 3 4 5 6 7 8HP

DIMMS

PCIRISERCAGE

FANS

POWERSUPPLY

POWERSUPPLY

PROCPROC

DIMMS

MIRROR

OVERTEMP

INTERLOCK

PPM

ProLiantDL385 G2

UID 1 2

1 2 3 4 5 6 7 8HP

DIMMS

PCIRISERCAGE

FANS

POWERSUPPLY

POWERSUPPLY

PROCPROC

DIMMS

MIRROR

OVERTEMP

INTERLOCK

PPM

ProLiantDL385 G2

UID 1 2

1 2 3 4 5 6 7 8HP

DIMMS

PCIRISERCAGE

FANS

POWERSUPPLY

POWERSUPPLY

PROCPROC

DIMMS

MIRROR

OVERTEMP

INTERLOCK

PPM

ProLiantDL385 G2

UID 1 2

1 2 3 4 5 6 7 8HP

DIMMS

PCIRISERCAGE

FANS

POWERSUPPLY

POWERSUPPLY

PROCPROC

DIMMS

MIRROR

OVERTEMP

INTERLOCK

PPM

ProLiantDL385 G2

UID 1 2

1 2 3 4 5 6 7 8HP

DIMMS

PCIRISERCAGE

FANS

POWERSUPPLY

POWERSUPPLY

PROCPROC

DIMMS

MIRROR

OVERTEMP

INTERLOCK

PPM

ProLiantDL385 G2

UID 1 2

1 2 3 4 5 6 7 8HP

DIMMS

PCIRISERCAGE

FANS

POWERSUPPLY

POWERSUPPLY

PROCPROC

DIMMS

MIRROR

OVERTEMP

INTERLOCK

PPM

ProLiantDL385 G2

1 2 3 4 5 6

25 26 27 28 29 30

7 8 9 10 11 12

31 32 33 34 35 36

13 14 15 16 17 18

37 38 39 40 41 42

19 20 21 22 23 24

43 44 45 46 47 48

1 2 3 4 5 6

25 26 27 28 29 30

7 8 9 10 11 12

31 32 33 34 35 36

13 14 15 16 17 18

37 38 39 40 41 42

19 20 21 22 23 24

43 44 45 46 47 48

1 2 3 4 5 6

25 26 27 28 29 30

7 8 9 10 11 12

31 32 33 34 35 36

13 14 15 16 17 18

37 38 39 40 41 42

19 20 21 22 23 24

43 44 45 46 47 48

1 2 3 4 5 6

25 26 27 28 29 30

7 8 9 10 11 12

31 32 33 34 35 36

13 14 15 16 17 18

37 38 39 40 41 42

19 20 21 22 23 24

43 44 45 46 47 48

1 2 3 4 5 6

25 26 27 28 29 30

7 8 9 10 11 12

31 32 33 34 35 36

13 14 15 16 17 18

37 38 39 40 41 42

19 20 21 22 23 24

43 44 45 46 47 48

1 2 3 4 5 6

25 26 27 28 29 30

7 8 9 10 11 12

31 32 33 34 35 36

13 14 15 16 17 18

37 38 39 40 41 42

19 20 21 22 23 24

43 44 45 46 47 48

1 2 3 4 5 6

25 26 27 28 29 30

7 8 9 10 11 12

31 32 33 34 35 36

13 14 15 16 17 18

37 38 39 40 41 42

19 20 21 22 23 24

43 44 45 46 47 48

1 2 3 4 5 6

25 26 27 28 29 30

7 8 9 10 11 12

31 32 33 34 35 36

13 14 15 16 17 18

37 38 39 40 41 42

19 20 21 22 23 24

43 44 45 46 47 48

1 2 3 4 5 6

25 26 27 28 29 30

7 8 9 10 11 12

31 32 33 34 35 36

13 14 15 16 17 18

37 38 39 40 41 42

19 20 21 22 23 24

43 44 45 46 47 48

1 2 3 4 5 6

25 26 27 28 29 30

7 8 9 10 11 12

31 32 33 34 35 36

13 14 15 16 17 18

37 38 39 40 41 42

19 20 21 22 23 24

43 44 45 46 47 48

TestI

O

w w w .ap cc .c om

Smart-UPS

3 0 0 0

2423222120191817161514137 8 9 10 11 121 2 3 4 5 6

25 26 27 28 29 30 32 33 34 35 3631 424140393837 484746454443

Cat 8 CopperPatch Cords

Fibre Links

Cat 8 CopperPatch Cords

FibrePatchCords

Cat 8 Copper Trunks

ToR

MoR

EoR

Topology

Cabling for End-of-Row and Middle-of-Row

EoR and MoR designs have every server cabled back to a single switch dedicated to a row of server racks. The upside of this structured cabling approach is a simplified management environment with just one switch to manage per row.

These topologies require longer links than those for ToR designs, and for 25 and 40 Gb/s networks in EoR and MoR topologies, your two options are to use Cat 8 or multimode fibre. The longer cabling requirements eliminate short-length DAC assemblies as an option.

Multimode fibre offers the benefit of working over longer distances and low power, and it can provide a smaller cable profile. However, the high costs of fibre active equipment makes it an option that not all end users can justify.

Page 4: Practical Applications for CAT 8 - Leviton Network Solutions Europe · But what are the practical applications for Cat 8? Where will it be deployed? First of all, these cabling systems

4

Rele

ased

Aug

ust

2017

H17

688

0f

TECH BRIEF | Cat 8 Applications Leviton.com/ns

If you have more questions about Cat 8, Leviton data centre designers and engineers have extensive experience with the most popular network topologies, active equipment, and transmission methods. Many of them are active members on standards bodies that define future data centre networks. You can reach them at +44 (0)207 489 7637.

Leviton Leads with Atlas-X1™

Altas-X1 Cat 8 connectivity uses the same form factor and termination methods as other Atlas-X1 connectors. In fact, Atlas-X1 is the industry's first system to support shielded applications from Cat 8 to 5e and UTP applications from Cat 6A to 5e, all from one unified connectivity platform.

This comprehensive system is made in the United States, and delivers the highest level of verified performance across all categories to seamlessly support network migration up to 40GBASE-T. It has been third-party tested to comply with the ISO/IEC 11801 Class I channel standard, and components support Power over Ethernet (PoE) applications up to 100 Watts.

Category 8 can support the longer distances required in EoR and MoR designs, but it is limited to 30 metres or less. However, according to IEEE, links of 30 metres or less make up 80 percent of data centre connections in the industry. If you require longer distances, fibre is the only option. Cat 8 also offers the benefit of operating over low power: it will not likely require any greater power or cooling requirements than a typical 10GBASE-T system used today.

Even if Cat 8 is not part of your immediate data centre strategy, you may want to anticipiate future tech refreshes in your current network infrastructure design. This means considering cable distances, connection counts, shielding, and more. Preparing for Cat 8 now will create a simple and cost effective migration in the future.

LEARN MORE ABOUT CAT 8 AND LEVITON’S ATLAS-X1 SYSTEM AT LEVITON.COM/CAT8.

Cat 8 is limited to 30 metres or less. However, according to IEEE, links of 30 metres or less make up 80 percent of data centre connections in the industry.