DESIGNING FOR FIRE SAFETY PARTS 1,2,3 and 4

Ar Chong Lee SiongAPAM MIFireE MMIArbs

PAM CPD SEMINAR

“A re-visit to the interpretations and applications of the Uniform Building By-Laws 1984”

And revisions to Fire Safety Provisions Selangor Uniform Building

(amendment)(no2) By-Laws 2012

Page 2: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

Uniform Building By-Laws 1984

is a“PRESCRIPTIVE” BUILDING CODE

• Compliance with this code is a requirement by law• Sets rules and regulations on the application of the code• Provides pre-determined prescriptions

The prescriptions are absolute :

no smaller than…….. no bigger than……..

no shorter than……no longer than……

or no less than and no more than.

Page 3: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

CONCEPTS OF FIRE SAFETY

1 EVACUATION

2 PASSIVE CONTAINMENT

3 ACTIVE INTERVENTION

4 ACCESS FOR FIRE FIGHTING AND RESCUE

Page 4: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

occupants

• Numbers and distribution• State of mind• Familiarity of place• Physical mobility

Contributing factors to designing for evacuation

Page 5: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

buildingsContributing factors to designing for evacuation

• Detection and alarm• Complexity of plan• Passive and active systems

These factors lead to the designation of purpose groups in the

Fifth Schedule, UBBL

Page 6: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

Designation of purpose group• UBBL 5th schedule• UBBL 134• UBBL 135, 136, 137, 138, 139• Every building is to have one overall designation

• Individual components of building with different usage from overall must be designed to accommodate the more stringent requirement, and where these requirements ‘spill’ into the other parts of the building, the more stringent requirement applies.

• Only ‘horizontal’ separation is allowed between buildings of different purpose groups

Page 7: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

I : Small Residential

II : Institutional

III : Other Residential

V : Shop

VII : Place of Assembly

PURPOSE GROUP

Page 8: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

MIXED USE BUILDINGS BASIC CONCEPT

part of buildinguse/purpose grp : hotel/iiiHT. 1 to be used for compliancewith Schedules 6,7,9,10 of By-law.

part B of buildinguse/purpose grp : SHOPS/VHT. 2 to be used for compliancewith Schedules 6,7,9,10 of By-law.

HT. 2b- shops

c - basement

Compartment floorabove basement

By-Law 138(d)

Vertical compartment wall separating Purpose Groups III & V -By-Law 215

Ground level

HT. 1

A- HOTEL

Ground level

part C of buildinguse/purpose grp : basement parking/viiidepth/ht. 3 to be used for compliancewith Schedules 7,9,10 of By-law.

Depth 3

B-SHOPS

C-CARPARKS

Page 9: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

• EVACUATION

• Detection• Alarm• Exits • Travel distance• Components• Capacity of exits

Accepted assumption in designing for safe evacuation:

“Only one fire at one location at a time”

Page 10: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

Time

Tem

pera

ture

/ si

ze

Stage 1Ignition & growth

Stage 2development

Stage 3Full fire

Stage 4Decay

Flashover

Untenable condition

NATURE OF FIRE

Page 11: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

Tem

pera

ture

/ si

ze

Time

Unt

enab

le c

ondi

tion

Available Safe Egress Time ASET

detection

alarm

movementTotal evacuation

ignition

Required Safe Egress Time RSET

Factor of safety:

RSET < 0.75 ASET

Page 12: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

exit• Final exit

• ‘Alternative exits’

• Storey exit

• Horizontal exit

• Exit route

Page 13: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

Final exit

• UBBL 133 – interpretations

• Final exit refers to the threshold that separates “still within the building” and “out of the building”. The liability of the design for evacuation from the building ends at this point.

Page 14: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

‘Alternative exits’

• UBBL 166

• This is the primary concept for safe evacuation. Every floor space shall be provided with at least two exits on the basis that if one exit is inoperable, the other exit can serve the function.

• This ‘designing for redundancy’ principle applies to all aspects of evacuation.

Page 15: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

Final exit

Final exit

Final exit

Alternative exits

Alternative exits

Page 16: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

Horizontal exit

• UBBL 171

• Exits that lead to an adjacent (horizontal) separated compartment within the same floor

Page 17: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

Storey exit

• UBBL 167, 174

• Exits from a floor which is of a different level from the final exit, or, if on the same level, a distance away from the final exit.

• A storey exit is to lead to a final exit.

Page 18: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

Exit route

• UBBL 133 – interpretations• UBBL 169

• the protected passage from a storey exit that leads to the final exit.

• Can include spaces that are designated as areas of refuge anywhere between the storey exit and the final exit

Page 19: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

Final exit

Exit route

horizontal exit

storey exit

Travel distance

Travel distanceTravel distance

Final exit

Page 20: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

Travel distance• UBBL 165• 7th Schedule• Dead end • initial travel distance before a point where an alternative path

becomes available• Direct distance• Stipulates that travel distance must be measured along the actual

path of travel• Open plan• Where an actual path of travel cannot be determined, the direct

distance can be measured as a straight line direct to the exit. Permitted travel distance is then reduced to 2/3.

Page 21: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

Evacuation : small area

Page 22: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

Evacuation : larger area

Page 23: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

Evacuation : multiple areas

Final exits

UBBL 165 (B)Max 15m if room< 6 pax

To comply with dead end and travel distance

Max distance is 15m within room plus max allowable travel distanceFrom door of room to final exit

Page 24: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

165. Measurement of travel distance to exits.  (3) In the case of individual rooms which are subject to occupancy of not more than six persons, the travel distance shall be measured from the doors of such rooms: Provided that the travel distance from any point in the room to the room door does not exceed 15 metres. 

 (3) In any of individual room which is subjected to occupancy of not more than six persons, the travel distance shall be measured from the door of such room:  

Provided that the area of the room does not exceed 15 square metres or any other area determined by the Fire Authority. 

   To clarify that this requirement is applicable to each individual room.    Measurement based on floor area of a room provides stricter control. 

Page 25: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

Evacuation : multiple areas

Final exits UBBL 165 (B)Max 15m2 and < 6 pax

Travel distance measured from door if room is less than 15m2 and with less than 6 occupants

Page 26: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

Evacuation : multiple areas

Horizontal exits

storey exits

Page 27: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

Horizontal exits

12 3

Page 28: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

Horizontal exits

12 2

Page 29: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

components

• Exit door• Exit discharge• Protected corridor• Protected staircase• Balcony approach• Single staircase

Page 30: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

Exit door, exit discharge• UBBL 173• UBBL 186• UBBL 193• UBBL 133 - interpretations

• ‘Door’ refers to the physical door installed at an exit, and all its functional components e.g. locksets, latches, hinges and closers

• ‘discharge’ refers to the ‘doorway’ or threshold of an exit

Page 31: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

Exit door, exit discharge• Not all fire rated doors are exit doors• Not all exit doors need to be fire doors• Not all doors need to be exit doors• Not all doors can be exit doors

• Exit doors must always be able to be opened (without undue effort) at all times

• Exit discharge must always allow the passage of people at all times

• ‘Exit’ in this context means storey exit, horizontal exit or final exit

Page 32: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

Evacuation : separation of routes

Final exitFinal exit

Page 33: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

Protected corridor, protected staircase

• UBBL 133-interpretations• UBBL 157, 189, 190, 191

• While not expressed, it is inferred from the UBBL that all components that form the Exit Route shall be of protected construction.

• Using the same inference, ‘protected’ shall mean ‘enclosed’, ‘separated’ or ‘isolated’

Page 34: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

Single stair

• UBBL 194

• Special provision for the common ‘shop-house’ design

• Usage limited to shop (ground floor only), residential or office.

• Uppermost floor level limited to 12m

Page 35: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

By-Law 194 stipulates when a single staircase may be permitted. Essentially, this is only allowed where the occupancy above ground level is confined to either domestic or office purposes. The ground floor may be used for shops or car parks. (shop offices, shop houses)

All elements of structure shall have a FRP of not less than one hour except the enclosure for the staircase at the ground floor where the wall shall have an FRP of not less than two hours, assuming the ground floor will not be used for residential purposes.

12mmax.

12mmax.

Diagram 4.4.8.2.Maximum travel distance

not more 12m

Assumed Room of occupancy < 6Shop or car park

Diagram 4.4.8.1.Height of topmost floor of building with single staircase

Height oftopmost floor < 12m

Domestic or office use

SINGLE STAIRCASEPROVISIONUBBL 194

Page 36: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

194. Building with single staircase. A single staircase may be permitted in the following premises: (a) any dwellings at a height of 12 metres measured from the fire

appliance access level to the highest and lowest floor; and 

(b) any shophouses or dwellings not exceeding two (2) storeys or the first storey not exceeding 6 metres from the ground level.

 

Page 37: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

Clause 194 (b) : single staircase for shop house

<=12m

Shop

House/office

Single staircase

Houseonly

<= 6m

1) House only on upper floor2) No more than 2 storeys

3) Height of first floor no more than 6m above ground level

Clause 166 and 167 (not less than two exits) shall apply for other building types

Page 38: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

Capacity of exits• UBBL 7th Schedule• UBBL 175, 176, 178

• Occupant load

• Exit width

• Application of horizontal exit

Page 39: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

Sample calculation

Scenario 1: upper floor assembly area in an institutional building

50m

20m

Stair A Stair B

Lobby C

Occupancy load

(UBBL 180(b)) =1.35m2/pax

1000m2 / 1.35m2 = 741 persons

Assume lobby C is inaccessible,

Therefore A and B must accommodate total occupancy

741 / 2 stairs = 371 persons per stair

VII persons per unit for stair = 75

371 / 75 = 4.95, say 5

5 x 0.55m = 2.75m width each stair

C = horizontal exit, persons per unit = 100

371 pax / 100 = 3.71,

3.71 x 0.55m = 2.04 m min width for lobby C

Page 40: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

Sample calculation

Scenario 2: upper floor assembly area in an institutional building

35m

Stair A Stair B

Lobby C

20m

15m

222 persons 519 persons

door D

Assume C inaccessible, either B or DMust accommodate

519 / 2 exits = 260 persons

B = stair = 75 pax per unit260/ 75 = 3.473.47 x 0.55m = 1.9m width

D = horizontal exit = 100 pax per unit260/ 100 = 2.62.6 x 0.55m = 1.43m width

222 persons

Page 41: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

Final exit

Exit route

horizontal exit

storey exit

Final exit250 pax

400 pax

200 pax 150 pax

300 pax

250 pax

400 pax

400 pax

400 pax

400 pax

200 pax

Page 42: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

7th Schedule : Maximum Travel Distance

6 60 9

0 30 45 10 45

10

22.5 45

0 61

30 45 60

NR 22.5 22.5 NR

NR NR NR NR 22.5 30 30 45

UBBL 1984 provisions shown in RED

Page 43: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

7th Schedule : Occupant Load and capacity of exits

22

100 60 60 60 45

------OFFICE

------SHOP

UBBL 1984 provisions shown in RED

Page 44: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

• Size limitations of ‘compartments’

• Fire Resistance Ratings of ‘elements of structure’

Compartmentation

Page 45: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

• To contain the spread of fire from point of origin• To limit the potential size of the fire• To separate areas of different levels of hazard• To separate areas for safe exit, evacuation or

refuge• To limit threat to the structural integrity of the

building• To allow sufficient time for safe evacuation,

active extinguishment of fire and rescue.

Compartmentation

Page 46: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

compartmentation

• Surface area / volume of combustible content (A)

• Combustion heat per area / volume (B)• Fire Load = (A) x (B)

Fire Load

Page 47: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

Time

Tem

pera

ture

/ si

ze

Stage 1Ignition & growth

Stage 2development

Stage 3Full fire

Stage 4Decay

Flashover

Untenable condition

NATURE OF FIRE

Page 48: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

Time

Tem

pera

ture

/ si

zeEQUAL VOLUME

‘low’ Btu

‘moderate’ Btu

‘high’ Btu

Page 49: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

Time

Tem

pera

ture

/ si

zeEQUAL Btu

‘low’ volume

‘moderate’ volume

‘high’ volume

Page 50: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

Time

Tem

pera

ture

/ si

zeEQUAL VOLUME

‘low’ Btu

‘moderate’ Btu

‘high’ Btu

Time

Tem

pera

ture

/ si

ze

EQUAL Btu

‘low’ volume

‘moderate’ volume

‘high’ volume

Limitation ofFloor Areas and Volume

Prescription ofFire Resistance Rating

Purpose Group classification

Page 51: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

Accepted assumption in designing for safe evacuation:

“Only one fire at one location at a time”

Primary objective of compartmentation:

“To contain the one fire within the one location at all times”

Page 52: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

Contents of the building

• Fittings and furnishings………..• ……………..including the building itself• Furniture and equipment• Consumables• Storage items• Presence of hazardous materials• Presence (or absence) of human

occupants

Contributing factors to potential fire load :

Page 53: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

These factors lead to the designation of purpose groups in the 5th Schedule, UBBL, …….

……and to the prescriptions of UBBL

6th Schedule8th Schedule9th Schedule

Page 54: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

UBBL 5th Schedule• UBBL 5th schedule• UBBL 134• UBBL 135, 136, 137, 138, 139• Every building is to have one overall designation

• Individual components of building with different usage from overall must be designed to accommodate the more stringent requirement, and where these requirements ‘spill’ into the other parts of the building, the more stringent requirement applies.

• Only ‘horizontal’ separation is allowed between buildings of different purpose groups

Page 55: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

• Dimensions of buildings and compartments

• Single storey buildings : limitations apply only to II and III

• Others : dimensional limitations does not apply to I, IV and VII

UBBL 5th Schedule

Page 56: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

other limitations that may affect areas and volumes

• UBBL• 136, 220 : if automatic sprinklers installed,

limits can be doubled ( x 2 )• 137 : floor to floor compartmentation• 138 : floor and wall compartmentation for

flats, basement and areas of different usage

• 139 : compartmentation of hazardous areas

Page 57: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

other limitations that may affect areas and volumes

• 158, 178 to 188 : specific coverage for VII – places of assembly

• Travel distances and occupant loads

Page 58: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

UBBL 6th Schedule

• UBBL 142, 145 Construction and protection of external walls

Page 59: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

UBBL 8th Schedule

• UBBL 204 to 207• Flame spread over surfaces of walls and

ceilings

Page 60: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

UBBL 9th Schedule

• Minimum periods of Fire Resistance for Elements of Structure.

• UBBL 213 : every element of structure to have FRP no less than as specified in 9th Schedule

Page 61: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

Elements of structurefor application of FRP

• Structural frame, beams and columns (excluding roof structures)

• Floor (except the lowest floor)• Compartment floor• External wall• Separating wall ( including party wall )• Compartment wall• Protected shaft : structure and enclosure• Load bearing wall• gallery

Page 62: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

• Constructional function : Party Wall UBBL 86• Fire safety function : Separating wall to be Compartment Wall UBBL

138(c) • Check compartment size• Check Fire Resistance Period of elements of structure

• UBBL 214 : External Wall and Separating Wall minimum FRP

SEPARATING WALL : TERRACE HOUSES

Page 63: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

86 Party walls. 

(1) All party walls shall generally be of not less than 200 millimetres total thickness of solid masonry or insitu concrete which may be made up of two separate skins each of not less than 100 millimetres thickness if consctructed at different times:

Provided that in multi-storeyed flats and terrace houses of reinforced concrete or of protected steel framed construction having floors and roofs constructed to the requirements of these By-laws, the party wall thereof shall not be less than 100 millimetres total thickness.

(2) Party walls in single storeyed houses may be in load-bearing 100 millimetres solid masonry or insitu concrete provided the requirements of Part V, VI and VII of these By-laws are complied with.

(3) All party walls shall be carried above the upper surface of the roof to a distance of not less than 230 millimetres at right angles to such upper surface.

(4) Other non-combustible materials may be used for party walls provided the requirements of Part V, VI and VII of these By-laws are complied with.

 

 

 

-Deleted-

 

 

 

 

 

By-law 141: Separating walls has already provided the necessary fire requirements served to prevent the spread of fire from one separate unit of house to another. As such the Fire Authority will only make reference to by-law 141.

 

Page 64: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

COMPARTMENTS, ELEMENTS OF STRUCTURE AND FRP

215(2) : reference to height, by building only

215(1) : reference to elements of structure, by building, or by compartments

137 : floor to floor compartment for buildings > 30m height

138(b) : floor and walls separating flats

138(c) : floor and walls separating purpose group

138(d) : floor separating basements

Serviceapts

Offices

Shops

Carpark

Cineplex

Page 65: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

Basement compartment volume limit 42,000m3

Compartment A

Compartment B

Compartment C

Separation of vertical ‘shaft’

Compartment D

COMPARTMENTS, ELEMENTS OF STRUCTURE AND FRP

Page 66: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

Shop compartment limit 4,000m2 14,000m3 (sprinklered )

Compartment A

Compartment B No limits if

At least 60% area are shopsLess than 280m2 each

Compartment C

COMPARTMENTS, ELEMENTS OF STRUCTURE AND FRP Large Shopping Malls (Sarawak Building Ordinance)

Page 67: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

UBBL 6th SCHEDULE

Ref

eren

ce p

lane

Reference planere

leva

nt b

ound

ary

Page 68: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

UBBL 6th SCHEDULE

Ref

eren

ce p

lane

Reference planenotio

nal b

ound

ary

SEPARATING WALL

Page 69: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

Sample calculation1) Establish Purpose Group

2) Establish height and width of enclosing rectangle

2h x 3w

Office building Protected staircase

3h x 9w

9m

24m

1) Enclosing rectangle on reference plane : 24m high x 9m wide = 216m2 2) Total unprotected area : ( 2m x 3m) x 10 = 60m2 3m x 9m = 27m2 total = 87m2

3) Percentage of unprotected area : 87m2 / 216m2 = 40 %

4) Minimum distance from reference plane to relevant boundary : 5m (IV –Office)

Page 70: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings
Page 71: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

FLAME TRAJECTORY OUTSIDE WALL OPENINGS

heig

ht

Distance from face of wall

Shape of opening

Square

1: 3

1: 2

Page 72: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

EXTERNAL WALL BARRIERS

UBBL 149

900mm vertical or750mm horizontal barrier

Page 73: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

COMPARTMENTS, ELEMENTS OF STRUCTURE AND FRP Atrium Space (NFPA 101)

Page 74: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

137 Floor in building exceeding 30 metres in height to be constructed as compartment floor. 

In any building which exceeds 30 metres in height, any floor which is more than 9 metres above ground floor level which separates one storey from another storey, other than a floor which is either within a maisonette or a mezzanine floor shall be constructed as a compartment floor.  

-None-      

-None- 

 

Compartmentation by height.

 (1) In any building not exceeding 30 metres in height, any floor which is more than 9 metres above ground floor level which separates one storey from another storey, other than a floor which is either within a maisonette or a mezzanine floor shall be constructed as a compartment floor.  

(2) In any building exceeding 30 metres in height, all floors shall be constructed as compartment floors, other than a compartment which is within a residential maisonette which may comprise two storey levels. (3) An atrium shall comply with the requirements of by-law 252A. 

To provide stricter requirements in relation to the extent of subdivision of a building as compartment floors.

Page 75: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

COMPARTMENTS, ELEMENTS OF STRUCTURE AND FRP Atrium Space (NFPA 101)

• Minimum dimension of 6m and minimum area of 95m• Required exits to be separated from atrium volume• Atrium construction and usage to be of hazard level no

higher than ‘ordinary’• Entire building to have automatic sprinklers• Designed for smoke exhaust and smoke control• Atrium volume to be separated from adjacent

occupancy, or to be engineered such that the adjacent occupancies are not at risk from a fire originating from the atrium

Page 76: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

COMPARTMENTS, ELEMENTS OF STRUCTURE AND FRP Atrium Space (NFPA 101)

UBBL 251Smoke venting forSafe exit

Page 77: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

Compartmentation of large volumes

Page 78: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

Compartmentation of large volumes

Page 79: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

Protection of penetrations through compartments and elements

• UBBL 141 : Separating walls

• Diameter of combustible pipe < 25mm• Diameter of non-combustible pipe <150mm• No flue pipes allowed• Doors to have equal or greater FRP as with the element

UBBL 148 : Compartment floor and walls

• Opening for protected shaft• Ventilation duct with fire damper• Encased ducts to have FRP no less than half of the element

Page 80: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

Protection of penetrations through compartments and elements

UBBL 150 : Protected Shafts

• for pipes, ducts, sanitary facilities, staircase, lift

UBBL 156 : Ventilating Duct in Protected Shaft

• To have automatic Fire Dampers at ‘appropriate’ intervals

Page 81: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

Max 25mm (/)

Max 150mm (/)

Required FRP

Half of required FRP

Required FRP

Page 82: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

Half of required FRP

Required FRP

Page 83: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

Half of required FRP

Full FRP for structures

Page 84: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

Active systems for…..

• EVACUATION and FIRST AID– Detection and Alarm– Communication– Smoke control – Portable fire extinguishers

Page 85: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

Tem

pera

ture

/ si

ze

Time

Unt

enab

le c

ondi

tion

Available Safe Egress Time ASET

detection

alarm

movementTotal evacuation

ignition

Required Safe Egress Time RSET

Factor of safety:

RSET < 0.75 ASET

Page 86: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

10th Schedule

Page 87: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

1. Manual Electric Fire Alarm2. Automatic Fire Detector System3. Centralised Monitoring System4. Public Address System5. Fire Command Center

A. Hose Reel SystemB. Sprinkler SystemC. Gaseous Extinquishing SystemD. Pressurized Fire Hydrant

Page 88: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

1. Manual Electric Fire Alarm2. Automatic Fire Detector System3. Centralised Monitoring System4. Public Address System5. Fire Command Center

A. Hose Reel SystemB. Sprinkler SystemC. Gaseous Extinquishing SystemD. Pressurized Fire Hydrant

Page 89: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

1. Manual Electric Fire Alarm2. Automatic Fire Detector System3. Centralised Monitoring System4. Public Address System5. Fire Command Center

A. Hose Reel SystemB. Sprinkler SystemC. Gaseous Extinquishing SystemD. Pressurized Fire Hydrant

Page 90: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

1. Manual Electric Fire Alarm2. Automatic Fire Detector System3. Centralised Monitoring System4. Public Address System5. Fire Command Center

A. Hose Reel SystemB. Sprinkler SystemC. Gaseous Extinquishing SystemD. Pressurized Fire Hydrant

Page 91: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

1. Manual Electric Fire Alarm2. Automatic Fire Detector System3. Centralised Monitoring System4. Public Address System5. Fire Command Center

A. Hose Reel SystemB. Sprinkler SystemC. Gaseous Extinquishing SystemD. Pressurized Fire Hydrant

Page 92: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

1. Manual Electric Fire Alarm2. Automatic Fire Detector System3. Centralised Monitoring System4. Public Address System5. Fire Command Center

A. Hose Reel SystemB. Sprinkler SystemC. Gaseous Extinquishing SystemD. Pressurized Fire Hydrant

Page 93: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

1. Manual Electric Fire Alarm2. Automatic Fire Detector System3. Centralised Monitoring System4. Public Address System5. Fire Command Center

A. Hose Reel SystemB. Sprinkler SystemC. Gaseous Extinquishing SystemD. Pressurized Fire Hydrant

Page 94: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

1. Manual Electric Fire Alarm2. Automatic Fire Detector System3. Centralised Monitoring System4. Public Address System5. Fire Command Center

A. Hose Reel SystemB. Sprinkler SystemC. Gaseous Extinquishing SystemD. Pressurized Fire Hydrant

Page 95: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

1. Manual Electric Fire Alarm2. Automatic Fire Detector System3. Centralised Monitoring System4. Public Address System5. Fire Command Center

A. Hose Reel SystemB. Sprinkler SystemC. Gaseous Extinquishing SystemD. Pressurized Fire Hydrant

Page 96: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

OPEN STRUCTURE

(1)Total surface area of openings is to be no less than 40% of the total perimeter wall area enclosing the floor or compartment

(2)The opening is to be shaped and located in such a way that total length in plan of the opening(s) is to be no less than 50% of the perimeter of the floor or compartment

“ Openings” is to be opened to outside, unenclosed space or permitted airwells. Any individual opening having a surface area less than 600mm2 or area width of opening is less than 25mm is not to be regarded as an opening for this purpose.

Page 97: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

OPEN STRUCTURES

50m25m

5m

Example:Total perimeter length (25m + 50m ) x 2 = 150m

minimum 50% = 75m Total perimeter wall area 150m x 5m = 750m2 minimum 40% = 300m2

Total length of openings : 25m + 50m = 75mTotal area of openings : 75m x 4m = 300m2Total length of openings : 50m + 50m = 100mTotal area of openings : 100m x 3m = 300m2Total length of openings (25m + 50m)x2 = 150mTotal area of openings : 150m x 2m = 300m2

Page 98: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

OPEN CORRIDOR

(1)Total surface area of opening(s) is to be no less than 25% of the total perimeter wall area enclosing the balcony (corridor)

(2)The opening(s) is to be shaped and located in such a way that total length in plan of the opening(s) is to be no less than 50% of the perimeter of the floor or compartment

“ Openings” is to be opened to outside, unenclosed space or permitted airwells. Any individual opening having a surface area less than 600mm2 or area width of opening is less than 25mm is not to be regarded as an opening for this purpose.

Page 99: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

OPEN CORRIDORExample (corridor)Total perimeter length (24m + 2m ) x 2 = 52m

minimum 50% = 26m Total perimeter wall area 52m x 3m = 156m2 minimum 25% = 39m2

Total length of openings 24m + 2m + 2m= 28mTotal area of openings : 28m x 1.5m = 42m2

Permitted Airwells(UBBL 40)

6m

3m

6m 6m6m

3m

2m

Page 100: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

A : HRB : SpkrC : GasExD : PrHy

1 : ManAl2 : AutoD3 : CMS4 : PAS5 : FCC

10th SCHEDULE

Page 101: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

A : HRB : SpkrC : GasExD : PrHy

1 : ManAl2 : AutoD3 : CMS4 : PAS5 : FCC

10th SCHEDULE

Page 102: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

A : HRB : SpkrC : GasExD : PrHy

1 : ManAl2 : AutoD3 : CMS4 : PAS5 : FCC

10th SCHEDULE

Page 103: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

A : HRB : SpkrC : GasExD : PrHy

10th SCHEDULE

HOTELS

1 : ManAl2 : AutoD3 : CMS4 : PAS5 : FCC

Page 104: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

A : HRB : SpkrC : GasExD : PrHy

1 : ManAl2 : AutoD3 : CMS4 : PAS5 : FCC

10th SCHEDULE

Page 105: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

detection

• Very early detection

• Early detection

• Manual detection

Page 106: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

alarm

• Automatic

• Pre alarm

• Local / manual

Page 107: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

FIRE DETECTION AND ALARM

System objective are:• To detect outbreak of fire and warn occupants• To activate fire safety systems• To inform Fire Brigade• To monitor fire safety equipment

Page 108: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

RELEVANT BY-LAWS

Under UBBL 237, fire alarm systems are required for buildings defined under the 10th Schedule

Under UBBL 238, a fire command center is required for all buildings above 30.5 meters or exceeding 9,290 sq. meters in gross area.

Page 109: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

LOCATION AND SPACING

• Manual call points and bells to be along escape corridors or beside exit and staircase doors, such that no occupant need travel more than 30 meters to reach a call point.

Page 110: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

MAIN FIRE ALARM PANELMain fire alarm panel comprises:• Alarm, fault and isolation indication for each

zone.• Indicator lights to monitor status of power

supply and fire safety systems such as fire pumps, smoke control equipment, carbon dioxide systems, fire tank water levels, etc.

• Mimic panel to identify location of each zone.• Battery with charger to provide power supply

for the whole system.

Page 111: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

FIRE DETECTION DEVICES

• Manual break glass for occupants to activate manually.

• Heat detectors to detect heat intensive fires automatically for spaces up to 9 meters high.

• Smoke detectors to detect smoke intensive fires automatically for spaces up to 10 meters high.

• Beam (smoke) detectors for high spaces such as atriums up to 25 meters high.

• Flame (IR or UV) detectors

Page 112: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

Heat …..or Smoke?

• Smoke detectors for electrical rooms and store rooms.

• Heat detectors for general areas.• Smoke detectors for areas where rapid heat

development is normal for the function of the space, or where combustibles may burn with high release of smoke

• Heat detectors for areas where smoke may be a common presence in the space, or where combustibles may burn rapidly and efficiently

Page 113: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

VOICE COMMUNICATION SYSTEMS

• To guide the occupants in an orderly manner during evacuation upon detection of fire.

• For the firemen to communicate with one another during fire fighting operations.

Page 114: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

RELEVANT BY-LAW

Under UBBL 239, two voice communication system is required for all large buildings and high rise buildings and they are:

• Public address system, and

• Fire brigade intercommunication system

Page 115: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

PORTABLE FIRE EXTINGUISHERS

Intended for use by the occupants during the early stages of the fire

Under UBBL 227, portable fire extinguishers are required for first aid use.

Page 116: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

CLASSES OF FIRES

• Class A: Combustible solids like paper, wood• Class B: Inflammable Liquids like kerosene,

diesel• Class C: Flammable gases• Class D: Reactive metals like sodium,

potassium,• Class E: Ignition of an electrical nature• Class F: Cooking oil fires

Page 117: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

TYPES OF EXTINGUISHERS

• Water type for Class A fires• Dry powder type for Class A, B, C and F fires• Carbon Dioxide type for Class E fires• Foam type for Class B fires

Dry powder type of 6 kg for general use.Carbon Dioxide type for electrical rooms

Page 118: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

LOCATION AND SPACING

• Beside exit and staircase doors

• Generally located within 20 meters of any potential hazard

Page 119: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

Active systems for…..

• COMPARTMENTATION and FIRE FIGHTING

– Smoke Control– Extinquishment

• Manual• Automatic

Page 120: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

SMOKE CONTROLTYPES

• Pressurization system to prevent entry of smoke by pressurizing the compartment with air.

• Space depressurization system to prevent the spread of smoke by extraction.

• Smoke dilution system to remove the smoke by extraction and make-up of air.

Page 121: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

PRESSURIZATION SYSTEMS

Typical application are in protected shafts and corridors.

• Air is actively supplied into the compartment to be protected to maintain a positive pressure relative to the adjacent compartments.

Page 122: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings
Page 123: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

DEPRESSURIZATION SYSTEMS

Typical application are multi-storey office buildings.

• Floor on fire is maintained under negative pressure by extracting the smoke laden air.

• Immediate floors above and below are maintained at positive pressure by supplying air to these floors.

Page 124: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings
Page 125: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

DILUTION SYSTEMS

Typical application are basement car parks and shopping complexes.

• Smoke is extracted from zone on fire.

• Make-up air is provided to zones adjacent to area on fire.

Page 126: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings
Page 127: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

HOSE REELS

Intended for the occupants to use during early stages of the fire

Page 128: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

LOCATION AND SPACING

• Near exit and staircase doors

• All spaces to be within 36 meters of a hose reel.

• No restriction on location of hose reel pumps and tanks.

Page 129: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings
Page 130: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

SPRINKLER SYSTEM

Intended to detect and extinguish a fire and warn the occupants to evacuate.

Under UBBL 226, automatic sprinkler systems are required for storage and other types of occupancies where automatic extinguishing system is necessary.

Page 131: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings
Page 132: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

TYPES OF SYSTEMS• Wet pipe system where pipe work is charged

with water at all times.• Dry pipe system where pipe is charged with

water only after the sprinkler head is activated. • Pre-action system where system is charged

with water after fire is detected but before the sprinkler head is activated.

• Deluge system where water is discharged simultaneously from all sprinkler heads upon activation.

Page 133: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

TYPES OF HAZARDS• Light Hazard e.g. apartments, schools• Ordinary Hazards:

– OH Group I : Offices, restaurants– OH Group II : Laundries, bakeries– OH Group III : Departmental Stores, Car

parks– OH Group IV : Film and television studios

• High Hazards:– Process risks– High piled storage risks

Page 134: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

SPRINKLER TANKS

• Typical location at ground or first basement although no restriction on the location except for distance from pump.

Page 135: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

AREAS EXEMPTED

– Transformer Rooms;– Switch gear Rooms;– Lift Motor Rooms; and– Toilets;

Page 136: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

INSTALLATION CONTROL VALVE

Water supply to sprinklers feed from Installation control valve with alarm gong and shut-off valves.

For life safety systems, Sprinklers are grouped such that each zone does not have more than 200 sprinkler heads with its own flow switch.

Page 137: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

SPRINKLER PIPE WORK

• The height between the lowest and highest sprinkler within one stage not to exceed 45 m.

• For buildings exceeding 45 m., multiple stages are required.

• Express risers are permitted to bypass lower stgages and serve the upper stage.

Page 138: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

AUTOMATIC ACTIVATION

• Heat and smoke detectors installed to detect fire.

• Activation of one detector initiates alarm but not gas discharge.

• Activation of any two detectors initiates gas discharge.

• Time delay of 30 sec. before gas discharge.

Page 139: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

MANUAL ACTIVATION

• Manual activation by pull station in event of failure of automatic activation.

• Pull station to be outside of room protected.• Audio and visual warning activated upon gas

discharge to warn occupants from entering.

Page 140: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

Active systems for…..

• FIRE FIGHTING and RESCUE– Lifts– Risers– Hydrants

Page 141: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

FIRE LIFT

Intended to assist the firemen to reach the floors on fire rapidly.

Under UBBL 243, any building exceeding 18.5 meters high shall be provided with firemen’s lift.

Page 142: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

LOCATION AND SPACING

• Not more than 61 meters from the furthermost point of the floor.

• Not more than 61 meters from the main entrance of the building or the fire control room whichever is nearer.

Page 143: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

DESIGN REQUIREMENTS

• Lift capacity to be able to carry 550kg. min.• Lift car platform size to be not less than 1.45

sq. meters.• Lift car door to be min. 800 mm clear in width. • Lift to serve all occupied floors.

Page 144: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

FIRE MODE OF OPERATION

• Lift to be provided with emergency power for operation during power failure.

• Lift to return to main landing upon detection of power failure and remain inoperable until firemen arrive.

• Fire switch to be provided at main landing for firemen to activate the lift for their use.

Page 145: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

DRY RISER SYSTEMS

Intended for the firemen to pump water up to the floors on fire.

Under UBBL 230, dry risers required for all buildings with topmost floor above 18.3 meters from fire appliance access level

Page 146: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings
Page 147: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

LOCATION AND SPACING

• Landing valves located within fire access lobbies.

• Provided on every upper floor such that all spaces are within 45 m from a landing valve.

• Breeching inlet to be no more than 18 m. from fire appliance access road and not more than 30 meters from nearest outdoor hydrant.

Page 148: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

DRY RISER PIPE WORK

• Dry riser to be 100 mm dia. If highest outlet is no more than 23 m. above breeching inlet.

• Dry riser to be 150 mm dia. If highest outlet is more than 23 m. above breeching inlet.

Page 149: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

5. WET RISER SYSTEMS

Intended to supply water up to the floors on fire for the firemen to use.

Under UBBL 231, wet risers required for all buildings with topmost floor above 30.5m. From the fire appliance access level.

Page 150: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

LOCATION AND SPACING

• Landing valves located within fire access lobbies.

• Provided on every upper floor such that all spaces are within 45 m from a landing valve.

• Distance between landing valves on the same floor not to exceed 60 m.

• Breeching inlet to be no more than 18 m. from fire appliance access road and not more than 30 meters from nearest outdoor hydrant.

Page 151: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings
Page 152: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

PUMPS AND PIPE WORK

• Each stack not to exceed 60 m or 71 m if approved by the Director General of Fire and Rescue Dept.

Stack height is defined as the height from the wet riser pump to the topmost floor protected.

Page 153: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

WET RISER PUMPS AND TANKS

• Location of wet riser pumps and tanks restricted to ground, first or second basement.

• Lowest basement may not be premitted due to possibility of flooding.

Page 154: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

6. DOWNCOMER SYSTEMS

Intended to provide water from roof fire tank to the floors on fire using static head available.

Only permitted for private residential buildings where the topmost floor is no higher than 60 m. above fire appliance access level.

Page 155: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings
Page 156: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

LOCATION AND SPACING

• Landing valves located within fire access lobbies

• Provided on every upper floor such that all spaces are within 45 m from a landing valve.

• Breeching inlet to be no more than 18 m. from fire appliance access road and not more than 30 meters from nearest outdoor hydrant.

Page 157: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

DOWNCOMER TANKS

• Tanks located on roof of building for maximum pressure.

Page 158: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

• 196, 197 - smoke lobbies, protected lobbies

• 198, 199, 200, 201 – ventilation of stairs• 229 – fire fighting lobbies

UBBL

Protection of stairs and lobbies

Page 159: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

Protection of stairs and lobbies

• Protected Lobby : protected lobby separated or isolated from fire and smoke infiltration

• Smoke Lobby : a protected lobby primarily to isolate staircases from smoke infiltration

• ventilated lobby : protected/smoke lobby by means of natural ventilation from outside

• Fire Fighting Access Lobby : a protected lobby designed for fire fighting access

Page 160: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

SMOKE CONTROL SYSTEMS

To control the spread of smoke from the source of fire to other occupied spaces and maintain visibility as much as possible during evacuation.

Page 161: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

RELEVANT BY-LAWS

Under UBBL clauses 196 and 197 requires fire fighting access lobbies and smoke lobbies to be pressurized if natural ventilation cannot be provided.

Under UBBL clauses 200, 201 and 202 requires escape staircases to be pressurized if natural ventilation cannot be provided.

Page 162: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

STAIRCASE PRESSURIZATION

• Entire staircase pressurized with air.

• Air pressure within staircase is controlled to permit opening of exit doors without the need of excessive force.

Page 163: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

LIFT LOBBY PRESSURIZATION

• Lift lobbies are individually pressurized with air.

• Air pressure within lift lobbies is controlled to permit opening of exit doors without the need of excessive force.

Page 164: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

Protected lobby requirement for building > 18m(By-Law 197)

External wall

Protected lobbyrequirement Building more

than 18m above ground level

No protectedlobby required

Ventilation opening

Page 165: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

No protectedlobby required

Omission of protected lobby for pressurised staircase for buildings below 45m

For building above18m but below 45m

No protectedlobby required

Ventilated opening

Staircasepressurised

Page 166: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

Above 18m, need PROTECTIONAbove 45m, protection by PRESSURISATION

Ventilation opening

No protectedlobby required

Protectedlobby to bepressurised

Protected lobby requirement for building > 45m[By-Law 197(2)]

Page 167: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

PROTECTED / PRESSURISED

Page 168: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

UBBL 229

Page 169: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

EXTERNAL FIRE HYDRANTS

System of Pipe work connected to public water mains to provide water for the pumps in the fire engine.

For industrial plants, fire pumps have to be provided where flow is unreliable or pressure is inadequate

Page 170: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

RELEVANT BY-LAWS

Under UBBL 225, every building shall be provided with at least one fire hydrant.

Page 171: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

EMERGENCY POWER SUPPLY

Intended to provide emergency power to operate all fire safety systems.

Under UBBL 253, emergency power is to be provided for fire pumps, fire lifts, fire alarm, smoke control, emergency lighting, voice communication, firemen intercom, etc.

Page 172: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

SOURCES OF EMERGENCY POWER

• Standby electrical generator with changeover switch activated upon power failure;

• Battery banks with charger to maintain them in charged condition.

Page 173: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

LOCATION

• Generator to be located at ground or first basement for easy access by firemen.

• Outdoor air required to cool diesel engine’s radiator.

Page 174: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

140. Fire appliances access. (1) Accessway shall be provided within the site of a building to enable fire appliances to gain access to the building. Access openings shall also be provided along the external walls of buildings fronting the accessway to provide access into the building for fire fighting and rescue operations. (2) The requirements of accessway shall be as follows:

(a) the accessway shall have a minimum width of 6 metres throughout its entire length and shall be able to accommodate the entry and manouvering of fire engine, extended ladders pumping appliances, turntable and hydraulic platforms;

(b) the accessway shall be metalled or paved or laid with strengthened perforated slabs to withstand the loading capacity of

stationary 30 tonnes fire appliance;

(c) the accessway shall be positioned so that the nearer edge shall be not less than 2 metres or more than 10 metres from the centre position of the access opening, measured horizontally;

(d) the accessway shall be laid on a level platform or if on an incline, the gradient shall not exceed 1:15. The access road

shall be laid on a incline not exceeding a gradient of 1:8.3;

(e) the dead-end accessway and fire engine access road shall not exceed 46 metres in length or if exceeding 46 metres, be provided with turning facilities;

(f) the outer radius for turning of accessway and fire engine access road shall comply with the requirements of the Fire

Authority;

(g) the overhead clearance of fire engine access road shall be at least 4.5 metres for passage of fire appliances;

(h) public roads may serve as accessway provided that the location of such public roads is in compliance with the requirements of distance from access openings as the Fire Authority may specify; and

140 Fire Appliance Access

Page 175: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

197A. Means of access and fire fighting in building over 18.0 metres high. (1) Buildings in which the topmost floor is more than 18.0 metres above fire appliance access level shall be provided with means of gaining access and fighting fire from within the building consisting of fire fighting access lobbies, fire fighting staircases, fire lifts and dry or wet rising systems. 197B. Fire fighting access lobbies. Fire fighting access lobbies shall conform to the following requirements: (a) each lobby shall have a floor area of not less than 6.0 square metres; and (b) the openable area of windows or area of permanent ventilation shall be not less than 25% of the floor area of the lobby and, if ventilation is by means of openable windows, additional permanent ventilation having a free opening of 464 square centimetres shall be provided except that mechanical pressurisation may be provided as an alternative

Page 176: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

FIRE APPLIANCE ACCESSUBBL 140

ACCESS WAYAn area for the entry, maneuvering and parking of Fire Appliances during fire fighting and rescue operations

ACCESS ROADA road capable of accommodating the passage of Fire Appliances to enter an Access Way

ACCESS OPENINGSDoorways or openings that allows fast and safe entry of Fire Fighting and Rescue personnel into a building during fire fighting and rescue operations

Page 177: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

EXTERNAL ACCESS

Access for emergency and rescue vehicles, equipment and personnel

• Roads• Pavements• Parking

Availability of water : • Hydrants• Storage tanks• Lakes, rivers, ponds

And access to fire fighting systems in the premises

Page 178: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

Clarity of :• Type of building and function• Configuration of building• Location of fire control panel• Location of breaching inlets and pump

rooms

AT THE PREMISES

Access into the building• Protected passage• Protected stairs• Firemen’s lift• Fire fighting lobby

Page 179: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

Pressurised Hydrant System

Page 180: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

Sprinkler System

Page 181: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

Dry Riser system

Page 182: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

Wet Riser System

Page 183: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

External source of water• Hydrants• Lakes, Ponds, Pools, rivers

• Fire Tenders

Fire Fighting Applianceon ‘Access Way’

Internal Systems• Sprinklers• Hose reels• Dry/Wet Risers

Breaching Inlet• Sprinklers• Risers

Page 184: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

ACCESS WAY• Minimum 6m width• 30 tonnes load• Gradient <= 1:15• No overhead obstructionsACCESS ROAD

• (Suggested) minimum width 4m

• Gradient <= 1: 8.3• Minimum

overhead clearance 4.5mACCESS OPENING

• Located fronting Access Way

• (suggested) width >= required exit width

Required portion of building fronting the Access Way

Edge of Access Way• Minimum 2m• Maximum 10m

Required portion of building fronting the Access Way

ACCESS WAY

ACCESS ROAD• (Suggested)

minimum width 4m• Gradient <= 1: 8.3• Minimum

overhead clearance 4.5m

Page 185: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

Fire Fighting Access Lobbies

Emergency Power Generators

Fire Pumps

Breeching Inlets

Hydrant

Hydrant

LALUAN JENTERA BOMBA

KOSONGKAN LALUAN

Maximum 30mHydrant to Breeching Inlet

Maximum 90mHydrant to Hydrant

Page 186: [PPT]Slide 1 - Pertubuhan Akitek Malaysia Sarawak Chapterpamsc.org.my/wp-content/uploads/2015/08/Designing-for... · Web viewUnder UBBL 237, fire alarm systems are required for buildings

THANK YOU